GUDEADS-ESB7214-MIB
The GUDEADS-ESB7214-MIB module facilitates the monitoring and management of the Expert Power Control 7214 power distribution unit, specifically exposing metrics for input/output voltage, current, power consumption, temperature sensors, and relay status via SNMP.
Imported Objects
Objects
78 total| Object Name |
|---|
gudeadsExpert Power Control 7214 MIB MODULE-IDENTITY .1.3.6.1.4.1.28507 |
gadsESB7214 OBJECT IDENTIFIER .1.3.6.1.4.1.28507.67 |
esb7214Objects OBJECT IDENTIFIER .1.3.6.1.4.1.28507.67.1 |
esb7214CommonConfig OBJECT IDENTIFIER .1.3.6.1.4.1.28507.67.1.1 |
esb7214SNMPaccess OBJECT IDENTIFIER .1.3.6.1.4.1.28507.67.1.1.1 |
esb7214TrapCtrl0 = off 1 = Ver. 1 2 = Ver. 2c 3 = Ver. 3rw Integer32 .1.3.6.1.4.1.28507.67.1.1.1.1 |
esb7214TrapIPTablelist of all Trap receiver SEQUENCE OF Esb7214TrapIPEntry .1.3.6.1.4.1.28507.67.1.1.1.2 |
esb7214TrapIPEntryan entry containing management informations regarding the list of trap receivers Esb7214TrapIPEntry .1.3.6.1.4.1.28507.67.1.1.1.2.1 |
esb7214TrapIPIndexA unique value, greater than zero, for each receiver slot.ro Integer32 .1.3.6.1.4.1.28507.67.1.1.1.2.1.1 |
esb7214TrapAddrDNS name or IP address specifying one Trap receiver slot. A port can optionally be specified: 'name:port' An empty string disables this slot.rw OCTET STRING .1.3.6.1.4.1.28507.67.1.1.1.2.1.2 |
esb7214DeviceConfig OBJECT IDENTIFIER .1.3.6.1.4.1.28507.67.1.2 |
esb7214IntActors OBJECT IDENTIFIER .1.3.6.1.4.1.28507.67.1.3 |
esb7214relayports OBJECT IDENTIFIER .1.3.6.1.4.1.28507.67.1.3.1 |
esb7214portNumberThe number of Relay Portsro Integer32 .1.3.6.1.4.1.28507.67.1.3.1.1 |
esb7214portTablelist of all ENC Relay Ports SEQUENCE OF Esb7214portEntry .1.3.6.1.4.1.28507.67.1.3.1.2 |
esb7214portEntryAn entry containing management information applicable to a particular relay port. Esb7214portEntry .1.3.6.1.4.1.28507.67.1.3.1.2.1 |
esb7214PortIndexA unique value, greater than zero, for each Relay Port.ro Integer32 .1.3.6.1.4.1.28507.67.1.3.1.2.1.1 |
esb7214PortNameA textual string containing name of a Relay Port.rw OCTET STRING .1.3.6.1.4.1.28507.67.1.3.1.2.1.2 |
esb7214PortStatecurrent state of a Relay Portrw Enumeration .1.3.6.1.4.1.28507.67.1.3.1.2.1.3 |
esb7214PortSwitchCountThe total number of switch actions ocurred on a Relay Port. Does not count switch commands which will not switch the ralay state, so just real relay switches are displayed here.ro Integer32 .1.3.6.1.4.1.28507.67.1.3.1.2.1.4 |
esb7214PortStartupModeset Mode of startup sequence (off, on , remember last state)rw Enumeration .1.3.6.1.4.1.28507.67.1.3.1.2.1.5 |
esb7214PortStartupDelayDelay in sec for startup actionrw Integer32 UNITS "seconds" .1.3.6.1.4.1.28507.67.1.3.1.2.1.6 |
esb7214PortRepowerTimeDelay in sec for repower port after switching offrw Integer32 .1.3.6.1.4.1.28507.67.1.3.1.2.1.7 |
esb7214PortResetDurationDelay in sec for turning Port on again after Reset actionrw Integer32 .1.3.6.1.4.1.28507.67.1.3.1.2.1.8 |
