Home/Catalog/LIEBERT-UPS-MIB

LIEBERT-UPS-MIB

AI MIB Summary

Standard SNMP MIB module defining data structures for LIEBERT-UPS-MIB.

278
Objects
Active
Status
4
Dependencies

Imported Objects

Objects

278 total
Object Name
emerson
OBJECT IDENTIFIER
.1.3.6.1.4.1.476
RFC1155-SMI
Unknown
.1.3.6.1.4.1.476
liebertCorp
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1
liebertUps
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1
luExtensions
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1
luCore
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.1
lcUpsIdent
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.1.1
lcUpsIdentManufacturerThe UPS manufacturer.ro
DisplayString
.1.3.6.1.4.1.476.1.1.1.1.1.1
lcUpsIdentModelThe UPS Model designation.rw
DisplayString
.1.3.6.1.4.1.476.1.1.1.1.1.2
lcUpsIdentSoftwareVersionThe UPS SNMP Agent software version.ro
DisplayString
.1.3.6.1.4.1.476.1.1.1.1.1.3
lcUpsIdentSpecificA reference to MIB definitions specific to the particular UPS being managed. This object is used to locate the product-specific MIB for this device. If this information is not present, its value should be the OBJECT IDENTIFIER { 0 0 }, which is a syntactically valid object identifier, and any conformant implementation of ASN.1 and BER must be able to generate and recognize this value.ro
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.1.1.4
lcUpsIdentFirmwareVersionThe firmware revision level of the UPS.ro
DisplayString
.1.3.6.1.4.1.476.1.1.1.1.1.5
lcUpsIdentSerialNumberThe serial number of the UPS.ro
DisplayString
.1.3.6.1.4.1.476.1.1.1.1.1.6
lcUpsIdentManufactureDateThe date of manufacture of the UPS.ro
DisplayString
.1.3.6.1.4.1.476.1.1.1.1.1.7
lcUpsBattery
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.1.2
lcUpsBatTimeRemainingThe estimated time to depletion of battery charge. (Unit of measure: Minute)ro
INTEGER
.1.3.6.1.4.1.476.1.1.1.1.2.1
lcUpsBatTemperatureThe battery temperature. (Unit of measure: Degree, Centigrade)ro
INTEGER (-32768..32767)
.1.3.6.1.4.1.476.1.1.1.1.2.2
lcUpsBatVoltageThe current battery voltage. (Unit of measure: volt)ro
INTEGER (-32768..32767)
.1.3.6.1.4.1.476.1.1.1.1.2.3
lcUpsBatCurrentThe current battery discharging/charging current. (Unit of measure: Amp)ro
INTEGER (-32768..32767)
.1.3.6.1.4.1.476.1.1.1.1.2.4
lcUpsBatCapacityThe current battery capacity in percentage of total available.ro
INTEGER
.1.3.6.1.4.1.476.1.1.1.1.2.6
lcUpsBatTotalDischCountsThe number of discharges the UPS has experienced.ro
Counter
.1.3.6.1.4.1.476.1.1.1.1.2.7
lcUpsBatCycleDurationInSecondsThe total accumulated discharge time in seconds.ro
Counter
.1.3.6.1.4.1.476.1.1.1.1.2.8
lcUpsBatAmpHoursThe number of amp hours withdrawn from battery.ro
Counter
.1.3.6.1.4.1.476.1.1.1.1.2.9
lcUpsBatKWhoursThe number of Kilowatt-hours withdrawn from battery.ro
Counter
.1.3.6.1.4.1.476.1.1.1.1.2.10
lcUpsBatWattHoursThe number of Watt-hours withdrawn from battery.ro
Counter
.1.3.6.1.4.1.476.1.1.1.1.2.11
lcUpsInput
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.1.3
lcUpsInputFrequencyThe current input frequency. (Unit of measure: Hertz)ro
INTEGER
.1.3.6.1.4.1.476.1.1.1.1.3.1
lcUpsInputBrownOutsThe number of brown-out conditions the UPS has experienced.ro
Counter
.1.3.6.1.4.1.476.1.1.1.1.3.2
lcUpsInputBlackOutsThe number of black-out conditions the UPS has experienced.ro
Counter
.1.3.6.1.4.1.476.1.1.1.1.3.3
lcUpsInputTransientsThe number of transient (surge and spike) conditions the UPS has experienced.ro
Counter
.1.3.6.1.4.1.476.1.1.1.1.3.4
lcUpsInputNumLinesThe number of input lines utilized in this device. This entry indicates the number of rows in the input table.ro
INTEGER
.1.3.6.1.4.1.476.1.1.1.1.3.5
lcUpsInputTable
SEQUENCE OF LcUpsInputEntry
.1.3.6.1.4.1.476.1.1.1.1.3.6
lcUpsInputEntry
LcUpsInputEntry
.1.3.6.1.4.1.476.1.1.1.1.3.6.1
lcUpsInputLineThe input Line.ro
INTEGER
.1.3.6.1.4.1.476.1.1.1.1.3.6.1.1
lcUpsInputVoltageThe input voltage. (Unit of measure: Volt)ro
INTEGER
.1.3.6.1.4.1.476.1.1.1.1.3.6.1.2
lcUpsInputCurrentThe input current. (Unit of measure: Amp)ro
INTEGER
.1.3.6.1.4.1.476.1.1.1.1.3.6.1.3
lcUpsInputVAThe input volt-amps.ro
INTEGER
.1.3.6.1.4.1.476.1.1.1.1.3.6.1.4
lcUpsOutput
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.1.4
lcUpsOutputFrequencyThe current output frequency. (Unit of measure: Hertz)ro
INTEGER
.1.3.6.1.4.1.476.1.1.1.1.4.1
lcUpsOutputLoadThe current output load percentage.ro
INTEGER
.1.3.6.1.4.1.476.1.1.1.1.4.2
lcUpsOutputNumLinesThe number of output lines utilized in this device. This entry indicates the number of rows in the output table.ro
INTEGER
.1.3.6.1.4.1.476.1.1.1.1.4.3
lcUpsOutputTable
SEQUENCE OF LcUpsOutputEntry
.1.3.6.1.4.1.476.1.1.1.1.4.4
lcUpsOutputEntry
LcUpsOutputEntry
.1.3.6.1.4.1.476.1.1.1.1.4.4.1
lcUpsOutputLineThe output Line.ro
INTEGER
.1.3.6.1.4.1.476.1.1.1.1.4.4.1.1
lcUpsOutputVoltageThe output voltage. (Unit of measure: Volt)ro
INTEGER
.1.3.6.1.4.1.476.1.1.1.1.4.4.1.2
lcUpsOutputCurrentThe output current. (Unit of measure: Amp)ro
INTEGER
.1.3.6.1.4.1.476.1.1.1.1.4.4.1.3
lcUpsOutputVAThe output volt-amps.ro
INTEGER
.1.3.6.1.4.1.476.1.1.1.1.4.4.1.4
