KELVIN-pCOWeb-Chiller-MIB
This is the MIB module for the kelvin-pCOWeb-Chiller device.
Main OID:
kelvin_pCOWebMIB_Chiller.1.3.6.1.4.1.9839.2.1
373
Objects
Active
Status
3
Dependencies
Imported Objects
Objects
373 total| Object Name |
|---|
carel OBJECT IDENTIFIER .1.3.6.1.4.1.9839 |
systm OBJECT IDENTIFIER .1.3.6.1.4.1.9839.1 |
agentReleaseRelease of the Agent.ro Integer32 UNITS "N/A" .1.3.6.1.4.1.9839.1.1 |
agentCodeCode of the Agent. 2=pCOWeb.ro Integer32 UNITS "N/A" .1.3.6.1.4.1.9839.1.2 |
instruments OBJECT IDENTIFIER .1.3.6.1.4.1.9839.2 |
pCOWebInfo OBJECT IDENTIFIER .1.3.6.1.4.1.9839.2.0 |
pCOStatusgroup OBJECT IDENTIFIER .1.3.6.1.4.1.9839.2.0.10 |
pCOId1_StatusStatus of pCOId1. 0=Offline, 1=Init, 2=Onlinero Integer32 .1.3.6.1.4.1.9839.2.0.10.1 |
pCOErrorsNumbergroup OBJECT IDENTIFIER .1.3.6.1.4.1.9839.2.0.11 |
pCOId1_ErrorsNumberNumber of Communication Errors from pCOId1 to pCOWeb.ro Integer32 .1.3.6.1.4.1.9839.2.0.11.1 |
kelvin_pCOWebMIB_ChillerThis is the MIB module for the kelvin-pCOWeb-Chiller device. MODULE-IDENTITY .1.3.6.1.4.1.9839.2.1 |
digitalObjects OBJECT IDENTIFIER .1.3.6.1.4.1.9839.2.1.1 |
al_pa1High pressure switch 1 alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.1 |
al_pa2High pressure switch 2 alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.2 |
al_pb1Low pressure switch 1 alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.3 |
al_pb2Low pressure switch 2 alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.4 |
al_leWater level alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.6 |
al_idrofrigo_fl1Flow switch alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.8 |
static_press_alarmWater static pressure alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.9 |
w_static_press_alarmWater static pressure warningro Integer32 .1.3.6.1.4.1.9839.2.1.1.10 |
flow_value_alarmFlow rate alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.11 |
al_q_comp1Overload compressor 1 circuit 1 alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.12 |
al_q_comp2Overload compressor 2 circuit 1 alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.13 |
al_q_comp3Overload compressor 3 circuit 1 alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.14 |
al_q_comp4Overload compressor 1 circuit 2 alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.15 |
al_q_comp5Overload compressor 2 circuit 2 alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.16 |
al_q_comp6Overload compressor 3 circuit 2 alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.17 |
al_q_fan_1Overload fans circuit 1ro Integer32 .1.3.6.1.4.1.9839.2.1.1.18 |
al_q_fan_2Overload fans circuit 2ro Integer32 .1.3.6.1.4.1.9839.2.1.1.19 |
al_q_fan11Overload fan 1 circuit 1 alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.20 |
al_q_fan12Overload fan 2 circuit 1 alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.21 |
al_q_fan13Overload fan 3 circuit 1 alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.22 |
al_q_fan14Overload fan 4 circuit 1 alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.23 |
al_q_fan21Overload fan 1 circuit 2 alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.24 |
al_q_fan22Overload fan 2 circuit 2 alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.25 |
al_q_fan_23Overload fan 3 circuit 2 alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.26 |
al_q_fan24Overload fan 4 circuit 2 alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.27 |
al_idrofrigo_pump1Overload pump 1 alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.28 |
al_idrofrigo_pump2Overload pump 2 alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.29 |
al_phase_contWrong phase rotation alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.30 |
al_door_swBack Door open alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.31 |
compressor_FlowRateCompressor FlowRate Managementrw Integer32 .1.3.6.1.4.1.9839.2.1.1.32 |
setpoint_inv_pumpsSetpoint Type for Inverter pumpsrw Integer32 .1.3.6.1.4.1.9839.2.1.1.33 |
enable_pumps_redundanceEnable Pumps redundancerw Integer32 .1.3.6.1.4.1.9839.2.1.1.34 |
enable_chiller_redundanceEnable Chiller redundancerw Integer32 .1.3.6.1.4.1.9839.2.1.1.35 |
status_in_alarmStatus in alarmrw Integer32 .1.3.6.1.4.1.9839.2.1.1.36 |
compressor_recoveryCompressor Recoveryrw Integer32 .1.3.6.1.4.1.9839.2.1.1.37 |
