XUPS-MIB
AI MIB Summary
Standard SNMP MIB module defining data structures for XUPS-MIB.
265
Objects
Active
Status
4
Dependencies
Imported Objects
Objects
265 total| Object Name |
|---|
powerware OBJECT IDENTIFIER .1.3.6.1.4.1.534 |
RFC1213-MIB Unknown .1.3.6.1.4.1.534 |
xups OBJECT IDENTIFIER .1.3.6.1.4.1.534.1 |
xupsNull OBJECT IDENTIFIER .1.3.6.1.4.1.534.1.0 |
xupsTrapBasic OBJECT IDENTIFIER .1.3.6.1.4.1.534.1.0.0 |
xupstbControlOffThe UPS output power will turn off in a number of
seconds equal to upsControlOutputOffTrapDelay. TRAP-TYPE .1.3.6.1.4.1.534.1.0.0.0.1 |
xupstbControlOnThe UPS output power will turn on in a number of
seconds equal to upsControlOutputOnTrapDelay. TRAP-TYPE .1.3.6.1.4.1.534.1.0.0.0.2 |
xupstbOnBatteryThe UPS has no AC input power and is running on
battery. TRAP-TYPE .1.3.6.1.4.1.534.1.0.0.0.3 |
xupstbLowBatteryThe UPS batteries are low. Tied to low battery
alarm condition. TRAP-TYPE .1.3.6.1.4.1.534.1.0.0.0.4 |
xupstbUtilityPowerRestoredInput power has been restored after running on battery. TRAP-TYPE .1.3.6.1.4.1.534.1.0.0.0.5 |
xupstbReturnFromLowBatteryThe battery has recovered from a low battery condition. TRAP-TYPE .1.3.6.1.4.1.534.1.0.0.0.6 |
xupstbOutputOverloadThe ups has sensed an overload of greater than
106 percent. Tied to the 106% overload alarm. TRAP-TYPE .1.3.6.1.4.1.534.1.0.0.0.7 |
xupstbInternalFailureSome component of the ups - rectifier, inverter,
control panel has failed. Tied to alarms indicating failure. TRAP-TYPE .1.3.6.1.4.1.534.1.0.0.0.8 |
xupstbBatteryDischargedThe Battery Totally Discharged Alarm has occurred. TRAP-TYPE .1.3.6.1.4.1.534.1.0.0.0.9 |
xupstbInverterFailureThe ups inverter is unavailable due to an internal failure. TRAP-TYPE .1.3.6.1.4.1.534.1.0.0.0.10 |
xupstbOnBypassThe ups has gone on bypass for some reason. TRAP-TYPE .1.3.6.1.4.1.534.1.0.0.0.11 |
xupstbBypassNotAvailableThe ups bypass is unavailable TRAP-TYPE .1.3.6.1.4.1.534.1.0.0.0.12 |
xupstbOutputOffThe ups output is switched off. TRAP-TYPE .1.3.6.1.4.1.534.1.0.0.0.13 |
xupstbInputFailureThe ups input power is incorrect in voltage,
frequency, or phase rotation. TRAP-TYPE .1.3.6.1.4.1.534.1.0.0.0.14 |
xupstbBuildingAlarmOne of the defined building alarms has occurred. TRAP-TYPE .1.3.6.1.4.1.534.1.0.0.0.15 |
xupstbShutdownImminentThe ups shutdown imminent alarm has occurred. TRAP-TYPE .1.3.6.1.4.1.534.1.0.0.0.16 |
xupstbOnInverterThe ups is returned to utility power running the inverter
after either a transfer to bypass or a run on battery. TRAP-TYPE .1.3.6.1.4.1.534.1.0.0.0.17 |
xupstbBreakerOpenOne of the UPS breakers or contactors has been opened. TRAP-TYPE .1.3.6.1.4.1.534.1.0.0.0.20 |
xupstbAlarmEntryAddedAn alarm not defined in the xups Well Known Alarms
(eg, an alarm defined in RFC1628)
has been added to the Alarm Table. TRAP-TYPE .1.3.6.1.4.1.534.1.0.0.0.21 |
xupstbAlarmEntryRemovedAn alarm not defined in the xups Well Known Alarms
has been removed from the Alarm Table. TRAP-TYPE .1.3.6.1.4.1.534.1.0.0.0.22 |
xupsIdent OBJECT IDENTIFIER .1.3.6.1.4.1.534.1.1 |
xupsIdentManufacturerThe UPS Manufacturer Name (e.g. Powerware Corporation).ro DisplayString .1.3.6.1.4.1.534.1.1.1 |
xupsIdentModelThe UPS Model (e.g. Powerware Plus Model 18).ro DisplayString .1.3.6.1.4.1.534.1.1.2 |
xupsIdentSoftwareVersionThe firmware revision level(s) of the UPS microcontroller(s).ro DisplayString .1.3.6.1.4.1.534.1.1.3 |
xupsIdentOemCodeA binary code indicating who the UPS was manufactured or labeled for.
0 or 255 indicates Powerware itself.ro INTEGER .1.3.6.1.4.1.534.1.1.4 |
xupsBattery OBJECT IDENTIFIER .1.3.6.1.4.1.534.1.2 |
xupsBatTimeRemainingBattery run time in seconds before UPS turns off due
to low battery.ro INTEGER .1.3.6.1.4.1.534.1.2.1 |
xupsBatVoltageBattery voltage as reported by the UPS meters.ro INTEGER .1.3.6.1.4.1.534.1.2.2 |
xupsBatCurrentBattery Current as reported by the UPS metering.
