This is the MIB module for the kelvin-pCOWeb-Chiller device.
Main OID:
kelvin_pCOWebMIB_Chiller.1.3.6.1.4.1.9839.2.1
373
Objects
Active
Status
3
Dependencies

Imported Objects

Objects

373 total
Object Name
carel
OBJECT IDENTIFIER
.1.3.6.1.4.1.9839
systm
OBJECT IDENTIFIER
.1.3.6.1.4.1.9839.1
agentReleaseRelease of the Agent.ro
Integer32 UNITS "N/A"
.1.3.6.1.4.1.9839.1.1
agentCodeCode of the Agent. 2=pCOWeb.ro
Integer32 UNITS "N/A"
.1.3.6.1.4.1.9839.1.2
instruments
OBJECT IDENTIFIER
.1.3.6.1.4.1.9839.2
pCOWebInfo
OBJECT IDENTIFIER
.1.3.6.1.4.1.9839.2.0
pCOStatusgroup
OBJECT IDENTIFIER
.1.3.6.1.4.1.9839.2.0.10
pCOId1_StatusStatus of pCOId1. 0=Offline, 1=Init, 2=Onlinero
Integer32
.1.3.6.1.4.1.9839.2.0.10.1
pCOErrorsNumbergroup
OBJECT IDENTIFIER
.1.3.6.1.4.1.9839.2.0.11
pCOId1_ErrorsNumberNumber of Communication Errors from pCOId1 to pCOWeb.ro
Integer32
.1.3.6.1.4.1.9839.2.0.11.1
kelvin_pCOWebMIB_ChillerThis is the MIB module for the kelvin-pCOWeb-Chiller device.
MODULE-IDENTITY
.1.3.6.1.4.1.9839.2.1
digitalObjects
OBJECT IDENTIFIER
.1.3.6.1.4.1.9839.2.1.1
al_pa1High pressure switch 1 alarmro
Integer32
.1.3.6.1.4.1.9839.2.1.1.1
al_pa2High pressure switch 2 alarmro
Integer32
.1.3.6.1.4.1.9839.2.1.1.2
al_pb1Low pressure switch 1 alarmro
Integer32
.1.3.6.1.4.1.9839.2.1.1.3
al_pb2Low pressure switch 2 alarmro
Integer32
.1.3.6.1.4.1.9839.2.1.1.4
al_leWater level alarmro
Integer32
.1.3.6.1.4.1.9839.2.1.1.6
al_idrofrigo_fl1Flow switch alarmro
Integer32
.1.3.6.1.4.1.9839.2.1.1.8
static_press_alarmWater static pressure alarmro
Integer32
.1.3.6.1.4.1.9839.2.1.1.9
w_static_press_alarmWater static pressure warningro
Integer32
.1.3.6.1.4.1.9839.2.1.1.10
flow_value_alarmFlow rate alarmro
Integer32
.1.3.6.1.4.1.9839.2.1.1.11
al_q_comp1Overload compressor 1 circuit 1 alarmro
Integer32
.1.3.6.1.4.1.9839.2.1.1.12
al_q_comp2Overload compressor 2 circuit 1 alarmro
Integer32
.1.3.6.1.4.1.9839.2.1.1.13
al_q_comp3Overload compressor 3 circuit 1 alarmro
Integer32
.1.3.6.1.4.1.9839.2.1.1.14
al_q_comp4Overload compressor 1 circuit 2 alarmro
Integer32
.1.3.6.1.4.1.9839.2.1.1.15
al_q_comp5Overload compressor 2 circuit 2 alarmro
Integer32
.1.3.6.1.4.1.9839.2.1.1.16
al_q_comp6Overload compressor 3 circuit 2 alarmro
Integer32
.1.3.6.1.4.1.9839.2.1.1.17
al_q_fan_1Overload fans circuit 1ro
Integer32
.1.3.6.1.4.1.9839.2.1.1.18
al_q_fan_2Overload fans circuit 2ro
Integer32
.1.3.6.1.4.1.9839.2.1.1.19
al_q_fan11Overload fan 1 circuit 1 alarmro
Integer32
.1.3.6.1.4.1.9839.2.1.1.20
al_q_fan12Overload fan 2 circuit 1 alarmro
Integer32
.1.3.6.1.4.1.9839.2.1.1.21
al_q_fan13Overload fan 3 circuit 1 alarmro
Integer32
.1.3.6.1.4.1.9839.2.1.1.22
al_q_fan14Overload fan 4 circuit 1 alarmro
Integer32
.1.3.6.1.4.1.9839.2.1.1.23
al_q_fan21Overload fan 1 circuit 2 alarmro
Integer32
.1.3.6.1.4.1.9839.2.1.1.24
al_q_fan22Overload fan 2 circuit 2 alarmro
Integer32
.1.3.6.1.4.1.9839.2.1.1.25
al_q_fan_23Overload fan 3 circuit 2 alarmro
Integer32
.1.3.6.1.4.1.9839.2.1.1.26
al_q_fan24Overload fan 4 circuit 2 alarmro
Integer32
.1.3.6.1.4.1.9839.2.1.1.27
al_idrofrigo_pump1Overload pump 1 alarmro
Integer32
.1.3.6.1.4.1.9839.2.1.1.28
al_idrofrigo_pump2Overload pump 2 alarmro
Integer32
.1.3.6.1.4.1.9839.2.1.1.29
al_phase_contWrong phase rotation alarmro
Integer32
.1.3.6.1.4.1.9839.2.1.1.30
al_door_swBack Door open alarmro
Integer32
.1.3.6.1.4.1.9839.2.1.1.31
compressor_FlowRateCompressor FlowRate Managementrw
Integer32
.1.3.6.1.4.1.9839.2.1.1.32
setpoint_inv_pumpsSetpoint Type for Inverter pumpsrw
Integer32
.1.3.6.1.4.1.9839.2.1.1.33
enable_pumps_redundanceEnable Pumps redundancerw
Integer32
.1.3.6.1.4.1.9839.2.1.1.34
enable_chiller_redundanceEnable Chiller redundancerw
Integer32
.1.3.6.1.4.1.9839.2.1.1.35
status_in_alarmStatus in alarmrw
Integer32
.1.3.6.1.4.1.9839.2.1.1.36
compressor_recoveryCompressor Recoveryrw
Integer32
.1.3.6.1.4.1.9839.2.1.1.37
enable_thermal_redundanceEnable Thermal redundancerw
Integer32
.1.3.6.1.4.1.9839.2.1.1.38
enable_multi_pumps_functionEnable multi-pumps functionrw
Integer32
.1.3.6.1.4.1.9839.2.1.1.39
enable_pumps_offlineEnable function pumps-Offlinerw
