Home/Catalog/ROOMALERT32S-MIB

ROOMALERT32S-MIB

AI MIB Summary

Standard SNMP MIB module defining data structures for ROOMALERT32S-MIB.

128
Objects
Active
Status
2
Dependencies

Imported Objects

Objects

128 total
Object Name
avtech
OBJECT IDENTIFIER
.1.3.6.1.4.1.20916
RFC1155-SMI
Unknown
.1.3.6.1.4.1.20916
products
OBJECT IDENTIFIER
.1.3.6.1.4.1.20916.1
roomalert32S
OBJECT IDENTIFIER
.1.3.6.1.4.1.20916.1.11
sensors
OBJECT IDENTIFIER
.1.3.6.1.4.1.20916.1.11.1
internal
OBJECT IDENTIFIER
.1.3.6.1.4.1.20916.1.11.1.1
temperature
OBJECT IDENTIFIER
.1.3.6.1.4.1.20916.1.11.1.1.1
internal-tempfThe internal temperature reading in Fahrenheit.ro
INTEGER
.1.3.6.1.4.1.20916.1.11.1.1.1.1
internal-tempcThe internal temperature reading in Celsius.ro
INTEGER
.1.3.6.1.4.1.20916.1.11.1.1.1.2
humidity
OBJECT IDENTIFIER
.1.3.6.1.4.1.20916.1.11.1.1.2
internal-humidityThe internal relative humidity reading in %RH.ro
INTEGER
.1.3.6.1.4.1.20916.1.11.1.1.2.1
power
OBJECT IDENTIFIER
.1.3.6.1.4.1.20916.1.11.1.1.3
internal-powerThe current status of the Room Alert 32S power supply. A '1' indicates the unit is running on AC/Utility power. A '0' indicates the unit is running on battery backup power.ro
INTEGER
.1.3.6.1.4.1.20916.1.11.1.1.3.1
heat-index
OBJECT IDENTIFIER
.1.3.6.1.4.1.20916.1.11.1.1.4
internal-heat-indexThe internal heat index reading in Fahrenheit.ro
INTEGER
.1.3.6.1.4.1.20916.1.11.1.1.4.1
internal-heat-indexCThe internal heat index reading in Celsius.ro
INTEGER
.1.3.6.1.4.1.20916.1.11.1.1.4.2
analog
OBJECT IDENTIFIER
.1.3.6.1.4.1.20916.1.11.1.1.5
internal-analog1The current status of the Room Alert 32S analog input (0-5VDC).ro
INTEGER
.1.3.6.1.4.1.20916.1.11.1.1.5.1
internal-analog2The current status of the Room Alert 32S analog input (0-5VDC).ro
INTEGER
.1.3.6.1.4.1.20916.1.11.1.1.5.2
relay
OBJECT IDENTIFIER
.1.3.6.1.4.1.20916.1.11.1.1.6
internal-relay1The status of the on-board relay outputrw
INTEGER
.1.3.6.1.4.1.20916.1.11.1.1.6.1
internal-relay2The status of the on-board relay outputrw
INTEGER
.1.3.6.1.4.1.20916.1.11.1.1.6.2
dew-point
OBJECT IDENTIFIER
.1.3.6.1.4.1.20916.1.11.1.1.7
internal-dew-point-cThe internal dew-point reading in Celsius.ro
INTEGER
.1.3.6.1.4.1.20916.1.11.1.1.7.1
internal-dew-point-fThe internal dew-point reading in Fahrenheit.ro
INTEGER
.1.3.6.1.4.1.20916.1.11.1.1.7.2
digital
OBJECT IDENTIFIER
.1.3.6.1.4.1.20916.1.11.1.2
digital-sen1
OBJECT IDENTIFIER
.1.3.6.1.4.1.20916.1.11.1.2.1
digital-sen1-1The sensor's current temperature in Celsius.ro
INTEGER
.1.3.6.1.4.1.20916.1.11.1.2.1.1
digital-sen1-2The sensor's current temperature in Fahrenheit.ro
INTEGER
.1.3.6.1.4.1.20916.1.11.1.2.1.2
digital-sen1-3Varies by sensor type: current % relative humidity, voltage reading (V), power state (1=Power Detected, 0=No Power Detected), thermocouple temperature (C), or air speed (m/s).ro
INTEGER
.1.3.6.1.4.1.20916.1.11.1.2.1.3
digital-sen1-4Varies by sensor type: current heat index (F), custom analog reading, thermocouple temperature (F), or air speed (f/m).ro
