RackMonitor-MIB
Standard SNMP MIB module defining data structures for RackMonitor-MIB.
Imported Objects
Objects
176 total| Object Name |
|---|
powerware OBJECT IDENTIFIER .1.3.6.1.4.1.534 |
RFC1155-SMI Unknown .1.3.6.1.4.1.534 |
product OBJECT IDENTIFIER .1.3.6.1.4.1.534.6 |
dataCenter OBJECT IDENTIFIER .1.3.6.1.4.1.534.6.7 |
environmentalMonitor OBJECT IDENTIFIER .1.3.6.1.4.1.534.6.7.1 |
insObjects OBJECT IDENTIFIER .1.3.6.1.4.1.534.6.7.1.1 |
rmIdent OBJECT IDENTIFIER .1.3.6.1.4.1.534.6.7.1.1.1 |
insIdentManufacturerThe name of the RackMonitor manufacturer.ro DisplayString .1.3.6.1.4.1.534.6.7.1.1.1.1 |
insIdentModelThe RackMonitor Model designation.ro DisplayString .1.3.6.1.4.1.534.6.7.1.1.1.2 |
insIdentAgentSoftwareVersionThe RackMonitor software/firmware version. This variable may or
may not have the same value as
upsIdentUPSSoftwareVersion in some implementations.ro DisplayString .1.3.6.1.4.1.534.6.7.1.1.1.3 |
insIdentNameA string identifying the RackMonitor. This object should be
set by the administrator.rw DisplayString .1.3.6.1.4.1.534.6.7.1.1.1.4 |
rmConfig OBJECT IDENTIFIER .1.3.6.1.4.1.534.6.7.1.1.2 |
rmConfigMibVersionThe version of MIB spec.ro INTEGER .1.3.6.1.4.1.534.6.7.1.1.2.1 |
rmConfigNetwork OBJECT IDENTIFIER .1.3.6.1.4.1.534.6.7.1.1.2.2 |
rmConfigIpAddressThe ip address that NMS can identify the managed
devicerw IpAddress .1.3.6.1.4.1.534.6.7.1.1.2.2.1 |
rmConfigGatewayThe default gateway that allow device managed
through routersrw IpAddress .1.3.6.1.4.1.534.6.7.1.1.2.2.2 |
rmConfigSubnetMaskInternet address subnet maskrw IpAddress .1.3.6.1.4.1.534.6.7.1.1.2.2.3 |
rmConfigDateTime OBJECT IDENTIFIER .1.3.6.1.4.1.534.6.7.1.1.2.3 |
rmConfigDateThe date in Environmental Rack Monitor, format is (dd/mm/yyyy)rw DisplayString .1.3.6.1.4.1.534.6.7.1.1.2.3.1 |
rmConfigTimeThe time in Environmental Rack Monitor, format is (hh:mm:ss)rw DisplayString .1.3.6.1.4.1.534.6.7.1.1.2.3.2 |
rmConfigTimeFromNtpEnable/disable update of the date and time from the NTP server.rw Enumeration .1.3.6.1.4.1.534.6.7.1.1.2.3.3 |
rmConfigNtpIpAddressNTP IP address.rw IpAddress .1.3.6.1.4.1.534.6.7.1.1.2.3.4 |
rmConfigNtpTimeZoneEnable/disable update of the date and time from the NTP server.rw Enumeration .1.3.6.1.4.1.534.6.7.1.1.2.3.5 |
rmConfigDayLightSavingEnable/disable daylight saving for NTP time, if enabled, the time
obtained from the NTP will be set one hour in advance to reflect daylight saving status.rw Enumeration .1.3.6.1.4.1.534.6.7.1.1.2.3.6 |
rmConfigLog OBJECT IDENTIFIER .1.3.6.1.4.1.534.6.7.1.1.2.4 |
rmConfigHistoryLogFrequencyThe frequency of the history log update. The value
is in secondsrw INTEGER .1.3.6.1.4.1.534.6.7.1.1.2.4.1 |
rmConfigExtHistoryLogFrequencyThe frequency of the extended history log update.
