Home/Catalog/WebGraph-Thermo-Hygro-Barometer-US-MIB

WebGraph-Thermo-Hygro-Barometer-US-MIB

AI MIB Summary

Standard SNMP MIB module defining data structures for WebGraph-Thermo-Hygro-Barometer-US-MIB.

237
Objects
Active
Status
4
Dependencies

Imported Objects

Objects

237 total
Object Name
wut
OBJECT IDENTIFIER
.1.3.6.1.4.1.5040
IMPORTS
Unknown
.1.3.6.1.4.1.5040
wtComServer
OBJECT IDENTIFIER
.1.3.6.1.4.1.5040.1
wtWebio
OBJECT IDENTIFIER
.1.3.6.1.4.1.5040.1.2
wtWebGraphThermoBaro
OBJECT IDENTIFIER
.1.3.6.1.4.1.5040.1.2.37
wtWebGraphThermoBaroAlert1This SNMP trap is generated when Alarm 1 was triggered, SNMP trap enable is set and SNMP is enabled.
TRAP-TYPE
.1.3.6.1.4.1.5040.1.2.37.0.31
wtWebGraphThermoBaroAlert2This SNMP trap is generated when Alarm 2 was triggered, SNMP trap enable is set and SNMP is enabled.
TRAP-TYPE
.1.3.6.1.4.1.5040.1.2.37.0.32
wtWebGraphThermoBaroAlert3This SNMP trap is generated when Alarm 3 was triggered, SNMP trap enable is set and SNMP is enabled.
TRAP-TYPE
.1.3.6.1.4.1.5040.1.2.37.0.33
wtWebGraphThermoBaroAlert4This SNMP trap is generated when Alarm 4 was triggered, SNMP trap enable is set and SNMP is enabled.
TRAP-TYPE
.1.3.6.1.4.1.5040.1.2.37.0.34
wtWebGraphThermoBaroAlert5This SNMP trap is generated when Alarm 5 was triggered, SNMP trap enable is set and SNMP is enabled.
TRAP-TYPE
.1.3.6.1.4.1.5040.1.2.37.0.35
wtWebGraphThermoBaroAlert6This SNMP trap is generated when Alarm 6 was triggered, SNMP trap enable is set and SNMP is enabled.
TRAP-TYPE
.1.3.6.1.4.1.5040.1.2.37.0.36
wtWebGraphThermoBaroAlert7This SNMP trap is generated when Alarm 7 was triggered, SNMP trap enable is set and SNMP is enabled.
TRAP-TYPE
.1.3.6.1.4.1.5040.1.2.37.0.37
wtWebGraphThermoBaroAlert8This SNMP trap is generated when Alarm 8 was triggered, SNMP trap enable is set and SNMP is enabled.
TRAP-TYPE
.1.3.6.1.4.1.5040.1.2.37.0.38
wtWebGraphThermoBaroAlert9This SNMP trap is generated when Alarm 1 was cleared, SNMP trap enable is set and SNMP is enabled.
TRAP-TYPE
.1.3.6.1.4.1.5040.1.2.37.0.91
wtWebGraphThermoBaroAlert10This SNMP trap is generated when Alarm 2 was cleared, SNMP trap enable is set and SNMP is enabled.
TRAP-TYPE
.1.3.6.1.4.1.5040.1.2.37.0.92
wtWebGraphThermoBaroAlert11This SNMP trap is generated when Alarm 3 was cleared, SNMP trap enable is set and SNMP is enabled.
TRAP-TYPE
.1.3.6.1.4.1.5040.1.2.37.0.93
wtWebGraphThermoBaroAlert12This SNMP trap is generated when Alarm 4 was cleared, SNMP trap enable is set and SNMP is enabled.
TRAP-TYPE
.1.3.6.1.4.1.5040.1.2.37.0.94
wtWebGraphThermoBaroAlert13This SNMP trap is generated when Alarm 5 was cleared, SNMP trap enable is set and SNMP is enabled.
TRAP-TYPE
.1.3.6.1.4.1.5040.1.2.37.0.95
wtWebGraphThermoBaroAlert14This SNMP trap is generated when Alarm 6 was cleared, SNMP trap enable is set and SNMP is enabled.
TRAP-TYPE
.1.3.6.1.4.1.5040.1.2.37.0.96
wtWebGraphThermoBaroAlert15This SNMP trap is generated when Alarm 7 was cleared, SNMP trap enable is set and SNMP is enabled.
TRAP-TYPE
.1.3.6.1.4.1.5040.1.2.37.0.97
wtWebGraphThermoBaroAlert16This SNMP trap is generated when Alarm 8 was cleared, SNMP trap enable is set and SNMP is enabled.
TRAP-TYPE
.1.3.6.1.4.1.5040.1.2.37.0.98
wtWebGraphThermoBaroAlertDiagThis SNMP trap is generated when a diagnosis/error message was triggered, SNMP trap enable is set and SNMP is enabled.
TRAP-TYPE
.1.3.6.1.4.1.5040.1.2.37.0.110
wtWebGraphThermoBaroTemp
OBJECT IDENTIFIER
.1.3.6.1.4.1.5040.1.2.37.1
wtWebGraphThermoBaroSensorsNumber of sensorsro
INTEGER
.1.3.6.1.4.1.5040.1.2.37.1.1
wtWebGraphThermoBaroSensorTableList of sensors.