INTEGER
.1.3.6.1.4.1.20916.1.11.1.2.1.4
digital-sen1-5Varies by sensor type: current heat index (C), thermocouple fault code (0=No Fault), or air flow (CMH).ro
INTEGER
.1.3.6.1.4.1.20916.1.11.1.2.1.5
digital-sen1-6Varies by sensor type: current dew point (C) or air flow (CFM).ro
INTEGER
.1.3.6.1.4.1.20916.1.11.1.2.1.6
digital-sen1-7Varies by sensor type: current dew point (F).ro
INTEGER
.1.3.6.1.4.1.20916.1.11.1.2.1.7
digital-sen2
OBJECT IDENTIFIER
.1.3.6.1.4.1.20916.1.11.1.2.2
digital-sen2-1The sensor's current temperature in Celsius.ro
INTEGER
.1.3.6.1.4.1.20916.1.11.1.2.2.1
digital-sen2-2The sensor's current temperature in Fahrenheit.ro
INTEGER
.1.3.6.1.4.1.20916.1.11.1.2.2.2
digital-sen2-3Varies by sensor type: current % relative humidity, voltage reading (V), power state (1=Power Detected, 0=No Power Detected), thermocouple temperature (C), or air speed (m/s).ro
INTEGER
.1.3.6.1.4.1.20916.1.11.1.2.2.3
digital-sen2-4Varies by sensor type: current heat index (F), custom analog reading, thermocouple temperature (F), or air speed (f/m).ro
INTEGER
.1.3.6.1.4.1.20916.1.11.1.2.2.4
digital-sen2-5Varies by sensor type: current heat index (C), thermocouple fault code (0=No Fault), or air flow (CMH).ro
INTEGER
.1.3.6.1.4.1.20916.1.11.1.2.2.5
digital-sen2-6Varies by sensor type: current dew point (C) or air flow (CFM).ro
INTEGER
.1.3.6.1.4.1.20916.1.11.1.2.2.6
digital-sen2-7Varies by sensor type: current dew point (F).ro
INTEGER
.1.3.6.1.4.1.20916.1.11.1.2.2.7
digital-sen3
OBJECT IDENTIFIER
.1.3.6.1.4.1.20916.1.11.1.2.3
digital-sen3-1The sensor's current temperature in Celsius.ro
INTEGER
.1.3.6.1.4.1.20916.1.11.1.2.3.1
digital-sen3-2The sensor's current temperature in Fahrenheit.ro
INTEGER
.1.3.6.1.4.1.20916.1.11.1.2.3.2
digital-sen3-3Varies by sensor type: current % relative humidity, voltage reading (V), power state (1=Power Detected, 0=No Power Detected), thermocouple temperature (C), or air speed (m/s).ro
INTEGER
.1.3.6.1.4.1.20916.1.11.1.2.3.3
digital-sen3-4Varies by sensor type: current heat index (F), custom analog reading, thermocouple temperature (F), or air speed (f/m).ro
INTEGER
.1.3.6.1.4.1.20916.1.11.1.2.3.4
digital-sen3-5Varies by sensor type: current heat index (C), thermocouple fault code (0=No Fault), or air flow (CMH).ro
INTEGER
.1.3.6.1.4.1.20916.1.11.1.2.3.5
digital-sen3-6Varies by sensor type: current dew point (C) or air flow (CFM).ro
INTEGER
.1.3.6.1.4.1.20916.1.11.1.2.3.6
digital-sen3-7Varies by sensor type: current dew point (F).ro
INTEGER
.1.3.6.1.4.1.20916.1.11.1.2.3.7
digital-sen4
OBJECT IDENTIFIER
.1.3.6.1.4.1.20916.1.11.1.2.4
digital-sen4-1The sensor's current temperature in Celsius.ro
INTEGER
.1.3.6.1.4.1.20916.1.11.1.2.4.1
digital-sen4-2The sensor's current temperature in Fahrenheit.ro
INTEGER
.1.3.6.1.4.1.20916.1.11.1.2.4.2
digital-sen4-3Varies by sensor type: current % relative humidity, voltage reading (V), power state (1=Power Detected, 0=No Power Detected), thermocouple temperature (C), or air speed (m/s).ro