Integer32
.1.3.6.1.4.1.9839.2.1.1.40
enable_3way_valveEnable 3way valverw
Integer32
.1.3.6.1.4.1.9839.2.1.1.41
enable_speed_up_FCMEnable speed-up FCMrw
Integer32
.1.3.6.1.4.1.9839.2.1.1.42
enable_soft_start_FCMEnable soft-start FCMrw
Integer32
.1.3.6.1.4.1.9839.2.1.1.43
enable_freecoolingEnable Freecoolingrw
Integer32
.1.3.6.1.4.1.9839.2.1.1.44
enable_rot_FIFO_FCEnable rotation FIFO Freecoolingrw
Integer32
.1.3.6.1.4.1.9839.2.1.1.45
enable_HT_functionEnable HT-functionrw
Integer32
.1.3.6.1.4.1.9839.2.1.1.46
enable_PID_Fc_valveEnable PID-regulation for Freecooling valverw
Integer32
.1.3.6.1.4.1.9839.2.1.1.47
enable_Fc_Thermal_ExclusionEnable Freecooling Thermal Exclusionrw
Integer32
.1.3.6.1.4.1.9839.2.1.1.48
manual_Reset_Ext_Drycooler_AlarmManual Reset External Dry-cooler Alarmrw
Integer32
.1.3.6.1.4.1.9839.2.1.1.49
enable_static_press_AlarmEnable static pressure Alarmrw
Integer32
.1.3.6.1.4.1.9839.2.1.1.50
manual_reset_static_press_AlarmManual reset static pressure Alarmrw
Integer32
.1.3.6.1.4.1.9839.2.1.1.51
enable_static_press_WarningEnable static pressure Warningrw
Integer32
.1.3.6.1.4.1.9839.2.1.1.52
manual_reset_static_press_WarningManual reset static pressure Warningrw
Integer32
.1.3.6.1.4.1.9839.2.1.1.53
enable_diff_press_AlarmEnable differential pressure Alarmrw
Integer32
.1.3.6.1.4.1.9839.2.1.1.54
manual_reset_diff_press_AlarmManual reset differential pressure Alarmrw
Integer32
.1.3.6.1.4.1.9839.2.1.1.55
enable_pressure_recoveryEnable pressure recoveryrw
Integer32
.1.3.6.1.4.1.9839.2.1.1.56
enable_Flow_Rate_AlarmEnable Flow-Rate Alarmrw
Integer32
.1.3.6.1.4.1.9839.2.1.1.57
manual_reset_Flow_Rate_AlarmManual reset Flow-Rate Alarmrw
Integer32
.1.3.6.1.4.1.9839.2.1.1.58
enable_Flow_Rate_recoveryEnable Flow-Rate recoveryrw
Integer32
.1.3.6.1.4.1.9839.2.1.1.59
enable_pCOWebEnable pCOWebrw
Integer32
.1.3.6.1.4.1.9839.2.1.1.60
fc_single_chillerFreecooling single chiller functionrw
Integer32
.1.3.6.1.4.1.9839.2.1.1.61
al_idrofrigo_pump_c_1Condensation pump 1 breaker switch alarmro
Integer32
.1.3.6.1.4.1.9839.2.1.1.75
al_idrofrigo_pump_c_2Condensation pump 2 breaker switch alarmro
Integer32
.1.3.6.1.4.1.9839.2.1.1.76
al_idrofrigo_fl_CCondensation flow switch alarmro
Integer32
.1.3.6.1.4.1.9839.2.1.1.80
c11_onCompressor 1 circuit 1 ONro
Integer32
.1.3.6.1.4.1.9839.2.1.1.100
c12_onCompressor 2 circuit 1 ONro
Integer32
.1.3.6.1.4.1.9839.2.1.1.101
c13_onCompressor 3 circuit 1 ONro
Integer32
.1.3.6.1.4.1.9839.2.1.1.102
c21_onCompressor 1 circuit 2 ONro
Integer32
.1.3.6.1.4.1.9839.2.1.1.103
c22_onCompressor 2 circuit 2 ONro
Integer32
.1.3.6.1.4.1.9839.2.1.1.104
c23_onCompressor 3 circuit 2 ONro
Integer32
.1.3.6.1.4.1.9839.2.1.1.105
pump1_onPump 1 ONro
Integer32
.1.3.6.1.4.1.9839.2.1.1.106
pump2_onPump 2 ONro
Integer32
.1.3.6.1.4.1.9839.2.1.1.107
on_fan_gr1Fans group 1 ONro
Integer32
.1.3.6.1.4.1.9839.2.1.1.108
on_fan_gr2Fans group 2 ONro
Integer32
.1.3.6.1.4.1.9839.2.1.1.109
fc_onFreecooling or external dry-cooler 1 ONro
Integer32
.1.3.6.1.4.1.9839.2.1.1.110
en_on_off_remRemote on-offrw
Integer32
.1.3.6.1.4.1.9839.2.1.1.130
unit_onChiller ONrw
Integer32
.1.3.6.1.4.1.9839.2.1.1.131
disch_alarm_scw_1Discharge screw compressor 1 alarmro
Integer32
.1.3.6.1.4.1.9839.2.1.1.148
disch_alarm_scw_2Discharge screw compressor 2 alarmro
Integer32
.1.3.6.1.4.1.9839.2.1.1.149
al_probe_inletInlet probe alarm (broken or disconnected)ro
Integer32
.1.3.6.1.4.1.9839.2.1.1.150
al_probe_ambAmbient probe alarm (broken or disconnected)ro
Integer32
.1.3.6.1.4.1.9839.2.1.1.151
al_frigo_fl1Flow switch alarm (cooling alarm)ro
Integer32
.1.3.6.1.4.1.9839.2.1.1.152
al_idro_pump1Pump 1 hydraulic alarmro
Integer32
.1.3.6.1.4.1.9839.2.1.1.153
al_idro_pump2Pump 2 hydraulic alarmro
Integer32
.1.3.6.1.4.1.9839.2.1.1.154
al_idro_fl1Flow switch alarm (hydraulic alarm)ro
Integer32
.1.3.6.1.4.1.9839.2.1.1.155
al_warning_fl1Flow switch alarm (warning alarm)ro
Integer32
.1.3.6.1.4.1.9839.2.1.1.156
al_hi_water_tempHigh Temperature alarmro
Integer32
.1.3.6.1.4.1.9839.2.1.1.157
al_lo_water_tempLow Temperature alarmro
Integer32
.1.3.6.1.4.1.9839.2.1.1.158
