LIEBERT-SITENET-INTEGRATOR-MIB
AI MIB Summary
Standard SNMP MIB module defining data structures for LIEBERT-SITENET-INTEGRATOR-MIB.
157
Objects
Active
Status
5
Dependencies
Imported Objects
Objects
157 total| Object Name |
|---|
emerson OBJECT IDENTIFIER .1.3.6.1.4.1.476 |
RFC1213-MIB Unknown .1.3.6.1.4.1.476 |
liebertCorp OBJECT IDENTIFIER .1.3.6.1.4.1.476.1 |
liebertUps OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.1 |
liebertEnvironment OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.2 |
leExtensions OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.2.1 |
leSiteNet01 OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.2.1.1 |
envMIB OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.2.1.1.1 |
envIdent OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.2.1.1.1.1 |
envIdentManufacturerThe Environmental Control Unit manufacturer.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.476.1.2.1.1.1.1.1 |
envIdentModelThe Environmental Control Unit Model designation.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.476.1.2.1.1.1.1.2 |
envIdentSoftwareVersionThe Environmental SNMP Agent software version.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.476.1.2.1.1.1.1.3 |
envIdentSpecificA reference to MIB definitions specific to the
particular Environmental Unit being managed. This
object is used to locate the product-specific MIB
for this device.
If this information is not present, its value
should be the OBJECT IDENTIFIER { 0 0 },
which is a syntactically valid object identifier,
and any conformant implementation of ASN.1 and BER
must be able to generate and recognize this
value.ro OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.2.1.1.1.1.4 |
envDigitalInputs OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.2.1.1.1.2 |
envDigInput1 OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.2.1.1.1.2.1 |
envDigInput1StateThe state of Digital Input Number 1.
When the envDigInput1Polarity is set to notDefined(3)
this variable returns notInstalled(3). When the
envDigInput1Polarity is set to activeHigh(1) and the
input on Digital Input Number 1 is asserted, this
variable returns true(1). When the envDigInput1Polarity
is set to activeLow(2) and the input on Digital Input 1
is deasserted, this variable returns true(1). In all
other cases, this variable returns false(2).ro Enumeration .1.3.6.1.4.1.476.1.2.1.1.1.2.1.1 |
envDigInput1LabelA user-defined text string associated with
Digital Input Number 1. The text string is stored
in non-volatile memory.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.476.1.2.1.1.1.2.1.2 |
envDigInput1PolarityThe Polarity to be associated with the State variable for
Digital Input Number 1. It controls the value returned by
the State variable.
When Polarity is set to notDefined(3), State will return
notInstalled(3). When Polarity is set to activeHigh(1),
State will return false(2) if Digital Input Number 1 is
being deasserted and return true(1) if Digital Input
Number 1 is being asserted. When Polarity is set to
activeLow(2), State will return false(2) if Digital Input
Number 1 is being asserted and return true(1) if Digital
Input Number 1 is being deasserted. Polarity is stored
in non-volatile memory.rw Enumeration .1.3.6.1.4.1.476.1.2.1.1.1.2.1.3 |
envDigInput1TrapEnabledA TRAP may be associated with the State variable for
Digital Input Number 1.
When envDigInput1TrapEnabled is set to true(1), a TRAP
message will be generated when State is true(1). When
envDigInput1TrapEnabled is set to false(2), a TRAP message
will not be generated regardless of the value of State.
TrapEnabled is stored in non-volatile memory.rw TruthValue (SNMPv2-TC) .1.3.6.1.4.1.476.1.2.1.1.1.2.1.4 |
envDigInput2 OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.2.1.1.1.2.2 |
envDigInput2StateThe state of Digital Input Number 2.
When the envDigInput2Polarity is set to notDefined(3)
this variable returns notInstalled(3). When the
envDigInput2Polarity is set to activeHigh(1) and the
input on Digital Input Number 2 is asserted, this
variable returns true(1). When the envDigInput2Polarity
is set to activeLow(2) and the input on Digital Input 2
is deasserted, this variable returns true(1). In all
other cases, this variable returns false(2).ro Enumeration .1.3.6.1.4.1.476.1.2.1.1.1.2.2.1 |
envDigInput2LabelA user-defined text string associated with
Digital Input Number 2. The text string is stored
in non-volatile memory.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.476.1.2.1.1.1.2.2.2 |
envDigInput2PolarityThe Polarity to be associated with the State variable for
Digital Input Number 2. It controls the value returned by
the State variable.
When Polarity is set to notDefined(3), State will return
notInstalled(3). When Polarity is set to activeHigh(1),
State will return false(2) if Digital Input Number 2 is
being deasserted and return true(1) if Digital Input
Number 2 is being asserted. When Polarity is set to
activeLow(2), State will return false(2) if Digital Input
Number 2 is being asserted and return true(1) if Digital
Input Number 2 is being deasserted. Polarity is stored
in non-volatile memory.rw Enumeration .1.3.6.1.4.1.476.1.2.1.1.1.2.2.3 |
envDigInput2TrapEnabledA TRAP may be associated with the State variable for
Digital Input Number 2.
When envDigInput2TrapEnabled is set to true(1), a TRAP
message will be generated when State is true(1). When
envDigInput2TrapEnabled is set to false(2), a TRAP message
will not be generated regardless of the value of State.
TrapEnabled is stored in non-volatile memory.rw TruthValue (SNMPv2-TC) .1.3.6.1.4.1.476.1.2.1.1.1.2.2.4 |
envDigInput3 OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.2.1.1.1.2.3 |
envDigInput3StateThe state of Digital Input Number 3.
When the envDigInput3Polarity is set to notDefined(3)
this variable returns notInstalled(3). When the
envDigInput3Polarity is set to activeHigh(1) and the
input on Digital Input Number 3 is asserted, this
variable returns true(1). When the envDigInput3Polarity
is set to activeLow(2) and the input on Digital Input 3
is deasserted, this variable returns true(1). In all
other cases, this variable returns false(2).ro Enumeration .1.3.6.1.4.1.476.1.2.1.1.1.2.3.1 |
envDigInput3LabelA user-defined text string associated with
Digital Input Number 3. The text string is stored
in non-volatile memory.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.476.1.2.1.1.1.2.3.2 |
envDigInput3PolarityThe Polarity to be associated with the State variable for
Digital Input Number 3. It controls the value returned by
the State variable.
