DataAire-dap4-al-MIB

AI MIB Summary

The DataAire-dap4-al-MIB provides SNMP-based monitoring and management for Data Aire DAP4-AL precision air conditioning units, exposing critical environmental telemetry such as temperature, humidity, fan status, and alarm conditions. This module enables centralized infrastructure monitoring of cooling system health and operational parameters within data center or server room environments.

This is the MIB module for the dap4_al device.
Main OID:
dap4_alMIB.1.3.6.1.4.1.9839.2.1
200
Objects
Active
Status
3
Dependencies

Imported Objects

Objects

200 total
Object Name
carel
OBJECT IDENTIFIER
.1.3.6.1.4.1.9839
systm
OBJECT IDENTIFIER
.1.3.6.1.4.1.9839.1
agentReleaseRelease of the Agent.ro
Integer32 UNITS "N/A"
.1.3.6.1.4.1.9839.1.1
agentCodeCode of the Agent. 2=pCOWeb.ro
Integer32 UNITS "N/A"
.1.3.6.1.4.1.9839.1.2
instruments
OBJECT IDENTIFIER
.1.3.6.1.4.1.9839.2
pCOWebInfo
OBJECT IDENTIFIER
.1.3.6.1.4.1.9839.2.0
pCOStatusgroup
OBJECT IDENTIFIER
.1.3.6.1.4.1.9839.2.0.10
pCOId1_StatusStatus of pCOId1. 0=Offline, 1=Init, 2=Onlinero
Integer32
.1.3.6.1.4.1.9839.2.0.10.1
pCOErrorsNumbergroup
OBJECT IDENTIFIER
.1.3.6.1.4.1.9839.2.0.11
pCOId1_ErrorsNumberNumber of Communication Errors from pCOId1 to pCOWeb.ro
Integer32
.1.3.6.1.4.1.9839.2.0.11.1
dap4_alMIBThis is the MIB module for the dap4_al device.
MODULE-IDENTITY
.1.3.6.1.4.1.9839.2.1
digitalObjects
OBJECT IDENTIFIER
.1.3.6.1.4.1.9839.2.1.1
dehum_onDehumidify mode is runningro
Integer32
.1.3.6.1.4.1.9839.2.1.1.1
hum_onHumidifier is runningro
Integer32
.1.3.6.1.4.1.9839.2.1.1.2
engy_onEnergy saver is runningro
Integer32
.1.3.6.1.4.1.9839.2.1.1.3
cool_inhibitCooling inhibit from Zone Masterro
Integer32
.1.3.6.1.4.1.9839.2.1.1.4
heat_heldHeat inhibited due to alarm conditionro
Integer32
.1.3.6.1.4.1.9839.2.1.1.5
humidifier_inhibitHumidifier stopped due to alarmro
Integer32
.1.3.6.1.4.1.9839.2.1.1.6
dehum_inhibitDehum is inhibitedro
Integer32
.1.3.6.1.4.1.9839.2.1.1.7
rht_during_dehumreheat during dehumro
Integer32
.1.3.6.1.4.1.9839.2.1.1.8
floor_wtr_almWater under floor alarmro
Integer32
.1.3.6.1.4.1.9839.2.1.1.9
air_flow_almNo air flow alarmro
Integer32
.1.3.6.1.4.1.9839.2.1.1.10
filter_almDirty filter from digital inputro
Integer32
.1.3.6.1.4.1.9839.2.1.1.11
humidifier_almAlarm from humidifier digital inputro
Integer32
.1.3.6.1.4.1.9839.2.1.1.12
firestat_almTemperature of return air above firestat alarm set pointro
Integer32
.1.3.6.1.4.1.9839.2.1.1.13
shortcycle_almOne or more comps has short cycledro
Integer32
.1.3.6.1.4.1.9839.2.1.1.14
humidity_failSensor is out of rangero
Integer32
.1.3.6.1.4.1.9839.2.1.1.15
ret_air_failSensor is out of rangero
Integer32
.1.3.6.1.4.1.9839.2.1.1.16
maint_almMaintenance Schedule Due alarmro
Integer32
.1.3.6.1.4.1.9839.2.1.1.17
