GUDEADS-EPC8X-MIB
Standard SNMP MIB module defining data structures for GUDEADS-EPC8X-MIB.
Imported Objects
Objects
46 total| Object Name |
|---|
gudeads MODULE-IDENTITY .1.3.6.1.4.1.28507 |
gadsEPC8 OBJECT IDENTIFIER .1.3.6.1.4.1.28507.1 |
events OBJECT IDENTIFIER .1.3.6.1.4.1.28507.1.0 |
epcSwitchEvtPort1Event is triggered when a port is switched NOTIFICATION-TYPE .1.3.6.1.4.1.28507.1.0.1 |
epcSwitchEvtPort2Event is triggered when a port is switched NOTIFICATION-TYPE .1.3.6.1.4.1.28507.1.0.2 |
epcSwitchEvtPort3Event is triggered when a port is switched NOTIFICATION-TYPE .1.3.6.1.4.1.28507.1.0.3 |
epcSwitchEvtPort4Event is triggered when a port is switched NOTIFICATION-TYPE .1.3.6.1.4.1.28507.1.0.4 |
epcSwitchEvtPort5Event is triggered when a port is switched NOTIFICATION-TYPE .1.3.6.1.4.1.28507.1.0.5 |
epcSwitchEvtPort6Event is triggered when a port is switched NOTIFICATION-TYPE .1.3.6.1.4.1.28507.1.0.6 |
epcSwitchEvtPort7Event is triggered when a port is switched NOTIFICATION-TYPE .1.3.6.1.4.1.28507.1.0.7 |
epcSwitchEvtPort8Event is triggered when a port is switched NOTIFICATION-TYPE .1.3.6.1.4.1.28507.1.0.8 |
epc8TempEvtSen1temperature limits exceeded NOTIFICATION-TYPE .1.3.6.1.4.1.28507.1.0.9 |
epc8TempEvtSen2temperature limits exceeded NOTIFICATION-TYPE .1.3.6.1.4.1.28507.1.0.10 |
epc8HygroEvtSen1hygro limits exceeded NOTIFICATION-TYPE .1.3.6.1.4.1.28507.1.0.11 |
epc8HygroEvtSen2hygro limits exceeded NOTIFICATION-TYPE .1.3.6.1.4.1.28507.1.0.12 |
epc8Objects OBJECT IDENTIFIER .1.3.6.1.4.1.28507.1.1 |
epc8SNMPaccess OBJECT IDENTIFIER .1.3.6.1.4.1.28507.1.1.1 |
epc8TrapCtrl0 = off 1 = Ver. 1 2 = Ver. 2crw Integer32 .1.3.6.1.4.1.28507.1.1.1.1 |
epc8TrapIPTablelist of all Trap receiver SEQUENCE OF Epc8TrapIPEntry .1.3.6.1.4.1.28507.1.1.1.2 |
epc8TrapIPEntryan entry containing management informations regarding the list of trap receivers Epc8TrapIPEntry .1.3.6.1.4.1.28507.1.1.1.2.1 |
epc8TrapIPIndexA unique value, greater than zero, for each receiver slot. Integer32 .1.3.6.1.4.1.28507.1.1.1.2.1.1 |
epc8TrapIPAddrIP Address specifying one Trap receiver slot. A value of '00000000'H disables this slot.rw IpAddress .1.3.6.1.4.1.28507.1.1.1.2.1.2 |
epc8TrapIPPortIP Port specifying one Trap receiver slot. A value of 0 disables this slot.rw Integer32 .1.3.6.1.4.1.28507.1.1.1.2.1.3 |
epc8powerports OBJECT IDENTIFIER .1.3.6.1.4.1.28507.1.1.2 |
epc8portNumberThe number of PowerPortsro Integer32 .1.3.6.1.4.1.28507.1.1.2.1 |
epc8portTablelist of all EPC Powerports SEQUENCE OF Epc8portEntry .1.3.6.1.4.1.28507.1.1.2.2 |
epc8portEntryAn entry containing management information applicable to a particular powerport. Epc8portEntry .1.3.6.1.4.1.28507.1.1.2.2.1 |
epc8PortIndexA unique value, greater than zero, for each PowerPort. Integer32 .1.3.6.1.4.1.28507.1.1.2.2.1.1 |