The value is in secondsrw INTEGER .1.3.6.1.4.1.534.6.7.1.1.2.4.2 |
rmConfigConfigurationLogEnable/Disable Environmental Rack Monitor parameters change logging.rw Enumeration .1.3.6.1.4.1.534.6.7.1.1.2.4.3 |
rmConfigDhcpStatueEnable or Disable DHCP/BootP capabilityrw Enumeration .1.3.6.1.4.1.534.6.7.1.1.2.5 |
rmConfigPingStatueEnable or Disable Ping Echo capabilityrw Enumeration .1.3.6.1.4.1.534.6.7.1.1.2.6 |
rmConfigTftpStatueEnable or Disable TFTP network upgrade capabilityrw Enumeration .1.3.6.1.4.1.534.6.7.1.1.2.7 |
rmConfigTelnet OBJECT IDENTIFIER .1.3.6.1.4.1.534.6.7.1.1.2.8 |
rmConfigTelnetStatueEnable or Disable telnet accessrw Enumeration .1.3.6.1.4.1.534.6.7.1.1.2.8.1 |
rmConfigTelnetPortNumberSetting the server port for telnet.rw INTEGER .1.3.6.1.4.1.534.6.7.1.1.2.8.2 |
rmConfigHttp OBJECT IDENTIFIER .1.3.6.1.4.1.534.6.7.1.1.2.9 |
rmConfigHttpStatueEnable or Disable HTTP accessrw Enumeration .1.3.6.1.4.1.534.6.7.1.1.2.9.1 |
rmConfigHttpPortNumberSetting the server port of HTTP.rw INTEGER .1.3.6.1.4.1.534.6.7.1.1.2.9.2 |
rmConfigHttpSecurityEnable/Disable HTTP access for read-only usersrw Enumeration .1.3.6.1.4.1.534.6.7.1.1.2.9.3 |
rmConfigSnmp OBJECT IDENTIFIER .1.3.6.1.4.1.534.6.7.1.1.2.10 |
rmConfigSnmpStatueEnable or Disable SNMP accessrw Enumeration .1.3.6.1.4.1.534.6.7.1.1.2.10.1 |
rmConfigSnmpPortNumberSetting the server port for SNMP.rw INTEGER .1.3.6.1.4.1.534.6.7.1.1.2.10.2 |
rmConfigControl OBJECT IDENTIFIER .1.3.6.1.4.1.534.6.7.1.1.2.11 |
rmConfigResetToDefaultReset all parameters of Environmental Rack Monitor to default valuesrw Enumeration .1.3.6.1.4.1.534.6.7.1.1.2.11.1 |
rmConfigRestartRestart rmrw Enumeration .1.3.6.1.4.1.534.6.7.1.1.2.11.2 |
rmConfigTrap OBJECT IDENTIFIER .1.3.6.1.4.1.534.6.7.1.1.2.12 |
rmConfigTrapRetryCountThe count of repeat traps to send to NMS before trap
acknowledge received.rw INTEGER .1.3.6.1.4.1.534.6.7.1.1.2.12.1 |
rmConfigTrapRetryTimeThe time between retry traps sent to NMS.rw INTEGER .1.3.6.1.4.1.534.6.7.1.1.2.12.2 |
rmConfigTrapAckSignatureThe signature of trap acknowledge.rw INTEGER .1.3.6.1.4.1.534.6.7.1.1.2.12.3 |
rmConfigPollRateThe frequency that the Rack Monitor will read from sensors
(unit : second).rw INTEGER .1.3.6.1.4.1.534.6.7.1.1.2.13 |
rmConfigTrapsReceiversTableA list of managers to send traps to. The number of
entries is given by the value of rmConfigNumTrapReceivers SEQUENCE OF RmConfigTrapsReceiversEntry .1.3.6.1.4.1.534.6.7.1.1.2.14 |
rmConfigTrapsReceiversEntryThe managers to send traps to. RmConfigTrapsReceiversEntry .1.3.6.1.4.1.534.6.7.1.1.2.14.1 |
trapsIndexThe index to a trap receiver entry.ro INTEGER .1.3.6.1.4.1.534.6.7.1.1.2.14.1.1 |
trapsReceiverAddrThe IP address of the manager to send a trap to.rw IpAddress .1.3.6.1.4.1.534.6.7.1.1.2.14.1.2 |