c1_hp_almHigh pressure alarmro
Integer32
.1.3.6.1.4.1.9839.2.1.1.18
c1_lp_almLow pressure alarmro
Integer32
.1.3.6.1.4.1.9839.2.1.1.19
c2_hp_almHigh pressure alarmro
Integer32
.1.3.6.1.4.1.9839.2.1.1.20
c2_lp_almLow pressure alarmro
Integer32
.1.3.6.1.4.1.9839.2.1.1.21
smoke_almSmoke detected from digital inputro
Integer32
.1.3.6.1.4.1.9839.2.1.1.22
wtr_flow_almNo water flow alarmro
Integer32
.1.3.6.1.4.1.9839.2.1.1.23
disch_air_failSensor is out of rangero
Integer32
.1.3.6.1.4.1.9839.2.1.1.24
ra_tmp_hi_almTemperature of return air above alarm set pointro
Integer32
.1.3.6.1.4.1.9839.2.1.1.25
ra_tmp_lo_almTemperature of return air below alarm set pointro
Integer32
.1.3.6.1.4.1.9839.2.1.1.26
hum_hi_almHumidity above alarm set pointro
Integer32
.1.3.6.1.4.1.9839.2.1.1.27
hum_lo_almHumidity below alarm set pointro
Integer32
.1.3.6.1.4.1.9839.2.1.1.28
fan_overloadFan overloadro
Integer32
.1.3.6.1.4.1.9839.2.1.1.29
stdby_pump_onStandby pump on: Check primary pump -Optional alarm. Pump failure input signal requiredro
Integer32
.1.3.6.1.4.1.9839.2.1.1.30
cust_msg_sw1Custom alarm #1 -Optional alarm. External alarm input required. Factory programmed custom message requiredro
Integer32
.1.3.6.1.4.1.9839.2.1.1.31
cust_msg_sw2Custom alarm #2 -Optional alarm. External alarm input required. Factory programmed custom message requiredro
Integer32
.1.3.6.1.4.1.9839.2.1.1.32
cust_msg_sw3Custom alarm #3 -Optional alarm. External alarm input required. Factory programmed custom message requiredro
Integer32
.1.3.6.1.4.1.9839.2.1.1.33
cust_msg_sw4Custom alarm #4 -Optional alarm. External alarm input required. Factory programmed custom message requiredro
Integer32
.1.3.6.1.4.1.9839.2.1.1.34
humsw_inhibitHumidifier stopped due to custom alarm switchro
Integer32
.1.3.6.1.4.1.9839.2.1.1.35
heat_inhibitHeat inhibited due to custom switch alarm conditionro
Integer32
.1.3.6.1.4.1.9839.2.1.1.36
rht_hum_inhibitReheat and humidification inhibited from operationro
Integer32
.1.3.6.1.4.1.9839.2.1.1.37
disch_tmp_lo_almTemperature of discharge air below alarm set pointro
Integer32
.1.3.6.1.4.1.9839.2.1.1.38
override_almManual override: Check bypass switches - Standard alarm. Manual override switch is onro
Integer32
.1.3.6.1.4.1.9839.2.1.1.39
condensation_almHigh condensation from digital inputro
Integer32
.1.3.6.1.4.1.9839.2.1.1.40
unit_in_standbyUnit in standby, all functions held off - Optional alarm. Control input signal required Factory setting requiredro
Integer32
.1.3.6.1.4.1.9839.2.1.1.41
cw_sns_failSensor is out of rangero
Integer32
.1.3.6.1.4.1.9839.2.1.1.42
humsw_chk_cylHumidifier stopped due to custom alarm switchro
Integer32
.1.3.6.1.4.1.9839.2.1.1.43
bms_cooling_inhibitCooling operation inhibited by BMSrw
Integer32
.1.3.6.1.4.1.9839.2.1.1.44