When Polarity is set to notDefined(3), State will return
notInstalled(3). When Polarity is set to activeHigh(1),
State will return false(2) if Digital Input Number 3 is
being deasserted and return true(1) if Digital Input
Number 3 is being asserted. When Polarity is set to
activeLow(2), State will return false(2) if Digital Input
Number 3 is being asserted and return true(1) if Digital
Input Number 3 is being deasserted. Polarity is stored
in non-volatile memory.rw Enumeration .1.3.6.1.4.1.476.1.2.1.1.1.2.3.3 |
envDigInput3TrapEnabledA TRAP may be associated with the State variable for
Digital Input Number 3.
When envDigInput3TrapEnabled is set to true(1), a TRAP
message will be generated when State is true(1). When
envDigInput3TrapEnabled is set to false(2), a TRAP message
will not be generated regardless of the value of State.
TrapEnabled is stored in non-volatile memory.rw TruthValue (SNMPv2-TC) .1.3.6.1.4.1.476.1.2.1.1.1.2.3.4 |
envDigInput4 OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.2.1.1.1.2.4 |
envDigInput4StateThe state of Digital Input Number 4.
When the envDigInput4Polarity is set to notDefined(3)
this variable returns notInstalled(3). When the
envDigInput4Polarity is set to activeHigh(1) and the
input on Digital Input Number 4 is asserted, this
variable returns true(1). When the envDigInput4Polarity
is set to activeLow(2) and the input on Digital Input 4
is deasserted, this variable returns true(1). In all
other cases, this variable returns false(2).ro Enumeration .1.3.6.1.4.1.476.1.2.1.1.1.2.4.1 |
envDigInput4LabelA user-defined text string associated with
Digital Input Number 4. The text string is stored
in non-volatile memory.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.476.1.2.1.1.1.2.4.2 |
envDigInput4PolarityThe Polarity to be associated with the State variable for
Digital Input Number 4. It controls the value returned by
the State variable.
When Polarity is set to notDefined(3), State will return
notInstalled(3). When Polarity is set to activeHigh(1),
State will return false(2) if Digital Input Number 4 is
being deasserted and return true(1) if Digital Input
Number 4 is being asserted. When Polarity is set to
activeLow(2), State will return false(2) if Digital Input
Number 4 is being asserted and return true(1) if Digital
Input Number 4 is being deasserted. Polarity is stored
in non-volatile memory.rw Enumeration .1.3.6.1.4.1.476.1.2.1.1.1.2.4.3 |
envDigInput4TrapEnabledA TRAP may be associated with the State variable for
Digital Input Number 4.
When envDigInput4TrapEnabled is set to true(1), a TRAP
message will be generated when State is true(1). When
envDigInput4TrapEnabled is set to false(2), a TRAP message
will not be generated regardless of the value of State.
TrapEnabled is stored in non-volatile memory.rw TruthValue (SNMPv2-TC) .1.3.6.1.4.1.476.1.2.1.1.1.2.4.4 |
envDigInput5 OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.2.1.1.1.2.5 |
envDigInput5StateThe state of Digital Input Number 5.
When the envDigInput5Polarity is set to notDefined(3)
this variable returns notInstalled(3). When the
envDigInput5Polarity is set to activeHigh(1) and the
input on Digital Input Number 5 is asserted, this
variable returns true(1). When the envDigInput5Polarity
is set to activeLow(2) and the input on Digital Input 5
is deasserted, this variable returns true(1). In all
other cases, this variable returns false(2).ro Enumeration .1.3.6.1.4.1.476.1.2.1.1.1.2.5.1 |
envDigInput5LabelA user-defined text string associated with
Digital Input Number 5. The text string is stored
in non-volatile memory.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.476.1.2.1.1.1.2.5.2 |
envDigInput5PolarityThe Polarity to be associated with the State variable for
Digital Input Number 5. It controls the value returned by
the State variable.
When Polarity is set to notDefined(3), State will return
notInstalled(3). When Polarity is set to activeHigh(1),
State will return false(2) if Digital Input Number 5 is
being deasserted and return true(1) if Digital Input
Number 5 is being asserted. When Polarity is set to
activeLow(2), State will return false(2) if Digital Input
Number 5 is being asserted and return true(1) if Digital
Input Number 5 is being deasserted. Polarity is stored
in non-volatile memory.rw Enumeration .1.3.6.1.4.1.476.1.2.1.1.1.2.5.3 |
envDigInput5TrapEnabledA TRAP may be associated with the State variable for
Digital Input Number 5.
When envDigInput5TrapEnabled is set to true(1), a TRAP
message will be generated when State is true(1). When
envDigInput5TrapEnabled is set to false(2), a TRAP message
will not be generated regardless of the value of State.
TrapEnabled is stored in non-volatile memory.rw TruthValue (SNMPv2-TC) .1.3.6.1.4.1.476.1.2.1.1.1.2.5.4 |
envDigInput6 OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.2.1.1.1.2.6 |
envDigInput6StateThe state of Digital Input Number 6.
When the envDigInput6Polarity is set to notDefined(3)
this variable returns notInstalled(3). When the
envDigInput6Polarity is set to activeHigh(1) and the
input on Digital Input Number 6 is asserted, this
variable returns true(1). When the envDigInput6Polarity
is set to activeLow(2) and the input on Digital Input 6
is deasserted, this variable returns true(1). In all
other cases, this variable returns false(2).ro Enumeration .1.3.6.1.4.1.476.1.2.1.1.1.2.6.1 |
envDigInput6LabelA user-defined text string associated with
Digital Input Number 6. The text string is stored
in non-volatile memory.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.476.1.2.1.1.1.2.6.2 |
envDigInput6PolarityThe Polarity to be associated with the State variable for
Digital Input Number 6. It controls the value returned by
the State variable.
