Home/Catalog/HM2-IOMODULE-MIB

HM2-IOMODULE-MIB

Hirschmann IO Module MIB. Copyright (C) 2012. All Rights Reserved.
Main OID:
hm2IOModuleMib.1.3.6.1.4.1.248.11.100
40
Objects
Active
Status
3
Dependencies

Imported Objects

Objects

40 total
Object Name
hm2IOModuleMibHirschmann IO Module MIB. Copyright (C) 2012. All Rights Reserved.
MODULE-IDENTITY
.1.3.6.1.4.1.248.11.100
hm2IOModuleMibNotifications
OBJECT IDENTIFIER
.1.3.6.1.4.1.248.11.100.0
hm2IOModDigInputChangeTrapThis trap is sent if the state of an input changes. This trap is sent only when hm2IOModConfigDigInputSnmpTrap is set to enabled (1).
NOTIFICATION-TYPE
.1.3.6.1.4.1.248.11.100.0.1
hm2IOModDigOutputChangeTrapThis trap is sent if the state of an input changes. This trap is sent when hm2IOModConfigDigOutputSnmpTrap is set to enabled (1) or when the output value changes from or to invalid (3).
NOTIFICATION-TYPE
.1.3.6.1.4.1.248.11.100.0.2
hm2IOModuleMibObjects
OBJECT IDENTIFIER
.1.3.6.1.4.1.248.11.100.1
hm2IOModConfigGroup
OBJECT IDENTIFIER
.1.3.6.1.4.1.248.11.100.1.1
hm2IOModConfigCommon
OBJECT IDENTIFIER
.1.3.6.1.4.1.248.11.100.1.1.1
hm2IOModConfigDigInputAdminStateEnables polling of input values. (if disable(2) input task will do nothing)rw
HmEnabledStatus (HM2-TC-MIB)
.1.3.6.1.4.1.248.11.100.1.1.1.1
hm2IOModConfigDigOutputAdminStateEnables mirroring of input values to output ports. (if disable(2) output task will do nothing)rw
HmEnabledStatus (HM2-TC-MIB)
.1.3.6.1.4.1.248.11.100.1.1.1.2
hm2IOModConfigDigInputRefreshIntervalThe refresh interval (in ms) of the input values. The accuracy of the interval value is 100ms. Minimum 1000ms (1s), Maximum 10000ms (10s).rw
Integer32
.1.3.6.1.4.1.248.11.100.1.1.1.3
hm2IOModConfigDigOutputRefreshIntervalThe refresh interval (in ms) of the output values. The accuracy of the interval value is 100ms. Minimum 1000ms (1s), Maximum 10000ms (10s).rw
Integer32
.1.3.6.1.4.1.248.11.100.1.1.1.4
hm2IOModConfigDigOutputRetryCountThe retry count for the output values. when after the number of configured retries no SNMP get request was answered, the output value (hm2IOModValueDigOutputValue) will be set to invalid (3). Minimum 1, Maximum 10.rw
Integer32
.1.3.6.1.4.1.248.11.100.1.1.1.5
hm2IOModConfigDigInputTableIO module config table for inputs
SEQUENCE OF Hm2IOModConfigDigInputEntry
.1.3.6.1.4.1.248.11.100.1.1.2
hm2IOModConfigDigInputEntryIO module config entry for inputs
Hm2IOModConfigDigInputEntry
.1.3.6.1.4.1.248.11.100.1.1.2.1
hm2IOModConfigDigInputModIDThe module ID of an input. Module ID 0 corresponds to the power supply module.
Integer32
.1.3.6.1.4.1.248.11.100.1.1.2.1.1
hm2IOModConfigDigInputIDThe ID of an input.
Integer32
.1.3.6.1.4.1.248.11.100.1.1.2.1.2
hm2IOModConfigDigInputLogEventTrigger an event log when input status changes. If the value is disable (2), no event log entry will be written. If the value is enable (1), an event log entry will be written when the input state changes. The input state will be checked according to the refresh interval entered in hm2IOModConfigDigInputRefreshInterval.rw
HmEnabledStatus (HM2-TC-MIB)
.1.3.6.1.4.1.248.11.100.1.1.2.1.3
hm2IOModConfigDigInputSnmpTrapTrigger an SNMP trap log when input status changes. If the value is disable (2), no SNMP trap will be sent. If the value is enable (1), a SNMP trap will be sent when the input state changes. The SNMP trap will be sent to all receivers configured in the snmpTargetAddrTable. The input state will be checked according to the refresh interval entered in hm2IOModConfigDigInputRefreshInterval.rw
HmEnabledStatus (HM2-TC-MIB)
.1.3.6.1.4.1.248.11.100.1.1.2.1.4
hm2IOModConfigDigOutputTableIO module config table for outputs.
SEQUENCE OF Hm2IOModConfigDigOutputEntry
.1.3.6.1.4.1.248.11.100.1.1.3
hm2IOModConfigDigOutputEntryIO module config entry for outputs
Hm2IOModConfigDigOutputEntry
.1.3.6.1.4.1.248.11.100.1.1.3.1
hm2IOModConfigDigOutputModIDThe module ID of an output. Module ID 0 corresponds to the power supply module.
Integer32
.1.3.6.1.4.1.248.11.100.1.1.3.1.1
