ROOMALERT12E-MIB
AI MIB Summary
Standard SNMP MIB module defining data structures for ROOMALERT12E-MIB.
82
Objects
Active
Status
3
Dependencies
Imported Objects
Objects
82 total| Object Name |
|---|
avtech OBJECT IDENTIFIER .1.3.6.1.4.1.20916 |
RFC1155-SMI Unknown .1.3.6.1.4.1.20916 |
products OBJECT IDENTIFIER .1.3.6.1.4.1.20916.1 |
roomalert12E OBJECT IDENTIFIER .1.3.6.1.4.1.20916.1.9 |
tempalarm1-12EA tempalarm1 trap signifies that the current
temperature on external sensor 1 is outside the
defined high or low threshold. TRAP-TYPE .1.3.6.1.4.1.20916.1.9.0.1 |
room-alert-12E-snmp-trapA room-alert-12E-snmp-trap indicates that an alarm
condition has occurred on the sensor inidcated
by the alarmMessage variable. TRAP-TYPE .1.3.6.1.4.1.20916.1.9.0.2 |
tempalarm2-12EA tempalarm2 trap signifies that the current
temperature on external sensor 2 is outside the
defined high or low threshold. TRAP-TYPE .1.3.6.1.4.1.20916.1.9.0.3 |
tempclear2-12EA tempclear2 trap signifies that the current
temperature on external sensor 2 has returned to
a normal condition and is within the defined
high or low threshold. TRAP-TYPE .1.3.6.1.4.1.20916.1.9.0.4 |
tempalarm3-12EA tempalarm3 trap signifies that the current
temperature on external sensor 3 is outside the
defined high or low threshold. TRAP-TYPE .1.3.6.1.4.1.20916.1.9.0.5 |
tempclear3-12EA tempclear3 trap signifies that the current
temperature on external sensor 3 has returned to
a normal condition and is within the defined
high or low threshold. TRAP-TYPE .1.3.6.1.4.1.20916.1.9.0.6 |
humidityalarm1-12EA humidityalarm1 trap signifies that the current
humidity on external sensor 1 is outside the
defined high or low threshold. TRAP-TYPE .1.3.6.1.4.1.20916.1.9.0.7 |
humidityclear1-12EA humidityclear1 trap signifies that the current
humidity on external sensor 1 has returned to
a normal condition and is within the defined
high or low threshold. TRAP-TYPE .1.3.6.1.4.1.20916.1.9.0.8 |
humidityalarm2-12EA humidityalarm2 trap signifies that the current
humidity on external sensor 2 is outside the
defined high or low threshold. TRAP-TYPE .1.3.6.1.4.1.20916.1.9.0.9 |
humidityclear2-12EA humidityclear2 trap signifies that the current
humidity on external sensor 2 has returned to
a normal condition and is within the defined
high or low threshold. TRAP-TYPE .1.3.6.1.4.1.20916.1.9.0.10 |
humidityalarm3-12EA humidityalarm3 trap signifies that the current
humidity on external sensor 3 is outside the
defined high or low threshold. TRAP-TYPE .1.3.6.1.4.1.20916.1.9.0.11 |
humidityclear3-12EA humidityclear3 trap signifies that the current
humidity on external sensor 3 has returned to
a normal condition and is within the defined
high or low threshold. TRAP-TYPE .1.3.6.1.4.1.20916.1.9.0.12 |
switchalarm1-12EA switchalarm1 trap signifies that switch sensor 1
is in an alarm state. TRAP-TYPE .1.3.6.1.4.1.20916.1.9.0.13 |
switchclear1-12EA switchclear1 trap signifies that the switch sensor 1
has returned to a normal state. TRAP-TYPE .1.3.6.1.4.1.20916.1.9.0.14 |
switchalarm2-12EA switchalarm2 trap signifies that switch sensor 2
is in an alarm state. TRAP-TYPE .1.3.6.1.4.1.20916.1.9.0.15 |
switchclear2-12EA switchclear2 trap signifies that the switch sensor 2
has returned to a normal state. TRAP-TYPE .1.3.6.1.4.1.20916.1.9.0.16 |
switchalarm3-12EA switchalarm3 trap signifies that switch sensor 3
is in an alarm state. TRAP-TYPE .1.3.6.1.4.1.20916.1.9.0.17 |
switchclear3-12EA switchclear3 trap signifies that the switch sensor 3
has returned to a normal state. TRAP-TYPE .1.3.6.1.4.1.20916.1.9.0.18 |
switchalarm4-12EA switchalarm4 trap signifies that switch sensor 4
is in an alarm state. TRAP-TYPE .1.3.6.1.4.1.20916.1.9.0.19 |
