Home/Catalog/ROOMALERT12E-MIB

ROOMALERT12E-MIB

AI MIB Summary

Standard SNMP MIB module defining data structures for ROOMALERT12E-MIB.

82
Objects
Active
Status
3
Dependencies

Imported Objects

Objects

82 total
Object Name
avtech
OBJECT IDENTIFIER
.1.3.6.1.4.1.20916
RFC1155-SMI
Unknown
.1.3.6.1.4.1.20916
products
OBJECT IDENTIFIER
.1.3.6.1.4.1.20916.1
roomalert12E
OBJECT IDENTIFIER
.1.3.6.1.4.1.20916.1.9
tempalarm1-12EA tempalarm1 trap signifies that the current temperature on external sensor 1 is outside the defined high or low threshold.
TRAP-TYPE
.1.3.6.1.4.1.20916.1.9.0.1
room-alert-12E-snmp-trapA room-alert-12E-snmp-trap indicates that an alarm condition has occurred on the sensor inidcated by the alarmMessage variable.
TRAP-TYPE
.1.3.6.1.4.1.20916.1.9.0.2
tempalarm2-12EA tempalarm2 trap signifies that the current temperature on external sensor 2 is outside the defined high or low threshold.
TRAP-TYPE
.1.3.6.1.4.1.20916.1.9.0.3
tempclear2-12EA tempclear2 trap signifies that the current temperature on external sensor 2 has returned to a normal condition and is within the defined high or low threshold.
TRAP-TYPE
.1.3.6.1.4.1.20916.1.9.0.4
tempalarm3-12EA tempalarm3 trap signifies that the current temperature on external sensor 3 is outside the defined high or low threshold.
TRAP-TYPE
.1.3.6.1.4.1.20916.1.9.0.5
tempclear3-12EA tempclear3 trap signifies that the current temperature on external sensor 3 has returned to a normal condition and is within the defined high or low threshold.
TRAP-TYPE
.1.3.6.1.4.1.20916.1.9.0.6
humidityalarm1-12EA humidityalarm1 trap signifies that the current humidity on external sensor 1 is outside the defined high or low threshold.
TRAP-TYPE
.1.3.6.1.4.1.20916.1.9.0.7
humidityclear1-12EA humidityclear1 trap signifies that the current humidity on external sensor 1 has returned to a normal condition and is within the defined high or low threshold.
TRAP-TYPE
.1.3.6.1.4.1.20916.1.9.0.8
humidityalarm2-12EA humidityalarm2 trap signifies that the current humidity on external sensor 2 is outside the defined high or low threshold.
TRAP-TYPE
.1.3.6.1.4.1.20916.1.9.0.9
humidityclear2-12EA humidityclear2 trap signifies that the current humidity on external sensor 2 has returned to a normal condition and is within the defined high or low threshold.
TRAP-TYPE
.1.3.6.1.4.1.20916.1.9.0.10
humidityalarm3-12EA humidityalarm3 trap signifies that the current humidity on external sensor 3 is outside the defined high or low threshold.
TRAP-TYPE
.1.3.6.1.4.1.20916.1.9.0.11
humidityclear3-12EA humidityclear3 trap signifies that the current humidity on external sensor 3 has returned to a normal condition and is within the defined high or low threshold.
TRAP-TYPE
.1.3.6.1.4.1.20916.1.9.0.12
switchalarm1-12EA switchalarm1 trap signifies that switch sensor 1 is in an alarm state.
TRAP-TYPE
.1.3.6.1.4.1.20916.1.9.0.13
switchclear1-12EA switchclear1 trap signifies that the switch sensor 1 has returned to a normal state.
TRAP-TYPE
.1.3.6.1.4.1.20916.1.9.0.14
switchalarm2-12EA switchalarm2 trap signifies that switch sensor 2 is in an alarm state.
TRAP-TYPE
.1.3.6.1.4.1.20916.1.9.0.15
switchclear2-12EA switchclear2 trap signifies that the switch sensor 2 has returned to a normal state.
TRAP-TYPE
.1.3.6.1.4.1.20916.1.9.0.16
switchalarm3-12EA switchalarm3 trap signifies that switch sensor 3 is in an alarm state.
TRAP-TYPE
.1.3.6.1.4.1.20916.1.9.0.17
switchclear3-12EA switchclear3 trap signifies that the switch sensor 3 has returned to a normal state.
TRAP-TYPE
.1.3.6.1.4.1.20916.1.9.0.18
switchalarm4-12EA switchalarm4 trap signifies that switch sensor 4 is in an alarm state.
TRAP-TYPE
