Home/Catalog/LIEBERT-GP-ENVIRONMENTAL-MIB

LIEBERT-GP-ENVIRONMENTAL-MIB

AI MIB Summary

The LIEBERT-GP-ENVIRONMENTAL-MIB enables SNMP-based monitoring of Liebert GP-series precision cooling units and environmental control systems, specifically exposing metrics for temperature, humidity, airflow, and alarm states. This module facilitates the collection of critical facility infrastructure data required for data center thermal management and environmental fault detection.

The MIB module used to register Liebert SNMP OIDs. Copyright 2000-2008 Liebert Corporation. All rights reserved. Reproduction of this document is authorized on the condition that the forgoing copyright notice is included. This Specification is supplied 'AS IS' and Liebert Corporation makes no warranty, either express or implied, as to the use, operation, condition, or performance of the Specification.
Main OID:
liebertGlobalProductsEnvironmentalModule.1.3.6.1.4.1.476.1.42.1.5.1
295
Objects
Active
Status
2
Dependencies

Imported Objects

Objects

295 total
Object Name
liebertGlobalProductsEnvironmentalModuleThe MIB module used to register Liebert SNMP OIDs. Copyright 2000-2008 Liebert Corporation. All rights reserved. Reproduction of this document is authorized on the condition that the forgoing copyright notice is included. This Specification is supplied 'AS IS' and Liebert Corporation makes no warranty, either express or implied, as to the use, operation, condition, or performance of the Specification.
MODULE-IDENTITY
.1.3.6.1.4.1.476.1.42.1.5.1
lgpEnvTemperatureThis sub-tree is used to register Liebert temperature object identifiers.
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.1
lgpEnvTemperatureWellKnownLiebert well known temperature objects are identified by OIDs that reside in this sub-tree.
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.1.1
lgpEnvControlTemperatureTemperature measurement used as control feedback.
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.1.1.1
lgpEnvReturnAirTemperatureTemperature measurement of return air.
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.1.1.2
lgpEnvSupplyAirTemperatureTemperature measurement of supply air.
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.1.1.3
lgpAmbientTemperatureAmbient temperature measurement.
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.1.1.4
lgpInverterTemperatureTemperature measurement of the inverter.
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.1.1.5
lgpBatteryTempteratureTemperature measurement of the battery.
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.1.1.6
lgpAcDcConverterTemperatureTemperature measurement of the AC-to-DC Converter.
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.1.1.7
lgpPfcTemperatureTemperature measurement of the power factor correction circuitry.
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.1.1.8
lgpTransformerTemperatureTemperature measurement of the transformer.
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.1.1.9
lgpLocalTemperatureTemperature measurement of local temperature sensor.
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.1.1.10
lgpLocal1TemperatureTemperature and humidity measurements of Local Sensor 1.
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.1.1.10.1
lgpLocal2TemperatureTemperature and humidity measurements of Local Sensor 2.
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.1.1.10.2
lgpLocal3TemperatureTemperature and humidity measurements of Local Sensor 3.
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.1.1.10.3
lgpDigitalScrollCompressorTemperatureTemperature and humidity measurements of a digital Scroll Compressor.
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.1.1.11
lgpDigitalScrollCompressor1TemperatureTemperature and humidity measurements of a digital Scroll Compressor 1.
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.1.1.11.1
lgpDigitalScrollCompressor2TemperatureTemperature and humidity measurements of a digital Scroll Compressor 2.
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.1.1.11.2
lgpChillWaterTemperatureTemperature measurements of a chill water system.
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.1.1.12
lgpCoolantTemperatureTemperature measurements of an environmental system's coolant.
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.1.1.13
lgpEnvEnclosureTemperatureSensorsEnclosure temperature sensors
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.1.1.14
lgpEnvEnclosureTemperatureSensor1Enclosure temperature sensor 1
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.1.1.14.1
lgpEnvEnclosureTemperatureSensor2Enclosure temperature sensor 2
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.1.1.14.2
lgpEnvEnclosureTemperatureSensor3Enclosure temperature sensor 3
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.1.1.14.3
lgpEnvEnclosureTemperatureSensor4Enclosure temperature sensor 4
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.1.1.14.4
lgpEnvValueAmbientRoomTemperatureTemperature outside enclosure.
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.1.1.15
lgpEnvDewPointTemperatureThe calculated temperature outside of the enclosure at which condensation is likely to occur.
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.1.1.16
lgpEnvEnclosureTemperatureTemperature inside of enclosure.
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.1.1.17
lgpEnvAdjustedTemperatureThe current temperature set-point which is computed by the system and may be temporarily different from the user set-point because of external factors.
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.1.1.18
lgpEnvExternalSensorsExternal sensors to monitor environmental variables such as temperature and humidity
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.1.1.19
lgpEnvExternalAirSensorATemperature and humidity measurements from external air sensor A.
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.1.1.19.1
lgpEnvExternalAirSensorADewPointDewpoint temperature for External Air Sensor A.
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.1.1.19.2
lgpEnvExternalAirSensorBTemperature and humidity measurements from external air sensor B.
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.1.1.19.3
lgpEnvExternalAirSensorBDewPointDewpoint temperature for External Air Sensor B.
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.1.1.19.4
lgpEnvSupplyFluidTemperatureThe current temperature of the fluid being supplied.
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.1.1.20
lgpEnvSupplyRefrigerantTemperatureThe current temperature of the refrigerant being supplied.
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.1.1.21
lgpEnvMinDesiredRoomAirTemperatureThe minimum desired room air temperature. If the room air temperature falls below this set point, the unit will reduce the cooling.
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.1.1.22
lgpEnvDewPointTemperaturesThis sub-tree identifies well-known dew point temperatures in the system.
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.1.1.23
lgpEnvInletDewPointTemperatureDew point temperature measured at the inlet of the unit.
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.1.1.23.1
lgpEnvTemperatureFahrenheitThis sub-tree contains OIDs that are used to control and monitor temperature using the Fahrenheit temperature scale.
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.1.2
lgpEnvTemperatureSettingDegFThe temperature setting used to control the well known temperature object 'lgpEnvControlTemperature'. This setting is cloned in 'lgpEnvTemperatureSettingDegC' with the value converted to Celsius.rw
Integer32 UNITS "degrees Fahrenheit"
.1.3.6.1.4.1.476.1.42.3.4.1.2.1
lgpEnvTemperatureToleranceDegFThe acceptable variance from 'lgpEnvTemperatureSettingDegF', without initiating a control action. This setting is cloned in 'lgpEnvTemperatureToleranceDegC' with the value converted to Celsius.rw
Integer32 UNITS "0.1 degrees Fahrenheit"
.1.3.6.1.4.1.476.1.42.3.4.1.2.2
lgpEnvTemperatureTableDegFA list of temperature table entries. The table contains zero, one, or many rows, depending upon the number of temperature objects available. The NMS cannot create or delete rows from the table. The rows are created by the agent based upon the capabilities of the managed device. The entries in this table are cloned in 'lgpEnvTemperatureTableDegC' where Fahrenheit values are converted to Celsius.
SEQUENCE OF LgpEnvTemperatureEntryDegF
.1.3.6.1.4.1.476.1.42.3.4.1.2.3
lgpEnvTemperatureEntryDegFThis entry defines the contents of the rows for the table 'lgpEnvTemperatureTableDegF'.