al_ta_probe1Antifreeze/evaporator probe 1 alarmro
Integer32
.1.3.6.1.4.1.9839.2.1.1.159
al_hi_pressHigh condensation pressure alarmro
Integer32
.1.3.6.1.4.1.9839.2.1.1.160
al_lo_pressLow condensation pressure alarmro
Integer32
.1.3.6.1.4.1.9839.2.1.1.161
al_probe_evap_1Antifreeze/evaporator probe 1 alarm (broken or disconnected)ro
Integer32
.1.3.6.1.4.1.9839.2.1.1.162
al_probe_evap_2Antifreeze/evaporator probe 2 alarm (broken or disconnected)ro
Integer32
.1.3.6.1.4.1.9839.2.1.1.163
al_hi_press_1High condensation pressure 1 alarmro
Integer32
.1.3.6.1.4.1.9839.2.1.1.164
al_hi_press_2High condensation pressure 2 alarmro
Integer32
.1.3.6.1.4.1.9839.2.1.1.165
al_lo_press_1Low condensation pressure 1 alarmro
Integer32
.1.3.6.1.4.1.9839.2.1.1.166
al_lo_press_2Low condensation pressure 2 alarmro
Integer32
.1.3.6.1.4.1.9839.2.1.1.167
al_probe_tankTank/Out probe alarm (broken or disconnected)ro
Integer32
.1.3.6.1.4.1.9839.2.1.1.168
off_line_1Chiller 1 offlinero
Integer32
.1.3.6.1.4.1.9839.2.1.1.169
off_line_2Chiller 2 offlinero
Integer32
.1.3.6.1.4.1.9839.2.1.1.170
off_line_3Chiller 3 offlinero
Integer32
.1.3.6.1.4.1.9839.2.1.1.171
off_line_4Chiller 4 offlinero
Integer32
.1.3.6.1.4.1.9839.2.1.1.172
off_line_5Chiller 5 offlinero
Integer32
.1.3.6.1.4.1.9839.2.1.1.173
off_line_6Chiller 6 offlinero
Integer32
.1.3.6.1.4.1.9839.2.1.1.174
off_line_7Chiller 7 offlinero
Integer32
.1.3.6.1.4.1.9839.2.1.1.175
off_line_8Chiller 8 offlinero
Integer32
.1.3.6.1.4.1.9839.2.1.1.176
al_ta_probe2Antifreeze/evaporator probe 2 alarmro
Integer32
.1.3.6.1.4.1.9839.2.1.1.177
al_smsSMS alarmro
Integer32
.1.3.6.1.4.1.9839.2.1.1.178
al_modemModem alarmro
Integer32
.1.3.6.1.4.1.9839.2.1.1.179
sms_coda_alarmSMS coda alarmro
Integer32
.1.3.6.1.4.1.9839.2.1.1.180
al_probe_fcFreecooling probe alarm (broken or disconnected)ro
Integer32
.1.3.6.1.4.1.9839.2.1.1.181
al_maint_pw1Maintenance pump 1 alarm)ro
Integer32
.1.3.6.1.4.1.9839.2.1.1.182
al_maint_pw2Maintenance pump 2 alarm)ro
Integer32
.1.3.6.1.4.1.9839.2.1.1.183
al_hi_temp_ridHigh temperature alarm (redundance)ro
Integer32
.1.3.6.1.4.1.9839.2.1.1.184
al_q_fc_sepDryCooler breaker switch alarmro
Integer32
.1.3.6.1.4.1.9839.2.1.1.185
al_p_wat2Water pressure 2 alarmro
Integer32
.1.3.6.1.4.1.9839.2.1.1.186
al_p_wat1Water pressure 1 alarmro
Integer32
.1.3.6.1.4.1.9839.2.1.1.187
al_foult_flow_p1Pump 1 flow alarmro
Integer32
.1.3.6.1.4.1.9839.2.1.1.188
al_foult_flow_p2Pump 2 flow alarmro
Integer32
.1.3.6.1.4.1.9839.2.1.1.189
al_foult_fl1_p1Pump 1 flow-switch alarmro
Integer32
.1.3.6.1.4.1.9839.2.1.1.190
al_foult_fl1_p2Pump 2 flow-switch alarmro
Integer32
.1.3.6.1.4.1.9839.2.1.1.191
al_warning_leWater level warningro
Integer32
.1.3.6.1.4.1.9839.2.1.1.192
al_frigo_fl_CFlow switch condensation alarm (cooling alarm)ro
Integer32
.1.3.6.1.4.1.9839.2.1.1.193
al_idro_pump_c_1Pump 1 condensation hydraulic alarmro
Integer32
.1.3.6.1.4.1.9839.2.1.1.194
al_idro_pump_c_2Pump 2 condensation hydraulic alarmro
Integer32
.1.3.6.1.4.1.9839.2.1.1.195
al_idro_fl_CFlow switch condensation alarm (hydraulic alarm)ro
Integer32
.1.3.6.1.4.1.9839.2.1.1.196
al_warning_fl_CFlow switch condensation alarm (warning alarm)ro
Integer32
.1.3.6.1.4.1.9839.2.1.1.197
al_foul_fl_C_p1Pump 1 condensation flow-switch alarmro
Integer32
.1.3.6.1.4.1.9839.2.1.1.198
al_foul_fl_C_p2Pump 2 condensation flow-switch alarmro
Integer32
.1.3.6.1.4.1.9839.2.1.1.199
analogObjects
OBJECT IDENTIFIER
.1.3.6.1.4.1.9839.2.1.2
setpoint_antifreeze1Setpoint Antifreeze 1rw
Integer32
.1.3.6.1.4.1.9839.2.1.2.1
setpoint_antifreeze2Setpoint Antifreeze 2rw
Integer32
.1.3.6.1.4.1.9839.2.1.2.2
setpoint_CompensationSetpoint Compensationrw
Integer32
.1.3.6.1.4.1.9839.2.1.2.3
hysteresis_CompensationHysteresis Compensationrw
Integer32
.1.3.6.1.4.1.9839.2.1.2.4
max_CompensationMax. Compensationrw
Integer32
.1.3.6.1.4.1.9839.2.1.2.5
setpoint_DifferentialSetpoint Differentialrw
Integer32
.1.3.6.1.4.1.9839.2.1.2.6
high_LimitHigh Limitrw
Integer32
.1.3.6.1.4.1.9839.2.1.2.7
low_LimitLow Limitrw
Integer32
.1.3.6.1.4.1.9839.2.1.2.8
max_Setpoint_DifferentialMax. Setpoint Differentialrw
Integer32
