gudeads MODULE-IDENTITY .1.3.6.1.4.1.28507 |
gadsPDU8310 OBJECT IDENTIFIER .1.3.6.1.4.1.28507.27 |
events OBJECT IDENTIFIER .1.3.6.1.4.1.28507.27.0 |
pdu8310AmperageEvt1Event is triggered when a measured current is crossing the entered limits NOTIFICATION-TYPE .1.3.6.1.4.1.28507.27.0.1 |
pdu8310Objects OBJECT IDENTIFIER .1.3.6.1.4.1.28507.27.1 |
pdu8310CommonConfig OBJECT IDENTIFIER .1.3.6.1.4.1.28507.27.1.1 |
pdu8310SNMPaccess OBJECT IDENTIFIER .1.3.6.1.4.1.28507.27.1.1.1 |
pdu8310TrapCtrl0 = off 1 = Ver. 1 2 = Ver. 2crw Integer32 .1.3.6.1.4.1.28507.27.1.1.1.1 |
pdu8310TrapIPTablelist of all Trap receiver SEQUENCE OF Epc8TrapIPEntry .1.3.6.1.4.1.28507.27.1.1.1.2 |
pdu8310TrapIPEntryan entry containing management informations regarding the list of trap receivers Epc8TrapIPEntry .1.3.6.1.4.1.28507.27.1.1.1.2.1 |
pdu8310TrapIPIndexA unique value, greater than zero, for each receiver slot. Integer32 .1.3.6.1.4.1.28507.27.1.1.1.2.1.1 |
pdu8310TrapAddrDNS name or IP address specifying one Trap receiver slot. A port can optionally be specified: 'name:port' An empty string disables this slot.rw OCTET STRING .1.3.6.1.4.1.28507.27.1.1.1.2.1.2 |
pdu8310DeviceConfig OBJECT IDENTIFIER .1.3.6.1.4.1.28507.27.1.2 |
pdu8310IntActors OBJECT IDENTIFIER .1.3.6.1.4.1.28507.27.1.3 |
pdu8310ExtActors OBJECT IDENTIFIER .1.3.6.1.4.1.28507.27.1.4 |
pdu8310IntSensors OBJECT IDENTIFIER .1.3.6.1.4.1.28507.27.1.5 |
pdu8310PowerChan OBJECT IDENTIFIER .1.3.6.1.4.1.28507.27.1.5.1 |
pdu8310ActivePowerChanNumber of suppported Power Channels.ro Unsigned32 (1) .1.3.6.1.4.1.28507.27.1.5.1.1 |
pdu8310PowerTableAll available Channel Interfaces. SEQUENCE OF Pdu8310PowerEntry .1.3.6.1.4.1.28507.27.1.5.1.2 |
pdu8310PowerEntryAn entry containing management information applicable to a particular Power Channel. Pdu8310PowerEntry .1.3.6.1.4.1.28507.27.1.5.1.2.1 |
pdu8310PowerIndexIndex of Power Channel entries Integer32 (1) .1.3.6.1.4.1.28507.27.1.5.1.2.1.1 |
pdu8310ChanStatus0 = data not active, 1 = data validro Integer32 .1.3.6.1.4.1.28507.27.1.5.1.2.1.2 |
pdu8310EnergyActiveTotal accumulated Active Energy of Power Channel.ro Unsigned32 UNITS "Wh" .1.3.6.1.4.1.28507.27.1.5.1.2.1.3 |
pdu8310PowerActiveActive Powerro Unsigned32 UNITS "W" .1.3.6.1.4.1.28507.27.1.5.1.2.1.4 |
pdu8310CurrentActual Curent on Power Channel.ro Unsigned32 UNITS "mA" .1.3.6.1.4.1.28507.27.1.5.1.2.1.5 |
pdu8310VoltageActual Voltage on Power Channelro Unsigned32 UNITS "V" .1.3.6.1.4.1.28507.27.1.5.1.2.1.6 |
pdu8310FrequencyFreqency of Power Channelro Unsigned32 UNITS "0.01 hz" .1.3.6.1.4.1.28507.27.1.5.1.2.1.7 |
pdu8310PowerFactorPower Factor of Channel between -1.0 and 1.00ro Integer32 UNITS "0.001" .1.3.6.1.4.1.28507.27.1.5.1.2.1.8 |
pdu8310PanglePhase Angle between Voltage and L Line Current between -180.0 and 180.0ro Integer32 UNITS "0.1 degree" .1.3.6.1.4.1.28507.27.1.5.1.2.1.9 |
pdu8310PowerApparentL Line Mean Apparent Powerro Unsigned32 UNITS "VA" .1.3.6.1.4.1.28507.27.1.5.1.2.1.10 |
pdu8310PowerReactiveL Line Mean Reactive Powerro Unsigned32 UNITS "VAR" .1.3.6.1.4.1.28507.27.1.5.1.2.1.11 |
pdu8310EnergyReactiveTotal accumulated Reactive Energy of Power Channel.ro Unsigned32 UNITS "VARh" .1.3.6.1.4.1.28507.27.1.5.1.2.1.12 |
pdu8310EnergyActiveResettableResettable accumulated Active Energy of Power Channel.ro Unsigned32 UNITS "Wh" .1.3.6.1.4.1.28507.27.1.5.1.2.1.13 |
pdu8310EnergyReactiveResettableResettable accumulated Reactive Energy of Power Channel.ro Unsigned32 UNITS "VARh" .1.3.6.1.4.1.28507.27.1.5.1.2.1.14 |
pdu8310ResetTimeTime in seconds since last Energy Counter reset.ro Unsigned32 UNITS "s" .1.3.6.1.4.1.28507.27.1.5.1.2.1.15 |
pdu8310ExtSensors OBJECT IDENTIFIER .1.3.6.1.4.1.28507.27.1.6 |
pdu8310Conf OBJECT IDENTIFIER .1.3.6.1.4.1.28507.27.2 |
pdu8310Groups OBJECT IDENTIFIER .1.3.6.1.4.1.28507.27.2.1 |
pdu8310BasicGroupBasic objects. Unknown .1.3.6.1.4.1.28507.27.2.1.1 |
pdu8310NotificationGroup Unknown .1.3.6.1.4.1.28507.27.2.1.2 |
pdu8310Compls OBJECT IDENTIFIER .1.3.6.1.4.1.28507.27.2.2 |
More MIBs from Gude Analog- und Digitalsysteme GmbH
Browse all Gude Analog- und Digitalsysteme GmbHMIBs →The GUDEADS-ESB7214-MIB module facilitates the monitoring and management of the Expert Power Control 7214 power distribution unit, specifically exposing metrics for input/output voltage, current, power consumption, temperature sensors, and relay status via SNMP.
The GUDEADS-ESB7213-MIB module facilitates SNMP-based monitoring and management of the Expert Power Control 7213 hardware platform, specifically exposing telemetry for power supply status, voltage levels, current draw, and thermal sensor readings. This module enables network administrators to track real-time power consumption metrics and fault conditions on the ESB7213 chassis to ensure electrical stability and prevent hardware failure.
Standard SNMP MIB module defining data structures for GUDEADS-EPC8X-MIB.
Standard SNMP MIB module defining data structures for GUDEADS-EPC2X6-MIB.
Standard SNMP MIB module defining data structures for GUDEADS-PDU8110-MIB.
Standard SNMP MIB module defining data structures for GUDEADS-ETS-MIB.