LgpEnvTemperatureEntryDegF
.1.3.6.1.4.1.476.1.42.3.4.1.2.3.1
lgpEnvTemperatureIdDegFThis OID is used as an index to identify a row in the table 'lgpEnvTemperatureTableDegF'.ro
Unsigned32
.1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.1
lgpEnvTemperatureDescrDegFA reference to a temperature description object. The object referenced should not be accessible, but rather be used to provide a unique description of the temperature.ro
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.2
lgpEnvTemperatureMeasurementDegFThe measured temperature value.ro
Integer32 UNITS "degrees Fahrenheit"
.1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.3
lgpEnvTemperatureHighThresholdDegFThe high temperature notification threshold. This is the maximum value of 'lgpEnvTemperatureMeasurementDegF' before the agent sends a notification.rw
Integer32 UNITS "degrees Fahrenheit"
.1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.4
lgpEnvTemperatureLowThresholdDegFThe low temperature notification threshold. This is the minimum value of 'lgpEnvTemperatureMeasurementDegF' before the agent sends a notification.rw
Integer32 UNITS "degrees Fahrenheit"
.1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.5
lgpEnvTemperatureSetPointDegFThe temperature setting for the well known 'lgpEnvTemperatureDescrDegF' point. This setting may or may not be the setting used from control. Some systems have the capability to dynamically change the control setting based on environmental conditions and/or user configuration.rw
Integer32 UNITS "degrees Fahrenheit"
.1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.6
lgpEnvTemperatureDailyHighDegFThe daily high temperature measurement.ro
Integer32 UNITS "degrees Fahrenheit"
.1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.7
lgpEnvTemperatureDailyLowDegFThe daily low temperature measurement.ro
Integer32 UNITS "degrees Fahrenheit"
.1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.8
lgpEnvTempDailyHighTimeHourDegFThe hours digit of the time corresponding to the daily high temperature measurement.ro
Integer32
.1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.9
lgpEnvTempDailyHighTimeMinuteDegFThe minutes digit of the time corresponding to the daily high temperature measurement.ro
Integer32
.1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.10
lgpEnvTempDailyHighTimeSecondDegFThe seconds digit of the time corresponding to the daily high temperature measurement.ro
Integer32
.1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.11
lgpEnvTempDailyLowTimeHourDegFThe hours digit of the time corresponding to the daily low temperature measurement.ro
Integer32
.1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.12
lgpEnvTempDailyLowTimeMinuteDegFThe minutes digit of the time corresponding to the daily low temperature measurement.ro
Integer32
.1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.13
lgpEnvTempDailyLowTimeSecondDegFThe seconds digit of the time corresponding to the daily low temperature measurement.ro
Integer32
.1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.14
lgpEnvTemperatureMeasurementTenthsDegFThe measured temperature value.ro
Integer32 UNITS ".1 degrees Fahrenheit"
.1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.50
lgpEnvTemperatureHighThresholdTenthsDegFThe high temperature notification threshold. This is the maximum value of 'lgpEnvTemperatureMeasurementTenthsDegF' before the agent sends a notification.rw
Integer32 UNITS ".1 degrees Fahrenheit"
.1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.51
lgpEnvTemperatureLowThresholdTenthsDegFThe low temperature notification threshold. This is the minimum value of 'lgpEnvTemperatureMeasurementTenthsDegF' before the agent sends a notification.rw
Integer32 UNITS ".1 degrees Fahrenheit"
.1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.52
lgpEnvTemperatureSetPointTenthsDegFThe temperature setting for the well known 'lgpEnvTemperatureDescrDegF' point. This setting may or may not be the setting used from control. Some systems have the capability to dynamically change the control setting based on environmental conditions and/or user configuration.rw
Integer32 UNITS ".1 degrees Fahrenheit"
.1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.53
lgpEnvTemperatureDeadBandTenthsDegFThe deadband region around the setpoint value (lgpEnvTemperatureSetPointTenthsDegF) where no heating or cooling will occur.rw
Integer32 UNITS ".1 degrees Fahrenheit"
.1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.60
lgpEnvTempHeatingPropBandTenthsDegFThe proportional region below the setpoint value (lgpEnvTemperatureSetPointTenthsDegF) where heating will be proportionally controlled.rw
Integer32 UNITS ".1 degrees Fahrenheit"
.1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.61
lgpEnvTempCoolingPropBandTenthsDegFThe proportional region above the setpoint value (lgpEnvTemperatureSetPointTenthsDegF) where cooling will be proportionally controlled.rw
Integer32 UNITS ".1 degrees Fahrenheit"
.1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.62
lgpEnvTemperatureDeadbandRangeDegFThe allowable deviation above and below the temperature set point used to create a no control region, a dead-band, where heating and cooling control are disabled.rw
Integer32 UNITS ".1 degrees Fahrenheit"
.1.3.6.1.4.1.476.1.42.3.4.1.2.4
lgpEnvTemperatureCelsiusThis sub-tree contains OIDs that are used to control and monitor temperature using the Celsius temperature scale.
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.1.3
lgpEnvTemperatureSettingDegCThe temperature setting used to control the well known temperature object 'lgpEnvControlTemperature'. This setting is cloned in 'lgpEnvTemperatureSettingDegF' with the value converted to Fahrenheit.rw
Integer32 UNITS "degrees Celsius"
.1.3.6.1.4.1.476.1.42.3.4.1.3.1
lgpEnvTemperatureToleranceDegCThe acceptable variance from 'lgpEnvTemperatureSettingDegC', without initiating a control action. This setting is cloned in 'lgpEnvTemperatureToleranceDegF' with the value converted to Fahrenheit.rw
Integer32 UNITS "0.1 degrees Celsius"
.1.3.6.1.4.1.476.1.42.3.4.1.3.2
lgpEnvTemperatureTableDegCA list of temperature table entries. The table contains zero, one, or many rows, depending upon the number of temperature objects available. The NMS cannot create or delete rows from the table. The rows are created by the agent based upon the capabilities of the managed device. The entries in this table are cloned in 'lgpEnvTemperatureTableDegF' where Celsius values are converted to Fahrenheit.
SEQUENCE OF LgpEnvTemperatureEntryDegC
.1.3.6.1.4.1.476.1.42.3.4.1.3.3
lgpEnvTemperatureEntryDegCThis entry defines the contents of the rows for the table 'lgpEnvTemperatureTableDegC'.
