KELVIN-pCOWeb-Chiller-MIB
Imported Objects
Objects
373 total| Object Name |
|---|
carel OBJECT IDENTIFIER .1.3.6.1.4.1.9839 |
systm OBJECT IDENTIFIER .1.3.6.1.4.1.9839.1 |
agentReleaseRelease of the Agent.ro Integer32 UNITS "N/A" .1.3.6.1.4.1.9839.1.1 |
agentCodeCode of the Agent. 2=pCOWeb.ro Integer32 UNITS "N/A" .1.3.6.1.4.1.9839.1.2 |
instruments OBJECT IDENTIFIER .1.3.6.1.4.1.9839.2 |
pCOWebInfo OBJECT IDENTIFIER .1.3.6.1.4.1.9839.2.0 |
pCOStatusgroup OBJECT IDENTIFIER .1.3.6.1.4.1.9839.2.0.10 |
pCOId1_StatusStatus of pCOId1. 0=Offline, 1=Init, 2=Onlinero Integer32 .1.3.6.1.4.1.9839.2.0.10.1 |
pCOErrorsNumbergroup OBJECT IDENTIFIER .1.3.6.1.4.1.9839.2.0.11 |
pCOId1_ErrorsNumberNumber of Communication Errors from pCOId1 to pCOWeb.ro Integer32 .1.3.6.1.4.1.9839.2.0.11.1 |
kelvin_pCOWebMIB_ChillerThis is the MIB module for the kelvin-pCOWeb-Chiller device. MODULE-IDENTITY .1.3.6.1.4.1.9839.2.1 |
digitalObjects OBJECT IDENTIFIER .1.3.6.1.4.1.9839.2.1.1 |
al_pa1High pressure switch 1 alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.1 |
al_pa2High pressure switch 2 alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.2 |
al_pb1Low pressure switch 1 alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.3 |
al_pb2Low pressure switch 2 alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.4 |
al_leWater level alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.6 |
al_idrofrigo_fl1Flow switch alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.8 |
static_press_alarmWater static pressure alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.9 |
w_static_press_alarmWater static pressure warningro Integer32 .1.3.6.1.4.1.9839.2.1.1.10 |
flow_value_alarmFlow rate alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.11 |
al_q_comp1Overload compressor 1 circuit 1 alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.12 |
al_q_comp2Overload compressor 2 circuit 1 alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.13 |
al_q_comp3Overload compressor 3 circuit 1 alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.14 |
al_q_comp4Overload compressor 1 circuit 2 alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.15 |
al_q_comp5Overload compressor 2 circuit 2 alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.16 |
al_q_comp6Overload compressor 3 circuit 2 alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.17 |
al_q_fan_1Overload fans circuit 1ro Integer32 .1.3.6.1.4.1.9839.2.1.1.18 |
al_q_fan_2Overload fans circuit 2ro Integer32 .1.3.6.1.4.1.9839.2.1.1.19 |
al_q_fan11Overload fan 1 circuit 1 alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.20 |
al_q_fan12Overload fan 2 circuit 1 alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.21 |
al_q_fan13Overload fan 3 circuit 1 alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.22 |
al_q_fan14Overload fan 4 circuit 1 alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.23 |
al_q_fan21Overload fan 1 circuit 2 alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.24 |
al_q_fan22Overload fan 2 circuit 2 alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.25 |
al_q_fan_23Overload fan 3 circuit 2 alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.26 |
al_q_fan24Overload fan 4 circuit 2 alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.27 |
al_idrofrigo_pump1Overload pump 1 alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.28 |
al_idrofrigo_pump2Overload pump 2 alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.29 |
al_phase_contWrong phase rotation alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.30 |
al_door_swBack Door open alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.31 |
compressor_FlowRateCompressor FlowRate Managementrw Integer32 .1.3.6.1.4.1.9839.2.1.1.32 |
setpoint_inv_pumpsSetpoint Type for Inverter pumpsrw Integer32 .1.3.6.1.4.1.9839.2.1.1.33 |
enable_pumps_redundanceEnable Pumps redundancerw Integer32 .1.3.6.1.4.1.9839.2.1.1.34 |
enable_chiller_redundanceEnable Chiller redundancerw Integer32 .1.3.6.1.4.1.9839.2.1.1.35 |
status_in_alarmStatus in alarmrw Integer32 .1.3.6.1.4.1.9839.2.1.1.36 |
compressor_recoveryCompressor Recoveryrw Integer32 .1.3.6.1.4.1.9839.2.1.1.37 |
enable_thermal_redundanceEnable Thermal redundancerw Integer32 .1.3.6.1.4.1.9839.2.1.1.38 |
enable_multi_pumps_functionEnable multi-pumps functionrw Integer32 .1.3.6.1.4.1.9839.2.1.1.39 |
enable_pumps_offlineEnable function pumps-Offlinerw Integer32 .1.3.6.1.4.1.9839.2.1.1.40 |
enable_3way_valveEnable 3way valverw Integer32 .1.3.6.1.4.1.9839.2.1.1.41 |