lcUpsOutputWattsThe output power in watts.ro
INTEGER
.1.3.6.1.4.1.476.1.1.1.1.4.5
lcUpsInverter
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.1.5
lcUpsInverterStatusThe state of the inverter. Unknown is returned if the state can not be determined.ro
Enumeration
.1.3.6.1.4.1.476.1.1.1.1.5.1
lcUpsInverterTempThe temperature of the inverter. (Unit of measure: degree, Centigrade)ro
INTEGER (-32768..32767)
.1.3.6.1.4.1.476.1.1.1.1.5.2
lcUpsAlarm
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.1.6
lcUpsAlarmsThe current number of alarm conditions.ro
Gauge
.1.3.6.1.4.1.476.1.1.1.1.6.1
lcUpsAlarmTable
SEQUENCE OF LcUpsAlarmEntry
.1.3.6.1.4.1.476.1.1.1.1.6.2
lcUpsAlarmEntry
LcUpsAlarmEntry
.1.3.6.1.4.1.476.1.1.1.1.6.2.1
lcUpsAlarmIdA unique identifier for an alarm condition. This value must remain constant between agent initializations.ro
INTEGER
.1.3.6.1.4.1.476.1.1.1.1.6.2.1.1
lcUpsAlarmDescrA reference to an alarm description object. The object referenced should not be accessible, but rather be used to provide a unique description of the alarm condition.ro
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.1.6.2.1.2
lcUpsAlarmTimeThe value of sysUpTime when the alarm condition occured.ro
TimeTicks (SNMPv2-SMI)
.1.3.6.1.4.1.476.1.1.1.1.6.2.1.3
lcUpsAlarmConditions
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.1.6.3
lcUpsAlarmLowBatteryWarning
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.1.6.3.1
lcUpsAlarmLowBatteryShutdown
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.1.6.3.2
lcUpsAlarmUtilFailed
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.1.6.3.3
lcUpsAlarmOverTempWarning
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.1.6.3.4
lcUpsAlarmOverTempShutdown
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.1.6.3.5
lcUpsAlarmOutputOverloadWarning
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.1.6.3.6
lcUpsAlarmOutputOverloadShutdown
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.1.6.3.7
lcUpsAlarmInputOverVoltage
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.1.6.3.8
lcUpsAlarmBatteryBad
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.1.6.3.9
lcUpsAlarmOnBattery
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.1.6.3.10
lcUpsAlarmStopNoticeIssued
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.1.6.3.11
lcUpsAlarmUpsOff
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.1.6.3.12
lcUpsAlarmInputFreqError
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.1.6.3.13
lcUpsAlarmOutputUnderVoltage
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.1.6.3.15
lcUpsAlarmOutputOverVoltage
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.1.6.3.16
lcUpsBadBypassPower
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.1.6.3.17
lcUpsAlarmDCOverVoltageShutdown
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.1.6.3.18
lcUpsAlarmHardwareShutdown
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.1.6.3.23
lcUpsAlarmEmergencyXferToBypass
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.1.6.3.24
lcUpsAlarmInverterFault
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.1.6.3.25
lcUpsAlarmPhaseRotationError
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.1.6.3.26
lcUpsAlarmFuseBlown
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.1.6.3.28
lcUpsAlarmAmbientOverTemp
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.1.6.3.29
lcUpsAlarmEmergencyPowerOff
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.1.6.3.30
lcUpsAlarmFanFailed
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.1.6.3.31
lcUpsAlarmControlPowerFailed
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.1.6.3.32
lcUpsAlarmReversePower
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.1.6.3.33
lcUpsAlarmDCgroundFault
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.1.6.3.34
lcUpsAlarmLoadOnBypass
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.1.6.3.35
lcUpsAlarmBatteryCbOpen
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.1.6.3.37
lcUpsAlarmInputCbOpen
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.1.6.3.38
lcUpsAlarmOutputCbOpen
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.1.6.3.39
lcUpsAlarmOutputFreqError
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.1.6.3.40
lcUpsAlarmStaticSwUnable
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.1.6.3.41
lcUpsAlarmManualResetXfer
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.1.6.3.42
lcUpsAlarmAutoRexferPrimed
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.1.6.3.43
lcUpsAlarmBattCycleBuffWarn
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.1.6.3.44
lcUpsAlarmModuleSummary
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.1.6.3.45
lcUpsLineCorrectionActive
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.1.6.3.46
lcUpsTest
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.1.7
lcUpsTestBatterySetting this variable to 'start' will initiate the battery test. Setting this variable to 'abort' will stop the battery test if the test is in- progress, otherwise it has no effect. Setting this variable to 'unknown' has no effect. Reading this variable will always result in a return value of 'unknown'. If 'lcUpsTestBatteryStatus' is 'failed' the test may not be performed again and the status will remain in the failure state.rw