bms_heat_inhibitHeat inhibited due to bmsrw
Integer32
.1.3.6.1.4.1.9839.2.1.1.45
bms_humidifier_inhibitHumidifier operation inhibited by BMSrw
Integer32
.1.3.6.1.4.1.9839.2.1.1.46
bms_dehum_inhibitDehumidify mode inhibited by bmsrw
Integer32
.1.3.6.1.4.1.9839.2.1.1.47
fan_inhibit_bmsInhibit fan by bmsrw
Integer32
.1.3.6.1.4.1.9839.2.1.1.48
hum_expectReduces control humidity cyclingro
Integer32
.1.3.6.1.4.1.9839.2.1.1.49
usashr_f_cTemperature Mode 0=_C 1=_Frw
Integer32
.1.3.6.1.4.1.9839.2.1.1.50
lead_compLead compressor select 0= C1, 1= C2ro
Integer32
.1.3.6.1.4.1.9839.2.1.1.52
wtrvlv_dirWater valve direct or reverse actingro
Integer32
.1.3.6.1.4.1.9839.2.1.1.53
ups_on_almAlarm: UPS power on: Check main power -Optional alarm. External alarm input requiredro
Integer32
.1.3.6.1.4.1.9839.2.1.1.54
pwrup_almLoss of power requires manual reset of alarmro
Integer32
.1.3.6.1.4.1.9839.2.1.1.55
seetag_cust_alm1Local alarm #1: See tag inside door =Optional alarm. External alarm input requiredro
Integer32
.1.3.6.1.4.1.9839.2.1.1.56
seetag_cust_alm2Local alarm #2: See tag inside door =Optional alarm. External alarm input requiredro
Integer32
.1.3.6.1.4.1.9839.2.1.1.57
seetag_cust_alm3Local alarm #3: See tag inside door =Optional alarm. External alarm input requiredro
Integer32
.1.3.6.1.4.1.9839.2.1.1.58
seetag_cust_alm4Local alarm #4: See tag inside door =Optional alarm. External alarm input requiredro
Integer32
.1.3.6.1.4.1.9839.2.1.1.59
shortcycle_alm_enEnable short cycle alarm of the compressorsro
Integer32
.1.3.6.1.4.1.9839.2.1.1.60
superv_offSupervisor (BMS) On-Off. Show the state OFFbyBMS in main mask (1: Off; 0: Onro
Integer32
.1.3.6.1.4.1.9839.2.1.1.61
bms_heartbeatBms heartbeat - pCO looks for update every 10 minutesro
Integer32
.1.3.6.1.4.1.9839.2.1.1.62
analogObjects
OBJECT IDENTIFIER
.1.3.6.1.4.1.9839.2.1.2
ret_air_tmpTemperature of return airro
Integer32
.1.3.6.1.4.1.9839.2.1.2.1
minmax_24hr_retair_maximumMaximum Return air temp in last 24hrsro
Integer32
.1.3.6.1.4.1.9839.2.1.2.2
minmax_24hr_retair_minumumMinimum Return air temp in last 24hrsro
Integer32
.1.3.6.1.4.1.9839.2.1.2.3
temp_setpointTemperature setpointrw
Integer32
.1.3.6.1.4.1.9839.2.1.2.4
temp_deadbandAmount from setpoint before a comp is staged onrw
Integer32
.1.3.6.1.4.1.9839.2.1.2.5
humidity_ain_offsHumidity Sensor Calibrationro
Integer32
.1.3.6.1.4.1.9839.2.1.2.6
return_ain_offsReturn Temperature Sensor Calibrationro
Integer32
.1.3.6.1.4.1.9839.2.1.2.7
cw_tmpTemperature of chilled waterro
Integer32
.1.3.6.1.4.1.9839.2.1.2.8
disch_air_tmpTemperature of discharge airro
Integer32
.1.3.6.1.4.1.9839.2.1.2.9
discharge_ain_offsDischarge Temperature Sensor Calibration - Optional discharge air temperature sensor required (B9)ro
Integer32
.1.3.6.1.4.1.9839.2.1.2.10