enable_speed_up_FCMEnable speed-up FCMrw Integer32 .1.3.6.1.4.1.9839.2.1.1.42 |
enable_soft_start_FCMEnable soft-start FCMrw Integer32 .1.3.6.1.4.1.9839.2.1.1.43 |
enable_freecoolingEnable Freecoolingrw Integer32 .1.3.6.1.4.1.9839.2.1.1.44 |
enable_rot_FIFO_FCEnable rotation FIFO Freecoolingrw Integer32 .1.3.6.1.4.1.9839.2.1.1.45 |
enable_HT_functionEnable HT-functionrw Integer32 .1.3.6.1.4.1.9839.2.1.1.46 |
enable_PID_Fc_valveEnable PID-regulation for Freecooling valverw Integer32 .1.3.6.1.4.1.9839.2.1.1.47 |
enable_Fc_Thermal_ExclusionEnable Freecooling Thermal Exclusionrw Integer32 .1.3.6.1.4.1.9839.2.1.1.48 |
manual_Reset_Ext_Drycooler_AlarmManual Reset External Dry-cooler Alarmrw Integer32 .1.3.6.1.4.1.9839.2.1.1.49 |
enable_static_press_AlarmEnable static pressure Alarmrw Integer32 .1.3.6.1.4.1.9839.2.1.1.50 |
manual_reset_static_press_AlarmManual reset static pressure Alarmrw Integer32 .1.3.6.1.4.1.9839.2.1.1.51 |
enable_static_press_WarningEnable static pressure Warningrw Integer32 .1.3.6.1.4.1.9839.2.1.1.52 |
manual_reset_static_press_WarningManual reset static pressure Warningrw Integer32 .1.3.6.1.4.1.9839.2.1.1.53 |
enable_diff_press_AlarmEnable differential pressure Alarmrw Integer32 .1.3.6.1.4.1.9839.2.1.1.54 |
manual_reset_diff_press_AlarmManual reset differential pressure Alarmrw Integer32 .1.3.6.1.4.1.9839.2.1.1.55 |
enable_pressure_recoveryEnable pressure recoveryrw Integer32 .1.3.6.1.4.1.9839.2.1.1.56 |
enable_Flow_Rate_AlarmEnable Flow-Rate Alarmrw Integer32 .1.3.6.1.4.1.9839.2.1.1.57 |
manual_reset_Flow_Rate_AlarmManual reset Flow-Rate Alarmrw Integer32 .1.3.6.1.4.1.9839.2.1.1.58 |
enable_Flow_Rate_recoveryEnable Flow-Rate recoveryrw Integer32 .1.3.6.1.4.1.9839.2.1.1.59 |
enable_pCOWebEnable pCOWebrw Integer32 .1.3.6.1.4.1.9839.2.1.1.60 |
fc_single_chillerFreecooling single chiller functionrw Integer32 .1.3.6.1.4.1.9839.2.1.1.61 |
al_idrofrigo_pump_c_1Condensation pump 1 breaker switch alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.75 |
al_idrofrigo_pump_c_2Condensation pump 2 breaker switch alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.76 |
al_idrofrigo_fl_CCondensation flow switch alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.80 |
c11_onCompressor 1 circuit 1 ONro Integer32 .1.3.6.1.4.1.9839.2.1.1.100 |
c12_onCompressor 2 circuit 1 ONro Integer32 .1.3.6.1.4.1.9839.2.1.1.101 |
c13_onCompressor 3 circuit 1 ONro Integer32 .1.3.6.1.4.1.9839.2.1.1.102 |
c21_onCompressor 1 circuit 2 ONro Integer32 .1.3.6.1.4.1.9839.2.1.1.103 |
c22_onCompressor 2 circuit 2 ONro Integer32 .1.3.6.1.4.1.9839.2.1.1.104 |
c23_onCompressor 3 circuit 2 ONro Integer32 .1.3.6.1.4.1.9839.2.1.1.105 |
pump1_onPump 1 ONro Integer32 .1.3.6.1.4.1.9839.2.1.1.106 |
pump2_onPump 2 ONro Integer32 .1.3.6.1.4.1.9839.2.1.1.107 |
on_fan_gr1Fans group 1 ONro Integer32 .1.3.6.1.4.1.9839.2.1.1.108 |
on_fan_gr2Fans group 2 ONro Integer32 .1.3.6.1.4.1.9839.2.1.1.109 |
fc_onFreecooling or external dry-cooler 1 ONro Integer32 .1.3.6.1.4.1.9839.2.1.1.110 |
en_on_off_remRemote on-offrw Integer32 .1.3.6.1.4.1.9839.2.1.1.130 |
unit_onChiller ONrw Integer32 .1.3.6.1.4.1.9839.2.1.1.131 |
disch_alarm_scw_1Discharge screw compressor 1 alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.148 |
disch_alarm_scw_2Discharge screw compressor 2 alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.149 |
al_probe_inletInlet probe alarm (broken or disconnected)ro Integer32 .1.3.6.1.4.1.9839.2.1.1.150 |
al_probe_ambAmbient probe alarm (broken or disconnected)ro Integer32 .1.3.6.1.4.1.9839.2.1.1.151 |
al_frigo_fl1Flow switch alarm (cooling alarm)ro Integer32 .1.3.6.1.4.1.9839.2.1.1.152 |
al_idro_pump1Pump 1 hydraulic alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.153 |
al_idro_pump2Pump 2 hydraulic alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.154 |
al_idro_fl1Flow switch alarm (hydraulic alarm)ro Integer32 .1.3.6.1.4.1.9839.2.1.1.155 |
al_warning_fl1Flow switch alarm (warning alarm)ro Integer32 .1.3.6.1.4.1.9839.2.1.1.156 |
al_hi_water_tempHigh Temperature alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.157 |
al_lo_water_tempLow Temperature alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.158 |
al_ta_probe1Antifreeze/evaporator probe 1 alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.159 |
al_hi_pressHigh condensation pressure alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.160 |
al_lo_pressLow condensation pressure alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.161 |
