LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB
AI MIB Summary
The LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB enables SNMP-based monitoring and management of Liebert GP series power and environmental control units, specifically exposing configurable alarm thresholds and conditional logic states for critical infrastructure parameters. This module facilitates the retrieval of dynamic condition variables and event triggers to automate fault detection and response within data center power distribution and cooling systems.
The MIB module used to register Liebert SNMP OIDs. Copyright 2000-2016 Liebert Corporation. All rights reserved. Reproduction of this document is authorized on the condition that the forgoing copyright notice is included. This Specification is supplied 'AS IS' and Liebert Corporation makes no warranty, either express or implied, as to the use, operation, condition, or performance of the Specification.
Main OID:
liebertGlobalProductsFlexibleConditionsModule.1.3.6.1.4.1.476.1.42.1.11.1
727
Objects
Active
Status
3
Dependencies
Imported Objects
Objects
727 total| Object Name |
|---|
liebertGlobalProductsFlexibleConditionsModuleThe MIB module used to register Liebert SNMP OIDs. Copyright 2000-2016 Liebert Corporation. All rights reserved. Reproduction of this document is authorized on the condition that the forgoing copyright notice is included. This Specification is supplied 'AS IS' and Liebert Corporation makes no warranty, either express or implied, as to the use, operation, condition, or performance of the Specification. MODULE-IDENTITY .1.3.6.1.4.1.476.1.42.1.11.1 |
lgpFlexConditionsWellKnown OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1 |
lgpCondId4122SystemInputPowerProblemThe input is not qualified to provide power to the system. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4122 |
lgpCondId4132BypassOverloadPhaseAAn overload exists on output phase A while operating on the bypass. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4132 |
lgpCondId4133BypassOverloadPhaseBAn overload exists on output phase B while operating on the bypass. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4133 |
lgpCondId4134BypassOverloadPhaseCAn overload exists on output phase C while operating on the bypass. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4134 |
lgpCondId4135BypassNotAvailableA problem associated with the bypass has been detected. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4135 |
lgpCondId4137BypassAutoRetransferPrimedAutomatic retransfer from bypass to inverter is possible. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4137 |
lgpCondId4138BypassAutoRetransferFailedAfter performing a recoverable transfer to bypass, an attempt to auto retransfer from bypass to inverter failed. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4138 |
lgpCondId4139BypassExcessAutoRetransfersThe number of auto retransfers, from bypass to inverter, has exceeded the maximum for a specified time interval. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4139 |
lgpCondId4140BypassRestartInhibitExternalRestart of the bypass is inhibited by the state of an external signal. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4140 |
lgpCondId4141BypassBreakerClosedThe bypass breaker is closed. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4141 |
lgpCondId4142BypassStaticSwitchOverloadBypass off due to static switch overload. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4142 |
lgpCondId4143BypassStaticSwitchUnavailableThe static bypass is unavailable to support the critical load. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4143 |
lgpCondId4144BypassExcessivePulseParallelThe system has performed too many pulse parallel operations within a specified time interval. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4144 |
lgpCondId4145BypassAutoTransferFailedAn automatic transfer to static bypass failed. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4145 |
lgpCondId4146SystemInputPhsRotationErrorThe power conductors on the input line are not wired to the UPS in the sequence preferred for the rectifier (A-B-C). OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4146 |
lgpCondId4147SystemInputCurrentLimitThe RMS input current has reached the input current limit threshold. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4147 |
lgpCondId4162BatteryLowThe calculated battery time remaining has reached the low battery threshold. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4162 |
lgpCondId4163OutputOffEndofDischargeOutput turned off due to battery reaching end-of-discharge. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4163 |
lgpCondId4164BatteryChargingErrorThe battery is not charging properly. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4164 |
lgpCondId4165BatteryChargingReducedExtrnlUsing a reduced battery charging algorithm due to an external signal. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4165 |
lgpCondId4166BatteryCapacityLowBattery capacity is low. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4166 |
lgpCondId4167OutputOffOutput is off. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4167 |
lgpCondId4168BatteryDischargingThe battery is discharging. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4168 |
lgpCondId4169BatteryTemperatureImbalanceExcessive temperature differences between battery sensors detected. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4169 |
lgpCondId4170BatteryEqualizeThe rectifier output voltage is increased to equalize the battery voltage level. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4170 |
lgpCondId4171BatteryManualTestInProgressManual battery test is in progress. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4171 |
lgpCondId4172BatteryAutoTestInProgressAutomatic battery test is in progress. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4172 |
lgpCondId4173MainBatteryDisconnectOpenMain battery disconnect is open. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4173 |
lgpCondId4174BatteryTemperatureSensorFaultA battery temperature sensor fault has been detected. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4174 |
lgpCondId4175BypassFrequencyErrorThe bypass frequency is outside the inverter synchronization limits. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4175 |
lgpCondId4176BatteryCircuitBreaker1OpenBattery circuit breaker 1 is open. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4176 |
lgpCondId4177BatteryBreaker1OpenFailureBattery circuit breaker 1 failed to open. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4177 |
lgpCondId4178BatteryBreaker1CloseFailureBattery circuit breaker 1 failed to close. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4178 |
lgpCondId4179BatteryCircuitBreaker2OpenBattery circuit breaker 2 is open. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4179 |
lgpCondId4180BatteryBreaker2OpenFailureBattery circuit breaker 2 failed to open. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4180 |
lgpCondId4181BatteryBreaker2CloseFailureBattery circuit breaker 2 failed to close. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4181 |
lgpCondId4182BatteryCircuitBreaker3OpenBattery circuit breaker 3 is open. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4182 |
lgpCondId4183BatteryBreaker3OpenFailureBattery circuit breaker 3 failed to open. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4183 |
lgpCondId4184BatteryBreaker3CloseFailureBattery circuit breaker 3 failed to close. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4184 |
lgpCondId4185BatteryCircuitBreaker4OpenBattery circuit breaker 4 is open. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4185 |
lgpCondId4186BatteryBreaker4OpenFailureBattery circuit breaker 4 failed to open. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4186 |
lgpCondId4187BatteryBreaker4CloseFailureBattery circuit breaker 4 failed to close. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4187 |
lgpCondId4188BatteryCircuitBreaker5OpenBattery circuit breaker 5 is open. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4188 |
lgpCondId4189BatteryBreaker5OpenFailureBattery circuit breaker 5 failed to open. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4189 |
lgpCondId4190BatteryBreaker5CloseFailureBattery circuit breaker 5 failed to close. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4190 |
lgpCondId4191BatteryCircuitBreaker6OpenBattery circuit breaker 6 is open. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4191 |
lgpCondId4192BatteryBreaker6OpenFailureBattery circuit breaker 6 failed to open. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4192 |
lgpCondId4193BatteryBreaker6CloseFailureBattery circuit breaker 6 failed to close. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4193 |
lgpCondId4194BatteryCircuitBreaker7OpenBattery circuit breaker 7 is open. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4194 |
lgpCondId4195BatteryBreaker7OpenFailureBattery circuit breaker 7 failed to open. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4195 |
lgpCondId4196BatteryBreaker7CloseFailureBattery circuit breaker 7 failed to close. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4196 |
lgpCondId4197BatteryCircuitBreaker8OpenBattery circuit breaker 8 is open. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4197 |
lgpCondId4198BatteryBreaker8OpenFailureBattery circuit breaker 8 failed to open. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4198 |
lgpCondId4199BatteryBreaker8CloseFailureBattery circuit breaker 8 failed to close. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4199 |
lgpCondId4200BatteryChargingInhibitedBattery charging is inhibited due to an external inhibit signal. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4200 |
lgpCondId4213SystemShutdownEPOSystem shutdown due to Emergency Power Off (EPO). OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4213 |
lgpCondId4214SystemShutdownREPOSystem shutdown due to Remote Emergency Power Off (REPO). OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4214 |
lgpCondId4215SystemOutputOffThe system output is off. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4215 |
lgpCondId4216BypassBackfeedDetectedThe system detected a voltage on the bypass when none was expected. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4216 |
lgpCondId4217BypassManualXfrInhibitedManual transfer from inverter to bypass is inhibited - bypass not qualified. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4217 |
lgpCondId4218BypassManualRexfrInhibitedManual transfer from bypass to inverter is inhibited - inverter output not qualified. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4218 |
lgpCondId4219BatteryOverTemperatureA battery temperature sensor is reporting a value above a threshold. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4219 |
lgpCondId4220BatteryExternalMonitor1External battery monitor 1 - battery maintenance required. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4220 |
lgpCondId4221BatteryExternalMonitor2External battery monitor 2 - battery maintenance required. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4221 |
lgpCondId4222BatteryGroundFaultBattery system ground fault amperage exceeds the threshold. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4222 |
lgpCondId4229EmergencyPowerOffLatchedSystem output is off - 'Emergency Power Off (EPO) - latched' requires manual reset. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4229 |
lgpCondId4230SystemOutputLowPowerFactorThe system output power factor is low, resulting in reduced output capacity. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4230 |
lgpCondId4231OutputCurrentExceedsThresholdOutput current for one or more phases exceeds a threshold. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4231 |
lgpCondId4233InverterFailureInverter failure - inverter output is off. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4233 |
lgpCondId4234InverterOverloadPhaseAInverter is operating with an overload on phase A. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4234 |
lgpCondId4235InverterOverloadPhaseBInverter is operating with an overload on phase B. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4235 |
lgpCondId4236InverterOverloadPhaseCInverter is operating with an overload on phase C. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4236 |
lgpCondId4237InverterInhibitExternalRestart of the inverter is inhibited by an external signal. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4237 |
lgpCondId4238InverterOutBreakerOpenFailInverter output breaker failed to open. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4238 |
lgpCondId4239InverterOutBreakerCloseFailInverter output breaker failed to close. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4239 |
lgpCondId4270InputContact01The external input contact 1. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4270 |
lgpCondId4271InputContact02The external input contact 2. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4271 |
lgpCondId4272InputContact03The external input contact 3. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4272 |
lgpCondId4273InputContact04The external input contact 4. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4273 |
lgpCondId4274InputContact05The external input contact 5. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4274 |
lgpCondId4275InputContact06The external input contact 6. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4275 |
lgpCondId4276InputContact07The external input contact 7. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4276 |
lgpCondId4277InputContact08The external input contact 8. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4277 |
lgpCondId4278InputContact09The external input contact 9. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4278 |
lgpCondId4279InputContact10The external input contact 10. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4279 |
lgpCondId4280InputContact11The external input contact 11. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4280 |
lgpCondId4281InputContact12The external input contact 12. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4281 |
lgpCondId4282InputContact13The external input contact 13. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4282 |
lgpCondId4283InputContact14The external input contact 14. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4283 |
