WebGraph-Thermo-Hygrometer-US-MIB
AI MIB Summary
Standard SNMP MIB module defining data structures for WebGraph-Thermo-Hygrometer-US-MIB.
197
Objects
Active
Status
4
Dependencies
Imported Objects
Objects
197 total| Object Name |
|---|
wut OBJECT IDENTIFIER .1.3.6.1.4.1.5040 |
IMPORTS Unknown .1.3.6.1.4.1.5040 |
wtComServer OBJECT IDENTIFIER .1.3.6.1.4.1.5040.1 |
wtWebio OBJECT IDENTIFIER .1.3.6.1.4.1.5040.1.2 |
wtWebGraphThermHygro OBJECT IDENTIFIER .1.3.6.1.4.1.5040.1.2.9 |
wtWebGraphThermHygroAlert1This SNMP trap is generated when Alarm 1 was triggered,
SNMP trap enable is set and
SNMP is enabled. TRAP-TYPE .1.3.6.1.4.1.5040.1.2.9.0.31 |
wtWebGraphThermHygroAlert2This SNMP trap is generated when Alarm 2 was triggered,
SNMP trap enable is set and
SNMP is enabled. TRAP-TYPE .1.3.6.1.4.1.5040.1.2.9.0.32 |
wtWebGraphThermHygroAlert3This SNMP trap is generated when Alarm 3 was triggered,
SNMP trap enable is set and
SNMP is enabled. TRAP-TYPE .1.3.6.1.4.1.5040.1.2.9.0.33 |
wtWebGraphThermHygroAlert4This SNMP trap is generated when Alarm 4 was triggered,
SNMP trap enable is set and
SNMP is enabled. TRAP-TYPE .1.3.6.1.4.1.5040.1.2.9.0.34 |
wtWebGraphThermHygroAlert5This SNMP trap is generated when Alarm 5 was triggered,
SNMP trap enable is set and
SNMP is enabled. TRAP-TYPE .1.3.6.1.4.1.5040.1.2.9.0.35 |
wtWebGraphThermHygroAlert6This SNMP trap is generated when Alarm 6 was triggered,
SNMP trap enable is set and
SNMP is enabled. TRAP-TYPE .1.3.6.1.4.1.5040.1.2.9.0.36 |
wtWebGraphThermHygroAlert7This SNMP trap is generated when Alarm 7 was triggered,
SNMP trap enable is set and
SNMP is enabled. TRAP-TYPE .1.3.6.1.4.1.5040.1.2.9.0.37 |
wtWebGraphThermHygroAlert8This SNMP trap is generated when Alarm 8 was triggered,
SNMP trap enable is set and
SNMP is enabled. TRAP-TYPE .1.3.6.1.4.1.5040.1.2.9.0.38 |
wtWebGraphThermHygroAlert9This SNMP trap is generated when Alarm 1 was cleared,
SNMP trap enable is set and
SNMP is enabled. TRAP-TYPE .1.3.6.1.4.1.5040.1.2.9.0.91 |
wtWebGraphThermHygroAlert10This SNMP trap is generated when Alarm 2 was cleared,
SNMP trap enable is set and
SNMP is enabled. TRAP-TYPE .1.3.6.1.4.1.5040.1.2.9.0.92 |
wtWebGraphThermHygroAlert11This SNMP trap is generated when Alarm 3 was cleared,
SNMP trap enable is set and
SNMP is enabled. TRAP-TYPE .1.3.6.1.4.1.5040.1.2.9.0.93 |
wtWebGraphThermHygroAlert12This SNMP trap is generated when Alarm 4 was cleared,
SNMP trap enable is set and
SNMP is enabled. TRAP-TYPE .1.3.6.1.4.1.5040.1.2.9.0.94 |
wtWebGraphThermHygroAlert13This SNMP trap is generated when Alarm 5 was cleared,
SNMP trap enable is set and
SNMP is enabled. TRAP-TYPE .1.3.6.1.4.1.5040.1.2.9.0.95 |
wtWebGraphThermHygroAlert14This SNMP trap is generated when Alarm 6 was cleared,
SNMP trap enable is set and
SNMP is enabled. TRAP-TYPE .1.3.6.1.4.1.5040.1.2.9.0.96 |
wtWebGraphThermHygroAlert15This SNMP trap is generated when Alarm 7 was cleared,
SNMP trap enable is set and
SNMP is enabled. TRAP-TYPE .1.3.6.1.4.1.5040.1.2.9.0.97 |
