AI MIB Summary
The GUDEADS-ESB7213-MIB module facilitates SNMP-based monitoring and management of the Expert Power Control 7213 hardware platform, specifically exposing telemetry for power supply status, voltage levels, current draw, and thermal sensor readings. This module enables network administrators to track real-time power consumption metrics and fault conditions on the ESB7213 chassis to ensure electrical stability and prevent hardware failure.
Expert Power Control 7213 MIB
Main OID:
gudeads.1.3.6.1.4.1.28507
52
Objects
Active
Status
2
Dependencies
Imported Objects
Objects
52 total| Object Name |
|---|
gudeadsExpert Power Control 7213 MIB MODULE-IDENTITY .1.3.6.1.4.1.28507 |
gadsESB7213 OBJECT IDENTIFIER .1.3.6.1.4.1.28507.66 |
esb7213Objects OBJECT IDENTIFIER .1.3.6.1.4.1.28507.66.1 |
esb7213CommonConfig OBJECT IDENTIFIER .1.3.6.1.4.1.28507.66.1.1 |
esb7213SNMPaccess OBJECT IDENTIFIER .1.3.6.1.4.1.28507.66.1.1.1 |
esb7213TrapCtrl0 = off 1 = Ver. 1 2 = Ver. 2c 3 = Ver. 3rw Integer32 .1.3.6.1.4.1.28507.66.1.1.1.1 |
esb7213TrapIPTablelist of all Trap receiver SEQUENCE OF Esb7213TrapIPEntry .1.3.6.1.4.1.28507.66.1.1.1.2 |
esb7213TrapIPEntryan entry containing management informations regarding the list of trap receivers Esb7213TrapIPEntry .1.3.6.1.4.1.28507.66.1.1.1.2.1 |
esb7213TrapIPIndexA unique value, greater than zero, for each receiver slot.ro Integer32 .1.3.6.1.4.1.28507.66.1.1.1.2.1.1 |
esb7213TrapAddrDNS name or IP address specifying one Trap receiver slot. A port can optionally be specified: 'name:port' An empty string disables this slot.rw OCTET STRING .1.3.6.1.4.1.28507.66.1.1.1.2.1.2 |
esb7213DeviceConfig OBJECT IDENTIFIER .1.3.6.1.4.1.28507.66.1.2 |
esb7213IntActors OBJECT IDENTIFIER .1.3.6.1.4.1.28507.66.1.3 |
esb7213ExtActors OBJECT IDENTIFIER .1.3.6.1.4.1.28507.66.1.4 |
esb7213IntSensors OBJECT IDENTIFIER .1.3.6.1.4.1.28507.66.1.5 |
esb7213POEsignals POE availabilityro Integer32 .1.3.6.1.4.1.28507.66.1.5.10 |
esb7213NTPClient OBJECT IDENTIFIER .1.3.6.1.4.1.28507.66.1.5.15 |
esb7213NTPTimeValidShow if valid Time is receivedro Enumeration .1.3.6.1.4.1.28507.66.1.5.15.1 |
esb7213NTPUnixTimeshow received NTP time as unixtime (secs since 1 January 1970)ro Unsigned32 UNITS "s" .1.3.6.1.4.1.28507.66.1.5.15.2 |
esb7213NTPLastValidTimestampshow seconds since last valid NTP timestamp receivedro Unsigned32 UNITS "s" .1.3.6.1.4.1.28507.66.1.5.15.3 |
esb7213ExtSensors OBJECT IDENTIFIER .1.3.6.1.4.1.28507.66.1.6 |
esb7213SensorTable SEQUENCE OF Esb7213SensorEntry .1.3.6.1.4.1.28507.66.1.6.1 |
esb7213SensorEntry Esb7213SensorEntry .1.3.6.1.4.1.28507.66.1.6.1.1 |
esb7213SensorIndexro Integer32 .1.3.6.1.4.1.28507.66.1.6.1.1.1 |
esb7213TempSensoractual temperaturero Integer32 UNITS "0.1 degree Celsius" .1.3.6.1.4.1.28507.66.1.6.1.1.2 |