switchclear4-12EA switchclear4 trap signifies that the switch sensor 4
has returned to a normal state. TRAP-TYPE .1.3.6.1.4.1.20916.1.9.0.20 |
sensors OBJECT IDENTIFIER .1.3.6.1.4.1.20916.1.9.1 |
internal-sen OBJECT IDENTIFIER .1.3.6.1.4.1.20916.1.9.1.1 |
internal-sen-1If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Celsius. If this sensor is a Digital Power Sensor, this value represents the Current reading in Amperage.ro INTEGER .1.3.6.1.4.1.20916.1.9.1.1.1 |
internal-sen-2If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Fahrenheit. If this sensor is a Digital Power Sensor, this value represents the Power reading in Watts.ro INTEGER .1.3.6.1.4.1.20916.1.9.1.1.2 |
internal-sen-3If this sensor is a Temp/Humidity sensor, this value represents the current relative humidity in % Relative Humidity. If this sensor is a Digital Power Sensor, this value represents the Voltage reading in Volts.ro INTEGER .1.3.6.1.4.1.20916.1.9.1.1.3 |
internal-sen-4If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Fahrenheit. If this sensor is a Digital Power Sensor, this value represents the Reference reading in Volts.ro INTEGER .1.3.6.1.4.1.20916.1.9.1.1.4 |
internal-sen-5If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Celsius.ro INTEGER .1.3.6.1.4.1.20916.1.9.1.1.5 |
internal-sen-6Represents the sensor's label/ro OCTET STRING .1.3.6.1.4.1.20916.1.9.1.1.6 |
digital-sen1 OBJECT IDENTIFIER .1.3.6.1.4.1.20916.1.9.1.2 |
digital-sen1-1If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Celsius. If this sensor is a Digital Power Sensor, this value represents the Current reading in Amperage.ro INTEGER .1.3.6.1.4.1.20916.1.9.1.2.1 |
digital-sen1-2If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Fahrenheit. If this sensor is a Digital Power Sensor, this value represents the Power reading in Watts.ro INTEGER .1.3.6.1.4.1.20916.1.9.1.2.2 |
digital-sen1-3If this sensor is a Temp/Humidity sensor, this value represents the current relative humidity in % Relative Humidity. If this sensor is a Digital Power Sensor, this value represents the Voltage reading in Volts.ro INTEGER .1.3.6.1.4.1.20916.1.9.1.2.3 |
digital-sen1-4If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Fahrenheit. If this sensor is a Digital Power Sensor, this value represents the Reference reading in Volts.ro INTEGER .1.3.6.1.4.1.20916.1.9.1.2.4 |
digital-sen1-5If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Celsius.ro INTEGER .1.3.6.1.4.1.20916.1.9.1.2.5 |
digital-sen1-6Represents the sensor's label/ro OCTET STRING .1.3.6.1.4.1.20916.1.9.1.2.6 |
digital-sen2 OBJECT IDENTIFIER .1.3.6.1.4.1.20916.1.9.1.3 |
digital-sen2-1If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Celsius. If this sensor is a Digital Power Sensor, this value represents the Current reading in Amperage.ro INTEGER .1.3.6.1.4.1.20916.1.9.1.3.1 |
digital-sen2-2If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Fahrenheit. If this sensor is a Digital Power Sensor, this value represents the Power reading in Watts.ro INTEGER .1.3.6.1.4.1.20916.1.9.1.3.2 |
digital-sen2-3If this sensor is a Temp/Humidity sensor, this value represents the current relative humidity in % Relative Humidity. If this sensor is a Digital Power Sensor, this value represents the Voltage reading in Volts.ro INTEGER .1.3.6.1.4.1.20916.1.9.1.3.3 |
digital-sen2-4If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Fahrenheit. If this sensor is a Digital Power Sensor, this value represents the Reference reading in Volts.ro INTEGER .1.3.6.1.4.1.20916.1.9.1.3.4 |
digital-sen2-5If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Celsius.ro INTEGER .1.3.6.1.4.1.20916.1.9.1.3.5 |
digital-sen2-6Represents the sensor's label/ro OCTET STRING .1.3.6.1.4.1.20916.1.9.1.3.6 |