LgpEnvTemperatureEntryDegC
.1.3.6.1.4.1.476.1.42.3.4.1.3.3.1
lgpEnvTemperatureIdDegCThis OID is used as an index to identify a row in the table 'lgpEnvTemperatureTableDegC'.ro
Unsigned32
.1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.1
lgpEnvTemperatureDescrDegCA reference to a temperature description object. The object referenced should not be accessible, but rather be used to provide a unique description of the temperature.ro
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.2
lgpEnvTemperatureMeasurementDegCThe measured temperature value.ro
Integer32 UNITS "degrees Celsius"
.1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.3
lgpEnvTemperatureHighThresholdDegCThe high temperature notification threshold. This is the maximum value of 'lgpEnvTemperatureMeasurementDegC' before the agent sends a notification.rw
Integer32 UNITS "degrees Celsius"
.1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.4
lgpEnvTemperatureLowThresholdDegCThe low temperature notification threshold. This is the minimum value of 'lgpEnvTemperatureMeasurementDegC' before the agent sends a notification.rw
Integer32 UNITS "degrees Celsius"
.1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.5
lgpEnvTemperatureSetPointDegCThe temperature setting for the well known 'lgpEnvTemperatureDescrDegC' point. This setting may or may not be the setting used from control. Some systems have the capability to dynamically change the control setting based on environmental conditions and/or user configuration.rw
Integer32 UNITS "degrees Celsius"
.1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.6
lgpEnvTemperatureDailyHighDegCThe daily high temperature measurement.ro
Integer32 UNITS "degrees Celsius"
.1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.7
lgpEnvTemperatureDailyLowDegCThe daily low temperature measurement.ro
Integer32 UNITS "degrees Celsius"
.1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.8
lgpEnvTempDailyHighTimeHourDegCThe hours digit of the time corresponding to the daily high temperature measurement.ro
Integer32
.1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.9
lgpEnvTempDailyHighTimeMinuteDegCThe minutes digit of the time corresponding to the daily high temperature measurement.ro
Integer32
.1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.10
lgpEnvTempDailyHighTimeSecondDegCThe seconds digit of the time corresponding to the daily high temperature measurement.ro
Integer32
.1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.11
lgpEnvTempDailyLowTimeHourDegCThe hours digit of the time corresponding to the daily low temperature measurement.ro
Integer32
.1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.12
lgpEnvTempDailyLowTimeMinuteDegCThe minutes digit of the time corresponding to the daily low temperature measurement.ro
Integer32
.1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.13
lgpEnvTempDailyLowTimeSecondDegCThe seconds digit of the time corresponding to the daily low temperature measurement.ro
Integer32
.1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.14
lgpEnvTemperatureMeasurementTenthsDegCThe measured temperature value.ro
Integer32 UNITS ".1 degrees Celsius"
.1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.50
lgpEnvTemperatureHighThresholdTenthsDegCThe high temperature notification threshold. This is the maximum value of 'lgpEnvTemperatureMeasurementTenthsDegC' before the agent sends a notification.rw
Integer32 UNITS ".1 degrees Celsius"
.1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.51
lgpEnvTemperatureLowThresholdTenthsDegCThe low temperature notification threshold. This is the minimum value of 'lgpEnvTemperatureMeasurementTenthsDegC' before the agent sends a notification.rw
Integer32 UNITS ".1 degrees Celsius"
.1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.52
lgpEnvTemperatureSetPointTenthsDegCThe temperature setting for the well known 'lgpEnvTemperatureDescrDegC' point. This setting may or may not be the setting used from control. Some systems have the capability to dynamically change the control setting based on environmental conditions and/or user configuration.rw
Integer32 UNITS ".1 degrees Celsius"
.1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.53
lgpEnvTemperatureDeadBandTenthsDegCThe deadband region around the setpoint value (lgpEnvTemperatureSetPointTenthsDegC) where no heating or cooling will occur.rw
Integer32 UNITS ".1 degrees Celsius"
.1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.60
lgpEnvTempHeatingPropBandTenthsDegCThe proportional region below the setpoint value (lgpEnvTemperatureSetPointTenthsDegC) where heating will be proportionally controlled.rw
Integer32 UNITS ".1 degrees Celsius"
.1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.61
lgpEnvTempCoolingPropBandTenthsDegCThe proportional region above the setpoint value (lgpEnvTemperatureSetPointTenthsDegC) where cooling will be proportionally controlled.rw
Integer32 UNITS ".1 degrees Celsius"
.1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.62
lgpEnvTemperatureDeadbandRangeDegCThe allowable deviation above and below the temperature set point used to create a no control region, a dead-band, where heating and cooling control are disabled.rw
Integer32 UNITS ".1 degrees Celsius"
.1.3.6.1.4.1.476.1.42.3.4.1.3.4
lgpEnvTemperatureControlModeA reference to a temperature description object. The object referenced should not be accessible, but rather be used to provide a unique description of the temperature object that is used for control.ro
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.1.4
lgpEnvHumidityThis sub-tree is used to register Liebert humidity object identifiers.
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.2
lgpEnvHumidityWellKnownLiebert well known humidity objects are defined by OIDs that reside in this sub-tree.
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.2.1
lgpEnvControlHumidityHumidity measurement used as control feedback.
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.2.1.1
lgpEnvReturnAirHumidityHumidity measurement of return air.
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.2.1.2
lgpEnvSupplyAirHumidityHumidity measurement of supply air.
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.2.1.3
lgpEnvValueAmbientHumidityHumidity outside enclosure.
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.2.1.4
lgpEnvHumidityRelativeThis sub-tree contains OIDs that are used to control and monitor relative humidity.
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.2.2
lgpEnvHumiditySettingRelThe humidity setting used to control the well known humidity point.rw
Integer32 UNITS "percent Relative Humidity"
.1.3.6.1.4.1.476.1.42.3.4.2.2.1
lgpEnvHumidityToleranceRelAcceptable variance from lgpEnvHumiditySettingRel, without initiating a control action.rw
Integer32 UNITS "percent Relative Humidity"
.1.3.6.1.4.1.476.1.42.3.4.2.2.2
lgpEnvHumidityTableRelA list of humidity table entries. The table contains zero, one, or many rows, depending upon the number of humidity objects available. The NMS cannot create or delete rows from the table. The rows are created by the agent based upon the capabilities of the managed device.
SEQUENCE OF LgpEnvHumidityEntryRel
.1.3.6.1.4.1.476.1.42.3.4.2.2.3
lgpEnvHumidityEntryRelThis entry defines the contents of the rows for the table 'lgpEnvHumidityTableRel'.
LgpEnvHumidityEntryRel
.1.3.6.1.4.1.476.1.42.3.4.2.2.3.1
lgpEnvHumidityIdRelThis OID is used as an index to identify a row in the table 'lgpEnvHumidityTableRel'.ro
Unsigned32
.1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.1
lgpEnvHumidityDescrRelA reference to a humidity description object. The object referenced should not be accessible, but rather be used to provide a unique description of the humidity.ro
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.2
lgpEnvHumidityMeasurementRelThe measured humidity value.ro
Integer32 UNITS "percent Relative Humidity"
.1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.3
lgpEnvHumidityHighThresholdRelThe high humidity notification threshold. This is the maximum value of 'lgpEnvHumidityMeasurementRel' before the agent sends a notification.rw
Integer32 UNITS "percent Relative Humidity"
.1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.4
lgpEnvHumidityLowThresholdRelThe low humidity notification threshold. This is the minimum value of 'lgpEnvHumidityMeasurementRel' before the agent sends a notification.rw
Integer32 UNITS "percent Relative Humidity"
.1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.5
lgpEnvHumiditySetPointThe humidity setting used to control the well known humidity object 'lgpEnvHumidityDescrRel'. This setting may or may not be the setting used from control. Some systems have the capability to dynamically change the control setting based on environmental conditions and/or user configuration.rw
Integer32 UNITS "percent Relative Humidity"
.1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.6
lgpEnvHumidityDailyHighThe daily high relative humidity measurement.ro
Integer32 UNITS "percent Relative Humidity"
.1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.7
lgpEnvHumidityDailyLowThe daily low relative humidity measurement.ro
Integer32 UNITS "percent Relative Humidity"
.1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.8
lgpEnvHumidityDailyHighTimeHourThe hours digit of the time corresponding to the daily high humidity measurement.ro
Integer32
.1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.9
lgpEnvHumidityDailyHighTimeMinuteThe minutes digit of the time corresponding to the daily high humidity measurement.ro
Integer32
.1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.10
lgpEnvHumidityDailyHighTimeSecondThe seconds digit of the time corresponding to the daily high humidity measurement.ro
Integer32
.1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.11
lgpEnvHumidityDailyLowTimeHourThe hours digit of the time corresponding to the daily low humidity measurement.ro
Integer32
.1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.12
lgpEnvHumidityDailyLowTimeMinuteThe minutes digit of the time corresponding to the daily low humidity measurement.ro
Integer32
.1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.13
lgpEnvHumidityDailyLowTimeSecondThe seconds digit of the time corresponding to the daily low humidity measurement.ro
Integer32
.1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.14
lgpEnvHumidityDeadBandThe deadband region around the setpoint value (lgpEnvHumiditySetPoint) where no humidifying or dehumidifying will occur.rw
Integer32 UNITS "percent Relative Humidity"
.1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.15
lgpEnvHumidifyPropBandThe proportional region below the setpoint value (lgpEnvHumiditySetPoint) where humidifying will be proportionally controlled.rw
Integer32 UNITS "percent Relative Humidity"
.1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.16
lgpEnvDehumidifyPropBandThe proportional region above the setpoint value (lgpEnvHumiditySetPoint) where dehumidifying will be proportionally controlled.rw
Integer32 UNITS "percent Relative Humidity"
.1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.17
lgpEnvHumidityMeasurementRelTenthsThe measured humidity value.ro
Integer32 UNITS ".1 percent Relative Humidity"
.1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.50
lgpEnvHumidityHighThresholdRelTenthsThe high humidity notification threshold. This is the maximum value of 'lgpEnvHumidityMeasurementRelTenths' before the agent sends a notification.rw
Integer32 UNITS ".1 percent Relative Humidity"
.1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.51
lgpEnvHumidityLowThresholdRelTenthsThe low humidity notification threshold. This is the minimum value of 'lgpEnvHumidityMeasurementRelTenths' before the agent sends a notification.rw
Integer32 UNITS ".1 percent Relative Humidity"
.1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.52
lgpEnvHumidityDeadbandRangeThe allowable deviation above and below the humidity set point used to create a no control region, a dead-band, where humidifying and dehumidifying control are disabled.rw
Integer32 UNITS ".1 percent RH"
.1.3.6.1.4.1.476.1.42.3.4.2.2.4
lgpEnvStateThis sub-tree is used to register Liebert environmental state object identifiers.