Current is positive when discharging, negative
when recharging the battery.ro INTEGER (-2147483648..2147483647) -- UNITS Amp DC .1.3.6.1.4.1.534.1.2.3 |
xupsBatCapacityBattery percent charge.ro INTEGER .1.3.6.1.4.1.534.1.2.4 |
xupsBatteryAbmStatusGives the status of the Advanced Battery Management;
batteryFloating(3) status means that the charger is temporarily
charging the battery to its float voltage; batteryResting(4) is the
state when the battery is fully charged and none of the other actions
(charging/discharging/floating) is being done.ro Enumeration .1.3.6.1.4.1.534.1.2.5 |
xupsInput OBJECT IDENTIFIER .1.3.6.1.4.1.534.1.3 |
xupsInputFrequencyThe utility line frequency in tenths of Hz.ro INTEGER .1.3.6.1.4.1.534.1.3.1 |
xupsInputLineBadsThe number of times the Input was out of tolerance
in voltage or frequency.ro Counter .1.3.6.1.4.1.534.1.3.2 |
xupsInputNumPhasesro INTEGER .1.3.6.1.4.1.534.1.3.3 |
xupsInputTableThe Aggregate Object with number of entries equal to
NumPhases and including the xupsInput group. SEQUENCE OF XupsInputEntry .1.3.6.1.4.1.534.1.3.4 |
xupsInputEntryThe input table entry containing the current,
voltage, etc. XupsInputEntry .1.3.6.1.4.1.534.1.3.4.1 |
xupsInputPhaseThe number of the phase. Serves as index for input table.ro INTEGER .1.3.6.1.4.1.534.1.3.4.1.1 |
xupsInputVoltageThe measured input voltage from the UPS meters in volts.ro INTEGER .1.3.6.1.4.1.534.1.3.4.1.2 |
xupsInputCurrentThe measured input current from the UPS meters in amps.ro INTEGER .1.3.6.1.4.1.534.1.3.4.1.3 |
xupsInputWattsThe measured input real power in watts.ro INTEGER .1.3.6.1.4.1.534.1.3.4.1.4 |
xupsInputSourceThe present external source of input power. The enumeration
none(2) indicates that there is no external source of
power, for example, the UPS is On Battery (an internal source).
The bypassFeed(4) can only be used when the Bypass source is known
to be a separate utility feed than the primaryUtility(3).ro Enumeration .1.3.6.1.4.1.534.1.3.5 |
xupsOutput OBJECT IDENTIFIER .1.3.6.1.4.1.534.1.4 |
xupsOutputLoadThe UPS output load in percent of rated capacity.ro INTEGER .1.3.6.1.4.1.534.1.4.1 |
xupsOutputFrequencyThe measured UPS output frequency in tenths of Hz.ro INTEGER .1.3.6.1.4.1.534.1.4.2 |
xupsOutputNumPhasesThe number of metered output phases, serves as the table
index.ro INTEGER .1.3.6.1.4.1.534.1.4.3 |
xupsOutputTableThe Aggregate Object with number of entries equal to NumPhases
and including the xupsOutput group. SEQUENCE OF XupsOutputEntry .1.3.6.1.4.1.534.1.4.4 |
xupsOutputEntryOutput Table Entry containing voltage, current, etc. XupsOutputEntry .1.3.6.1.4.1.534.1.4.4.1 |
xupsOutputPhaseThe number {1..3} of the output phase.ro INTEGER .1.3.6.1.4.1.534.1.4.4.1.1 |
xupsOutputVoltageThe measured output voltage from the UPS metering in volts.ro INTEGER .1.3.6.1.4.1.534.1.4.4.1.2 |
xupsOutputCurrentThe measured UPS output current in amps.ro INTEGER .1.3.6.1.4.1.534.1.4.4.1.3 |
xupsOutputWattsThe measured real output power in watts.ro INTEGER .1.3.6.1.4.1.534.1.4.4.1.4 |
xupsOutputSourceThe present source of output power. The enumeration
none(2) indicates that there is no source of output
power (and therefore no output power), for example,
the system has opened the output breaker.ro Enumeration .1.3.6.1.4.1.534.1.4.5 |
xupsBypass OBJECT IDENTIFIER .1.3.6.1.4.1.534.1.5 |
xupsBypassFrequencyThe bypass frequency in tenths of Hz.ro INTEGER .1.3.6.1.4.1.534.1.5.1 |
xupsBypassNumPhasesThe number of lines in the UPS bypass table.ro INTEGER .1.3.6.1.4.1.534.1.5.2 |
xupsBypassTable SEQUENCE OF XupsBypassEntry .1.3.6.1.4.1.534.1.5.3 |
xupsBypassEntryEntry in the XUPS bypass table. XupsBypassEntry .1.3.6.1.4.1.534.1.5.3.1 |
xupsBypassPhaseThe Bypass Phase, index for the table.ro INTEGER .1.3.6.1.4.1.534.1.5.3.1.1 |
xupsBypassVoltageThe measured UPS bypass voltage in volts.ro INTEGER .1.3.6.1.4.1.534.1.5.3.1.2 |
xupsEnvironment OBJECT IDENTIFIER .1.3.6.1.4.1.534.1.6 |
xupsEnvAmbientTempThe reading of the ambient temperature in the vicinity of the
UPS or SNMP agent.ro INTEGER (-100..200) -- UNITS Degrees Centigrade .1.3.6.1.4.1.534.1.6.1 |
xupsEnvAmbientLowerLimitThe Lower Limit of the ambient temperature; if xupsEnvAmbientTemp
falls below this value, the xupsAmbientTempBad alarm will occur.rw INTEGER (-100..200) -- UNITS Degrees Centigrade .1.3.6.1.4.1.534.1.6.2 |
xupsEnvAmbientUpperLimitThe Upper Limit of the ambient temperature; if xupsEnvAmbientTemp
rises above this value, the xupsAmbientTempBad alarm will occur.
This value should be greater than xupsEnvAmbientLowerLimit.rw INTEGER (-100..200) -- UNITS Degrees Centigrade .1.3.6.1.4.1.534.1.6.3 |
xupsEnvAmbientHumidityThe reading of the ambient humidity in the vicinity of the
UPS or SNMP agent.ro INTEGER .1.3.6.1.4.1.534.1.6.4 |
xupsEnvRemoteTempThe reading of a remote temperature sensor connected to the
UPS or SNMP agent.ro INTEGER (-100..200) -- UNITS Degrees Centigrade .1.3.6.1.4.1.534.1.6.5 |
xupsEnvRemoteHumidityThe reading of a remote humidity sensor connected to the
UPS or SNMP agent.ro INTEGER .1.3.6.1.4.1.534.1.6.6 |
xupsEnvNumContactsThe number of Contacts in the xupsContactSenseTable.
This object indicates the number of rows in the
xupsContactSenseTable.ro INTEGER .1.3.6.1.4.1.534.1.6.7 |
xupsContactSenseTableA list of Contact Sensing table entries.
The number of entries is given by the value of
xupsEnvNumContacts. SEQUENCE OF XupsContactsTableEntry .1.3.6.1.4.1.534.1.6.8 |
xupsContactsTableEntryAn entry containing information applicable
to a particular Contact input. XupsContactsTableEntry .1.3.6.1.4.1.534.1.6.8.1 |
xupsContactIndexThe Contact identifier; identical to the Contact Number. INTEGER .1.3.6.1.4.1.534.1.6.8.1.1 |
xupsContactTypeThe normal state for this contact. The 'other'
state is the Active state for generating the xupstdContactActiveNotice
trap. If anyChange(3) is selected, then this trap is sent
any time the contact changes to either Open or Closed.