Enumeration
.1.3.6.1.4.1.476.1.1.1.1.7.1
lcUpsTestBatteryStatusThe status of the battery test.ro
Enumeration
.1.3.6.1.4.1.476.1.1.1.1.7.2
lcUpsTestDiagSetting this variable to 'start' will initiate the diagnostics test. Setting this variable to 'abort' will stop the diagnostics test if the test is in-progress, otherwise it has no effect. Setting this variable to 'unknown' has no effect. Reading this variable will always result in a return value of 'unknown'.rw
Enumeration
.1.3.6.1.4.1.476.1.1.1.1.7.3
lcUpsTestDiagStatusThe status of the diagnostics test.ro
Enumeration
.1.3.6.1.4.1.476.1.1.1.1.7.4
lcUpsControl
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.1.8
lcUpsControlOutputOffDelaySetting this object causes the agent to instruct the UPS to turn off the output after the indicated number of seconds. The agent counts down the number of seconds until the event will take place. The agent issues an lcUpsOutputOffTrap when the countdown finishes. Note that different models have different clock resolutions, usually greater than 1 second. As a result, the command will only be accurate to the resolution of the UPS's clock. The command can be cancelled by setting lcUpsControlCancelCommand to the value cancel.rw
INTEGER
.1.3.6.1.4.1.476.1.1.1.1.8.1
lcUpsControlOutputOnDelaySetting this object causes the agent to instruct the UPS to turn on the output after the indicated number of seconds. The agent counts down the number of seconds until the event will take place. The agent issues an lcUpsOutputOnTrap when the countdown finishes. Note that different models have different clock resolutions, usually greater than 1 second. As a result, the command will only be accurate to the resolution of the UPS's clock. The command can be cancelled by setting lcUpsControlCancelCommand to the value cancel.rw
INTEGER
.1.3.6.1.4.1.476.1.1.1.1.8.2
lcUpsControlOutputOffTrapDelayWhen 'lcUpsControlOutputOffDelay' reaches a value less than or equal to this object's value, an lcUpsOutputOffWarningTrap will be produced and this object will be reset to 0.rw
INTEGER
.1.3.6.1.4.1.476.1.1.1.1.8.3
lcUpsControlOutputOnTrapDelayWhen 'lcUpsControlOutputOnDelay' reaches a value less than or equal to this object's value, an lcUpsOutputOnWarningTrap will be produced and this object will be reset to 0.rw
INTEGER
.1.3.6.1.4.1.476.1.1.1.1.8.4
lcUpsControlUnixShutdownDelaySetting this object causes the agent to instruct the UPS to perform a UNIX Shutdown in the indicated number of seconds. The agent counts down the number of seconds until the event will take place. A Unix shutdown is only valid if the UPS is on Battery. During a UNIX Shutdown, the UPS will turn off the output even if the Utility comes back on line before the shutdown time arrives. Note that different models have different clock resolutions, usually greater than 1 second. As a result, the command will only be accurate to the resolution of the UPS's clock. The command can be cancelled by setting lcUpsControlCancelCommand to the value 'cancel'.rw
INTEGER
.1.3.6.1.4.1.476.1.1.1.1.8.5
lcUpsControlUnixShutdownTrapDelayWhen 'lcUpsControlUnixShutdownDelay' reaches a value less than or equal to this object's value, an lcUpsUnixShutdownWarningTrap will be produced and this object will be reset to 0.rw
INTEGER
.1.3.6.1.4.1.476.1.1.1.1.8.6
lcUpsControlCancelCommandsSetting this variable to 'cancel' will cause the agent to issue instructions to the UPS to cancel all outstanding commands, such as lcUpsControlOutputOff, lcUpsControlOutputOn, lcUpsControlUnixShutdown.rw
Enumeration
.1.3.6.1.4.1.476.1.1.1.1.8.7
lcUpsControlRebootAgentDelaySetting this object causes the agent to reboot after the indicated number of seconds have expired. The value will count down until the event takes place.rw
INTEGER
.1.3.6.1.4.1.476.1.1.1.1.8.8
lcUpsNominal
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.1.9
lcUpsNominalOutputVoltageThe nominal output voltage. (Unit of measure: volt)rw
INTEGER
.1.3.6.1.4.1.476.1.1.1.1.9.1
lcUpsNominalInputVoltageThe nominal input voltage. (Unit of measure: volt)rw
INTEGER
.1.3.6.1.4.1.476.1.1.1.1.9.2
lcUpsNominalOutputVAThe nominal Volt-Amp rating.rw
INTEGER
.1.3.6.1.4.1.476.1.1.1.1.9.3
lcUpsNominalOutputWattsThe nominal power rating. (Unit of measure: watt)rw
INTEGER
.1.3.6.1.4.1.476.1.1.1.1.9.4
lcUpsNominalOutputFreqThe nominal output frequency. (Unit of measure: Hertz)rw
INTEGER
.1.3.6.1.4.1.476.1.1.1.1.9.5
lcUpsNominalInputFreqThe nominal input frequency. (Unit of measure: Hertz)rw
INTEGER
.1.3.6.1.4.1.476.1.1.1.1.9.6
lcUpsNominalOutputVaRatingThe nominal Volt-Amp rating.rw
INTEGER
.1.3.6.1.4.1.476.1.1.1.1.9.7
lcUpsNominalOutputWattsRatingThe nominal power rating. (Unit of measure: watt)rw
INTEGER
.1.3.6.1.4.1.476.1.1.1.1.9.8
lcUpsTraps
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.1.11
lcUpsOverloadWarningTrapAn lcUpsOverloadWarningTrap signifies that the UPS has detected an Overload condition where the output load has exceeded the UPS's rated capacity.