SEQUENCE OF WtWebGraphThermoBaroSensorEntry
.1.3.6.1.4.1.5040.1.2.37.1.2
wtWebGraphThermoBaroSensorEntryList of sensor numbers.
WtWebGraphThermoBaroSensorEntry
.1.3.6.1.4.1.5040.1.2.37.1.2.1
wtWebGraphThermoBaroSensorNoSensor number.ro
INTEGER
.1.3.6.1.4.1.5040.1.2.37.1.2.1.1
wtWebGraphThermoBaroTempValueTableList of measurement values corresponding to the channel numbers.
SEQUENCE OF WtWebGraphThermoBaroTempValueEntry
.1.3.6.1.4.1.5040.1.2.37.1.3
wtWebGraphThermoBaroTempValueEntryMeasurement values of the sensors.
WtWebGraphThermoBaroTempValueEntry
.1.3.6.1.4.1.5040.1.2.37.1.3.1
wtWebGraphThermoBaroTempValueMeasurement value of the sensor, ASCII, 5 characters in length.ro
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.1.3.1.1
wtWebGraphThermoBaroBinaryTempValueTableList of binary measurement values corresponding to the channel numbers.
SEQUENCE OF WtWebGraphThermoBaroBinaryTempValueEntry
.1.3.6.1.4.1.5040.1.2.37.1.4
wtWebGraphThermoBaroBinaryTempValueEntryBinary measurement values of the sensors.
WtWebGraphThermoBaroBinaryTempValueEntry
.1.3.6.1.4.1.5040.1.2.37.1.4.1
wtWebGraphThermoBaroBinaryTempValueBinary measurement value of the sensor in 1/10 degrees Celsius or 1/10 per cent, signed number, 0x4FFF6 indicates an invalid measured value.ro
INTEGER
.1.3.6.1.4.1.5040.1.2.37.1.4.1.1
wtWebGraphThermoBaroTempValuePktTableList of measurement values corresponding to the channel numbers.
SEQUENCE OF WtWebGraphThermoBaroTempValuePktEntry
.1.3.6.1.4.1.5040.1.2.37.1.8
wtWebGraphThermoBaroTempValuePktEntryMeasurement values of the sensors.
WtWebGraphThermoBaroTempValuePktEntry
.1.3.6.1.4.1.5040.1.2.37.1.8.1
wtWebGraphThermoBaroTempValuePktMeasurement value of the sensor, ASCII, 5 characters in length, delimeter is decimal point.ro
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.1.8.1.1
wtWebGraphThermoBaroSessCntrl
OBJECT IDENTIFIER
.1.3.6.1.4.1.5040.1.2.37.2
wtWebGraphThermoBaroSessCntrlPasswordEntering this password opens a session which is ended by writing a 1 to wtWebGraphThermoBaroSessCntrlLogout. When read this variable provides a string of length zero.rw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.2.1
wtWebGraphThermoBaroSessCntrlConfigModeWhen the device is in SNMP configuration mode, the value 1 is returned, otherwise 0. If the read value is 0 even though the password was written, the device is already in config mode and the variables can only be read.ro
Enumeration
.1.3.6.1.4.1.5040.1.2.37.2.2
wtWebGraphThermoBaroSessCntrlLogoutIf the device is in configuration mode and the session was opened by this SNMP Manager, writing a 1 to this variable will end the session and all parameters are stored. Writing a 2 discards all entries again. When read this variable provides the value 0.rw
INTEGER
.1.3.6.1.4.1.5040.1.2.37.2.3
wtWebGraphThermoBaroSessCntrlAdminPasswordThis password protects access to the variables with administrator rights. It can only be changed by the administrator. If no password was assigned, the valid password is public.rw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.2.4
wtWebGraphThermoBaroSessCntrlConfigPasswordThis password protects access to the variables with configurator rights. It can be changed by the administrator and by the configurator. If no password was assigned, the valid password is public. When read this variable provides a null-pointer.rw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.2.5
wtWebGraphThermoBaroConfig
OBJECT IDENTIFIER
.1.3.6.1.4.1.5040.1.2.37.3
wtWebGraphThermoBaroDevice
OBJECT IDENTIFIER
.1.3.6.1.4.1.5040.1.2.37.3.1
wtWebGraphThermoBaroText
OBJECT IDENTIFIER
.1.3.6.1.4.1.5040.1.2.37.3.1.1
wtWebGraphThermoBaroDeviceNameName of the Webio, which is user definable.rw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.1.1
wtWebGraphThermoBaroDeviceTextDescription of the Webio, which is user definable.rw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.1.2
wtWebGraphThermoBaroDeviceLocationDescription of the location of the Webio, which is user definable.rw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.1.3
wtWebGraphThermoBaroDeviceContactContact address of the system operator of the Webio, which is user definable.rw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.1.4
wtWebGraphThermoBaroTimeDate
OBJECT IDENTIFIER
.1.3.6.1.4.1.5040.1.2.37.3.1.2
wtWebGraphThermoBaroTimeZone
OBJECT IDENTIFIER
.1.3.6.1.4.1.5040.1.2.37.3.1.2.1
wtWebGraphThermoBaroTzOffsetHrsOffset hours for the time zone (winter time) with respect to UTC.rw