wtWebGraphThermHygroAlert16This SNMP trap is generated when Alarm 8 was cleared,
SNMP trap enable is set and
SNMP is enabled. TRAP-TYPE .1.3.6.1.4.1.5040.1.2.9.0.98 |
wtWebGraphThermHygroAlertDiagThis SNMP trap is generated when a diagnosis/error message was triggered,
SNMP trap enable is set and
SNMP is enabled. TRAP-TYPE .1.3.6.1.4.1.5040.1.2.9.0.110 |
wtWebGraphThermHygroTemp OBJECT IDENTIFIER .1.3.6.1.4.1.5040.1.2.9.1 |
wtWebGraphThermHygroSensorsNumber of sensorsro INTEGER .1.3.6.1.4.1.5040.1.2.9.1.1 |
wtWebGraphThermHygroSensorTableList of sensors. SEQUENCE OF WtWebGraphThermHygroSensorEntry .1.3.6.1.4.1.5040.1.2.9.1.2 |
wtWebGraphThermHygroSensorEntryList of sensor numbers. WtWebGraphThermHygroSensorEntry .1.3.6.1.4.1.5040.1.2.9.1.2.1 |
wtWebGraphThermHygroSensorNoSensor number.ro INTEGER .1.3.6.1.4.1.5040.1.2.9.1.2.1.1 |
wtWebGraphThermHygroTempValueTableList of measurement values corresponding to the channel numbers. SEQUENCE OF WtWebGraphThermHygroTempValueEntry .1.3.6.1.4.1.5040.1.2.9.1.3 |
wtWebGraphThermHygroTempValueEntryMeasurement values of the sensors. WtWebGraphThermHygroTempValueEntry .1.3.6.1.4.1.5040.1.2.9.1.3.1 |
wtWebGraphThermHygroTempValueMeasurement value of the sensor, ASCII, 5 characters in length.ro OCTET STRING .1.3.6.1.4.1.5040.1.2.9.1.3.1.1 |
wtWebGraphThermHygroBinaryTempValueTableList of binary measurement values corresponding to the channel numbers. SEQUENCE OF WtWebGraphThermHygroBinaryTempValueEntry .1.3.6.1.4.1.5040.1.2.9.1.4 |
wtWebGraphThermHygroBinaryTempValueEntryBinary measurement values of the sensors. WtWebGraphThermHygroBinaryTempValueEntry .1.3.6.1.4.1.5040.1.2.9.1.4.1 |
wtWebGraphThermHygroBinaryTempValueBinary measurement value of the sensor in 1/10 degrees Celsius or 1/10 per cent,
signed number, 0x4FFF6 indicates an
invalid measured value.ro INTEGER .1.3.6.1.4.1.5040.1.2.9.1.4.1.1 |
wtWebGraphThermHygroSessCntrl OBJECT IDENTIFIER .1.3.6.1.4.1.5040.1.2.9.2 |
wtWebGraphThermHygroSessCntrlPasswordEntering this password opens a session which is ended by writing a 1 to
wtWebGraphThermHygroSessCntrlLogout. When read this variable provides a string of
length zero.rw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.2.1 |
wtWebGraphThermHygroSessCntrlConfigModeWhen the device is in SNMP configuration mode, the value 1 is
returned, otherwise 0. If the read value is 0 even though the
password was written, the device is already in config mode and the
variables can only be read.ro Enumeration .1.3.6.1.4.1.5040.1.2.9.2.2 |
wtWebGraphThermHygroSessCntrlLogoutIf the device is in configuration mode and the session was opened by
this SNMP Manager, writing a 1 to this variable will end the session
and all parameters are stored.
Writing a 2 discards all entries again.
When read this variable provides the value 0.rw INTEGER .1.3.6.1.4.1.5040.1.2.9.2.3 |
wtWebGraphThermHygroSessCntrlAdminPasswordThis password protects access to the variables with administrator rights.