lgpCondId4284InputContact15The external input contact 15. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4284 |
lgpCondId4285InputContact16The external input contact 16. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4285 |
lgpCondId4286OutputAmpOverUserLimitPhsAThe phase A output has exceeded the user amperage threshold. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4286 |
lgpCondId4287OutputAmpOverUserLimitPhsBThe phase B output has exceeded the user amperage threshold. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4287 |
lgpCondId4288OutputAmpOverUserLimitPhsCThe phase C output has exceeded the user amperage threshold. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4288 |
lgpCondId4289InverterTransferInhibitExtTransfer of critical bus source to inverter is inhibited by an external signal. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4289 |
lgpCondId4290InverterShutdownOverloadThe inverter has shutdown due to a sustained overload. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4290 |
lgpCondId4294InletAirOverTemperatureThe inlet air exceeds the maximum temperature threshold. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4294 |
lgpCondId4295RectifierFailureRectifier failure - rectifier is off. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4295 |
lgpCondId4296RectifierOperationInhibitExtThe operation of the rectifier is inhibited by an external signal. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4296 |
lgpCondId4297UPSOutputonInverterThe output power is supplied by the inverter. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4297 |
lgpCondId4298UPSOutputonBypassThe output power is supplied by the bypass. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4298 |
lgpCondId4299OutputLoadonMaintBypassThe output power is supplied by the maintenance bypass. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4299 |
lgpCondId4300InternalCommunicationsFailureThe control has detected a communication failure of a component on the internal communication bus. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4300 |
lgpCondId4308DCBusGroundFaultPositiveA ground fault has been detected on the positive DC Bus link. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4308 |
lgpCondId4309DCBusGroundFaultNegativeA ground fault has been detected on the negative DC Bus link. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4309 |
lgpCondId4310EquipmentOverTemperatureEquipment over temperature summary event. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4310 |
lgpCondId4311SystemFanFailureSystem fan failure - one or more fans have failed. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4311 |
lgpCondId4313PasswordChangedPassword changed. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4313 |
lgpCondId4314PowerSupplyFailurePower supply failure. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4314 |
lgpCondId4315OnGeneratorA generator is supplying the power to the system. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4315 |
lgpCondId4316AutoRestartInProgressAuto restart is in progress. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4316 |
lgpCondId4317AutoRestartInhibitedExtAuto restart inhibited due to an external signal. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4317 |
lgpCondId4320InitiatedTransfertoBypassUser initiated manual transfer to bypass. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4320 |
lgpCondId4321InitiatedTransfertoInverterUser initiated manual transfer to inverter. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4321 |
lgpCondId4322BatteryTestPassedBattery test passed. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4322 |
lgpCondId4323BatteryTestFailedBattery test failed. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4323 |
lgpCondId4324BatteryTestManuallyStoppedThe battery test was manually stopped prior to completion. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4324 |
lgpCondId4325BackfeedBreakerOpenThe backfeed breaker is in the open position. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4325 |
lgpCondId4341VelocityAuthenticationFailureNotification of a message rejected by Velocity due to an authentication failure. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4341 |
lgpCondId4360ReceptacleOverCurrentThe system has detected a receptacle over current condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4360 |
lgpCondId4361ReceptacleUnderCurrentThe system has detected a receptacle under current condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4361 |
lgpCondId4382SystemInputCurrentImbalanceSystem Input Currents are Imbalanced. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4382 |
lgpCondId4383BypassStaticSwitchOffExtrnlBypass static switch is off due to the state of an external signal. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4383 |
lgpCondId4384BatteryEoDDisconnectBattery disconnect due to end-of-discharge. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4384 |
lgpCondId4389SystemOutputFaultA fault has been detected in the system output. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4389 |
lgpCondId4390InverterOffExternalInverter is off (operation is inhibited) due to external signal state. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4390 |
lgpCondId4391InverterStaticSwitchSCRShortThe system has detected a short across one or more inverter static switch Silicon Controlled Rectifiers (SCR). OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4391 |
lgpCondId4392TemperatureSensorErrorOne or more temperature sensors cannot provide a valid temperature reading (i.e. sensor failure, wiring failure, sense circuit failure, etc). OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4392 |
lgpCondId4406BranchOverCurrentThe system has detected a module over current condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4406 |
lgpCondId4407BranchUnderCurrentThe system has detected a module under current condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4407 |
lgpCondId4416BranchOverCurrentThe system has detected a module over current condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4416 |
lgpCondId4417BranchUnderCurrentThe system has detected a module under current condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4417 |
lgpCondId4421BranchFailureOne or more conditions indicate a Branch Receptacle Module failure , service is required. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4421 |
lgpCondId4436PDUOverCurrentThe system has detected a module over current condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4436 |
lgpCondId4437PDUUnderCurrentThe system has detected a module under current condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4437 |
lgpCondId4438SystemInternalTemperatureRiseExcessive temperature rise internal to the system (i.e. difference between the output versus input temperature is too large). OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4438 |
lgpCondId4439AutomaticRestartFailedAutomatic restart failed. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4439 |
lgpCondId4440FuseFailureA summary event indicating one or more fuse failures. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4440 |
lgpCondId4441SystemControllerErrorSystem controller internal error. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4441 |
lgpCondId4442SystemBreakersOpenFailureOne or more breakers in the system failed to open. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4442 |
lgpCondId4448PDUOverCurrentThe system has detected a module over current condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4448 |
lgpCondId4449PDUUnderCurrentThe system has detected a module under current condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4449 |
lgpCondId4468PDUOverCurrentL1The system has detected a module over current condition on line 1. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4468 |
lgpCondId4469PDUOverCurrentL2The system has detected a module over current condition on line 2. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4469 |
lgpCondId4470PDUOverCurrentL3The system has detected a module over current condition on line 3. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4470 |
lgpCondId4471PDUUnderCurrentL1The system has detected a module under current condition on line 1. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4471 |
lgpCondId4472PDUUnderCurrentL2The system has detected a module under current condition on line 2. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4472 |
lgpCondId4473PDUUnderCurrentL3The system has detected a module under current condition on line 3. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4473 |
lgpCondId4492ReceptaclePowerStateOnThe receptacle power state changed to the ON state. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4492 |
lgpCondId4493ReceptaclePowerStateOffThe receptacle power state changed to the OFF state. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4493 |
lgpCondId4494BranchBreakerOpenThe Branch Receptacle Module's input breaker is open. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4494 |
lgpCondId4495DeviceConfigurationChangeDevice Configuration Change. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4495 |
lgpCondId4496BasicDisplayModuleRemovedBasic Display Module Removed. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4496 |
lgpCondId4497BasicDisplayModuleDiscoveredBasic Display Module Discovered. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4497 |
lgpCondId4500PDUOverCurrentThe system has detected a power module over current condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4500 |
lgpCondId4501PDUUnderCurrentThe system has detected a power module under current condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4501 |
lgpCondId4502PDUFailureOne or more conditions indicate a power module failure, service is required. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4502 |
lgpCondId4503PDUCommunicationFailInternal communications failure with the Power Module. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4503 |
lgpCondId4504BranchRemovedBranch Receptacle Module Removed. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4504 |
lgpCondId4505BranchDiscoveredBranch Receptacle Module Discovered. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4505 |
lgpCondId4506BranchOverCurrentThe system has detected a Branch Receptacle Module over current condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4506 |
lgpCondId4507BranchCurrentThe system has detected a Branch Receptacle Module under current condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4507 |
lgpCondId4508ReceptacleLoadRemovedThe receptacle's load stopped drawing power. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4508 |
lgpCondId4509ReceptacleLoadAddedThe receptacle's load started to draw power. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4509 |
lgpCondId4523ModuleRemovedModule Removed. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4523 |
lgpCondId4524ModuleAddedModule Added. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4524 |
lgpCondId4550FirmwareUpdateRequiredModule compatibility error requires a system firmware update to resolve. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4550 |
lgpCondId4551GenericTestEventA generic test event designed to evaluate system handling of events. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4551 |
lgpCondId4580OverTemperatureAn over temperature condition was detected. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4580 |
lgpCondId4581UnderTemperatureAn under temperature condition was detected. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4581 |
lgpCondId4588OverRelativeHumidityAn over relative humidity condition was detected. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4588 |
lgpCondId4589UnderRelativeHumidityAn under relative humidity condition was detected. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4589 |
lgpCondId4601ExternalAirSensorAOverTemperature[Ext Air Sensor A Temperature] has exceeded [External Air Over Temp Threshold]. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4601 |
lgpCondId4604ExternalAirSensorBOverTemperature[Ext Air Sensor B Temperature] has exceeded [External Air Over Temp Threshold]. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4604 |
lgpCondId4608ExtAirSensorAUnderTemperature[Ext Air Sensor A Temperature] has dropped below [Ext Air Under Temp Threshold]. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4608 |
lgpCondId4611ExtAirSensorBUnderTemperature[Ext Air Sensor B Temperature] has dropped below [Ext Air Under Temp Threshold]. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4611 |
lgpCondId4615ExtDewPointOverTemperatureAt least one dew point temperature reading ([Ext Air Sensor A Dew Point Temp], [Ext Air Sensor B Dew Point Temp]...) has exceeded [Ext Dew Point Over Temp Threshold]. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4615 |
lgpCondId4618ExternalAirSensorAIssueThe external air sensor A is disconnected or the signal is out of range. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4618 |
lgpCondId4621ExternalAirSensorBIssueThe external air sensor B is disconnected or the signal is out of range. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4621 |
lgpCondId4626SupplyChilledWaterOverTemp[Supply Fluid Temperature] has exceeded [High Supply Fluid Temperature Threshold]. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4626 |
lgpCondId4629SupplyChilledWaterTempSensorIssueThe supply chilled water temperature sensor is disconnected or the signal is out of range. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4629 |
lgpCondId4634SupplyRefrigerantOverTempEvent that is activated when [Supply Refrigerant Temperature] exceeds [Supply Refrig Over Temp Threshold]. The event is deactivated when the temperature drops below the threshold. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4634 |
lgpCondId4637SupplyRefrigerantUnderTemp[Supply Refrigerant Temperature] has dropped below a specified threshold. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4637 |
lgpCondId4640SupplyRefrigerantTempSensorIssueThe supply refrigeramt temperature sensor is disconnected or the signal is out of range. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4640 |
lgpCondId4645SupplyFluidOverTemp[Supply Fluid Temperature] has exceeded [Supply Fluid Over Temp Threshold]. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4645 |