INTEGER
.1.3.6.1.4.1.5040.1.2.37.3.1.2.1.1
wtWebGraphThermoBaroTzOffsetMinOffset minutes for the time zone (winter time) with respect to UTC.rw
INTEGER
.1.3.6.1.4.1.5040.1.2.37.3.1.2.1.2
wtWebGraphThermoBaroTzEnableBinary coded conditions: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 1-7: unused Bit 0 : Apply Timezonerw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.2.1.3
wtWebGraphThermoBaroStTzOffsetHrsOffset hours of the time zone (summer time) with respect to UTC.rw
INTEGER
.1.3.6.1.4.1.5040.1.2.37.3.1.2.1.4
wtWebGraphThermoBaroStTzOffsetMinOffset minutes of the time zone (summer time) with respect to UTC.rw
INTEGER
.1.3.6.1.4.1.5040.1.2.37.3.1.2.1.5
wtWebGraphThermoBaroStTzEnableBinary coded conditions: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 1-7: unused Bit 0 : Apply Summertimerw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.2.1.6
wtWebGraphThermoBaroStTzStartMonthMonth in which the change is made from winter time to summer time.rw
Enumeration
.1.3.6.1.4.1.5040.1.2.37.3.1.2.1.7
wtWebGraphThermoBaroStTzStartModeMode of the day of the week for which the change is made from winter time to summer time.rw
Enumeration
.1.3.6.1.4.1.5040.1.2.37.3.1.2.1.8
wtWebGraphThermoBaroStTzStartWdayDay of the week on which the change is made from winter time to summer timerw
Enumeration
.1.3.6.1.4.1.5040.1.2.37.3.1.2.1.9
wtWebGraphThermoBaroStTzStartHrsHour in which the time zone is changed from winter to summer time with respect to UTC.rw
INTEGER
.1.3.6.1.4.1.5040.1.2.37.3.1.2.1.10
wtWebGraphThermoBaroStTzStartMinMinute in which the time zone is changed from winter to summer time with respect to UTC.rw
INTEGER
.1.3.6.1.4.1.5040.1.2.37.3.1.2.1.11
wtWebGraphThermoBaroStTzStopMonthMonth in which the change is made from summer time to winter time.rw
Enumeration
.1.3.6.1.4.1.5040.1.2.37.3.1.2.1.12
wtWebGraphThermoBaroStTzStopModeMode of the week day on which the change is made from summer time to winter time.rw
Enumeration
.1.3.6.1.4.1.5040.1.2.37.3.1.2.1.13
wtWebGraphThermoBaroStTzStopWdayDay of the week on which the change is made from summer time to winter time.rw
Enumeration
.1.3.6.1.4.1.5040.1.2.37.3.1.2.1.14
wtWebGraphThermoBaroStTzStopHrsHour at which the time zone is changed from summer to winter time with respect to UTC.rw
INTEGER
.1.3.6.1.4.1.5040.1.2.37.3.1.2.1.15
wtWebGraphThermoBaroStTzStopMinMinute at which the time zone is changed from summer to winter time with respect to UTC.rw
INTEGER
.1.3.6.1.4.1.5040.1.2.37.3.1.2.1.16
wtWebGraphThermoBaroTimeServer
OBJECT IDENTIFIER
.1.3.6.1.4.1.5040.1.2.37.3.1.2.2
wtWebGraphThermoBaroTimeServer1IP address or name of the 1st time server in ASCIIrw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.2.2.1
wtWebGraphThermoBaroTimeServer2IP address or name of the 2nd time server in ASCIIrw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.2.2.2
wtWebGraphThermoBaroTsEnableBinary coded conditions: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 1-7: unused Bit 0 : Apply Time Serverrw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.2.2.3
wtWebGraphThermoBaroTsSyncTimeDaily synchronisation time with the time server (hour: 0-23).rw
INTEGER
.1.3.6.1.4.1.5040.1.2.37.3.1.2.2.4
wtWebGraphThermoBaroDeviceClock
OBJECT IDENTIFIER
.1.3.6.1.4.1.5040.1.2.37.3.1.2.3
wtWebGraphThermoBaroClockHrsClock hours taking into account the time zone settings.rw
INTEGER
.1.3.6.1.4.1.5040.1.2.37.3.1.2.3.1
wtWebGraphThermoBaroClockMinClock minutes taking into account the time zone settings.rw
INTEGER
.1.3.6.1.4.1.5040.1.2.37.3.1.2.3.2
wtWebGraphThermoBaroClockDayDate: Day of the month, taking into account the time zone settings.rw
INTEGER
.1.3.6.1.4.1.5040.1.2.37.3.1.2.3.3
wtWebGraphThermoBaroClockMonthDate: Month, taking into account the time zone settings.rw
Enumeration
.1.3.6.1.4.1.5040.1.2.37.3.1.2.3.4
wtWebGraphThermoBaroClockYearDate: Year, taking into account the time zone settings.rw
INTEGER
.1.3.6.1.4.1.5040.1.2.37.3.1.2.3.5
wtWebGraphThermoBaroBasic
OBJECT IDENTIFIER
.1.3.6.1.4.1.5040.1.2.37.3.1.3
wtWebGraphThermoBaroNetwork
OBJECT IDENTIFIER
.1.3.6.1.4.1.5040.1.2.37.3.1.3.1
wtWebGraphThermoBaroIpAddressIP address of the Webiorw
IpAddress
.1.3.6.1.4.1.5040.1.2.37.3.1.3.1.1
wtWebGraphThermoBaroSubnetMaskSubnet mask of the Webiorw
IpAddress
.1.3.6.1.4.1.5040.1.2.37.3.1.3.1.2
wtWebGraphThermoBaroGatewayGateway of the Webiorw
IpAddress
.1.3.6.1.4.1.5040.1.2.37.3.1.3.1.3