It can only be changed by the administrator. If no password was assigned,
the valid password is public.rw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.2.4 |
wtWebGraphThermHygroSessCntrlConfigPasswordThis password protects access to the variables with configurator rights. It can
be changed by the administrator and by the configurator. If no password was assigned,
the valid password is public. When read this variable provides a null-pointer.rw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.2.5 |
wtWebGraphThermHygroConfig OBJECT IDENTIFIER .1.3.6.1.4.1.5040.1.2.9.3 |
wtWebGraphThermHygroDevice OBJECT IDENTIFIER .1.3.6.1.4.1.5040.1.2.9.3.1 |
wtWebGraphThermHygroText OBJECT IDENTIFIER .1.3.6.1.4.1.5040.1.2.9.3.1.1 |
wtWebGraphThermHygroDeviceNameName of the Webio, which is user definable.rw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.3.1.1.1 |
wtWebGraphThermHygroDeviceTextDescription of the Webio, which is user definable.rw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.3.1.1.2 |
wtWebGraphThermHygroDeviceLocationDescription of the location of the Webio, which is user definable.rw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.3.1.1.3 |
wtWebGraphThermHygroDeviceContactContact address of the system operator of the Webio, which is user definable.rw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.3.1.1.4 |
wtWebGraphThermHygroTimeDate OBJECT IDENTIFIER .1.3.6.1.4.1.5040.1.2.9.3.1.2 |
wtWebGraphThermHygroTimeZone OBJECT IDENTIFIER .1.3.6.1.4.1.5040.1.2.9.3.1.2.1 |
wtWebGraphThermHygroTzOffsetHrsOffset hours for the time zone (winter time) with respect to UTC.rw INTEGER .1.3.6.1.4.1.5040.1.2.9.3.1.2.1.1 |
wtWebGraphThermHygroTzOffsetMinOffset minutes for the time zone (winter time) with respect to UTC.rw INTEGER .1.3.6.1.4.1.5040.1.2.9.3.1.2.1.2 |
wtWebGraphThermHygroTzEnableBinary coded conditions:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 1-7: unused
Bit 0 : Apply Timezonerw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.3.1.2.1.3 |
wtWebGraphThermHygroStTzOffsetHrsOffset hours of the time zone (summer time) with respect to UTC.rw INTEGER .1.3.6.1.4.1.5040.1.2.9.3.1.2.1.4 |
wtWebGraphThermHygroStTzOffsetMinOffset minutes of the time zone (summer time) with respect to UTC.rw INTEGER .1.3.6.1.4.1.5040.1.2.9.3.1.2.1.5 |
wtWebGraphThermHygroStTzEnableBinary coded conditions:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 1-7: unused
Bit 0 : Apply Summertimerw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.3.1.2.1.6 |
wtWebGraphThermHygroStTzStartMonthMonth in which the change is made from winter time to summer time.rw Enumeration .1.3.6.1.4.1.5040.1.2.9.3.1.2.1.7 |
wtWebGraphThermHygroStTzStartModeMode of the day of the week for which the change is made from winter time to summer time.rw Enumeration .1.3.6.1.4.1.5040.1.2.9.3.1.2.1.8 |
wtWebGraphThermHygroStTzStartWdayDay of the week on which the change is made from winter time to summer timerw Enumeration .1.3.6.1.4.1.5040.1.2.9.3.1.2.1.9 |
wtWebGraphThermHygroStTzStartHrsHour in which the time zone is changed from winter to summer time with
respect to UTC.rw INTEGER .1.3.6.1.4.1.5040.1.2.9.3.1.2.1.10 |
wtWebGraphThermHygroStTzStartMinMinute in which the time zone is changed from winter to summer time with
respect to UTC.rw INTEGER .1.3.6.1.4.1.5040.1.2.9.3.1.2.1.11 |
wtWebGraphThermHygroStTzStopMonthMonth in which the change is made from summer time to winter time.rw Enumeration .1.3.6.1.4.1.5040.1.2.9.3.1.2.1.12 |
wtWebGraphThermHygroStTzStopModeMode of the week day on which the change is made from summer time to winter time.rw Enumeration .1.3.6.1.4.1.5040.1.2.9.3.1.2.1.13 |
wtWebGraphThermHygroStTzStopWdayDay of the week on which the change is made from summer time to winter time.rw Enumeration .1.3.6.1.4.1.5040.1.2.9.3.1.2.1.14 |
wtWebGraphThermHygroStTzStopHrsHour at which the time zone is changed from summer to winter time with
respect to UTC.rw INTEGER .1.3.6.1.4.1.5040.1.2.9.3.1.2.1.15 |
wtWebGraphThermHygroStTzStopMinMinute at which the time zone is changed from summer to winter time with