cw_ain_offsChilled Water Temperature Sensor Calibration - Optional chilled water temperature sensor required (B10)ro
Integer32
.1.3.6.1.4.1.9839.2.1.2.11
engsaver_setpointTemperature setpoint where chilled water will is requestedrw
Integer32
.1.3.6.1.4.1.9839.2.1.2.12
opt1_analogValue of the analog inputro
Integer32
.1.3.6.1.4.1.9839.2.1.2.13
opt2_analogValue of the analog inputro
Integer32
.1.3.6.1.4.1.9839.2.1.2.14
opt3_analogValue of the analog inputro
Integer32
.1.3.6.1.4.1.9839.2.1.2.15
opt4_analogValue of the analog inputro
Integer32
.1.3.6.1.4.1.9839.2.1.2.16
opt_sns_1_y1Analog Sensor 1 Minimum Valuero
Integer32
.1.3.6.1.4.1.9839.2.1.2.17
opt_sns_1_y2Analog Sensor 1 Maximum Valuero
Integer32
.1.3.6.1.4.1.9839.2.1.2.18
opt_sns_1_ain_offsAnalog Sensor 1 Calibrationro
Integer32
.1.3.6.1.4.1.9839.2.1.2.19
opt_sns_2_y1Analog Sensor 2 Minimum Valuero
Integer32
.1.3.6.1.4.1.9839.2.1.2.20
opt_sns_2_y2Analog Sensor 2 Maximum Valuero
Integer32
.1.3.6.1.4.1.9839.2.1.2.21
opt_sns_2_ain_offsAnalog Sensor 2 Calibrationro
Integer32
.1.3.6.1.4.1.9839.2.1.2.22
opt_sns_3_y1Analog Sensor 3 Minimum Valuero
Integer32
.1.3.6.1.4.1.9839.2.1.2.23
opt_sns_3_y2Analog Sensor 3 Maximum Valuero
Integer32
.1.3.6.1.4.1.9839.2.1.2.24
opt_sns_3_ain_offsAnalog Sensor 3 Calibrationro
Integer32
.1.3.6.1.4.1.9839.2.1.2.25
opt_sns_4_y1Analog Sensor 4 Minimum Valuero
Integer32
.1.3.6.1.4.1.9839.2.1.2.26
opt_sns_4_y2Analog Sensor 4 Maximum Valuero
Integer32
.1.3.6.1.4.1.9839.2.1.2.27
opt_sns_4_ain_offsAnalog Sensor 4 Calibrationro
Integer32
.1.3.6.1.4.1.9839.2.1.2.28
integerObjects
OBJECT IDENTIFIER
.1.3.6.1.4.1.9839.2.1.3
disch_air_lo_spLower Limit alarm of discharge air temprw
Integer32
.1.3.6.1.4.1.9839.2.1.3.1
humidity_disRelative humidity displayed as xx%ro
Integer32
.1.3.6.1.4.1.9839.2.1.3.2
stages_onCooling Stages On, DX onlyro
Integer32
.1.3.6.1.4.1.9839.2.1.3.3
heaters_onNumber of heat stages runningro
Integer32
.1.3.6.1.4.1.9839.2.1.3.4
minmax_24hr_hum_maximumMaximum humidity in last 24hrsro
Integer32
.1.3.6.1.4.1.9839.2.1.3.5
minmax_24hr_hum_minumumMinimum humidity in last 24hrsro
Integer32
.1.3.6.1.4.1.9839.2.1.3.6
comp_dutyCooling Utilization Over Last Hour -Percentage of cooling is used in the last hour of operation; this point applies to DX unit.ro
Integer32
.1.3.6.1.4.1.9839.2.1.3.7
heat_dutyHeating Utilization Over Last Hour -Percentage of heating is used in the last hour of operationro
Integer32
.1.3.6.1.4.1.9839.2.1.3.8
hum_dutyHumidifier Utilization Over Last Hour -Percentage of humidifier is used in the last hour of operationro
Integer32
.1.3.6.1.4.1.9839.2.1.3.9
c1_hours_hCompressor 1 Runtime -This point applies to DX unit with one compressor -highro
Integer32
.1.3.6.1.4.1.9839.2.1.3.10
c1_hours_lCompressor 1 Runtime -This point applies to DX unit with one compressor -lowro
Integer32