wtWebGraphThermoBaroDnsServer1IP address of the 1st DNS server in ASCIIrw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.3.1.4
wtWebGraphThermoBaroDnsServer2IP address of the 2nd DNS server in ASCIIrw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.3.1.5
wtWebGraphThermoBaroAddConfigAdditional configuration (1=ON): Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 1: DHCP disable Bit 0: BOOTP disablerw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.3.1.6
wtWebGraphThermoBaroHTTP
OBJECT IDENTIFIER
.1.3.6.1.4.1.5040.1.2.37.3.1.3.2
wtWebGraphThermoBaroStartupBinary coded start page: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 1: Index.htm Bit 2: Home.htm Bit 3: User.htm Only one page may be selected at a time.rw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.3.2.1
wtWebGraphThermoBaroGetHeaderEnableIf these bits are set, every answer of a short form GET question will be lead by the IP-address and name of the device and/or a HTTP header: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 1-6: unused Bit 1 : GET HTTP enable Bit 0 : GET Header enablerw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.3.2.2
wtWebGraphThermoBaroHttpPortDefinition of the standard HTML port (Default: 80).rw
INTEGER
.1.3.6.1.4.1.5040.1.2.37.3.1.3.2.3
wtWebGraphThermoBaroMail
OBJECT IDENTIFIER
.1.3.6.1.4.1.5040.1.2.37.3.1.3.3
wtWebGraphThermoBaroMailAdNameDevice name for mail administration.rw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.3.3.1
wtWebGraphThermoBaroMailReplyReply address for the mail server.rw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.3.3.2
wtWebGraphThermoBaroMailServerName or IP address of the mail server.rw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.3.3.3
wtWebioAn1MailEnableSet this bit to enable the sending of mails: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 1-7: unused Bit 0 : Mail enablerw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.3.3.4
wtWebGraphThermoBaroMailAuthenticationSelection of the authentication modi: The OCTETS are interpreted bit-by-bit, with each bit corresponding to an output. Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 3-7: unused Bit 2 : POP3 before SMTP Bit 1 : ESMTP, authentication Bit 0 : SMTP, no authenticationrw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.3.3.5
wtWebGraphThermoBaroMailAuthUserName of the user to be authenticated.rw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.3.3.6
wtWebGraphThermoBaroMailAuthPasswordAuthentication password.rw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.3.3.7
wtWebGraphThermoBaroMailPop3ServerName or Ip-address of the POP3 Servers.rw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.3.3.8
wtWebGraphThermoBaroSNMP
OBJECT IDENTIFIER
.1.3.6.1.4.1.5040.1.2.37.3.1.3.4
wtWebGraphThermoBaroSnmpCommunityStringReadCommunity string read onlyrw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.3.4.1
wtWebGraphThermoBaroSnmpCommunityStringReadWriteCommunity string read / writerw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.3.4.2
wtWebGraphThermoBaroSystemTrapManagerIPName or IP address of the TCP server which accepts the system trap.rw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.3.4.3
wtWebGraphThermoBaroSystemTrapEnableBinary coded trigger conditions: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0: ColdStart Bit 1: WarmStart Bit 2-7: unusedrw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.3.4.4
wtWebGraphThermoBaroSnmpEnableSet bit 0 to enable SNMP. If disabled, the device did not respond to any SNMP requests. Bit 1 decided wether the community string of read operations is compared with the system password or not: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 1-7: unused Bit 0 : SNMP enablerw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.3.4.5
wtWebGraphThermoBaroSnmpCommunityStringTrapCommunity string send within traps.rw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.3.4.6
wtWebGraphThermoBaroUDP
OBJECT IDENTIFIER
.1.3.6.1.4.1.5040.1.2.37.3.1.3.5
wtWebGraphThermoBaroUdpPortUdp port to which the Udp queries ( short form GET requests) can be sent. This port number must be unique within the device.rw
INTEGER
.1.3.6.1.4.1.5040.1.2.37.3.1.3.5.1
wtWebGraphThermoBaroUdpEnableSet this bit to enable UDP support: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 1-7: unused Bit 0 : UDP enablerw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.3.5.2
wtWebGraphThermoBaroSyslog
OBJECT IDENTIFIER