INTEGER
.1.3.6.1.4.1.20916.1.11.1.2.4.3
digital-sen4-4Varies by sensor type: current heat index (F), custom analog reading, thermocouple temperature (F), or air speed (f/m).ro
INTEGER
.1.3.6.1.4.1.20916.1.11.1.2.4.4
digital-sen4-5Varies by sensor type: current heat index (C), thermocouple fault code (0=No Fault), or air flow (CMH).ro
INTEGER
.1.3.6.1.4.1.20916.1.11.1.2.4.5
digital-sen4-6Varies by sensor type: current dew point (C) or air flow (CFM).ro
INTEGER
.1.3.6.1.4.1.20916.1.11.1.2.4.6
digital-sen4-7Varies by sensor type: current dew point (F).ro
INTEGER
.1.3.6.1.4.1.20916.1.11.1.2.4.7
digital-sen5
OBJECT IDENTIFIER
.1.3.6.1.4.1.20916.1.11.1.2.5
digital-sen5-1The sensor's current temperature in Celsius.ro
INTEGER
.1.3.6.1.4.1.20916.1.11.1.2.5.1
digital-sen5-2The sensor's current temperature in Fahrenheit.ro
INTEGER
.1.3.6.1.4.1.20916.1.11.1.2.5.2
digital-sen5-3Varies by sensor type: current % relative humidity, voltage reading (V), power state (1=Power Detected, 0=No Power Detected), thermocouple temperature (C), or air speed (m/s).ro
INTEGER
.1.3.6.1.4.1.20916.1.11.1.2.5.3
digital-sen5-4Varies by sensor type: current heat index (F), custom analog reading, thermocouple temperature (F), or air speed (f/m).ro
INTEGER
.1.3.6.1.4.1.20916.1.11.1.2.5.4
digital-sen5-5Varies by sensor type: current heat index (C), thermocouple fault code (0=No Fault), or air flow (CMH).ro
INTEGER
.1.3.6.1.4.1.20916.1.11.1.2.5.5
digital-sen5-6Varies by sensor type: current dew point (C) or air flow (CFM).ro
INTEGER
.1.3.6.1.4.1.20916.1.11.1.2.5.6
digital-sen5-7Varies by sensor type: current dew point (F).ro
INTEGER
.1.3.6.1.4.1.20916.1.11.1.2.5.7
digital-sen6
OBJECT IDENTIFIER
.1.3.6.1.4.1.20916.1.11.1.2.6
digital-sen6-1The sensor's current temperature in Celsius.ro
INTEGER
.1.3.6.1.4.1.20916.1.11.1.2.6.1
digital-sen6-2The sensor's current temperature in Fahrenheit.ro
INTEGER
.1.3.6.1.4.1.20916.1.11.1.2.6.2
digital-sen6-3Varies by sensor type: current % relative humidity, voltage reading (V), power state (1=Power Detected, 0=No Power Detected), thermocouple temperature (C), or air speed (m/s).ro
INTEGER
.1.3.6.1.4.1.20916.1.11.1.2.6.3
digital-sen6-4Varies by sensor type: current heat index (F), custom analog reading, thermocouple temperature (F), or air speed (f/m).ro
INTEGER
.1.3.6.1.4.1.20916.1.11.1.2.6.4
digital-sen6-5Varies by sensor type: current heat index (C), thermocouple fault code (0=No Fault), or air flow (CMH).ro
INTEGER
.1.3.6.1.4.1.20916.1.11.1.2.6.5
digital-sen6-6Varies by sensor type: current dew point (C) or air flow (CFM).ro
INTEGER
.1.3.6.1.4.1.20916.1.11.1.2.6.6
digital-sen6-7Varies by sensor type: current dew point (F).ro
INTEGER
.1.3.6.1.4.1.20916.1.11.1.2.6.7
digital-sen7
OBJECT IDENTIFIER
.1.3.6.1.4.1.20916.1.11.1.2.7
digital-sen7-1The sensor's current temperature in Celsius.ro
INTEGER
.1.3.6.1.4.1.20916.1.11.1.2.7.1
digital-sen7-2The sensor's current temperature in Fahrenheit.ro