No traps are sent if the Contact is set to notUsed(4).
In many cases, the configuration for Contacts may be done by other
means, so this object may be read-only.rw Enumeration .1.3.6.1.4.1.534.1.6.8.1.2 |
xupsContactStateThe current state of the Contact input;
the value is based on the open/closed input state
and the setting for xupsContactType.
When entering the openWithNotice(3) and closedWithNotice(4)
states, no entries added to the xupsAlarmTable, but
the xupstdContactActiveNotice trap is sent.ro Enumeration .1.3.6.1.4.1.534.1.6.8.1.3 |
xupsContactDescrA label identifying the Contact. This object should be
set by the administrator.rw DisplayString .1.3.6.1.4.1.534.1.6.8.1.4 |
xupsEnvRemoteTempLowerLimitThe Lower Limit of the remote temperature; if xupsEnvRemoteTemp
falls below this value, the xupsRemoteTempBad alarm will occur.rw INTEGER (-100..200) -- UNITS Degrees Centigrade .1.3.6.1.4.1.534.1.6.9 |
xupsEnvRemoteTempUpperLimitThe Upper Limit of the remote temperature; if xupsEnvRemoteTemp
rises above this value, the xupsRemoteTempBad alarm will occur.
This value should be greater than xupsEnvRemoteTempLowerLimit.rw INTEGER (-100..200) -- UNITS Degrees Centigrade .1.3.6.1.4.1.534.1.6.10 |
xupsEnvRemoteHumidityLowerLimitThe Lower Limit of the remote humidity reading; if xupsEnvRemoteHumidity
falls below this value, the xupsRemoteHumidityBad alarm will occur.rw INTEGER .1.3.6.1.4.1.534.1.6.11 |
xupsEnvRemoteHumidityUpperLimitThe Upper Limit of the remote humidity reading; if xupsEnvRemoteHumidity
rises above this value, the xupsRemoteHumidityBad alarm will occur.
This value should be greater than xupsEnvRemoteHumidityLowerLimit.rw INTEGER .1.3.6.1.4.1.534.1.6.12 |
xupsAlarm OBJECT IDENTIFIER .1.3.6.1.4.1.534.1.7 |
xupsAlarmsThe current number of alarm conditions.ro Gauge .1.3.6.1.4.1.534.1.7.1 |
xupsAlarmTable SEQUENCE OF XupsAlarmEntry .1.3.6.1.4.1.534.1.7.2 |
xupsAlarmEntry XupsAlarmEntry .1.3.6.1.4.1.534.1.7.2.1 |
xupsAlarmIDA unique identifier for an alarm condition.ro INTEGER .1.3.6.1.4.1.534.1.7.2.1.1 |
xupsAlarmDescrA reference to an alarm description object. The object
referenced should not be accessible, but rather be used to
provide a unique description of the alarm condition.ro OBJECT IDENTIFIER .1.3.6.1.4.1.534.1.7.2.1.2 |
xupsAlarmTimeThe value of the MIB-II variable sysUpTime when the alarm
condition occurred.ro TimeTicks (SNMPv2-SMI) .1.3.6.1.4.1.534.1.7.2.1.3 |
xupsOnBattery OBJECT IDENTIFIER .1.3.6.1.4.1.534.1.7.3 |
xupsLowBattery OBJECT IDENTIFIER .1.3.6.1.4.1.534.1.7.4 |
xupsUtilityPowerRestored OBJECT IDENTIFIER .1.3.6.1.4.1.534.1.7.5 |
xupsReturnFromLowBattery OBJECT IDENTIFIER .1.3.6.1.4.1.534.1.7.6 |
xupsOutputOverload OBJECT IDENTIFIER .1.3.6.1.4.1.534.1.7.7 |
xupsInternalFailure OBJECT IDENTIFIER .1.3.6.1.4.1.534.1.7.8 |
xupsBatteryDischarged OBJECT IDENTIFIER .1.3.6.1.4.1.534.1.7.9 |
xupsInverterFailure OBJECT IDENTIFIER .1.3.6.1.4.1.534.1.7.10 |
xupsOnBypass OBJECT IDENTIFIER .1.3.6.1.4.1.534.1.7.11 |
xupsBypassNotAvailable OBJECT IDENTIFIER .1.3.6.1.4.1.534.1.7.12 |
xupsOutputOff OBJECT IDENTIFIER .1.3.6.1.4.1.534.1.7.13 |
xupsInputFailure OBJECT IDENTIFIER .1.3.6.1.4.1.534.1.7.14 |
xupsBuildingAlarm OBJECT IDENTIFIER .1.3.6.1.4.1.534.1.7.15 |
xupsShutdownImminent OBJECT IDENTIFIER .1.3.6.1.4.1.534.1.7.16 |
xupsOnInverter OBJECT IDENTIFIER .1.3.6.1.4.1.534.1.7.17 |
xupsAlarmNumEventsThe number of entries in the UPS event history queue.ro Gauge .1.3.6.1.4.1.534.1.7.18 |
xupsAlarmEventTableA table of the UPS internal event history queue. SEQUENCE OF XupsAlarmEventEntry .1.3.6.1.4.1.534.1.7.19 |
xupsAlarmEventEntryOne of the entries in the UPS event history queue. XupsAlarmEventEntry .1.3.6.1.4.1.534.1.7.19.1 |
xupsAlarmEventIDA unique number that reflects the order in which the event
occurred. The oldest event in the queue will be number 1.
Subsequent events will be numbered 2, 3, 4, etc.rodeprecated INTEGER .1.3.6.1.4.1.534.1.7.19.1.1 |
xupsAlarmEventDateAndTimeThe time and date that an event occurred as recorded in the UPS
internal event queue. This string will reflect the time and
date as set in the UPS itself and will not be referenced to
sysUpTime. The format is MM/DD/YYYY:HH:MM:SS. Time is 24 hour standard.rodeprecated DisplayString .1.3.6.1.4.1.534.1.7.19.1.2 |
xupsAlarmEventKindEnumerated value that tells whether the event is an
occurrence of an alarm condition or a clearing of an
alarm condition.rodeprecated Enumeration .1.3.6.1.4.1.534.1.7.19.1.3 |
xupsAlarmEventDescrA description of the event stored in the UPS event queue.