esb7213HygroSensoractual humidityro Integer32 UNITS "0.1 percent humidity" .1.3.6.1.4.1.28507.66.1.6.1.1.3 |
esb7213InputSensorlogical state of input sensorro Enumeration .1.3.6.1.4.1.28507.66.1.6.1.1.4 |
esb7213AirPressureactual air pressurero Integer32 UNITS "1 hPA (hectopascal) ~ 1 milibar" .1.3.6.1.4.1.28507.66.1.6.1.1.5 |
esb7213DewPointdew point for actual temperature and humidityro Integer32 UNITS "0.1 degree Celsius" .1.3.6.1.4.1.28507.66.1.6.1.1.6 |
esb7213DewPointDiffdifference between dew point and actual temperature (Temp - DewPoint)ro Integer32 UNITS "0.1 degree Celsius" .1.3.6.1.4.1.28507.66.1.6.1.1.7 |
esb7213ExtSensorNameA textual string containing name of a external Sensorrw OCTET STRING .1.3.6.1.4.1.28507.66.1.6.1.1.32 |
esb7213ExtInputs OBJECT IDENTIFIER .1.3.6.1.4.1.28507.66.1.6.2 |
esb7213ExtActiveInputsNumber of suppported Input Channels.ro Unsigned32 .1.3.6.1.4.1.28507.66.1.6.2.1 |
esb7213ExtInputTable SEQUENCE OF Esb7213ExtInputEntry .1.3.6.1.4.1.28507.66.1.6.2.2 |
esb7213ExtInputEntry Esb7213ExtInputEntry .1.3.6.1.4.1.28507.66.1.6.2.2.1 |
esb7213ExtInputIndexro Unsigned32 .1.3.6.1.4.1.28507.66.1.6.2.2.1.1 |
esb7213ExtInputInput state of devicero Enumeration .1.3.6.1.4.1.28507.66.1.6.2.2.1.2 |
esb7213ExtInputNameA textual string containing name of the Inputrw OCTET STRING .1.3.6.1.4.1.28507.66.1.6.2.2.1.32 |
esb7213ExtInputPortNumNumber of external Sensor Port when value greater zero, else device built-in Input.ro Integer32 .1.3.6.1.4.1.28507.66.1.6.2.2.1.33 |
esb7213ExtInputBlockIndexEither index of device built-in Input, or index of Input in external sensor.ro Integer32 .1.3.6.1.4.1.28507.66.1.6.2.2.1.34 |
esb7213Conf OBJECT IDENTIFIER .1.3.6.1.4.1.28507.66.2 |
esb7213Groups OBJECT IDENTIFIER .1.3.6.1.4.1.28507.66.2.1 |
esb7213BasicGroupBasic objects. Unknown .1.3.6.1.4.1.28507.66.2.1.1 |
esb7213NotificationGroup Unknown .1.3.6.1.4.1.28507.66.2.1.2 |
esb7213Compls OBJECT IDENTIFIER .1.3.6.1.4.1.28507.66.2.2 |
events OBJECT IDENTIFIER .1.3.6.1.4.1.28507.66.3 |
esb7213TempEvtSentemperature limits exceeded NOTIFICATION-TYPE .1.3.6.1.4.1.28507.66.3.1 |
esb7213HygroEvtSenhygro limits exceeded NOTIFICATION-TYPE .1.3.6.1.4.1.28507.66.3.2 |
esb7213InputEvtSenchange of logical input sensor state NOTIFICATION-TYPE .1.3.6.1.4.1.28507.66.3.3 |
esb7213AirPressureEvtSenAir Pressure limits exceeded NOTIFICATION-TYPE .1.3.6.1.4.1.28507.66.3.4 |
esb7213DewPtDiffEvtSenDew Point Difference limits exceeded NOTIFICATION-TYPE .1.3.6.1.4.1.28507.66.3.5 |
esb7213POEEvtPower over Ethernet changed NOTIFICATION-TYPE .1.3.6.1.4.1.28507.66.3.6 |
esb7213ExtInputEvtChange of external sensor input. NOTIFICATION-TYPE .1.3.6.1.4.1.28507.66.3.25 |