INTEGER
.1.3.6.1.4.1.20916.1.11.1.2.7.2
digital-sen7-3Varies by sensor type: current % relative humidity, voltage reading (V), power state (1=Power Detected, 0=No Power Detected), thermocouple temperature (C), or air speed (m/s).ro
INTEGER
.1.3.6.1.4.1.20916.1.11.1.2.7.3
digital-sen7-4Varies by sensor type: current heat index (F), custom analog reading, thermocouple temperature (F), or air speed (f/m).ro
INTEGER
.1.3.6.1.4.1.20916.1.11.1.2.7.4
digital-sen7-5Varies by sensor type: current heat index (C), thermocouple fault code (0=No Fault), or air flow (CMH).ro
INTEGER
.1.3.6.1.4.1.20916.1.11.1.2.7.5
digital-sen7-6Varies by sensor type: current dew point (C) or air flow (CFM).ro
INTEGER
.1.3.6.1.4.1.20916.1.11.1.2.7.6
digital-sen7-7Varies by sensor type: current dew point (F).ro
INTEGER
.1.3.6.1.4.1.20916.1.11.1.2.7.7
digital-sen8
OBJECT IDENTIFIER
.1.3.6.1.4.1.20916.1.11.1.2.8
digital-sen8-1The sensor's current temperature in Celsius.ro
INTEGER
.1.3.6.1.4.1.20916.1.11.1.2.8.1
digital-sen8-2The sensor's current temperature in Fahrenheit.ro
INTEGER
.1.3.6.1.4.1.20916.1.11.1.2.8.2
digital-sen8-3Varies by sensor type: current % relative humidity, voltage reading (V), power state (1=Power Detected, 0=No Power Detected), thermocouple temperature (C), or air speed (m/s).ro
INTEGER
.1.3.6.1.4.1.20916.1.11.1.2.8.3
digital-sen8-4Varies by sensor type: current heat index (F), custom analog reading, thermocouple temperature (F), or air speed (f/m).ro
INTEGER
.1.3.6.1.4.1.20916.1.11.1.2.8.4
digital-sen8-5Varies by sensor type: current heat index (C), thermocouple fault code (0=No Fault), or air flow (CMH).ro
INTEGER
.1.3.6.1.4.1.20916.1.11.1.2.8.5
digital-sen8-6Varies by sensor type: current dew point (C) or air flow (CFM).ro
INTEGER
.1.3.6.1.4.1.20916.1.11.1.2.8.6
digital-sen8-7Varies by sensor type: current dew point (F).ro
INTEGER
.1.3.6.1.4.1.20916.1.11.1.2.8.7
switch
OBJECT IDENTIFIER
.1.3.6.1.4.1.20916.1.11.1.3
switch-sen1The reading for switch sensor 1 (0 = OPEN, 1 = CLOSED).ro
INTEGER
.1.3.6.1.4.1.20916.1.11.1.3.1
switch-sen2The reading for switch sensor 2 (0 = OPEN, 1 = CLOSED).ro
INTEGER
.1.3.6.1.4.1.20916.1.11.1.3.2
switch-sen3The reading for switch sensor 3 (0 = OPEN, 1 = CLOSED).ro
INTEGER
.1.3.6.1.4.1.20916.1.11.1.3.3
switch-sen4The reading for switch sensor 4 (0 = OPEN, 1 = CLOSED).ro
INTEGER
.1.3.6.1.4.1.20916.1.11.1.3.4
switch-sen5The reading for switch sensor 5 (0 = OPEN, 1 = CLOSED).ro
INTEGER
.1.3.6.1.4.1.20916.1.11.1.3.5
switch-sen6The reading for switch sensor 6 (0 = OPEN, 1 = CLOSED).ro
INTEGER
.1.3.6.1.4.1.20916.1.11.1.3.6
switch-sen7The reading for switch sensor 7 (0 = OPEN, 1 = CLOSED).ro
INTEGER
.1.3.6.1.4.1.20916.1.11.1.3.7
switch-sen8The reading for switch sensor 8 (0 = OPEN, 1 = CLOSED).ro
INTEGER
.1.3.6.1.4.1.20916.1.11.1.3.8
switch-sen9The reading for switch sensor 9 (0 = OPEN, 1 = CLOSED).ro
INTEGER
.1.3.6.1.4.1.20916.1.11.1.3.9
switch-sen10The reading for switch sensor 10 (0 = OPEN, 1 = CLOSED).ro
INTEGER