lgpCondId4648SupplyFluidUnderTemp[Supply Fluid Temperature] has dropped below a specified threshold. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4648 |
lgpCondId4651SupplyFluidTempSensorIssueThe supply fluid temperature sensor is disconnected or the signal is out of range. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4651 |
lgpCondId4656Pump1LossofFlowLoss of flow is detected in pump 1. The loss of flow condition occurs when no differential pressure is detected across the pump. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4656 |
lgpCondId4659Pump2LossofFlowLoss of flow is detected in pump 2. The loss of flow condition occurs when no differential pressure is detected across the pump. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4659 |
lgpCondId4662PumpShortCyclePumps have short cycled. A short cycle is defined as turning on and off a number of times over a set time period. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4662 |
lgpCondId4669Compressor1AHighHeadPressureCompressor 1A high head pressure. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4669 |
lgpCondId4672Compressor1BHighHeadPressureCompressor 1B high head pressure. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4672 |
lgpCondId4675Compressor2AHighHeadPressureCompressor 2A high head pressure. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4675 |
lgpCondId4678Compressor2BHighHeadPressureCompressor 2B high head pressure. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4678 |
lgpCondId4681Compressor1AShortCycleCompressor 1A short cycle. A short cycle is defined as turning on and off a number of times over a set time period. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4681 |
lgpCondId4684Compressor1BShortCycleCompressor 1B short cycle. A short cycle is defined as turning on and off a number of times over a set time period. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4684 |
lgpCondId4687Compressor2AShortCycleCompressor 2A short cycle. A short cycle is defined as turning on and off a number of times over a set time period. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4687 |
lgpCondId4690Compressor2BShortCycleCompressor 2B short cycle. A short cycle is defined as turning on and off a number of times over a set time period. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4690 |
lgpCondId4693Tandem1LowSuctionPressure'Tandem compressors' 1 low suction pressure. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4693 |
lgpCondId4696Tandem2LowSuctionPressure'Tandem compressors' 2 low suction pressure. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4696 |
lgpCondId4703ChilledWaterControlValvePositionChilled water valve out of position. Chilled water control valve position does not match expected value. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4703 |
lgpCondId4711SystemCondensationDetectedSystem condensation detected. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4711 |
lgpCondId4714ShutdownLossOfPowerSystem lost power. This event becomes active when the unit is powered on following an unexpected loss of power. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4714 |
lgpCondId4720SmokeDetectedSmoke detected. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4720 |
lgpCondId4723WaterUnderFloorWater under the floor is detected. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4723 |
lgpCondId4726ServiceRequiredUnit requires servicing. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4726 |
lgpCondId4729FanIssueOne or more fans are not operating within their operational parameters. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4729 |
lgpCondId4732ReceptacleLoadDroppedThe receptacle's load is not drawing power. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4732 |
lgpCondId4740BatteryAutomaticTestInhibitedAutomatic (scheduled) battery tests are inhibited. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4740 |
lgpCondId4741BatterySelfTestBattery self test is in progress. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4741 |
lgpCondId4742BatteryLowShutdownBattery disconnect due to end-of-discharge. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4742 |
lgpCondId4747EquipmentTemperatureSensorFailOne or more temperature sensors report a temperature outside of the range of expected operation. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4747 |
lgpCondId4749SystemFanFailureRedundantRedundant system fan failure. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4749 |
lgpCondId4750MultipleFanFailureMultiple fan failure. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4750 |
lgpCondId4753MainControllerFaultA Main Controller fault has been detected. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4753 |
lgpCondId4754SystemBreakersCloseFailureOne or more breakers in the system failed to close. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4754 |
lgpCondId4755InputFilterCycleLockThe input filter disconnect is open due to exceeding the maximum number of cycles. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4755 |
lgpCondId4756ServiceCodeActiveService code is running. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4756 |
lgpCondId4757LBSActiveThe Load Bus Sync option is active. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4757 |
lgpCondId4758LBSInhibitedThe system has detected that conditions to perform Load Bus Sync are not satisfied. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4758 |
lgpCondId4759LeadingPowerFactorThe leading output Power Factor has fallen below a specified value. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4759 |
lgpCondId4760ControlsResetRequiredA controls reset is required due to one or more critical settings changing. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4760 |
lgpCondId4823ParallelCommWarningParallel communication bus warning. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4823 |
lgpCondId4824SystemCommFailFailure of a device on the multi-module system communication bus. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4824 |
lgpCondId4825LossofRedundancyThe multi-module collection doesn't have enough modules to satisfy the redundancy configuration. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4825 |
lgpCondId4826BPSSStartupInhibitThe Bypass Static Switch startup is inhibited. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4826 |
lgpCondId4827MMSTransferInhibitThe critical load can not be manually transferred from inverter to bypass. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4827 |
lgpCondId4828MMSRetransferInhibitThe critical load can not be manually retransferred from bypass to inverter. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4828 |
lgpCondId4830MMSLossofSyncPulseMulti-module system loss of sync pulse. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4830 |
lgpCondId4831MMSOverloadMulti-module system overload. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4831 |
lgpCondId4834MMSOnBatteryThe multi-module system is on battery. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4834 |
lgpCondId4835MMSLowBatteryWarningMulti-module system low battery warning. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4835 |
lgpCondId4906LowAmbientTemperatureThe system has detected a low ambient temperature condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4906 |
lgpCondId4907HighAmbientTemperatureThe system has detected a high ambient temperature condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4907 |
lgpCondId4908LowOverallVoltageThe system has detected a low battery string overall voltage condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4908 |
lgpCondId4909HighOverallVoltageThe system has detected a high battery string overall voltage condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4909 |
lgpCondId4910HighBatteryStringCurrentThe system has detected a high battery string current condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4910 |
lgpCondId4911LowBatteryStringFloatCurrentThe system has detected a low battery string float current condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4911 |
lgpCondId4912HighBatteryStringFloatCurrentThe system has detected a high battery string float current condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4912 |
lgpCondId4913HighBatteryStringRippleCurrentThe system has detected a high battery string ripple current condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4913 |
lgpCondId4914BatteryStringDischargeDetectedThe system has detected a battery string discharge condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4914 |
lgpCondId4915MaximumDischargeTimeExceededThe system has detected an excessive discharge time condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4915 |
lgpCondId4916DischargeLowOverallVoltageThe system has detected a low battery string overall voltage condition during a discharge. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4916 |
lgpCondId4917DischargeLowCellVoltageThe system has detected a low cell voltage condition during a discharge. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4917 |
lgpCondId4918DischargeHighBatteryStringCurrentThe system has detected a high battery string current condition during a discharge. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4918 |
lgpCondId4919ExcessiveCelltoCellTemperatureDeviationThe system has detected an excessive cell to cell temperature deviation condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4919 |
lgpCondId4920ExcessiveCelltoAmbientTemperatureDeviationThe system has detected an excessive cell to ambient temperature deviation condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4920 |
lgpCondId4964LowCellVoltageThe system has detected a low cell voltage condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4964 |
lgpCondId4965HighCellVoltageThe system has detected a high cell voltage condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4965 |
lgpCondId4966LowCellTemperatureThe system has detected a low cell temperature condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4966 |
lgpCondId4967HighCellTemperatureThe system has detected a high cell temperature condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4967 |
lgpCondId4968LowInternalResistanceThe system has detected a low internal resistance condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4968 |
lgpCondId4969HighInternalResistanceThe system has detected a high internal resistance condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4969 |
lgpCondId4970HighIntercellResistanceThe system has detected a high intercell resistance condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4970 |
lgpCondId4978IntertierResistanceHighThe system has detected a high intertier resistance condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4978 |
lgpCondId4980SupplyChilledWaterLossofFlowSupply chilled water or glycol flow is too low. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4980 |
lgpCondId4983SupplyRefrigOverTempBand1[Supply Refrigerant Temperature] is above the upper threshold specified by [Supply Refrig Temp Band 1]. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4983 |
lgpCondId4986SupplyRefrigUnderTempBand1[Supply Refrigerant Temperature] is below the lower threshold specified by [Supply Refrig Temp Band 1]. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4986 |
lgpCondId4990SupplyRefrigOverTempBand2[Supply Refrigerant Temperature] is above the upper threshold specified by [Supply Refrig Temp Band 2]. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4990 |
lgpCondId4993SupplyRefrigUnderTempBand2[Supply Refrigerant Temperature] is below the lower threshold specified by [Supply Refrig Temp Band 2]. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4993 |
lgpCondId4996Inverter1ShortCycleInverter for pump 1 has short cycled and is temporarily locked out from further operation to protect from thermal overload. A short cycle is defined as powering on and off a number of times over a set time period. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4996 |
lgpCondId4999Inverter2ShortCycleInverter for pump 2 has short cycled and is temporarily locked out from further operation to protect from thermal overload. A short cycle is defined as powering on and off a number of times over a set time period. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.4999 |
lgpCondId5015SupplyAirOverTemperature[Supply Air Temperature] has exceeded [High Supply Air Temperature Threshold]. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5015 |
lgpCondId5019SupplyAirUnderTemperature[Supply Air Temperature] has dropped below [Low Supply Air Temperature Threshold]. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5019 |
lgpCondId5023ReturnAirOverTemperature[Return Air Temperature] has exceeded [High Return Air Temperature Threshold]. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5023 |
lgpCondId5026SupplyAirSensorIssueThe air sensor at the outlet of the unit is disconnected or the signal is out of range. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5026 |
lgpCondId5034HighReturnHumidity[Return Humidity] has exceeded [High Return Humidity Threshold]. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5034 |
lgpCondId5036LowReturnHumidity[Return Humidity] has dropped below [Low Return Humidity Threshold]. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5036 |
lgpCondId5037HumidifierHoursExceededOperating hours for the humidifier have exceeded the threshold. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5037 |
lgpCondId5038DehumidifierHoursExceededOperating hours for the dehumidifier have exceeded the threshold. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5038 |
lgpCondId5039HumidifierUnderCurrentThe electrical current to the humidifier has dropped below its lower threshold. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5039 |
lgpCondId5040HumidifierOverCurrentThe electrical current to the humidifier has exceeded its upper threshold. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5040 |
lgpCondId5041HumidifierLowWaterThe water level in the humidifier has dropped below its threshold. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5041 |
lgpCondId5042HumidifierCylinderWornHumidifier cylinder is not operating properly and needs to be replaced. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5042 |
lgpCondId5043HumidifierIssueHumidifier issue detected, causing it to be locked out. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5043 |