epc8PortNameA textual string containing name of a PowerPort.ro OCTET STRING .1.3.6.1.4.1.28507.1.1.2.2.1.2 |
epc8PortStatecurrent state a PowerPortrw Enumeration .1.3.6.1.4.1.28507.1.1.2.2.1.3 |
epc8PortSwitchCountThe total number of switch actions ocurred on a PowerPort. Does not count switch commands which will not switch the ralay state, so just real relay switches are displayed here.ro Counter32 .1.3.6.1.4.1.28507.1.1.2.2.1.4 |
epc8PortStartupModeset Mode of startup sequence (off, on , remember last state)rw Enumeration .1.3.6.1.4.1.28507.1.1.2.2.1.5 |
epc8PortStartupDelayDelay in sec for startup actionrw Integer32 UNITS "seconds" .1.3.6.1.4.1.28507.1.1.2.2.1.6 |
epc8PortRepowerTimeDelay in sec for repower port after switching offrw Integer32 .1.3.6.1.4.1.28507.1.1.2.2.1.7 |
epc8Sensors OBJECT IDENTIFIER .1.3.6.1.4.1.28507.1.1.3 |
epc8Irmsactual rms Current, a value of -9999 indicates that data is not availablero Integer32 UNITS "mA" .1.3.6.1.4.1.28507.1.1.3.1 |
epc8SensorTable SEQUENCE OF Epc8SensorEntry .1.3.6.1.4.1.28507.1.1.3.2 |
epc8SensorEntry Epc8SensorEntry .1.3.6.1.4.1.28507.1.1.3.2.1 |
epc8SensorIndex Integer32 .1.3.6.1.4.1.28507.1.1.3.2.1.1 |
epc8TempSensoractual temperature, a value of -9999 indicates that data is not availablero Integer32 UNITS "10th of degree Celsius" .1.3.6.1.4.1.28507.1.1.3.2.1.2 |
epc8HygroSensoractual humidity, a value of -9999 indicates that data is not availablero Integer32 UNITS "10th of percentage humidity" .1.3.6.1.4.1.28507.1.1.3.2.1.3 |
epc8Conf OBJECT IDENTIFIER .1.3.6.1.4.1.28507.1.3 |
epc8Groups OBJECT IDENTIFIER .1.3.6.1.4.1.28507.1.3.1 |
epc8BasicGroupBasic objects. Unknown .1.3.6.1.4.1.28507.1.3.1.1 |
epc8NotificationGroup Unknown .1.3.6.1.4.1.28507.1.3.1.2 |
epc8Compls OBJECT IDENTIFIER .1.3.6.1.4.1.28507.1.3.2 |
More MIBs from Gude Analog- und Digitalsysteme GmbH
Browse all Gude Analog- und Digitalsysteme GmbHMIBs →The GUDEADS-ESB7214-MIB module facilitates the monitoring and management of the Expert Power Control 7214 power distribution unit, specifically exposing metrics for input/output voltage, current, power consumption, temperature sensors, and relay status via SNMP.
The GUDEADS-ESB7213-MIB module facilitates SNMP-based monitoring and management of the Expert Power Control 7213 hardware platform, specifically exposing telemetry for power supply status, voltage levels, current draw, and thermal sensor readings. This module enables network administrators to track real-time power consumption metrics and fault conditions on the ESB7213 chassis to ensure electrical stability and prevent hardware failure.
Standard SNMP MIB module defining data structures for GUDEADS-EPC2X6-MIB.
Standard SNMP MIB module defining data structures for GUDEADS-PDU8310-MIB.
Standard SNMP MIB module defining data structures for GUDEADS-PDU8110-MIB.