.1.3.6.1.4.1.5040.1.2.37.3.1.3.6
wtWebGraphThermoBaroSyslogServerIPName or IP address of the Syslog server, which accepts the Syslog messgaes.rw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.3.6.1
wtWebGraphThermoBaroSyslogServerPortPortnumber of the Syslog servers, default 514.rw
INTEGER
.1.3.6.1.4.1.5040.1.2.37.3.1.3.6.2
wtWebGraphThermoBaroSyslogSystemMessagesEnableBinary coded trigger conditions: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0: ColdStart Bit 1: WarmStart Bit 2: Diag Messages Bit 3-7: unusedrw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.3.6.3
wtWebGraphThermoBaroSyslogEnableSet bit 0to enable Syslog: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 1-7: unused Bit 0 : Syslog enablerw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.3.6.4
wtWebGraphThermoBaroFTP
OBJECT IDENTIFIER
.1.3.6.1.4.1.5040.1.2.37.3.1.3.7
wtWebGraphThermoBaroFTPServerIPName or IP address of the FTP server, which accepts the FTP messages.rw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.3.7.1
wtWebGraphThermoBaroFTPServerControlPortPortnumber of the control port of the FTP server, default 21.rw
INTEGER
.1.3.6.1.4.1.5040.1.2.37.3.1.3.7.2
wtWebGraphThermoBaroFTPUserNameFTP Loggin: user name.rw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.3.7.3
wtWebGraphThermoBaroFTPPasswordFTP Loggin: user password.rw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.3.7.4
wtWebGraphThermoBaroFTPAccountFTP Loggin: name of account.rw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.3.7.5
wtWebGraphThermoBaroFTPOptionBit 0 switches the FTP Server in Passiv-Mode, the Client controls the data connection on its own: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 1-7: unused Bit 0 : PASV enablerw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.3.7.6
wtWebGraphThermoBaroFTPEnableSet Bit 0 to enable FTP: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 1-7: unused Bit 0 : FTP enablerw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.3.7.7
wtWebGraphThermoBaroRSS
OBJECT IDENTIFIER
.1.3.6.1.4.1.5040.1.2.37.3.1.3.8
wtWebGraphThermoBaroRSSChannelTitleName of the RSS Feed.rw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.3.8.1
wtWebGraphThermoBaroRSSChannelDescriptionDescription of the RSS Feed.rw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.3.8.3
wtWebGraphThermoBaroRSSChannelImageLink of a picture, which will be shown at the headline of the output window.rw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.3.8.4
wtWebGraphThermoBaroRSSChannelImageTitleAlias Name of the picture.rw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.3.8.5
wtWebGraphThermoBaroRSSChannelItemTitleTitle of the RSS Feed.rw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.3.8.7
wtWebGraphThermoBaroRSSChannelItemDescriptionText of the RSS Feed.rw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.3.8.9
wtWebGraphThermoBaroRSSChannelItemQuantityNumber of lines.rw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.3.8.10
wtWebGraphThermoBaroLanguage
OBJECT IDENTIFIER
.1.3.6.1.4.1.5040.1.2.37.3.1.3.9
wtWebGraphThermoBaroLanguageSelectSprachauswahl: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 2-7: unused Bit 1 : englisch Bit 0 : germanrw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.3.9.1
wtWebGraphThermoBaroDatalogger
OBJECT IDENTIFIER
.1.3.6.1.4.1.5040.1.2.37.3.1.4
wtWebGraphThermoBaroLoggerTimebaseTime base of the data loggerrw
Enumeration
.1.3.6.1.4.1.5040.1.2.37.3.1.4.1
wtWebGraphThermoBaroLoggerSensorSelBinary coded trigger conditions: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0: Sensor 1 Bit 1: Sensor 2 Bit 2-7: unusedrw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.4.2
wtWebGraphThermoBaroAlarm
OBJECT IDENTIFIER
.1.3.6.1.4.1.5040.1.2.37.3.1.5
wtWebGraphThermoBaroAlarmCountNumber of independent alarms.ro
INTEGER
.1.3.6.1.4.1.5040.1.2.37.3.1.5.1
wtWebGraphThermoBaroAlarmIfTableList of alarm indices.
SEQUENCE OF WtWebGraphThermoBaroAlarmIfEntry
.1.3.6.1.4.1.5040.1.2.37.3.1.5.2
wtWebGraphThermoBaroAlarmIfEntryNumbers of the alarms.
WtWebGraphThermoBaroAlarmIfEntry
.1.3.6.1.4.1.5040.1.2.37.3.1.5.2.1
wtWebGraphThermoBaroAlarmNoAlarm number.ro
INTEGER
.1.3.6.1.4.1.5040.1.2.37.3.1.5.2.1.1
wtWebGraphThermoBaroAlarmTableList of settings depending on the alarm number.
SEQUENCE OF WtWebGraphThermoBaroAlarmEntry
.1.3.6.1.4.1.5040.1.2.37.3.1.5.3
wtWebGraphThermoBaroAlarmEntryAlarm parameters of the individual alarms.
