Home/Catalog/EATON-PDU-MIB

EATON-PDU-MIB

AI MIB Summary

The EATON-PDU-MIB enables SNMP-based monitoring and management of Eaton Power Distribution Units, providing access to real-time electrical metrics including voltage, current, power consumption, and outlet-level status. It facilitates granular control over individual PDU outlets and aggregates environmental data such as temperature and humidity for infrastructure capacity planning and fault detection.

The MIB module for Eaton PDUs (Power Distribution Units). Copyright (C) Eaton Corporation (2007).
Main OID:
eatonPduMIB.1.3.6.1.4.1.534.6.6.4
92
Objects
Active
Status
4
Dependencies

Imported Objects

Objects

92 total
Object Name
eatonPduMIBThe MIB module for Eaton PDUs (Power Distribution Units). Copyright (C) Eaton Corporation (2007).
MODULE-IDENTITY
.1.3.6.1.4.1.534.6.6.4
eatonPduMIBObjects
OBJECT IDENTIFIER
.1.3.6.1.4.1.534.6.6.4.1
mainPdu
OBJECT IDENTIFIER
.1.3.6.1.4.1.534.6.6.4.1.1
pduNameplate
OBJECT IDENTIFIER
.1.3.6.1.4.1.534.6.6.4.1.1.1
pduRatingVAThe full VA rating of this PDU (for all phases).ro
PositiveInteger UNITS "volt-amps"
.1.3.6.1.4.1.534.6.6.4.1.1.1.1
pduNominalOutputVoltageThe nominal Output Voltage of this PDU (as distributed to the panels). May differ from the nominal Input Voltage if the PDU has an input transformer. This is either Line-to-Line or Line-to-Neutral, as indicated in pduOutputVoltageUnits.ro
PositiveInteger UNITS "Volts RMS"
.1.3.6.1.4.1.534.6.6.4.1.1.1.2
pduNumPhasesThe number of lines (phases) for this PDU. The number of Input phases must equal the number of Output phases.ro
PositiveInteger
.1.3.6.1.4.1.534.6.6.4.1.1.1.3
pduNumPanelsThe number of panels or subfeeds contained in this PDU system. This determines the number of rows found in the panel tables.ro
PositiveInteger
.1.3.6.1.4.1.534.6.6.4.1.1.1.4
pduInput
OBJECT IDENTIFIER
.1.3.6.1.4.1.534.6.6.4.1.1.2
pduFrequencyThe present frequency reading for the full PDU.ro
NonNegativeInteger UNITS "0.1 Hertz"
.1.3.6.1.4.1.534.6.6.4.1.1.2.1
pduInputVAThe present VA input demand of the full PDU system.ro
NonNegativeInteger UNITS "VA"
.1.3.6.1.4.1.534.6.6.4.1.1.2.2
pduInputPowerThe present input power demand of the full PDU system.ro
NonNegativeInteger UNITS "Watts"
.1.3.6.1.4.1.534.6.6.4.1.1.2.3
pduInputPowerFactorThe input power factor for the full PDU system. Varies from -1.00 to 1.00, multiplied by 100. If negative values are used, they indicate lagging pf.ro
Integer32 (-100..100) UNITS "pf * 100"
.1.3.6.1.4.1.534.6.6.4.1.1.2.4
pduGroundCurrentThe present current in the PDU's ground phase. Ideally, this value stays at 0.ro
NonNegativeInteger UNITS "0.1 Amps RMS"
.1.3.6.1.4.1.534.6.6.4.1.1.2.5
pduInputVoltageUnitsIndicates whether the pduInputPhaseVoltage readings are 'Vrms Line-Line' or 'Vrms Line-Neutral'.ro
DisplayString
.1.3.6.1.4.1.534.6.6.4.1.1.2.6
pduInputNumPhasesThe number of input phases for this PDU. This variable indicates the number of rows in the pduInputTable.ro
PositiveInteger
.1.3.6.1.4.1.534.6.6.4.1.1.2.7
pduInputTableA list of input table entries. The number of entries is given by the value of pduInputNumPhases.