When Polarity is set to notDefined(3), State will return
notInstalled(3). When Polarity is set to activeHigh(1),
State will return false(2) if Digital Input Number 6 is
being deasserted and return true(1) if Digital Input
Number 6 is being asserted. When Polarity is set to
activeLow(2), State will return false(2) if Digital Input
Number 6 is being asserted and return true(1) if Digital
Input Number 6 is being deasserted. Polarity is stored
in non-volatile memory.rw Enumeration .1.3.6.1.4.1.476.1.2.1.1.1.2.6.3 |
envDigInput6TrapEnabledA TRAP may be associated with the State variable for
Digital Input Number 6.
When envDigInput6TrapEnabled is set to true(1), a TRAP
message will be generated when State is true(1). When
envDigInput6TrapEnabled is set to false(2), a TRAP message
will not be generated regardless of the value of State.
TrapEnabled is stored in non-volatile memory.rw TruthValue (SNMPv2-TC) .1.3.6.1.4.1.476.1.2.1.1.1.2.6.4 |
envDigInput7 OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.2.1.1.1.2.7 |
envDigInput7StateThe state of Digital Input Number 7.
When the envDigInput7Polarity is set to notDefined(3)
this variable returns notInstalled(3). When the
envDigInput7Polarity is set to activeHigh(1) and the
input on Digital Input Number 7 is asserted, this
variable returns true(1). When the envDigInput7Polarity
is set to activeLow(2) and the input on Digital Input 7
is deasserted, this variable returns true(1). In all
other cases, this variable returns false(2).ro Enumeration .1.3.6.1.4.1.476.1.2.1.1.1.2.7.1 |
envDigInput7LabelA user-defined text string associated with
Digital Input Number 7. The text string is stored
in non-volatile memory.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.476.1.2.1.1.1.2.7.2 |
envDigInput7PolarityThe Polarity to be associated with the State variable for
Digital Input Number 7. It controls the value returned by
the State variable.
When Polarity is set to notDefined(3), State will return
notInstalled(3). When Polarity is set to activeHigh(1),
State will return false(2) if Digital Input Number 7 is
being deasserted and return true(1) if Digital Input
Number 7 is being asserted. When Polarity is set to
activeLow(2), State will return false(2) if Digital Input
Number 7 is being asserted and return true(1) if Digital
Input Number 7 is being deasserted. Polarity is stored
in non-volatile memory.rw Enumeration .1.3.6.1.4.1.476.1.2.1.1.1.2.7.3 |
envDigInput7TrapEnabledA TRAP may be associated with the State variable for
Digital Input Number 7.
When envDigInput7TrapEnabled is set to true(1), a TRAP
message will be generated when State is true(1). When
envDigInput7TrapEnabled is set to false(2), a TRAP message
will not be generated regardless of the value of State.
TrapEnabled is stored in non-volatile memory.rw TruthValue (SNMPv2-TC) .1.3.6.1.4.1.476.1.2.1.1.1.2.7.4 |
envDigInput8 OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.2.1.1.1.2.8 |
envDigInput8StateThe state of Digital Input Number 8.
When the envDigInput8Polarity is set to notDefined(3)
this variable returns notInstalled(3). When the
envDigInput8Polarity is set to activeHigh(1) and the
input on Digital Input Number 8 is asserted, this
variable returns true(1). When the envDigInput8Polarity
is set to activeLow(2) and the input on Digital Input 8
is deasserted, this variable returns true(1). In all
other cases, this variable returns false(2).ro Enumeration .1.3.6.1.4.1.476.1.2.1.1.1.2.8.1 |
envDigInput8LabelA user-defined text string associated with
Digital Input Number 8. The text string is stored
in non-volatile memory.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.476.1.2.1.1.1.2.8.2 |
envDigInput8PolarityThe Polarity to be associated with the State variable for
Digital Input Number 8. It controls the value returned by
the State variable.
When Polarity is set to notDefined(3), State will return
notInstalled(3). When Polarity is set to activeHigh(1),
State will return false(2) if Digital Input Number 8 is
being deasserted and return true(1) if Digital Input
Number 8 is being asserted. When Polarity is set to
activeLow(2), State will return false(2) if Digital Input
Number 8 is being asserted and return true(1) if Digital
Input Number 8 is being deasserted. Polarity is stored
in non-volatile memory.rw Enumeration .1.3.6.1.4.1.476.1.2.1.1.1.2.8.3 |
envDigInput8TrapEnabledA TRAP may be associated with the State variable for
Digital Input Number 8.
When envDigInput8TrapEnabled is set to true(1), a TRAP
message will be generated when State is true(1). When
envDigInput8TrapEnabled is set to false(2), a TRAP message
will not be generated regardless of the value of State.
TrapEnabled is stored in non-volatile memory.rw TruthValue (SNMPv2-TC) .1.3.6.1.4.1.476.1.2.1.1.1.2.8.4 |
envDigInput9 OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.2.1.1.1.2.9 |
envDigInput9StateThe state of Digital Input Number 9.
When the envDigInput9Polarity is set to notDefined(3)
this variable returns notInstalled(3). When the
envDigInput9Polarity is set to activeHigh(1) and the
input on Digital Input Number 9 is asserted, this
variable returns true(1). When the envDigInput9Polarity
is set to activeLow(2) and the input on Digital Input 9
is deasserted, this variable returns true(1). In all
other cases, this variable returns false(2).ro Enumeration .1.3.6.1.4.1.476.1.2.1.1.1.2.9.1 |
envDigInput9LabelA user-defined text string associated with
Digital Input Number 9. The text string is stored
in non-volatile memory.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.476.1.2.1.1.1.2.9.2 |
envDigInput9PolarityThe Polarity to be associated with the State variable for
Digital Input Number 9. It controls the value returned by
the State variable.
When Polarity is set to notDefined(3), State will return
notInstalled(3). When Polarity is set to activeHigh(1),
State will return false(2) if Digital Input Number 9 is
being deasserted and return true(1) if Digital Input
Number 9 is being asserted. When Polarity is set to
activeLow(2), State will return false(2) if Digital Input
Number 9 is being asserted and return true(1) if Digital
Input Number 9 is being deasserted. Polarity is stored
in non-volatile memory.rw Enumeration .1.3.6.1.4.1.476.1.2.1.1.1.2.9.3 |
envDigInput9TrapEnabledA TRAP may be associated with the State variable for
Digital Input Number 9.