This description will be a sixteen bit integer value
representing one of the defined alarms in the Powerware Binary
Computer Mode communication specification; for example,
a value of 0 represents the 'Inverter AC Over Voltage'
alarm (byte 1, bit 0 in the BCM Alarm Map).rodeprecated INTEGER .1.3.6.1.4.1.534.1.7.19.1.4 |
xupsAlarmEventMsgA text string describing each entry in the Event Log. The format of this
text message is free (not fixed) for the operator to read; good contents
would be a time & date stamp, the event type, and a description of the event.ro DisplayString .1.3.6.1.4.1.534.1.7.19.1.5 |
xupsBreakerOpen OBJECT IDENTIFIER .1.3.6.1.4.1.534.1.7.20 |
xupsAlarmEntryAdded OBJECT IDENTIFIER .1.3.6.1.4.1.534.1.7.21 |
xupsAlarmEntryRemoved OBJECT IDENTIFIER .1.3.6.1.4.1.534.1.7.22 |
xupsAlarmBatteryBad OBJECT IDENTIFIER .1.3.6.1.4.1.534.1.7.23 |
xupsOutputOffAsRequested OBJECT IDENTIFIER .1.3.6.1.4.1.534.1.7.24 |
xupsDiagnosticTestFailed OBJECT IDENTIFIER .1.3.6.1.4.1.534.1.7.25 |
xupsCommunicationsLost OBJECT IDENTIFIER .1.3.6.1.4.1.534.1.7.26 |
xupsUpsShutdownPending OBJECT IDENTIFIER .1.3.6.1.4.1.534.1.7.27 |
xupsAlarmTestInProgress OBJECT IDENTIFIER .1.3.6.1.4.1.534.1.7.28 |
xupsAmbientTempBad OBJECT IDENTIFIER .1.3.6.1.4.1.534.1.7.29 |
xupsLossOfRedundancy OBJECT IDENTIFIER .1.3.6.1.4.1.534.1.7.30 |
xupsAlarmTempBad OBJECT IDENTIFIER .1.3.6.1.4.1.534.1.7.31 |
xupsAlarmChargerFailed OBJECT IDENTIFIER .1.3.6.1.4.1.534.1.7.32 |
xupsAlarmFanFailure OBJECT IDENTIFIER .1.3.6.1.4.1.534.1.7.33 |
xupsAlarmFuseFailure OBJECT IDENTIFIER .1.3.6.1.4.1.534.1.7.34 |
xupsPowerSwitchBad OBJECT IDENTIFIER .1.3.6.1.4.1.534.1.7.35 |
xupsModuleFailure OBJECT IDENTIFIER .1.3.6.1.4.1.534.1.7.36 |
xupsOnAlternatePowerSource OBJECT IDENTIFIER .1.3.6.1.4.1.534.1.7.37 |
xupsAltPowerNotAvailable OBJECT IDENTIFIER .1.3.6.1.4.1.534.1.7.38 |
xupsNoticeCondition OBJECT IDENTIFIER .1.3.6.1.4.1.534.1.7.39 |
xupsRemoteTempBad OBJECT IDENTIFIER .1.3.6.1.4.1.534.1.7.40 |
xupsRemoteHumidityBad OBJECT IDENTIFIER .1.3.6.1.4.1.534.1.7.41 |
xupsTest OBJECT IDENTIFIER .1.3.6.1.4.1.534.1.8 |
xupsTestBatterySetting this variable to startTest initiates the
battery test. All other set values are invalid.rw Enumeration .1.3.6.1.4.1.534.1.8.1 |
xupsTestBatteryStatusReading this enumerated value gives an indication of the
UPS Battery test status.ro Enumeration .1.3.6.1.4.1.534.1.8.2 |
xupsControl OBJECT IDENTIFIER .1.3.6.1.4.1.534.1.9 |
xupsControlOutputOffDelaySetting this value to other than zero will cause the UPS
output to turn off after the number of seconds.
Setting it to 0 will cause an attempt to abort a pending
shutdown.rw INTEGER .1.3.6.1.4.1.534.1.9.1 |
xupsControlOutputOnDelaySetting this value to other than zero will cause the UPS
output to turn on after the number of seconds.
Setting it to 0 will cause an attempt to abort a pending
startup.rw INTEGER .1.3.6.1.4.1.534.1.9.2 |
xupsControlOutputOffTrapDelayWhen xupsControlOutputOffDelay reaches this value, a trap will
be sent.rw INTEGER .1.3.6.1.4.1.534.1.9.3 |
xupsControlOutputOnTrapDelayWhen xupsControlOutputOnDelay reaches this value, a
xupsOutputOff trap will be sent.rwdeprecated INTEGER .1.3.6.1.4.1.534.1.9.4 |
xupsControlToBypassDelaySetting this value to other than zero will cause the UPS
output to go to Bypass after the number of seconds.
If the Bypass is unavailable, this may cause the UPS
to not supply power to the load.
Setting it to 0 will cause an attempt to abort a pending
shutdown.rw INTEGER .1.3.6.1.4.1.534.1.9.5 |
xupsLoadShedSecsWithRestartSetting this value will cause the UPS output to turn off
after the set number of seconds, then restart (after a UPS-defined
'down time') when the utility is again available.
Unlike xupsControlOutputOffDelay, which might or might not,
this object always maps to the XCP 0x8A Load Dump & Restart command,
so the desired shutdown and restart behavior is guaranteed to happen.
Once set, this command cannot be aborted.
This is the preferred Control object to use when performing an On
Battery OS Shutdown.rw INTEGER .1.3.6.1.4.1.534.1.9.6 |
xupsConfig OBJECT IDENTIFIER .1.3.6.1.4.1.534.1.10 |
xupsConfigOutputVoltageThe nominal UPS Output voltage per phase in volts.ro INTEGER .1.3.6.1.4.1.534.1.10.1 |
xupsConfigInputVoltageThe nominal UPS Input voltage per phase in volts.ro INTEGER .1.3.6.1.4.1.534.1.10.2 |
xupsConfigOutputWattsThe nominal UPS available real power output in watts.ro INTEGER .1.3.6.1.4.1.534.1.10.3 |
xupsConfigOutputFreqThe nominal output frequency in tenths of Hz.ro INTEGER .1.3.6.1.4.1.534.1.10.4 |
xupsConfigDateAndTimeDate and time information for the UPS. Setting this variable
will initiate a set UPS date and time to this value. Reading
this variable will return the UPS time and date. This value
is not referenced to sysUpTime. It is simply the clock value
from the UPS real time clock.