WtWebGraphThermoBaroAlarmEntry
.1.3.6.1.4.1.5040.1.2.37.3.1.5.3.1
wtWebGraphThermoBaroAlarmTriggerBinary coded trigger conditions: Octet 1: unused Octet 2: unused Octet 3: Bit 0: Timer Bit 1: ColdStart Bit 2: WarmStart Octet 4: Bit 0: Sensor 1 Bit 1: Sensor 2 Bit 2-7: unusedrw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.5.3.1.1
wtWebGraphThermoBaroAlarmMinMinimum temperature in degrees with maximum 2 decimal places.rw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.5.3.1.2
wtWebGraphThermoBaroAlarmMaxMaximum temperature in degrees with maximum 2 decimal places.rw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.5.3.1.3
wtWebGraphThermoBaroAlarmHysteresisTemperature changes of this size clears the alarm state (MAX-hyst, MIN+hyst.) , in degrees with maximum 2 decimal places.rw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.5.3.1.4
wtWebGraphThermoBaroAlarmDelayAlarm will be delayed by setting this time while stable alarm condition occur (time in minutes).rw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.5.3.1.5
wtWebGraphThermoBaroAlarmIntervalSend interval for alarm messages.rw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.5.3.1.6
wtWebGraphThermoBaroAlarmEnableBinary coded alarm enable: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0: Mail Enable Bit 1: SNMP Trap enable Bit 2: TCP Client enable Bit 3: Syslog enable Bit 4: FTP enablerw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.5.3.1.7
wtWebGraphThermoBaroAlarmEMailAddrE-Mail address for sending the alarm mail to.rw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.5.3.1.8
wtWebGraphThermoBaroAlarmMailSubjectSubject line for alarm mail.rw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.5.3.1.9
wtWebGraphThermoBaroAlarmMailTextAlarm mail text: <Tn> provides the current temperature; n = 1..8. <Z> provides the current time.rw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.5.3.1.10
wtWebGraphThermoBaroAlarmManagerIPName or IP address of the SNMP Manager which accepts the trap.rw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.5.3.1.11
wtWebGraphThermoBaroAlarmTrapTextThis text is sent in the trap body.rw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.5.3.1.12
wtWebGraphThermoBaroAlarmMailOptionsBinary coded options: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0 : Attach Thermo.csv Enable Bit 1 : CSV-Data_since_last_report Bit 2-7: unusedrw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.5.3.1.13
wtWebGraphThermoBaroAlarmTcpIpAddrName or IP address of the TCP server which accepts the trap.rw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.5.3.1.14
wtWebGraphThermoBaroAlarmTcpPortPort number of the TCP server which accepts the trap.rw
INTEGER
.1.3.6.1.4.1.5040.1.2.37.3.1.5.3.1.15
wtWebGraphThermoBaroAlarmTcpTextThis text is sent in the TCP trap body.rw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.5.3.1.16
wtWebGraphThermoBaroAlarmClearMailSubjectSubject line for alarm clear mail.rw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.5.3.1.17
wtWebGraphThermoBaroAlarmClearMailTextAlarm clear mail text: <Tn> provides the current temperature; n = 1..8. <Z> provides the current time.rw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.5.3.1.18
wtWebGraphThermoBaroAlarmClearTrapTextThis text is sent in the trap body.rw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.5.3.1.19
wtWebGraphThermoBaroAlarmClearTcpTextThis text is sent in the TCP trap body.rw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.5.3.1.20
wtWebGraphThermoBaroAlarmDeltaTempMaximum rate of change degrees/min with maximum 2 decimal places. Compared with the average of a period of 5 minutes.rw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.5.3.1.21
wtWebGraphThermoBaroAlarmRHMinMinimum rel. Humidity in percent with maximum 2 decimal places.rw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.5.3.1.22
wtWebGraphThermoBaroAlarmRHMaxMaximum rel.Humidity in percent with maximum 2 decimal places.rw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.5.3.1.23
wtWebGraphThermoBaroAlarmRHHysteresisHysterese rel. Humidity in percent with maximum 2 decimal places.rw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.5.3.1.24
wtWebGraphThermoBaroAlarmAHMinMinimum abs. Humidity in g/(m*m*m) with maximum 2 decimal places.rw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.5.3.1.25
wtWebGraphThermoBaroAlarmAHMaxMaximum abs. Humidity in g/(m*m*m) with maximum 2 decimal places.rw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.5.3.1.26
wtWebGraphThermoBaroAlarmSyslogIpAddrIP address of the syslog server to which the Webio device should send syslog messages.rw
IpAddress
.1.3.6.1.4.1.5040.1.2.37.3.1.5.3.1.27
wtWebGraphThermoBaroAlarmSyslogPortPort number of the syslog server to which the Webio device should send syslog messages.rw
INTEGER
.1.3.6.1.4.1.5040.1.2.37.3.1.5.3.1.28
wtWebGraphThermoBaroAlarmSyslogTextEvery message starts with the priority key, a time stamp and the host ip address, according RFC3164. This text appears in the following syslog message body.rw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.5.3.1.29