.1.3.6.1.4.1.9839.2.1.2.9
min_Setpoint_DifferentialMin. Setpoint Differentialrw
Integer32
.1.3.6.1.4.1.9839.2.1.2.10
setpoint_ASB_Inverter_pumpsSetpoint ASB Inverter pumpsrw
Integer32
.1.3.6.1.4.1.9839.2.1.2.11
setpoint_DIFF_Inverter_pumpsSetpoint DIFF Inverter pumpsrw
Integer32
.1.3.6.1.4.1.9839.2.1.2.12
pressure_OutPressure Outro
Integer32
.1.3.6.1.4.1.9839.2.1.2.13
proportional_Band_Inverter_Pumps_PIDProportional Band Inverter Pumps PIDrw
Integer32
.1.3.6.1.4.1.9839.2.1.2.14
integral_Time_Inverter_Pumps_PIDIntegral Time Inverter Pumps PIDrw
Integer32
.1.3.6.1.4.1.9839.2.1.2.15
derivative_Time_Inverter_Pumps_PIDDerivative Time Inverter Pumps PIDrw
Integer32
.1.3.6.1.4.1.9839.2.1.2.16
hysteresis_Thermal_redundanceHysteresis Thermal redundancerw
Integer32
.1.3.6.1.4.1.9839.2.1.2.17
min_Opening_3Way_Valve_HydraulicMin. Opening 3Way Valve Hydraulicrw
Integer32
.1.3.6.1.4.1.9839.2.1.2.18
max_Opening_3Way_Valve_HydraulicMax. Opening 3Way Valve Hydraulicrw
Integer32
.1.3.6.1.4.1.9839.2.1.2.19
proportional_Band_3Way_Valve_Hydrauli_PIDProportional Band 3Way Valve Hydraulic PIDrw
Integer32
.1.3.6.1.4.1.9839.2.1.2.20
setpoint_FCMSetpoint FCMrw
Integer32
.1.3.6.1.4.1.9839.2.1.2.21
hysteresis_FCMHysteresis FCMrw
Integer32
.1.3.6.1.4.1.9839.2.1.2.22
max_Out_Speed_FCMMax. Out Speed FCMrw
Integer32
.1.3.6.1.4.1.9839.2.1.2.23
min_Out_Speed_FCMMin. Out Speed FCMrw
Integer32
.1.3.6.1.4.1.9839.2.1.2.24
hysteresis_Cut_off_FCMHysteresis Cut-off FCMrw
Integer32
.1.3.6.1.4.1.9839.2.1.2.25
max_Pressure_Alarm_FCMMax. Pressure Alarm FCMrw
Integer32
.1.3.6.1.4.1.9839.2.1.2.26
hysteresis_Max_Pressure_Alarm_FCMHysteresis Max.Pressure Alarm FCMrw
Integer32
.1.3.6.1.4.1.9839.2.1.2.27
max_Out_FCMMax. Out FCMrw
Integer32
.1.3.6.1.4.1.9839.2.1.2.28
min_Pressure_Alarm_FCMMin. Pressure Alarm FCMrw
Integer32
.1.3.6.1.4.1.9839.2.1.2.29
hysteresis_Min_Pressure_Alarm_FCMHysteresis Min.Pressure Alarm FCMrw
Integer32
.1.3.6.1.4.1.9839.2.1.2.30
min_Out_FCMMin. Out FCMrw
Integer32
.1.3.6.1.4.1.9839.2.1.2.31
delta_FreecoolingDelta Freecoolingrw
Integer32
.1.3.6.1.4.1.9839.2.1.2.32
hysteresis_FreecoolingHysteresis Freecoolingrw
Integer32
.1.3.6.1.4.1.9839.2.1.2.33
proportional_Band_Freecooling_PIDProportional Band Freecooling PIDrw
Integer32
.1.3.6.1.4.1.9839.2.1.2.34
offset_Freecooling_PIDOffset Freecooling PIDrw
Integer32
.1.3.6.1.4.1.9839.2.1.2.35
temperature_Overlap_FreecoolingTemperature Overlap Freecoolingrw
Integer32
.1.3.6.1.4.1.9839.2.1.2.36
min_out_freecoolingMin. out freecoolingrw
Integer32
.1.3.6.1.4.1.9839.2.1.2.37
neutral_zone_K_costantNeutral zone K costantrw
Integer32
.1.3.6.1.4.1.9839.2.1.2.38
neutral_zone_V_variableNeutral zone V variablerw
Integer32
.1.3.6.1.4.1.9839.2.1.2.39
proportional_Band_freecooling_Valve_PIDProportional Band freecooling Valve PIDrw
Integer32
.1.3.6.1.4.1.9839.2.1.2.40
offset_Freecooling_Valve_PIDOffset Freecooling Valve PIDrw
Integer32
.1.3.6.1.4.1.9839.2.1.2.41
temperature_A_BTemperature A-Bro
Integer32
.1.3.6.1.4.1.9839.2.1.2.42
delta_Thermal_Excusion_FreecolingDelta Thermal Excusion Freecolingrw
Integer32
.1.3.6.1.4.1.9839.2.1.2.43
hysteresis_Thermal_Excusion_Freecolinghysteresis Thermal Excusion Freecolingrw
Integer32
.1.3.6.1.4.1.9839.2.1.2.44
alarm_Setpoint_Static_Pressure_Hydraulic_circuitAlarm Setpoint Static Pressure Hydraulic circuitrw
Integer32
.1.3.6.1.4.1.9839.2.1.2.45
warnig_Setpoint_Static_Pressure_Hydraulic_circuitWarnig Setpoint Static Pressure Hydraulic circuitrw
Integer32
.1.3.6.1.4.1.9839.2.1.2.46
alarm_Setpoint_Differential_Pressure_Hydraulic_circuitAlarm Setpoint Differential Pressure Hydraulic circuitrw
Integer32
.1.3.6.1.4.1.9839.2.1.2.47
alarm_Setpoint_Flow_Rate_Hydraulic_circuitAlarm Setpoint Flow-Rate Hydraulic circuitrw
Integer32
.1.3.6.1.4.1.9839.2.1.2.48
tempertaure_Cut_off_FCMTempertaure Cut-off FCMrw
Integer32
.1.3.6.1.4.1.9839.2.1.2.50
set_effectiveSet-effectivero
Integer32
.1.3.6.1.4.1.9839.2.1.2.59
set_fcFreecooling or drycooler Set-pointro
Integer32
.1.3.6.1.4.1.9839.2.1.2.60
setpoint_a_usSet-point MAINrw
Integer32
.1.3.6.1.4.1.9839.2.1.2.61
max_setpointMax.setpointrw
Integer32
.1.3.6.1.4.1.9839.2.1.2.62