When envDigInput9TrapEnabled is set to true(1), a TRAP
message will be generated when State is true(1). When
envDigInput9TrapEnabled is set to false(2), a TRAP message
will not be generated regardless of the value of State.
TrapEnabled is stored in non-volatile memory.rw TruthValue (SNMPv2-TC) .1.3.6.1.4.1.476.1.2.1.1.1.2.9.4 |
envDigInput10 OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.2.1.1.1.2.10 |
envDigInput10StateThe state of Digital Input Number 10.
When the envDigInput10Polarity is set to notDefined(3)
this variable returns notInstalled(3). When the
envDigInput10Polarity is set to activeHigh(1) and the
input on Digital Input Number 10 is asserted, this
variable returns true(1). When the envDigInput10Polarity
is set to activeLow(2) and the input on Digital Input 10
is deasserted, this variable returns true(1). In all
other cases, this variable returns false(2).ro Enumeration .1.3.6.1.4.1.476.1.2.1.1.1.2.10.1 |
envDigInput10LabelA user-defined text string associated with
Digital Input Number 10. The text string is stored
in non-volatile memory.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.476.1.2.1.1.1.2.10.2 |
envDigInput10PolarityThe Polarity to be associated with the State variable for
Digital Input Number 10. It controls the value returned by
the State variable.
When Polarity is set to notDefined(3), State will return
notInstalled(3). When Polarity is set to activeHigh(1),
State will return false(2) if Digital Input Number 10 is
being deasserted and return true(1) if Digital Input
Number 10 is being asserted. When Polarity is set to
activeLow(2), State will return false(2) if Digital Input
Number 10 is being asserted and return true(1) if Digital
Input Number 10 is being deasserted. Polarity is stored
in non-volatile memory.rw Enumeration .1.3.6.1.4.1.476.1.2.1.1.1.2.10.3 |
envDigInput10TrapEnabledA TRAP may be associated with the State variable for
Digital Input Number 10.
When envDigInput10TrapEnabled is set to true(1), a TRAP
message will be generated when State is true(1). When
envDigInput10TrapEnabled is set to false(2), a TRAP message
will not be generated regardless of the value of State.
TrapEnabled is stored in non-volatile memory.rw TruthValue (SNMPv2-TC) .1.3.6.1.4.1.476.1.2.1.1.1.2.10.4 |
envRelays OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.2.1.1.1.3 |
envRelay1 OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.2.1.1.1.3.1 |
envRelay1StateThe state of Output Relay Number 1.
When State is set to on(1) Output Relay Number 1 is
activated and the normally open contacts are closed.
When State is set to off(2) Output Relay Number 1 is
deactivated and the normally closed contacts are closed.rw Enumeration .1.3.6.1.4.1.476.1.2.1.1.1.3.1.1 |
envRelay1LabelA user-defined text string associated with
Output Relay Number 1. The text string is stored
in non-volatile memory.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.476.1.2.1.1.1.3.1.2 |
envRelay1ControlIf Control value is 0 then this output may be directly
controlled by the SNMP Manager. When Control contains any
of the following values, or a value resulting from the sum
of any of these values the Agent will activate the output
when the any of the associated conditions is sensed and
de-activate the output when all conditions clear.
DigitalInput1State true(1) 1
DigitalInput2State true(1) 2
DigitalInput3State true(1) 4
DigitalInput4State true(1) 8
DigitalInput5State true(1) 16
DigitalInput6State true(1) 32
DigitalInput7State true(1) 64
DigitalInput8State true(1) 128
DigitalInput9State true(1) 256
DigitalInput10State true(1) 512
Temperature1 above HighLimit 1024
Temperature1 below LowLimit 2048
Temperature2 above HighLimit 4096
Temperature2 below LowLimit 8192
Temperature3 above HighLimit 16384
Temperature3 below LowLimit 32768
Humidity1 above HighLimit 65536
Humidity1 below LowLimit 131072
Humidity2 above HighLimit 262144
Humidity2 below LowLimit 524288
The Control variable is stored in non-volatile memory.rw INTEGER (-2147483648..2147483647) .1.3.6.1.4.1.476.1.2.1.1.1.3.1.3 |
envRelay2 OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.2.1.1.1.3.2 |
envRelay2StateThe state of Output Relay Number 2.
When State is set to on(1) Output Relay Number 2 is
activated and the normally open contacts are closed.
When State is set to off(2) Output Relay Number 2 is
deactivated and the normally closed contacts are closed.rw Enumeration .1.3.6.1.4.1.476.1.2.1.1.1.3.2.1 |
envRelay2LabelA user-defined text string associated with
Output Relay Number 2. The text string is stored
in non-volatile memory.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.476.1.2.1.1.1.3.2.2 |
envRelay2ControlIf Control value is 0 then this output may be directly
controlled by the SNMP Manager. When Control contains any
of the following values, or a value resulting from the sum
of any of these values the Agent will activate the output
when the any of the associated conditions is sensed and
de-activate the output when all conditions clear.
DigitalInput1State true(1) 1
DigitalInput2State true(1) 2
DigitalInput3State true(1) 4
DigitalInput4State true(1) 8
DigitalInput5State true(1) 16
DigitalInput6State true(1) 32
DigitalInput7State true(1) 64
DigitalInput8State true(1) 128
DigitalInput9State true(1) 256
DigitalInput10State true(1) 512
Temperature1 above HighLimit 1024
Temperature1 below LowLimit 2048
Temperature2 above HighLimit 4096
Temperature2 below LowLimit 8192
Temperature3 above HighLimit 16384
Temperature3 below LowLimit 32768
Humidity1 above HighLimit 65536
Humidity1 below LowLimit 131072
Humidity2 above HighLimit 262144
Humidity2 below LowLimit 524288
The Control variable is stored in non-volatile memory.rw INTEGER (-2147483648..2147483647) .1.3.6.1.4.1.476.1.2.1.1.1.3.2.3 |
envOutputs OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.2.1.1.1.4 |
envAudible OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.2.1.1.1.4.1 |
envAudibleStateThe state of the Audible Output.