hm2IOModConfigDigOutputIDThe ID of an output.
Integer32
.1.3.6.1.4.1.248.11.100.1.1.3.1.2
hm2IOModConfigDigOutputLogEventTrigger an event log when output status changes. If the value is disable (2), no event log entry will be written. If the value is enable (1), an event log entry will be written when the output state changes. The output state will be checked according to the refresh interval entered in hm2IOModConfigDigOutputRefreshInterval.rw
HmEnabledStatus (HM2-TC-MIB)
.1.3.6.1.4.1.248.11.100.1.1.3.1.3
hm2IOModConfigDigOutputSnmpTrapTrigger an SNMP trap log when output status changes. If the value is disable (2), no SNMP trap will be sent. If the value is enable (1), a SNMP trap will be sent when the output state changes. The SNMP trap will be sent to all receivers configured in the snmpTargetAddrTable. The output state will be checked according to the refresh interval entered in hm2IOModConfigDigOutputRefreshInterval.rw
HmEnabledStatus (HM2-TC-MIB)
.1.3.6.1.4.1.248.11.100.1.1.3.1.4
hm2IOModConfigDigOutputSourceAddressTypeAddress type of an input mirrored to the output. Currently, only ipv4 is supported.rw
InetAddressType (INET-ADDRESS-MIB)
.1.3.6.1.4.1.248.11.100.1.1.3.1.5
hm2IOModConfigDigOutputSourceAddressThe IP address of an input mirrored to the output. Use 0.0.0.0 if the output should not be set. In this case hm2IOModValueDigOutputValue is not-configured(4). Use 127.0.0.1 if a local input should be used.rw
InetAddress (INET-ADDRESS-MIB)
.1.3.6.1.4.1.248.11.100.1.1.3.1.6
hm2IOModConfigDigOutputSourcePortThe SNMP port number being used by the input mirrored to the output. This port would be the destination of the SNMP requests for polling the state of the input.rw
InetPortNumber (INET-ADDRESS-MIB)
.1.3.6.1.4.1.248.11.100.1.1.3.1.7
hm2IOModConfigDigOutputSourceModIDThe module ID of an input mirrored to the output. Module ID 0 corresponds to the power supply module. Ignored when hm2IOModConfigDigOutputSourceIP is 0.0.0.0.rw
Integer32
.1.3.6.1.4.1.248.11.100.1.1.3.1.8
hm2IOModConfigDigOutputSourceIDThe ID of an input mirrored to the output. Ignored when hm2IOModConfigDigOutputSourceIP is 0.0.0.0.rw
Integer32
.1.3.6.1.4.1.248.11.100.1.1.3.1.9
hm2IOModValueGroup
OBJECT IDENTIFIER
.1.3.6.1.4.1.248.11.100.1.2
hm2IOModValueDigInputTableIO module value table for inputs
SEQUENCE OF Hm2IOModValueDigInputEntry
.1.3.6.1.4.1.248.11.100.1.2.1
hm2IOModValueDigInputEntryIO module value entry for inputs
Hm2IOModValueDigInputEntry
.1.3.6.1.4.1.248.11.100.1.2.1.1
hm2IOModValueDigInputModIDThe module ID of an input. Module ID 0 corresponds to the power supply module.
Integer32
.1.3.6.1.4.1.248.11.100.1.2.1.1.1
hm2IOModValueDigInputIDThe ID of an input.
Integer32
.1.3.6.1.4.1.248.11.100.1.2.1.1.2
hm2IOModValueDigInputValueStatus of the input. If the value is not-available(0), then the IO module is not plugged in, if the value is high(1), the input has high (+24V) value, if the value is low(2), the input has low (0V) value.ro
Enumeration
.1.3.6.1.4.1.248.11.100.1.2.1.1.3
hm2IOModValueDigOutputTableIO module value table for outputs
SEQUENCE OF Hm2IOModValueDigOutputEntry
.1.3.6.1.4.1.248.11.100.1.2.2
hm2IOModValueDigOutputEntryIO module value entry for outputs
Hm2IOModValueDigOutputEntry
.1.3.6.1.4.1.248.11.100.1.2.2.1
hm2IOModValueDigOutputModIDThe module ID of an Output. Module ID 0 corresponds to the power supply module.
Integer32
.1.3.6.1.4.1.248.11.100.1.2.2.1.1
hm2IOModValueDigOutputIDThe ID of an Output.
Integer32
.1.3.6.1.4.1.248.11.100.1.2.2.1.2
hm2IOModValueDigOutputValueStatus of the output. If the value is not-available(0), then the IO module is not plugged in, if the value is high(1), the output has high (+24V) value, if the value is low(2), the output has low (0V) value. If the value is invalid (3), the output has low (0V) value and the IO input source is configured but cannot be read. If the value is not-configured (4), the output has low (0V) value and has no IO input source configured.ro
Enumeration
.1.3.6.1.4.1.248.11.100.1.2.2.1.3