receiverCommunityStringThe community name to use in the trap when
sent to the manager.rw DisplayString .1.3.6.1.4.1.534.6.7.1.1.2.14.1.3 |
receiverSeverityLevelThe severity level of traps to be received by this manager.rw Enumeration .1.3.6.1.4.1.534.6.7.1.1.2.14.1.4 |
receiverDescriptionDescription of trap receiversrw DisplayString .1.3.6.1.4.1.534.6.7.1.1.2.14.1.5 |
rmConfigAccessControlTableA list of managers which can access rm with private
community string. SEQUENCE OF RmConfigAccessControlEntry .1.3.6.1.4.1.534.6.7.1.1.2.15 |
rmConfigAccessControlEntryThe managers. RmConfigAccessControlEntry .1.3.6.1.4.1.534.6.7.1.1.2.15.1 |
accessIndexThe index to a access control entry.ro INTEGER .1.3.6.1.4.1.534.6.7.1.1.2.15.1.1 |
accessControlAddrThe IP address of the manager to access RackMonitorrw IpAddress .1.3.6.1.4.1.534.6.7.1.1.2.15.1.2 |
accessCommunityStringThe community name to use in the manager when
access RackMonitorrw DisplayString .1.3.6.1.4.1.534.6.7.1.1.2.15.1.3 |
accessControlModeAccess type, only read/Write access type can change parameter
of RackMonitorrw Enumeration .1.3.6.1.4.1.534.6.7.1.1.2.15.1.4 |
rmConfigTemperatureUnitThe temperature unit of the system, can be Celsius or Fahrenheitrw Enumeration .1.3.6.1.4.1.534.6.7.1.1.2.16 |
rmConfigDateFormatThe date format of the system, can be dd/mm/yyyy or mm/dd/yyyyrw Enumeration .1.3.6.1.4.1.534.6.7.1.1.2.17 |
sensorMonitor OBJECT IDENTIFIER .1.3.6.1.4.1.534.6.7.1.1.3 |
smSensorNumberThe number of sensors that can be monitored.ro INTEGER .1.3.6.1.4.1.534.6.7.1.1.3.1 |
smSensorTableA list of sensor devices to be monitored. SEQUENCE OF SmSensorEntry .1.3.6.1.4.1.534.6.7.1.1.3.2 |
smSensorEntryThe sensor device. SmSensorEntry .1.3.6.1.4.1.534.6.7.1.1.3.2.1 |
smDeviceIndexThe index to a sensor device entry.ro INTEGER .1.3.6.1.4.1.534.6.7.1.1.3.2.1.1 |
smDeviceStatusThe device type plugged into RackMonitor.ro Enumeration .1.3.6.1.4.1.534.6.7.1.1.3.2.1.2 |
smDeviceTemperatureThe temperature of sensor on device RackMonitor, the unit is 0.1 degree.ro INTEGER .1.3.6.1.4.1.534.6.7.1.1.3.2.1.3 |
smDeviceTemperatureAlarmThe status of temperature sensor on device RackMonitor.ro Enumeration .1.3.6.1.4.1.534.6.7.1.1.3.2.1.4 |
smDeviceHumidityThe humidity of sensor on device RackMonitor, the unit is 0.1%.ro INTEGER .1.3.6.1.4.1.534.6.7.1.1.3.2.1.5 |
smDeviceHumidityAlarmThe device type plugged into RackMonitor.ro Enumeration .1.3.6.1.4.1.534.6.7.1.1.3.2.1.6 |
smAlarm1The device type plugged into RackMonitor.ro Enumeration .1.3.6.1.4.1.534.6.7.1.1.3.2.1.7 |
smAlarm2The device type plugged into RackMonitor.ro Enumeration .1.3.6.1.4.1.534.6.7.1.1.3.2.1.8 |
sensorConfig OBJECT IDENTIFIER .1.3.6.1.4.1.534.6.7.1.1.4 |