respect to UTC.rw INTEGER .1.3.6.1.4.1.5040.1.2.9.3.1.2.1.16 |
wtWebGraphThermHygroTimeServer OBJECT IDENTIFIER .1.3.6.1.4.1.5040.1.2.9.3.1.2.2 |
wtWebGraphThermHygroTimeServer1IP address or name of the 1st time server in ASCIIrw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.3.1.2.2.1 |
wtWebGraphThermHygroTimeServer2IP address or name of the 2nd time server in ASCIIrw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.3.1.2.2.2 |
wtWebGraphThermHygroTsEnableBinary coded conditions:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 1-7: unused
Bit 0 : Apply Time Serverrw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.3.1.2.2.3 |
wtWebGraphThermHygroTsSyncTimeDaily synchronisation time with the time server (hour: 0-23).rw INTEGER .1.3.6.1.4.1.5040.1.2.9.3.1.2.2.4 |
wtWebGraphThermHygroDeviceClock OBJECT IDENTIFIER .1.3.6.1.4.1.5040.1.2.9.3.1.2.3 |
wtWebGraphThermHygroClockHrsClock hours taking into account the time zone settings.rw INTEGER .1.3.6.1.4.1.5040.1.2.9.3.1.2.3.1 |
wtWebGraphThermHygroClockMinClock minutes taking into account the time zone settings.rw INTEGER .1.3.6.1.4.1.5040.1.2.9.3.1.2.3.2 |
wtWebGraphThermHygroClockDayDate: Day of the month, taking into account the time zone settings.rw INTEGER .1.3.6.1.4.1.5040.1.2.9.3.1.2.3.3 |
wtWebGraphThermHygroClockMonthDate: Month, taking into account the time zone settings.rw Enumeration .1.3.6.1.4.1.5040.1.2.9.3.1.2.3.4 |
wtWebGraphThermHygroClockYearDate: Year, taking into account the time zone settings.rw INTEGER .1.3.6.1.4.1.5040.1.2.9.3.1.2.3.5 |
wtWebGraphThermHygroBasic OBJECT IDENTIFIER .1.3.6.1.4.1.5040.1.2.9.3.1.3 |
wtWebGraphThermHygroNetwork OBJECT IDENTIFIER .1.3.6.1.4.1.5040.1.2.9.3.1.3.1 |
wtWebGraphThermHygroIpAddressIP address of the Webiorw IpAddress .1.3.6.1.4.1.5040.1.2.9.3.1.3.1.1 |
wtWebGraphThermHygroSubnetMaskSubnet mask of the Webiorw IpAddress .1.3.6.1.4.1.5040.1.2.9.3.1.3.1.2 |
wtWebGraphThermHygroGatewayGateway of the Webiorw IpAddress .1.3.6.1.4.1.5040.1.2.9.3.1.3.1.3 |
wtWebGraphThermHygroDnsServer1IP address of the 1st DNS server in ASCIIrw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.3.1.3.1.4 |
wtWebGraphThermHygroDnsServer2IP address of the 2nd DNS server in ASCIIrw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.3.1.3.1.5 |
wtWebGraphThermHygroAddConfigAdditional configuration (1=ON):
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 0: BOOTP disablerw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.3.1.3.1.6 |
wtWebGraphThermHygroHTTP OBJECT IDENTIFIER .1.3.6.1.4.1.5040.1.2.9.3.1.3.2 |
wtWebGraphThermHygroStartupBinary coded start page:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 1: Index.htm
Bit 2: Home.htm
Bit 3: User.htm
Only one page may be selected at a time.rw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.3.1.3.2.1 |
wtWebGraphThermHygroGetHeaderEnableIf this bit is set, every answer of a short form GET question will be lead
by the IP-address and name of the device:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 1-7: unused
Bit 0 : GET Header enablerw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.3.1.3.2.2 |
wtWebGraphThermHygroHttpPortDefinition of the standard HTML port (Default: 80).rw INTEGER .1.3.6.1.4.1.5040.1.2.9.3.1.3.2.3 |
wtWebGraphThermHygroMail OBJECT IDENTIFIER .1.3.6.1.4.1.5040.1.2.9.3.1.3.3 |
wtWebGraphThermHygroMailAdNameDevice name for mail administration.rw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.3.1.3.3.1 |
wtWebGraphThermHygroMailReplyReply address for the mail server.rw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.3.1.3.3.2 |
wtWebGraphThermHygroMailServerName or IP address of the mail server.rw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.3.1.3.3.3 |
wtWebioAn1MailEnableSet this bit to enable the sending of mails:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 1-7: unused
Bit 0 : Mail enablerw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.3.1.3.3.4 |
wtWebGraphThermHygroMailAuthenticationSelection of the authentication modi:
The OCTETS are interpreted bit-by-bit, with each bit corresponding to an output.
Bit 0 corresponds to the LSB.