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.3
lgpEnvStateSystemThe present state of the system.ro
Enumeration
.1.3.6.1.4.1.476.1.42.3.4.3.1
lgpEnvStateCoolingThe present state of the cooling subsystem.ro
Enumeration
.1.3.6.1.4.1.476.1.42.3.4.3.2
lgpEnvStateHeatingThe present state of the heating subsystem.ro
Enumeration
.1.3.6.1.4.1.476.1.42.3.4.3.3
lgpEnvStateHumidifyingThe present state of the humidifier subsystem.ro
Enumeration
.1.3.6.1.4.1.476.1.42.3.4.3.4
lgpEnvStateDehumidifyingThe present state of the dehumidifier subsystemro
Enumeration
.1.3.6.1.4.1.476.1.42.3.4.3.5
lgpEnvStateEconoCycleThe present state of the Econ-o-cycle subsystem.ro
Enumeration
.1.3.6.1.4.1.476.1.42.3.4.3.6
lgpEnvStateFanThe present state of the system fan.ro
Enumeration
.1.3.6.1.4.1.476.1.42.3.4.3.7
lgpEnvStateGeneralAlarmOutputThe present state of the general alarm output. This indicates if an alarm is active in the system.ro
Enumeration
.1.3.6.1.4.1.476.1.42.3.4.3.8
lgpEnvStateCoolingCapacityThe percentage of the cooling capacity presently in use.ro
Unsigned32 UNITS "percent"
.1.3.6.1.4.1.476.1.42.3.4.3.9
lgpEnvStateHeatingCapacityThe percentage of the heating capacity presently in use.ro
Unsigned32 UNITS "percent"
.1.3.6.1.4.1.476.1.42.3.4.3.10
lgpEnvStateAudibleAlarmThe present state of the audible alarm output.ro
Enumeration
.1.3.6.1.4.1.476.1.42.3.4.3.11
lgpEnvStateCoolingUnitsThis sub-tree contains OIDs that are used to indicate the status of cooling units.
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.3.12
lgpEnvStateCoolingUnit1The present state of cooling unit 1.ro
Enumeration
.1.3.6.1.4.1.476.1.42.3.4.3.12.2
lgpEnvStateCoolingUnit2The present state of cooling unit 2.ro
Enumeration
.1.3.6.1.4.1.476.1.42.3.4.3.12.3
lgpEnvStateCoolingUnit3The present state of cooling unit 3.ro
Enumeration
.1.3.6.1.4.1.476.1.42.3.4.3.12.4
lgpEnvStateCoolingUnit4The present state of cooling unit 4.ro
Enumeration
.1.3.6.1.4.1.476.1.42.3.4.3.12.5
lgpEnvStateHeatingUnitsThis sub-tree contains OIDs that are used to indicate the status of heating units.
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.3.13
lgpEnvStateHeatingUnit1The present state of heating unit 1.ro
Enumeration
.1.3.6.1.4.1.476.1.42.3.4.3.13.2
lgpEnvStateHeatingUnit2The present state of heating unit 2.ro
Enumeration
.1.3.6.1.4.1.476.1.42.3.4.3.13.3
lgpEnvStateHeatingUnit3The present state of heating unit 3.ro
Enumeration
.1.3.6.1.4.1.476.1.42.3.4.3.13.4
lgpEnvStateHeatingUnit4The present state of heating unit 4.ro
Enumeration
.1.3.6.1.4.1.476.1.42.3.4.3.13.5
lgpEnvStateOperatingReasonThe reason for the current operating state of the system.ro
Enumeration
.1.3.6.1.4.1.476.1.42.3.4.3.14
lgpEnvStateOperatingModeThe present operating mode of the system.ro
Enumeration
.1.3.6.1.4.1.476.1.42.3.4.3.15
lgpEnvStateFanCapacityThe percentage of the fan capacity presently in use.ro
Unsigned32 UNITS "percent"
.1.3.6.1.4.1.476.1.42.3.4.3.16
lgpEnvStateFreeCoolingCapacityThe percentage of the free cooling capacity presently in use.ro
Unsigned32 UNITS "percent"
.1.3.6.1.4.1.476.1.42.3.4.3.17
lgpEnvStateDehumidifyingCapacityThe percentage of the dehumidifying capacity presently in use.ro
Unsigned32 UNITS "percent"
.1.3.6.1.4.1.476.1.42.3.4.3.18
lgpEnvStateHumidifyingCapacityThe percentage of the humidifying capacity presently in use.ro
Unsigned32 UNITS "percent"
.1.3.6.1.4.1.476.1.42.3.4.3.19
lgpEnvStateFreeCoolingThe present state of the system free cooling process of heat exchange. When 'off', free cooling is not in use. When 'on' free cooling is in use. When 'start', free cooling is preparing to turn on. When 'unavailable', the state information is unavailable.ro
Enumeration
.1.3.6.1.4.1.476.1.42.3.4.3.20
lgpEnvStateElectricHeaterThe present state of the electric heaters.ro
Enumeration
.1.3.6.1.4.1.476.1.42.3.4.3.21
lgpEnvStateHotWaterThe present state of hot water system.ro
Enumeration
.1.3.6.1.4.1.476.1.42.3.4.3.22
lgpEnvStateOperatingEfficiencyThe ratio of cooling energy provided to the amount of total energy being used.ro
Unsigned32 UNITS "percent"
.1.3.6.1.4.1.476.1.42.3.4.3.23
lgpEnvComponentStateTableThis table contains a list of the units components that have a state associated with them. The table contains zero, one, or more rows, depending upon the number of components associated with the unit. The NMS cannot create or delete rows in the table. The rows are created by the agent based upon the capabilities of the units being monitored.
SEQUENCE OF LgpEnvComponentStateEntry
.1.3.6.1.4.1.476.1.42.3.4.3.50
lgpEnvComponentStateEntryThis entry defines the attributes to be populated in the various columns of the 'lgpEnvComponentStateTable'.
LgpEnvComponentStateEntry
.1.3.6.1.4.1.476.1.42.3.4.3.50.1
lgpEnvComponentStateIndexThis is the index indicating the nth element of the table.