enable_thermal_redundanceEnable Thermal redundancerw Integer32 .1.3.6.1.4.1.9839.2.1.1.38 |
enable_multi_pumps_functionEnable multi-pumps functionrw Integer32 .1.3.6.1.4.1.9839.2.1.1.39 |
enable_pumps_offlineEnable function pumps-Offlinerw Integer32 .1.3.6.1.4.1.9839.2.1.1.40 |
enable_3way_valveEnable 3way valverw Integer32 .1.3.6.1.4.1.9839.2.1.1.41 |
enable_speed_up_FCMEnable speed-up FCMrw Integer32 .1.3.6.1.4.1.9839.2.1.1.42 |
enable_soft_start_FCMEnable soft-start FCMrw Integer32 .1.3.6.1.4.1.9839.2.1.1.43 |
enable_freecoolingEnable Freecoolingrw Integer32 .1.3.6.1.4.1.9839.2.1.1.44 |
enable_rot_FIFO_FCEnable rotation FIFO Freecoolingrw Integer32 .1.3.6.1.4.1.9839.2.1.1.45 |
enable_HT_functionEnable HT-functionrw Integer32 .1.3.6.1.4.1.9839.2.1.1.46 |
enable_PID_Fc_valveEnable PID-regulation for Freecooling valverw Integer32 .1.3.6.1.4.1.9839.2.1.1.47 |
enable_Fc_Thermal_ExclusionEnable Freecooling Thermal Exclusionrw Integer32 .1.3.6.1.4.1.9839.2.1.1.48 |
manual_Reset_Ext_Drycooler_AlarmManual Reset External Dry-cooler Alarmrw Integer32 .1.3.6.1.4.1.9839.2.1.1.49 |
enable_static_press_AlarmEnable static pressure Alarmrw Integer32 .1.3.6.1.4.1.9839.2.1.1.50 |
manual_reset_static_press_AlarmManual reset static pressure Alarmrw Integer32 .1.3.6.1.4.1.9839.2.1.1.51 |
enable_static_press_WarningEnable static pressure Warningrw Integer32 .1.3.6.1.4.1.9839.2.1.1.52 |
manual_reset_static_press_WarningManual reset static pressure Warningrw Integer32 .1.3.6.1.4.1.9839.2.1.1.53 |
enable_diff_press_AlarmEnable differential pressure Alarmrw Integer32 .1.3.6.1.4.1.9839.2.1.1.54 |
manual_reset_diff_press_AlarmManual reset differential pressure Alarmrw Integer32 .1.3.6.1.4.1.9839.2.1.1.55 |
enable_pressure_recoveryEnable pressure recoveryrw Integer32 .1.3.6.1.4.1.9839.2.1.1.56 |
enable_Flow_Rate_AlarmEnable Flow-Rate Alarmrw Integer32 .1.3.6.1.4.1.9839.2.1.1.57 |
manual_reset_Flow_Rate_AlarmManual reset Flow-Rate Alarmrw Integer32 .1.3.6.1.4.1.9839.2.1.1.58 |
enable_Flow_Rate_recoveryEnable Flow-Rate recoveryrw Integer32 .1.3.6.1.4.1.9839.2.1.1.59 |
enable_pCOWebEnable pCOWebrw Integer32 .1.3.6.1.4.1.9839.2.1.1.60 |
fc_single_chillerFreecooling single chiller functionrw Integer32 .1.3.6.1.4.1.9839.2.1.1.61 |
al_idrofrigo_pump_c_1Condensation pump 1 breaker switch alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.75 |
al_idrofrigo_pump_c_2Condensation pump 2 breaker switch alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.76 |
al_idrofrigo_fl_CCondensation flow switch alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.80 |
c11_onCompressor 1 circuit 1 ONro Integer32 .1.3.6.1.4.1.9839.2.1.1.100 |
c12_onCompressor 2 circuit 1 ONro Integer32 .1.3.6.1.4.1.9839.2.1.1.101 |
c13_onCompressor 3 circuit 1 ONro Integer32 .1.3.6.1.4.1.9839.2.1.1.102 |
c21_onCompressor 1 circuit 2 ONro Integer32 .1.3.6.1.4.1.9839.2.1.1.103 |
c22_onCompressor 2 circuit 2 ONro Integer32 .1.3.6.1.4.1.9839.2.1.1.104 |
c23_onCompressor 3 circuit 2 ONro Integer32 .1.3.6.1.4.1.9839.2.1.1.105 |
pump1_onPump 1 ONro Integer32 .1.3.6.1.4.1.9839.2.1.1.106 |
pump2_onPump 2 ONro Integer32 .1.3.6.1.4.1.9839.2.1.1.107 |
on_fan_gr1Fans group 1 ONro Integer32 .1.3.6.1.4.1.9839.2.1.1.108 |
on_fan_gr2Fans group 2 ONro Integer32 .1.3.6.1.4.1.9839.2.1.1.109 |
fc_onFreecooling or external dry-cooler 1 ONro Integer32 .1.3.6.1.4.1.9839.2.1.1.110 |
en_on_off_remRemote on-offrw Integer32 .1.3.6.1.4.1.9839.2.1.1.130 |
unit_onChiller ONrw Integer32 .1.3.6.1.4.1.9839.2.1.1.131 |
disch_alarm_scw_1Discharge screw compressor 1 alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.148 |
disch_alarm_scw_2Discharge screw compressor 2 alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.149 |
al_probe_inletInlet probe alarm (broken or disconnected)ro Integer32 .1.3.6.1.4.1.9839.2.1.1.150 |
al_probe_ambAmbient probe alarm (broken or disconnected)ro Integer32 .1.3.6.1.4.1.9839.2.1.1.151 |
al_frigo_fl1Flow switch alarm (cooling alarm)ro Integer32 .1.3.6.1.4.1.9839.2.1.1.152 |
al_idro_pump1Pump 1 hydraulic alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.153 |
al_idro_pump2Pump 2 hydraulic alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.154 |
al_idro_fl1Flow switch alarm (hydraulic alarm)ro Integer32 .1.3.6.1.4.1.9839.2.1.1.155 |
al_warning_fl1Flow switch alarm (warning alarm)ro Integer32 .1.3.6.1.4.1.9839.2.1.1.156 |