wtWebGraphThermoBaroAlarmSyslogClearTextEvery message starts with the priority key, a time stamp and the host ip address, according RFC3164. This text appears in the following syslog message body.rw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.5.3.1.30
wtWebGraphThermoBaroAlarmFtpDataPortLocal data port: 1..65535 or AUTO: the next free port will be assigned.rw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.5.3.1.31
wtWebGraphThermoBaroAlarmFtpFileNameName of the file including path informations.rw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.5.3.1.32
wtWebGraphThermoBaroAlarmFtpTextMessage text to store on the FTP server.rw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.5.3.1.33
wtWebGraphThermoBaroAlarmFtpClearTextAlarm clear message to store on the FTP server.rw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.5.3.1.34
wtWebGraphThermoBaroAlarmFtpOptionBinary coded options, select only one option at the same time: STORE = replace file APPEND = append message at the end of the file Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0 : STORE Bit 1 : APPEND Bit 2-7: unusedrw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.5.3.1.35
wtWebGraphThermoBaroAlarmTimerCronThis entry contains 5 space or tab seperated text fields for time trigger definition. Each field must match with the actual time to trigger a message, weekday and day of month are interpreted separatley. 1: Minutes Range 0-59 2. Hours Range 0-23, 0 is midnight 3: Day of month Range 1-31 4: Month Range 1-12 5: Weekday Range 0-6, 0 is sunday Syntax for every field: - an asterix (*) enables every possible setting of a field - single numbers seperated by commas - a partition within the allowed range (1-5) - step size within an partition of the allowed range (0-59/2: every second minute).rw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.5.3.1.36
wtWebGraphThermoBaroAlarmNameAlert namerw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.5.3.1.39
wtWebGraphThermoBaroAlarmActiveAlert active 1 = ON 0 = OFFrw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.5.3.1.40
wtWebGraphThermoBaroGraphics
OBJECT IDENTIFIER
.1.3.6.1.4.1.5040.1.2.37.3.1.6
wtWebGraphThermoBaroGraphicsBase
OBJECT IDENTIFIER
.1.3.6.1.4.1.5040.1.2.37.3.1.6.1
wtWebGraphThermoBaroGraphicsBaseEnableDefines the viewing options of the graphic: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0 : Auto scroll enable Bit 1 : Show table Bit 2 : Show graph Bit 3 : Show control buttons Bit 4 : Show config menu Bit 5-7: unusedrw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.6.1.1
wtWebGraphThermoBaroGraphicsBaseWidthDefines the width of the graphic in pixels.rw
INTEGER
.1.3.6.1.4.1.5040.1.2.37.3.1.6.1.2
wtWebGraphThermoBaroGraphicsBaseHeightDefines the height of the graphic in pixels.rw
INTEGER
.1.3.6.1.4.1.5040.1.2.37.3.1.6.1.3
wtWebGraphThermoBaroGraphicsBaseFrameColorFrame color definition in RGB.rw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.6.1.4
wtWebGraphThermoBaroGraphicsBaseBackgroundColorBackground color definition in RGB.rw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.6.1.5
wtWebGraphThermoBaroGraphicsBasePollingrateDefines the pollingrate in seconds, which defines the refreshing intervall of the graphic.rw
INTEGER
.1.3.6.1.4.1.5040.1.2.37.3.1.6.1.6
wtWebGraphThermoBaroGraphicsSelect
OBJECT IDENTIFIER
.1.3.6.1.4.1.5040.1.2.37.3.1.6.2
wtWebGraphThermoBaroGraphicsSelectDisplaySensorSelBinary coded sensor selection: only selected sensors will be shown in the graphical presentation: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0: Sensor 1 Bit 1: Sensor 2 Bit 2: Sensor 3 Bit 3-7: unusedrw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.6.2.1
wtWebGraphThermoBaroGraphicsSelectDisplayShowExtremBinary coded sensor selection: only selected sensors will be shown with minima and maxima: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0: Sensor 1 Bit 1: Sensor 2 Bit 2: Sensor 3 Bit 3-7: unusedrw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.6.2.2
wtWebGraphThermoBaroSensorColorTableList of sensor colors for the praphical presentation.
SEQUENCE OF WtWebGraphThermoBaroSensorColorEntry
.1.3.6.1.4.1.5040.1.2.37.3.1.6.2.3
wtWebGraphThermoBaroSensorColorEntryNumbers of the sensors.
WtWebGraphThermoBaroSensorColorEntry
.1.3.6.1.4.1.5040.1.2.37.3.1.6.2.3.1
wtWebGraphThermoBaroGraphicsSensorColorColor of the sensors at the praphical presention.rw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.6.2.3.1.1
wtWebGraphThermoBaroGraphicsSelectScaleAssignes one of 4 scales to a sensor: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0 : Use Scale 1 Bit 1 : Use Scale 2 Bit 2 : Use Scale 3 Bit 3-7: unusedrw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.6.2.3.1.2
wtWebGraphThermoBaroGraphicsScale
OBJECT IDENTIFIER
.1.3.6.1.4.1.5040.1.2.37.3.1.6.3
wtWebGraphThermoBaroGraphicsScaleAutoScaleEnableSelect the Auto Scale Mode: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0 : Scale 1 Auto scale enable Bit 1 : Scale 2 Auto scale enable Bit 2 : Scale 3 Auto scale enable Bit 3-7: unusedrw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.6.3.1