OCTET 1: unused
OCTET 2: unused
OCTET 3: unused
OCTET 4: Bit 3-7: unused
Bit 2 : POP3 before SMTP
Bit 1 : ESMTP, authentication
Bit 0 : SMTP, no authenticationrw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.3.1.3.3.5 |
wtWebGraphThermHygroMailAuthUserName of the user to be authenticated.rw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.3.1.3.3.6 |
wtWebGraphThermHygroMailAuthPasswordAuthentication password.rw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.3.1.3.3.7 |
wtWebGraphThermHygroMailPop3ServerName or Ip-address of the POP3 Servers.rw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.3.1.3.3.8 |
wtWebGraphThermHygroSNMP OBJECT IDENTIFIER .1.3.6.1.4.1.5040.1.2.9.3.1.3.4 |
wtWebGraphThermHygroSnmpCommunityStringReadCommunity string read onlyrw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.3.1.3.4.1 |
wtWebGraphThermHygroSnmpCommunityStringReadWriteCommunity string read / writerw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.3.1.3.4.2 |
wtWebGraphThermHygroSystemTrapManagerIPName or IP address of the TCP server which accepts the system trap.rw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.3.1.3.4.3 |
wtWebGraphThermHygroSystemTrapEnableBinary coded trigger conditions:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 0: ColdStart
Bit 1: WarmStart
Bit 2-7: unusedrw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.3.1.3.4.4 |
wtWebGraphThermHygroSnmpEnableSet bit 0 to enable SNMP.
If disabled, the device did not respond to any SNMP requests.
Bit 1 decided wether the community string of read operations
is compared with the system password or not:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 1-7: unused
Bit 0 : SNMP enablerw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.3.1.3.4.5 |
wtWebGraphThermHygroSnmpCommunityStringTrapCommunity string send within traps.rw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.3.1.3.4.6 |
wtWebGraphThermHygroUDP OBJECT IDENTIFIER .1.3.6.1.4.1.5040.1.2.9.3.1.3.5 |
wtWebGraphThermHygroUdpPortUdp port to which the Udp queries ( short form GET requests) can be sent. This
port number must be unique within the device.rw INTEGER .1.3.6.1.4.1.5040.1.2.9.3.1.3.5.1 |
wtWebGraphThermHygroUdpEnableSet this bit to enable UDP support:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 1-7: unused
Bit 0 : UDP enablerw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.3.1.3.5.2 |
wtWebGraphThermHygroSyslog OBJECT IDENTIFIER .1.3.6.1.4.1.5040.1.2.9.3.1.3.6 |
wtWebGraphThermHygroSyslogServerIPName or IP address of the Syslog server, which accepts the Syslog messgaes.rw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.3.1.3.6.1 |
wtWebGraphThermHygroSyslogServerPortPortnumber of the Syslog servers, default 514.rw INTEGER .1.3.6.1.4.1.5040.1.2.9.3.1.3.6.2 |
wtWebGraphThermHygroSyslogSystemMessagesEnableBinary coded trigger conditions:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 0: ColdStart
Bit 1: WarmStart
Bit 2: Diag Messages
Bit 3-7: unusedrw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.3.1.3.6.3 |
wtWebGraphThermHygroSyslogEnableSet bit 0to enable Syslog:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 1-7: unused
Bit 0 : Syslog enablerw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.3.1.3.6.4 |
wtWebGraphThermHygroFTP OBJECT IDENTIFIER .1.3.6.1.4.1.5040.1.2.9.3.1.3.7 |
wtWebGraphThermHygroFTPServerIPName or IP address of the FTP server, which accepts the FTP messages.rw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.3.1.3.7.1 |
wtWebGraphThermHygroFTPServerControlPortPortnumber of the control port of the FTP server, default 21.rw INTEGER .1.3.6.1.4.1.5040.1.2.9.3.1.3.7.2 |
wtWebGraphThermHygroFTPUserNameFTP Loggin: user name.rw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.3.1.3.7.3 |
wtWebGraphThermHygroFTPPasswordFTP Loggin: user password.rw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.3.1.3.7.4 |
wtWebGraphThermHygroFTPAccountFTP Loggin: name of account.rw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.3.1.3.7.5 |