.1.3.6.1.4.1.20916.1.11.1.3.10
switch-sen11The reading for switch sensor 11 (0 = OPEN, 1 = CLOSED).ro
INTEGER
.1.3.6.1.4.1.20916.1.11.1.3.11
switch-sen12The reading for switch sensor 12 (0 = OPEN, 1 = CLOSED).ro
INTEGER
.1.3.6.1.4.1.20916.1.11.1.3.12
switch-sen13The reading for switch sensor 13 (0 = OPEN, 1 = CLOSED).ro
INTEGER
.1.3.6.1.4.1.20916.1.11.1.3.13
switch-sen14The reading for switch sensor 14 (0 = OPEN, 1 = CLOSED).ro
INTEGER
.1.3.6.1.4.1.20916.1.11.1.3.14
switch-sen15The reading for switch sensor 15 (0 = OPEN, 1 = CLOSED).ro
INTEGER
.1.3.6.1.4.1.20916.1.11.1.3.15
switch-sen16The reading for switch sensor 16 (0 = OPEN, 1 = CLOSED).ro
INTEGER
.1.3.6.1.4.1.20916.1.11.1.3.16
traps
OBJECT IDENTIFIER
.1.3.6.1.4.1.20916.1.11.2
alarmmessageLast Alarm Messagero
OCTET STRING
.1.3.6.1.4.1.20916.1.11.2.1
externalrelays
OBJECT IDENTIFIER
.1.3.6.1.4.1.20916.1.11.3
externalrelay1
OBJECT IDENTIFIER
.1.3.6.1.4.1.20916.1.11.3.1
externalrelay1-element-oneThe status of the first element on external relay 1.rw
INTEGER
.1.3.6.1.4.1.20916.1.11.3.1.1
externalrelay1-element-twoThe status of the second element on external relay 1.rw
INTEGER
.1.3.6.1.4.1.20916.1.11.3.1.2
externalrelay1-element-threeThe status of the third element on external relay 1.rw
INTEGER
.1.3.6.1.4.1.20916.1.11.3.1.3
externalrelay1-element-fourThe status of the fourth element on external relay 1.rw
INTEGER
.1.3.6.1.4.1.20916.1.11.3.1.4
externalrelay1-element-fiveThe status of the fifth element on external relay 1.rw
INTEGER
.1.3.6.1.4.1.20916.1.11.3.1.5
externalrelay1-element-sixThe status of the sixth element on external relay 1.rw
INTEGER
.1.3.6.1.4.1.20916.1.11.3.1.6
externalrelay1-element-sevenThe status of the seventh element on external relay 1.rw
INTEGER
.1.3.6.1.4.1.20916.1.11.3.1.7
externalrelay1-element-eightThe status of the eighth element on external relay 1rw
INTEGER
.1.3.6.1.4.1.20916.1.11.3.1.8
externalrelay2
OBJECT IDENTIFIER
.1.3.6.1.4.1.20916.1.11.3.2
externalrelay2-element-oneThe status of the first element on external relay 2.rw
INTEGER
.1.3.6.1.4.1.20916.1.11.3.2.1
externalrelay2-element-twoThe status of the second element on external relay 2.rw
INTEGER
.1.3.6.1.4.1.20916.1.11.3.2.2
externalrelay2-element-threeThe status of the third element on external relay 2.rw
INTEGER
.1.3.6.1.4.1.20916.1.11.3.2.3
externalrelay2-element-fourThe status of the fourth element on external relay 2.rw
INTEGER
.1.3.6.1.4.1.20916.1.11.3.2.4
externalrelay2-element-fiveThe status of the fifth element on external relay 2.rw
INTEGER
.1.3.6.1.4.1.20916.1.11.3.2.5
externalrelay2-element-sixThe status of the sixth element on external relay 2.rw
INTEGER
.1.3.6.1.4.1.20916.1.11.3.2.6
externalrelay2-element-sevenThe status of the seventh element on external relay 2.rw
INTEGER
.1.3.6.1.4.1.20916.1.11.3.2.7
externalrelay2-element-eightThe status of the eighth element on external relay 2rw
INTEGER
.1.3.6.1.4.1.20916.1.11.3.2.8
ROOMALERT32S-MIB - SNMP MIB Reference | MIBs Explorer