LIEBERT-GP-CONDITIONS-MIB
AI MIB Summary
The LIEBERT-GP-CONDITIONS-MIB defines the Liebert-specific Object Identifiers required to monitor environmental conditions and operational states of Liebert GP series power and cooling infrastructure. This module enables the retrieval of critical telemetry data, including temperature, humidity, and alarm status, from Liebert network management agents via the SNMP protocol.
The MIB module used to register Liebert SNMP OIDs. Copyright 2000-2008,2013 Liebert Corporation. All rights reserved. Reproduction of this document is authorized on the condition that the forgoing copyright notice is included. This Specification is supplied 'AS IS' and Liebert Corporation makes no warranty, either express or implied, as to the use, operation, condition, or performance of the Specification.
Main OID:
liebertGlobalProductsConditionsModule.1.3.6.1.4.1.476.1.42.1.3.1
639
Objects
Active
Status
3
Dependencies
Imported Objects
Objects
639 total| Object Name |
|---|
liebertGlobalProductsConditionsModuleThe MIB module used to register Liebert SNMP OIDs. Copyright 2000-2008,2013 Liebert Corporation. All rights reserved. Reproduction of this document is authorized on the condition that the forgoing copyright notice is included. This Specification is supplied 'AS IS' and Liebert Corporation makes no warranty, either express or implied, as to the use, operation, condition, or performance of the Specification. MODULE-IDENTITY .1.3.6.1.4.1.476.1.42.1.3.1 |
lgpConditionsWellKnown OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1 |
lgpConditionHighTemperatureThe temperature has exceeded the high temperature threshold. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.1 |
lgpConditionLowTemperatureThe temperature is below the low temperature threshold. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.2 |
lgpConditionHighHumidityThe humidity has exceeded the high humidity threshold. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.3 |
lgpConditionLowHumidityThe humidity is below the low humidity threshold. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.4 |
lgpConditionLossOfAirflowThe system has detected a loss of air flow. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.5 |
lgpConditionLossOfAirflow1The system has detected a loss of air flow at sensor 1. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.5.1 |
lgpConditionLossOfAirflow2The system has detected a loss of air flow at sensor 2. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.5.2 |
lgpConditionLossOfAirflowBlower1The system has detected a loss of air flow from blower 1. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.5.3 |
lgpConditionLossOfAirflowAllBlowersNo air flow through the unit due to failure of all blowers. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.5.4 |
lgpConditionChangeFilterThe system has detected a condition indicating the air filter should be changed. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.6 |
lgpConditionCompressorHighHeadPressureThis system has detected an excessive head pressure condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.7 |
lgpConditionCompressor1HighHeadPressureThe system has detected excessive head pressure in compressor 1. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.7.1 |
lgpConditionCompressor1AHighHeadPressureThe system has detected excessive head pressure in compressor 1A. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.7.1.1 |
lgpConditionCompressor1BHighHeadPressureThe system has detected excessive head pressure in compressor 1B. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.7.1.2 |
lgpConditionCompressor2HighHeadPressureThe system has detected excessive head pressure in compressor 2. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.7.2 |
lgpConditionCompressor2AHighHeadPressureThe system has detected excessive head pressure in compressor 2A. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.7.2.1 |
lgpConditionCompressor2BHighHeadPressureThe system has detected excessive head pressure in compressor 2B. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.7.2.2 |
lgpConditionCompressor3HighHeadPressureThe system has detected excessive head pressure in compressor 3. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.7.3 |
lgpConditionCompressor4HighHeadPressureThe system has detected excessive head pressure in compressor 4. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.7.4 |
lgpConditionCompressorOverloadThis system has detected a compressor overload condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.8 |
lgpConditionCompressor1OverloadThe system has detected an overload condition on compressor 1. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.8.1 |
lgpConditionCompressor2OverloadThe system has detected an overload condition on compressor 2. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.8.2 |
lgpConditionCompressorShortCycleA compressor has exceeded the maximum number of starts in a minimum time period. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.9 |
lgpConditionCompressor1ShortCycleThe system has detected a short cycle event on compressor 1. The compressor has exceeded the maximum number of starts for specified amount of time. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.9.1 |
lgpConditionCompressor1AShortCycleThe system has detected a short cycle event on compressor 1A. The compressor has exceeded the maximum number of starts for specified amount of time. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.9.1.1 |