SEQUENCE OF PduInputEntry
.1.3.6.1.4.1.534.6.6.4.1.1.2.8
pduInputEntryAn entry containing information applicable to a particular input phase.
PduInputEntry
.1.3.6.1.4.1.534.6.6.4.1.1.2.8.1
pduInputPhaseIndexThe input line identifier.
PositiveInteger
.1.3.6.1.4.1.534.6.6.4.1.1.2.8.1.1
pduInputPhaseVoltageThe present input voltage for this phase.ro
NonNegativeInteger UNITS "Volts RMS"
.1.3.6.1.4.1.534.6.6.4.1.1.2.8.1.2
pduInputPhaseCurrentThe present input current for this phase.ro
NonNegativeInteger UNITS "0.1 Amps RMS"
.1.3.6.1.4.1.534.6.6.4.1.1.2.8.1.3
pduInputPhasePercentLoadThe percentage of the pdu power capacity presently being used on this line, normally based on the ratio of pduInputPhaseCurrent to the rated input current.ro
Integer32
.1.3.6.1.4.1.534.6.6.4.1.1.2.8.1.4
pduOutput
OBJECT IDENTIFIER
.1.3.6.1.4.1.534.6.6.4.1.1.3
pduOutputKilowattHoursThe accumulated kilowatt-hour value for the full PDU system since the last reset.ro
NonNegativeInteger UNITS "KWH"
.1.3.6.1.4.1.534.6.6.4.1.1.3.1
pduOutputVAThe present VA output of the full PDU system.ro
NonNegativeInteger UNITS "VA"
.1.3.6.1.4.1.534.6.6.4.1.1.3.2
pduOutputPowerThe present output power of the full PDU system.ro
NonNegativeInteger UNITS "Watts"
.1.3.6.1.4.1.534.6.6.4.1.1.3.3
pduOutputPowerFactorThe output power factor for the full PDU system. Varies from -1.00 to 1.00, multiplied by 100. If negative values are used, they indicate lagging pf.ro
Integer32 (-100..100) UNITS "pf * 100"
.1.3.6.1.4.1.534.6.6.4.1.1.3.4
pduNeutralCurrentThe present current in the PDU's output neutral phase. Ideally, this value stays at 0.ro
NonNegativeInteger UNITS "0.1 Amps RMS"
.1.3.6.1.4.1.534.6.6.4.1.1.3.5
pduRatedOutputCurrentThe rated current value for one PDU Output phase at full load (100%).ro
PositiveInteger UNITS "0.1 Amps RMS"
.1.3.6.1.4.1.534.6.6.4.1.1.3.6
pduOutputVoltageUnitsIndicates whether the pduOutputPhaseVoltage readings are 'Vrms Line-Line' or 'Vrms Line-Neutral'.ro
DisplayString
.1.3.6.1.4.1.534.6.6.4.1.1.3.7
pduOutputNumPhasesThe number of output phases for this PDU. This variable indicates the number of rows in the pduOutputTable.ro
PositiveInteger
.1.3.6.1.4.1.534.6.6.4.1.1.3.8
pduOutputTableA list of output table entries. The number of entries is given by the value of pduOutputNumPhases.
SEQUENCE OF PduOutputEntry
.1.3.6.1.4.1.534.6.6.4.1.1.3.9
pduOutputEntryAn entry containing information applicable to a particular output phase.
PduOutputEntry
.1.3.6.1.4.1.534.6.6.4.1.1.3.9.1
pduOutputPhaseIndexThe output line identifier.