al_hi_water_tempHigh Temperature alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.157 |
al_lo_water_tempLow Temperature alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.158 |
al_ta_probe1Antifreeze/evaporator probe 1 alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.159 |
al_hi_pressHigh condensation pressure alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.160 |
al_lo_pressLow condensation pressure alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.161 |
al_probe_evap_1Antifreeze/evaporator probe 1 alarm (broken or disconnected)ro Integer32 .1.3.6.1.4.1.9839.2.1.1.162 |
al_probe_evap_2Antifreeze/evaporator probe 2 alarm (broken or disconnected)ro Integer32 .1.3.6.1.4.1.9839.2.1.1.163 |
al_hi_press_1High condensation pressure 1 alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.164 |
al_hi_press_2High condensation pressure 2 alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.165 |
al_lo_press_1Low condensation pressure 1 alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.166 |
al_lo_press_2Low condensation pressure 2 alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.167 |
al_probe_tankTank/Out probe alarm (broken or disconnected)ro Integer32 .1.3.6.1.4.1.9839.2.1.1.168 |
off_line_1Chiller 1 offlinero Integer32 .1.3.6.1.4.1.9839.2.1.1.169 |
off_line_2Chiller 2 offlinero Integer32 .1.3.6.1.4.1.9839.2.1.1.170 |
off_line_3Chiller 3 offlinero Integer32 .1.3.6.1.4.1.9839.2.1.1.171 |
off_line_4Chiller 4 offlinero Integer32 .1.3.6.1.4.1.9839.2.1.1.172 |
off_line_5Chiller 5 offlinero Integer32 .1.3.6.1.4.1.9839.2.1.1.173 |
off_line_6Chiller 6 offlinero Integer32 .1.3.6.1.4.1.9839.2.1.1.174 |
off_line_7Chiller 7 offlinero Integer32 .1.3.6.1.4.1.9839.2.1.1.175 |
off_line_8Chiller 8 offlinero Integer32 .1.3.6.1.4.1.9839.2.1.1.176 |
al_ta_probe2Antifreeze/evaporator probe 2 alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.177 |
al_smsSMS alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.178 |
al_modemModem alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.179 |
sms_coda_alarmSMS coda alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.180 |
al_probe_fcFreecooling probe alarm (broken or disconnected)ro Integer32 .1.3.6.1.4.1.9839.2.1.1.181 |
al_maint_pw1Maintenance pump 1 alarm)ro Integer32 .1.3.6.1.4.1.9839.2.1.1.182 |
al_maint_pw2Maintenance pump 2 alarm)ro Integer32 .1.3.6.1.4.1.9839.2.1.1.183 |
al_hi_temp_ridHigh temperature alarm (redundance)ro Integer32 .1.3.6.1.4.1.9839.2.1.1.184 |
al_q_fc_sepDryCooler breaker switch alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.185 |
al_p_wat2Water pressure 2 alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.186 |
al_p_wat1Water pressure 1 alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.187 |
al_foult_flow_p1Pump 1 flow alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.188 |
al_foult_flow_p2Pump 2 flow alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.189 |
al_foult_fl1_p1Pump 1 flow-switch alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.190 |
al_foult_fl1_p2Pump 2 flow-switch alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.191 |
al_warning_leWater level warningro Integer32 .1.3.6.1.4.1.9839.2.1.1.192 |
al_frigo_fl_CFlow switch condensation alarm (cooling alarm)ro Integer32 .1.3.6.1.4.1.9839.2.1.1.193 |
al_idro_pump_c_1Pump 1 condensation hydraulic alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.194 |
al_idro_pump_c_2Pump 2 condensation hydraulic alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.195 |
al_idro_fl_CFlow switch condensation alarm (hydraulic alarm)ro Integer32 .1.3.6.1.4.1.9839.2.1.1.196 |
al_warning_fl_CFlow switch condensation alarm (warning alarm)ro Integer32 .1.3.6.1.4.1.9839.2.1.1.197 |
al_foul_fl_C_p1Pump 1 condensation flow-switch alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.198 |
al_foul_fl_C_p2Pump 2 condensation flow-switch alarmro Integer32 .1.3.6.1.4.1.9839.2.1.1.199 |
analogObjects OBJECT IDENTIFIER .1.3.6.1.4.1.9839.2.1.2 |
setpoint_antifreeze1Setpoint Antifreeze 1rw Integer32 .1.3.6.1.4.1.9839.2.1.2.1 |
setpoint_antifreeze2Setpoint Antifreeze 2rw Integer32 .1.3.6.1.4.1.9839.2.1.2.2 |
setpoint_CompensationSetpoint Compensationrw Integer32 .1.3.6.1.4.1.9839.2.1.2.3 |
hysteresis_CompensationHysteresis Compensationrw Integer32 .1.3.6.1.4.1.9839.2.1.2.4 |
max_CompensationMax. Compensationrw Integer32 .1.3.6.1.4.1.9839.2.1.2.5 |