lgpCondId5044ExtHumidifierLockoutThe humidifier is shut down and disabled by an external input signal. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5044 |
lgpCondId5045HumidifierControlBoardNotDetectedHumidifier control board is required to be connected, but no signal is detected. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5045 |
lgpCondId5046ReturnHumidityOutOfProportionalBand[Return Humidity] has exceeded the upper limit of [Dehumidification Proportional Band], or has dropped below the lower limit of [Humidification Proportional Band] ], for an extended period of time. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5046 |
lgpCondId5053LossofAirFlowNo air flow through the unit due to failure of all fans. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5053 |
lgpCondId5054FanHoursExceededOperating hours for the unit blower fan have exceeded the threshold. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5054 |
lgpCondId5055TopFanIssueThe top fan is not operating within its normal parameters. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5055 |
lgpCondId5056BottomFanIssueThe bottom fan is not operating within its normal parameters. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5056 |
lgpCondId5060RemoteSensorIssueRemote sensor is disconnected or the signal is out of range. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5060 |
lgpCondId5062Compressor1LowSuctionPressureCompressor 1 low suction pressure. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5062 |
lgpCondId5063Compressor1HoursExceededOperating hours for compressor 1 have exceeded the threshold. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5063 |
lgpCondId5064DigScrollComp1TempSensorIssueDigital scroll compressor 1 temperature sensor is disconnected or the signal is out of range. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5064 |
lgpCondId5065DigScrollComp1OverTempDigital scroll compressor 1 shut off because its head temperature has exceeded the upper threshold. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5065 |
lgpCondId5066Compressor1LowPressureTransducerIssueCompressor 1 low pressure transducer is disconnected or the signal is out of range. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5066 |
lgpCondId5067ExtCompressorLockoutThe compressor is shut down and disabled by an external input signal. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5067 |
lgpCondId5068ReheaterOverTemperatureThe temperature of the reheater has exceeded its threshold. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5068 |
lgpCondId5069ElectricReheater1HoursExceededOperating hours for electric reheater 1 have exceeded the threshold. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5069 |
lgpCondId5070ExtReheatLockoutThe reheater is shut down and disabled by an external input signal. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5070 |
lgpCondId5071Condenser1IssueCondenser 1 is not operating within its normal parameters. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5071 |
lgpCondId5072CondenserVFDIssueThe condenser fan Variable Frequency Drive is offline. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5072 |
lgpCondId5073CondenserTVSSIssueThe condenser Transient Voltage Surge Suppressor or Surge Protection Device has failed. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5073 |
lgpCondId5104ExtOverTemperatureA temperature has exceeded its threshold, as indicated by an external input signal. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5104 |
lgpCondId5105ExtLossofFlowLoss of flow is detected, as indicated by an external input signal. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5105 |
lgpCondId5106ExtCondenserPumpHighWaterHigh water is detected in the condensate pump by the auxiliary float, as indicated by an external input signal. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5106 |
lgpCondId5107ExtStandbyGlycolPumpOnThe standby glycol pump is on, as indicated by an external input signal. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5107 |
lgpCondId5108ExternalFireDetectedFire detected, as indicated by an external input signal. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5108 |
lgpCondId5109UnitOnUnit was turned on. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5109 |
lgpCondId5110UnitOffUnit was turned off. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5110 |
lgpCondId5111UnitStandbyUnit was placed in standby mode. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5111 |
lgpCondId5112UnitPartialShutdownAn event has occurred requiring some system components to be shutdown and disabled. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5112 |
lgpCondId5113UnitShutdownAn event has occurred requiring the unit to be shutdown and disabled to prevent damage to the system. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5113 |
lgpCondId5114WaterLeakageDetectorSensorIssueThe water leakage detector sensor is disconnected or the signal is out of range. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5114 |
lgpCondId5115BMSCommunicationsTimeoutBuilding Management System (or external monitoring system) has not communicated with the system within the expected timeframe. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5115 |
lgpCondId5116MaintenanceDueThe calculated maintenance date has been reached. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5116 |
lgpCondId5117MaintenanceCompletedMaintenance has been completed on the unit. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5117 |
lgpCondId5118CloggedAirFilterAir filter is dirty and needs to be (cleaned or) replaced. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5118 |
lgpCondId5119RAMBatteryIssueRAM or RAM backup battery is not operating correctly. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5119 |
lgpCondId5120MasterUnitCommunicationLostCommunication with master unit has been lost. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5120 |
lgpCondId5121HighPowerShutdownSupply to high power components has been shutdown. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5121 |
lgpCondId5126DigScrollComp2OverTempDigital scroll compressor 2 shut off because its head temperature has exceeded the upper threshold. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5126 |
lgpCondId5144OutputOfUfThe output frequency has exceeded a specified range for a specified period of time. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5144 |
lgpCondId5145MMSModuleAlarmActiveActive alarm or fault of any module in a multi-module system. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5145 |
lgpCondId5146CompressorPumpDownIssueUnable to pump down suction-side pressure during compressor shutdown. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5146 |
lgpCondId5147ReturnAirSensorIssueThe air sensor at the inlet of the unit is disconnected or the signal is out of range. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5147 |
lgpCondId5148CompressorHighPressureTransducerIssueCompressor high pressure transducer is disconnected or the signal is out of range. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5148 |
lgpCondId5149BatteryNotQualifiedThe UPS battery voltage is not qualified. This event will be detected even in the absence of battery disconnect or when it is open. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5149 |
lgpCondId5150BatteryTerminalsReversedThe measured battery voltage is a negative value due to reverse battery terminal connections. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5150 |
lgpCondId5151BatteryConverterFailureBattery converter failure. This is a summary event caused by one or more power sub-modules in a UPS module. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5151 |
lgpCondId5152InverterSCROpenThe system has detected an open across one or more inverter static switch Silicon Controlled Rectifiers. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5152 |
lgpCondId5153LoadSharingFaultDifference between any phase inverter current of unit and the relevant average output current of parallel system is more than a specific percent of nominal current. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5153 |
lgpCondId5154DCBusAbnormalThe system has detected an abnormal DC Bus Voltage. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5154 |
lgpCondId5155MainsInputNeutralLostLoss of neutral in the input source is detected. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5155 |
lgpCondId5156LoadImpactTransferOn bypass as result of load impact. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5156 |
lgpCondId5157UserOperationInvalidUser attempted an invalid operation. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5157 |
lgpCondId5158PowerSubModuleFaultOne or more failures detected in power module, inverter or rectifier. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5158 |
lgpCondId5178OutputOvervoltageOne or more of the output phase voltages has exceeded the limit. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5178 |
lgpCondId5179OutputUndervoltageOne or more of the output phase voltages has dropped below the limit. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5179 |
lgpCondId5180OutputOvercurrentOne or more of the phase currents has exceeded the limit. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5180 |
lgpCondId5181NeutralOvercurrentThe system's neutral current has exceeded the limit. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5181 |
lgpCondId5182GroundOvercurrentSystem ground current has exceeded the limit. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5182 |
lgpCondId5183OutputVoltageTHDThe Total Harmonic Distortion of the voltage on one or more of the output phases has exceeded the limit. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5183 |
lgpCondId5184OutputFrequencyErrorThe output frequency is outside a specified range. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5184 |
lgpCondId5185TransformerOvertemperatureIndicates a unit transformer overtemperature condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5185 |
lgpCondId5212PanelSummaryStatusThe status for the panel. Detects and annunciates upon occurrence of any branch or panelboard main breaker active event. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5212 |
lgpCondId5213PanelOvervoltageOne or more of the phase voltages of this panel has exceeded the limit. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5213 |
lgpCondId5214PanelUndervoltageOne or more of the phase voltages of this panel is less than the limit. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5214 |
lgpCondId5215PanelOvercurrentOne or more of the phase currents of this panel has exceeded the limit. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5215 |
lgpCondId5216PanelNeutralOvercurrentThe Neutral current of this panel has exceeded the limit. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5216 |
lgpCondId5217PanelGroundOvercurrentThe Ground current of this panel has exceeded the limit. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5217 |
lgpCondId5226BranchOvercurrentThe current in one or more phases of this branch exceeds the limit. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5226 |
lgpCondId5227BranchUndercurrentThe current in one or more phases of this branch is less than the limit. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5227 |
lgpCondId5245SubfeedPhaseOvercurrentOne or more of the phase currents in this subfeed has exceeded the limit. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5245 |
lgpCondId5246SubfeedNeutralOvercurrentThe Neutral current in this subfeed has exceeded the limit. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5246 |
lgpCondId5247SubfeedGroundOvercurrentThe Ground current of this subfeed has exceeded the limit. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5247 |
lgpCondId5249EventStateThe present state of this digital event input. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5249 |
lgpCondId5263CompressorNotStoppingCompressor commanded to stop, but continues to run. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5263 |
lgpCondId5269CompressorHoursExceeded[Compressor Hours] has exceeded [Compressor Hours Threshold]. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5269 |
lgpCondId5270CompressorHighHeadPressureCompressor is shut down due to high head pressure. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5270 |
lgpCondId5271CompressorLowSuctionPressureCompressor is shut down due to low suction pressure. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5271 |
lgpCondId5272CompressorThermalOverloadCompressor is shut down due to thermal overload. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5272 |
lgpCondId5273CompressorLowOilPressureCompressor low oil pressure. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5273 |
lgpCondId5274CompressorHeadPressureOverThresholdCompressor head pressure has exceeded an upper threshold. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5274 |
lgpCondId5275CompressorLossofDifferentialPressureCompressor is shut down due to low differential pressure. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5275 |
lgpCondId5277CondenserFanIssueCondenser fan is not operating within its operational parameters. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5277 |
lgpCondId5278LowCondenserRefrigerantPressureRefrigerant pressure in condenser coil is too low. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5278 |
lgpCondId5280LowFluidPressure[Fluid Pressure] has dropped below a specified threshold. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5280 |
lgpCondId5293ReturnFluidOverTemp[Return Fluid Temperature] has exceeded a specified threshold. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5293 |
lgpCondId5294ReturnFluidUnderTemp[Return Fluid Temperature] has dropped below a specified threshold. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5294 |
lgpCondId5295ReturnFluidTempSensorIssueThe return fluid temperature sensor is disconnected or the signal is out of range. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5295 |
lgpCondId5296TeamworkReturnFluidTempSensorIssueThe return fluid temperature sensors for all Teamwork units are disconnected or the signals are out of range. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5296 |
lgpCondId5297AllPumpsLossofFlowSystem is shut down due to loss of flow in all available pumps. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5297 |