scSensorNumberThe number of sensors that can be plugged into RackMonitor.ro INTEGER .1.3.6.1.4.1.534.6.7.1.1.4.1 |
scSensorTableA list of sensor devices to be configured. SEQUENCE OF ScSensorEntry .1.3.6.1.4.1.534.6.7.1.1.4.2 |
scSensorEntryThe sensor device. ScSensorEntry .1.3.6.1.4.1.534.6.7.1.1.4.2.1 |
scDeviceIndexThe index to a sensor device entry.ro INTEGER .1.3.6.1.4.1.534.6.7.1.1.4.2.1.1 |
scDeviceNameThe name of the sensor device for identification.rw DisplayString .1.3.6.1.4.1.534.6.7.1.1.4.2.1.2 |
scDeviceStateThe setup of sensor device type.rw Enumeration .1.3.6.1.4.1.534.6.7.1.1.4.2.1.3 |
scSensor1 OBJECT IDENTIFIER .1.3.6.1.4.1.534.6.7.1.1.4.3 |
scSensor1DeviceNameThe name of sensor device.rw DisplayString .1.3.6.1.4.1.534.6.7.1.1.4.3.1 |
scSensor1DeviceStateThe setup of sensor device type.rw Enumeration .1.3.6.1.4.1.534.6.7.1.1.4.3.2 |
scSensor1Temperature OBJECT IDENTIFIER .1.3.6.1.4.1.534.6.7.1.1.4.3.3 |
scSensor1TemperatureNameThe temperature sensor name.rw DisplayString .1.3.6.1.4.1.534.6.7.1.1.4.3.3.1 |
scSensor1TemperatureLowWarningThe set point to trigger low warning alarm.rw INTEGER .1.3.6.1.4.1.534.6.7.1.1.4.3.3.2 |
scSensor1TemperatureLowCriticalThe threshold to trigger low critical alarm.rw INTEGER .1.3.6.1.4.1.534.6.7.1.1.4.3.3.3 |
scSensor1TemperatureHighWarningThe threshold to trigger high warning alarm.rw INTEGER .1.3.6.1.4.1.534.6.7.1.1.4.3.3.4 |
scSensor1TemperatureHighCriticalThe threshold to trigger high critical alarm.rw INTEGER .1.3.6.1.4.1.534.6.7.1.1.4.3.3.5 |
scSensor1TemperatureHysteresisThe set value to prevent too many alarms when temperature is hovering around the
set threshold.rw INTEGER .1.3.6.1.4.1.534.6.7.1.1.4.3.3.6 |
scSensor1TemperatureCalibrationThe set value to get the correct temperature according to the reference temperature.rw Enumeration .1.3.6.1.4.1.534.6.7.1.1.4.3.3.7 |
scSensor1TemperatureLowWarningStatusEnable/Disable the set point to trigger low warning alarm.rw Enumeration .1.3.6.1.4.1.534.6.7.1.1.4.3.3.8 |
scSensor1TemperatureLowCriticalStatusEnable/Disable the set point to trigger low critical alarm.rw Enumeration .1.3.6.1.4.1.534.6.7.1.1.4.3.3.9 |
scSensor1TemperatureHighWarningStatusEnable/Disable the set point to trigger high warning alarm.rw Enumeration .1.3.6.1.4.1.534.6.7.1.1.4.3.3.10 |
scSensor1TemperatureHighCriticalStatusEnable/disable the set point to trigger high critical alarm.rw Enumeration .1.3.6.1.4.1.534.6.7.1.1.4.3.3.11 |
scSensor1Humidity OBJECT IDENTIFIER .1.3.6.1.4.1.534.6.7.1.1.4.3.4 |
scSensor1HumdityNameThe humidity sensor name.rw DisplayString .1.3.6.1.4.1.534.6.7.1.1.4.3.4.1 |
scSensor1HumidityLowWarningThe set point to trigger low warning alarm.rw INTEGER .1.3.6.1.4.1.534.6.7.1.1.4.3.4.2 |
scSensor1HumidityLowCriticalThe threshold to trigger low critical alarm.rw INTEGER .1.3.6.1.4.1.534.6.7.1.1.4.3.4.3 |