wtWebGraphThermoBaroGraphicsScaleAutoFitEnableSelect the Auto Fit Mode:: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0 : Scale 1 Auto fit enable Bit 1 : Scale 2 Auto fit enable Bit 2 : Scale 3 Auto fit enable Bit 3-7: unusedrw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.6.3.2
wtWebGraphThermoBaroGraphicsScale1MinScale 1: Minimum.ro
INTEGER
.1.3.6.1.4.1.5040.1.2.37.3.1.6.3.3
wtWebGraphThermoBaroGraphicsScale2MinScale 2: Minimum.ro
INTEGER
.1.3.6.1.4.1.5040.1.2.37.3.1.6.3.4
wtWebGraphThermoBaroGraphicsScale3MinScale 3: Minimum.ro
INTEGER
.1.3.6.1.4.1.5040.1.2.37.3.1.6.3.5
wtWebGraphThermoBaroGraphicsScale4MinScale 4: Minimum.ro
INTEGER
.1.3.6.1.4.1.5040.1.2.37.3.1.6.3.6
wtWebGraphThermoBaroGraphicsScale1MaxScale 1: Maximum.ro
INTEGER
.1.3.6.1.4.1.5040.1.2.37.3.1.6.3.7
wtWebGraphThermoBaroGraphicsScale2MaxScale 2: Maximum.ro
INTEGER
.1.3.6.1.4.1.5040.1.2.37.3.1.6.3.8
wtWebGraphThermoBaroGraphicsScale3MaxScale 3: Maximum.ro
INTEGER
.1.3.6.1.4.1.5040.1.2.37.3.1.6.3.9
wtWebGraphThermoBaroGraphicsScale4MaxScale 4: Maximum.ro
INTEGER
.1.3.6.1.4.1.5040.1.2.37.3.1.6.3.10
wtWebGraphThermoBaroGraphicsScale1UnitScale 1: Unit.ro
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.6.3.11
wtWebGraphThermoBaroGraphicsScale2UnitScale 2: Unit.ro
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.6.3.12
wtWebGraphThermoBaroGraphicsScale3UnitScale 3: Unit.ro
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.6.3.13
wtWebGraphThermoBaroGraphicsScale4UnitScale 4: Unit.ro
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.1.6.3.14
wtWebGraphThermoBaroPorts
OBJECT IDENTIFIER
.1.3.6.1.4.1.5040.1.2.37.3.2
wtWebGraphThermoBaroPortTableList of settings depending on the sensor number.
SEQUENCE OF WtWebGraphThermoBaroPortEntry
.1.3.6.1.4.1.5040.1.2.37.3.2.1
wtWebGraphThermoBaroPortEntrySensor parameters for the individual sensors.
WtWebGraphThermoBaroPortEntry
.1.3.6.1.4.1.5040.1.2.37.3.2.1.1
wtWebGraphThermoBaroPortNameName of the sensor.rw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.2.1.1.1
wtWebGraphThermoBaroPortTextDescription of the sensor.rw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.2.1.1.2
wtWebGraphThermoBaroPortOffset1Offset calibration: Offset in degrees with maximum 2 decimal places at temperature 1.rw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.2.1.1.3
wtWebGraphThermoBaroPortTemperature1Offset calibration: Reference temperature 1 in degrees with maximum 2 decimal places.rw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.2.1.1.4
wtWebGraphThermoBaroPortOffset2Offset calibration: Offset in degrees with maximum 2 decimal places at temperature 2.rw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.2.1.1.5
wtWebGraphThermoBaroPortTemperature2Offset calibration: Reference temperature 1 in degrees with maximum 2 decimal places.rw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.2.1.1.6
wtWebGraphThermoBaroPortCommentOffset calibration: informations of date, name of operator, reference devices.rw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.2.1.1.7
wtWebGraphThermoBaroPortAltidudeAltidude oh the Sensor over mean sea level (MSL).rw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.2.2
wtWebGraphThermoBaroManufact
OBJECT IDENTIFIER
.1.3.6.1.4.1.5040.1.2.37.3.3
wtWebGraphThermoBaroMfNameManufacturer company namerw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.3.1
wtWebGraphThermoBaroMfAddrManufacturer address.rw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.3.2
wtWebGraphThermoBaroMfHotlineManufacturer hotline.rw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.3.3
wtWebGraphThermoBaroMfInternetManufacturer Internet address.rw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.3.4
wtWebGraphThermoBaroMfDeviceTypManufacturer device name (model number).rw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.3.5
wtWebGraphThermoBaroMfOrderNoManufacturer part number.rw
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.3.3.6
wtWebGraphThermoBaroDiag
OBJECT IDENTIFIER
.1.3.6.1.4.1.5040.1.2.37.4
wtWebGraphThermoBaroDiagErrorCountNumber of entries in the error memory.ro
INTEGER
.1.3.6.1.4.1.5040.1.2.37.4.1
wtWebGraphThermoBaroDiagBinaryErrorError causes coded bit-by-bit.ro
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.4.2
wtWebGraphThermoBaroDiagErrorIndexThe value of this variable is used as an index to read an error massege from wtWebGraphThermoBaroDiagErrorMessage. Errors are numbered from 1 to wtWebGraphThermoBaroDiagErrorCount. Writing a valid value into this variable, making the appropriate message readable from wtWebGraphThermoBaroDiagErrorMessage.rw
INTEGER
.1.3.6.1.4.1.5040.1.2.37.4.3
wtWebGraphThermoBaroDiagErrorMessageUsing wtWebGraphThermoBaroDiagErrorIndex as an index, the appropriate message is available.ro
OCTET STRING
.1.3.6.1.4.1.5040.1.2.37.4.4
wtWebGraphThermoBaroDiagErrorClearWriting 1 into this variable clears all diagnosis messages.rw
INTEGER
.1.3.6.1.4.1.5040.1.2.37.4.5
WebGraph-Thermo-Hygro-Barometer-US-MIB - SNMP MIB Reference | MIBs Explorer