setpoint_DifferentialSetpoint Differentialrw Integer32 .1.3.6.1.4.1.9839.2.1.2.6 |
high_LimitHigh Limitrw Integer32 .1.3.6.1.4.1.9839.2.1.2.7 |
low_LimitLow Limitrw Integer32 .1.3.6.1.4.1.9839.2.1.2.8 |
max_Setpoint_DifferentialMax. Setpoint Differentialrw Integer32 .1.3.6.1.4.1.9839.2.1.2.9 |
min_Setpoint_DifferentialMin. Setpoint Differentialrw Integer32 .1.3.6.1.4.1.9839.2.1.2.10 |
setpoint_ASB_Inverter_pumpsSetpoint ASB Inverter pumpsrw Integer32 .1.3.6.1.4.1.9839.2.1.2.11 |
setpoint_DIFF_Inverter_pumpsSetpoint DIFF Inverter pumpsrw Integer32 .1.3.6.1.4.1.9839.2.1.2.12 |
pressure_OutPressure Outro Integer32 .1.3.6.1.4.1.9839.2.1.2.13 |
proportional_Band_Inverter_Pumps_PIDProportional Band Inverter Pumps PIDrw Integer32 .1.3.6.1.4.1.9839.2.1.2.14 |
integral_Time_Inverter_Pumps_PIDIntegral Time Inverter Pumps PIDrw Integer32 .1.3.6.1.4.1.9839.2.1.2.15 |
derivative_Time_Inverter_Pumps_PIDDerivative Time Inverter Pumps PIDrw Integer32 .1.3.6.1.4.1.9839.2.1.2.16 |
hysteresis_Thermal_redundanceHysteresis Thermal redundancerw Integer32 .1.3.6.1.4.1.9839.2.1.2.17 |
min_Opening_3Way_Valve_HydraulicMin. Opening 3Way Valve Hydraulicrw Integer32 .1.3.6.1.4.1.9839.2.1.2.18 |
max_Opening_3Way_Valve_HydraulicMax. Opening 3Way Valve Hydraulicrw Integer32 .1.3.6.1.4.1.9839.2.1.2.19 |
proportional_Band_3Way_Valve_Hydrauli_PIDProportional Band 3Way Valve Hydraulic PIDrw Integer32 .1.3.6.1.4.1.9839.2.1.2.20 |
setpoint_FCMSetpoint FCMrw Integer32 .1.3.6.1.4.1.9839.2.1.2.21 |
hysteresis_FCMHysteresis FCMrw Integer32 .1.3.6.1.4.1.9839.2.1.2.22 |
max_Out_Speed_FCMMax. Out Speed FCMrw Integer32 .1.3.6.1.4.1.9839.2.1.2.23 |
min_Out_Speed_FCMMin. Out Speed FCMrw Integer32 .1.3.6.1.4.1.9839.2.1.2.24 |
hysteresis_Cut_off_FCMHysteresis Cut-off FCMrw Integer32 .1.3.6.1.4.1.9839.2.1.2.25 |
max_Pressure_Alarm_FCMMax. Pressure Alarm FCMrw Integer32 .1.3.6.1.4.1.9839.2.1.2.26 |
hysteresis_Max_Pressure_Alarm_FCMHysteresis Max.Pressure Alarm FCMrw Integer32 .1.3.6.1.4.1.9839.2.1.2.27 |
max_Out_FCMMax. Out FCMrw Integer32 .1.3.6.1.4.1.9839.2.1.2.28 |
min_Pressure_Alarm_FCMMin. Pressure Alarm FCMrw Integer32 .1.3.6.1.4.1.9839.2.1.2.29 |
hysteresis_Min_Pressure_Alarm_FCMHysteresis Min.Pressure Alarm FCMrw Integer32 .1.3.6.1.4.1.9839.2.1.2.30 |
min_Out_FCMMin. Out FCMrw Integer32 .1.3.6.1.4.1.9839.2.1.2.31 |
delta_FreecoolingDelta Freecoolingrw Integer32 .1.3.6.1.4.1.9839.2.1.2.32 |
hysteresis_FreecoolingHysteresis Freecoolingrw Integer32 .1.3.6.1.4.1.9839.2.1.2.33 |
proportional_Band_Freecooling_PIDProportional Band Freecooling PIDrw Integer32 .1.3.6.1.4.1.9839.2.1.2.34 |
offset_Freecooling_PIDOffset Freecooling PIDrw Integer32 .1.3.6.1.4.1.9839.2.1.2.35 |
temperature_Overlap_FreecoolingTemperature Overlap Freecoolingrw Integer32 .1.3.6.1.4.1.9839.2.1.2.36 |
min_out_freecoolingMin. out freecoolingrw Integer32 .1.3.6.1.4.1.9839.2.1.2.37 |
neutral_zone_K_costantNeutral zone K costantrw Integer32 .1.3.6.1.4.1.9839.2.1.2.38 |
neutral_zone_V_variableNeutral zone V variablerw Integer32 .1.3.6.1.4.1.9839.2.1.2.39 |
proportional_Band_freecooling_Valve_PIDProportional Band freecooling Valve PIDrw Integer32 .1.3.6.1.4.1.9839.2.1.2.40 |
offset_Freecooling_Valve_PIDOffset Freecooling Valve PIDrw Integer32 .1.3.6.1.4.1.9839.2.1.2.41 |
temperature_A_BTemperature A-Bro Integer32 .1.3.6.1.4.1.9839.2.1.2.42 |
delta_Thermal_Excusion_FreecolingDelta Thermal Excusion Freecolingrw Integer32 .1.3.6.1.4.1.9839.2.1.2.43 |
hysteresis_Thermal_Excusion_Freecolinghysteresis Thermal Excusion Freecolingrw Integer32 .1.3.6.1.4.1.9839.2.1.2.44 |
alarm_Setpoint_Static_Pressure_Hydraulic_circuitAlarm Setpoint Static Pressure Hydraulic circuitrw Integer32 .1.3.6.1.4.1.9839.2.1.2.45 |
warnig_Setpoint_Static_Pressure_Hydraulic_circuitWarnig Setpoint Static Pressure Hydraulic circuitrw Integer32 .1.3.6.1.4.1.9839.2.1.2.46 |
alarm_Setpoint_Differential_Pressure_Hydraulic_circuitAlarm Setpoint Differential Pressure Hydraulic circuitrw Integer32 .1.3.6.1.4.1.9839.2.1.2.47 |
alarm_Setpoint_Flow_Rate_Hydraulic_circuitAlarm Setpoint Flow-Rate Hydraulic circuitrw Integer32 .1.3.6.1.4.1.9839.2.1.2.48 |
tempertaure_Cut_off_FCMTempertaure Cut-off FCMrw Integer32 .1.3.6.1.4.1.9839.2.1.2.50 |
set_effectiveSet-effectivero Integer32 .1.3.6.1.4.1.9839.2.1.2.59 |
set_fcFreecooling or drycooler Set-pointro Integer32 .1.3.6.1.4.1.9839.2.1.2.60 |