lgpCondId5300PumpHoursExceeded[Pump Hours] has exceeded [Pump Hours Threshold]. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5300 |
lgpCondId5306FreeCoolingValveHoursExceeded[Free Cooling Valve Hours] has exceeded [Free Cooling Valve Hours Threshold]. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5306 |
lgpCondId5308EvaporatorInletTempSensorIssueThe evaporator inlet temperature sensor is disconnected or the signal is out of range. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5308 |
lgpCondId5309TeamworkEvaporatorInletTempSensorIssueThe evaporator inlet temperature sensors for all Teamwork units are disconnected or the signals are out of range. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5309 |
lgpCondId5310EvaporatorFluidFreezeAutoResetEvaporator outlet fluid temperature has dropped below the freeze threshold. Evaporator has been shut down, but will restart when the temperature rises above the threshold. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5310 |
lgpCondId5311EvaporatorFluidFreezeManualResetRequiredEvaporator outlet fluid temperature has dropped below the freeze threshold. Evaporator has been shut down and requires a manual reset. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5311 |
lgpCondId5315SubgroupEventOccurredDuringCommunicationLossWhile subgroup unit communication was lost, an event occurred on the subgroup unit. Please check subgroup unit event log. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5315 |
lgpCondId5335ReturnAirUnderTemperature[Return Air Temperature] has dropped below [Low Return Air Temperature Threshold]. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5335 |
lgpCondId5349ExtAirSensorAHighHumidity[Ext Air Sensor A Humidity] has exceeded [Ext Air Sensor A High Humidity Threshold]. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5349 |
lgpCondId5351ExtAirSensorALowHumidity[Ext Air Sensor A Humidity] has dropped below [Ext Air Sensor A Low Humidity Threshold]. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5351 |
lgpCondId5352CompressorShortCycleCompressor short cycle. A short cycle is defined as turning on and off a number of times over a set time period. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5352 |
lgpCondId5354DigScrollCompDischargeTempSensorIssueDigital scroll compressor discharge temperature sensor is disconnected or the signal is out of range. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5354 |
lgpCondId5355DigScrollCompOverTempDigital scroll compressor is shut down due to head temperature exceeding an upper threshold. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5355 |
lgpCondId5361ExtFreeCoolingLockoutFree cooling is disabled by an external input signal. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5361 |
lgpCondId5362FreeCoolingTempSensorIssueThe free cooling fluid temperature sensor is disconnected or the signal is out of range. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5362 |
lgpCondId5365HotWaterHotGasValveHoursExceeded[Hot Water / Hot Gas Valve Hours] has exceeded [Hot Water / Hot Gas Valve Hours Threshold]. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5365 |
lgpCondId5368ElectricReheaterHoursExceeded[Electric Reheater Hours] has exceeded [Electric Reheaters Hours Threshold]. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5368 |
lgpCondId5376MainFanOverloadMain fan is shut down due to thermal overload. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5376 |
lgpCondId5377CondenserCondenser is not operating within its operational parameters. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5377 |
lgpCondId5415ExtLossofAirBlowerLoss of air blower is detected, as indicated by an external input signal. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5415 |
lgpCondId5416ExtStandbyUnitOnStandby unit is on, as indicated by an external input signal. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5416 |
lgpCondId5417DigitalOutputBoardNotDetectedDigital output board is required to be connected, but no signal is detected. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5417 |
lgpCondId5418UnitCodeMissingUnit code has not been entered and saved. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5418 |
lgpCondId5419UnitCommunicationLostMaster has lost communication with one or more networked units. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5419 |
lgpCondId5422OvertemperaturePowerOffPower turned off because equipment over temperature limit. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5422 |
lgpCondId5423TooManySensorsThe number of sensors connected to the PDU exceeds the allowable limit. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5423 |
lgpCondId5432TransformerOvertemperaturePowerOffOutput power shutdown due to high transformer temperature. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5432 |
lgpCondId5433TransformerOvertemperatureTransformer temperature has exceeded the limit. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5433 |
lgpCondId5434TransformerTemperatureSensorFailTransformer temperature sensor has failed. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5434 |
lgpCondId5436LowAmbientTemperatureProbeTwoThe system has detected a low ambient temperature condition on temperature probe 2. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5436 |
lgpCondId5437HighAmbientTemperatureProbeTwoThe system has detected a high ambient temperature condition on temperature probe 2. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5437 |
lgpCondId5438ThermalRunawayDetectedThe system has detected a thermal runaway condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5438 |
lgpCondId5439BatteryStringEqualizeThe system has detected a battery string equalize condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5439 |
lgpCondId5440BatteryStringOfflineThe system has detected the battery string is offline. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5440 |
lgpCondId5442DischargeLowCellVoltageThe system has detected a low cell voltage condition during a discharge. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5442 |
lgpCondId5447MMSPowerSharingA module is not sharing power with the other modules in a multi -module system. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5447 |
lgpCondId5453ModuleInStandbyIntelligentParallelingModule is placed into standby operation per Intelligent Paralleling. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5453 |
lgpCondId5456ECOModeActiveConditions for Activation or Automatic Reactivation have been satisfied. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5456 |
lgpCondId5457ECOModeSuspendedECO Mode session is suspended. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5457 |
lgpCondId5458ExcessECOSuspendsNumber of automatic suspensions has exceeded the ECO Mode - Maximum Auto Suspensions setting. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5458 |
lgpCondId5471DoorOpenAn open door was detected. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5471 |
lgpCondId5472DoorSensorDisconnectedDoor sensor disconnect detected. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5472 |
lgpCondId5479ContactClosureOpenAn open circuit was detected. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5479 |
lgpCondId5480ContactClosureClosedA closed circuit was detected. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5480 |
lgpCondId5492ExtSystemCondensationDetectedExternal system condensation detected. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5492 |
lgpCondId5495ExtFanIssueOne or more fans are not operating within their operational parameters. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5495 |
lgpCondId5500ExtRemoteShutdownUnit is shut down by a remote signal. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5500 |
lgpCondId5505HotAisleTempOutofRangeThe air temperature in the Hot aisle is either above [Hot Aisle Over Temp Threshold] or below [Hot Aisle Under Temp Threshold]. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5505 |
lgpCondId5508ColdAisleTempOutofRangeThe air temperature in the cold aisle is either above [Cold Aisle Over Temp Threshold] or below [Cold Aisle Under Temp Threshold]. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5508 |
lgpCondId5512RemoteShutdownUnit is shut down by a remote signal. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5512 |
lgpCondId5513CompressorCapacityReducedCompressor capacity has been reduced. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5513 |
lgpCondId5514CompressorLowPressureTransducerIssueCompressor low pressure transducer is disconnected or the signal is out of range. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5514 |
lgpCondId5524PDUNeutralOverCurrentThe system has detected a neutral over current condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5524 |
lgpCondId5531CondenserCommunicationLostCommunication with condenser unit has been lost. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5531 |
lgpCondId5535CondenserOutsideAirTempSensorIssueCondenser outside air temperature sensor is disconnected or the signal is out of range. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5535 |
lgpCondId5536CondenserOutsideAirTempOutofOperatingRange[Condenser Outside Air Temperature] is either above an upper threshold or below a lower threshold. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5536 |
lgpCondId5537CondenserControlBoardIssueThe condenser control board is reporting an issue. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5537 |
lgpCondId5539CondenserRefrigerantPressureOverThresholdCondenser refrigerant pressure has exceeded a threshold. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5539 |
lgpCondId5540CondenserRefrigerantPressureUnderThresholdCondenser refrigerant pressure has dropped below a threshold. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5540 |
lgpCondId5541CondenserRefrigerantPressureSensorIssueCondenser refrigerant pressure sensor is disconnected or the signal is out of range. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5541 |
lgpCondId5542CondenserSupplyRefrigerantOverTempCondenser supply refrigerant temperature has exceeded a threshold. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5542 |
lgpCondId5543CondenserSupplyRefrigerantUnderTempCondenser supply refrigerant temperature has dropped below a specified threshold. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5543 |
lgpCondId5544CondenserSupplyRefrigerantTempSensorIssueCondenser supply refrigerant temperature sensor is disconnected or the signal is out of range. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5544 |
lgpCondId5545CondenserMaxFanSpeedOverrideFan speed exceeding the maximum set point in order to alleviate a high temperature or pressure condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5545 |
lgpCondId5559EvaporatorReturnFluidOverTemp[Evaporator Return Fluid Temperature] has exceeded a threshold. The event is deactivated when the temperature drops below the threshold. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5559 |
lgpCondId5560EvaporatorReturnFluidUnderTemp[Evaporator Return Fluid Temperature] has dropped below a threshold. The event is deactivated when the temperature rises above the threshold. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5560 |
lgpCondId5561LBSActiveMasterThis UPS system has been selected as the functional Master Load Bus Synchronization (LBS) system. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5561 |
lgpCondId5562LBSActiveSlaveThis UPS system is synchronized to the output bus of the UPS system that has been selected as the Master Load Bus Synchronization (LBS) system. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5562 |
lgpCondId5563DCBusLowFaultThe DC Bus voltage has reached a critical low level. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5563 |
lgpCondId5564FanContactorOpenThe fan contactor is open. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5564 |
lgpCondId5565FanContactorOpenFailThe fan contactor failed to open. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5565 |
lgpCondId5566FanContactorCloseFailThe fan contactor failed to close. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5566 |
lgpCondId5567IPInhibitThe intelligent paralleling operation is inhibited. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5567 |
lgpCondId5568InputUndervoltageOne or more of the input phase voltages has dropped below the limit. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5568 |
lgpCondId5569InputOvervoltageOne or more of the input phase voltages has exceeded the limit. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5569 |
lgpCondId5573AmbientAirSensorIssueAmbient air sensor is disconnected or the signal is out of range. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5573 |
lgpCondId5577ExtDewPointUnderTemperatureAt least one dew point temperature reading ([Ext Air Sensor A Dew Point Temp], [Ext Air Sensor B Dew Point Temp]...) has dropped below [Ext Dew Point Under Temp Threshold]. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5577 |
lgpCondId5578DewPointOverTemperatureDew point temperature reading has exceeded the upper threshold. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5578 |
lgpCondId5579DewPointUnderTemperatureDew point temperature reading has dropped below the lower threshold. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5579 |
lgpCondId5588UnspecifiedGeneralEventOne or more unspecified events active. See local unit display for further details. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5588 |
lgpCondId5593RemoteSensorAverageOverTemperature[Remote Sensor Average Temperature] has exceeded [Remote Sensor Over Temp Threshold]. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5593 |
lgpCondId5594RemoteSensorAverageUnderTemperature[Remote Sensor Average Temperature] has dropped below [Remote Sensor Under Temp Threshold]. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5594 |
lgpCondId5595RemoteSensorSystemAverageOverTemperature[Remote Sensor System Average Temperature] has exceeded [Remote Sensor Over Temp Threshold]. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5595 |
lgpCondId5596RemoteSensorSystemAverageUnderTemperature[Remote Sensor System Average Temperature] has dropped below [Remote Sensor Under Temp Threshold]. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5596 |