scSensor1HumidityHighWarningThe threshold to trigger high warning alarm.rw INTEGER .1.3.6.1.4.1.534.6.7.1.1.4.3.4.4 |
scSensor1HumidityHighCriticalThe threshold to trigger high critical alarm.rw INTEGER .1.3.6.1.4.1.534.6.7.1.1.4.3.4.5 |
scSensor1HumidityHysteresisThe set value to prevent too many alarms when Humidity is hovering around the
set threshold.rw INTEGER .1.3.6.1.4.1.534.6.7.1.1.4.3.4.6 |
scSensor1HumidityCalibrationThe set value to get the correct temperature according to your reference temperature.rw Enumeration .1.3.6.1.4.1.534.6.7.1.1.4.3.4.7 |
scSensor1HumidityLowWarningStatusEnable/Disable the set point to trigger low warning alarm.rw Enumeration .1.3.6.1.4.1.534.6.7.1.1.4.3.4.8 |
scSensor1HumidityLowCriticalStatusEnable/Disable the set point to trigger low critical alarm.rw Enumeration .1.3.6.1.4.1.534.6.7.1.1.4.3.4.9 |
scSensor1HumidityHighWarningStatusEnable/Disable the set point to trigger high warning alarm.rw Enumeration .1.3.6.1.4.1.534.6.7.1.1.4.3.4.10 |
scSensor1HumidityHighCriticalStatusEnable/Disable the set point to trigger high critical alarm.rw Enumeration .1.3.6.1.4.1.534.6.7.1.1.4.3.4.11 |
scSensor1Alarm1 OBJECT IDENTIFIER .1.3.6.1.4.1.534.6.7.1.1.4.3.5 |
scSensor1Alarm1NameThe name of alarm-1.rw DisplayString .1.3.6.1.4.1.534.6.7.1.1.4.3.5.1 |
scSensor1Alarm1StateSetup the signal type to trigger alarm.rw Enumeration .1.3.6.1.4.1.534.6.7.1.1.4.3.5.2 |
scSensor1Alarm1HysteresisThe set value to delay the alarm triggered when event occurs.rw INTEGER .1.3.6.1.4.1.534.6.7.1.1.4.3.5.3 |
scSensor1Alarm2 OBJECT IDENTIFIER .1.3.6.1.4.1.534.6.7.1.1.4.3.6 |
scSensor1Alarm2NameThe name of alarm-1.rw DisplayString .1.3.6.1.4.1.534.6.7.1.1.4.3.6.1 |
scSensor1Alarm2StateSetup the signal type to trigger alarm.rw Enumeration .1.3.6.1.4.1.534.6.7.1.1.4.3.6.2 |
scSensor1Alarm2HysteresisThe set value to delay the alarm triggered when event occurs.rw INTEGER .1.3.6.1.4.1.534.6.7.1.1.4.3.6.3 |
scSensor2 OBJECT IDENTIFIER .1.3.6.1.4.1.534.6.7.1.1.4.4 |
scSensor2DeviceNameThe name of sensor device.rw DisplayString .1.3.6.1.4.1.534.6.7.1.1.4.4.1 |
scSensor2DeviceStateThe setup of sensor device type.rw Enumeration .1.3.6.1.4.1.534.6.7.1.1.4.4.2 |
scSensor2Temperature OBJECT IDENTIFIER .1.3.6.1.4.1.534.6.7.1.1.4.4.3 |
scSensor2TemperatureNameThe temperature sensor name.rw DisplayString .1.3.6.1.4.1.534.6.7.1.1.4.4.3.1 |
scSensor2TemperatureLowWarningThe set point to trigger low warning alarm.rw INTEGER .1.3.6.1.4.1.534.6.7.1.1.4.4.3.2 |
scSensor2TemperatureLowCriticalThe threshold to trigger low critical alarm.rw INTEGER .1.3.6.1.4.1.534.6.7.1.1.4.4.3.3 |
scSensor2TemperatureHighWarningThe threshold to trigger high warning alarm.rw INTEGER .1.3.6.1.4.1.534.6.7.1.1.4.4.3.4 |