TRAP-TYPE
.1.3.6.1.4.1.476.1.1.1.1.11.0.1
lcUpsOverloadShutdownTrapAn lcUpsOverloadShutdownTrap signifies that the UPS has detected an Overload condition where the output load has exceeded the UPS's rated capacity and has shut off the output.
TRAP-TYPE
.1.3.6.1.4.1.476.1.1.1.1.11.0.2
lcUpsOnBatteryTrapAn lcUpsOnBatteryTrap signifies that the UPS is currently on Battery Power.
TRAP-TYPE
.1.3.6.1.4.1.476.1.1.1.1.11.0.3
lcUpsLowBatteryWarningTrapAn lcUpsLowBatteryWarningTrap signifies that the UPS has entered a Low Battery state.
TRAP-TYPE
.1.3.6.1.4.1.476.1.1.1.1.11.0.4
lcUpsLowBatteryShutdownTrapAn lcUpsLowBatteryShutdownTrap signifies that the UPS has shut off the output due to a Low Battery state.
TRAP-TYPE
.1.3.6.1.4.1.476.1.1.1.1.11.0.5
lcUpsUtilPowerFailedTrapAn lcUpsUtilPowerFailedTrap signifies that the utility power input to the UPS has been lost.
TRAP-TYPE
.1.3.6.1.4.1.476.1.1.1.1.11.0.6
lcUpsUtilPowerRestoredTrapAn lcUpsUtilPowerRestoredTrap signifies that the utility power has been restored to the UPS.
TRAP-TYPE
.1.3.6.1.4.1.476.1.1.1.1.11.0.7
lcUpsInputOverVoltageTrapAn lcUpsInputOverVoltageTrap signifies that the UPS has detected a high input voltage condition.
TRAP-TYPE
.1.3.6.1.4.1.476.1.1.1.1.11.0.8
lcUpsOverTempWarningTrapAn lcUpsOverTempWarningTrap signifies that the UPS has detected a excessive temperature condition.
TRAP-TYPE
.1.3.6.1.4.1.476.1.1.1.1.11.0.9
lcUpsOverTempShutdownTrapAn lcUpsOverTempShutdownTrap signifies that the UPS has detected a excessive temperature condition and shut off the output.
TRAP-TYPE
.1.3.6.1.4.1.476.1.1.1.1.11.0.10
lcUpsAlarmTrapAn Alarm condition has occurred and is being reported in the lcUpsAlarmTable.
TRAP-TYPE
.1.3.6.1.4.1.476.1.1.1.1.11.0.11
lcUpsOutputOffTrapAn lcUpsOutputOffTrap is sent when the UPS turns all of its output off, either at the inverter or via a relay.
TRAP-TYPE
.1.3.6.1.4.1.476.1.1.1.1.11.0.12
lcUpsOutputOffWarningTrapAn lcUpsOutputOffWarningTrap is sent when the lcUpsControlOutputOffDelay reaches the value of lcUpsControlOutputOffTrapDelay.
TRAP-TYPE
.1.3.6.1.4.1.476.1.1.1.1.11.0.13
lcUpsOutputOnTrapAn lcUpsOutputOnTrap is sent when the UPS turns all of its output back on, either at the inverter or via a relay.
TRAP-TYPE
.1.3.6.1.4.1.476.1.1.1.1.11.0.14
lcUpsOutputOnWarningTrapAn lcUpsOutputOnWarningTrap is sent when the lcUpsControlOutputOnDelay reaches the value of lcUpsControlOutputOnTrapDelay.
TRAP-TYPE
.1.3.6.1.4.1.476.1.1.1.1.11.0.15
lcUpsUnixShutdownTrapAn lcUpsUnixShutodwnTrap is sent 2 seconds before the UPS is scheduled to perform a Unix Shutdown.
TRAP-TYPE
.1.3.6.1.4.1.476.1.1.1.1.11.0.16
lcUpsUnixShutdownWarningTrapAn lcUpsUnixShutdownWarningTrap is sent when the lcUpsControlUnixShudownDelay reaches the value of lcUpsControlUnixShutdownTrapDelay.