setpoint_a_usSet-point MAINrw Integer32 .1.3.6.1.4.1.9839.2.1.2.61 |
max_setpointMax.setpointrw Integer32 .1.3.6.1.4.1.9839.2.1.2.62 |
min_setpointMin.setpointrw Integer32 .1.3.6.1.4.1.9839.2.1.2.63 |
diffdifferentialrw Integer32 (-999..999) UNITS "N/A" .1.3.6.1.4.1.9839.2.1.2.64 |
max_diffMax. differentialrw Integer32 .1.3.6.1.4.1.9839.2.1.2.65 |
min_diffMin.Differentialrw Integer32 .1.3.6.1.4.1.9839.2.1.2.66 |
fcs_outFans speed controller output %ro Integer32 .1.3.6.1.4.1.9839.2.1.2.67 |
water_tempTank - Process water temperaturero Integer32 .1.3.6.1.4.1.9839.2.1.2.70 |
temp_inletWater inlet temperaturero Integer32 .1.3.6.1.4.1.9839.2.1.2.71 |
temp_outletWater outlet temperaturero Integer32 .1.3.6.1.4.1.9839.2.1.2.72 |
flow_valueFlow rate valuero Integer32 .1.3.6.1.4.1.9839.2.1.2.73 |
amp_valueCurrent cunsumptionro Integer32 .1.3.6.1.4.1.9839.2.1.2.74 |
ta_probe_temp_1Antifreeze 1 temperature monitoringro Integer32 .1.3.6.1.4.1.9839.2.1.2.75 |
ta_probe_temp_2Antifreeze 2 temperature monitoringro Integer32 .1.3.6.1.4.1.9839.2.1.2.76 |
pressione1Condensation pressure circuit 1ro Integer32 (-999..999) UNITS "N/A" .1.3.6.1.4.1.9839.2.1.2.77 |
pressione2Condensation pressure circuit 2ro Integer32 (-999..999) UNITS "N/A" .1.3.6.1.4.1.9839.2.1.2.78 |
pump_sp_pressPump discharge pressurero Integer32 .1.3.6.1.4.1.9839.2.1.2.79 |
p_wat2Pump suction or static pressurero Integer32 .1.3.6.1.4.1.9839.2.1.2.80 |
temp_ambAmbient temperaturero Integer32 .1.3.6.1.4.1.9839.2.1.2.81 |
temp_fcInlet - freecooling temperaturero Integer32 .1.3.6.1.4.1.9839.2.1.2.82 |
pp1Pump 1 speedro Integer32 .1.3.6.1.4.1.9839.2.1.2.90 |
pp2Pump 2 speedro Integer32 .1.3.6.1.4.1.9839.2.1.2.91 |
cooling_capacityCooling Capacityro Integer32 .1.3.6.1.4.1.9839.2.1.2.100 |
freecooling_capacityFreeCooling Capacityro Integer32 .1.3.6.1.4.1.9839.2.1.2.101 |
total_capacityTotalCooling Capacityro Integer32 .1.3.6.1.4.1.9839.2.1.2.102 |
integerObjects OBJECT IDENTIFIER .1.3.6.1.4.1.9839.2.1.3 |
ip_Address1IP Address 1 (XXX.xxx.xxx.xxx)ro Integer32 .1.3.6.1.4.1.9839.2.1.3.6 |
ip_Address2IP Address 2 (xxx.XXX.xxx.xxx)ro Integer32 .1.3.6.1.4.1.9839.2.1.3.7 |
ip_Address3IP Address 3 (xxx.xxx.XXX.xxx)ro Integer32 .1.3.6.1.4.1.9839.2.1.3.8 |
ip_Address4IP Address 4 (xxx.xxx.xxx.XXX)ro Integer32 .1.3.6.1.4.1.9839.2.1.3.9 |
netMaskNetMask 8-16-24-32ro Integer32 .1.3.6.1.4.1.9839.2.1.3.10 |
gateway1Gateway 1 (XXX.xxx.xxx.xxx)ro Integer32 .1.3.6.1.4.1.9839.2.1.3.11 |
gateway2Gateway 2 (xxx.XXX.xxx.xxx)ro Integer32 .1.3.6.1.4.1.9839.2.1.3.12 |
gateway3Gateway 3 (xxx.xxx.XXX.xxx)ro Integer32 .1.3.6.1.4.1.9839.2.1.3.13 |
gateway4Gateway 4 (xxx.xxx.xxx.XXX)ro Integer32 .1.3.6.1.4.1.9839.2.1.3.14 |
dns1_1DNS (1) 1 (XXX.xxx.xxx.xxx)ro Integer32 .1.3.6.1.4.1.9839.2.1.3.15 |
dns1_2DNS (1) 2 (xxx.XXX.xxx.xxx)ro Integer32 .1.3.6.1.4.1.9839.2.1.3.16 |
dns1_3DNS (1) 3 (xxx.xxx.XXX.xxx)ro Integer32 .1.3.6.1.4.1.9839.2.1.3.17 |
dns1_4DNS (1) 4 (xxx.xxx.xxx.XXX)ro Integer32 .1.3.6.1.4.1.9839.2.1.3.18 |
dns2_1DNS (2) 1 (XXX.xxx.xxx.xxx)ro Integer32 .1.3.6.1.4.1.9839.2.1.3.19 |
dns2_2DNS (2) 2 (xxx.XXX.xxx.xxx)ro Integer32 .1.3.6.1.4.1.9839.2.1.3.20 |
dns2_3DNS (2) 3 (xxx.xxx.XXX.xxx)ro Integer32 .1.3.6.1.4.1.9839.2.1.3.21 |
dns2_4DNS (2) 4 (xxx.xxx.xxx.XXX)ro Integer32 .1.3.6.1.4.1.9839.2.1.3.22 |
ip_Address1_OutIP Address Out 1 (XXX.xxx.xxx.xxx)ro Integer32 .1.3.6.1.4.1.9839.2.1.3.26 |
ip_Address2_OutIP Address Out 2 (xxx.XXX.xxx.xxx)ro Integer32 .1.3.6.1.4.1.9839.2.1.3.27 |
ip_Address3_OutIP Address Out 3 (xxx.xxx.XXX.xxx)ro Integer32 .1.3.6.1.4.1.9839.2.1.3.28 |
ip_Address4_OutIP Address Out 4 (xxx.xxx.xxx.XXX)ro Integer32 .1.3.6.1.4.1.9839.2.1.3.29 |
starting_delay_Second_PumpStarting delay Second Pumprw Integer32 .1.3.6.1.4.1.9839.2.1.3.30 |
starting_delay_btw_Pump_CompressorStarting delay btw Pump - Compressorrw Integer32 .1.3.6.1.4.1.9839.2.1.3.31 |
overlap_time_PumpsOverlap time Pumpsrw Integer32 .1.3.6.1.4.1.9839.2.1.3.32 |
working_time_PumpsWorking time Pumpsrw Integer32 .1.3.6.1.4.1.9839.2.1.3.33 |
running_time_ChillersRunning time Chillersrw Integer32 .1.3.6.1.4.1.9839.2.1.3.34 |
overlap_time_ChillersOverlap time Chillersrw Integer32 .1.3.6.1.4.1.9839.2.1.3.35 |
n_chillers_MaxN chillers Maxrw Integer32 .1.3.6.1.4.1.9839.2.1.3.36 |
n_chillers_ONN chillers ONrw Integer32 .1.3.6.1.4.1.9839.2.1.3.37 |
n_pumps_ONN pumps ONrw Integer32 .1.3.6.1.4.1.9839.2.1.3.38 |