wtWebGraphThermHygroFTPOptionBit 0 switches the FTP Server in Passiv-Mode,
the Client controls the data connection on its own:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 1-7: unused
Bit 0 : PASV enablerw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.3.1.3.7.6 |
wtWebGraphThermHygroFTPEnableSet Bit 0 to enable FTP:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 1-7: unused
Bit 0 : FTP enablerw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.3.1.3.7.7 |
wtWebGraphThermHygroDatalogger OBJECT IDENTIFIER .1.3.6.1.4.1.5040.1.2.9.3.1.4 |
wtWebGraphThermHygroLoggerTimebaseTime base of the data loggerrw Enumeration .1.3.6.1.4.1.5040.1.2.9.3.1.4.1 |
wtWebGraphThermHygroLoggerSensorSelBinary coded trigger conditions:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 0: Sensor 1
Bit 1: Sensor 2
Bit 2-7: unusedrw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.3.1.4.2 |
wtWebGraphThermHygroDisplaySensorSelBinary coded sensor selection:
only selected sensors will be shown in the graphical presentation:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 0: Sensor 1
Bit 1: Sensor 2
Bit 2-7: unusedrw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.3.1.4.3 |
wtWebGraphThermHygroSensorColorTableList of sensor colors for the praphical presentation. SEQUENCE OF WtWebGraphThermHygroSensorColorEntry .1.3.6.1.4.1.5040.1.2.9.3.1.4.4 |
wtWebGraphThermHygroSensorColorEntryIndex numbers of the sensors. WtWebGraphThermHygroSensorColorEntry .1.3.6.1.4.1.5040.1.2.9.3.1.4.4.1 |
wtWebGraphThermHygroSensorColorColor of the sensors at the praphical presention.rw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.3.1.4.4.1.1 |
wtWebGraphThermHygroAutoScaleEnableIf bit 0 is set, vertical auto scale is enabled:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 1-7: unused
Bit 0 : Auto Scale enablerw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.3.1.4.5 |
wtWebGraphThermHygroVerticalUpperLimitThis value defines the maximum temperature shown in the graphical presentation,
if no auto scaling is selected.
Temperature in degrees with maximum 2 decimal places.rw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.3.1.4.6 |
wtWebGraphThermHygroVerticalLowerLimitThis value defines the minimum temperature shown in the graphical presentation,
if no auto scaling is selected.
Temperature in degrees with maximum 2 decimal places.rw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.3.1.4.7 |
wtWebGraphThermHygroHorizontalZoomDefines the default zoom stage, if no auto scaling is selected.rw Enumeration .1.3.6.1.4.1.5040.1.2.9.3.1.4.8 |
wtWebGraphThermHygroAlarm OBJECT IDENTIFIER .1.3.6.1.4.1.5040.1.2.9.3.1.5 |
wtWebGraphThermHygroAlarmCountNumber of independent alarms.ro INTEGER .1.3.6.1.4.1.5040.1.2.9.3.1.5.1 |
wtWebGraphThermHygroAlarmIfTableList of alarm indices. SEQUENCE OF WtWebGraphThermHygroAlarmIfEntry .1.3.6.1.4.1.5040.1.2.9.3.1.5.2 |
wtWebGraphThermHygroAlarmIfEntryNumbers of the alarms. WtWebGraphThermHygroAlarmIfEntry .1.3.6.1.4.1.5040.1.2.9.3.1.5.2.1 |
wtWebGraphThermHygroAlarmNoAlarm number.ro INTEGER .1.3.6.1.4.1.5040.1.2.9.3.1.5.2.1.1 |
wtWebGraphThermHygroAlarmTableList of settings depending on the alarm number. SEQUENCE OF WtWebGraphThermHygroAlarmEntry .1.3.6.1.4.1.5040.1.2.9.3.1.5.3 |
wtWebGraphThermHygroAlarmEntryAlarm parameters of the individual alarms. WtWebGraphThermHygroAlarmEntry .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1 |
wtWebGraphThermHygroAlarmTriggerBinary coded trigger conditions:
Octet 1: unused
Octet 2: unused
Octet 3:
Bit 0: Timer
Bit 1: ColdStart
Bit 2: WarmStart
Octet 4:
Bit 0: Sensor 1
Bit 1: Sensor 2
Bit 2-7: unusedrw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.1 |
wtWebGraphThermHygroAlarmMinMinimum temperature in degrees with maximum 2 decimal places.rw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.2 |
wtWebGraphThermHygroAlarmMaxMaximum temperature in degrees with maximum 2 decimal places.rw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.3 |
wtWebGraphThermHygroAlarmHysteresisTemperature changes of this size clears the alarm state (MAX-hyst, MIN+hyst.)