Format is as follows: MM/DD/YYYY:HH:MM:SS.rw DisplayString .1.3.6.1.4.1.534.1.10.5 |
xupsConfigLowOutputVoltageLimitThe Lower limit for acceptable Output Voltage, per the UPS
specifications.ro INTEGER .1.3.6.1.4.1.534.1.10.6 |
xupsConfigHighOutputVoltageLimitThe Upper limit for acceptable Output Voltage, per the UPS
specifications.ro INTEGER .1.3.6.1.4.1.534.1.10.7 |
xupsTrapControl OBJECT IDENTIFIER .1.3.6.1.4.1.534.1.11 |
xupsMaxTrapLevelThe level of severity of traps which will be sent to the
requesting host; individual trap receivers will have
individual values for this variable. Values are:
(1) none: no traps will be sent to this host;
(2) critical: only traps for Critical alarm conditions will
be sent to this host;
(3) major: Critical and Major traps will be sent;
(4) allTraps: all Traps will be sent to this host
(Critical, Major, Minor, Informational).rw Enumeration .1.3.6.1.4.1.534.1.11.1 |
xupsSendTrapTypeThe type of traps which will be sent to the
requesting host; individual trap receivers will have
individual values for this variable. The additional
variables in types (3) and (4) are useful for determining
which UPS is the source on multi-port network adapters,
and for getting additional descriptive information.
Types (1) through (4) are all SNMP version 1 trap PDUs.
Values are:
(1) stnd: Traps as defined in the Standard UPS MIB (RFC1628)
and Generic (MIB II) traps as defined in RFC 1215.
(2) xups: xupsTrapDefined Traps as defined in the PowerMIB
and Generic (MIB II) traps as defined in RFC 1215.
(3) stndPlus: same as stnd plus variables from the interface
group and, where appropriate, xupsTrapMessage.
(4) xupsPlus: xupsTrapPortN Traps (same as xups plus
variables from the interface group) and,
for authFail, xupsTrapMessage.rw Enumeration .1.3.6.1.4.1.534.1.11.2 |
xupsTrapMessageA descriptive message which may be sent with traps to
further explain the reason for the trap. DisplayString .1.3.6.1.4.1.534.1.11.3 |
xupsTrapSource OBJECT IDENTIFIER .1.3.6.1.4.1.534.1.11.4 |
xupsTrapDefined OBJECT IDENTIFIER .1.3.6.1.4.1.534.1.11.4.1 |
xupstdControlOffThe UPS output power will turn off in a number of
seconds equal to upsControlOutputOffTrapDelay. TRAP-TYPE .1.3.6.1.4.1.534.1.11.4.1.0.1 |
xupstdControlOnThe UPS output power will turn on in a number of
seconds equal to upsControlOutputOnTrapDelay. TRAP-TYPE .1.3.6.1.4.1.534.1.11.4.1.0.2 |
xupstdOnBatteryThe UPS has no AC input power and is running on
battery. TRAP-TYPE .1.3.6.1.4.1.534.1.11.4.1.0.3 |
xupstdLowBatteryThe UPS batteries are low. Tied to low battery
alarm condition. TRAP-TYPE .1.3.6.1.4.1.534.1.11.4.1.0.4 |
xupstdUtilityPowerRestoredInput power has been restored after running on battery. TRAP-TYPE .1.3.6.1.4.1.534.1.11.4.1.0.5 |
xupstdReturnFromLowBatteryThe battery has recovered from a low battery condition. TRAP-TYPE .1.3.6.1.4.1.534.1.11.4.1.0.6 |
xupstdOutputOverloadThe ups has sensed an overload of greater than
106 percent. Tied to the 106% overload alarm. TRAP-TYPE .1.3.6.1.4.1.534.1.11.4.1.0.7 |
xupstdInternalFailureSome component of the ups - rectifier, inverter,
control panel has failed. Tied to alarms indi-
cating failure. TRAP-TYPE .1.3.6.1.4.1.534.1.11.4.1.0.8 |
xupstdBatteryDischargedThe Battery Totally Discharged Alarm has occurred. TRAP-TYPE .1.3.6.1.4.1.534.1.11.4.1.0.9 |
xupstdInverterFailureThe ups inverter is unavailable due to an internal failure. TRAP-TYPE .1.3.6.1.4.1.534.1.11.4.1.0.10 |
xupstdOnBypassThe ups has gone on bypass for some reason. TRAP-TYPE .1.3.6.1.4.1.534.1.11.4.1.0.11 |
xupstdBypassNotAvailableThe ups bypass is unavailable TRAP-TYPE .1.3.6.1.4.1.534.1.11.4.1.0.12 |
xupstdOutputOffThe ups output is switched off. TRAP-TYPE .1.3.6.1.4.1.534.1.11.4.1.0.13 |
xupstdInputFailureThe ups input power is incorrect in voltage,
frequency, or phase rotation. TRAP-TYPE .1.3.6.1.4.1.534.1.11.4.1.0.14 |
xupstdBuildingAlarmOne of the defined building alarms has occurred. TRAP-TYPE .1.3.6.1.4.1.534.1.11.4.1.0.15 |
xupstdShutdownImminentThe ups shutdown imminent alarm has occurred. TRAP-TYPE .1.3.6.1.4.1.534.1.11.4.1.0.16 |
xupstdOnInverterThe ups is returned to utility power running the inverter
after either a transfer to bypass or a run on battery. TRAP-TYPE .1.3.6.1.4.1.534.1.11.4.1.0.17 |
xupstdBreakerOpenOne of the UPS breakers or contactors has been opened. TRAP-TYPE .1.3.6.1.4.1.534.1.11.4.1.0.20 |
xupstdAlarmEntryAddedAn alarm not defined in the xups Well Known Alarms
(eg, an alarm defined in RFC1628)
has been added to the Alarm Table. TRAP-TYPE .1.3.6.1.4.1.534.1.11.4.1.0.21 |
xupstdAlarmEntryRemovedAn alarm not defined in the xups Well Known Alarms
has been removed from the Alarm Table. TRAP-TYPE .1.3.6.1.4.1.534.1.11.4.1.0.22 |
xupstdAlarmBatteryBadOne or more batteries have been determined to require replacement. TRAP-TYPE .1.3.6.1.4.1.534.1.11.4.1.0.23 |
xupstdOutputOffAsRequestedThe UPS has shutdown as requested, i.e., the output is off. TRAP-TYPE .1.3.6.1.4.1.534.1.11.4.1.0.24 |
xupstdDiagnosticTestFailedThe result of the last diagnostic test indicates a failure. TRAP-TYPE .1.3.6.1.4.1.534.1.11.4.1.0.25 |
xupstdCommunicationsLostA problem has been encountered in the communications
between the agent and the UPS. TRAP-TYPE .1.3.6.1.4.1.534.1.11.4.1.0.26 |
xupstdUpsShutdownPendingAn xupsControlOutputOffDelay countdown is underway. TRAP-TYPE .1.3.6.1.4.1.534.1.11.4.1.0.27 |
xupstdAlarmTestInProgressA test is in progress, as initiated and indicated by the
Battery Test Group. TRAP-TYPE .1.3.6.1.4.1.534.1.11.4.1.0.28 |
xupstdAmbientTempBadThe ambient temperature, xupsEnvAmbientTemp, has fallen below
the set lower limit, xupsEnvAmbientLowerLimit, or has risen above
the set upper limit, xupsEnvAmbientUpperLimit. TRAP-TYPE .1.3.6.1.4.1.534.1.11.4.1.0.29 |
xupstdContactActiveNoticeThe Contact indicated by xupsContactIndex is in its Active state.