Unsigned32
.1.3.6.1.4.1.476.1.42.3.4.3.50.1.1
lgpEnvComponentStateDescrA reference to a component description object. The object referenced should not be accessible, but rather be used to provide a unique description of the component being described in the row of the table.ro
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.3.50.1.2
lgpEnvComponentStatenot-specified The state of the component is unknown. on The component is on. off The component is off.ro
Enumeration
.1.3.6.1.4.1.476.1.42.3.4.3.50.1.3
lgpEnvValveTableThis table contains a list of the unit valves that have information associated with them. The table contains zero, one, or more rows, depending upon the number of valves associated with the unit. The NMS cannot create or delete rows in the table. The rows are created by the agent based upon the capabilities of the units being monitored.
SEQUENCE OF LgpEnvValveEntry
.1.3.6.1.4.1.476.1.42.3.4.3.70
lgpEnvValveEntryThis entry defines the attributes to be populated in the various columns of the 'lgpEnvValveTable'.
LgpEnvValveEntry
.1.3.6.1.4.1.476.1.42.3.4.3.70.1
lgpEnvValveIndexThis is the index indicating the nth element of the table.
Unsigned32
.1.3.6.1.4.1.476.1.42.3.4.3.70.1.1
lgpEnvValveDescrA reference to a valve description object. The object referenced should not be accessible, but rather be used to provide a unique description of the valve being described in the row of the table.ro
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.3.70.1.2
lgpEnvValveStatenot-specified The state of the component is unknown. open The valve is open. off The valve is closed.ro
Enumeration
.1.3.6.1.4.1.476.1.42.3.4.3.70.1.3
lgpEnvValvePositionTenthsThis gives a value describing the position of the valve.ro
Unsigned32 UNITS ".1 percent"
.1.3.6.1.4.1.476.1.42.3.4.3.70.1.20
lgpEnvConfigThis sub-tree is used to register Liebert environmental configuration object identifiers.
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.4
lgpEnvConfigReheatLockoutIf locked-out the reheats will not operate even if controller calls for its operation.rw
Enumeration
.1.3.6.1.4.1.476.1.42.3.4.4.1
lgpEnvConfigHumLockoutIf locked-out the humidifier will not operate even if controller calls for its operation.rw
Enumeration
.1.3.6.1.4.1.476.1.42.3.4.4.2
lgpEnvConfigRestartDelayWhen utility power is disrupted, this is the delay interval to wait before restarting the system after the utility power is restored. A Restart Delay of zero denotes a manual restart, the unit will NOT automatically restart.rw
Unsigned32 UNITS "seconds"
.1.3.6.1.4.1.476.1.42.3.4.4.4
lgpEnvConfigRemoteShutdownWhen in the disabled state, the remote shutdown feature should be locked out. The enabled state is self-describing.rw
Enumeration
.1.3.6.1.4.1.476.1.42.3.4.4.7
lgpEnvConfigCoolingServiceIntervalThe amount of time, in hours, between scheduled maintenance of the cooling system. When the cooling service timer reaches this value an lgpConditionServiceCooling will be activated. Once service has been completed the cooling service timer should be reset to 0.rw
Unsigned32 UNITS "hours"
.1.3.6.1.4.1.476.1.42.3.4.4.8
lgpEnvConfigHumidifierServiceIntervalThe amount of time, in hours, between scheduled maintenance of the humidifier. When the humidifier service timer reaches this value an lgpConditionServiceHumidifier will be activated. Once service has been completed humidifier service timer should be reset to 0.rw
Unsigned32 UNITS "hours"
.1.3.6.1.4.1.476.1.42.3.4.4.9
lgpEnvConfigFilterServiceIntervalThe amount of time, in hours, between scheduled maintenance of the system filter. When the filter service timer reaches this value an lgpConditionChangeFilter will be activated. Once service has been completed the filter service timer should be reset to 0.rw
Unsigned32 UNITS "hours"
.1.3.6.1.4.1.476.1.42.3.4.4.10
lgpEnvConfigSleepModeDeadbandRangeDegCThe allowable deviation above and below the temperature set point used to create a no control region, a dead-band, where heating and cooling control are disabled. This dead-band is applied only when the system's sleep mode function is in operation.rw
Integer32 UNITS ".1 degrees Celsius"
.1.3.6.1.4.1.476.1.42.3.4.4.11
lgpEnvConfigSleepModeDeadbandRangeDegFThe allowable deviation above and below the temperature set point used to create a no control region, a dead-band, where heating and cooling control are disabled. This dead-band is applied only when the system's sleep mode function is in operation.rw
Integer32 UNITS ".1 degrees Fahrenheit"
.1.3.6.1.4.1.476.1.42.3.4.4.12
lgpEnvConfigSupplyTempLowLimitDegFThe minimum allowable supply temperature.rw
Integer32 UNITS "degrees Fahrenheit"
.1.3.6.1.4.1.476.1.42.3.4.4.13
lgpEnvConfigSupplyTempLowLimitDegCThe minimum allowable supply temperature.rw
Integer32 UNITS "degrees Celsius"
.1.3.6.1.4.1.476.1.42.3.4.4.14
lgpEnvConfigTemperatureIntegTimeThe value used as the integration factor in the proportional integral derivative (PID) temperature calculation.rw
Integer32 UNITS "minutes"
.1.3.6.1.4.1.476.1.42.3.4.4.15
lgpEnvConfigLocalTemperatureUnitThe local temperature unit of the system.rw
Enumeration
.1.3.6.1.4.1.476.1.42.3.4.4.16
lgpEnvConfigSleepModeThe configured mode of the device's sleep function. If 'enabled', the device will sleep, or not operate, for each 'lgpEnvSleepDay' that is enabled and also during the periods defined in the 'lgpEnvSleepTimeTable' each day. If 'disabled', the device will operate continually and not sleep at all. If 'auto', the device will sleep, or not operate, for each 'lgpEnvSleepDay' that is enabled and also during the periods defined in the 'lgpEnvSleepTimeTable' each day unless the environmental conditions fall outside the desired operation ranges.rw
Enumeration
.1.3.6.1.4.1.476.1.42.3.4.4.17
lgpEnvConfigHumidityIntegTimeThe value used as the integration factor in the proportional integral derivative (PID) humidity calculation.rw
Integer32 UNITS "minutes"
.1.3.6.1.4.1.476.1.42.3.4.4.18
lgpEnvConfigFreecoolingDeltaDegFThe minimum temperature differential between the control temperature measurement and the coolant required to utilize free-cooling.rw
Integer32 UNITS "degrees Fahrenheit"
.1.3.6.1.4.1.476.1.42.3.4.4.19
lgpEnvConfigFreecoolingDeltaDegCThe minimum temperature differential between the control temperature measurement and the coolant required to utilize free-cooling.rw
Integer32 UNITS "degrees Celsius"
.1.3.6.1.4.1.476.1.42.3.4.4.20
lgpEnvConfigSupplyTempLowLimitThe system configuration parameter to enable or disable the supply air low temperature limit.rw
Enumeration
.1.3.6.1.4.1.476.1.42.3.4.4.21
lgpEnvConfigSensorEventsStandardThe system configuration parameter to enable or disable the standard sensor events.rw
Enumeration
.1.3.6.1.4.1.476.1.42.3.4.4.22
lgpEnvConfigSensorEvents1The system configuration parameter to enable or disable sensor 1 events.rw
Enumeration
.1.3.6.1.4.1.476.1.42.3.4.4.23
lgpEnvConfigSleepModeDeadbandRangeThe system configuration parameter to enable or disable the use of the sleep interval dead-band range in the sleep mode temperature calculations and control algorithm.rw
Enumeration
.1.3.6.1.4.1.476.1.42.3.4.4.24
lgpEnvConfigAutoConfigurationThe system configuration parameter to enable or disable the auto configuration feature. This feature configures temperature and humidity control parameters.rw
Enumeration
.1.3.6.1.4.1.476.1.42.3.4.4.25
lgpEnvConfigDeltaGlycolTypeThe system configuration parameter that specifies how the system will determine if there is enough capacity to initiate free cooling. If 'disabled', the system will use the valve temperature to initiate free cooling. If 'contact', a input to the system will initiate free cooling. If 'valve', the system compares the room and glycol temperature differential with the valve temperature to initiate free cooling. If the temperature differential is greater than or equal to the valve temperature, free cooling will be initiated.rw
Enumeration
.1.3.6.1.4.1.476.1.42.3.4.4.26
lgpEnvConfigChillWaterControlThe system configuration parameter to enable or disable the minimum chill water temperature control.rw
Enumeration
.1.3.6.1.4.1.476.1.42.3.4.4.27
lgpEnvConfigInfaredFlushRateThe Infrared humidifier pan overfill rate. This parameter configures the amount of water that flows into the humidifier pan when the 'humidifier is in operation.rw
Unsigned32 UNITS "percent"
.1.3.6.1.4.1.476.1.42.3.4.4.28
lgpEnvConfigHumidityControlThe present configured state of the automatic humidity compensation algorithm.rw
Enumeration
.1.3.6.1.4.1.476.1.42.3.4.4.29
lgpEnvConfigCompressorLockoutThe system as locked out the compressor(s). If locked-out, the compressor(s) will not operate even if the controller calls for their operation.rw
Enumeration
.1.3.6.1.4.1.476.1.42.3.4.4.30
lgpEnvConfigReheatAndHumidifierLockoutThe system as locked out the compressor(s). If locked-out, the electrical reheats and humidifier will not operate even if the controller calls for their operation.rw
Enumeration
.1.3.6.1.4.1.476.1.42.3.4.4.31
lgpEnvOperationalTimeTableA list of environmental operational time ranges for a given environmental unit. The entries in this table may be duplicated from values in the 'lgpEnvStatistics' group. This table contains zero, one, or many rows, depending upon the number of 'lgpEnvOperationTimePoint' and 'lgpEnvOperationTimeSubID' available in the table. The NMS cannot create or delete rows from the table. The rows are created by the agent based upon the capabilities of the managed device.