lgpConditionCompressor1BShortCycleThe system has detected a short cycle event on compressor 1B. The compressor has exceeded the maximum number of starts for specified amount of time. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.9.1.2 |
lgpConditionCompressor2ShortCycleThe system has detected a short cycle event on compressor 2. The compressor has exceeded the maximum number of starts for specified amount of time. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.9.2 |
lgpConditionCompressor2AShortCycleThe system has detected a short cycle event on compressor 2A. The compressor has exceeded the maximum number of starts for specified amount of time. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.9.2.1 |
lgpConditionCompressor2BShortCycleThe system has detected a short cycle event on compressor 2B. The compressor has exceeded the maximum number of starts for specified amount of time. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.9.2.2 |
lgpConditionCompressorLowSuctionPressureThe pressure at a compressor inlet has dropped below the minimum setting. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.10 |
lgpConditionCompressor1LowSuctionPressureThe pressure at compressor 1 inlet has dropped below the minimum setting. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.10.1 |
lgpConditionCompressor2LowSuctionPressureThe pressure at compressor 2 inlet has dropped below the minimum setting. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.10.2 |
lgpConditionMainFanOverLoadThe system has detected a main fan overload condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.11 |
lgpConditionManualOverrideThe system has detected a manual override condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.12 |
lgpConditionStandbyGlycoolPumpOnThe standby Glycol or Glycool pump is activated. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.13 |
lgpConditionWaterUnderFloorMoisture has been detected under the floor. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.14 |
lgpConditionHumidifierProblemThe system has detected a humidifier problem. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.15 |
lgpConditionLowWaterInHumidifierThe system has detected a low water condition in the humidifier reservoir. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.16 |
lgpConditionSmokeDetectedThe system has detected smoke. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.17 |
lgpConditionLowWaterFlowThe system has detected a low water flow rate condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.18 |
lgpConditionLostPowerThe system has lost power before being switched off using the controls. This condition is activated when power is restored. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.19 |
lgpGeneralFaultA fault condition has been detected that is not identified in the well known list. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.20 |
lgpConditionLocalAlarmThis system has detected a local, or customer, alarm condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.21 |
lgpConditionLocalAlarm1The system has detected that customer alarm condition 1 is active. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.21.1 |
lgpConditionLocalAlarm2The system has detected that customer alarm condition 2 is active. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.21.2 |
lgpConditionLocalAlarm3The system has detected that customer alarm condition 3 is active. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.21.3 |
lgpConditionLocalAlarm4The system has detected that customer alarm condition 4 is active. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.21.4 |
lgpConditionLocalAlarm5The system has detected that customer alarm condition 5 is active. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.21.5 |
lgpConditionLocalAlarm6The system has detected that customer alarm condition 6 is active. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.21.6 |
lgpConditionLocalAlarm7The system has detected that customer alarm condition 7 is active. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.21.7 |
lgpConditionLocalAlarm8The system has detected that customer alarm condition 8 is active. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.21.8 |
lgpConditionStandbyUnitOnThe system has detected the standby unit is operating. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.22 |
lgpConditionCompressorLowPressureThis system has detected a low head compressor condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.23 |
lgpConditionCompressor1LowPressureThe system has detected low pressure in compressor 1. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.23.1 |
lgpConditionTandemCompressorCircuit1LowPressureThe system has detected low pressure in tandem compressor circuit 1. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.23.1.1 |
lgpConditionCompressor2LowPressureThe system has detected low pressure in compressor 2. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.23.2 |
lgpConditionTandemCompressorCircuit2LowPressureThe system has detected low pressure in tandem compressor circuit 2. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.23.2.1 |
lgpConditionCompressor3LowPressureThe system has detected low pressure in compressor 3. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.23.3 |
lgpConditionCompressor4LowPressureThe system has detected low pressure in compressor 4. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.23.4 |
lgpConditionHighWaterInPanThe system has detected a high water condition in the condenser pan. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.24 |