TRAP-TYPE
.1.3.6.1.4.1.476.1.1.1.1.11.0.17
lcUpsReceptOffTrapAn lcUpsReceptOffTrap is sent when the UPS turns an output receptacle off.
TRAP-TYPE
.1.3.6.1.4.1.476.1.1.1.1.11.0.18
lcUpsReceptOffWarningTrapAn lcUpsReceptOffWarningTrap is sent when the lcUpsSwitchedReceptOffDelay reaches the value of lcUpsSwitchedReceptOffTrapDelay.
TRAP-TYPE
.1.3.6.1.4.1.476.1.1.1.1.11.0.19
lcUpsReceptOnTrapAn lcUpsReceptOnTrap is sent when the UPS turns an output receptacle on.
TRAP-TYPE
.1.3.6.1.4.1.476.1.1.1.1.11.0.20
lcUpsReceptOnWarningTrapAn lcUpsReceptOnWarningTrap is sent when the lcUpsSwitchedReceptOnDelay reaches the value of lcUpsSwitchedReceptOnTrapDelay.
TRAP-TYPE
.1.3.6.1.4.1.476.1.1.1.1.11.0.21
lcUpsInputFreqErrorTrapAn ldUpsInputFreqErrorTrap signifies that the UPS has detected that input frequency is outside tolerable variance.
TRAP-TYPE
.1.3.6.1.4.1.476.1.1.1.1.11.0.22
lcUpsDCOverVoltageShutdownTrapAn lcUpsDCOverVoltageShutdownTrap signifies that the UPS has detected that battery voltage is over the tolarable level.
TRAP-TYPE
.1.3.6.1.4.1.476.1.1.1.1.11.0.23
lcUpsOutputOverVoltageTrapAn lcUpsOutputOverVoltageTrap signifies that the UPS has detected that the output voltage is too high.
TRAP-TYPE
.1.3.6.1.4.1.476.1.1.1.1.11.0.24
lcUpsFuseBlownTrapAn lcUpsFuseBlownTrap is sent when the UPS's rectifier or DC capacitor fuse has failed.
TRAP-TYPE
.1.3.6.1.4.1.476.1.1.1.1.11.0.25
lcUpsEmergencyPowerOffTrapAn lcUpsEmergencyPowerOffTrap signifies that the UPS has shut off output due to an emergency condition.
TRAP-TYPE
.1.3.6.1.4.1.476.1.1.1.1.11.0.26
lcUpsControlPowerFailureTrapAn lcUpsControlPowerFailureTrap signifies a failure in the secondary control power.
TRAP-TYPE
.1.3.6.1.4.1.476.1.1.1.1.11.0.27
lcUpsReversePowerTrapAn lcUpsReversePowerTrap signifies that output has been shut off due to a reverse power flow condition.
TRAP-TYPE
.1.3.6.1.4.1.476.1.1.1.1.11.0.28
lcUpsPhaseRotationErrorTrapAn lcUpsPhaseRotationErrorTrap signifies a phase-rotation error in the bypass power.
TRAP-TYPE
.1.3.6.1.4.1.476.1.1.1.1.11.0.29
lcUpsLoadOnBypassTrapAn lcUpsLoadOnBypassTrap signifies that the load has been transferred to bypass power.
TRAP-TYPE
.1.3.6.1.4.1.476.1.1.1.1.11.0.30
lcUpsEmergencyXferToBypassTrapAn lcUpsEmergencyXferToBypassTrap signifies that the UPS has automatically tranferred the load to bypass power.
TRAP-TYPE
.1.3.6.1.4.1.476.1.1.1.1.11.0.31
lcUpsInverterFaultTrapAn lcUpsInverterFaultTrap signifies that the UPS detected a problem with the Inverter.