time_Enable_Pumps_Chiller_OfflineTime Enable Pumps - Chiller Offlinerw Integer32 .1.3.6.1.4.1.9839.2.1.3.39 |
time_Running_Pumps_Chiller_OfflineTime Running Pumps - Chiller Offlinerw Integer32 .1.3.6.1.4.1.9839.2.1.3.40 |
integral_Time_3Way_Valve_Hydraulic_PIDIntegral Time 3Way Valve Hydraulic (PID)rw Integer32 .1.3.6.1.4.1.9839.2.1.3.41 |
derivative_Time_3Way_Valve_Hydraulic_PIDDerivative Time 3Way Valve Hydraulic (PID)rw Integer32 .1.3.6.1.4.1.9839.2.1.3.42 |
output_Address_3Way_Valve_HydraulicOutput Address 3Way Valve Hydraulicrw Integer32 .1.3.6.1.4.1.9839.2.1.3.43 |
time_Speed_Up_FCMTime Speed-Up (FCM)rw Integer32 .1.3.6.1.4.1.9839.2.1.3.44 |
time_Soft_Start_FCMTime Soft-Start (FCM)rw Integer32 .1.3.6.1.4.1.9839.2.1.3.45 |
delay_FreecoolingDelay Freecoolingrw Integer32 .1.3.6.1.4.1.9839.2.1.3.47 |
integral_Time_Freeccoling_PIDIntegral Time Freeccoling (PID)rw Integer32 .1.3.6.1.4.1.9839.2.1.3.48 |
derivative_Time_Freeccoling_PIDDerivative Time Freeccoling (PID)rw Integer32 .1.3.6.1.4.1.9839.2.1.3.49 |
time_Min_On_Freecooling_Chiller_timingTime Min. On (Freecooling - Chiller timing)rw Integer32 .1.3.6.1.4.1.9839.2.1.3.50 |
time_Min_Off_Freecooling_Chiller_timingTime Min. Off (Freecooling - Chiller timing)rw Integer32 .1.3.6.1.4.1.9839.2.1.3.51 |
time_Min_Different_Freecooling_Chiller_timingTime Min. Different (Freecooling - Chiller timing)rw Integer32 .1.3.6.1.4.1.9839.2.1.3.52 |
time_Min_Same_Freecooling_Chiller_timingTime Min. Same (Freecooling - Chiller timing)rw Integer32 .1.3.6.1.4.1.9839.2.1.3.53 |
integral_Time_Freeccoling_Valve_PIDIntegral Time Freeccoling Valve (PID)rw Integer32 .1.3.6.1.4.1.9839.2.1.3.54 |
derivative_Time_Freeccoling_Valve_PIDDerivative Time Freeccoling Valve (PID)rw Integer32 .1.3.6.1.4.1.9839.2.1.3.55 |
output_Address_Valve_FreecoolingOutput Address Valve Freecoolingrw Integer32 .1.3.6.1.4.1.9839.2.1.3.56 |
delay_Freecooling_Thermal_ExclusionDelay Freecoolimg Thermal Exclusionrw Integer32 .1.3.6.1.4.1.9839.2.1.3.57 |
n_of_alarm_External_Dry_CoolerN of alarm (External Dry-Cooler)rw Integer32 .1.3.6.1.4.1.9839.2.1.3.58 |
delay_Alarm_Static_PressureDelay Alarm (Static Pressure)rw Integer32 .1.3.6.1.4.1.9839.2.1.3.59 |
n_of_Alarm_Static_PressureN of Alarm (Static Pressure)rw Integer32 .1.3.6.1.4.1.9839.2.1.3.60 |
delay_Warning_Static_PressureDelay Warning (Static Pressure)rw Integer32 .1.3.6.1.4.1.9839.2.1.3.61 |
n_of_Warning_Static_PressureN of Warning (Static Pressure)rw Integer32 .1.3.6.1.4.1.9839.2.1.3.62 |
n_of_Alarm_Differential_PressureN of Alarm (Differential Pressure)rw Integer32 .1.3.6.1.4.1.9839.2.1.3.63 |
priming_Time_Hydraulic_PressurePriming Time (Hydraulic Pressure)rw Integer32 .1.3.6.1.4.1.9839.2.1.3.64 |
delay_priming_Time_Hydraulic_PressureDelay Priming Time (Hydraulic Pressure)rw Integer32 .1.3.6.1.4.1.9839.2.1.3.65 |
output_Address_Alarm_Static_PressureOutput Address Alarm (Static Pressure)rw Integer32 .1.3.6.1.4.1.9839.2.1.3.66 |
n_of_Alarm_Flow_RateN of Alarm (Flow Rate)rw Integer32 .1.3.6.1.4.1.9839.2.1.3.67 |
priming_Time_Flow_RatePriming Time (Flow Rate)rw Integer32 .1.3.6.1.4.1.9839.2.1.3.68 |
delay_priming_Time_Flow_RateDelay Priming Time (Flow Rate)rw Integer32 .1.3.6.1.4.1.9839.2.1.3.69 |
bms_address_IDENTBMS address (IDENT)ro Integer32 .1.3.6.1.4.1.9839.2.1.3.70 |
chiller_name0Chiller Model - Article Number - 0ro Integer32 .1.3.6.1.4.1.9839.2.1.3.99 |
chiller_name1Chiller Model - Article Number - 1ro Integer32 .1.3.6.1.4.1.9839.2.1.3.100 |
current_dayCurrent Dayro Integer32 .1.3.6.1.4.1.9839.2.1.3.123 |
current_monthCurrent Monthro Integer32 .1.3.6.1.4.1.9839.2.1.3.124 |
current_yearCurrent Yearro Integer32 .1.3.6.1.4.1.9839.2.1.3.125 |
current_hourCurrent Hourro Integer32 .1.3.6.1.4.1.9839.2.1.3.126 |
current_minuteCurrent Minutero Integer32 .1.3.6.1.4.1.9839.2.1.3.127 |
chiller_mode_operationChiller mode operationro Integer32 .1.3.6.1.4.1.9839.2.1.3.150 |
trapObjects OBJECT IDENTIFIER .1.3.6.1.4.1.9839.2.1.100 |
high_pressure_switch_1_alarmHigh pressure switch 1 alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.1 |
high_pressure_switch_2_alarmHigh pressure switch 2 alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.2 |
low_pressure_switch_1_alarmLow pressure switch 1 alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.3 |
low_pressure_switch_2_alarmLow pressure switch 2 alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.4 |