scSensor2TemperatureHighCriticalThe threshold to trigger high critical alarm.rw INTEGER .1.3.6.1.4.1.534.6.7.1.1.4.4.3.5 |
scSensor2TemperatureHysteresisThe set value to prevent too many alarms when temperature is hovering around the
set threshold.rw INTEGER .1.3.6.1.4.1.534.6.7.1.1.4.4.3.6 |
scSensor2TemperatureCalibrationThe set value to get the correct temperature according to your reference temperature.rw Enumeration .1.3.6.1.4.1.534.6.7.1.1.4.4.3.7 |
scSensor2TemperatureLowWarningStatusEnable/Disable the set point to trigger low warning alarm.rw Enumeration .1.3.6.1.4.1.534.6.7.1.1.4.4.3.8 |
scSensor2TemperatureLowCriticalStatusEnable/Disable the set point to trigger low critical alarm.rw Enumeration .1.3.6.1.4.1.534.6.7.1.1.4.4.3.9 |
scSensor2TemperatureHighWarningStatusEnable/Disable the set point to trigger high warning alarm.rw Enumeration .1.3.6.1.4.1.534.6.7.1.1.4.4.3.10 |
scSensor2TemperatureHighCriticalStatusEnable/Disable the set point to trigger high critical alarm.rw Enumeration .1.3.6.1.4.1.534.6.7.1.1.4.4.3.11 |
scSensor2Humidity OBJECT IDENTIFIER .1.3.6.1.4.1.534.6.7.1.1.4.4.4 |
scSensor2HumdityNameThe humidity sensor name.rw DisplayString .1.3.6.1.4.1.534.6.7.1.1.4.4.4.1 |
scSensor2HumidityLowWarningThe set point to trigger low warning alarm.rw INTEGER .1.3.6.1.4.1.534.6.7.1.1.4.4.4.2 |
scSensor2HumidityLowCriticalThe threshold to trigger low critical alarm.rw INTEGER .1.3.6.1.4.1.534.6.7.1.1.4.4.4.3 |
scSensor2HumidityHighWarningThe threshold to trigger high warning alarm.rw INTEGER .1.3.6.1.4.1.534.6.7.1.1.4.4.4.4 |
scSensor2HumidityHighCriticalThe threshold to trigger high critical alarm.rw INTEGER .1.3.6.1.4.1.534.6.7.1.1.4.4.4.5 |
scSensor2HumidityHysteresisThe set value to prevent too many alarms when Humidity is hovering around the
set threshold.rw INTEGER .1.3.6.1.4.1.534.6.7.1.1.4.4.4.6 |
scSensor2HumidityCalibrationThe set value to get the correct temperature according to the reference temperature.rw Enumeration .1.3.6.1.4.1.534.6.7.1.1.4.4.4.7 |
scSensor2HumidityLowWarningStatusEnable/Disable the set point to trigger low warning alarm.rw Enumeration .1.3.6.1.4.1.534.6.7.1.1.4.4.4.8 |
scSensor2HumidityLowCriticalStatusEnable/Disable the set point to trigger low critical alarm.rw Enumeration .1.3.6.1.4.1.534.6.7.1.1.4.4.4.9 |
scSensor2HumidityHighWarningStatusEnable/Disable the set point to trigger high warning alarm.rw Enumeration .1.3.6.1.4.1.534.6.7.1.1.4.4.4.10 |
scSensor2HumidityHighCriticalStatusEnable/Disable the set point to trigger high critical alarm.rw Enumeration .1.3.6.1.4.1.534.6.7.1.1.4.4.4.11 |
scSensor2Alarm1 OBJECT IDENTIFIER .1.3.6.1.4.1.534.6.7.1.1.4.4.5 |
scSensor2Alarm1NameThe name of alarm-1.rw DisplayString .1.3.6.1.4.1.534.6.7.1.1.4.4.5.1 |