TRAP-TYPE
.1.3.6.1.4.1.476.1.1.1.1.11.0.34
lcUpsSwitchedReceptacles
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.1.12
lcUpsSwitchedReceptMaxNumThe maximum number of switched receptacles supported by the Ups.ro
INTEGER
.1.3.6.1.4.1.476.1.1.1.1.12.1
lcUpsSwitchedReceptTable
SEQUENCE OF LcUpsSwitchedReceptEntry
.1.3.6.1.4.1.476.1.1.1.1.12.2
lcUpsSwitchedReceptEntry
LcUpsSwitchedReceptEntry
.1.3.6.1.4.1.476.1.1.1.1.12.2.1
lcUpsSwitchedReceptIndexro
INTEGER
.1.3.6.1.4.1.476.1.1.1.1.12.2.1.1
lcUpsSwitchedReceptOnDelaySetting this object causes the agent to instruct the UPS to turn on a receptacle after the indicated number of seconds. The agent counts down the number of seconds until the event will take place. The agent issues an lcUpsReceptOnTrap when the countdown finishes. Note that different models have different clock resolutions, usually greater than 1 second. As a result, the command will only be accurate to the resolution of the UPS's clock. The command can be cancelled by setting lcUpsSwitchedCancelCommand to the value cancel.rw
INTEGER
.1.3.6.1.4.1.476.1.1.1.1.12.2.1.2
lcUpsSwitchedReceptOnTrapDelayWhen 'lcUpsSwitchedReceptOnDelay' reaches a value less than or equal to this object's value, an lcUpsReceptOnWarningTrap will be produced and this object will be reset to 0.rw
INTEGER
.1.3.6.1.4.1.476.1.1.1.1.12.2.1.3
lcUpsSwitchedReceptOffDelaySetting this object causes the agent to instruct the UPS to turn off a receptacle after the indicated number of seconds. The agent counts down the number of seconds until the event will take place. The agent issues an lcUpsReceptOffTrap when the countdown finishes. Note that different models have different clock resolutions, usually greater than 1 second. As a result, the command will only be accurate to the resolution of the UPS's clock. The command can be cancelled by setting lcUpsSwitchedCancelCommand to the value cancel.rw
INTEGER
.1.3.6.1.4.1.476.1.1.1.1.12.2.1.4
lcUpsSwitchedReceptOffTrapDelayWhen 'lcUpsSwitchedReceptOffDelay' reaches a value less than or equal to this object's value, an lcUpsReceptOffWarningTrap will be produced and this object will be reset to 0.rw
INTEGER
.1.3.6.1.4.1.476.1.1.1.1.12.2.1.5
lcUpsSwitchedReceptStatusThe status of the device receptacle. Note that some devices may support Switched of device receptacles as a group only (by using lcUpsSwitchedOutputOffDelay and lcUpsSwitchedOutputOnDelay).ro
Enumeration
.1.3.6.1.4.1.476.1.1.1.1.12.2.1.6
lcUpsSwitchedReceptLabelA user-defined text string associated with a switched receptacle. This may be used to describe the load powered from the receptacle. The text string is stored in non-volatile memory.rw
DisplayString
.1.3.6.1.4.1.476.1.1.1.1.12.2.1.7
lcUpsBypass
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.1.13
lcUpsOnBypassIndicates that the UPS is currently on bypass.ro
Enumeration
.1.3.6.1.4.1.476.1.1.1.1.13.1
lcUpsBypassFrequencyThe current bypass frequency. (Unit of measure: Hertz)ro
INTEGER
.1.3.6.1.4.1.476.1.1.1.1.13.2
lcUpsBypassNumLinesThe number of bypass lines utilized in this device. This entry indicates the number of rows in the bypass table.ro
INTEGER
.1.3.6.1.4.1.476.1.1.1.1.13.3
lcUpsBypassTable
SEQUENCE OF LcUpsBypassEntry
.1.3.6.1.4.1.476.1.1.1.1.13.4
lcUpsBypassEntry
LcUpsBypassEntry
.1.3.6.1.4.1.476.1.1.1.1.13.4.1
lcUpsBypassLineThe bypass Line.ro
INTEGER
.1.3.6.1.4.1.476.1.1.1.1.13.4.1.1
lcUpsBypassVoltageThe bypass voltage. (Unit of measure: Volt)ro
INTEGER
.1.3.6.1.4.1.476.1.1.1.1.13.4.1.2
lcUpsBypassCurrentThe bypass current. (Unit of measure: Amp)ro
INTEGER
.1.3.6.1.4.1.476.1.1.1.1.13.4.1.3
lcUpsConfig
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.1.14
lcUpsConfigTypeIndicates the UPS topology.ro
Enumeration
.1.3.6.1.4.1.476.1.1.1.1.14.1
lcUpsConfigBypassInstalledIndicates if a bypass is installed in the UPS.ro
Enumeration
.1.3.6.1.4.1.476.1.1.1.1.14.2
lcUpsConfigModuleCountA number identifying how many multi-module UPS are connected to the System Control Cabinet.ro
INTEGER
.1.3.6.1.4.1.476.1.1.1.1.14.3
lcUpsConfigCurrentModuleA number identifying which module of a multi-module UPS is currently being monitored.rw
INTEGER
.1.3.6.1.4.1.476.1.1.1.1.14.4
lcUpsConfigAudibleStatusThe requested state of the audible alarm. When in the disabled state, the audible alarm should never sound. The enabled state is self-describing. Setting this object to muted(3) when the audible alarm is sounding shall temporarily silence the alarm.rw
Enumeration
.1.3.6.1.4.1.476.1.1.1.1.14.5
lcUpsConfigLowBattTimeThe value of lcUpsBatTimeRemaining at which a lowBatteryWarning condition is declared. (Unit of measure: Minute)rw
INTEGER
.1.3.6.1.4.1.476.1.1.1.1.14.6
lcUpsConfigAutoRestartSetting this object will start the output after the indicated number of ticks (1 tick = 10 seconds), including starting the UPS, if necessary. Setting this object to 0 will cause the startup to occur immediately. Setting this object to -1 will disable autorestart.rw
INTEGER (-1..32767)
.1.3.6.1.4.1.476.1.1.1.1.14.7
luUPStationS
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.2
lsUpsIdent
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.2.1
lsUpsIdentFirmwareVersionThe firmware revision level of the UPS.ro
DisplayString
.1.3.6.1.4.1.476.1.1.1.2.1.1
lsUpsAlarm
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.2.6
lsUpsAlarmConditions
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.2.6.1
lsUpsAlarmCheckAirFilter
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.2.6.1.1
lsUpsTraps
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.2.11
lsUpsCheckAirFilterTrapAn lsUpsCheckAirFilterTrap signifies that the programmed time interval for checking the air filter has passed and it is time to check the air filter.