water_level_alarmWater level alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.6 |
flow_switch_alarmFlow switch alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.8 |
water_static_pressure_alarmWater static pressure alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.9 |
water_static_pressure_warningWater static pressure warning NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.10 |
flow_rate_alarmFlow rate alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.11 |
overload_compressor1_circuit1_alarmOverload compressor 1 circuit 1 alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.12 |
overload_compressor2_circuit1_alarmOverload compressor 2 circuit 1 alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.13 |
overload_compressor3_circuit1_alarmOverload compressor 3 circuit 1 alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.14 |
overload_compressor1_circuit2_alarmOverload compressor 1 circuit 2 alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.15 |
overload_compressor2_circuit2_alarmOverload compressor 2 circuit 2 alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.16 |
overload_compressor3_circuit2_alarmOverload compressor 3 circuit 2 alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.17 |
overload_fans_circuit1Overload fans circuit 1 NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.18 |
overload_fans_circuit2Overload fans circuit 2 NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.19 |
overload_fan1_circuit1_alarmOverload fan 1 circuit 1 alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.20 |
overload_fan2_circuit1_alarmOverload fan 2 circuit 1 alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.21 |
overload_fan3_circuit1_alarmOverload fan 3 circuit 1 alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.22 |
overload_fan4_circuit1_alarmOverload fan 4 circuit 1 alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.23 |
overload_fan1_circuit_2_alarmOverload fan 1 circuit 2 alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.24 |
overload_fan2_circuit2_alarmOverload fan 2 circuit 2 alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.25 |
overload_fan3_circuit2_alarmOverload fan 3 circuit 2 alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.26 |
overload_fan4_circuit2_alarmOverload fan 4 circuit 2 alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.27 |
overload_pump1_alarmOverload pump 1 alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.28 |
overload_pump2_alarmOverload pump 2 alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.29 |
wrong_phase_rotation_alarmWrong phase rotation alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.30 |
back_Door_open_alarmBack Door open alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.31 |
alarm_idrofrigo_pump_c_1Condensation pump 1 breaker switch alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.75 |
alarm_idrofrigo_pump_c_2Condensation pump 2 breaker switch alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.76 |
alarm_idrofrigo_fl_CCondensation flow switch alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.80 |
remote_on_offRemote on-off NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.130 |
chiller_ON_OFFChiller ON/OFF NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.131 |
alarm_disch_scw_1Discharge screw compressor 1 alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.148 |
alarm_disch_scw_2Discharge screw compressor 2 alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.149 |
alarm_probe_inletInlet probe alarm (broken or disconnected) NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.150 |
alarm_probe_ambAmbient probe alarm (broken or disconnected) NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.151 |
alarm_frigo_fl1Flow switch alarm (cooling alarm) NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.152 |
alarm_idro_pump1Pump 1 hydraulic alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.153 |
alarm_idro_pump2Pump 2 hydraulic alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.154 |
alarm_idro_fl1Flow switch alarm (hydraulic alarm) NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.155 |
alarm_warning_fl1Flow switch alarm (warning alarm) NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.156 |
alarm_hi_water_tempHigh Temperature alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.157 |