esb7214ExtActors OBJECT IDENTIFIER .1.3.6.1.4.1.28507.67.1.4 |
esb7214IntSensors OBJECT IDENTIFIER .1.3.6.1.4.1.28507.67.1.5 |
esb7214Inputs OBJECT IDENTIFIER .1.3.6.1.4.1.28507.67.1.5.6 |
esb7214ActiveInputsNumber of suppported Input Channels.ro Unsigned32 .1.3.6.1.4.1.28507.67.1.5.6.1 |
esb7214InputTable SEQUENCE OF Esb7214InputEntry .1.3.6.1.4.1.28507.67.1.5.6.2 |
esb7214InputEntry Esb7214InputEntry .1.3.6.1.4.1.28507.67.1.5.6.2.1 |
esb7214InputIndexro Integer32 .1.3.6.1.4.1.28507.67.1.5.6.2.1.1 |
esb7214InputInput state of devicero Enumeration .1.3.6.1.4.1.28507.67.1.5.6.2.1.2 |
esb7214InputNameA textual string containing name of the Inputrw OCTET STRING .1.3.6.1.4.1.28507.67.1.5.6.2.1.32 |
esb7214POEsignals POE availabilityro Integer32 .1.3.6.1.4.1.28507.67.1.5.10 |
esb7214PwrSupplyTablePower Supply Table - shows if Power Supply is avail SEQUENCE OF Esb7214PwrSupplyEntry .1.3.6.1.4.1.28507.67.1.5.13 |
esb7214PwrSupplyEntry Esb7214PwrSupplyEntry .1.3.6.1.4.1.28507.67.1.5.13.1 |
esb7214PwrSupplyIndexIndex of Power Supply entriesro Integer32 .1.3.6.1.4.1.28507.67.1.5.13.1.1 |
esb7214PwrSupplyStatusshows status of the Power Supply 1 = fst, 2 = snd etc.ro Enumeration .1.3.6.1.4.1.28507.67.1.5.13.1.2 |
esb7214NTPClient OBJECT IDENTIFIER .1.3.6.1.4.1.28507.67.1.5.15 |
esb7214NTPTimeValidShow if valid Time is receivedro Enumeration .1.3.6.1.4.1.28507.67.1.5.15.1 |
esb7214NTPUnixTimeshow received NTP time as unixtime (secs since 1 January 1970)ro Unsigned32 UNITS "s" .1.3.6.1.4.1.28507.67.1.5.15.2 |
esb7214NTPLastValidTimestampshow seconds since last valid NTP timestamp receivedro Unsigned32 UNITS "s" .1.3.6.1.4.1.28507.67.1.5.15.3 |
esb7214ExtSensors OBJECT IDENTIFIER .1.3.6.1.4.1.28507.67.1.6 |
esb7214SensorTable SEQUENCE OF Esb7214SensorEntry .1.3.6.1.4.1.28507.67.1.6.1 |
esb7214SensorEntry Esb7214SensorEntry .1.3.6.1.4.1.28507.67.1.6.1.1 |
esb7214SensorIndexro Integer32 .1.3.6.1.4.1.28507.67.1.6.1.1.1 |
esb7214TempSensoractual temperaturero Integer32 UNITS "0.1 degree Celsius" .1.3.6.1.4.1.28507.67.1.6.1.1.2 |
esb7214HygroSensoractual humidityro Integer32 UNITS "0.1 percent humidity" .1.3.6.1.4.1.28507.67.1.6.1.1.3 |
esb7214InputSensorlogical state of input sensorro Enumeration .1.3.6.1.4.1.28507.67.1.6.1.1.4 |
esb7214AirPressureactual air pressurero Integer32 UNITS "1 hPA (hectopascal) ~ 1 milibar" .1.3.6.1.4.1.28507.67.1.6.1.1.5 |
esb7214DewPointdew point for actual temperature and humidityro Integer32 UNITS "0.1 degree Celsius" .1.3.6.1.4.1.28507.67.1.6.1.1.6 |
esb7214DewPointDiffdifference between dew point and actual temperature (Temp - DewPoint)ro Integer32 UNITS "0.1 degree Celsius" .1.3.6.1.4.1.28507.67.1.6.1.1.7 |
esb7214ExtSensorNameA textual string containing name of a external Sensorrw OCTET STRING .1.3.6.1.4.1.28507.67.1.6.1.1.32 |
esb7214ExtInputs OBJECT IDENTIFIER .1.3.6.1.4.1.28507.67.1.6.2 |
esb7214ExtActiveInputsNumber of suppported Input Channels.ro Unsigned32 .1.3.6.1.4.1.28507.67.1.6.2.1 |