.1.3.6.1.4.1.20916.1.9.0.19
switchclear4-12EA switchclear4 trap signifies that the switch sensor 4 has returned to a normal state.
TRAP-TYPE
.1.3.6.1.4.1.20916.1.9.0.20
sensors
OBJECT IDENTIFIER
.1.3.6.1.4.1.20916.1.9.1
internal-sen
OBJECT IDENTIFIER
.1.3.6.1.4.1.20916.1.9.1.1
internal-sen-1If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Celsius. If this sensor is a Digital Power Sensor, this value represents the Current reading in Amperage.ro
INTEGER
.1.3.6.1.4.1.20916.1.9.1.1.1
internal-sen-2If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Fahrenheit. If this sensor is a Digital Power Sensor, this value represents the Power reading in Watts.ro
INTEGER
.1.3.6.1.4.1.20916.1.9.1.1.2
internal-sen-3If this sensor is a Temp/Humidity sensor, this value represents the current relative humidity in % Relative Humidity. If this sensor is a Digital Power Sensor, this value represents the Voltage reading in Volts.ro
INTEGER
.1.3.6.1.4.1.20916.1.9.1.1.3
internal-sen-4If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Fahrenheit. If this sensor is a Digital Power Sensor, this value represents the Reference reading in Volts.ro
INTEGER
.1.3.6.1.4.1.20916.1.9.1.1.4
internal-sen-5If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Celsius.ro
INTEGER
.1.3.6.1.4.1.20916.1.9.1.1.5
internal-sen-6Represents the sensor's label/ro
OCTET STRING
.1.3.6.1.4.1.20916.1.9.1.1.6
digital-sen1
OBJECT IDENTIFIER
.1.3.6.1.4.1.20916.1.9.1.2
digital-sen1-1If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Celsius. If this sensor is a Digital Power Sensor, this value represents the Current reading in Amperage.ro
INTEGER
.1.3.6.1.4.1.20916.1.9.1.2.1
digital-sen1-2If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Fahrenheit. If this sensor is a Digital Power Sensor, this value represents the Power reading in Watts.ro
INTEGER
.1.3.6.1.4.1.20916.1.9.1.2.2
digital-sen1-3If this sensor is a Temp/Humidity sensor, this value represents the current relative humidity in % Relative Humidity. If this sensor is a Digital Power Sensor, this value represents the Voltage reading in Volts.ro
INTEGER
.1.3.6.1.4.1.20916.1.9.1.2.3
digital-sen1-4If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Fahrenheit. If this sensor is a Digital Power Sensor, this value represents the Reference reading in Volts.ro
INTEGER
.1.3.6.1.4.1.20916.1.9.1.2.4
digital-sen1-5If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Celsius.ro
INTEGER
.1.3.6.1.4.1.20916.1.9.1.2.5
digital-sen1-6Represents the sensor's label/ro
OCTET STRING
.1.3.6.1.4.1.20916.1.9.1.2.6
digital-sen2
OBJECT IDENTIFIER
.1.3.6.1.4.1.20916.1.9.1.3
digital-sen2-1If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Celsius. If this sensor is a Digital Power Sensor, this value represents the Current reading in Amperage.ro
INTEGER
.1.3.6.1.4.1.20916.1.9.1.3.1
digital-sen2-2If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Fahrenheit. If this sensor is a Digital Power Sensor, this value represents the Power reading in Watts.ro
INTEGER
.1.3.6.1.4.1.20916.1.9.1.3.2
digital-sen2-3If this sensor is a Temp/Humidity sensor, this value represents the current relative humidity in % Relative Humidity. If this sensor is a Digital Power Sensor, this value represents the Voltage reading in Volts.ro
INTEGER
.1.3.6.1.4.1.20916.1.9.1.3.3
digital-sen2-4If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Fahrenheit. If this sensor is a Digital Power Sensor, this value represents the Reference reading in Volts.ro
INTEGER
.1.3.6.1.4.1.20916.1.9.1.3.4
digital-sen2-5If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Celsius.ro
INTEGER
.1.3.6.1.4.1.20916.1.9.1.3.5
digital-sen2-6Represents the sensor's label/ro