, in degrees with maximum 2 decimal places.rw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.4 |
wtWebGraphThermHygroAlarmDelayAlarm will be delayed by setting this time while stable alarm
condition occur (time in minutes).rw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.5 |
wtWebGraphThermHygroAlarmIntervalSend interval for alarm messages.rw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.6 |
wtWebGraphThermHygroAlarmEnableBinary coded alarm enable:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 0: Mail Enable
Bit 1: SNMP Trap enable
Bit 2: TCP Client enablerw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.7 |
wtWebGraphThermHygroAlarmEMailAddrE-Mail address for sending the alarm mail to.rw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.8 |
wtWebGraphThermHygroAlarmMailSubjectSubject line for alarm mail.rw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.9 |
wtWebGraphThermHygroAlarmMailTextAlarm mail text: <Tn> provides the current temperature; n = 1..8.
<Z> provides the current time.rw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.10 |
wtWebGraphThermHygroAlarmManagerIPName or IP address of the SNMP Manager which accepts the trap.rw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.11 |
wtWebGraphThermHygroAlarmTrapTextThis text is sent in the trap body.rw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.12 |
wtWebGraphThermHygroAlarmMailOptionsBinary coded options:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 0 : Attach Thermo.csv Enable
Bit 1 : CSV-Data_since_last_report
Bit 2-7: unusedrw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.13 |
wtWebGraphThermHygroAlarmTcpIpAddrName or IP address of the TCP server which accepts the trap.rw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.14 |
wtWebGraphThermHygroAlarmTcpPortPort number of the TCP server which accepts the trap.rw INTEGER .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.15 |
wtWebGraphThermHygroAlarmTcpTextThis text is sent in the TCP trap body.rw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.16 |
wtWebGraphThermHygroAlarmClearMailSubjectSubject line for alarm clear mail.rw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.17 |
wtWebGraphThermHygroAlarmClearMailTextAlarm clear mail text: <Tn> provides the current temperature; n = 1..8.
<Z> provides the current time.rw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.18 |
wtWebGraphThermHygroAlarmClearTrapTextThis text is sent in the trap body.rw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.19 |
wtWebGraphThermHygroAlarmClearTcpTextThis text is sent in the TCP trap body.rw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.20 |
wtWebGraphThermHygroAlarmDeltaTempMaximum rate of change degrees/min with maximum 2 decimal places.
Compared with the average of a period of 5 minutes.rw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.21 |
wtWebGraphThermHygroAlarmRHMinMinimum rel. Humidity in percent with maximum 2 decimal places.rw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.22 |
wtWebGraphThermHygroAlarmRHMaxMaximum rel.Humidity in percent with maximum 2 decimal places.rw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.23 |
wtWebGraphThermHygroAlarmRHHysteresisHysterese rel. Humidity in percent with maximum 2 decimal places.rw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.24 |
wtWebGraphThermHygroAlarmAHMinMinimum abs. Humidity in g/(m*m*m) with maximum 2 decimal places.rw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.25 |
wtWebGraphThermHygroAlarmAHMaxMaximum abs. Humidity in g/(m*m*m) with maximum 2 decimal places.rw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.26 |
wtWebGraphThermHygroAlarmSyslogIpAddrIP address of the syslog server to which the Webio device should send syslog messages.rw IpAddress .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.27 |
wtWebGraphThermHygroAlarmSyslogPortPort number of the syslog server to which the Webio device should send syslog messages.rw INTEGER .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.28 |
wtWebGraphThermHygroAlarmSyslogTextEvery message starts with the priority key, a time stamp and the host ip address, according RFC3164.
This text appears in the following syslog message body.rw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.29 |
wtWebGraphThermHygroAlarmSyslogClearTextEvery message starts with the priority key, a time stamp and the host ip address, according RFC3164.
This text appears in the following syslog message body.rw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.30 |
wtWebGraphThermHygroAlarmFtpDataPortLocal data port: 1..65535 or AUTO: the next free port will be assigned.rw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.31 |
wtWebGraphThermHygroAlarmFtpFileNameName of the file including path informations.rw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.32 |
wtWebGraphThermHygroAlarmFtpTextMessage text to store on the FTP server.rw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.33 |
wtWebGraphThermHygroAlarmFtpClearTextAlarm clear message to store on the FTP server.rw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.34 |
wtWebGraphThermHygroAlarmFtpOptionsBinary coded options, select only one option at the same time:
STORE = replace file
APPEND = append message at the end of the file
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 0 : STORE
Bit 1 : APPEND
Bit 2-7: unusedrw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.35 |
wtWebGraphThermHygroAlarmTimerCronThis entry contains 5 space or tab seperated text fields for time trigger definition.
Each field must match with the actual time to trigger a message, weekday and day of month
are interpreted separatley.