esb7214ExtInputTable SEQUENCE OF Esb7214ExtInputEntry .1.3.6.1.4.1.28507.67.1.6.2.2 |
esb7214ExtInputEntry Esb7214ExtInputEntry .1.3.6.1.4.1.28507.67.1.6.2.2.1 |
esb7214ExtInputIndexro Unsigned32 .1.3.6.1.4.1.28507.67.1.6.2.2.1.1 |
esb7214ExtInputInput state of devicero Enumeration .1.3.6.1.4.1.28507.67.1.6.2.2.1.2 |
esb7214ExtInputNameA textual string containing name of the Inputrw OCTET STRING .1.3.6.1.4.1.28507.67.1.6.2.2.1.32 |
esb7214ExtInputPortNumNumber of external Sensor Port when value greater zero, else device built-in Input.ro Integer32 .1.3.6.1.4.1.28507.67.1.6.2.2.1.33 |
esb7214ExtInputBlockIndexEither index of device built-in Input, or index of Input in external sensor.ro Integer32 .1.3.6.1.4.1.28507.67.1.6.2.2.1.34 |
esb7214Conf OBJECT IDENTIFIER .1.3.6.1.4.1.28507.67.2 |
esb7214Groups OBJECT IDENTIFIER .1.3.6.1.4.1.28507.67.2.1 |
esb7214BasicGroupBasic objects. Unknown .1.3.6.1.4.1.28507.67.2.1.1 |
esb7214NotificationGroup Unknown .1.3.6.1.4.1.28507.67.2.1.2 |
esb7214Compls OBJECT IDENTIFIER .1.3.6.1.4.1.28507.67.2.2 |
events OBJECT IDENTIFIER .1.3.6.1.4.1.28507.67.3 |
esb7214SwitchEvtPortEvent is triggered when a port is switched NOTIFICATION-TYPE .1.3.6.1.4.1.28507.67.3.1 |
esb7214InputEvtChange of device input. NOTIFICATION-TYPE .1.3.6.1.4.1.28507.67.3.2 |
esb7214TempEvtSentemperature limits exceeded NOTIFICATION-TYPE .1.3.6.1.4.1.28507.67.3.3 |
esb7214HygroEvtSenhygro limits exceeded NOTIFICATION-TYPE .1.3.6.1.4.1.28507.67.3.4 |
esb7214InputEvtSenchange of logical input sensor state NOTIFICATION-TYPE .1.3.6.1.4.1.28507.67.3.5 |
esb7214AirPressureEvtSenAir Pressure limits exceeded NOTIFICATION-TYPE .1.3.6.1.4.1.28507.67.3.6 |
esb7214DewPtDiffEvtSenDew Point Difference limits exceeded NOTIFICATION-TYPE .1.3.6.1.4.1.28507.67.3.7 |
esb7214POEEvtPower over Ethernet changed NOTIFICATION-TYPE .1.3.6.1.4.1.28507.67.3.8 |
esb7214PwrSupplyChangeEvtEvent is triggered when Power Supply state changes NOTIFICATION-TYPE .1.3.6.1.4.1.28507.67.3.9 |
esb7214ExtInputEvtChange of external sensor input. NOTIFICATION-TYPE .1.3.6.1.4.1.28507.67.3.25 |
More MIBs from Gude Analog- und Digitalsysteme GmbH
Browse all Gude Analog- und Digitalsysteme GmbHMIBs →The GUDEADS-ESB7213-MIB module facilitates SNMP-based monitoring and management of the Expert Power Control 7213 hardware platform, specifically exposing telemetry for power supply status, voltage levels, current draw, and thermal sensor readings. This module enables network administrators to track real-time power consumption metrics and fault conditions on the ESB7213 chassis to ensure electrical stability and prevent hardware failure.
Standard SNMP MIB module defining data structures for GUDEADS-EPC8X-MIB.
Standard SNMP MIB module defining data structures for GUDEADS-EPC2X6-MIB.
Standard SNMP MIB module defining data structures for GUDEADS-PDU8310-MIB.
Standard SNMP MIB module defining data structures for GUDEADS-PDU8110-MIB.
Standard SNMP MIB module defining data structures for GUDEADS-ETS-MIB.