PositiveInteger
.1.3.6.1.4.1.534.6.6.4.1.1.3.9.1.1
pduOutputPhaseVoltageThe present output voltage for this phase.ro
NonNegativeInteger UNITS "Volts RMS"
.1.3.6.1.4.1.534.6.6.4.1.1.3.9.1.2
pduOutputPhaseCurrentThe present output current for this phase.ro
NonNegativeInteger UNITS "0.1 Amps RMS"
.1.3.6.1.4.1.534.6.6.4.1.1.3.9.1.3
pduOutputPhasePercentLoadThe percentage of the pdu power capacity presently being used on this line, normally based on the ratio of pduOutputPhaseCurrent to pduRatedOutputCurrent.ro
Integer32
.1.3.6.1.4.1.534.6.6.4.1.1.3.9.1.4
pduPanel
OBJECT IDENTIFIER
.1.3.6.1.4.1.534.6.6.4.1.2
panelRatingsTableA sparsely populated (ie, not sequentially numbered) table of ratings for each panel. The number of entries is given by the value of pduNumPanels.
SEQUENCE OF PanelRatingsEntry
.1.3.6.1.4.1.534.6.6.4.1.2.1
panelRatingsEntryAn entry containing information applicable to a particular output phase.
PanelRatingsEntry
.1.3.6.1.4.1.534.6.6.4.1.2.1.1
panelNumberIndex for the Panel Ratings and Meters tables. Corresponds to the physical panel number in the PDU system. There must be a #1. The maximum value is 16. Panels are not required to be numbered sequentially.
PositiveInteger
.1.3.6.1.4.1.534.6.6.4.1.2.1.1.1
panelRatedVoltageThe nominal Voltage of this panel (as distributed to the breakers or subfeeds). This is either Line-to-Line or Line-to-Neutral, as indicated in panelVoltageUnits.ro
PositiveInteger UNITS "Volts RMS"
.1.3.6.1.4.1.534.6.6.4.1.2.1.1.2
panelRatedBreakerCurrentThe rated current value for one panel (input) phase at full load (100%). This is set by the panel's input breaker; if there is no input breaker for this panel, then this object is not accessible.ro
PositiveInteger UNITS "0.1 Amps RMS"
.1.3.6.1.4.1.534.6.6.4.1.2.1.1.3
panelNumPhasesThe number of lines (phases) for this panel.ro
PositiveInteger
.1.3.6.1.4.1.534.6.6.4.1.2.1.1.4
panelNumBreakersThe number of breakers contained in this panel. This determines the number of rows found in the breaker tables.ro
PositiveInteger
.1.3.6.1.4.1.534.6.6.4.1.2.1.1.5
panelVoltageUnitsIndicates whether the panelPhaseVoltage readings are 'Vrms Line-Line' or 'Vrms Line-Neutral'.ro
DisplayString
.1.3.6.1.4.1.534.6.6.4.1.2.1.1.6
panelMetersTableA sparsely populated (ie, not sequentially numbered) table of ratings for each panel. The number of entries is given by the value of pduNumPanels.
SEQUENCE OF PanelMetersEntry
.1.3.6.1.4.1.534.6.6.4.1.2.2
panelMetersEntryAn entry containing meter readings applicable to a particular panel.
PanelMetersEntry
.1.3.6.1.4.1.534.6.6.4.1.2.2.1
panelTotalKilowattHoursThe accumulated kilowatt-hours for this panel since it was commissioned and put into service, or since the last reset of the system KHW measures.ro
NonNegativeInteger UNITS "KWH"
.1.3.6.1.4.1.534.6.6.4.1.2.2.1.1
panelMonthlyKilowattHoursThe accumulated kilowatt-hours for this panel since the beginning of this calendar month, or since the last reset of the system KHW measures.ro
NonNegativeInteger UNITS "KWH"
.1.3.6.1.4.1.534.6.6.4.1.2.2.1.2
panelYtdKilowattHoursThe accumulated kilowatt-hours for this panel since the beginning of this calendar year (YTD), or since the last reset of the system KHW measures.ro
NonNegativeInteger UNITS "KWH"
.1.3.6.1.4.1.534.6.6.4.1.2.2.1.3
panelVAThe present VA (input) demand of this panel.ro
NonNegativeInteger UNITS "VA"
.1.3.6.1.4.1.534.6.6.4.1.2.2.1.4
panelPowerThe present power (input) demand of this panel.ro
NonNegativeInteger UNITS "Watts"
.1.3.6.1.4.1.534.6.6.4.1.2.2.1.5
panelPowerFactorThe input power factor for this panel. Varies from -1.00 to 1.00, multiplied by 100. If negative values are used, they indicate lagging pf.ro
Integer32 (-100..100) UNITS "pf * 100"
.1.3.6.1.4.1.534.6.6.4.1.2.2.1.6
panelNeutralCurrentThe present neutral phase current for this panel.ro
NonNegativeInteger UNITS "0.1 Amps RMS"
.1.3.6.1.4.1.534.6.6.4.1.2.2.1.7
panelPhaseMetersTableA sparsely populated (ie, not sequentially panel numbered) table of ratings for each panel. The number of entries is given by the sum of panelNumPhases for pduNumPanels.