.1.3.6.1.4.1.9839.2.1.3.11
c2_hours_hCompressor 2 Runtime -This point applies to DX unit with dual compressor - highro
Integer32
.1.3.6.1.4.1.9839.2.1.3.12
c2_hours_lCompressor 2 Runtime -This point applies to DX unit with dual compressor - lowro
Integer32
.1.3.6.1.4.1.9839.2.1.3.13
ht1_hours_hHeater 1 Runtime - highro
Integer32
.1.3.6.1.4.1.9839.2.1.3.14
ht1_hours_lHeater 1 Runtime - lowro
Integer32
.1.3.6.1.4.1.9839.2.1.3.15
current_secondCurrent secondro
Integer32
.1.3.6.1.4.1.9839.2.1.3.16
current_minuteCurrent minutero
Integer32
.1.3.6.1.4.1.9839.2.1.3.17
current_hourCurrent hourro
Integer32
.1.3.6.1.4.1.9839.2.1.3.18
current_dayCurrent dayro
Integer32
.1.3.6.1.4.1.9839.2.1.3.19
current_monthCurrent monthro
Integer32
.1.3.6.1.4.1.9839.2.1.3.20
current_yearCurrent yearro
Integer32
.1.3.6.1.4.1.9839.2.1.3.21
firestat_spAlarm settting of return air temp to determine there is a firerw
Integer32
.1.3.6.1.4.1.9839.2.1.3.22
hum_hi_spHumidity upper limit alarmrw
Integer32
.1.3.6.1.4.1.9839.2.1.3.23
ret_air_hi_spUpper limit alarm of return air temprw
Integer32
.1.3.6.1.4.1.9839.2.1.3.24
hum_lo_spHumidity lower limit alarmrw
Integer32
.1.3.6.1.4.1.9839.2.1.3.25
ret_air_lo_spLower limit alarm of return air temprw
Integer32
.1.3.6.1.4.1.9839.2.1.3.26
hum_deadbandamount hum must change from setpoint before actingrw
Integer32
.1.3.6.1.4.1.9839.2.1.3.27
hum_setpointhumidity setpointrw
Integer32
.1.3.6.1.4.1.9839.2.1.3.28
start_dlyTime before the system starts uprw
Integer32
.1.3.6.1.4.1.9839.2.1.3.29
alm1_delOptional Alarm 1 Delayro
Integer32
.1.3.6.1.4.1.9839.2.1.3.30
alm2_delOptional Alarm 2 Delayro
Integer32
.1.3.6.1.4.1.9839.2.1.3.31
alm3_delOptional Alarm 3 Delayro
Integer32
.1.3.6.1.4.1.9839.2.1.3.32
alarm1_txtMessage on optional alarm screen, some also add functionro
Integer32
.1.3.6.1.4.1.9839.2.1.3.33
alarm2_txtMessage on optional alarm screen, some also add functionro
Integer32
.1.3.6.1.4.1.9839.2.1.3.34
alarm3_txtMessage on optional alarm screen, some also add functionro
Integer32
.1.3.6.1.4.1.9839.2.1.3.35
alarm4_txtMessage on optional alarm screen, some also add functionro
Integer32
.1.3.6.1.4.1.9839.2.1.3.36
comp_selComps 0=none, 1=one, 2=one+UL, 3=two, 4=two+UL, 5=Four/two circuitro
Integer32
.1.3.6.1.4.1.9839.2.1.3.37
dehum_mode0=none, 1= comp limited, 2=twocomp limited, 3= comp unlimited, 4=twocomp unlimitedro
Integer32
.1.3.6.1.4.1.9839.2.1.3.38
reheat_selNumber of heat stagesro
Integer32
.1.3.6.1.4.1.9839.2.1.3.39
hum_sel0=none, 1=comp mod, 2=comp non, 3= comf mod, 4= conf non modro
Integer32
.1.3.6.1.4.1.9839.2.1.3.40
alm_contact_msgText displayed on all alarm screensro
Integer32
.1.3.6.1.4.1.9839.2.1.3.41
powerup_sel0= start wo/alarm, 1= start w/alarm, 2= requires reset of alarmro
Integer32
.1.3.6.1.4.1.9839.2.1.3.42