When State is set to on(1) the Audible will be sounded.
When State is set to off(2) the Audible is muted.rw Enumeration .1.3.6.1.4.1.476.1.2.1.1.1.4.1.1 |
envAudibleControlIf Control value is 0 then this output may be directly
controlled by the SNMP Manager. When Control contains any
of the following values, or a value resulting from the sum
of any of these values the Agent will activate the output
when the any of the associated conditions is sensed and
de-activate the output when all conditions clear.
DigitalInput1State true(1) 1
DigitalInput2State true(1) 2
DigitalInput3State true(1) 4
DigitalInput4State true(1) 8
DigitalInput5State true(1) 16
DigitalInput6State true(1) 32
DigitalInput7State true(1) 64
DigitalInput8State true(1) 128
DigitalInput9State true(1) 256
DigitalInput10State true(1) 512
Temperature1 above HighLimit 1024
Temperature1 below LowLimit 2048
Temperature2 above HighLimit 4096
Temperature2 below LowLimit 8192
Temperature3 above HighLimit 16384
Temperature3 below LowLimit 32768
Humidity1 above HighLimit 65536
Humidity1 below LowLimit 131072
Humidity2 above HighLimit 262144
Humidity2 below LowLimit 524288
The Control variable is stored in non-volatile memory.rw INTEGER (-2147483648..2147483647) .1.3.6.1.4.1.476.1.2.1.1.1.4.1.2 |
envLED1 OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.2.1.1.1.4.2 |
envLED1StateThe state of Output LED Number 1.
When State is set to on(1) LED Number 1 will be lighted.
When State is set to off(2) LED Number 1 will not be
lighted.rw Enumeration .1.3.6.1.4.1.476.1.2.1.1.1.4.2.1 |
envLED1LabelA user-defined text string associated with
Output LED Number 1. The text string is stored
in non-volatile memory.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.476.1.2.1.1.1.4.2.2 |
envLED1ControlIf Control value is 0 then this output may be directly
controlled by the SNMP Manager. When Control contains any
of the following values, or a value resulting from the sum
of any of these values the Agent will activate the output
when the any of the associated conditions is sensed and
de-activate the output when all conditions clear.
DigitalInput1State true(1) 1
DigitalInput2State true(1) 2
DigitalInput3State true(1) 4
DigitalInput4State true(1) 8
DigitalInput5State true(1) 16
DigitalInput6State true(1) 32
DigitalInput7State true(1) 64
DigitalInput8State true(1) 128
DigitalInput9State true(1) 256
DigitalInput10State true(1) 512
Temperature1 above HighLimit 1024
Temperature1 below LowLimit 2048
Temperature2 above HighLimit 4096
Temperature2 below LowLimit 8192
Temperature3 above HighLimit 16384
Temperature3 below LowLimit 32768
Humidity1 above HighLimit 65536
Humidity1 below LowLimit 131072
Humidity2 above HighLimit 262144
Humidity2 below LowLimit 524288
The Control variable is stored in non-volatile memory.rw INTEGER (-2147483648..2147483647) .1.3.6.1.4.1.476.1.2.1.1.1.4.2.3 |
envLED2 OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.2.1.1.1.4.3 |
envLED2StateThe state of Output LED Number 2.
When State is set to on(1) LED Number 2 will be lighted.
When State is set to off(2) LED Number 2 will not be
lighted.rw Enumeration .1.3.6.1.4.1.476.1.2.1.1.1.4.3.1 |
envLED2LabelA user-defined text string associated with
Output LED Number 2. The text string is stored
in non-volatile memory.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.476.1.2.1.1.1.4.3.2 |
envLED2ControlIf Control value is 0 then this output may be directly
controlled by the SNMP Manager. When Control contains any
of the following values, or a value resulting from the sum
of any of these values the Agent will activate the output
when the any of the associated conditions is sensed and
de-activate the output when all conditions clear.
DigitalInput1State true(1) 1
DigitalInput2State true(1) 2
DigitalInput3State true(1) 4
DigitalInput4State true(1) 8
DigitalInput5State true(1) 16
DigitalInput6State true(1) 32
DigitalInput7State true(1) 64
DigitalInput8State true(1) 128
DigitalInput9State true(1) 256
DigitalInput10State true(1) 512
Temperature1 above HighLimit 1024
Temperature1 below LowLimit 2048
Temperature2 above HighLimit 4096
Temperature2 below LowLimit 8192
Temperature3 above HighLimit 16384
Temperature3 below LowLimit 32768
Humidity1 above HighLimit 65536
Humidity1 below LowLimit 131072
Humidity2 above HighLimit 262144
Humidity2 below LowLimit 524288
The Control variable is stored in non-volatile memory.rw INTEGER (-2147483648..2147483647) .1.3.6.1.4.1.476.1.2.1.1.1.4.3.3 |
envLED3 OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.2.1.1.1.4.4 |
envLED3StateThe state of Output LED Number 3.
When State is set to on(1) LED Number 3 will be lighted.
When State is set to off(2) LED Number 3 will not be
lighted.rw Enumeration .1.3.6.1.4.1.476.1.2.1.1.1.4.4.1 |
envLED3LabelA user-defined text string associated with
Output LED Number 3. The text string is stored
in non-volatile memory.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.476.1.2.1.1.1.4.4.2 |
envLED3ControlIf Control value is 0 then this output may be directly
controlled by the SNMP Manager. When Control contains any
of the following values, or a value resulting from the sum
of any of these values the Agent will activate the output
when the any of the associated conditions is sensed and
de-activate the output when all conditions clear.
DigitalInput1State true(1) 1
DigitalInput2State true(1) 2
DigitalInput3State true(1) 4
DigitalInput4State true(1) 8
DigitalInput5State true(1) 16
DigitalInput6State true(1) 32
DigitalInput7State true(1) 64
DigitalInput8State true(1) 128
DigitalInput9State true(1) 256
DigitalInput10State true(1) 512
Temperature1 above HighLimit 1024
Temperature1 below LowLimit 2048
Temperature2 above HighLimit 4096
Temperature2 below LowLimit 8192
Temperature3 above HighLimit 16384
Temperature3 below LowLimit 32768
Humidity1 above HighLimit 65536
Humidity1 below LowLimit 131072
Humidity2 above HighLimit 262144
Humidity2 below LowLimit 524288
The Control variable is stored in non-volatile memory.rw INTEGER (-2147483648..2147483647) .1.3.6.1.4.1.476.1.2.1.1.1.4.4.3 |
envReceptacles OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.2.1.1.1.5 |
envReceptacle1 OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.2.1.1.1.5.1 |
envReceptacle1StateThe state of the Receptacle Number 1.