lgpCondId5597RemoteSensorOverTemperature[Remote Sensor Temperature] has exceeded [Remote Sensor Over Temp Threshold]. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5597 |
lgpCondId5598RemoteSensorUnderTemperature[Remote Sensor Temperature] has dropped below [Remote Sensor Under Temp Threshold]. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5598 |
lgpCondId5600AirEconomizerEmergencyOverrideIndoor room temperature has exceeded its upper threshold and the outdoor air damper has been opened for emergency cooling. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5600 |
lgpCondId5601AirEconomizerReducedAirflowAir economizer filter is dirty and needs to be cleaned or replaced. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5601 |
lgpCondId5604CompressorSuperheatOverThresholdCompressor discharge refrigerant superheat temperature has exceeded an upper threshold. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5604 |
lgpCondId5609ThermalRunawayCelltoAmbientTemperatureEventThe delta temperature between a cell temperature and the ambient temperature has exceeded the thermal runaway cell to ambient temperature threshold. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5609 |
lgpCondId5610ThermalRunawayCelltoCellTemperatureEventThe delta temperature between two cells has exceeded the thermal runaway cell to cell temperature threshold. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5610 |
lgpCondId5611ThermalRunawayChargerCurrentLevelOneEventThe Battery-String charger current has exceeded the thermal runaway charger current level one threshold. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5611 |
lgpCondId5612ThermalRunawayChargerCurrentLevelTwoEventThe Battery-String charger current has exceeded the thermal runaway charger current level two threshold. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5612 |
lgpCondId5617TemperatureControlSensorIssueThe air sensor selected for cooling control is disconnected or the signal is out of range. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5617 |
lgpCondId5621EEVSuperheatBelowThresholdElectronic expansion valve refrigerant low superheat event. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5621 |
lgpCondId5622EEVDischargeTempAboveThresholdElectronic expansion valve refrigerant high discharge temperature event. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5622 |
lgpCondId5623EEVBatteryIssueElectronic expansion valve battery cannot be recharged and needs to be replaced. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5623 |
lgpCondId5624EEVPowerIssueElectronic expansion valve lost power and is running on battery backup. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5624 |
lgpCondId5625EEVUnspecifiedGeneralEventOne or more unspecified electronic expansion valve events active. See local unit display for further details. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5625 |
lgpCondId5629StaticPressureSensorIssueThe static pressure sensor is disconnected or the signal is out of range. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5629 |
lgpCondId5630HighStaticPressureHigh static pressure event. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5630 |
lgpCondId5631LowStaticPressureLow static pressure event. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5631 |
lgpCondId5636PumpUnspecifiedGeneralEventOne or more unspecified pump events active. See local unit display for further details. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5636 |
lgpCondId5637CondenserUnitUnspecifiedGeneralEventOne or more unspecified condenser unit events active. See local unit display for further details. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5637 |
lgpCondId5638CondenserCircuitUnspecifiedGeneralEventOne or more unspecified condenser circuit events active. See local unit display for further details. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5638 |
lgpCondId5642SFAReservedEvent1Reserved event for SFA use. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5642 |
lgpCondId5643SFAReservedEvent2Reserved event for SFA use. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5643 |
lgpCondId5644SFAReservedEvent3Reserved event for SFA use. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5644 |
lgpCondId5645SFAReservedEvent4Reserved event for SFA use. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5645 |
lgpCondId5646SFAReservedEvent5Reserved event for SFA use. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5646 |
lgpCondId5647SFAReservedEvent6Reserved event for SFA use. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5647 |
lgpCondId5648SFAReservedEvent7Reserved event for SFA use. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5648 |
lgpCondId5649SFAReservedEvent8Reserved event for SFA use. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5649 |
lgpCondId5650SFAReservedEvent9Reserved event for SFA use. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5650 |
lgpCondId5651SFAReservedEvent10Reserved event for SFA use. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5651 |
lgpCondId5652SFAReservedEvent11Reserved event for SFA use. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5652 |
lgpCondId5653SFAReservedEvent12Reserved event for SFA use. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5653 |
lgpCondId5654SFAReservedEvent13Reserved event for SFA use. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5654 |
lgpCondId5655SFAReservedEvent14Reserved event for SFA use. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5655 |
lgpCondId5656SFAReservedEvent15Reserved event for SFA use. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5656 |
lgpCondId5657SFAReservedEvent16Reserved event for SFA use. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5657 |
lgpCondId5658SFAReservedEvent17Reserved event for SFA use. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5658 |
lgpCondId5659SFAReservedEvent18Reserved event for SFA use. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5659 |
lgpCondId5660SFAReservedEvent19Reserved event for SFA use. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5660 |
lgpCondId5661SFAReservedEvent20Reserved event for SFA use. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5661 |
lgpCondId5662SFAReservedEvent21Reserved event for SFA use. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5662 |
lgpCondId5663SFAReservedEvent22Reserved event for SFA use. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5663 |
lgpCondId5664SFAReservedEvent23Reserved event for SFA use. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5664 |
lgpCondId5665SFAReservedEvent24Reserved event for SFA use. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5665 |
lgpCondId5666SFAReservedEvent25Reserved event for SFA use. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5666 |
lgpCondId5768OutletAirOvertemperatureLimitThe difference between the outlet air temperature and inlet air temperature exceeds a specified maximum temperature. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5768 |
lgpCondId5769EMOShutdownAn Emergency Module Off command has been detected. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5769 |
lgpCondId5770TopOutletFanFaultTop outlet fan fault - one or more top outlet fans have failed. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5770 |
lgpCondId5771MMSOverCapacityThe multi-module system load is larger than the apparent power limit setting. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5771 |
lgpCondId5773CompressorCapacityNormalCompressor has returned to normal load capacity. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5773 |
lgpCondId5774CompressorContactorIssueCompressor contactor is not closing during compressor startup or is not opening during compressor shutdown. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5774 |
lgpCondId5775UnitShutdownUnspecifiedGeneralEventOne or more unspecified unit shutdown events active. See local unit display for further details. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5775 |
lgpCondId5776PDULowVoltageLNThe system has detected a module under voltage condition (LN). OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5776 |
lgpCondId5777PDULowVoltageLLThe system has detected a module under voltage condition (LL). OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5777 |
lgpCondId5778PDULowVoltageL1L2The system has detected a line-to-line under voltage condition (L1 -L2). OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5778 |
lgpCondId5779PDULowVoltageL2L3The system has detected a line-to-line under voltage condition (L2 -L3). OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5779 |
lgpCondId5780PDULowVoltageL3L1The system has detected a line-to-line under voltage condition (L3 -L1). OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5780 |
lgpCondId5781PDULowVoltageL1NThe system has detected a line to neutral under voltage condition (L1-N). OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5781 |
lgpCondId5782PDULowVoltageL2NThe system has detected a line to neutral under voltage condition (L2-N). OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5782 |
lgpCondId5783PDULowVoltageL3NThe system has detected a line to neutral under voltage condition (L3-N). OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5783 |
lgpCondId5784BranchLowVoltageLNThe system has detected a module under voltage condition (LN). OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5784 |
lgpCondId5785BranchLowVoltageLLThe system has detected a module under voltage condition (LL). OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5785 |
lgpCondId5786BranchLowVoltageThe system has detected a module under voltage condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5786 |
lgpCondId5788ContTieActiveContinuous Power Tie Active. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5788 |
lgpCondId5792UserkWhResetThe user kWh accumulator was reset to zero by the operator. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5792 |
lgpCondId5796PeakkWResetThe Peak kW was reset. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5796 |
lgpCondId5798BypassOverloadBypass overloaded, reduce load immediately. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5798 |
lgpCondId5801LowBatteryShutdownImminentIf active and guaranteed shutdown is enabled, a low battery reserve condition exists that will shutdown the UPS. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5801 |
lgpCondId5806OutputOverloadAn overload exists on the output. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5806 |
lgpCondId5807OutputOffPendingOutput off pending - shutdown imminent. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5807 |
lgpCondId5808SystemShutdownOutputShortShutdown was due to a short on the output. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5808 |
lgpCondId5809SystemShutdownLowBatteryShutdown was due to a low battery condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5809 |
lgpCondId5810SystemShutdownRemoteShutdownShutdown was due to a remote communications shutdown command. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5810 |
lgpCondId5811SystemShutdownHardwareFaultShutdown was due to an externally applied hardware control signal. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5811 |
lgpCondId5817LossofRedundancyThe system has an insufficient number of power modules to provide redundancy. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5817 |
lgpCondId5818PowerModuleFailureOne or more conditions indicate a power module failure, service is required. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5818 |
lgpCondId5819PowerModuleWarningOne or more power modules is reporting a warning condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5819 |
lgpCondId5838PowerModuleFanFaultThe Power Module has detected a fan fault. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5838 |
lgpCondId5839PowerModuleOverTemperatureThe Power Module has detected an over temperature condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5839 |
lgpCondId5840PowerModuleShutdownOverTemperaturePower Module has shutdown due to over temperature. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5840 |
lgpCondId5842ChargerModuleFanFaultThe Charger Module has detected a fan fault. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5842 |
lgpCondId5847BatteryModuleTemperatureSensorFaultA Battery Module temperature sensor fault has been detected. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5847 |
lgpCondId5848BatteryModuleOverTemperatureThe Battery Module has detected an over temperature condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5848 |
lgpCondId5849ReplaceBatteryModuleThe Battery Module needs to be replaced. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5849 |
lgpCondId5850SystemShutdownTransformerOverTemperatureSystem shutdown due to transformer over temperature. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5850 |
lgpCondId5851MaximumLoadAlarmMaximum load alarm indicating load setting has been exceeded. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5851 |
lgpCondId5856BatteryModuleFaultOne or more battery modules are reporting a fault condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5856 |
lgpCondId5857BatteryModuleWarningOne or more battery modules are reporting a warning condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5857 |
lgpCondId5862CheckAirFilterPlease check air filter, it may need to be cleaned or replaced. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5862 |
lgpCondId5863TransformerFanFaultThe transformer fan has failed. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5863 |
lgpCondId5865NoLoadWarningIndicates the UPS has output voltage but the output current is below a set threshold [No Load Warning Current Threshold] for a set period of time [No Load Warning Delay]. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5865 |
lgpCondId5871BatteryOverTemperatureLimitA battery temperature sensor is reporting a value above a predetermined limit. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5871 |
lgpCondId5873UnexpectedMainBatteryDisconnectClosureThe main battery disconnect has closed unexpectedly. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5873 |
lgpCondId5874BatteryOverVoltageThe system has detected that the battery voltage has exceeded a predetermined limit. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5874 |
lgpCondId5875BatteryFuseFaultOne or more battery fuse faults has occurred. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5875 |