buzzer_select0=None, 1=short beeps, 2=long beep, 3=Constantro
Integer32
.1.3.6.1.4.1.9839.2.1.3.43
cw_disp% of 10volts of analog output #1ro
Integer32
.1.3.6.1.4.1.9839.2.1.3.44
wtrvlv_dutyChilled Water Utilization Over Last Hour - This applies to Chilled water or Energy saver units.ro
Integer32
.1.3.6.1.4.1.9839.2.1.3.45
hum_hours_hHumidifier Runtime - highro
Integer32
.1.3.6.1.4.1.9839.2.1.3.46
hum_hours_lHumidifier Runtime - lowro
Integer32
.1.3.6.1.4.1.9839.2.1.3.47
blower_hours_hBlower Runtime - highro
Integer32
.1.3.6.1.4.1.9839.2.1.3.48
blower_hours_lBlower Runtime - lowro
Integer32
.1.3.6.1.4.1.9839.2.1.3.49
alm4_delOptional Alarm 4 Delayro
Integer32
.1.3.6.1.4.1.9839.2.1.3.50
assist_sel0= no comp assist, 1=one comp assist, 2= two comp assist, 3... 4...ro
Integer32
.1.3.6.1.4.1.9839.2.1.3.51
wtrvlv_selWater valve type 0=none, 1=chill, 2=Engy, 3=Aux chill, 4=Disc Regro
Integer32
.1.3.6.1.4.1.9839.2.1.3.52
wtrvlv_volts_selWater valve voltage 0= 0-10, 1=2-10, 2=7-10, 3=6-9, 4=4-7ro
Integer32
.1.3.6.1.4.1.9839.2.1.3.53
hum_volts% of 10volts of analog output #2ro
Integer32
.1.3.6.1.4.1.9839.2.1.3.54
dehum_hours_hDehumidifier Runtime - Highro
Integer32
.1.3.6.1.4.1.9839.2.1.3.55
dehum_hours_lDehumidifier Runtime - Lowro
Integer32
.1.3.6.1.4.1.9839.2.1.3.56
autoflush_dlyTime between drain cycles 0=12hr, 1=24hr, 2=48hr, 3=96hr, 4=Nonero
Integer32
.1.3.6.1.4.1.9839.2.1.3.58
y4_outValue sent to optional analog output#1ro
Integer32
.1.3.6.1.4.1.9839.2.1.3.59
y5_outValue sent to optional analog output#2ro
Integer32
.1.3.6.1.4.1.9839.2.1.3.60
air_flowCurrent Fan Airflow - Based on calculated Pressure Diff formularo
Integer32
.1.3.6.1.4.1.9839.2.1.3.61
opt_snsr1_nameName of the sensorro
Integer32
.1.3.6.1.4.1.9839.2.1.3.62
opt_sns_1_ain_typeAnalog Sensor 1 Type {0=NTC 1=PT1000 2=0-1VDC 3=0-10VDC 4=4-20mA 5=ON/OFF 6=0-5VDC 7=NTC HT 8=-50T90 9=10T170}ro
Integer32
.1.3.6.1.4.1.9839.2.1.3.63
opt_snsr2_nameName of the sensorro
Integer32
.1.3.6.1.4.1.9839.2.1.3.64
opt_sns_2_ain_typeAnalog Sensor 2 Type {0=NTC 1=PT1000 2=0-1VDC 3=0-10VDC 4=4-20mA 5=ON/OFF 6=0-5VDC 7=NTC HT 8=-50T90 9=10T170}ro
Integer32
.1.3.6.1.4.1.9839.2.1.3.65
opt_snsr3_nameName of the sensorro
Integer32
.1.3.6.1.4.1.9839.2.1.3.66
opt_sns_3_ain_typeAnalog Sensor 3 Type {0=NTC 1=PT1000 2=0-1VDC 3=0-10VDC 4=4-20mA 5=ON/OFF 6=0-5VDC 7=NTC HT 8=-50T90 9=10T170}ro
Integer32
.1.3.6.1.4.1.9839.2.1.3.67
opt_snsr4_nameName of the sensorro
Integer32
.1.3.6.1.4.1.9839.2.1.3.68
opt_sns_4_ain_typeAnalog Sensor 4 Type {0=NTC 1=PT1000 2=0-1VDC 3=0-10VDC 4=4-20mA 5=ON/OFF 6=0-5VDC 7=NTC HT 8=-50T90 9=10T170}ro
Integer32
.1.3.6.1.4.1.9839.2.1.3.69
cw_fan_speed_bmsCW Fan speed (%) sent via BMSrw
Integer32
.1.3.6.1.4.1.9839.2.1.3.70
dx_fan_speed_bmsDX Fan speed (%) sent via BMSrw
Integer32
.1.3.6.1.4.1.9839.2.1.3.71