When State is set to on(1) power will be live on
Receptacle Number 1. When State is set to off(2)
no power is available from Receptacle Number 1.rw Enumeration .1.3.6.1.4.1.476.1.2.1.1.1.5.1.1 |
envReceptacle1LabelA user-defined text string associated with
Receptacle Number 1. The text string is stored
in non-volatile memory.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.476.1.2.1.1.1.5.1.2 |
envReceptacle2 OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.2.1.1.1.5.2 |
envReceptacle2StateThe state of the Receptacle Number 2.
When State is set to on(1) power will be live on
Receptacle Number 2. When State is set to off(2)
no power is available from Receptacle Number 2.rw Enumeration .1.3.6.1.4.1.476.1.2.1.1.1.5.2.1 |
envReceptacle2LabelA user-defined text string associated with
Receptacle Number 2. The text string is stored
in non-volatile memory.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.476.1.2.1.1.1.5.2.2 |
envReceptacle3 OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.2.1.1.1.5.3 |
envReceptacle3StateThe state of the Receptacle Number 3.
When State is set to on(1) power will be live on
Receptacle Number 3. When State is set to off(2)
no power is available from Receptacle Number 3.rw Enumeration .1.3.6.1.4.1.476.1.2.1.1.1.5.3.1 |
envReceptacle3LabelA user-defined text string associated with
Receptacle Number 3. The text string is stored
in non-volatile memory.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.476.1.2.1.1.1.5.3.2 |
envReceptacle4 OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.2.1.1.1.5.4 |
envReceptacle4StateThe state of the Receptacle Number 4.
When State is set to on(1) power will be live on
Receptacle Number 4. When State is set to off(2)
no power is available from Receptacle Number 4.rw Enumeration .1.3.6.1.4.1.476.1.2.1.1.1.5.4.1 |
envReceptacle4LabelA user-defined text string associated with
Receptacle Number 4. The text string is stored
in non-volatile memory.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.476.1.2.1.1.1.5.4.2 |
envAlarms OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.2.1.1.1.6 |
envSummaryAlarmThe envSummaryAlarm varible will be 0 when no
Digital Inputs are true and no other alarm conditions
exist.
When alarms are active or Digital Inputs are true the
value of envSummaryAlarm indicates which alarms and
inputs are active as a sum of the values listed below:
DigitalInput1State true(1) 1
DigitalInput2State true(1) 2
DigitalInput3State true(1) 4
DigitalInput4State true(1) 8
DigitalInput5State true(1) 16
DigitalInput6State true(1) 32
DigitalInput7State true(1) 64
DigitalInput8State true(1) 128
DigitalInput9State true(1) 256
DigitalInput10State true(1) 512
Temperature1 above HighLimit 1024
Temperature1 below LowLimit 2048
Temperature2 above HighLimit 4096
Temperature2 below LowLimit 8192
Temperature3 above HighLimit 16384
Temperature3 below LowLimit 32768
Humidity1 above HighLimit 65536
Humidity1 below LowLimit 131072
Humidity2 above HighLimit 262144
Humidity2 below LowLimit 524288ro INTEGER (-2147483648..2147483647) .1.3.6.1.4.1.476.1.2.1.1.1.6.1 |
envTemperatureSensors OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.2.1.1.1.7 |
envTemperature1 OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.2.1.1.1.7.1 |
envTemperature1StateThe state of use of Temperature Input Number 1.
When a sensor is connected to Temperature Input 1
set State to installed(2) to indicate that the value
of envTemperature1F and envTemperature1C are valid.
When no sensor is connected to Temperature Input 1 set
State to notInstalled(1) to indicate that the value of
envTemperature1F and envTemperature1C may not be valid.
This variable is stored in non-volatile memory.rw Enumeration .1.3.6.1.4.1.476.1.2.1.1.1.7.1.1 |
envTemperature1FThe temperature for sensor 1 in degrees
Fahrenheit.ro INTEGER (-2147483648..2147483647) .1.3.6.1.4.1.476.1.2.1.1.1.7.1.2 |
envTemperature1CThe temperature for sensor 1 in degrees
Centigrade.ro INTEGER (-2147483648..2147483647) .1.3.6.1.4.1.476.1.2.1.1.1.7.1.3 |
envTemperature1LabelA user-defined text string associated with
Temperature Input Number 1. The text string is
stored in non-volatile memory.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.476.1.2.1.1.1.7.1.4 |
envTemperature1OffsetFA temperature correction Offset associated with
the envTemperature1F variable.
The value of OffsetF is added to the value from
Temperature Sensor Number 1 to obtain the value of
the envTemperature1F variable. When this variable is
changed the envTemperature1OffsetC variable may also
be effected. The OffsetF variable is stored in
non-volatile memory.rw INTEGER (-2147483648..2147483647) .1.3.6.1.4.1.476.1.2.1.1.1.7.1.5 |
envTemperature1OffsetCA temperature correction Offset associated with
the envTemperature1C variable.