digital-sen3 OBJECT IDENTIFIER .1.3.6.1.4.1.20916.1.9.1.4 |
digital-sen3-1If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Celsius. If this sensor is a Digital Power Sensor, this value represents the Current reading in Amperage.ro INTEGER .1.3.6.1.4.1.20916.1.9.1.4.1 |
digital-sen3-2If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Fahrenheit. If this sensor is a Digital Power Sensor, this value represents the Power reading in Watts.ro INTEGER .1.3.6.1.4.1.20916.1.9.1.4.2 |
digital-sen3-3If this sensor is a Temp/Humidity sensor, this value represents the current relative humidity in % Relative Humidity. If this sensor is a Digital Power Sensor, this value represents the Voltage reading in Volts.ro INTEGER .1.3.6.1.4.1.20916.1.9.1.4.3 |
digital-sen3-4If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Fahrenheit. If this sensor is a Digital Power Sensor, this value represents the Reference reading in Volts.ro INTEGER .1.3.6.1.4.1.20916.1.9.1.4.4 |
digital-sen3-5If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Celsius.ro INTEGER .1.3.6.1.4.1.20916.1.9.1.4.5 |
digital-sen3-6Represents the sensor's label/ro OCTET STRING .1.3.6.1.4.1.20916.1.9.1.4.6 |
switch1 OBJECT IDENTIFIER .1.3.6.1.4.1.20916.1.9.1.5 |
switch-sen1-1The reading for switch sensor 1 (0 = OPEN, 1 = CLOSED).ro INTEGER .1.3.6.1.4.1.20916.1.9.1.5.1 |
switch-sen1-2The label for switch sensor 1.ro OCTET STRING .1.3.6.1.4.1.20916.1.9.1.5.2 |
switch2 OBJECT IDENTIFIER .1.3.6.1.4.1.20916.1.9.1.6 |
switch-sen2The reading for switch sensor 2 (0 = OPEN, 1 = CLOSED).ro INTEGER .1.3.6.1.4.1.20916.1.9.1.6.1 |
switch-sen2-2The label for switch sensor 2.ro OCTET STRING .1.3.6.1.4.1.20916.1.9.1.6.2 |
switch3 OBJECT IDENTIFIER .1.3.6.1.4.1.20916.1.9.1.7 |
switch-sen3The reading for switch sensor 3 (0 = OPEN, 1 = CLOSED).ro INTEGER .1.3.6.1.4.1.20916.1.9.1.7.1 |
switch-sen3-2The label for switch sensor 3.ro OCTET STRING .1.3.6.1.4.1.20916.1.9.1.7.2 |
switch4 OBJECT IDENTIFIER .1.3.6.1.4.1.20916.1.9.1.8 |
switch-sen4The reading for switch sensor 4 (0 = OPEN, 1 = CLOSED).ro INTEGER .1.3.6.1.4.1.20916.1.9.1.8.1 |
switch-sen4-2The label for switch sensor 4.ro OCTET STRING .1.3.6.1.4.1.20916.1.9.1.8.2 |
analog OBJECT IDENTIFIER .1.3.6.1.4.1.20916.1.9.1.9 |
analog-1The current status of the Room Alert 12E analog input (0-5VDC).ro INTEGER .1.3.6.1.4.1.20916.1.9.1.9.1 |
analog-2The analog sensor's label.ro OCTET STRING .1.3.6.1.4.1.20916.1.9.1.9.2 |
relay OBJECT IDENTIFIER .1.3.6.1.4.1.20916.1.9.1.10 |
relay-1The current status of the Room Alert 12E relay output.rw INTEGER .1.3.6.1.4.1.20916.1.9.1.10.1 |
relay-2The relay output's label.ro OCTET STRING .1.3.6.1.4.1.20916.1.9.1.10.2 |
lightTower OBJECT IDENTIFIER .1.3.6.1.4.1.20916.1.9.2 |
lightTower-REThe status of the red LED on the Light Tower.rw INTEGER .1.3.6.1.4.1.20916.1.9.2.1 |
lightTower-ORThe status of the orange LED on the Light Tower.rw INTEGER .1.3.6.1.4.1.20916.1.9.2.2 |
lightTower-GRThe status of the green LED on the Light Tower.rw INTEGER .1.3.6.1.4.1.20916.1.9.2.3 |
lightTower-WHThe status of the white LED on the Light Tower.rw INTEGER .1.3.6.1.4.1.20916.1.9.2.4 |
lightTower-BLThe status of the blue LED on the Light Tower.rw INTEGER .1.3.6.1.4.1.20916.1.9.2.5 |
lightTower-A1The status of the 1st audio alarm on the Light Tower.rw INTEGER .1.3.6.1.4.1.20916.1.9.2.6 |
lightTower-A2The status of the 2nd audio alarm on the Light Tower.rw INTEGER .1.3.6.1.4.1.20916.1.9.2.7 |
lightTower-RLThe status of the LTA's on-board relay outputrw INTEGER .1.3.6.1.4.1.20916.1.9.2.8 |
traps OBJECT IDENTIFIER .1.3.6.1.4.1.20916.1.9.3 |
alarmmessageLast Alarm Messagero OCTET STRING .1.3.6.1.4.1.20916.1.9.3.1 |