OCTET STRING
.1.3.6.1.4.1.20916.1.9.1.3.6
digital-sen3
OBJECT IDENTIFIER
.1.3.6.1.4.1.20916.1.9.1.4
digital-sen3-1If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Celsius. If this sensor is a Digital Power Sensor, this value represents the Current reading in Amperage.ro
INTEGER
.1.3.6.1.4.1.20916.1.9.1.4.1
digital-sen3-2If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Fahrenheit. If this sensor is a Digital Power Sensor, this value represents the Power reading in Watts.ro
INTEGER
.1.3.6.1.4.1.20916.1.9.1.4.2
digital-sen3-3If this sensor is a Temp/Humidity sensor, this value represents the current relative humidity in % Relative Humidity. If this sensor is a Digital Power Sensor, this value represents the Voltage reading in Volts.ro
INTEGER
.1.3.6.1.4.1.20916.1.9.1.4.3
digital-sen3-4If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Fahrenheit. If this sensor is a Digital Power Sensor, this value represents the Reference reading in Volts.ro
INTEGER
.1.3.6.1.4.1.20916.1.9.1.4.4
digital-sen3-5If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Celsius.ro
INTEGER
.1.3.6.1.4.1.20916.1.9.1.4.5
digital-sen3-6Represents the sensor's label/ro
OCTET STRING
.1.3.6.1.4.1.20916.1.9.1.4.6
switch1
OBJECT IDENTIFIER
.1.3.6.1.4.1.20916.1.9.1.5
switch-sen1-1The reading for switch sensor 1 (0 = OPEN, 1 = CLOSED).ro
INTEGER
.1.3.6.1.4.1.20916.1.9.1.5.1
switch-sen1-2The label for switch sensor 1.ro
OCTET STRING
.1.3.6.1.4.1.20916.1.9.1.5.2
switch2
OBJECT IDENTIFIER
.1.3.6.1.4.1.20916.1.9.1.6
switch-sen2The reading for switch sensor 2 (0 = OPEN, 1 = CLOSED).ro
INTEGER
.1.3.6.1.4.1.20916.1.9.1.6.1
switch-sen2-2The label for switch sensor 2.ro
OCTET STRING
.1.3.6.1.4.1.20916.1.9.1.6.2
switch3
OBJECT IDENTIFIER
.1.3.6.1.4.1.20916.1.9.1.7
switch-sen3The reading for switch sensor 3 (0 = OPEN, 1 = CLOSED).ro
INTEGER
.1.3.6.1.4.1.20916.1.9.1.7.1
switch-sen3-2The label for switch sensor 3.ro
OCTET STRING
.1.3.6.1.4.1.20916.1.9.1.7.2
switch4
OBJECT IDENTIFIER
.1.3.6.1.4.1.20916.1.9.1.8
switch-sen4The reading for switch sensor 4 (0 = OPEN, 1 = CLOSED).ro
INTEGER
.1.3.6.1.4.1.20916.1.9.1.8.1
switch-sen4-2The label for switch sensor 4.ro
OCTET STRING
.1.3.6.1.4.1.20916.1.9.1.8.2
analog
OBJECT IDENTIFIER
.1.3.6.1.4.1.20916.1.9.1.9
analog-1The current status of the Room Alert 12E analog input (0-5VDC).ro
INTEGER
.1.3.6.1.4.1.20916.1.9.1.9.1
analog-2The analog sensor's label.ro
OCTET STRING
.1.3.6.1.4.1.20916.1.9.1.9.2
relay
OBJECT IDENTIFIER
.1.3.6.1.4.1.20916.1.9.1.10
relay-1The current status of the Room Alert 12E relay output.rw
INTEGER
.1.3.6.1.4.1.20916.1.9.1.10.1
relay-2The relay output's label.ro
OCTET STRING
.1.3.6.1.4.1.20916.1.9.1.10.2
lightTower
OBJECT IDENTIFIER
.1.3.6.1.4.1.20916.1.9.2
lightTower-REThe status of the red LED on the Light Tower.rw
INTEGER
.1.3.6.1.4.1.20916.1.9.2.1
lightTower-ORThe status of the orange LED on the Light Tower.rw
INTEGER
.1.3.6.1.4.1.20916.1.9.2.2
lightTower-GRThe status of the green LED on the Light Tower.rw
INTEGER
.1.3.6.1.4.1.20916.1.9.2.3
lightTower-WHThe status of the white LED on the Light Tower.rw
INTEGER
.1.3.6.1.4.1.20916.1.9.2.4
lightTower-BLThe status of the blue LED on the Light Tower.rw
INTEGER
.1.3.6.1.4.1.20916.1.9.2.5
lightTower-A1The status of the 1st audio alarm on the Light Tower.rw
INTEGER
.1.3.6.1.4.1.20916.1.9.2.6
lightTower-A2The status of the 2nd audio alarm on the Light Tower.rw
INTEGER
.1.3.6.1.4.1.20916.1.9.2.7
lightTower-RLThe status of the LTA's on-board relay outputrw
INTEGER
.1.3.6.1.4.1.20916.1.9.2.8
traps
OBJECT IDENTIFIER
.1.3.6.1.4.1.20916.1.9.3
alarmmessageLast Alarm Messagero
OCTET STRING
.1.3.6.1.4.1.20916.1.9.3.1