fan_speed_maxMaximum Fan speed (% of output) modulation.rw
Integer32
.1.3.6.1.4.1.9839.2.1.3.72
fan_speed_minMinimum Fan speed (% of output) modulation from pressure.rw
Integer32
.1.3.6.1.4.1.9839.2.1.3.73
fan_pr_spFan pressure setpoint (0.01 inches of water)rw
Integer32
.1.3.6.1.4.1.9839.2.1.3.74
fan_pr_bandFan pressure band (0.01 inches of water)rw
Integer32
.1.3.6.1.4.1.9839.2.1.3.75
fan_af_maxMaximum air flow limit of setpoint from BMS or valve modulation.rw
Integer32
.1.3.6.1.4.1.9839.2.1.3.76
fan_af_minMinimum air flow limit of setpoint from BMS or valve modulation.rw
Integer32
.1.3.6.1.4.1.9839.2.1.3.77
fan_kfactorFan K Factorrw
Integer32
.1.3.6.1.4.1.9839.2.1.3.78
num_fansNumber of fans installed in this unitrw
Integer32
.1.3.6.1.4.1.9839.2.1.3.79
ht2_hours_hHeater 2 Runtime - highro
Integer32
.1.3.6.1.4.1.9839.2.1.3.81
ht2_hours_lHeater 2 Runtime - lowro
Integer32
.1.3.6.1.4.1.9839.2.1.3.82
ht3_hours_hHeater 3 Runtime - highro
Integer32
.1.3.6.1.4.1.9839.2.1.3.83
ht3_hours_lHeater 3 Runtime - lowro
Integer32
.1.3.6.1.4.1.9839.2.1.3.84
engy_hours_hEnergy Saver Runtime - This optional point applies to energy saver units only -highro
Integer32
.1.3.6.1.4.1.9839.2.1.3.85
engy_hours_lEnergy Saver Runtime - This optional point applies to energy saver units only - lowro
Integer32
.1.3.6.1.4.1.9839.2.1.3.86
cw_hours_hChilled Water Runtime - This applies to chilled water units only - highro
Integer32
.1.3.6.1.4.1.9839.2.1.3.87
cw_hours_lChilled Water Runtime - This applies to chilled water units only - lowro
Integer32
.1.3.6.1.4.1.9839.2.1.3.88
c3_hours_hCompressor 3 Runtime - This applies when unit has four stages tandem compressors - highro
Integer32
.1.3.6.1.4.1.9839.2.1.3.89
c3_hours_lCompressor 3 Runtime - This applies when unit has four stages tandem compressors - lowro
Integer32
.1.3.6.1.4.1.9839.2.1.3.90
c4_hours_lCompressor 4 Runtime - This applies when unit has four stages tandem compressors. - highro
Integer32
.1.3.6.1.4.1.9839.2.1.3.91
c4_hours_hCompressor 4 Runtime - This applies when unit has four stages tandem compressors. - lowro
Integer32
.1.3.6.1.4.1.9839.2.1.3.92
cond_hours_hCondenser Runtime - highro
Integer32
.1.3.6.1.4.1.9839.2.1.3.93
cond_hours_lCondenser Runtime - lowro
Integer32
.1.3.6.1.4.1.9839.2.1.3.94
dx_fan_speedFan speed (% of output) when compressor cooling.ro
Integer32
.1.3.6.1.4.1.9839.2.1.3.95
cw_fan_speedFan speed (% of output) when cold water cooling.ro
Integer32
.1.3.6.1.4.1.9839.2.1.3.96
fan_af_dx_spFan air flow setpoint for DX unit (cfm)ro
Integer32
.1.3.6.1.4.1.9839.2.1.3.97
fan_af_cw_spFan air flow setpoint for CW unit (cfm)ro
Integer32
.1.3.6.1.4.1.9839.2.1.3.98
zm_airflow_spZone Airflow Setpoint kcfmrw
Integer32
.1.3.6.1.4.1.9839.2.1.3.99
DataAire-dap4-al-MIB - SNMP MIB Reference | MIBs Explorer