lgpCondId5878MainBatteryDisconnectForcedToUnlockThe main battery disconnect is forced to the unlocked state. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5878 |
lgpCondId5879VdcBackfeedThe voltage between battery and DC bus measurements is out of tolerance. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5879 |
lgpCondId5880RectifierConfigurationChangeRequestThis event indicates that the battery is not configured and PFC is not enabled. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5880 |
lgpCondId5881RegenerationActiveRegeneration operation is active. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5881 |
lgpCondId5882RegenerationOperationTerminatedRegeneration operation is not active. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5882 |
lgpCondId5883RegenerationOperationFailureRegeneration operation has been terminated due to bypass source instability or unit misoperation. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5883 |
lgpCondId5884ProgramInputContact01When the signal from [Program Input Contact 01] is active the function assigned to this contact is executed. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5884 |
lgpCondId5885ProgramInputContact02When the signal from [Program Input Contact 02] is active the function assigned to this contact is executed. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5885 |
lgpCondId5886ProgramInputContact03When the signal from [Program Input Contact 03] is active the function assigned to this contact is executed. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5886 |
lgpCondId5887ProgramInputContact04When the signal from [Program Input Contact 04] is active the function assigned to this contact is executed. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5887 |
lgpCondId5888ProgramInputContact05When the signal from [Program Input Contact 05] is active the function assigned to this contact is executed. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5888 |
lgpCondId5889ProgramInputContact06When the signal from [Program Input Contact 06] is active the function assigned to this contact is executed. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5889 |
lgpCondId5890ProgramInputContact07When the signal from [Program Input Contact 07] is active the function assigned to this contact is executed. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5890 |
lgpCondId5891ProgramInputContact08When the signal from [Program Input Contact 08] is active the function assigned to this contact is executed. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5891 |
lgpCondId5892ProgramInputContact09When the signal from [Program Input Contact 09] is active the function assigned to this contact is executed. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5892 |
lgpCondId5893ProgramInputContact10When the signal from [Program Input Contact 10] is active the function assigned to this contact is executed. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5893 |
lgpCondId5894ProgramInputContact11When the signal from [Program Input Contact 11] is active the function assigned to this contact is executed. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5894 |
lgpCondId5895ProgramInputContact12When the signal from [Program Input Contact 12] is active the function assigned to this contact is executed. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5895 |
lgpCondId5896GroundFaultDetectedThe system has detected a ground fault on a Battery-String. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5896 |
lgpCondId5902ReturnHumiditySensorIssueThe humidity sensor at the inlet of the unit is disconnected or the signal is out of range. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5902 |
lgpCondId5903CompressorLowDifferentialPressureLockoutCompressor exceeded maximum startup attempts due to low differential pressure. Compressor is shutdown and has been disabled. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5903 |
lgpCondId5906AirflowSensorIssueAirflow sensor is disconnected or the signal is out of range. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5906 |
lgpCondId5907ExtAirDamperPositionIssueAir damper position does not match expected value, as indicated by an external input signal. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5907 |
lgpCondId5908ExtPowerSourceAFailureUnit main power source A failure, as indicated by an external input signal. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5908 |
lgpCondId5909ExtPowerSourceBFailureUnit main power source B failure, as indicated by an external input signal. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5909 |
lgpCondId5910StaticPressureSensorOutofRangeStatic pressure sensor signal is out of its configured range. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5910 |
lgpCondId5911FluidTemperatureSensorIssueThe fluid temperature sensor is disconnected or the signal is out of range. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5911 |
lgpCondId5912FluidFlowSensorIssueThe fluid flow sensor is disconnected or the signal is out of range. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5912 |
lgpCondId5914OverDifferentialPressureAn over differential pressure condition was detected. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5914 |
lgpCondId5915UnderDifferentialPressureAn under differential pressure condition was detected. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5915 |
lgpCondId5924MixedModeLockoutMixed mode has been entered too many times over a rolling time period and has been temporarily disabled. Mixed mode is defined as the use of a compressor on one refrigeration circuit and the use of a refrigerant pump on the other circuit. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5924 |
lgpCondId5928UnbalancedLoadConditionThe system has detected a line-to-line unbalanced load condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5928 |
lgpCondId5939BranchOverCurrentProtectionThe Branch Receptacle Module's over current protection is triggered. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5939 |
lgpCondId5948BranchLowVoltageLLThe system has detected a module under voltage condition (LL). OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5948 |
lgpCondId5957BypassInputVoltageFaultThe system has detected the bypass voltage is unqualified. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5957 |
lgpCondId5958BatteryTemperatureOutofRangeBattery temperature is outside of acceptable range. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5958 |
lgpCondId5960InverterOverloadInverter in overload fault. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5960 |
lgpCondId5966AuxAirTempDeviceCommunicationLostCommunication with external auxiliary device providing an air temperature value has been lost. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5966 |
lgpCondId5967ModbusPowerMeterCommunicationLostCommunication with Modbus power meter has been lost. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5967 |
lgpCondId5968InverterDesaturationInverter Desaturation. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5968 |
lgpCondId5969GenericDICFaultThe control board reports a fault - Service required. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5969 |
lgpCondId5970GroundFaultAn AC phase to ground fault or three phase fault to ground exists on the output of the UPS. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5970 |
lgpCondId5973InputBreakerOpenThe main input breaker is open. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5973 |
lgpCondId5974NeutralBreakerOpenThe neutral breaker is open. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5974 |
lgpCondId5975OutputBreakerOpenThe output breaker is open. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5975 |
lgpCondId5976MaintenanceBypassBreakerClosedThe maintenance bypass breaker is closed. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5976 |
lgpCondId5977BatteryBreakerOpenThe battery circuit is open. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5977 |
lgpCondId5978RectifierIsolationBreakerRFBOpenThe rectifier isolation breaker (RFB) indicates that it is in the open position. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5978 |
lgpCondId5982BypassBreakerSBBOpenThe bypass circuit breaker (SBB) indicates that it is in the open position. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5982 |
lgpCondId5983BypassIsolationBreakerBIBOpenThe bypass isolation breaker (BIB) indicates that it is in the open position. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5983 |
lgpCondId5984BypassUndervoltageWarningThe voltage on one or more bypass phases is less than a specified percentage of the nominal voltage. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5984 |
lgpCondId5985BypassStaticSwitchBPSSOnThe Bypass Static Switch has been turned on. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5985 |
lgpCondId5998BattOvtempWarningA battery temperature sensor is reporting a value above the setpoint. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.5998 |
lgpCondId6009InverterOutputBreakerOpenThe inverter output breaker indicates that it is in the open position. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6009 |
lgpCondId6011EquipmentOverTempWarningEquipment over temperature warning is a summary event based on the detection of at least one measured temperature exceeding a threshold. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6011 |
lgpCondId6012EquipmentOvertemperatureLimitThe equipment air temperature has exceeded its maximum set point. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6012 |
lgpCondId6045RectifierInputBreakerOpenThe rectifier isolation breaker indicates that it is in the open position. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6045 |
lgpCondId6046LoadonUPSThe output is being supplied power from the inverter. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6046 |
lgpCondId6047Core2CoreFuseFailureCore-2-core fuse failure. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6047 |
lgpCondId6052SystemOutputBreakerOpenThe system output breaker is open. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6052 |
lgpCondId6059InverterRelayFaultThe inverter relay has malfunctioned. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6059 |
lgpCondId6060TransfertoBypassSystemOverloadThe UPS System has transferred to bypass because the active power modules cannot support the critical load. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6060 |
lgpCondId6061InputSourceBackfeedThe battery is backfeeding the input source. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6061 |
lgpCondId6062LossofSynchronizationThe inverter and bypass are no longer synchronized. . OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6062 |
lgpCondId6063BatteryConverterCurrentLimitThe battery converter has reached is maximum current limit. . OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6063 |
lgpCondId6064LBSCableFailureLoad Bus Sync communications is abnormal. A problem with the LBS cable may exist. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6064 |
lgpCondId6065BatteryChargeEqualizationTimeoutThe battery equalizing is time out. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6065 |
lgpCondId6066ParallelCableFailureThe UPS parallel system communications is abnormal. A problem with the parallel cable may exist. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6066 |
lgpCondId6067BatteryFaultA short circuit exists in the battery system. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6067 |
lgpCondId6068BatteryRoomAlarmThe ambient temperature of the battery room is abnormal. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6068 |
lgpCondId6080UPSCCommunicationFailureThe UPSC has failed to communicate in a designated time period. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6080 |
lgpCondId6092Compressor1BThermalOverloadFixed compressor 1B is shut down due to thermal overload. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6092 |
lgpCondId6093Compressor2BThermalOverloadFixed compressor 2B is shut down due to thermal overload. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6093 |
lgpCondId6094Compressor1BHoursExceededFixed compressor 1B run hours have exceeded the threshold. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6094 |
lgpCondId6095Compressor2BHoursExceededFixed compressor 2B run hours have exceeded the threshold. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6095 |
lgpCondId6100CondenserRemoteShutdownCondenser is shut down by a remote signal. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6100 |
lgpCondId6105ExternalCondenserTVSSIssueThe condenser Transient Voltage Surge Suppressor or Surge Protection Device has failed, as indicated by an external input signal. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6105 |
lgpCondId6106ExternalCondenserVFDIssueThe condenser fan Variable Frequency Drive is offline, as indicated by an external input signal. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6106 |
lgpCondId6107ExternalCondenserIssueCondenser is not operating within its operational parameters, as indicated by an external input signal. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6107 |
lgpCondId6119SlotsnotavailableThe number of sensors exceeds the number of allocated slots and cannot be displayed. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6119 |
lgpCondId6180BatteryUnderVoltageBattery voltage is too low. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6180 |
lgpCondId6182ReplaceBatteryThe battery is due for replacement. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6182 |
lgpCondId6186InputFrequencyDeviationThe input frequency is outside of the normal range. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6186 |
lgpCondId6187ShutdownPendingShutdown is pending. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6187 |
lgpCondId6194SystemRebootCommandIssuedReboot command issued to the system. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6194 |
lgpCondId6203SensorAddedSensor Added. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6203 |
lgpCondId6204SensorRemovedSensor Removed. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6204 |
lgpCondId6205WaterLeakDetectedWater leak detected. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6205 |
lgpCondId6210FirmwareUpdateInProgressFirmware update has started and is in progress. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6210 |