al_probe_evap_1Antifreeze/evaporator probe 1 alarm (broken or disconnected)ro Integer32 .1.3.6.1.4.1.9839.2.1.1.162 |
al_probe_evap_2Antifreeze/evaporator probe 2 alarm (broken or disconnected)ro Integer32 .1.3.6.1.4.1.9839.2.1.1.163 |
al_hi_press_1High condensation pressure 1 alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.164 |
al_hi_press_2High condensation pressure 2 alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.165 |
al_lo_press_1Low condensation pressure 1 alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.166 |
al_lo_press_2Low condensation pressure 2 alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.167 |
al_probe_tankTank/Out probe alarm (broken or disconnected)ro Integer32 .1.3.6.1.4.1.9839.2.1.1.168 |
off_line_1Chiller 1 offlinero Integer32 .1.3.6.1.4.1.9839.2.1.1.169 |
off_line_2Chiller 2 offlinero Integer32 .1.3.6.1.4.1.9839.2.1.1.170 |
off_line_3Chiller 3 offlinero Integer32 .1.3.6.1.4.1.9839.2.1.1.171 |
off_line_4Chiller 4 offlinero Integer32 .1.3.6.1.4.1.9839.2.1.1.172 |
off_line_5Chiller 5 offlinero Integer32 .1.3.6.1.4.1.9839.2.1.1.173 |
off_line_6Chiller 6 offlinero Integer32 .1.3.6.1.4.1.9839.2.1.1.174 |
off_line_7Chiller 7 offlinero Integer32 .1.3.6.1.4.1.9839.2.1.1.175 |
off_line_8Chiller 8 offlinero Integer32 .1.3.6.1.4.1.9839.2.1.1.176 |
al_ta_probe2Antifreeze/evaporator probe 2 alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.177 |
al_smsSMS alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.178 |
al_modemModem alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.179 |
sms_coda_alarmSMS coda alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.180 |
al_probe_fcFreecooling probe alarm (broken or disconnected)ro Integer32 .1.3.6.1.4.1.9839.2.1.1.181 |
al_maint_pw1Maintenance pump 1 alarm)ro Integer32 .1.3.6.1.4.1.9839.2.1.1.182 |
al_maint_pw2Maintenance pump 2 alarm)ro Integer32 .1.3.6.1.4.1.9839.2.1.1.183 |
al_hi_temp_ridHigh temperature alarm (redundance)ro Integer32 .1.3.6.1.4.1.9839.2.1.1.184 |
al_q_fc_sepDryCooler breaker switch alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.185 |
al_p_wat2Water pressure 2 alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.186 |
al_p_wat1Water pressure 1 alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.187 |
al_foult_flow_p1Pump 1 flow alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.188 |
al_foult_flow_p2Pump 2 flow alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.189 |
al_foult_fl1_p1Pump 1 flow-switch alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.190 |
al_foult_fl1_p2Pump 2 flow-switch alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.191 |
al_warning_leWater level warningro Integer32 .1.3.6.1.4.1.9839.2.1.1.192 |
al_frigo_fl_CFlow switch condensation alarm (cooling alarm)ro Integer32 .1.3.6.1.4.1.9839.2.1.1.193 |
al_idro_pump_c_1Pump 1 condensation hydraulic alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.194 |
al_idro_pump_c_2Pump 2 condensation hydraulic alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.195 |
al_idro_fl_CFlow switch condensation alarm (hydraulic alarm)ro Integer32 .1.3.6.1.4.1.9839.2.1.1.196 |
al_warning_fl_CFlow switch condensation alarm (warning alarm)ro Integer32 .1.3.6.1.4.1.9839.2.1.1.197 |
al_foul_fl_C_p1Pump 1 condensation flow-switch alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.198 |
al_foul_fl_C_p2Pump 2 condensation flow-switch alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.199 |
analogObjects OBJECT IDENTIFIER .1.3.6.1.4.1.9839.2.1.2 |
setpoint_antifreeze1Setpoint Antifreeze 1rw Integer32 .1.3.6.1.4.1.9839.2.1.2.1 |
setpoint_antifreeze2Setpoint Antifreeze 2rw Integer32 .1.3.6.1.4.1.9839.2.1.2.2 |
setpoint_CompensationSetpoint Compensationrw Integer32 .1.3.6.1.4.1.9839.2.1.2.3 |
hysteresis_CompensationHysteresis Compensationrw Integer32 .1.3.6.1.4.1.9839.2.1.2.4 |
max_CompensationMax. Compensationrw Integer32 .1.3.6.1.4.1.9839.2.1.2.5 |
setpoint_DifferentialSetpoint Differentialrw Integer32 .1.3.6.1.4.1.9839.2.1.2.6 |
high_LimitHigh Limitrw Integer32 .1.3.6.1.4.1.9839.2.1.2.7 |
low_LimitLow Limitrw Integer32 .1.3.6.1.4.1.9839.2.1.2.8 |
max_Setpoint_DifferentialMax. Setpoint Differentialrw Integer32 .1.3.6.1.4.1.9839.2.1.2.9 |
min_Setpoint_DifferentialMin. Setpoint Differentialrw Integer32 .1.3.6.1.4.1.9839.2.1.2.10 |
setpoint_ASB_Inverter_pumpsSetpoint ASB Inverter pumpsrw Integer32 .1.3.6.1.4.1.9839.2.1.2.11 |
setpoint_DIFF_Inverter_pumpsSetpoint DIFF Inverter pumpsrw Integer32 .1.3.6.1.4.1.9839.2.1.2.12 |