TRAP-TYPE
.1.3.6.1.4.1.476.1.1.1.2.11.0.1
lsUpsConfig
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.2.12
lsUpsConfigBypassInstalledIndicates if a bypass is installed in the UPS.ro
Enumeration
.1.3.6.1.4.1.476.1.1.1.2.12.1
lsUpsBypass
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.2.13
lsUpsOnBypassIndicates that the UPS is currently on bypass.ro
Enumeration
.1.3.6.1.4.1.476.1.1.1.2.13.1
lsUpsBypassFrequencyThe current bypass frequency. (Unit of measure: Hertz)ro
INTEGER
.1.3.6.1.4.1.476.1.1.1.2.13.2
lsUpsBypassNumLinesThe number of bypass lines utilized in this device. This entry indicates the number of rows in the bypass table.ro
INTEGER
.1.3.6.1.4.1.476.1.1.1.2.13.3
lsUpsBypassTable
SEQUENCE OF LsUpsBypassEntry
.1.3.6.1.4.1.476.1.1.1.2.13.4
lsUpsBypassEntry
LsUpsBypassEntry
.1.3.6.1.4.1.476.1.1.1.2.13.4.1
lsUpsBypassLineThe bypass Line.ro
INTEGER
.1.3.6.1.4.1.476.1.1.1.2.13.4.1.1
lsUpsBypassVoltageThe bypass voltage. (Unit of measure: Volt)ro
INTEGER
.1.3.6.1.4.1.476.1.1.1.2.13.4.1.2
lsUpsBypassCurrentThe bypass current. (Unit of measure: Amp)ro
INTEGER
.1.3.6.1.4.1.476.1.1.1.2.13.4.1.3
luUPStationD
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.3
ldUpsInput
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.3.3
ldUpsInputMaxVoltsSinceLastPollThe maximum input voltage encountered since the object was last retrieved. Note: if there are multiple managers talking to the same agent, the use of this object needs to be coordinated.ro
INTEGER
.1.3.6.1.4.1.476.1.1.1.3.3.1
ldUpsInputMinVoltsSinceLastPollThe minimum input voltage encountered since the object was last retrieved. Note: if there are multiple managers talking to the same agent, the use of this object needs to be coordinated.ro
INTEGER
.1.3.6.1.4.1.476.1.1.1.3.3.2
ldUpsOutput
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.3.4
ldUpsOutputMaxVoltsSinceLastPollThe maximum output voltage encountered since the object was last retrieved. Note: if there are multiple managers talking to the same agent, the use of this object needs to be coordinated.ro
INTEGER
.1.3.6.1.4.1.476.1.1.1.3.4.1
ldUpsOutputMinVoltsSinceLastPollThe minimum output voltage encountered since the object was last retrieved. Note: if there are multiple managers talking to the same agent, the use of this object needs to be coordinated.ro
INTEGER
.1.3.6.1.4.1.476.1.1.1.3.4.2
ldUpsAlarm
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.3.6
ldUpsAlarmConditions
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.3.6.1
ldUpsAlarmDCOverVoltageShutdown
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.3.6.1.1
ldUpsAlarmOutputShortShutdown
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.3.6.1.2
ldUpsAlarmLNReversedShutdown
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.3.6.1.3
ldUpsAlarmImminentShutdown
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.3.6.1.4
ldUpsAlarmInputFreqError
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.3.6.1.5
ldUpsAlarmBoostOn
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.3.6.1.6
ldUpsAlarmReplaceBattery
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.3.6.1.7
ldUpsAlarmOutputOverVoltage
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.3.6.1.8
ldUpsAlarmOutputUnderVoltage
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.3.6.1.9
ldUpsAlarmChargerFailed
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.3.6.1.10
ldUpsTraps
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.3.11
ldUpsDCOverVoltageShutdownTrapAn ldUpsDCOverVoltageShutdownTrap signifies that the UPS has detected that battery voltage is over the tolarable level.
TRAP-TYPE
.1.3.6.1.4.1.476.1.1.1.3.11.0.1
ldUpsOutputShortShutdownTrapAn ldUpsOutputShortShutdownTrap signifies that the UPS has detected a short circuit across the output.
TRAP-TYPE
.1.3.6.1.4.1.476.1.1.1.3.11.0.2
ldUpsLNReversedShutdownTrapAn ldUpsLNReversedShutdownTrap signifies that the UPS has detected that Line and Neutral have been reversed.
TRAP-TYPE
.1.3.6.1.4.1.476.1.1.1.3.11.0.3
ldUpsImminentShutdownTrapAn ldUpsImminentShutdownTrap signifies that the UPS is about to turn off output power.
TRAP-TYPE
.1.3.6.1.4.1.476.1.1.1.3.11.0.4
ldUpsInputFreqErrorTrapAn ldUpsInputFreqErrorTrap signifies that the UPS has detected that input frequency is outside tolerable variance.
TRAP-TYPE
.1.3.6.1.4.1.476.1.1.1.3.11.0.5
ldUpsOutputOverVoltageTrapAn ldUpsOutputOverVoltageTrap signifies that the UPS has detected that the output voltage is too high.
TRAP-TYPE
.1.3.6.1.4.1.476.1.1.1.3.11.0.6
ldUpsOutputUnderVoltageTrapAn ldUpsOutputUnderVoltageTrap signifies that the UPS has detected that the output voltage is too low.