SEQUENCE OF LgpEnvOperationalTimeEntry
.1.3.6.1.4.1.476.1.42.3.4.4.32
lgpEnvOperationalTimeEntryThis entry defines the contents of the columns for the table 'lgpEnvOperationalTimeTable'.
LgpEnvOperationalTimeEntry
.1.3.6.1.4.1.476.1.42.3.4.4.32.1
lgpEnvOperationTimeIndexThis is the index indicating the nth element of the table.
Unsigned32
.1.3.6.1.4.1.476.1.42.3.4.4.32.1.1
lgpEnvOperationTimePointAn OID representing a well known operation point. These object identifiers can indicate a point, location, or mode of an operation for which a measurement is recorded. The OID's name usually implies a location of the measurement point such as 'fan', 'compressor', etc.ro
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.4.32.1.2
lgpEnvOperationTimeSubIDThis is a sub identifier for the 'lgpEnvOperationPoint'. It indicates the instance number of the well known operation point. For example, a system could have two fans installed. This variable would identify fan 1 with a lgpEnvOperationSubID equal to 1 and fan 2 with a lgpEnvOperationSubID equal to 2.ro
Integer32
.1.3.6.1.4.1.476.1.42.3.4.4.32.1.3
lgpEnvOperationTimeUnitAn OID representing a well known operation time unit type. These object identifiers indicate the units of the operation time. The OID's name usually implies a measurement type such as 'lgpEnvHours', etc.ro
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.4.32.1.4
lgpEnvOperationTimeValueThe actual operation time value of the 'lgpEnvOperationTimePoint'. If multiple operation times are available for a 'lgpEnvOperationTimePoint' the 'lgpEnvOperationTimeSubID' will differentiate between them.rw
Integer32 UNITS "hours"
.1.3.6.1.4.1.476.1.42.3.4.4.32.1.5
lgpEnvOperationTimeHighWarningThe high warning time of the operation designated by the 'lgpEnvOperationTimePoint'. If operation times are available at a single 'lgpEnvOperationTimePoint' the 'lgpEnvOperationTimeSubID' will differentiate between them.rw
Integer32 UNITS "hours"
.1.3.6.1.4.1.476.1.42.3.4.4.32.1.6
lgpEnvConfigTempControlAlgorithmSelects the algorithm for controlling temperature.rw
Enumeration
.1.3.6.1.4.1.476.1.42.3.4.4.33
lgpEnvConfigFanSpeedModeChanges the function of the fan speed output. If auto, then the fan speed is modulated. If manual, the fan speed output follows lgpEnvConfigFanSpeedCapacity.rw
Enumeration
.1.3.6.1.4.1.476.1.42.3.4.4.34
lgpEnvConfigFanSpeedCapacitySets the fan speed output if lgpEnvConfigFanSpeedMode is set to 'manual'. Typical values range from 0 to 100% (actual valid ranges may differ from unit to unit).rw
Unsigned32 UNITS "percent"
.1.3.6.1.4.1.476.1.42.3.4.4.35
lgpEnvConfigBmsResetTimerThe current count-down time for a BMS to continue controlling the fan speed. If this value reaches 0, then the condition lgpConditionBmsResetTimerExpired will be generated. If a BMS wants to continue controlling the fan speed, it must reset this timer. Typical values range from 0 to 120 minutes (actual valid ranges may differ from unit to unit).rw
Unsigned32 UNITS "minutes"
.1.3.6.1.4.1.476.1.42.3.4.4.36
lgpEnvConfigDisableSensorOffsetDegCIf any of the enclosure temperature sensors (lgpEnvEnclosureTemperatureSensors) are outside the average reading by this amount, that sensor's readings will not be used.rw
Integer32 UNITS "degrees Celsius"
.1.3.6.1.4.1.476.1.42.3.4.4.37
lgpEnvConfigDisableSensorOffsetDegFIf any of the enclosure temperature sensors (lgpEnvEnclosureTemperatureSensors) are outside the average reading by this amount, that sensor's readings will not be used.rw
Integer32 UNITS "degrees Fahrenheit"
.1.3.6.1.4.1.476.1.42.3.4.4.38
lgpEnvConfigCabinetSensorAlarmsEnable or Disable Cabinet Sensor Alarms.rw
Enumeration
.1.3.6.1.4.1.476.1.42.3.4.4.39
lgpEnvConfigAirTemperatureControlSensorSensor from which air temperature measurements will be used for cooling and heating control.rw
Enumeration
.1.3.6.1.4.1.476.1.42.3.4.4.42
lgpEnvConfigFanSpeedControlSensorSensor from which air temperature measurements will be used for fan speed control.rw
Enumeration
.1.3.6.1.4.1.476.1.42.3.4.4.43
lgpEnvConfigMinFanSpeedSets the minimum fan speed output if lgpEnvConfigFanSpeedMode is set to 'Auto'.rw
Unsigned32 UNITS "percent"
.1.3.6.1.4.1.476.1.42.3.4.4.44
lgpEnvConfigMaxFanSpeedSets the maximum fan speed output if lgpEnvConfigFanSpeedMode is set to 'Auto'.rw
Unsigned32 UNITS "percent"
.1.3.6.1.4.1.476.1.42.3.4.4.45
lgpEnvConfigFanSpeedPropBandDegCTemperature control band above the temperature set point calculated for proportional fan speed control. If measured air temperature is within this band, fan speed operations are proportionally controlled.rw
Integer32 UNITS "degrees Celsius"
.1.3.6.1.4.1.476.1.42.3.4.4.46
lgpEnvConfigFanSpeedPropBandDegFTemperature control band above the temperature set point calculated for proportional fan speed control. If measured air temperature is within this band, fan speed operations are proportionally controlled.rw
Integer32 UNITS "degrees Fahrenheit"
.1.3.6.1.4.1.476.1.42.3.4.4.47
lgpEnvControlThis sub-tree is used to register Liebert environmental control object identifiers.