min_setpointMin.setpointrw
Integer32
.1.3.6.1.4.1.9839.2.1.2.63
diffdifferentialrw
Integer32 (-999..999) UNITS "N/A"
.1.3.6.1.4.1.9839.2.1.2.64
max_diffMax. differentialrw
Integer32
.1.3.6.1.4.1.9839.2.1.2.65
min_diffMin.Differentialrw
Integer32
.1.3.6.1.4.1.9839.2.1.2.66
fcs_outFans speed controller output %ro
Integer32
.1.3.6.1.4.1.9839.2.1.2.67
water_tempTank - Process water temperaturero
Integer32
.1.3.6.1.4.1.9839.2.1.2.70
temp_inletWater inlet temperaturero
Integer32
.1.3.6.1.4.1.9839.2.1.2.71
temp_outletWater outlet temperaturero
Integer32
.1.3.6.1.4.1.9839.2.1.2.72
flow_valueFlow rate valuero
Integer32
.1.3.6.1.4.1.9839.2.1.2.73
amp_valueCurrent cunsumptionro
Integer32
.1.3.6.1.4.1.9839.2.1.2.74
ta_probe_temp_1Antifreeze 1 temperature monitoringro
Integer32
.1.3.6.1.4.1.9839.2.1.2.75
ta_probe_temp_2Antifreeze 2 temperature monitoringro
Integer32
.1.3.6.1.4.1.9839.2.1.2.76
pressione1Condensation pressure circuit 1ro
Integer32 (-999..999) UNITS "N/A"
.1.3.6.1.4.1.9839.2.1.2.77
pressione2Condensation pressure circuit 2ro
Integer32 (-999..999) UNITS "N/A"
.1.3.6.1.4.1.9839.2.1.2.78
pump_sp_pressPump discharge pressurero
Integer32
.1.3.6.1.4.1.9839.2.1.2.79
p_wat2Pump suction or static pressurero
Integer32
.1.3.6.1.4.1.9839.2.1.2.80
temp_ambAmbient temperaturero
Integer32
.1.3.6.1.4.1.9839.2.1.2.81
temp_fcInlet - freecooling temperaturero
Integer32
.1.3.6.1.4.1.9839.2.1.2.82
pp1Pump 1 speedro
Integer32
.1.3.6.1.4.1.9839.2.1.2.90
pp2Pump 2 speedro
Integer32
.1.3.6.1.4.1.9839.2.1.2.91
cooling_capacityCooling Capacityro
Integer32
.1.3.6.1.4.1.9839.2.1.2.100
freecooling_capacityFreeCooling Capacityro
Integer32
.1.3.6.1.4.1.9839.2.1.2.101
total_capacityTotalCooling Capacityro
Integer32
.1.3.6.1.4.1.9839.2.1.2.102
integerObjects
OBJECT IDENTIFIER
.1.3.6.1.4.1.9839.2.1.3
ip_Address1IP Address 1 (XXX.xxx.xxx.xxx)ro
Integer32
.1.3.6.1.4.1.9839.2.1.3.6
ip_Address2IP Address 2 (xxx.XXX.xxx.xxx)ro
Integer32
.1.3.6.1.4.1.9839.2.1.3.7
ip_Address3IP Address 3 (xxx.xxx.XXX.xxx)ro
Integer32
.1.3.6.1.4.1.9839.2.1.3.8
ip_Address4IP Address 4 (xxx.xxx.xxx.XXX)ro
Integer32
.1.3.6.1.4.1.9839.2.1.3.9
netMaskNetMask 8-16-24-32ro
Integer32
.1.3.6.1.4.1.9839.2.1.3.10
gateway1Gateway 1 (XXX.xxx.xxx.xxx)ro
Integer32
.1.3.6.1.4.1.9839.2.1.3.11
gateway2Gateway 2 (xxx.XXX.xxx.xxx)ro
Integer32
.1.3.6.1.4.1.9839.2.1.3.12
gateway3Gateway 3 (xxx.xxx.XXX.xxx)ro
Integer32
.1.3.6.1.4.1.9839.2.1.3.13
gateway4Gateway 4 (xxx.xxx.xxx.XXX)ro
Integer32
.1.3.6.1.4.1.9839.2.1.3.14
dns1_1DNS (1) 1 (XXX.xxx.xxx.xxx)ro
Integer32
.1.3.6.1.4.1.9839.2.1.3.15
dns1_2DNS (1) 2 (xxx.XXX.xxx.xxx)ro
Integer32
.1.3.6.1.4.1.9839.2.1.3.16
dns1_3DNS (1) 3 (xxx.xxx.XXX.xxx)ro
Integer32
.1.3.6.1.4.1.9839.2.1.3.17
dns1_4DNS (1) 4 (xxx.xxx.xxx.XXX)ro
Integer32
.1.3.6.1.4.1.9839.2.1.3.18
dns2_1DNS (2) 1 (XXX.xxx.xxx.xxx)ro
Integer32
.1.3.6.1.4.1.9839.2.1.3.19
dns2_2DNS (2) 2 (xxx.XXX.xxx.xxx)ro
Integer32
.1.3.6.1.4.1.9839.2.1.3.20
dns2_3DNS (2) 3 (xxx.xxx.XXX.xxx)ro
Integer32
.1.3.6.1.4.1.9839.2.1.3.21
dns2_4DNS (2) 4 (xxx.xxx.xxx.XXX)ro
Integer32
.1.3.6.1.4.1.9839.2.1.3.22
ip_Address1_OutIP Address Out 1 (XXX.xxx.xxx.xxx)ro
Integer32
.1.3.6.1.4.1.9839.2.1.3.26
ip_Address2_OutIP Address Out 2 (xxx.XXX.xxx.xxx)ro
Integer32
.1.3.6.1.4.1.9839.2.1.3.27
ip_Address3_OutIP Address Out 3 (xxx.xxx.XXX.xxx)ro
Integer32
.1.3.6.1.4.1.9839.2.1.3.28
ip_Address4_OutIP Address Out 4 (xxx.xxx.xxx.XXX)ro
Integer32
.1.3.6.1.4.1.9839.2.1.3.29
starting_delay_Second_PumpStarting delay Second Pumprw
Integer32
.1.3.6.1.4.1.9839.2.1.3.30
starting_delay_btw_Pump_CompressorStarting delay btw Pump - Compressorrw
Integer32
.1.3.6.1.4.1.9839.2.1.3.31
overlap_time_PumpsOverlap time Pumpsrw
Integer32
.1.3.6.1.4.1.9839.2.1.3.32
working_time_PumpsWorking time Pumpsrw
Integer32
.1.3.6.1.4.1.9839.2.1.3.33
running_time_ChillersRunning time Chillersrw
Integer32
.1.3.6.1.4.1.9839.2.1.3.34
overlap_time_ChillersOverlap time Chillersrw
Integer32
.1.3.6.1.4.1.9839.2.1.3.35
n_chillers_MaxN chillers Maxrw
Integer32
.1.3.6.1.4.1.9839.2.1.3.36
n_chillers_ONN chillers ONrw
Integer32
.1.3.6.1.4.1.9839.2.1.3.37