SEQUENCE OF PanelPhaseMetersEntry
.1.3.6.1.4.1.534.6.6.4.1.2.3
panelPhaseMetersEntryAn entry containing meter readings applicable to a particular phase of a particular panel.
PanelPhaseMetersEntry
.1.3.6.1.4.1.534.6.6.4.1.2.3.1
panelPhaseIndexThe line or phase identifier.
PositiveInteger
.1.3.6.1.4.1.534.6.6.4.1.2.3.1.1
panelPhaseVoltageThe present voltage for this phase.ro
NonNegativeInteger UNITS "Volts RMS"
.1.3.6.1.4.1.534.6.6.4.1.2.3.1.2
panelPhaseCurrentThe present current for this phase.ro
NonNegativeInteger UNITS "0.1 Amps RMS"
.1.3.6.1.4.1.534.6.6.4.1.2.3.1.3
panelPhasePercentLoadThe percentage of the panel power capacity presently being used on this line, normally based on the ratio of panelPhaseCurrent to the rated phase current.ro
Integer32
.1.3.6.1.4.1.534.6.6.4.1.2.3.1.4
pduBreaker
OBJECT IDENTIFIER
.1.3.6.1.4.1.534.6.6.4.1.3
breakerRatingsTableA sparsely populated (ie, not sequentially numbered) table of ratings and fixed values for each breaker. The number of entries is given by the value of panelNumBreakers for this panel.
SEQUENCE OF BreakerRatingsEntry
.1.3.6.1.4.1.534.6.6.4.1.3.1
breakerRatingsEntryAn entry containing information applicable to a particular output phase.
BreakerRatingsEntry
.1.3.6.1.4.1.534.6.6.4.1.3.1.1
breakerNumberIndex for the Breaker Ratings and Meters tables. Corresponds to the physical breaker number in the PDU system. Breakers are not required to be numbered sequentially.
PositiveInteger
.1.3.6.1.4.1.534.6.6.4.1.3.1.1.1
breakerNameName given by the administrator to identify this breaker.ro
DisplayString
.1.3.6.1.4.1.534.6.6.4.1.3.1.1.2
breakerRatedCurrentThe rated current value of this breaker (for one phase) at full load (100%).ro
PositiveInteger UNITS "0.1 Amps RMS"
.1.3.6.1.4.1.534.6.6.4.1.3.1.1.3
breakerNumPhasesThe number of lines (phases) for this breaker.ro
PositiveInteger
.1.3.6.1.4.1.534.6.6.4.1.3.1.1.4
breakerMetersTableA sparsely populated (ie, not sequentially numbered) table of ratings for each breaker. The number of entries is given by the value of panelNumBreakers for this panel.
SEQUENCE OF BreakerMetersEntry
.1.3.6.1.4.1.534.6.6.4.1.3.2
breakerMetersEntryAn entry containing meter readings applicable to a particular breaker.
