CAREL-RITTAL-LCP-3311-MIB
AI MIB Summary
The CAREL-RITTAL-LCP-3311-MIB module enables SNMP-based monitoring and management of Rittal LCP 3311 chiller units via PCO web cards, exposing operational telemetry such as compressor status, refrigerant pressure, evaporator and condenser temperatures, fan speeds, and alarm states.
Custom MIB for Rittal LCP 3311 chillers connected to a pco web card
Main OID:
carel.1.3.6.1.4.1.9839
62
Objects
Active
Status
3
Dependencies
Imported Objects
Objects
62 total| Object Name |
|---|
carelCustom MIB for Rittal LCP 3311 chillers connected to a pco web card MODULE-IDENTITY .1.3.6.1.4.1.9839 |
rittal OBJECT IDENTIFIER .1.3.6.1.4.1.9839.2606 |
rittalLCP3311 OBJECT IDENTIFIER .1.3.6.1.4.1.9839.2606.2 |
sensors OBJECT IDENTIFIER .1.3.6.1.4.1.9839.2606.2.1 |
digital OBJECT IDENTIFIER .1.3.6.1.4.1.9839.2606.2.1.1 |
compressorOverloadAlarmCompressor overload alarm
ok (0),
alarm (1)ro Enumeration .1.3.6.1.4.1.9839.2606.2.1.1.2 |
highPressureAlarmHigh pressure alarm
ok (0),
alarm (1)ro Enumeration .1.3.6.1.4.1.9839.2606.2.1.1.3 |
remoteOnOffRemote On/Off
off (0),
on (1)ro Enumeration .1.3.6.1.4.1.9839.2606.2.1.1.8 |
inverterAlarmInverter alarm
ok (0),
alarm (1)ro Enumeration .1.3.6.1.4.1.9839.2606.2.1.1.11 |
driveAlarmPower+ drive off-line alarm
ok (0),
alarm (1)ro Enumeration .1.3.6.1.4.1.9839.2606.2.1.1.12 |
inverterOnOffInverter On/Off
off (0),
on (1)ro Enumeration .1.3.6.1.4.1.9839.2606.2.1.1.17 |
generalAlarmGeneral alarm
alarm (0),
ok (1)ro Enumeration .1.3.6.1.4.1.9839.2606.2.1.1.23 |
resetAllAlarmsReset all alarms
no (0),
yes (1)rw Enumeration .1.3.6.1.4.1.9839.2606.2.1.1.29 |
compressorEnvelopeAlarmCompressor forced off working out envelope
ok (0),
alarm (1)ro Enumeration .1.3.6.1.4.1.9839.2606.2.1.1.30 |
compressorStartupFailureAlarmCompressor startup failure alarm, reached max retries
ok (0),
alarm (1)ro Enumeration .1.3.6.1.4.1.9839.2606.2.1.1.31 |
maxDischargeTemperatureAlarmMaximum discharge temperature has been reached
ok (0),
alarm (1)ro Enumeration .1.3.6.1.4.1.9839.2606.2.1.1.33 |
compressorDeltaPressureAlarmDelta pressure too big to startup compressor
ok (0),
alarm (1)ro Enumeration .1.3.6.1.4.1.9839.2606.2.1.1.35 |
oilReturnAlarmOil return alarm for when the compressor is running. Lubrication issue.
ok (0),
alarm (1)ro Enumeration .1.3.6.1.4.1.9839.2606.2.1.1.36 |
outputTemperatureTopProbeAlarmTop output temperature probe broken
ok (0),
alarm (1)ro Enumeration .1.3.6.1.4.1.9839.2606.2.1.1.38 |
outputTemperatureMidProbeAlarmMid output temperature probe broken
ok (0),
alarm (1)ro Enumeration .1.3.6.1.4.1.9839.2606.2.1.1.39 |
outputTemperatureBottomProbeAlarmBottom output temperature probe broken
ok (0),
alarm (1)ro Enumeration .1.3.6.1.4.1.9839.2606.2.1.1.40 |
inputTemperatureTopProbeAlarmTop input temperature probe broken
ok (0),
alarm (1)ro Enumeration .1.3.6.1.4.1.9839.2606.2.1.1.42 |
inputTemperatureMidProbeAlarmMid input temperature probe broken
ok (0),
alarm (1)ro Enumeration .1.3.6.1.4.1.9839.2606.2.1.1.43 |
inputTemperatureBottomProbeAlarmBottom input temperature probe broken
ok (0),
alarm (1)ro Enumeration .1.3.6.1.4.1.9839.2606.2.1.1.44 |
compressorDischargeTemperatureProbeAlarmCompressor discharge temperature probe broken
ok (0),
alarm (1)ro Enumeration .1.3.6.1.4.1.9839.2606.2.1.1.45 |
compressorSuctionTemperatureProbeAlarmCompressor suction temperature probe broken
ok (0),
alarm (1)ro Enumeration .1.3.6.1.4.1.9839.2606.2.1.1.46 |
compressorDischargePressureProbeAlarmCompressor discharge pressure probe broken
ok (0),
alarm (1)ro Enumeration .1.3.6.1.4.1.9839.2606.2.1.1.47 |
compressorSuctionPressureProbeAlarmCompressor suction pressure probe broken
ok (0),