pressure_OutPressure Outro Integer32 .1.3.6.1.4.1.9839.2.1.2.13 |
proportional_Band_Inverter_Pumps_PIDProportional Band Inverter Pumps PIDrw Integer32 .1.3.6.1.4.1.9839.2.1.2.14 |
integral_Time_Inverter_Pumps_PIDIntegral Time Inverter Pumps PIDrw Integer32 .1.3.6.1.4.1.9839.2.1.2.15 |
derivative_Time_Inverter_Pumps_PIDDerivative Time Inverter Pumps PIDrw Integer32 .1.3.6.1.4.1.9839.2.1.2.16 |
hysteresis_Thermal_redundanceHysteresis Thermal redundancerw Integer32 .1.3.6.1.4.1.9839.2.1.2.17 |
min_Opening_3Way_Valve_HydraulicMin. Opening 3Way Valve Hydraulicrw Integer32 .1.3.6.1.4.1.9839.2.1.2.18 |
max_Opening_3Way_Valve_HydraulicMax. Opening 3Way Valve Hydraulicrw Integer32 .1.3.6.1.4.1.9839.2.1.2.19 |
proportional_Band_3Way_Valve_Hydrauli_PIDProportional Band 3Way Valve Hydraulic PIDrw Integer32 .1.3.6.1.4.1.9839.2.1.2.20 |
setpoint_FCMSetpoint FCMrw Integer32 .1.3.6.1.4.1.9839.2.1.2.21 |
hysteresis_FCMHysteresis FCMrw Integer32 .1.3.6.1.4.1.9839.2.1.2.22 |
max_Out_Speed_FCMMax. Out Speed FCMrw Integer32 .1.3.6.1.4.1.9839.2.1.2.23 |
min_Out_Speed_FCMMin. Out Speed FCMrw Integer32 .1.3.6.1.4.1.9839.2.1.2.24 |
hysteresis_Cut_off_FCMHysteresis Cut-off FCMrw Integer32 .1.3.6.1.4.1.9839.2.1.2.25 |
max_Pressure_Alarm_FCMMax. Pressure Alarm FCMrw Integer32 .1.3.6.1.4.1.9839.2.1.2.26 |
hysteresis_Max_Pressure_Alarm_FCMHysteresis Max.Pressure Alarm FCMrw Integer32 .1.3.6.1.4.1.9839.2.1.2.27 |
max_Out_FCMMax. Out FCMrw Integer32 .1.3.6.1.4.1.9839.2.1.2.28 |
min_Pressure_Alarm_FCMMin. Pressure Alarm FCMrw Integer32 .1.3.6.1.4.1.9839.2.1.2.29 |
hysteresis_Min_Pressure_Alarm_FCMHysteresis Min.Pressure Alarm FCMrw Integer32 .1.3.6.1.4.1.9839.2.1.2.30 |
min_Out_FCMMin. Out FCMrw Integer32 .1.3.6.1.4.1.9839.2.1.2.31 |
delta_FreecoolingDelta Freecoolingrw Integer32 .1.3.6.1.4.1.9839.2.1.2.32 |
hysteresis_FreecoolingHysteresis Freecoolingrw Integer32 .1.3.6.1.4.1.9839.2.1.2.33 |
proportional_Band_Freecooling_PIDProportional Band Freecooling PIDrw Integer32 .1.3.6.1.4.1.9839.2.1.2.34 |
offset_Freecooling_PIDOffset Freecooling PIDrw Integer32 .1.3.6.1.4.1.9839.2.1.2.35 |
temperature_Overlap_FreecoolingTemperature Overlap Freecoolingrw Integer32 .1.3.6.1.4.1.9839.2.1.2.36 |
min_out_freecoolingMin. out freecoolingrw Integer32 .1.3.6.1.4.1.9839.2.1.2.37 |
neutral_zone_K_costantNeutral zone K costantrw Integer32 .1.3.6.1.4.1.9839.2.1.2.38 |
neutral_zone_V_variableNeutral zone V variablerw Integer32 .1.3.6.1.4.1.9839.2.1.2.39 |
proportional_Band_freecooling_Valve_PIDProportional Band freecooling Valve PIDrw Integer32 .1.3.6.1.4.1.9839.2.1.2.40 |
offset_Freecooling_Valve_PIDOffset Freecooling Valve PIDrw Integer32 .1.3.6.1.4.1.9839.2.1.2.41 |
temperature_A_BTemperature A-Bro Integer32 .1.3.6.1.4.1.9839.2.1.2.42 |
delta_Thermal_Excusion_FreecolingDelta Thermal Excusion Freecolingrw Integer32 .1.3.6.1.4.1.9839.2.1.2.43 |
hysteresis_Thermal_Excusion_Freecolinghysteresis Thermal Excusion Freecolingrw Integer32 .1.3.6.1.4.1.9839.2.1.2.44 |
alarm_Setpoint_Static_Pressure_Hydraulic_circuitAlarm Setpoint Static Pressure Hydraulic circuitrw Integer32 .1.3.6.1.4.1.9839.2.1.2.45 |
warnig_Setpoint_Static_Pressure_Hydraulic_circuitWarnig Setpoint Static Pressure Hydraulic circuitrw Integer32 .1.3.6.1.4.1.9839.2.1.2.46 |
alarm_Setpoint_Differential_Pressure_Hydraulic_circuitAlarm Setpoint Differential Pressure Hydraulic circuitrw Integer32 .1.3.6.1.4.1.9839.2.1.2.47 |
alarm_Setpoint_Flow_Rate_Hydraulic_circuitAlarm Setpoint Flow-Rate Hydraulic circuitrw Integer32 .1.3.6.1.4.1.9839.2.1.2.48 |
tempertaure_Cut_off_FCMTempertaure Cut-off FCMrw Integer32 .1.3.6.1.4.1.9839.2.1.2.50 |
set_effectiveSet-effectivero Integer32 .1.3.6.1.4.1.9839.2.1.2.59 |
set_fcFreecooling or drycooler Set-pointro Integer32 .1.3.6.1.4.1.9839.2.1.2.60 |
setpoint_a_usSet-point MAINrw Integer32 .1.3.6.1.4.1.9839.2.1.2.61 |
max_setpointMax.setpointrw Integer32 .1.3.6.1.4.1.9839.2.1.2.62 |
min_setpointMin.setpointrw Integer32 .1.3.6.1.4.1.9839.2.1.2.63 |
diffdifferentialrw Integer32 (-999..999) UNITS "N/A" .1.3.6.1.4.1.9839.2.1.2.64 |
max_diffMax. differentialrw Integer32 .1.3.6.1.4.1.9839.2.1.2.65 |
min_diffMin.Differentialrw Integer32 .1.3.6.1.4.1.9839.2.1.2.66 |
fcs_outFans speed controller output %ro Integer32 .1.3.6.1.4.1.9839.2.1.2.67 |
water_tempTank - Process water temperaturero Integer32 .1.3.6.1.4.1.9839.2.1.2.70 |
temp_inletWater inlet temperaturero Integer32 .1.3.6.1.4.1.9839.2.1.2.71 |
temp_outletWater outlet temperaturero Integer32 .1.3.6.1.4.1.9839.2.1.2.72 |