BreakerMetersEntry
.1.3.6.1.4.1.534.6.6.4.1.3.2.1
breakerTotalKilowattHoursThe accumulated kilowatt-hours for this breaker since it was commissioned and put into service, or since the last reset of the panel KHW measures.ro
NonNegativeInteger UNITS "KWH"
.1.3.6.1.4.1.534.6.6.4.1.3.2.1.1
breakerMonthlyKilowattHoursThe accumulated kilowatt-hours for this breaker since the beginning of this calendar month, or since the last reset of the panel KHW measures.ro
NonNegativeInteger UNITS "KWH"
.1.3.6.1.4.1.534.6.6.4.1.3.2.1.2
breakerYtdKilowattHoursThe accumulated kilowatt-hours for this breaker since the beginning of this calendar year (YTD), or since the last reset of the panel KHW measures.ro
NonNegativeInteger UNITS "KWH"
.1.3.6.1.4.1.534.6.6.4.1.3.2.1.3
breakerPhaseMetersTableA sparsely populated (ie, not sequentially breaker numbered) table of ratings for each breaker. The number of entries is given by the sum of breakerNumPhases for panelNumBreakers for all panels (pduNumPanels).
SEQUENCE OF BreakerPhaseMetersEntry
.1.3.6.1.4.1.534.6.6.4.1.3.3
breakerPhaseMetersEntryAn entry containing meter readings applicable to a particular phase of a particular breaker on a particular panel.
BreakerPhaseMetersEntry
.1.3.6.1.4.1.534.6.6.4.1.3.3.1
breakerPhaseIndexThe line or phase identifier.
PositiveInteger
.1.3.6.1.4.1.534.6.6.4.1.3.3.1.1
breakerPhaseVAThe present VA (input) demand of this phase on this breaker.ro
NonNegativeInteger UNITS "VA"
.1.3.6.1.4.1.534.6.6.4.1.3.3.1.2
breakerPhasePowerThe present power (input) demand of phase on this breaker.ro
NonNegativeInteger UNITS "Watts"
.1.3.6.1.4.1.534.6.6.4.1.3.3.1.3
breakerPhasePowerFactorThe input power factor for this phase on this breaker. Varies from -1.00 to 1.00, multiplied by 100. If negative values are used, they indicate lagging pf.ro
Integer32 (-100..100) UNITS "pf * 100"
.1.3.6.1.4.1.534.6.6.4.1.3.3.1.4
breakerPhaseCurrentThe present current for this phase of this breaker.ro
NonNegativeInteger UNITS "0.1 Amps RMS"
.1.3.6.1.4.1.534.6.6.4.1.3.3.1.5
breakerPhasePercentLoadThe percentage of the breaker power capacity presently being used on this line, normally based on the ratio of breakerPhaseCurrent to the breakerRatedCurrent.ro
Integer32
.1.3.6.1.4.1.534.6.6.4.1.3.3.1.6
eatonPduConformance
OBJECT IDENTIFIER
.1.3.6.1.4.1.534.6.6.4.2
pduNameplateGroupThe pduNameplate subgroup objects.
Unknown
.1.3.6.1.4.1.534.6.6.4.2.1
pduInputGroupThe pduInput Meters subgroup objects.
Unknown
.1.3.6.1.4.1.534.6.6.4.2.2
pduOutputGroupThe pduOutput Meters subgroup objects.
Unknown
.1.3.6.1.4.1.534.6.6.4.2.3
panelRatingsGroupThe panelRatings table objects.
Unknown
.1.3.6.1.4.1.534.6.6.4.2.4
panelMetersGroupThe BreakerMeters Table objects.
Unknown
.1.3.6.1.4.1.534.6.6.4.2.5
panelPhaseMetersGroupThe BreakerPhaseMeters Table objects.
Unknown
.1.3.6.1.4.1.534.6.6.4.2.6
breakerRatingsGroupThe breakerRatings table objects.
Unknown
.1.3.6.1.4.1.534.6.6.4.2.7
breakerMetersGroupThe breakerMeters table objects.
Unknown
.1.3.6.1.4.1.534.6.6.4.2.8
breakerPhaseMetersGroupThe breakerPhaseMeters table objects.
Unknown
.1.3.6.1.4.1.534.6.6.4.2.9
pdu3phaseComplianceThe compliance statement for a normal 3-phase PDU, which implements the full set of objects.
Unknown
.1.3.6.1.4.1.534.6.6.4.2.10
EATON-PDU-MIB - SNMP MIB Reference | MIBs Explorer