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.5
lgpEnvControlShutdownAfterDelaySetting this object will shutdown (i.e., turn off) the system after the indicated number of seconds. Setting this object to 0 will cause the shutdown to occur immediately. Setting this object to -1 will abort the countdown. If the system is already in the desired state at the time the countdown reaches 0, then nothing will happen. When read, lgpEnvControlShutdownAfterDelay will return the number of seconds remaining until shutdown, or -1 if no shutdown countdown is in effect. On some systems, if the agent is restarted while a shutdown countdown is in effect, the countdown may be aborted. Sets to this object override any lgpEnvControlShutdownAfterDelay already in effect.rw
Integer32 (-1..2147483647) UNITS "seconds"
.1.3.6.1.4.1.476.1.42.3.4.5.1
lgpEnvControlStartupAfterDelaySetting this object will start the system after the indicated number of seconds. Setting this object to 0 will cause the startup to occur immediately. Setting this object to -1 will abort the countdown. If the system is already on at the time the countdown reaches 0, then nothing will happen. Sets to this object override the effect of any lgpEnvControlStartupAfterDelay countdown in progress. When read, lgpEnvControlStartupAfterDelay will return the number of seconds until startup, or -1 if no startup countdown is in effect. On some systems, if the agent is restarted while a startup countdown is in effect, the countdown is aborted.rw
Integer32 (-1..2147483647) UNITS "seconds"
.1.3.6.1.4.1.476.1.42.3.4.5.2
lgpEnvSleepIntervalTimeTableA sleep time interval table containing a list of the start and stop times to be used to take a device online or offline. The NMS cannot create or delete rows from the table. The rows are created by the agent based upon the capabilities of the managed device.
SEQUENCE OF LgpEnvSleepIntervalTimeEntry
.1.3.6.1.4.1.476.1.42.3.4.5.3
lgpEnvSleepIntervalTimeEntryThis entry defines the contents of the columns for the table 'lgpEnvSleepIntervalTimeTable'.
LgpEnvSleepIntervalTimeEntry
.1.3.6.1.4.1.476.1.42.3.4.5.3.1
lgpEnvSleepTimeIndexThis is the index indicating the row of the table 'lgpEnvSleepIntervalTimeTable'.
Unsigned32
.1.3.6.1.4.1.476.1.42.3.4.5.3.1.1
lgpEnvSleepTimeSubIDThis is a sub identifier for each 'lgpEnvSleepIntervalTimeEntry'. It indicates the instance number of the 'lgpEnvSleepIntervalTimeEntry'. For example, a system could have two sleep intervals and the first interval's sub ID would be 1 and the second interval's sub ID would be 2.ro
Integer32
.1.3.6.1.4.1.476.1.42.3.4.5.3.1.2
lgpEnvSleepTimeStartHourThis is the hours digit of the time when the system will be put online.rw
Integer32
.1.3.6.1.4.1.476.1.42.3.4.5.3.1.3
lgpEnvSleepTimeStartMinuteThis is the minutes digit of the time when the system will be put online.rw
Integer32
.1.3.6.1.4.1.476.1.42.3.4.5.3.1.4
lgpEnvSleepTimeStopHourThis is the hours digit containing the time when the system will be taken offline.rw
Integer32
.1.3.6.1.4.1.476.1.42.3.4.5.3.1.5
lgpEnvSleepTimeStopMinuteThis is the minutes digit containing the time when the system will be taken offline.rw
Integer32
.1.3.6.1.4.1.476.1.42.3.4.5.3.1.6
lgpEnvSleepDayTableA sleep table containing a list of the days of the week the system will be offline. The NMS cannot create or delete rows from the table. The rows are created by the agent based upon the capabilities of the managed device.
SEQUENCE OF LgpEnvSleepDayEntry
.1.3.6.1.4.1.476.1.42.3.4.5.4
lgpEnvSleepDayEntryThis entry defines the contents of the columns for the table 'lgpEnvSleepDayTable'.
LgpEnvSleepDayEntry
.1.3.6.1.4.1.476.1.42.3.4.5.4.1
lgpEnvSleepDayIndexThis is the index indicating the row of the table 'lgpEnvSleepDayTable'.
Unsigned32
.1.3.6.1.4.1.476.1.42.3.4.5.4.1.1
lgpEnvSleepDayThis is a sub identifier for the day of the week within 'lgpEnvSleepDayTable'.ro
Enumeration
.1.3.6.1.4.1.476.1.42.3.4.5.4.1.2
lgpEnvSleepAllDayEnabledThe all day sleep functionality has been enabled for the corresponding 'lgpEnvSleepDay' in the 'lgpEnvSleepDayTable'.rw
Enumeration
.1.3.6.1.4.1.476.1.42.3.4.5.4.1.3
lgpEnvStatisticsThis sub-tree is used to register Liebert environmental statistic object identifiers.
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.6
lgpEnvStatisticsComp1RunHrAccumulated run hours of compressor 1. This value may be duplicated in the 'lgpEnvOperationalTimeTable'.ro
Unsigned32 UNITS "hours"
.1.3.6.1.4.1.476.1.42.3.4.6.1
lgpEnvStatisticsComp2RunHrAccumulated run hours of compressor 2. This value may be duplicated in the 'lgpEnvOperationalTimeTable'.ro
Unsigned32 UNITS "hours"
.1.3.6.1.4.1.476.1.42.3.4.6.2
lgpEnvStatisticsFanRunHrAccumulated run hours of the main fan. This value may be duplicated in the 'lgpEnvOperationalTimeTable'.ro
Unsigned32
.1.3.6.1.4.1.476.1.42.3.4.6.3
lgpEnvStatisticsHumRunHrAccumulated run hours of the humidifier. This value may be duplicated in the 'lgpEnvOperationalTimeTable'.ro
Unsigned32
.1.3.6.1.4.1.476.1.42.3.4.6.4
lgpEnvStatisticsReheat1RunHrAccumulated run hours of reheat element 1. This value may be duplicated in the 'lgpEnvOperationalTimeTable'.ro
Unsigned32 UNITS "hours"
.1.3.6.1.4.1.476.1.42.3.4.6.7
lgpEnvStatisticsReheat2RunHrAccumulated run hours of reheat element 2. This value may be duplicated in the 'lgpEnvOperationalTimeTable'.ro
Unsigned32 UNITS "hours"
.1.3.6.1.4.1.476.1.42.3.4.6.8
lgpEnvStatisticsReheat3RunHrAccumulated run hours of reheat element 3. This value may be duplicated in the 'lgpEnvOperationalTimeTable'.ro
Unsigned32 UNITS "hours"
.1.3.6.1.4.1.476.1.42.3.4.6.9
lgpEnvStatisticsCoolingModeHrsAccumulated run hours while lgpEnvStateCooling is on(1). This value may be duplicated in the 'lgpEnvOperationalTimeTable'.ro
Unsigned32 UNITS "hours"
.1.3.6.1.4.1.476.1.42.3.4.6.10
lgpEnvStatisticsHeatingModeHrsAccumulated run hours while lgpEnvStateHeating is on(1). This value may be duplicated in the 'lgpEnvOperationalTimeTable'.ro
Unsigned32 UNITS "hours"
.1.3.6.1.4.1.476.1.42.3.4.6.11
lgpEnvStatisticsHumidifyModeHrsAccumulated run hours of the humidifying process of the system. This value may be duplicated in the 'lgpEnvOperationalTimeTable'.ro
Unsigned32 UNITS "hours"
.1.3.6.1.4.1.476.1.42.3.4.6.12
lgpEnvStatisticsDehumidifyModeHrsAccumulated run hours of the dehumidifying process of the system. This value may be duplicated in the 'lgpEnvOperationalTimeTable'.ro
Unsigned32 UNITS "hours"
.1.3.6.1.4.1.476.1.42.3.4.6.13
lgpEnvStatisticsHotGasRunHrAccumulated run hours of the hot gas system. This value may be duplicated in the 'lgpEnvOperationalTimeTable'.ro
Unsigned32 UNITS "hours"
.1.3.6.1.4.1.476.1.42.3.4.6.14
lgpEnvStatisticsHotWaterRunHrAccumulated run hours of the hot water system. This value may be duplicated in the 'lgpEnvOperationalTimeTable'.ro
Unsigned32 UNITS "hours"
.1.3.6.1.4.1.476.1.42.3.4.6.15
lgpEnvStatisticsFreeCoolRunHrAccumulated run hours of the free cooling process. This value may be duplicated in the 'lgpEnvOperationalTimeTable'.ro
Unsigned32 UNITS "hours"
.1.3.6.1.4.1.476.1.42.3.4.6.16
lgpEnvStatisticsComp3RunHrAccumulated run hours of compressor 3.ro
Unsigned32
.1.3.6.1.4.1.476.1.42.3.4.6.17
lgpEnvStatisticsComp4RunHrAccumulated run hours of compressor 4.ro
Unsigned32
.1.3.6.1.4.1.476.1.42.3.4.6.18
lgpEnvPointsThis sub-tree is used to register Liebert environmental point object identifiers.