flow_valueFlow rate valuero Integer32 .1.3.6.1.4.1.9839.2.1.2.73 |
amp_valueCurrent cunsumptionro Integer32 .1.3.6.1.4.1.9839.2.1.2.74 |
ta_probe_temp_1Antifreeze 1 temperature monitoringro Integer32 .1.3.6.1.4.1.9839.2.1.2.75 |
ta_probe_temp_2Antifreeze 2 temperature monitoringro Integer32 .1.3.6.1.4.1.9839.2.1.2.76 |
pressione1Condensation pressure circuit 1ro Integer32 (-999..999) UNITS "N/A" .1.3.6.1.4.1.9839.2.1.2.77 |
pressione2Condensation pressure circuit 2ro Integer32 (-999..999) UNITS "N/A" .1.3.6.1.4.1.9839.2.1.2.78 |
pump_sp_pressPump discharge pressurero Integer32 .1.3.6.1.4.1.9839.2.1.2.79 |
p_wat2Pump suction or static pressurero Integer32 .1.3.6.1.4.1.9839.2.1.2.80 |
temp_ambAmbient temperaturero Integer32 .1.3.6.1.4.1.9839.2.1.2.81 |
temp_fcInlet - freecooling temperaturero Integer32 .1.3.6.1.4.1.9839.2.1.2.82 |
pp1Pump 1 speedro Integer32 .1.3.6.1.4.1.9839.2.1.2.90 |
pp2Pump 2 speedro Integer32 .1.3.6.1.4.1.9839.2.1.2.91 |
cooling_capacityCooling Capacityro Integer32 .1.3.6.1.4.1.9839.2.1.2.100 |
freecooling_capacityFreeCooling Capacityro Integer32 .1.3.6.1.4.1.9839.2.1.2.101 |
total_capacityTotalCooling Capacityro Integer32 .1.3.6.1.4.1.9839.2.1.2.102 |
integerObjects OBJECT IDENTIFIER .1.3.6.1.4.1.9839.2.1.3 |
ip_Address1IP Address 1 (XXX.xxx.xxx.xxx)ro Integer32 .1.3.6.1.4.1.9839.2.1.3.6 |
ip_Address2IP Address 2 (xxx.XXX.xxx.xxx)ro Integer32 .1.3.6.1.4.1.9839.2.1.3.7 |
ip_Address3IP Address 3 (xxx.xxx.XXX.xxx)ro Integer32 .1.3.6.1.4.1.9839.2.1.3.8 |
ip_Address4IP Address 4 (xxx.xxx.xxx.XXX)ro Integer32 .1.3.6.1.4.1.9839.2.1.3.9 |
netMaskNetMask 8-16-24-32ro Integer32 .1.3.6.1.4.1.9839.2.1.3.10 |
gateway1Gateway 1 (XXX.xxx.xxx.xxx)ro Integer32 .1.3.6.1.4.1.9839.2.1.3.11 |
gateway2Gateway 2 (xxx.XXX.xxx.xxx)ro Integer32 .1.3.6.1.4.1.9839.2.1.3.12 |
gateway3Gateway 3 (xxx.xxx.XXX.xxx)ro Integer32 .1.3.6.1.4.1.9839.2.1.3.13 |
gateway4Gateway 4 (xxx.xxx.xxx.XXX)ro Integer32 .1.3.6.1.4.1.9839.2.1.3.14 |
dns1_1DNS (1) 1 (XXX.xxx.xxx.xxx)ro Integer32 .1.3.6.1.4.1.9839.2.1.3.15 |
dns1_2DNS (1) 2 (xxx.XXX.xxx.xxx)ro Integer32 .1.3.6.1.4.1.9839.2.1.3.16 |
dns1_3DNS (1) 3 (xxx.xxx.XXX.xxx)ro Integer32 .1.3.6.1.4.1.9839.2.1.3.17 |
dns1_4DNS (1) 4 (xxx.xxx.xxx.XXX)ro Integer32 .1.3.6.1.4.1.9839.2.1.3.18 |
dns2_1DNS (2) 1 (XXX.xxx.xxx.xxx)ro Integer32 .1.3.6.1.4.1.9839.2.1.3.19 |
dns2_2DNS (2) 2 (xxx.XXX.xxx.xxx)ro Integer32 .1.3.6.1.4.1.9839.2.1.3.20 |
dns2_3DNS (2) 3 (xxx.xxx.XXX.xxx)ro Integer32 .1.3.6.1.4.1.9839.2.1.3.21 |
dns2_4DNS (2) 4 (xxx.xxx.xxx.XXX)ro Integer32 .1.3.6.1.4.1.9839.2.1.3.22 |
ip_Address1_OutIP Address Out 1 (XXX.xxx.xxx.xxx)ro Integer32 .1.3.6.1.4.1.9839.2.1.3.26 |
ip_Address2_OutIP Address Out 2 (xxx.XXX.xxx.xxx)ro Integer32 .1.3.6.1.4.1.9839.2.1.3.27 |
ip_Address3_OutIP Address Out 3 (xxx.xxx.XXX.xxx)ro Integer32 .1.3.6.1.4.1.9839.2.1.3.28 |
ip_Address4_OutIP Address Out 4 (xxx.xxx.xxx.XXX)ro Integer32 .1.3.6.1.4.1.9839.2.1.3.29 |
starting_delay_Second_PumpStarting delay Second Pumprw Integer32 .1.3.6.1.4.1.9839.2.1.3.30 |
starting_delay_btw_Pump_CompressorStarting delay btw Pump - Compressorrw Integer32 .1.3.6.1.4.1.9839.2.1.3.31 |
overlap_time_PumpsOverlap time Pumpsrw Integer32 .1.3.6.1.4.1.9839.2.1.3.32 |
working_time_PumpsWorking time Pumpsrw Integer32 .1.3.6.1.4.1.9839.2.1.3.33 |
running_time_ChillersRunning time Chillersrw Integer32 .1.3.6.1.4.1.9839.2.1.3.34 |
overlap_time_ChillersOverlap time Chillersrw Integer32 .1.3.6.1.4.1.9839.2.1.3.35 |
n_chillers_MaxN chillers Maxrw Integer32 .1.3.6.1.4.1.9839.2.1.3.36 |
n_chillers_ONN chillers ONrw Integer32 .1.3.6.1.4.1.9839.2.1.3.37 |
n_pumps_ONN pumps ONrw Integer32 .1.3.6.1.4.1.9839.2.1.3.38 |
time_Enable_Pumps_Chiller_OfflineTime Enable Pumps - Chiller Offlinerw Integer32 .1.3.6.1.4.1.9839.2.1.3.39 |
time_Running_Pumps_Chiller_OfflineTime Running Pumps - Chiller Offlinerw Integer32 .1.3.6.1.4.1.9839.2.1.3.40 |
integral_Time_3Way_Valve_Hydraulic_PIDIntegral Time 3Way Valve Hydraulic (PID)rw Integer32 .1.3.6.1.4.1.9839.2.1.3.41 |
derivative_Time_3Way_Valve_Hydraulic_PIDDerivative Time 3Way Valve Hydraulic (PID)rw Integer32 .1.3.6.1.4.1.9839.2.1.3.42 |
output_Address_3Way_Valve_HydraulicOutput Address 3Way Valve Hydraulicrw Integer32 .1.3.6.1.4.1.9839.2.1.3.43 |
time_Speed_Up_FCMTime Speed-Up (FCM)rw Integer32 .1.3.6.1.4.1.9839.2.1.3.44 |
time_Soft_Start_FCMTime Soft-Start (FCM)rw Integer32 .1.3.6.1.4.1.9839.2.1.3.45 |
delay_FreecoolingDelay Freecoolingrw Integer32 .1.3.6.1.4.1.9839.2.1.3.47 |
integral_Time_Freeccoling_PIDIntegral Time Freeccoling (PID)rw Integer32 .1.3.6.1.4.1.9839.2.1.3.48 |