The value of OffsetC is added to the value from
Temperature Sensor Number 1 to obtain the value of
the envTemperature1C variable. When this variable is
changed the envTemperature1OffsetF variable may also
be effected. The OffsetC variable is stored in
in non-volatile memory.rw INTEGER (-2147483648..2147483647) .1.3.6.1.4.1.476.1.2.1.1.1.7.1.6 |
envTemp1HighLimitFWhen envTemperature1F reaches or exceeds this value
a trap will be generated signifying a high temperature
condition at temperature sensor 1. The HighLimitF
variable is stored in non-volatile memory.rw INTEGER (-2147483648..2147483647) .1.3.6.1.4.1.476.1.2.1.1.1.7.1.7 |
envTemp1HighLimitCWhen envTemperature1C reaches or exceeds this value
a trap will be generated signifying a high temperature
condition at temperature sensor 1. The HighLimitC
variable is stored in non-volatile memory.rw INTEGER (-2147483648..2147483647) .1.3.6.1.4.1.476.1.2.1.1.1.7.1.8 |
envTemp1LowLimitFWhen envTemperature1F reaches or goes below this value
a trap will be generated signifying a low temperature
condition at temperature sensor 1. The LowLimitF
variable is stored in non-volatile memory.rw INTEGER (-2147483648..2147483647) .1.3.6.1.4.1.476.1.2.1.1.1.7.1.9 |
envTemp1LowLimitCWhen envTemperature1C reaches or goes below this value
a trap will be generated signifying a low temperature
condition at temperature sensor 1. The LowLimitC
variable is stored in non-volatile memory.rw INTEGER (-2147483648..2147483647) .1.3.6.1.4.1.476.1.2.1.1.1.7.1.10 |
envTemperature2 OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.2.1.1.1.7.2 |
envTemperature2StateThe state of use of Temperature Input Number 2.
When a sensor is connected to Temperature Input 2
set State to installed(2) to indicate that the value
of envTemperature2F and envTemperature2C are valid.
When no sensor is connected to Temperature Input 2 set
State to notInstalled(1) to indicate that the value of
envTemperature2F and envTemperature2C may not be valid.
This variable is stored in non-volatile memory.rw Enumeration .1.3.6.1.4.1.476.1.2.1.1.1.7.2.1 |
envTemperature2FThe temperature for sensor 2 in degrees
Fahrenheit.ro INTEGER (-2147483648..2147483647) .1.3.6.1.4.1.476.1.2.1.1.1.7.2.2 |
envTemperature2CThe temperature for sensor 2 in degrees
Centigrade.ro INTEGER (-2147483648..2147483647) .1.3.6.1.4.1.476.1.2.1.1.1.7.2.3 |
envTemperature2LabelA user-defined text string associated with
Temperature Input Number 2. The text string is
stored in non-volatile memory.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.476.1.2.1.1.1.7.2.4 |
envTemperature2OffsetFA temperature correction Offset associated with
the envTemperature2F variable.
The value of OffsetF is added to the value from
Temperature Sensor Number 2 to obtain the value of
the envTemperature2F variable. When this variable is
changed the envTemperature2OffsetC variable may also
be effected. The OffsetF variable is stored in
non-volatile memory.rw INTEGER (-2147483648..2147483647) .1.3.6.1.4.1.476.1.2.1.1.1.7.2.5 |
envTemperature2OffsetCA temperature correction Offset associated with
the envTemperature2C variable.
The value of OffsetC is added to the value from
Temperature Sensor Number 2 to obtain the value of
the envTemperature2C variable. When this variable is
changed the envTemperature2OffsetF variable may also
be effected. The OffsetC variable is stored in
in non-volatile memory.rw INTEGER (-2147483648..2147483647) .1.3.6.1.4.1.476.1.2.1.1.1.7.2.6 |
envTemp2HighLimitFWhen envTemperature2F reaches or exceeds this value
a trap will be generated signifying a high temperature
condition at temperature sensor 2. The HighLimitF
variable is stored in non-volatile memory.rw INTEGER (-2147483648..2147483647) .1.3.6.1.4.1.476.1.2.1.1.1.7.2.7 |
envTemp2HighLimitCWhen envTemperature2C reaches or exceeds this value
a trap will be generated signifying a high temperature
condition at temperature sensor 2. The HighLimitC
variable is stored in non-volatile memory.rw INTEGER (-2147483648..2147483647) .1.3.6.1.4.1.476.1.2.1.1.1.7.2.8 |
envTemp2LowLimitFWhen envTemperature2F reaches or goes below this value
a trap will be generated signifying a low temperature
condition at temperature sensor 2. The LowLimitF
variable is stored in non-volatile memory.rw INTEGER (-2147483648..2147483647) .1.3.6.1.4.1.476.1.2.1.1.1.7.2.9 |
envTemp2LowLimitCWhen envTemperature2C reaches or goes below this value
a trap will be generated signifying a low temperature
condition at temperature sensor 2. The LowLimitC
variable is stored in non-volatile memory.rw INTEGER (-2147483648..2147483647) .1.3.6.1.4.1.476.1.2.1.1.1.7.2.10 |
envTemperature3 OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.2.1.1.1.7.3 |
envTemperature3StateThe state of use of Temperature Input Number 3.
When a water temperature sensor is connected to
Temperature Input 3 set State to waterSensorInstalled(3),
when and air temperature sensor is connected set State
to airSensorInstalled(2). When no sensor is connected
to Temperature Input 3 set State to notInstalled(1) to
indicate that the value of envTemperature3F and
envTemperature3C may not be valid.
This variable is stored in non-volatile memory.rw Enumeration .1.3.6.1.4.1.476.1.2.1.1.1.7.3.1 |
envTemperature3FThe temperature for sensor 3 in degrees
Fahrenheit.ro INTEGER (-2147483648..2147483647) .1.3.6.1.4.1.476.1.2.1.1.1.7.3.2 |
envTemperature3CThe temperature for sensor 3 in degrees
Centigrade.ro INTEGER (-2147483648..2147483647) .1.3.6.1.4.1.476.1.2.1.1.1.7.3.3 |
envTemperature3LabelA user-defined text string associated with
Temperature Input Number 3. The text string is
stored in non-volatile memory.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.476.1.2.1.1.1.7.3.4 |
envTemperature3OffsetFA temperature correction Offset associated with
the envTemperature3F variable.
The value of OffsetF is added to the value from
Temperature Sensor Number 3 to obtain the value of
the envTemperature3F variable. When this variable is
changed the envTemperature3OffsetF variable may also
be effected. The OffsetF variable is stored in
in non-volatile memory.rw INTEGER (-2147483648..2147483647) .1.3.6.1.4.1.476.1.2.1.1.1.7.3.5 |
envTemperature3OffsetCA temperature correction Offset associated with
the envTemperature3C variable.