lgpCondId6211FirmwareUpdateCompletedSuccessfullyFirmware update has completed successfully. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6211 |
lgpCondId6212FirmwareUpdateCompletedUnsuccessfullyFirmware update has completed, but was not successful. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6212 |
lgpCondId6216PrechargeCircuitFailedDC Bus precharge/discharge didn't reach specified level within a specified time. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6216 |
lgpCondId6217MemoryCardRemovedThe memory card on the control board has been removed. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6217 |
lgpCondId6218AutoCalibrationActiveThe system is automatically calibrating ADC channels. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6218 |
lgpCondId6219AutoCalibrationFailedADC channel calibration has failed. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6219 |
lgpCondId6220ModuleOutputBreakerOpenThe module output breaker is open. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6220 |
lgpCondId6221NeutralVoltageFaultVoltage observed on neutral line. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6221 |
lgpCondId6222BranchLoadLossLoss of load on branch detected. Branch circuit breaker might be open. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6222 |
lgpCondId6225RemoteSensorLowHumidityRemote sensor humidity has dropped below a lower threshold. The event is deactivated when the humidity rises above the threshold. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6225 |
lgpCondId6226RemoteSensorHighHumidityRemote sensor humidity has exceeded an upper threshold. The event is deactivated when the humidity drops below the threshold. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6226 |
lgpCondId6227RemoteSensorAverageLowHumidityThe average humidity of multiple remote sensors on the cooling unit has dropped below a lower threshold. The event is deactivated when the humidity rises above the threshold. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6227 |
lgpCondId6228RemoteSensorAverageHighHumidityThe average humidity of multiple remote sensors on the cooling unit has exceeded an upper threshold. The event is deactivated when the humidity drops below the threshold. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6228 |
lgpCondId6229RemoteSensorSystemAverageLowHumidityThe average humidity of multiple remote sensors on interconnected cooling units in a single system has dropped below a lower threshold. The event is deactivated when the humidity rises above the threshold. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6229 |
lgpCondId6230RemoteSensorSystemAverageHighHumidityThe average humidity of multiple remote sensors on interconnected cooling units in a single system has exceeded an upper threshold. The event is deactivated when the humidity drops below the threshold. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6230 |
lgpCondId6231LowCompressorSuperheatCompressor suction superheat has dropped below a lower threshold. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6231 |
lgpCondId6232SECUnspecifiedGeneralEventOne or more unspecified events active for the Superheat and Envelope Controller. See local unit display for further details. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6232 |
lgpCondId6233SECCommunicationLostCommunication with the Superheat and Envelope Controller has been lost. The event is deactivated when communication is re -established. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6233 |
lgpCondId6236PowerSourceAIssueNo power is detected at power source input 'A'. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6236 |
lgpCondId6237PowerSourceBIssueNo power is detected at power source input 'B'. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6237 |
lgpCondId6239FluidValveHoursExceededOperating hours for the fluid valve have exceeded the threshold. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6239 |
lgpCondId6253BoosterFailureBooster failure - boost is off. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6253 |
lgpCondId6254ChargerFailureCharger Failure - Charger is off. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6254 |
lgpCondId6274UnitTopReturnAirSensorFailureReturn air sensor at the top of the unit is disconnected or the signal is out of range. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6274 |
lgpCondId6275UnitMiddleReturnAirSensorFailureReturn air sensor in the middle of the unit is disconnected or the signal is out of range. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6275 |
lgpCondId6276UnitBottomReturnAirSensorFailureReturn air sensor at the bottom of the unit is disconnected or the signal is out of range. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6276 |
lgpCondId6277UnitTopSupplyAirSensorFailureSupply air sensor at the top of the unit is disconnected or the signal is out of range. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6277 |
lgpCondId6278UnitMiddleFirstSupplyAirSensorFailureFirst supply air sensor in the middle of the unit is disconnected or the signal is out of range. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6278 |
lgpCondId6279UnitBottomSupplyAirSensorFailureSupply air sensor at the bottom of the unit is disconnected or the signal is out of range. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6279 |
lgpCondId6284UnitMiddleSecondSupplyAirSensorFailureSecond supply air sensor in the middle of the unit is disconnected or the signal is out of range. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6284 |
lgpCondId6293ChilledWaterControlActiveChilled water inlet temperature control function is enabled due to 'bad' water. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6293 |
lgpCondId6294ChilledWaterFlowTransducerFailureChilled water flow transducer is disconnected or the signal is out of range. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6294 |
lgpCondId6295ChilledWaterInletTemperatureSensorFailureChilled water inlet temperature sensor is disconnected or the signal is out of range. The sensor is mandatory for the chilled water flow function. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6295 |
lgpCondId6296ChilledWaterHighInletTemperatureChilled water inlet temperature has exceeded an upper threshold. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6296 |
lgpCondId6297Modbus010VModuleCommunicationFailureModbus 0-10V module for managing the second Chilled Water circuit valve is disconnected or the signal is out of range. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6297 |
lgpCondId6299RackDoorsOpenRack doors opened due to supply air temperature exceeding the [Rack Door Open High Supply Air Temperature Threshold]. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6299 |
lgpCondId6303TeamStaticPressureSensorFailureThe team static pressure sensor is disconnected or the signal is out of range. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6303 |
lgpCondId6304HeatingLockoutHeating is shut down and disabled. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6304 |
lgpCondId6305FreeCoolingStoppedHighRoomTempFree cooling is temporarily disabled due to room temperature exceeding a preset delta above the the set point. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6305 |
lgpCondId6306ColdAisleTemperatureHumidityTeamSensorFailureCold aisle team sensor measuring air temperature and humidity is disconnected or the signal is out of range. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6306 |
lgpCondId6309ColdAisleAirSensorFailureCold aisle sensor measuring air temperature and humidity is disconnected or the signal is out of range. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6309 |
lgpCondId6310ChilledWaterInletTemperatureControlActiveChilled water inlet temperature control is active. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6310 |
lgpCondId6313ChilledWaterInletTemperatureSensorFailureChilled water inlet temperature sensor is disconnected or the signal is out of range. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6313 |
lgpCondId6314ChilledWaterOutletTemperatureSensorFailureChilled water outlet temperature sensor is disconnected or the signal is out of range. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6314 |
lgpCondId6315ChilledWaterFlowMeterSensorFailureChilled water flow meter sensor is disconnected or the signal is out of range. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6315 |
lgpCondId6333BypassoutofsyncBypass and Inverter inputs are not in sync. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6333 |
lgpCondId6348SystemOutputoffasrequestedThe UPS has shutdown as requested, i.e., the output is off. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6348 |
lgpCondId6349SystemOffasrequestedThe entire UPS has shutdown as commanded. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6349 |
lgpCondId6350GeneralFaultA general fault in the UPS has been detected. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6350 |
lgpCondId6351UPSAwaitingPowerThe UPS output is off and the UPS is awaiting the return of input power. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6351 |
lgpCondId6352AutonomyCalibrationCalibration test occurred. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6352 |
lgpCondId6353GeneralWarningA warning in the UPS has been detected. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6353 |
lgpCondId6354BatteryChargingThe UPS battery is charging (battery charge percentage lower than 98). OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6354 |
lgpCondId6355BackfeedRelayFailureBypass SCR is wrongly on or commutated. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6355 |
lgpCondId6356BatteryCircuitOpenBattery Circuit Open. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6356 |
lgpCondId6357SystemRestartPendingA request for UPS restart has been received. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6357 |
lgpCondId6358PipeTemperatureSensorFailureAir temperature sensor located in the pipe is not sending a valid value. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6358 |
lgpCondId6362SFAReservedEvent26Reserved event for SFA use. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6362 |
lgpCondId6363SFAReservedEvent27Reserved event for SFA use. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6363 |
lgpCondId6364SFAReservedEvent28Reserved event for SFA use. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6364 |
lgpCondId6365SFAReservedEvent29Reserved event for SFA use. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6365 |
lgpCondId6366SFAReservedEvent30Reserved event for SFA use. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6366 |
lgpCondId6367SFAReservedEvent31Reserved event for SFA use. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6367 |
lgpCondId6368SFAReservedEvent32Reserved event for SFA use. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6368 |
lgpCondId6369SFAReservedEvent33Reserved event for SFA use. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6369 |
lgpCondId6370SFAReservedEvent34Reserved event for SFA use. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6370 |
lgpCondId6371SFAReservedEvent35Reserved event for SFA use. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6371 |
lgpCondId6372SFAReservedEvent36Reserved event for SFA use. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6372 |
lgpCondId6373SFAReservedEvent37Reserved event for SFA use. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6373 |
lgpCondId6374SFAReservedEvent38Reserved event for SFA use. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6374 |
lgpCondId6375SFAReservedEvent39Reserved event for SFA use. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6375 |
lgpCondId6376SFAReservedEvent40Reserved event for SFA use. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6376 |
lgpCondId6377SFAReservedEvent41Reserved event for SFA use. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6377 |
lgpCondId6378SFAReservedEvent42Reserved event for SFA use. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6378 |
lgpCondId6379SFAReservedEvent43Reserved event for SFA use. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6379 |
lgpCondId6380SFAReservedEvent44Reserved event for SFA use. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6380 |
lgpCondId6381SFAReservedEvent45Reserved event for SFA use. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6381 |
lgpCondId6382SFAReservedEvent46Reserved event for SFA use. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6382 |
lgpCondId6383SFAReservedEvent47Reserved event for SFA use. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6383 |
lgpCondId6384SFAReservedEvent48Reserved event for SFA use. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6384 |
lgpCondId6385SFAReservedEvent49Reserved event for SFA use. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6385 |
lgpCondId6386SFAReservedEvent50Reserved event for SFA use. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6386 |
lgpCondId6438PowerModuleInputCurrentAbnormalInput current of the power module is abnormal. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6438 |
lgpCondId6439PowerModuleBalancerofDCBusFailureBalancer of DC Bus in the power module has failed. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6439 |
lgpCondId6440PowerModuleFuseFailureA summary event indicating one or more fuse failures in the power module. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6440 |
lgpCondId6441PowerModulePowerSupplyFailurePower module power supply failure. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6441 |
lgpCondId6450PDUPoweredOnThe PDU was powered on. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6450 |
lgpCondId6453InputWiringFaultThe neutral/ground conductors on the input wiring are not properly bonded, or the line/neutral conductors have been swapped. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6453 |
lgpCondId6454DCtoDCConverterFaultA failure has occurred in the battery discharge circuit. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6454 |
lgpCondId6455LeakSensorCableFaultA fault is detected in the 'Leak Sensor' cable. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6455 |
lgpCondId6518StandbyUnitActivatedDuetoChillerFailureExternal chiller unit has failed for this unit, so the standby cooling unit has been activated. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7.1.6518 |