The following are the situations that generate this trap:
For xupsContactType: and xupsContactState:
normallyOpen(1) and closedWithNotice(4)
normallyClosed(2) and openWithNotice(3)
anyChange(3) and openWithNotice(3) or closedWithNotice(4) TRAP-TYPE .1.3.6.1.4.1.534.1.11.4.1.0.30 |
xupstdContactInactiveNoticeThe Contact indicated by xupsContactIndex has changed to its Inactive state. TRAP-TYPE .1.3.6.1.4.1.534.1.11.4.1.0.31 |
xupstdLossOfRedundancyA parallel UPS system is no longer operating in N+1 redundant mode;
this may be due to module failure or removal, or due to overloading. TRAP-TYPE .1.3.6.1.4.1.534.1.11.4.1.0.32 |
xupstdAlarmTempBadAn internal temperature is out of tolerance. TRAP-TYPE .1.3.6.1.4.1.534.1.11.4.1.0.33 |
xupstdAlarmChargerFailedAn uncorrected problem has been detected within the UPS charger subsystem. TRAP-TYPE .1.3.6.1.4.1.534.1.11.4.1.0.34 |
xupstdAlarmFanFailureThe failure of one or more fans in the UPS has been detected. TRAP-TYPE .1.3.6.1.4.1.534.1.11.4.1.0.35 |
xupstdAlarmFuseFailureThe failure of one or more fuses has been detected. TRAP-TYPE .1.3.6.1.4.1.534.1.11.4.1.0.36 |
xupstdPowerSwitchBadA Relay, Contactor, or Breaker has failed. TRAP-TYPE .1.3.6.1.4.1.534.1.11.4.1.0.37 |
xupstdModuleFailureOne module in a parallel or composite system has failed. TRAP-TYPE .1.3.6.1.4.1.534.1.11.4.1.0.38 |
xupstdOnAlternatePowerSourceThe system is being powered by its Alternate Power Source, such as a
Secondary utility feed (on a dual AC input UPS), generator, flywheel,
or fuelcell. TRAP-TYPE .1.3.6.1.4.1.534.1.11.4.1.0.39 |
xupstdAltPowerNotAvailableOn systems with a separate alternate power source (eg, dual AC inputs),
that alternate power source is currently not available. This could be
a problem if the primary power source (eg, utility) fails for a period
of time longer than that for which the internal batteries can supply power. TRAP-TYPE .1.3.6.1.4.1.534.1.11.4.1.0.40 |
xupstdNoticeConditionSome Notice condition exists which is not covered by the other traps.
This is like an xupstdInternalFailure, but at a lower severity level. TRAP-TYPE .1.3.6.1.4.1.534.1.11.4.1.0.41 |
xupstdRemoteTempBadThe remote temperature, xupsEnvRemoteTemp, has fallen below
the set lower limit, xupsEnvRemoteTempLowerLimit, or has risen above
the set upper limit, xupsEnvRemoteTempUpperLimit. TRAP-TYPE .1.3.6.1.4.1.534.1.11.4.1.0.42 |
xupstdRemoteHumidityBadThe remote temperature, xupsEnvRemoteHumidity, has fallen below
the set lower limit, xupsEnvRemoteHumidityLowerLimit, or has risen above
the set upper limit, xupsEnvRemoteHumidityUpperLimit. TRAP-TYPE .1.3.6.1.4.1.534.1.11.4.1.0.43 |
xupsTrapPortN OBJECT IDENTIFIER .1.3.6.1.4.1.534.1.11.4.2 |
xupstpControlOffThe UPS output power will turn off in a number of
seconds equal to upsControlOutputOffTrapDelay. TRAP-TYPE .1.3.6.1.4.1.534.1.11.4.2.0.1 |
xupstpControlOnThe UPS output power will turn on in a number of
seconds equal to upsControlOutputOnTrapDelay. TRAP-TYPE .1.3.6.1.4.1.534.1.11.4.2.0.2 |
xupstpOnBatteryThe UPS has no AC input power and is running on
battery. TRAP-TYPE .1.3.6.1.4.1.534.1.11.4.2.0.3 |
xupstpLowBatteryThe UPS batteries are low. Tied to low battery
alarm condition. TRAP-TYPE .1.3.6.1.4.1.534.1.11.4.2.0.4 |
xupstpUtilityPowerRestoredInput power has been restored after running on battery. TRAP-TYPE .1.3.6.1.4.1.534.1.11.4.2.0.5 |
xupstpReturnFromLowBatteryThe battery has recovered from a low battery condition. TRAP-TYPE .1.3.6.1.4.1.534.1.11.4.2.0.6 |
xupstpOutputOverloadThe ups has sensed an overload of greater than
106 percent. Tied to the 106% overload alarm. TRAP-TYPE .1.3.6.1.4.1.534.1.11.4.2.0.7 |
xupstpInternalFailureSome component of the ups - rectifier, inverter,
control panel has failed. Tied to alarms indi-
cating failure. TRAP-TYPE .1.3.6.1.4.1.534.1.11.4.2.0.8 |
xupstpBatteryDischargedThe Battery Totally Discharged Alarm has occurred. TRAP-TYPE .1.3.6.1.4.1.534.1.11.4.2.0.9 |