n_pumps_ONN pumps ONrw
Integer32
.1.3.6.1.4.1.9839.2.1.3.38
time_Enable_Pumps_Chiller_OfflineTime Enable Pumps - Chiller Offlinerw
Integer32
.1.3.6.1.4.1.9839.2.1.3.39
time_Running_Pumps_Chiller_OfflineTime Running Pumps - Chiller Offlinerw
Integer32
.1.3.6.1.4.1.9839.2.1.3.40
integral_Time_3Way_Valve_Hydraulic_PIDIntegral Time 3Way Valve Hydraulic (PID)rw
Integer32
.1.3.6.1.4.1.9839.2.1.3.41
derivative_Time_3Way_Valve_Hydraulic_PIDDerivative Time 3Way Valve Hydraulic (PID)rw
Integer32
.1.3.6.1.4.1.9839.2.1.3.42
output_Address_3Way_Valve_HydraulicOutput Address 3Way Valve Hydraulicrw
Integer32
.1.3.6.1.4.1.9839.2.1.3.43
time_Speed_Up_FCMTime Speed-Up (FCM)rw
Integer32
.1.3.6.1.4.1.9839.2.1.3.44
time_Soft_Start_FCMTime Soft-Start (FCM)rw
Integer32
.1.3.6.1.4.1.9839.2.1.3.45
delay_FreecoolingDelay Freecoolingrw
Integer32
.1.3.6.1.4.1.9839.2.1.3.47
integral_Time_Freeccoling_PIDIntegral Time Freeccoling (PID)rw
Integer32
.1.3.6.1.4.1.9839.2.1.3.48
derivative_Time_Freeccoling_PIDDerivative Time Freeccoling (PID)rw
Integer32
.1.3.6.1.4.1.9839.2.1.3.49
time_Min_On_Freecooling_Chiller_timingTime Min. On (Freecooling - Chiller timing)rw
Integer32
.1.3.6.1.4.1.9839.2.1.3.50
time_Min_Off_Freecooling_Chiller_timingTime Min. Off (Freecooling - Chiller timing)rw
Integer32
.1.3.6.1.4.1.9839.2.1.3.51
time_Min_Different_Freecooling_Chiller_timingTime Min. Different (Freecooling - Chiller timing)rw
Integer32
.1.3.6.1.4.1.9839.2.1.3.52
time_Min_Same_Freecooling_Chiller_timingTime Min. Same (Freecooling - Chiller timing)rw
Integer32
.1.3.6.1.4.1.9839.2.1.3.53
integral_Time_Freeccoling_Valve_PIDIntegral Time Freeccoling Valve (PID)rw
Integer32
.1.3.6.1.4.1.9839.2.1.3.54
derivative_Time_Freeccoling_Valve_PIDDerivative Time Freeccoling Valve (PID)rw
Integer32
.1.3.6.1.4.1.9839.2.1.3.55
output_Address_Valve_FreecoolingOutput Address Valve Freecoolingrw
Integer32
.1.3.6.1.4.1.9839.2.1.3.56
delay_Freecooling_Thermal_ExclusionDelay Freecoolimg Thermal Exclusionrw
Integer32
.1.3.6.1.4.1.9839.2.1.3.57
n_of_alarm_External_Dry_CoolerN of alarm (External Dry-Cooler)rw
Integer32
.1.3.6.1.4.1.9839.2.1.3.58
delay_Alarm_Static_PressureDelay Alarm (Static Pressure)rw
Integer32
.1.3.6.1.4.1.9839.2.1.3.59
n_of_Alarm_Static_PressureN of Alarm (Static Pressure)rw
Integer32
.1.3.6.1.4.1.9839.2.1.3.60
delay_Warning_Static_PressureDelay Warning (Static Pressure)rw
Integer32
.1.3.6.1.4.1.9839.2.1.3.61
n_of_Warning_Static_PressureN of Warning (Static Pressure)rw
Integer32
.1.3.6.1.4.1.9839.2.1.3.62
n_of_Alarm_Differential_PressureN of Alarm (Differential Pressure)rw
Integer32
.1.3.6.1.4.1.9839.2.1.3.63
priming_Time_Hydraulic_PressurePriming Time (Hydraulic Pressure)rw
Integer32
.1.3.6.1.4.1.9839.2.1.3.64
delay_priming_Time_Hydraulic_PressureDelay Priming Time (Hydraulic Pressure)rw
Integer32
.1.3.6.1.4.1.9839.2.1.3.65
output_Address_Alarm_Static_PressureOutput Address Alarm (Static Pressure)rw
Integer32
.1.3.6.1.4.1.9839.2.1.3.66
n_of_Alarm_Flow_RateN of Alarm (Flow Rate)rw
Integer32
.1.3.6.1.4.1.9839.2.1.3.67
priming_Time_Flow_RatePriming Time (Flow Rate)rw
Integer32
.1.3.6.1.4.1.9839.2.1.3.68
delay_priming_Time_Flow_RateDelay Priming Time (Flow Rate)rw
Integer32
.1.3.6.1.4.1.9839.2.1.3.69
bms_address_IDENTBMS address (IDENT)ro
Integer32
.1.3.6.1.4.1.9839.2.1.3.70
chiller_name0Chiller Model - Article Number - 0ro
Integer32
.1.3.6.1.4.1.9839.2.1.3.99
chiller_name1Chiller Model - Article Number - 1ro
Integer32
.1.3.6.1.4.1.9839.2.1.3.100
current_dayCurrent Dayro
Integer32
.1.3.6.1.4.1.9839.2.1.3.123
current_monthCurrent Monthro
Integer32
.1.3.6.1.4.1.9839.2.1.3.124
current_yearCurrent Yearro
Integer32
.1.3.6.1.4.1.9839.2.1.3.125
current_hourCurrent Hourro
Integer32
.1.3.6.1.4.1.9839.2.1.3.126
current_minuteCurrent Minutero
Integer32
.1.3.6.1.4.1.9839.2.1.3.127
chiller_mode_operationChiller mode operationro
Integer32
.1.3.6.1.4.1.9839.2.1.3.150
trapObjects
OBJECT IDENTIFIER
.1.3.6.1.4.1.9839.2.1.100
high_pressure_switch_1_alarmHigh pressure switch 1 alarm
NOTIFICATION-TYPE
.1.3.6.1.4.1.9839.2.1.100.1
high_pressure_switch_2_alarmHigh pressure switch 2 alarm
NOTIFICATION-TYPE