The value of OffsetC is added to the value from
Temperature Sensor Number 3 to obtain the value of
the envTemperature3C variable. When this variable is
changed the envTemperature3OffsetF variable may also
be effected. The OffsetC variable is stored in
in non-volatile memory.rw INTEGER (-2147483648..2147483647) .1.3.6.1.4.1.476.1.2.1.1.1.7.3.6 |
envTemp3HighLimitFWhen envTemperature3F reaches or exceeds this value
a trap will be generated signifying a high temperature
condition at temperature sensor 3. The HighLimitF
variable is stored in non-volatile memory.rw INTEGER (-2147483648..2147483647) .1.3.6.1.4.1.476.1.2.1.1.1.7.3.7 |
envTemp3HighLimitCWhen envTemperature3C reaches or exceeds this value
a trap will be generated signifying a high temperature
condition at temperature sensor 3. The HighLimitC
variable is stored in non-volatile memory.rw INTEGER (-2147483648..2147483647) .1.3.6.1.4.1.476.1.2.1.1.1.7.3.8 |
envTemp3LowLimitFWhen envTemperature3F reaches or goes below this value
a trap will be generated signifying a low temperature
condition at temperature sensor 3. The LowLimitF
variable is stored in non-volatile memory.rw INTEGER (-2147483648..2147483647) .1.3.6.1.4.1.476.1.2.1.1.1.7.3.9 |
envTemp3LowLimitCWhen envTemperature3C reaches or goes below this value
a trap will be generated signifying a low temperature
condition at temperature sensor 3. The LowLimitC
variable is stored in non-volatile memory.rw INTEGER (-2147483648..2147483647) .1.3.6.1.4.1.476.1.2.1.1.1.7.3.10 |
envTemp3CalibrateA temperature Offset correction routine associated
with Temperature Sensor Number 3.
When Calibrate is set to on(1) and State is set to
waterSensorInstalled(3) the agent runs a self
calibration routine which automatically adjusts the
OffsetF and OffsetC variables.rw Enumeration .1.3.6.1.4.1.476.1.2.1.1.1.7.3.11 |
envHumiditySensors OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.2.1.1.1.8 |
envHumidity1 OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.2.1.1.1.8.1 |
envHumidity1StateThe state of use of Humidity Input Number 1.
When a sensor is connected to Humidity Input 1
set State to installed(2) to indicate that the
value of envHumidity1RH is valid. When no sensor
is connected to Humidity Input 1 set State to
notInstalled(1) to indicate that the value of
envHumidity1RH may not be valid.
This variable is stored in non-volatile memory.rw Enumeration .1.3.6.1.4.1.476.1.2.1.1.1.8.1.1 |
envHumidity1RHThe humidity for sensor 1 in percent RH.ro INTEGER (-2147483648..2147483647) .1.3.6.1.4.1.476.1.2.1.1.1.8.1.2 |
envHumidity1LabelA user-defined text string associated with
Humidity Input Number 1. The text string is
stored in non-volatile memory.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.476.1.2.1.1.1.8.1.3 |
envHumidity1OffsetA humidity correction Offset associated with
the envHumidity1RH variable.
The value of Offset is added to the value from
Humidity Sensor Number 1 to obtain the value of
the envHumidity1RH variable. The Offset variable
is stored in non-volatile memory.rw INTEGER (-2147483648..2147483647) .1.3.6.1.4.1.476.1.2.1.1.1.8.1.4 |
envHumidity1HighLimitWhen envHumidity1RH reaches or exceeds this value
a trap will be generated signifying a high humidity
condition at humidity sensor 1. The HighLimit
variable is stored in non-volatile memory.rw INTEGER (-2147483648..2147483647) .1.3.6.1.4.1.476.1.2.1.1.1.8.1.5 |
envHumidity1LowLimitWhen envHumidity1RH reaches or goes below this value
a trap will be generated signifying a low humidity
condition at humidity sensor 1. The LowLimit
variable is stored in non-volatile memory.rw INTEGER (-2147483648..2147483647) .1.3.6.1.4.1.476.1.2.1.1.1.8.1.6 |
envHumidity2 OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.2.1.1.1.8.2 |
envHumidity2StateThe state of use of Humidity Input Number 2.
When a sensor is connected to Humidity Input 2
set State to installed(2) to indicate that the
value of envHumidity2RH is valid. When no sensor
is connected to Humidity Input 2 set State to
notInstalled(1) to indicate that the value of
envHumidity2RH may not be valid.
This variable is stored in non-volatile memory.rw Enumeration .1.3.6.1.4.1.476.1.2.1.1.1.8.2.1 |
envHumidity2RHThe humidity for sensor 2 in percent RH.ro INTEGER (-2147483648..2147483647) .1.3.6.1.4.1.476.1.2.1.1.1.8.2.2 |
envHumidity2LabelA user-defined text string associated with
Humidity Input Number 2. The text string is
stored in non-volatile memory.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.476.1.2.1.1.1.8.2.3 |
envHumidity2OffsetA humidity correction Offset associated with
the envHumidity2RH variable.
The value of Offset is added to the value from
Humidity Sensor Number 2 to obtain the value of
the envHumidity2RH variable. The Offset variable
is stored in non-volatile memory.rw INTEGER (-2147483648..2147483647) .1.3.6.1.4.1.476.1.2.1.1.1.8.2.4 |
envHumidity2HighLimitWhen envHumidity2RH reaches or exceeds this value
a trap will be generated signifying a high humidity
condition at humidity sensor 2. The HighLimit
variable is stored in non-volatile memory.rw INTEGER (-2147483648..2147483647) .1.3.6.1.4.1.476.1.2.1.1.1.8.2.5 |
envHumidity2LowLimitWhen envHumidity2RH reaches or goes below this value
a trap will be generated signifying a low humidity
condition at humidity sensor 2. The LowLimit
variable is stored in non-volatile memory.rw INTEGER (-2147483648..2147483647) .1.3.6.1.4.1.476.1.2.1.1.1.8.2.6 |
envTraps OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.2.1.1.1.11 |
leExperimental OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.2.2 |
lePrivate OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.2.3 |