lgpConditionFaultySensorThe system has detected a faulty temperature/humidity sensor. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.25 |
lgpConditionServiceCoolingThe Cooling system requires scheduled maintenance. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.26 |
lgpConditionServiceHumidifierThe Humidifier requires scheduled maintenance. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.27 |
lgpConditionSystemControlBatteryLowCharge level of the system control's battery is below the alarm set point. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.28 |
lgpConditionGroundSystemFaultThe system has detected a ground system fault. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.29 |
lgpConditionGroundFailureThe system has detected a ground failure. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.30 |
lgpConditionSecurityBreachThe system has detected a security breach. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.31 |
lgpConditionEmergencyShutdownThe system has detected an emergency shutdown condition. The System is shutting down as a result of this emergency. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.32 |
lgpConditionOnBypassThis system has detected the load is being powered by a bypass source. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.33 |
lgpConditionLoadOnBypassThe load is being powered by a bypass source.obsolete OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.33.1 |
lgpConditionLoadOnMaintenceBypassThe load is being powered by a maintenance bypass source. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.33.2 |
lgpConditionParallelSysLoadOnBypassThe parallel system has transferred to bypass. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.33.3 |
lgpConditionLoadOnBypassByImpactThe system has detected a load impact and has transferred the load to the bypass source. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.33.4 |
lgpConditionLoadTransferedToBypassThe system has transferred to bypass. The load is being powered by the bypass source. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.33.5 |
lgpConditionEmergencyTransferToBypassThe system has performed an emergency transfer to bypass. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.33.6 |
lgpConditionOutputToLoadVoltTHDThe total harmonic distortion (THD) of the output voltage has exceeded a pre-determined threshold for a device, or system, defined amount of time. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.34 |
lgpConditionLogicFailureThe system has detected a control logic failure. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.35 |
lgpConditionPowerSupplyFaultThis system had detected a power supply fault condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.36 |
lgpConditionPowerSupply1FaultThe system has detected power supply 1 is in a fault condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.36.1 |
lgpConditionPowerSupply2FaultThe system has detected power supply 2 is in a fault condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.36.2 |
lgpConditionPowerSupplyFailureThis system has detected a power supply failure condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.37 |
lgpConditionPowerSupply1FailureThe system has detected power supply 1 has failed. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.37.1 |
lgpConditionPowerSupply2FailureThe system has detected power supply 2 has failed. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.37.2 |
lgpConditionSource1PowerSupplyInputFailureThe system has detected the source 1 Power supply input has failed. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.37.3 |
lgpConditionSource2PowerSupplyInputFailureThe system has detected the source 2 Power supply input has failed. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.37.4 |
lgpConditionPowerSupplyLogicFailureThe system has detected a power supply logic failure. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.37.5 |
lgpConditionCompressorPowerSupplyFailureThe system has detected the power supply to the compressors has failed. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.37.6 |
lgpConditionOverVoltageThis system has detected an over voltage condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.38 |
lgpConditionSource1OverVoltageThe system has detected an over voltage condition on source 1. The voltage measurement has risen above a pre-determined threshold for a device, or system, defined amount of time. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.38.1 |
lgpConditionSource2OverVoltageThe system has detected an over voltage condition on source 2. The voltage measurement has risen above a pre-determined threshold for a device, or system, defined amount of time. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.38.2 |
lgpConditionOutputToLoadOverVoltageThe system has detected the output to load is in an over-voltage condition. The voltage for the load has risen above a pre-determined threshold for a device, or system, defined amount of time. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.38.3 |
lgpConditionInputOverVoltageThe system has detected an input over voltage condition. The voltage measurement has risen above a pre-determined threshold for a specified amount of time. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.38.4 |
lgpConditionBypassOverVoltageThe system has detected an over voltage condition on the bypass. The voltage measurement has risen above a pre-determined threshold for a device, or system, defined amount of time. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.38.5 |