1: Minutes Range 0-59
2. Hours Range 0-23, 0 is midnight
3: Day of month Range 1-31
4: Month Range 1-12
5: Weekday Range 0-6, 0 is sunday
Syntax for every field:
- an asterix (*) enables every possible setting of a field
- single numbers seperated by commas
- a partition within the allowed range (1-5)
- step size within an partition of the allowed range (0-59/2: every second minute).rw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.36 |
wtWebGraphThermHygroPorts OBJECT IDENTIFIER .1.3.6.1.4.1.5040.1.2.9.3.2 |
wtWebGraphThermHygroPortTableList of settings depending on the sensor number. SEQUENCE OF WtWebGraphThermHygroPortEntry .1.3.6.1.4.1.5040.1.2.9.3.2.1 |
wtWebGraphThermHygroPortEntrySensor parameters for the individual sensors. WtWebGraphThermHygroPortEntry .1.3.6.1.4.1.5040.1.2.9.3.2.1.1 |
wtWebGraphThermHygroPortNameName of the sensor.rw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.3.2.1.1.1 |
wtWebGraphThermHygroPortTextDescription of the sensor.rw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.3.2.1.1.2 |
wtWebGraphThermHygroPortOffset1Offset calibration: Offset in degrees with maximum 2 decimal places at temperature 1.rw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.3.2.1.1.3 |
wtWebGraphThermHygroPortTemperature1Offset calibration: Reference temperature 1 in degrees with maximum 2 decimal places.rw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.3.2.1.1.4 |
wtWebGraphThermHygroPortOffset2Offset calibration: Offset in degrees with maximum 2 decimal places at temperature 2.rw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.3.2.1.1.5 |
wtWebGraphThermHygroPortTemperature2Offset calibration: Reference temperature 1 in degrees with maximum 2 decimal places.rw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.3.2.1.1.6 |
wtWebGraphThermHygroPortCommentOffset calibration: informations of date, name of operator, reference devices.rw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.3.2.1.1.7 |
wtWebGraphThermHygroPortSensorSelectBinary coded options for sensor 1:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 0 : PT100
Bit 1 : PT1000 (default)
Bit 2-7: unused
Binary coded options for sensor 2:
Octet 1: unused
Octet 2: unused
Octet 3: unused
Octet 4:
Bit 0 : W&T Sensor rel. humidity (default)
Bit 1 : Skalar 0-2.5V
Bit 2 : Disconnect
Bit 3-7: unusedrw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.3.2.1.1.8 |
wtWebGraphThermHygroManufact OBJECT IDENTIFIER .1.3.6.1.4.1.5040.1.2.9.3.3 |
wtWebGraphThermHygroMfNameManufacturer company namerw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.3.3.1 |
wtWebGraphThermHygroMfAddrManufacturer address.rw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.3.3.2 |
wtWebGraphThermHygroMfHotlineManufacturer hotline.rw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.3.3.3 |
wtWebGraphThermHygroMfInternetManufacturer Internet address.rw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.3.3.4 |
wtWebGraphThermHygroMfDeviceTypManufacturer device name (model number).rw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.3.3.5 |
wtWebGraphThermHygroMfOrderNoManufacturer part number.rw OCTET STRING .1.3.6.1.4.1.5040.1.2.9.3.3.6 |
wtWebGraphThermHygroDiag OBJECT IDENTIFIER .1.3.6.1.4.1.5040.1.2.9.4 |
wtWebGraphThermHygroDiagErrorCountNumber of entries in the error memory.ro INTEGER .1.3.6.1.4.1.5040.1.2.9.4.1 |
wtWebGraphThermHygroDiagBinaryErrorError causes coded bit-by-bit.ro OCTET STRING .1.3.6.1.4.1.5040.1.2.9.4.2 |
wtWebGraphThermHygroDiagErrorIndexThe value of this variable is used as an index to read
an error massege from wtWebGraphThermHygroDiagErrorMessage.
Errors are numbered from 1 to wtWebGraphThermHygroDiagErrorCount.
Writing a valid value into this variable, making the appropriate
message readable from wtWebGraphThermHygroDiagErrorMessage.rw INTEGER .1.3.6.1.4.1.5040.1.2.9.4.3 |
wtWebGraphThermHygroDiagErrorMessageUsing wtWebGraphThermHygroDiagErrorIndex as an index, the appropriate message is available.ro OCTET STRING .1.3.6.1.4.1.5040.1.2.9.4.4 |
wtWebGraphThermHygroDiagErrorClearWriting 1 into this variable clears all diagnosis messages.rw INTEGER .1.3.6.1.4.1.5040.1.2.9.4.5 |