xupstpInverterFailureThe ups inverter is unavailable due to an internal failure. TRAP-TYPE .1.3.6.1.4.1.534.1.11.4.2.0.10 |
xupstpOnBypassThe ups has gone on bypass for some reason. TRAP-TYPE .1.3.6.1.4.1.534.1.11.4.2.0.11 |
xupstpBypassNotAvailableThe ups bypass is unavailable TRAP-TYPE .1.3.6.1.4.1.534.1.11.4.2.0.12 |
xupstpOutputOffThe ups output is switched off. TRAP-TYPE .1.3.6.1.4.1.534.1.11.4.2.0.13 |
xupstpInputFailureThe ups input power is incorrect in voltage,
frequency, or phase rotation. TRAP-TYPE .1.3.6.1.4.1.534.1.11.4.2.0.14 |
xupstpBuildingAlarmOne of the defined building alarms has occurred. TRAP-TYPE .1.3.6.1.4.1.534.1.11.4.2.0.15 |
xupstpShutdownImminentThe ups shutdown imminent alarm has occurred. TRAP-TYPE .1.3.6.1.4.1.534.1.11.4.2.0.16 |
xupstpOnInverterThe ups is returned to utility power running the inverter
after either a transfer to bypass or a run on battery. TRAP-TYPE .1.3.6.1.4.1.534.1.11.4.2.0.17 |
xupstpBreakerOpenOne of the UPS breakers or contactors has been opened. TRAP-TYPE .1.3.6.1.4.1.534.1.11.4.2.0.20 |
xupstpAlarmEntryAddedAn alarm not defined in the xups Well Known Alarms
(eg, an alarm defined in RFC1628)
has been added to the Alarm Table. TRAP-TYPE .1.3.6.1.4.1.534.1.11.4.2.0.21 |
xupstpAlarmEntryRemovedAn alarm not defined in the xups Well Known Alarms
has been removed from the Alarm Table. TRAP-TYPE .1.3.6.1.4.1.534.1.11.4.2.0.22 |
xupstpAlarmBatteryBadOne or more batteries have been determined to require replacement. TRAP-TYPE .1.3.6.1.4.1.534.1.11.4.2.0.23 |
xupstpOutputOffAsRequestedThe UPS has shutdown as requested, i.e., the output is off. TRAP-TYPE .1.3.6.1.4.1.534.1.11.4.2.0.24 |
xupstpDiagnosticTestFailedThe result of the last diagnostic test indicates a failure. TRAP-TYPE .1.3.6.1.4.1.534.1.11.4.2.0.25 |
xupstpCommunicationsLostA problem has been encountered in the communications
between the agent and the UPS. TRAP-TYPE .1.3.6.1.4.1.534.1.11.4.2.0.26 |
xupstpUpsShutdownPendingAn xupsControlOutputOffDelay countdown is underway. TRAP-TYPE .1.3.6.1.4.1.534.1.11.4.2.0.27 |
xupstpAlarmTestInProgressA test is in progress, as initiated and indicated by the
Battery Test Group. TRAP-TYPE .1.3.6.1.4.1.534.1.11.4.2.0.28 |
xupstpAmbientTempBadThe ambient temperature, xupsEnvAmbientTemp, has fallen below
the set lower limit, xupsEnvAmbientLowerLimit, or has risen above
the set upper limit, xupsEnvAmbientUpperLimit. TRAP-TYPE .1.3.6.1.4.1.534.1.11.4.2.0.29 |
xupstpLossOfRedundancyA parallel UPS system is no longer operating in N+1 redundant mode;
this may be due to module failure or removal, or due to overloading. TRAP-TYPE .1.3.6.1.4.1.534.1.11.4.2.0.32 |
xupstpAlarmTempBadAn internal temperature is out of tolerance. TRAP-TYPE .1.3.6.1.4.1.534.1.11.4.2.0.33 |
xupstpAlarmChargerFailedAn uncorrected problem has been detected within the UPS charger subsystem. TRAP-TYPE .1.3.6.1.4.1.534.1.11.4.2.0.34 |
xupstpAlarmFanFailureThe failure of one or more fans in the UPS has been detected. TRAP-TYPE .1.3.6.1.4.1.534.1.11.4.2.0.35 |
xupstpAlarmFuseFailureThe failure of one or more fuses has been detected. TRAP-TYPE .1.3.6.1.4.1.534.1.11.4.2.0.36 |
xupstpPowerSwitchBadA Relay, Contactor, or Breaker has failed. TRAP-TYPE .1.3.6.1.4.1.534.1.11.4.2.0.37 |
xupstpModuleFailureOne module in a parallel or composite system has failed. TRAP-TYPE .1.3.6.1.4.1.534.1.11.4.2.0.38 |
xupstpOnAlternatePowerSourceThe system is being powered by its Alternate Power Source, such as a
Secondary utility feed (on a dual AC input UPS), generator, flywheel,
or fuelcell. TRAP-TYPE .1.3.6.1.4.1.534.1.11.4.2.0.39 |
xupstpAltPowerNotAvailableOn systems with a separate alternate power source (eg, dual AC inputs),
that alternate power source is currently not available. This could be
a problem if the primary power source (eg, utility) fails for a period
of time longer than that for which the internal batteries can supply power. TRAP-TYPE .1.3.6.1.4.1.534.1.11.4.2.0.40 |
xupstpNoticeConditionSome Notice condition exists which is not covered by the other traps.