.1.3.6.1.4.1.9839.2.1.100.2
low_pressure_switch_1_alarmLow pressure switch 1 alarm
NOTIFICATION-TYPE
.1.3.6.1.4.1.9839.2.1.100.3
low_pressure_switch_2_alarmLow pressure switch 2 alarm
NOTIFICATION-TYPE
.1.3.6.1.4.1.9839.2.1.100.4
water_level_alarmWater level alarm
NOTIFICATION-TYPE
.1.3.6.1.4.1.9839.2.1.100.6
flow_switch_alarmFlow switch alarm
NOTIFICATION-TYPE
.1.3.6.1.4.1.9839.2.1.100.8
water_static_pressure_alarmWater static pressure alarm
NOTIFICATION-TYPE
.1.3.6.1.4.1.9839.2.1.100.9
water_static_pressure_warningWater static pressure warning
NOTIFICATION-TYPE
.1.3.6.1.4.1.9839.2.1.100.10
flow_rate_alarmFlow rate alarm
NOTIFICATION-TYPE
.1.3.6.1.4.1.9839.2.1.100.11
overload_compressor1_circuit1_alarmOverload compressor 1 circuit 1 alarm
NOTIFICATION-TYPE
.1.3.6.1.4.1.9839.2.1.100.12
overload_compressor2_circuit1_alarmOverload compressor 2 circuit 1 alarm
NOTIFICATION-TYPE
.1.3.6.1.4.1.9839.2.1.100.13
overload_compressor3_circuit1_alarmOverload compressor 3 circuit 1 alarm
NOTIFICATION-TYPE
.1.3.6.1.4.1.9839.2.1.100.14
overload_compressor1_circuit2_alarmOverload compressor 1 circuit 2 alarm
NOTIFICATION-TYPE
.1.3.6.1.4.1.9839.2.1.100.15
overload_compressor2_circuit2_alarmOverload compressor 2 circuit 2 alarm
NOTIFICATION-TYPE
.1.3.6.1.4.1.9839.2.1.100.16
overload_compressor3_circuit2_alarmOverload compressor 3 circuit 2 alarm
NOTIFICATION-TYPE
.1.3.6.1.4.1.9839.2.1.100.17
overload_fans_circuit1Overload fans circuit 1
NOTIFICATION-TYPE
.1.3.6.1.4.1.9839.2.1.100.18
overload_fans_circuit2Overload fans circuit 2
NOTIFICATION-TYPE
.1.3.6.1.4.1.9839.2.1.100.19
overload_fan1_circuit1_alarmOverload fan 1 circuit 1 alarm
NOTIFICATION-TYPE
.1.3.6.1.4.1.9839.2.1.100.20
overload_fan2_circuit1_alarmOverload fan 2 circuit 1 alarm
NOTIFICATION-TYPE
.1.3.6.1.4.1.9839.2.1.100.21
overload_fan3_circuit1_alarmOverload fan 3 circuit 1 alarm
NOTIFICATION-TYPE
.1.3.6.1.4.1.9839.2.1.100.22
overload_fan4_circuit1_alarmOverload fan 4 circuit 1 alarm
NOTIFICATION-TYPE
.1.3.6.1.4.1.9839.2.1.100.23
overload_fan1_circuit_2_alarmOverload fan 1 circuit 2 alarm
NOTIFICATION-TYPE
.1.3.6.1.4.1.9839.2.1.100.24
overload_fan2_circuit2_alarmOverload fan 2 circuit 2 alarm
NOTIFICATION-TYPE
.1.3.6.1.4.1.9839.2.1.100.25
overload_fan3_circuit2_alarmOverload fan 3 circuit 2 alarm
NOTIFICATION-TYPE
.1.3.6.1.4.1.9839.2.1.100.26
overload_fan4_circuit2_alarmOverload fan 4 circuit 2 alarm
NOTIFICATION-TYPE
.1.3.6.1.4.1.9839.2.1.100.27
overload_pump1_alarmOverload pump 1 alarm
NOTIFICATION-TYPE
.1.3.6.1.4.1.9839.2.1.100.28
overload_pump2_alarmOverload pump 2 alarm
NOTIFICATION-TYPE
.1.3.6.1.4.1.9839.2.1.100.29
wrong_phase_rotation_alarmWrong phase rotation alarm
NOTIFICATION-TYPE
.1.3.6.1.4.1.9839.2.1.100.30
back_Door_open_alarmBack Door open alarm
NOTIFICATION-TYPE
.1.3.6.1.4.1.9839.2.1.100.31
alarm_idrofrigo_pump_c_1Condensation pump 1 breaker switch alarm
NOTIFICATION-TYPE
.1.3.6.1.4.1.9839.2.1.100.75
alarm_idrofrigo_pump_c_2Condensation pump 2 breaker switch alarm
NOTIFICATION-TYPE
.1.3.6.1.4.1.9839.2.1.100.76
alarm_idrofrigo_fl_CCondensation flow switch alarm
NOTIFICATION-TYPE
.1.3.6.1.4.1.9839.2.1.100.80
remote_on_offRemote on-off
NOTIFICATION-TYPE
.1.3.6.1.4.1.9839.2.1.100.130
chiller_ON_OFFChiller ON/OFF
NOTIFICATION-TYPE
.1.3.6.1.4.1.9839.2.1.100.131
alarm_disch_scw_1Discharge screw compressor 1 alarm
NOTIFICATION-TYPE
.1.3.6.1.4.1.9839.2.1.100.148
alarm_disch_scw_2Discharge screw compressor 2 alarm
NOTIFICATION-TYPE
.1.3.6.1.4.1.9839.2.1.100.149
alarm_probe_inletInlet probe alarm (broken or disconnected)
NOTIFICATION-TYPE
.1.3.6.1.4.1.9839.2.1.100.150
alarm_probe_ambAmbient probe alarm (broken or disconnected)
NOTIFICATION-TYPE
.1.3.6.1.4.1.9839.2.1.100.151
alarm_frigo_fl1Flow switch alarm (cooling alarm)
NOTIFICATION-TYPE
.1.3.6.1.4.1.9839.2.1.100.152
alarm_idro_pump1Pump 1 hydraulic alarm
NOTIFICATION-TYPE
.1.3.6.1.4.1.9839.2.1.100.153
alarm_idro_pump2Pump 2 hydraulic alarm
NOTIFICATION-TYPE
.1.3.6.1.4.1.9839.2.1.100.154
alarm_idro_fl1Flow switch alarm (hydraulic alarm)
NOTIFICATION-TYPE
.1.3.6.1.4.1.9839.2.1.100.155
alarm_warning_fl1Flow switch alarm (warning alarm)