derivative_Time_Freeccoling_PIDDerivative Time Freeccoling (PID)rw Integer32 .1.3.6.1.4.1.9839.2.1.3.49 |
time_Min_On_Freecooling_Chiller_timingTime Min. On (Freecooling - Chiller timing)rw Integer32 .1.3.6.1.4.1.9839.2.1.3.50 |
time_Min_Off_Freecooling_Chiller_timingTime Min. Off (Freecooling - Chiller timing)rw Integer32 .1.3.6.1.4.1.9839.2.1.3.51 |
time_Min_Different_Freecooling_Chiller_timingTime Min. Different (Freecooling - Chiller timing)rw Integer32 .1.3.6.1.4.1.9839.2.1.3.52 |
time_Min_Same_Freecooling_Chiller_timingTime Min. Same (Freecooling - Chiller timing)rw Integer32 .1.3.6.1.4.1.9839.2.1.3.53 |
integral_Time_Freeccoling_Valve_PIDIntegral Time Freeccoling Valve (PID)rw Integer32 .1.3.6.1.4.1.9839.2.1.3.54 |
derivative_Time_Freeccoling_Valve_PIDDerivative Time Freeccoling Valve (PID)rw Integer32 .1.3.6.1.4.1.9839.2.1.3.55 |
output_Address_Valve_FreecoolingOutput Address Valve Freecoolingrw Integer32 .1.3.6.1.4.1.9839.2.1.3.56 |
delay_Freecooling_Thermal_ExclusionDelay Freecoolimg Thermal Exclusionrw Integer32 .1.3.6.1.4.1.9839.2.1.3.57 |
n_of_alarm_External_Dry_CoolerN of alarm (External Dry-Cooler)rw Integer32 .1.3.6.1.4.1.9839.2.1.3.58 |
delay_Alarm_Static_PressureDelay Alarm (Static Pressure)rw Integer32 .1.3.6.1.4.1.9839.2.1.3.59 |
n_of_Alarm_Static_PressureN of Alarm (Static Pressure)rw Integer32 .1.3.6.1.4.1.9839.2.1.3.60 |
delay_Warning_Static_PressureDelay Warning (Static Pressure)rw Integer32 .1.3.6.1.4.1.9839.2.1.3.61 |
n_of_Warning_Static_PressureN of Warning (Static Pressure)rw Integer32 .1.3.6.1.4.1.9839.2.1.3.62 |
n_of_Alarm_Differential_PressureN of Alarm (Differential Pressure)rw Integer32 .1.3.6.1.4.1.9839.2.1.3.63 |
priming_Time_Hydraulic_PressurePriming Time (Hydraulic Pressure)rw Integer32 .1.3.6.1.4.1.9839.2.1.3.64 |
delay_priming_Time_Hydraulic_PressureDelay Priming Time (Hydraulic Pressure)rw Integer32 .1.3.6.1.4.1.9839.2.1.3.65 |
output_Address_Alarm_Static_PressureOutput Address Alarm (Static Pressure)rw Integer32 .1.3.6.1.4.1.9839.2.1.3.66 |
n_of_Alarm_Flow_RateN of Alarm (Flow Rate)rw Integer32 .1.3.6.1.4.1.9839.2.1.3.67 |
priming_Time_Flow_RatePriming Time (Flow Rate)rw Integer32 .1.3.6.1.4.1.9839.2.1.3.68 |
delay_priming_Time_Flow_RateDelay Priming Time (Flow Rate)rw Integer32 .1.3.6.1.4.1.9839.2.1.3.69 |
bms_address_IDENTBMS address (IDENT)ro Integer32 .1.3.6.1.4.1.9839.2.1.3.70 |
chiller_name0Chiller Model - Article Number - 0ro Integer32 .1.3.6.1.4.1.9839.2.1.3.99 |
chiller_name1Chiller Model - Article Number - 1ro Integer32 .1.3.6.1.4.1.9839.2.1.3.100 |
current_dayCurrent Dayro Integer32 .1.3.6.1.4.1.9839.2.1.3.123 |
current_monthCurrent Monthro Integer32 .1.3.6.1.4.1.9839.2.1.3.124 |
current_yearCurrent Yearro Integer32 .1.3.6.1.4.1.9839.2.1.3.125 |
current_hourCurrent Hourro Integer32 .1.3.6.1.4.1.9839.2.1.3.126 |
current_minuteCurrent Minutero Integer32 .1.3.6.1.4.1.9839.2.1.3.127 |
chiller_mode_operationChiller mode operationro Integer32 .1.3.6.1.4.1.9839.2.1.3.150 |
trapObjects OBJECT IDENTIFIER .1.3.6.1.4.1.9839.2.1.100 |
high_pressure_switch_1_alarmHigh pressure switch 1 alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.1 |
high_pressure_switch_2_alarmHigh pressure switch 2 alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.2 |
low_pressure_switch_1_alarmLow pressure switch 1 alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.3 |
low_pressure_switch_2_alarmLow pressure switch 2 alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.4 |
water_level_alarmWater level alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.6 |
flow_switch_alarmFlow switch alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.8 |
water_static_pressure_alarmWater static pressure alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.9 |
water_static_pressure_warningWater static pressure warning NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.10 |
flow_rate_alarmFlow rate alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.11 |
overload_compressor1_circuit1_alarmOverload compressor 1 circuit 1 alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.12 |
overload_compressor2_circuit1_alarmOverload compressor 2 circuit 1 alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.13 |
overload_compressor3_circuit1_alarmOverload compressor 3 circuit 1 alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.14 |
overload_compressor1_circuit2_alarmOverload compressor 1 circuit 2 alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.15 |