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.7
lgpEnvWellKnownPointsThis sub-tree registers well known Liebert Environmental Points. The object identifier names usually encompass a process, or location, where measurements are recorded or where values are applied.
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.7.1
lgpEnvFanPointThis identifier represents a well known fan measurement point.
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.7.1.1
lgpEnvCompressorPointThis identifier represents a well known compressor measurement point.
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.7.1.2
lgpEnvElectricHeaterPointThis identifier represents a well known electric heater measurement point.
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.7.1.3
lgpEnvChilledWaterPointThis identifier represents a well known chilled water measurement point.
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.7.1.4
lgpEnvHumidifierPointThis identifier represents a well known humidifier measurement point.
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.7.1.5
lgpEnvDehumidifierPointThis identifier represents a well known dehumidifier measurement point.
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.7.1.6
lgpEnvFreeCoolingPointThis identifier represents a well known free-cooling measurement process.
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.7.1.7
lgpEnvHotWaterPointThis identifier represents a well known hot water measurement point.
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.7.1.8
lgpEnvHotGasPointThis identifier represents a well known hot gas measurement point.
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.7.1.9
lgpEnvBatteryCabinetPointThis identifier represents a well known cabinet point. To determine the cabinet being described in a multi-cabinet system, this point implements two additional indexes. The first index describes the module being supplied with battery power. The second index identifies the number of the battery cabinet, which is typically a sequential number. Example: lgpPwrMeasBatteryCabinet.2.4 'lgpEnvBatteryCabinetPoint' = Point is a battery cabinet. '.2' = Cabinet is in the second module. '.4' = Cabinet number 4
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.7.1.10
lgpEnvPumpPointsThis sub-tree identifies well-known pumps in the system.
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.7.1.11
lgpEnvPump1PointThis identifier represents pump 1.
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.7.1.11.1
lgpEnvPump2PointThis identifier represents pump 2.
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.7.1.11.2
lgpEnvCompressorPointsThis sub-tree identifies well-known compressors in the system.
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.7.1.12
lgpEnvCompressor1PointThis identifier represents compressor 1.
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.7.1.12.1
lgpEnvCompressor1APointThis identifier represents compressor 1A.
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.7.1.12.1.1
lgpEnvCompressor1BPointThis identifier represents compressor 1B.
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.7.1.12.1.2
lgpEnvCompressor2PointThis identifier represents compressor 2.
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.7.1.12.2
lgpEnvCompressor2APointThis identifier represents compressor 2A.
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.7.1.12.2.1
lgpEnvCompressor2BPointThis identifier represents compressor 2B.
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.7.1.12.2.2
lgpEnvValvePointsThis sub-tree identifies well-known valves in the system.
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.7.1.13
lgpEnvHotGasValve1PointThis identifier represents hot gas valve 1.
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.7.1.13.1
lgpEnvHotGasValve2PointThis identifier represents hot gas valve 2.
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.7.1.13.2
lgpEnvRemoteSensorStatisticPointsThis sub-tree identifies well-known remote sensor statistics in the system.
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.7.1.14
lgpEnvRemoteSensorMinimumPointThis identifier represents the minimum value for remote sensor readings.
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.7.1.14.1
lgpEnvRemoteSensorMaximumPointThis identifier represents the maximum value for remote sensor readings.
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.7.1.14.2
lgpEnvRemoteSensorAveragePointThis identifier represents the average value for remote sensor readings.
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.7.1.14.3
lgpEnvUnitsThis sub-tree is used to register Liebert environmental unit object identifiers.
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.8
lgpEnvWellKnownUnitsThis sub-tree registers well known Liebert Environmental Units. The object identifier names usually encompass a process, or location, where measurements are recorded or where values are applied.
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.8.1
lgpEnvHoursThis identifier represents well known time unit of hours.
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.8.1.1
lgpEnvRemoteSensorsThis sub-tree is used to register Liebert environmental remote sensor object identifiers.
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.4.9
lgpEnvRemoteSensorCalcCalculation method applied to temperature readings from the remote sensors to determine a single temperature measurement value for cooling and heating control.rw
Enumeration
.1.3.6.1.4.1.476.1.42.3.4.9.1
lgpEnvRemoteSensorTableThis table contains a list of remote sensors attached to the environmental unit. The table contains zero, one, or more rows, depending upon the number of sensors attached to the unit.
SEQUENCE OF LgpEnvRemoteSensorEntry
.1.3.6.1.4.1.476.1.42.3.4.9.10
lgpEnvRemoteSensorEntryThis entry defines the attributes to be populated in the various columns of the 'lgpEnvRemoteSensorTable'.
LgpEnvRemoteSensorEntry
.1.3.6.1.4.1.476.1.42.3.4.9.10.1
lgpEnvRemoteSensorIndexThis is the index indicating the nth element of the table.
Unsigned32
.1.3.6.1.4.1.476.1.42.3.4.9.10.1.1
lgpEnvRemoteSensorIdThis is the sensor number identifying the sensor.ro
Unsigned32
.1.3.6.1.4.1.476.1.42.3.4.9.10.1.2
lgpEnvRemoteSensorModeFunction assigned to remote sensor. When set to control(2) the sensor will be used in calculation of remote sensor temperature which may be used for heating and cooling control. When set to disable(0) the remote sensor reading is not available. When set to reference(1) the remote sensor reading is available but not used for control.rw
Enumeration
.1.3.6.1.4.1.476.1.42.3.4.9.10.1.3
lgpEnvRemoteSensorUsrLabelUser assigned remote sensor label.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.476.1.42.3.4.9.10.1.4
lgpEnvRemoteSensorTempMeasurementDegFTemperature measured at the temperature sensor reported in degrees Fahrenheit.ro
Integer32 UNITS "degrees Fahrenheit"
.1.3.6.1.4.1.476.1.42.3.4.9.10.1.5
lgpEnvRemoteSensorTempMeasurementDegCTemperature measured at the temperature sensor reported in degrees Celsius.ro
Integer32 UNITS "degrees Celsius"
.1.3.6.1.4.1.476.1.42.3.4.9.10.1.6