NOTIFICATION-TYPE
.1.3.6.1.4.1.9839.2.1.100.156
alarm_hi_water_tempHigh Temperature alarm
NOTIFICATION-TYPE
.1.3.6.1.4.1.9839.2.1.100.157
alarm_lo_water_tempLow Temperature alarm
NOTIFICATION-TYPE
.1.3.6.1.4.1.9839.2.1.100.158
alarm_ta_probe1Antifreeze/evaporator probe 1 alarm
NOTIFICATION-TYPE
.1.3.6.1.4.1.9839.2.1.100.159
alarm_hi_pressHigh condensation pressure alarm
NOTIFICATION-TYPE
.1.3.6.1.4.1.9839.2.1.100.160
alarm_lo_pressLow condensation pressure alarm
NOTIFICATION-TYPE
.1.3.6.1.4.1.9839.2.1.100.161
alarm_probe_evap_1Antifreeze/evaporator probe 1 alarm (broken or disconnected)
NOTIFICATION-TYPE
.1.3.6.1.4.1.9839.2.1.100.162
alarm_probe_evap_2Antifreeze/evaporator probe 2 alarm (broken or disconnected)
NOTIFICATION-TYPE
.1.3.6.1.4.1.9839.2.1.100.163
alarm_hi_press_1High condensation pressure 1 alarm
NOTIFICATION-TYPE
.1.3.6.1.4.1.9839.2.1.100.164
alarm_hi_press_2High condensation pressure 2 alarm
NOTIFICATION-TYPE
.1.3.6.1.4.1.9839.2.1.100.165
alarm_lo_press_1Low condensation pressure 1 alarm
NOTIFICATION-TYPE
.1.3.6.1.4.1.9839.2.1.100.166
alarm_lo_press_2Low condensation pressure 2 alarm
NOTIFICATION-TYPE
.1.3.6.1.4.1.9839.2.1.100.167
alarm_probe_tankTank/Out probe alarm (broken or disconnected)
NOTIFICATION-TYPE
.1.3.6.1.4.1.9839.2.1.100.168
alarm_off_line_1Chiller 1 offline
NOTIFICATION-TYPE
.1.3.6.1.4.1.9839.2.1.100.169
alarm_off_line_2Chiller 2 offline
NOTIFICATION-TYPE
.1.3.6.1.4.1.9839.2.1.100.170
alarm_off_line_3Chiller 3 offline
NOTIFICATION-TYPE
.1.3.6.1.4.1.9839.2.1.100.171
alarm_off_line_4Chiller 4 offline
NOTIFICATION-TYPE
.1.3.6.1.4.1.9839.2.1.100.172
alarm_off_line_5Chiller 5 offline
NOTIFICATION-TYPE
.1.3.6.1.4.1.9839.2.1.100.173
alarm_off_line_6Chiller 6 offline
NOTIFICATION-TYPE
.1.3.6.1.4.1.9839.2.1.100.174
alarm_off_line_7Chiller 7 offline
NOTIFICATION-TYPE
.1.3.6.1.4.1.9839.2.1.100.175
alarm_off_line_8Chiller 8 offline
NOTIFICATION-TYPE
.1.3.6.1.4.1.9839.2.1.100.176
alarm_ta_probe2Antifreeze/evaporator probe 2 alarm
NOTIFICATION-TYPE
.1.3.6.1.4.1.9839.2.1.100.177
alarm_smsSMS alarm
NOTIFICATION-TYPE
.1.3.6.1.4.1.9839.2.1.100.178
alarm_modemModem alarm
NOTIFICATION-TYPE
.1.3.6.1.4.1.9839.2.1.100.179
alarm_sms_codaSMS coda alarm
NOTIFICATION-TYPE
.1.3.6.1.4.1.9839.2.1.100.180
alarm_probe_fcFreecooling probe alarm (broken or disconnected)
NOTIFICATION-TYPE
.1.3.6.1.4.1.9839.2.1.100.181
alarm_maint_pw1Maintenance pump 1 alarm)
NOTIFICATION-TYPE
.1.3.6.1.4.1.9839.2.1.100.182
alarm_maint_pw2Maintenance pump 2 alarm)
NOTIFICATION-TYPE
.1.3.6.1.4.1.9839.2.1.100.183
alarm_hi_temp_ridHigh temperature alarm (redundance)
NOTIFICATION-TYPE
.1.3.6.1.4.1.9839.2.1.100.184
alarm_q_fc_sepDryCooler breaker switch alarm
NOTIFICATION-TYPE
.1.3.6.1.4.1.9839.2.1.100.185
alarm_p_wat2Water pressure 2 alarm
NOTIFICATION-TYPE
.1.3.6.1.4.1.9839.2.1.100.186
alarm_p_wat1Water pressure 1 alarm
NOTIFICATION-TYPE
.1.3.6.1.4.1.9839.2.1.100.187
alarm_foult_flow_p1Pump 1 flow alarm
NOTIFICATION-TYPE
.1.3.6.1.4.1.9839.2.1.100.188
alarm_foult_flow_p2Pump 2 flow alarm
NOTIFICATION-TYPE
.1.3.6.1.4.1.9839.2.1.100.189
alarm_foult_fl1_p1Pump 1 flow-switch alarm
NOTIFICATION-TYPE
.1.3.6.1.4.1.9839.2.1.100.190
alarm_foult_fl1_p2Pump 2 flow-switch alarm
NOTIFICATION-TYPE
.1.3.6.1.4.1.9839.2.1.100.191
alarm_warning_leWater level warning
NOTIFICATION-TYPE
.1.3.6.1.4.1.9839.2.1.100.192
alarm_frigo_fl_CFlow switch condensation alarm (cooling alarm)
NOTIFICATION-TYPE
.1.3.6.1.4.1.9839.2.1.100.193
alarm_idro_pump_c_1Pump 1 condensation hydraulic alarm
NOTIFICATION-TYPE
.1.3.6.1.4.1.9839.2.1.100.194
alarm_idro_pump_c_2Pump 2 condensation hydraulic alarm
NOTIFICATION-TYPE
.1.3.6.1.4.1.9839.2.1.100.195
alarm_idro_fl_CFlow switch condensation alarm (hydraulic alarm)
NOTIFICATION-TYPE
.1.3.6.1.4.1.9839.2.1.100.196
alarm_warning_fl_CFlow switch condensation alarm (warning alarm)
NOTIFICATION-TYPE
.1.3.6.1.4.1.9839.2.1.100.197
alarm_foul_fl_C_p1Pump 1 condensation flow-switch alarm
NOTIFICATION-TYPE
.1.3.6.1.4.1.9839.2.1.100.198
alarm_foul_fl_C_p2Pump 2 condensation flow-switch alarm
NOTIFICATION-TYPE
.1.3.6.1.4.1.9839.2.1.100.199