scSensor2Alarm1StateSetup the signal type to trigger alarm.rw Enumeration .1.3.6.1.4.1.534.6.7.1.1.4.4.5.2 |
scSensor2Alarm1HysteresisThe set value to delay the alarm triggered when event occurs.rw INTEGER .1.3.6.1.4.1.534.6.7.1.1.4.4.5.3 |
scSensor2Alarm2 OBJECT IDENTIFIER .1.3.6.1.4.1.534.6.7.1.1.4.4.6 |
scSensor2Alarm2NameThe name of alarm-1.rw DisplayString .1.3.6.1.4.1.534.6.7.1.1.4.4.6.1 |
scSensor2Alarm2StateSetup the signal type to trigger alarm.rw Enumeration .1.3.6.1.4.1.534.6.7.1.1.4.4.6.2 |
scSensor2Alarm2HysteresisThe set value to delay the alarm triggered when event occurs.rw INTEGER .1.3.6.1.4.1.534.6.7.1.1.4.4.6.3 |
rmTraps OBJECT IDENTIFIER .1.3.6.1.4.1.534.6.7.1.2 |
rmCommunicationRestoredINFORMATION: Communication between RackMonitor and sensor had
established. TRAP-TYPE .1.3.6.1.4.1.534.6.7.1.2.0.1 |
rmCommunicationLostWARNING: Communication between RackMonitor and sensor had
lost. TRAP-TYPE .1.3.6.1.4.1.534.6.7.1.2.0.2 |
rmAlarm1InactiveINFORMATION: Alarm1 of sensor had return from active state. TRAP-TYPE .1.3.6.1.4.1.534.6.7.1.2.0.3 |
rmAlarm1ActiveWARNING: Alarm1 has become active. TRAP-TYPE .1.3.6.1.4.1.534.6.7.1.2.0.4 |
rmAlarm2InactiveINFORMATION: Alarm2 of sensor has returned to normal state. TRAP-TYPE .1.3.6.1.4.1.534.6.7.1.2.0.5 |
rmAlarm2ActiveWARNING: Alarm2 had became active. TRAP-TYPE .1.3.6.1.4.1.534.6.7.1.2.0.6 |
rmTemperatureNotHighWarningINFORMATION: The temperature of sensor had return from High warning to normal. TRAP-TYPE .1.3.6.1.4.1.534.6.7.1.2.0.7 |
rmTemperatureHighWarningWARNING: The temperature of sensor was higher than High warning set point. TRAP-TYPE .1.3.6.1.4.1.534.6.7.1.2.0.8 |
rmTemperatureNotLowWarningINFORMATION: The temperature of sensor had return from low warning to normal. TRAP-TYPE .1.3.6.1.4.1.534.6.7.1.2.0.9 |
rmTemperatureLowWarningWARNING: The temperature of sensor was lower than low warning set point. TRAP-TYPE .1.3.6.1.4.1.534.6.7.1.2.0.10 |
rmTemperatureNotHighCriticalINFORMATION: The temperature of sensor lower than high critical set point. TRAP-TYPE .1.3.6.1.4.1.534.6.7.1.2.0.11 |
rmTemperatureHighCriticalCRITICAL: The temperature of sensor was higher than high critical set point. TRAP-TYPE .1.3.6.1.4.1.534.6.7.1.2.0.12 |
rmTemperatureNotLowCriticalINFORMATION: The temperature of sensor was higher than low critical set point. TRAP-TYPE .1.3.6.1.4.1.534.6.7.1.2.0.13 |
rmTemperatureLowCriticalCRITICAL: The temperature of sensor was lower than low critical set point. TRAP-TYPE .1.3.6.1.4.1.534.6.7.1.2.0.14 |
rmHumidityNotHighWarningINFORMATION: The humidity of sensor had return from High warning to normal. TRAP-TYPE .1.3.6.1.4.1.534.6.7.1.2.0.15 |
rmHumidityHighWarningWARNING: The humidity of sensor was higher than High warning set point. TRAP-TYPE .1.3.6.1.4.1.534.6.7.1.2.0.16 |
