SCS-ks-MIB
The SCS-ks-MIB provides non-standard SNMP access to monitor and manage specific operational parameters and counters for the SCS KS hardware platform. This module enables the collection of device-specific telemetry data, such as session states and interface statistics, for the SCS KS system.
Imported Objects
Objects
25 total| Object Name |
|---|
carel OBJECT IDENTIFIER .1.3.6.1.4.1.9839 |
systm OBJECT IDENTIFIER .1.3.6.1.4.1.9839.1 |
scs-ksThis is the unofficial MIB module for the SCS KS. MODULE-IDENTITY .1.3.6.1.4.1.9839.1.1 |
scs OBJECT IDENTIFIER .1.3.6.1.4.1.9839.1.2 |
status-evaporator-fanEvaporator Fan alarm 0=OK;1=Errorro Integer32 .1.3.6.1.4.1.9839.1.2.1 |
status-condenser-fanCondenser Fan alarm 0=OK;1=Errorro Integer32 .1.3.6.1.4.1.9839.1.2.2 |
status-compressorCompressor alarm 0=OK;1=Errorro Integer32 .1.3.6.1.4.1.9839.1.2.3 |
status-heater-thermal-protectionHeater thermal protection alarm 0=OK;1=Errorro Integer32 .1.3.6.1.4.1.9839.1.2.4 |
status-exhaust-air-sensorExhaust air sensor alarm 0=OK;1=Errorro Integer32 .1.3.6.1.4.1.9839.1.2.5 |
status-supply-air-sensorSupply air sensor alarm 0=OK;1=Errorro Integer32 .1.3.6.1.4.1.9839.1.2.6 |
status-outside-sensorOutside temperature sensor alarm 0=OK;1=Errorro Integer32 .1.3.6.1.4.1.9839.1.2.7 |
status-room-temperature-sensorTemperature room sensor alarm 0=OK;1=Errorro Integer32 .1.3.6.1.4.1.9839.1.2.8 |
status-room-humidity-sensorHumidity room sensor alarm 0=OK;1=Errorro Integer32 .1.3.6.1.4.1.9839.1.2.9 |
status-min-exhaust-air-temperatureMinimum exhaust air temperature alarm 0=OK;1=Errorro Integer32 .1.3.6.1.4.1.9839.1.2.10 |
status-max-exhaust-air-temperatureMaximum exhaust air temperature alarm 0=OK;1=Errorro Integer32 .1.3.6.1.4.1.9839.1.2.11 |
status-min-supply-air-temperatureMinimum supply air temperature alarm 0=OK;1=Errorro Integer32 .1.3.6.1.4.1.9839.1.2.12 |
status-water-sensorWater sensor alarm 0=OK;1=Errorro Integer32 .1.3.6.1.4.1.9839.1.2.13 |
status-filter-monitoringFilter monitoring alarm 0=OK;1=Errorro Integer32 .1.3.6.1.4.1.9839.1.2.14 |
exhaust-air-temperatureExhaust air temperature 235 = 23.5 degree Celsiusro Integer32 (-999..999) UNITS "N/A" .1.3.6.1.4.1.9839.1.2.15 |
supply-air-temperatureSupply air temperature 235 = 23.5 degree Celsiusro Integer32 (-999..999) UNITS "N/A" .1.3.6.1.4.1.9839.1.2.16 |
outside-air-temperatureOutside air temperature 235 = 23.5 degree Celsiusro Integer32 (-999..999) UNITS "N/A" .1.3.6.1.4.1.9839.1.2.17 |
room-temperatureRoom temperature 235 = 23.5 degree Celsiusro Integer32 (-999..999) UNITS "N/A" .1.3.6.1.4.1.9839.1.2.18 |
room-humidityRoom humidity 235 = 23.5 %ro Integer32 (-999..999) UNITS "N/A" .1.3.6.1.4.1.9839.1.2.19 |
status-operational-statusOperational status 0=Off;1=Runningro Integer32 .1.3.6.1.4.1.9839.1.2.20 |
status-collective-faultCollective fault alarm 0=Error;1=Okro Integer32 .1.3.6.1.4.1.9839.1.2.21 |
More MIBs from CAREL SpA
Browse all CAREL SpAMIBs →SNMP MIB module
The DataAire-dap4-al-MIB provides SNMP-based monitoring and management for Data Aire DAP4-AL precision air conditioning units, exposing critical environmental telemetry such as temperature, humidity, fan status, and alarm conditions. This module enables centralized infrastructure monitoring of cooling system health and operational parameters within data center or server room environments.
The CAREL-ug40cdz-MIB enables SNMP-based monitoring and management of the CAREL UG40 Close Control Uniflair HVAC unit, exposing operational parameters such as compressor status, fan speeds, temperature setpoints, and alarm states for real-time facility environmental control.
SNMP MIB module
The CAREL-RITTAL-LCP-3311-MIB module enables SNMP-based monitoring and management of Rittal LCP 3311 chiller units via PCO web cards, exposing operational telemetry such as compressor status, refrigerant pressure, evaporator and condenser temperatures, fan speeds, and alarm states.