alarm (1)ro Enumeration .1.3.6.1.4.1.9839.2606.2.1.1.48 |
rebootReboot the system
no (0),
yes (1)rw Enumeration .1.3.6.1.4.1.9839.2606.2.1.1.100 |
analog OBJECT IDENTIFIER .1.3.6.1.4.1.9839.2606.2.1.2 |
outputTemperatureTopSensorTop sensor output temperature in Celciusro DivBy10 UNITS "C" .1.3.6.1.4.1.9839.2606.2.1.2.2 |
outputTemperatureMidSensorMid sensor output temperature in Celciusro DivBy10 UNITS "C" .1.3.6.1.4.1.9839.2606.2.1.2.3 |
outputTemperatureBottomSensorBottom sensor output temperature in Celciusro DivBy10 UNITS "C" .1.3.6.1.4.1.9839.2606.2.1.2.4 |
inputTemperatureTopSensorTop sensor input temperature in Celciusro DivBy10 UNITS "C" .1.3.6.1.4.1.9839.2606.2.1.2.6 |
inputTemperatureMidSensorMid sensor input temperature in Celciusro DivBy10 UNITS "C" .1.3.6.1.4.1.9839.2606.2.1.2.7 |
inputTemperatureBottomSensorBottom sensor input temperature in Celciusro DivBy10 UNITS "C" .1.3.6.1.4.1.9839.2606.2.1.2.8 |
compressorDischargeTemperatureCompressor discharge temperaturero DivBy10 UNITS "C" .1.3.6.1.4.1.9839.2606.2.1.2.9 |
compressorSuctionTemperatureCompressor suction temperaturero DivBy10 UNITS "C" .1.3.6.1.4.1.9839.2606.2.1.2.10 |
compressorDischargePressureCompressor discharge pressurero DivBy10 UNITS "bar" .1.3.6.1.4.1.9839.2606.2.1.2.11 |
compressorSuctionPressureCompressor suction pressurero DivBy10 UNITS "bar" .1.3.6.1.4.1.9839.2606.2.1.2.12 |
evaporatorTemperatureEvaporator temperature from Low pressure conversionro DivBy10 UNITS "C" .1.3.6.1.4.1.9839.2606.2.1.2.13 |
condensingTemperatureCondensing temperature from High pressure conversionro DivBy10 UNITS "C" .1.3.6.1.4.1.9839.2606.2.1.2.14 |
inputTemperatureAverageAverage input temperature in Celciusro DivBy10 UNITS "C" .1.3.6.1.4.1.9839.2606.2.1.2.21 |
outputTemperatureAverageAverage output temperature in Celciusro DivBy10 UNITS "C" .1.3.6.1.4.1.9839.2606.2.1.2.22 |
compressorRotorSpeedCompressor rotor speedro DivBy10 UNITS "rps" .1.3.6.1.4.1.9839.2606.2.1.2.45 |
compressorMotorCurrentCompressor motor currentro DivBy10 UNITS "A" .1.3.6.1.4.1.9839.2606.2.1.2.46 |
lcpSetpointMain LCP setpointrw DivBy10 UNITS "C" .1.3.6.1.4.1.9839.2606.2.1.2.48 |
integer OBJECT IDENTIFIER .1.3.6.1.4.1.9839.2606.2.1.3 |
compressorRotorSpeedHzCompressor rotor speed in Hzro INTEGER .1.3.6.1.4.1.9839.2606.2.1.3.1 |
driverPowerStatusDriver power status
stop (1),
run (2),
alarm (3)ro Enumeration .1.3.6.1.4.1.9839.2606.2.1.3.2 |
currentErrorCodeCurrent error codero Enumeration .1.3.6.1.4.1.9839.2606.2.1.3.3 |
driverTemperatureDriver Power+ Temperaturero DivBy10 UNITS "C" .1.3.6.1.4.1.9839.2606.2.1.3.4 |
dcBusVoltagePower+ DC Voltagero DivBy10 UNITS "V" .1.3.6.1.4.1.9839.2606.2.1.3.5 |
motorVoltageMotor Voltagero DivBy10 UNITS "V" .1.3.6.1.4.1.9839.2606.2.1.3.6 |
powerRequestRequest of power for inverter after envelopro DivBy10 UNITS "%" .1.3.6.1.4.1.9839.2606.2.1.3.7 |
unitOnOffUnit on/off state
off (0),
on (1),
energy-save (2),
auto (3)rw Enumeration .1.3.6.1.4.1.9839.2606.2.1.3.13 |
envelopeZoneenvelope zone
ok (0),
maximum compression ratio (1),
maximum discharge power (2),
current limit (3),
maximum suction power(4),
minimum compression ratio (5),
minimum delta power (6),
minimum discharge power(7),
minimum suction power (8)ro Enumeration .1.3.6.1.4.1.9839.2606.2.1.3.14 |
coolingCapacityActual EVD valve cooling capacityro INTEGER .1.3.6.1.4.1.9839.2606.2.1.3.16 |
evdValveStepsEVD valve steps positionro INTEGER .1.3.6.1.4.1.9839.2606.2.1.3.17 |
fanSpeedPercentThe fan speed percentagero INTEGER .1.3.6.1.4.1.9839.2606.2.1.3.28 |
fanSpeedRpmThe fan speed rpmro INTEGER .1.3.6.1.4.1.9839.2606.2.1.3.29 |
evdValveOpeningActual EVD valve openingro INTEGER .1.3.6.1.4.1.9839.2606.2.1.3.30 |