rmHumidityNotLowWarningINFORMATION: The humidity of sensor had return from low warning to normal. TRAP-TYPE .1.3.6.1.4.1.534.6.7.1.2.0.17 |
rmHumidityLowWarningWARNING: The humidity of sensor was lower than low warning set point. TRAP-TYPE .1.3.6.1.4.1.534.6.7.1.2.0.18 |
rmHumidityNotHighCriticalINFORMATION: The humidity of sensor lower than high critical set point. TRAP-TYPE .1.3.6.1.4.1.534.6.7.1.2.0.19 |
rmHumidityHighCriticalCRITICAL: The humidity of sensor was higher than high critical set point. TRAP-TYPE .1.3.6.1.4.1.534.6.7.1.2.0.20 |
rmHumidityNotLowCriticalINFORMATION: The humidity of sensor was higher than low critical set point. TRAP-TYPE .1.3.6.1.4.1.534.6.7.1.2.0.21 |
rmHumidityLowCriticalCRITICAL: The humidity of sensor was lower than low critical set point. TRAP-TYPE .1.3.6.1.4.1.534.6.7.1.2.0.22 |
More MIBs from Eaton
Browse all EatonMIBs →Standard SNMP MIB module defining data structures for XUPS-MIB.
The EATON-EPDU-MIB enables SNMP-based monitoring and management of Eaton Enclosure Power Distribution Units, providing granular access to real-time electrical metrics including voltage, current, power consumption, and outlet-level status. This module facilitates precise remote control of individual PDU outlets and the collection of environmental data such as temperature and humidity for infrastructure capacity planning and fault detection.
The EATON-EPDU-MA-MIB enables SNMP-based monitoring and control of Eaton Enclosed Power Distribution Units (ePDUs) in managed configurations, exposing critical power metrics such as outlet status, voltage, current, power consumption, and environmental sensor data.
The EATON-ATS2-MIB enables SNMP-based monitoring and management of Eaton Automatic Transfer Switch (ATS) hardware, providing real-time visibility into critical power status indicators such as source availability, transfer states, and alarm conditions.
The EATON-PDU-MIB enables SNMP-based monitoring and management of Eaton Power Distribution Units, providing access to real-time electrical metrics including voltage, current, power consumption, and outlet-level status. It facilitates granular control over individual PDU outlets and aggregates environmental data such as temperature and humidity for infrastructure capacity planning and fault detection.
The EATON-PXG-MIB module enables SNMP-based monitoring and management of Eaton Power Xpert Gateways, specifically exposing operational status, environmental sensor data, and power distribution metrics for the device's internal Toolkit software. This MIB facilitates the collection of critical infrastructure telemetry, including voltage, current, frequency, and alarm notifications, to support real-time power availability and fault detection within enterprise data centers.