alarm_lo_water_tempLow Temperature alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.158 |
alarm_ta_probe1Antifreeze/evaporator probe 1 alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.159 |
alarm_hi_pressHigh condensation pressure alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.160 |
alarm_lo_pressLow condensation pressure alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.161 |
alarm_probe_evap_1Antifreeze/evaporator probe 1 alarm (broken or disconnected) NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.162 |
alarm_probe_evap_2Antifreeze/evaporator probe 2 alarm (broken or disconnected) NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.163 |
alarm_hi_press_1High condensation pressure 1 alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.164 |
alarm_hi_press_2High condensation pressure 2 alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.165 |
alarm_lo_press_1Low condensation pressure 1 alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.166 |
alarm_lo_press_2Low condensation pressure 2 alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.167 |
alarm_probe_tankTank/Out probe alarm (broken or disconnected) NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.168 |
alarm_off_line_1Chiller 1 offline NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.169 |
alarm_off_line_2Chiller 2 offline NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.170 |
alarm_off_line_3Chiller 3 offline NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.171 |
alarm_off_line_4Chiller 4 offline NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.172 |
alarm_off_line_5Chiller 5 offline NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.173 |
alarm_off_line_6Chiller 6 offline NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.174 |
alarm_off_line_7Chiller 7 offline NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.175 |
alarm_off_line_8Chiller 8 offline NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.176 |
alarm_ta_probe2Antifreeze/evaporator probe 2 alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.177 |
alarm_smsSMS alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.178 |
alarm_modemModem alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.179 |
alarm_sms_codaSMS coda alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.180 |
alarm_probe_fcFreecooling probe alarm (broken or disconnected) NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.181 |
alarm_maint_pw1Maintenance pump 1 alarm) NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.182 |
alarm_maint_pw2Maintenance pump 2 alarm) NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.183 |
alarm_hi_temp_ridHigh temperature alarm (redundance) NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.184 |
alarm_q_fc_sepDryCooler breaker switch alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.185 |
alarm_p_wat2Water pressure 2 alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.186 |
alarm_p_wat1Water pressure 1 alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.187 |
alarm_foult_flow_p1Pump 1 flow alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.188 |
alarm_foult_flow_p2Pump 2 flow alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.189 |
alarm_foult_fl1_p1Pump 1 flow-switch alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.190 |
alarm_foult_fl1_p2Pump 2 flow-switch alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.191 |
alarm_warning_leWater level warning NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.192 |
alarm_frigo_fl_CFlow switch condensation alarm (cooling alarm) NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.193 |
alarm_idro_pump_c_1Pump 1 condensation hydraulic alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.194 |
alarm_idro_pump_c_2Pump 2 condensation hydraulic alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.195 |
alarm_idro_fl_CFlow switch condensation alarm (hydraulic alarm) NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.196 |
alarm_warning_fl_CFlow switch condensation alarm (warning alarm) NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.197 |
alarm_foul_fl_C_p1Pump 1 condensation flow-switch alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.198 |
alarm_foul_fl_C_p2Pump 2 condensation flow-switch alarm NOTIFICATION-TYPE .1.3.6.1.4.1.9839.2.1.100.199 |