overload_compressor2_circuit2_alarmOverload compressor 2 circuit 2 alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.16 |
overload_compressor3_circuit2_alarmOverload compressor 3 circuit 2 alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.17 |
overload_fans_circuit1Overload fans circuit 1 NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.18 |
overload_fans_circuit2Overload fans circuit 2 NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.19 |
overload_fan1_circuit1_alarmOverload fan 1 circuit 1 alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.20 |
overload_fan2_circuit1_alarmOverload fan 2 circuit 1 alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.21 |
overload_fan3_circuit1_alarmOverload fan 3 circuit 1 alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.22 |
overload_fan4_circuit1_alarmOverload fan 4 circuit 1 alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.23 |
overload_fan1_circuit_2_alarmOverload fan 1 circuit 2 alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.24 |
overload_fan2_circuit2_alarmOverload fan 2 circuit 2 alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.25 |
overload_fan3_circuit2_alarmOverload fan 3 circuit 2 alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.26 |
overload_fan4_circuit2_alarmOverload fan 4 circuit 2 alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.27 |
overload_pump1_alarmOverload pump 1 alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.28 |
overload_pump2_alarmOverload pump 2 alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.29 |
wrong_phase_rotation_alarmWrong phase rotation alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.30 |
back_Door_open_alarmBack Door open alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.31 |
alarm_idrofrigo_pump_c_1Condensation pump 1 breaker switch alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.75 |
alarm_idrofrigo_pump_c_2Condensation pump 2 breaker switch alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.76 |
alarm_idrofrigo_fl_CCondensation flow switch alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.80 |
remote_on_offRemote on-off NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.130 |
chiller_ON_OFFChiller ON/OFF NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.131 |
alarm_disch_scw_1Discharge screw compressor 1 alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.148 |
alarm_disch_scw_2Discharge screw compressor 2 alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.149 |
alarm_probe_inletInlet probe alarm (broken or disconnected) NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.150 |
alarm_probe_ambAmbient probe alarm (broken or disconnected) NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.151 |
alarm_frigo_fl1Flow switch alarm (cooling alarm) NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.152 |
alarm_idro_pump1Pump 1 hydraulic alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.153 |
alarm_idro_pump2Pump 2 hydraulic alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.154 |
alarm_idro_fl1Flow switch alarm (hydraulic alarm) NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.155 |
alarm_warning_fl1Flow switch alarm (warning alarm) NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.156 |
alarm_hi_water_tempHigh Temperature alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.157 |
alarm_lo_water_tempLow Temperature alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.158 |
alarm_ta_probe1Antifreeze/evaporator probe 1 alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.159 |
alarm_hi_pressHigh condensation pressure alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.160 |
alarm_lo_pressLow condensation pressure alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.161 |
alarm_probe_evap_1Antifreeze/evaporator probe 1 alarm (broken or disconnected) NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.162 |
alarm_probe_evap_2Antifreeze/evaporator probe 2 alarm (broken or disconnected) NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.163 |
alarm_hi_press_1High condensation pressure 1 alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.164 |
alarm_hi_press_2High condensation pressure 2 alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.165 |
alarm_lo_press_1Low condensation pressure 1 alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.166 |
alarm_lo_press_2Low condensation pressure 2 alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.167 |