This is like an xupstpInternalFailure, but at a lower severity level. TRAP-TYPE .1.3.6.1.4.1.534.1.11.4.2.0.41 |
xupstpRemoteTempBadThe remote temperature, xupsEnvRemoteTemp, has fallen below
the set lower limit, xupsEnvRemoteTempLowerLimit, or has risen above
the set upper limit, xupsEnvRemoteTempUpperLimit. TRAP-TYPE .1.3.6.1.4.1.534.1.11.4.2.0.42 |
xupstpRemoteHumidityBadThe remote temperature, xupsEnvRemoteHumidity, has fallen below
the set lower limit, xupsEnvRemoteHumidityLowerLimit, or has risen above
the set upper limit, xupsEnvRemoteHumidityUpperLimit. TRAP-TYPE .1.3.6.1.4.1.534.1.11.4.2.0.43 |
xupsRecep OBJECT IDENTIFIER .1.3.6.1.4.1.534.1.12 |
xupsNumReceptaclesThe number of independently controllable Receptacles, as described in the
xupsRecepTable.ro INTEGER .1.3.6.1.4.1.534.1.12.1 |
xupsRecepTableThe Aggregate Object with number of entries equal to
NumReceptacles and including the xupsRecep group. SEQUENCE OF XupsRecepEntry .1.3.6.1.4.1.534.1.12.2 |
xupsRecepEntryThe Recep table entry, etc. XupsRecepEntry .1.3.6.1.4.1.534.1.12.2.1 |
xupsRecepIndexThe number of the Receptacle. Serves as index for Receptacle table.ro INTEGER .1.3.6.1.4.1.534.1.12.2.1.1 |
xupsRecepStatusThe Recep Status 1=On/Close, 2=Off/Open, 3=On w/Pending Off,
4=Off w/Pending ON, 5=Unknown.ro Enumeration .1.3.6.1.4.1.534.1.12.2.1.2 |
xupsRecepOffDelaySecsThe Delay until the Receptacle is turned Off. Setting
this value to other than -1 will cause the UPS output to
turn off after the number of seconds (0 is immediately).
Setting it to -1 will cause an attempt to abort a pending shutdown.
When this object is set while the UPS is On Battery, it is not necessary
to set xupsRecepOnDelaySecs, since the outlet will turn back on
automatically when power is available again.rw INTEGER (-1..2147483647) -- UNITS seconds .1.3.6.1.4.1.534.1.12.2.1.3 |
xupsRecepOnDelaySecsThe Delay until the Receptacle is turned On. Setting
this value to other than -1 will cause the UPS output to
turn on after the number of seconds (0 is immediately).
Setting it to -1 will cause an attempt to abort a pending restart.rw INTEGER (-1..2147483647) -- UNITS seconds .1.3.6.1.4.1.534.1.12.2.1.4 |
xupsRecepAutoOffDelayThe delay after going On Battery until the Receptacle is
automatically turned Off. A value of -1 means that this Output should
never be turned Off automatically, but must be turned Off only by command.
Values from 0 to 30 are valid, but probably innappropriate.
The AutoOffDelay can be used to prioritize loads in the event of a prolonged
power outage; less critical loads will turn off earlier to extend battery
time for the more critical loads. If the utility power is restored before the
AutoOff delay counts down to 0 on an outlet, that outlet will not turn Off.rw INTEGER (-1..32767) -- UNITS seconds .1.3.6.1.4.1.534.1.12.2.1.5 |
xupsRecepAutoOnDelaySeconds delay after the Outlet is signaled to turn On before the Output is
Automatically turned ON. A value of -1 means that this Output should never
be turned On automatically, but only when specifically commanded to do so.
A value of 0 means that the Receptacle should come On immediately
at power-up or for an On command.rw INTEGER (-1..32767) -- UNITS seconds .1.3.6.1.4.1.534.1.12.2.1.6 |
xupsRecepShedSecsWithRestartSetting this value will cause the UPS output to turn off
after the set number of seconds, then restart (after a UPS-defined
'down time') when the utility is again available.
Unlike xupsRecepOffDelaySecs, which might or might not,
this object always maps to the XCP 0x8A Load Dump & Restart command,
so the desired shutdown and restart behavior is guaranteed to happen.
Once set, this command cannot be aborted.rw INTEGER .1.3.6.1.4.1.534.1.12.2.1.7 |
xupsTopology OBJECT IDENTIFIER .1.3.6.1.4.1.534.1.13 |
xupsTopologyTypeValue which denotes the type of UPS by its power topology. Values are the
same as those described in the XCP Topology block's Overall Topology field.ro INTEGER .1.3.6.1.4.1.534.1.13.1 |
xupsTopoMachineCodeID Value which denotes the Powerware model of the UPS for software. Values
are the same as those described in the XCP Configuration block's Machine Code
field.ro INTEGER .1.3.6.1.4.1.534.1.13.2 |
xupsTopoUnitNumberIdentifies which unit and what type of data is being reported.
A value of 0 means that this MIB information comes from the top-level system
view (eg, manifold module or system bypass cabinet reporting total system
output). Standalone units also use a value of 0, since they are the 'full
system' view.
A value of 1 or higher indicates the number of the module in the system
which is reporting only its own data in the PowerMIB objects.ro INTEGER .1.3.6.1.4.1.534.1.13.3 |
xupsTopoPowerStrategyValue which denotes which Power Strategy is currently set for the UPS.
The values are:
highAlert(1) - The UPS shall optimize its operating state to maximize its
power-protection levels. This mode will be held for at most 24 hours.
standard(2) - Balanced, normal power protection strategy. UPS will not enter
HE operating mode from this setting.
enableHighEfficiency(3) - The UPS is enabled to enter HE operating mode to
optimize its operating state to maximize its efficiency, when
conditions change to permit it (as determined by the UPS).
forceHighEfficiency(4) - If this value is permitted to be Set for this UPS,
and if conditions permit, requires the UPS to enter High Efficiency
mode now, without delay (for as long as utility conditions permit).
After successfully set to forceHighEfficiency(4),
xupsTopoPowerStrategy changes to value enableHighEfficiency(3).
xupsOutputSource will indicate if the UPS status is actually operating in
High Efficiency mode.rw Enumeration .1.3.6.1.4.1.534.1.13.4 |
xupsObjectId OBJECT IDENTIFIER .1.3.6.1.4.1.534.2 |
powerwareEthernetSnmpAdapter OBJECT IDENTIFIER .1.3.6.1.4.1.534.2.1 |
powerwareNetworkSnmpAdapterEther OBJECT IDENTIFIER .1.3.6.1.4.1.534.2.2 |
powerwareNetworkSnmpAdapterToken OBJECT IDENTIFIER .1.3.6.1.4.1.534.2.3 |
onlinetDaemon OBJECT IDENTIFIER .1.3.6.1.4.1.534.2.4 |
connectUPSAdapterEthernet OBJECT IDENTIFIER .1.3.6.1.4.1.534.2.5 |
powerwareNetworkDigitalIOEther OBJECT IDENTIFIER .1.3.6.1.4.1.534.2.6 |
connectUPSAdapterTokenRing OBJECT IDENTIFIER .1.3.6.1.4.1.534.2.7 |
simpleSnmpAdapter OBJECT IDENTIFIER .1.3.6.1.4.1.534.2.8 |