TRAP-TYPE
.1.3.6.1.4.1.476.1.1.1.3.11.0.7
ldUpsChargerFailedTrapAn ldUpsChargerFailedTrap signifies that the UPS has detected that the battery charger has failed.
TRAP-TYPE
.1.3.6.1.4.1.476.1.1.1.3.11.0.8
luUPStationG
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.4
lgUpsAlarm
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.4.6
lgUpsAlarmConditions
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.4.6.1
lgUpsAlarmDCOverVoltageShutdown
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.4.6.1.1
lgUpsAlarmOutputShortShutdown
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.4.6.1.2
lgUpsAlarmLNReversedShutdown
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.4.6.1.3
lgUpsAlarmRemoteShutdown
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.4.6.1.4
lgUpsAlarmInputUVOnStartup
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.4.6.1.5
lgUpsAlarmPFCFailedOnStartup
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.4.6.1.6
lgUpsTraps
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.4.11
lgUpsDCOverVoltageShutdownTrapAn lgUpsDCOverVoltageShutdownTrap signifies that the UPS has detected that battery voltage is over the nominal level.
TRAP-TYPE
.1.3.6.1.4.1.476.1.1.1.4.11.0.1
lgUpsOutputShortShutdownTrapAn lgUpsOutputShortShutdownTrap signifies that the UPS has detected a short circuit across the output.
TRAP-TYPE
.1.3.6.1.4.1.476.1.1.1.4.11.0.2
lgUpsLNReversedShutdownTrapAn lgUpsLNReversedShutdownTrap signifies that the UPS has detected that Line and Neutral have been reversed.
TRAP-TYPE
.1.3.6.1.4.1.476.1.1.1.4.11.0.3
lgUpsInputUVOnStartupTrapAn lgUpsInputUVOnStartupTrap signifies that the UPS detected a low voltage condition upon system startup.
TRAP-TYPE
.1.3.6.1.4.1.476.1.1.1.4.11.0.4
luSeries300
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.5
luExternal
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.6
luUPStationS3
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.7
luSeries200
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.8
luSeries200Input
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.8.3
luSeries200InputMaxVoltsSinceLastPollThe maximum input voltage encountered since the object was last retrieved. Note: if there are multiple managers talking to the same agent, the use of this object needs to be coordinated.ro
INTEGER
.1.3.6.1.4.1.476.1.1.1.8.3.1
luSeries200InputMinVoltsSinceLastPollThe minimum input voltage encountered since the object was last retrieved. Note: if there are multiple managers talking to the same agent, the use of this object needs to be coordinated.ro
INTEGER
.1.3.6.1.4.1.476.1.1.1.8.3.2
luSeries200Alarm
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.8.6
luSeries200AlarmConditions
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.8.6.1
luSeries200AlarmInputFreqError
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.8.6.1.1
luSeries200Config
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.8.12
luSeries200ConfigBypassInstalledIndicates if a bypass is installed in the UPS.ro
Enumeration
.1.3.6.1.4.1.476.1.1.1.8.12.1
luSeries200ConfigFrequencyChangerModelIndicates whether this AP200 model is a frequency changer model.ro
Enumeration
.1.3.6.1.4.1.476.1.1.1.8.12.2
luSeries200Bypass
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.8.13
luSeries200OnBypassIndicates that the UPS is currently on bypass.ro
Enumeration
.1.3.6.1.4.1.476.1.1.1.8.13.1
luSeries4300
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.10
ls43cUpsIdent
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.10.1
ls43cUpsIdentFirmwareVersionThe firmware revision level of the UPS.ro
DisplayString
.1.3.6.1.4.1.476.1.1.1.10.1.1
ls43cUpsConfig
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.10.12
ls43cUpsConfigBypassInstalledIndicates if a bypass is installed in the UPS.ro
Enumeration
.1.3.6.1.4.1.476.1.1.1.10.12.1
ls43cUpsBypass
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.10.13
ls43cUpsOnBypassIndicates that the UPS is currently on bypass.ro
Enumeration
.1.3.6.1.4.1.476.1.1.1.10.13.1
ls43cUpsBypassFrequencyThe current bypass frequency. (Unit of measure: Hertz)ro
INTEGER
.1.3.6.1.4.1.476.1.1.1.10.13.2
ls43cUpsBypassNumLinesThe number of bypass lines utilized in this device. This entry indicates the number of rows in the bypass table.ro
INTEGER
.1.3.6.1.4.1.476.1.1.1.10.13.3
ls43cUpsBypassTable
SEQUENCE OF Ls43cUpsBypassEntry
.1.3.6.1.4.1.476.1.1.1.10.13.4
ls43cUpsBypassEntry
Ls43cUpsBypassEntry
.1.3.6.1.4.1.476.1.1.1.10.13.4.1
ls43cUpsBypassLineThe bypass Line.ro
INTEGER
.1.3.6.1.4.1.476.1.1.1.10.13.4.1.1
ls43cUpsBypassVoltageThe bypass voltage. (Unit of measure: Volt)ro
INTEGER
.1.3.6.1.4.1.476.1.1.1.10.13.4.1.2
ls43cUpsBypassCurrentThe bypass current. (Unit of measure: Amp)ro
INTEGER
.1.3.6.1.4.1.476.1.1.1.10.13.4.1.3
luUpsModule
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.11
luSystemCabinet
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.12
luUPStationGxt
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.14
luPowerSure
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.15
luExperimental
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.2
luPrivate
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.3