alarm_probe_tankTank/Out probe alarm (broken or disconnected) NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.168 |
alarm_off_line_1Chiller 1 offline NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.169 |
alarm_off_line_2Chiller 2 offline NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.170 |
alarm_off_line_3Chiller 3 offline NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.171 |
alarm_off_line_4Chiller 4 offline NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.172 |
alarm_off_line_5Chiller 5 offline NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.173 |
alarm_off_line_6Chiller 6 offline NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.174 |
alarm_off_line_7Chiller 7 offline NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.175 |
alarm_off_line_8Chiller 8 offline NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.176 |
alarm_ta_probe2Antifreeze/evaporator probe 2 alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.177 |
alarm_smsSMS alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.178 |
alarm_modemModem alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.179 |
alarm_sms_codaSMS coda alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.180 |
alarm_probe_fcFreecooling probe alarm (broken or disconnected) NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.181 |
alarm_maint_pw1Maintenance pump 1 alarm) NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.182 |
alarm_maint_pw2Maintenance pump 2 alarm) NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.183 |
alarm_hi_temp_ridHigh temperature alarm (redundance) NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.184 |
alarm_q_fc_sepDryCooler breaker switch alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.185 |
alarm_p_wat2Water pressure 2 alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.186 |
alarm_p_wat1Water pressure 1 alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.187 |
alarm_foult_flow_p1Pump 1 flow alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.188 |
alarm_foult_flow_p2Pump 2 flow alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.189 |
alarm_foult_fl1_p1Pump 1 flow-switch alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.190 |
alarm_foult_fl1_p2Pump 2 flow-switch alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.191 |
alarm_warning_leWater level warning NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.192 |
alarm_frigo_fl_CFlow switch condensation alarm (cooling alarm) NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.193 |
alarm_idro_pump_c_1Pump 1 condensation hydraulic alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.194 |
alarm_idro_pump_c_2Pump 2 condensation hydraulic alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.195 |
alarm_idro_fl_CFlow switch condensation alarm (hydraulic alarm) NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.196 |
alarm_warning_fl_CFlow switch condensation alarm (warning alarm) NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.197 |
alarm_foul_fl_C_p1Pump 1 condensation flow-switch alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.198 |
alarm_foul_fl_C_p2Pump 2 condensation flow-switch alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.199 |
More MIBs from CAREL SpA
Browse all CAREL SpAMIBs →The DataAire-dap4-al-MIB provides SNMP-based monitoring and management for Data Aire DAP4-AL precision air conditioning units, exposing critical environmental telemetry such as temperature, humidity, fan status, and alarm conditions. This module enables centralized infrastructure monitoring of cooling system health and operational parameters within data center or server room environments.
The CAREL-ug40cdz-MIB enables SNMP-based monitoring and management of the CAREL UG40 Close Control Uniflair HVAC unit, exposing operational parameters such as compressor status, fan speeds, temperature setpoints, and alarm states for real-time facility environmental control.
SNMP MIB module
The CAREL-RITTAL-LCP-3311-MIB module enables SNMP-based monitoring and management of Rittal LCP 3311 chiller units via PCO web cards, exposing operational telemetry such as compressor status, refrigerant pressure, evaporator and condenser temperatures, fan speeds, and alarm states.
The SCS-ks-MIB provides non-standard SNMP access to monitor and manage specific operational parameters and counters for the SCS KS hardware platform. This module enables the collection of device-specific telemetry data, such as session states and interface statistics, for the SCS KS system.