lgpConditionBypassOverVoltageFailureThe system has detected an over voltage failure condition on the bypass. The voltage measurement has risen above a pre-determined threshold for a device, or system, defined amount of time. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.38.6 |
lgpConditionBatteryOverVoltageThe system has detected a battery over voltage condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.38.7 |
lgpConditionDcBusOverVoltageThis system has detected a DC Bus over voltage condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.38.8 |
lgpConditionDcBus1OverVoltageThe system has detected an over voltage condition on DC Bus 1. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.38.8.1 |
lgpConditionDcBus2OverVoltageThe system has detected an over voltage condition on DC Bus 2. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.38.8.2 |
lgpConditionDcBus1OverVoltageFailureThe system has detected an over voltage failure condition on DC Bus 1. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.38.8.3 |
lgpConditionDcBus2OverVoltageFailureThe system has detected an over voltage failure condition on DC Bus 2. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.38.8.4 |
lgpConditionUnderVoltageThis system has detected an under voltage condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.39 |
lgpConditionSource1UnderVoltageThe system has detected an under voltage condition on source 1. The voltage measurement has fallen below a pre-determined threshold for a device, or system, defined amount of time. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.39.1 |
lgpConditionSource2UnderVoltageThe system has detected an under voltage condition on source 2. The voltage measurement has fallen below a pre-determined threshold for a device, or system, defined amount of time. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.39.2 |
lgpConditionOutputToLoadUnderVoltageThe system has detected the output to load is in an under-voltage condition. The voltage for the load has fallen below a pre-determined threshold for a device, or system, defined amount of time. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.39.3 |
lgpConditionSource1UnderVoltageRMSThe system has detected an under voltage condition on source 1. The voltage measurement has fallen below a pre-determined threshold for a specified amount of time. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.39.4 |
lgpConditionSource2UnderVoltageRMSThe system has detected an under voltage condition on source 2. The voltage measurement has fallen below a pre-determined threshold for a specified amount of time. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.39.5 |
lgpConditionInputUnderVoltageThe system has detected an input under voltage condition. The voltage measurement has fallen below a pre-determined threshold for a device, or system, defined amount of time. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.39.6 |
lgpConditionBypassUnderVoltageThe system has detected an under voltage condition on the bypass. The voltage measurement has fallen below a pre-determined threshold for a device, or system, defined amount of time. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.39.7 |
lgpConditionBypassUnderVoltageFailureThe system has detected an under voltage failure condition on the bypass. The voltage measurement has fallen below a pre-determined threshold for a device, or system, defined amount of time. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.39.8 |
lgpConditionBatteryUnderVoltageThe system has detected a battery under voltage condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.39.9 |
lgpConditionDcBusUnderVoltageThis system has detected a DC bus under voltage condition OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.39.10 |
lgpConditionDcBus1UnderVoltageThe system has detected an under voltage condition on DC Bus 1. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.39.10.1 |
lgpConditionDcBus2UnderVoltageThe system has detected an under voltage condition on DC Bus 2. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.39.10.2 |
lgpConditionDcBus1UnderVoltageFailureThe system has detected an under voltage failure condition on DC Bus 1. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.39.10.3 |
lgpConditionDcBus2UnderVoltageFailureThe system has detected an under voltage failure condition on DC Bus 2. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.39.10.4 |
lgpConditionOverloadThis system has detected an overload condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.40 |
lgpConditionSource1OverloadThe system has detected an overload condition on source 1. The power requirement for this source has risen above a pre-determined threshold for a device, or system, defined amount of time. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.40.1 |
lgpConditionSystemOverloadThe system has detected an overload condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.40.2 |
lgpConditionSource1PeakCurrentOverLoadThe system has detected source 1 in is experiencing a peak over load condition. The current has risen above a pre-determined threshold for a specified amount of time. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.40.3 |
lgpConditionSource2PeakCurrentOverLoadThe system has detected source 2 in is experiencing a peak over load condition. The current has risen above a pre-determined threshold for a specified amount of time. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.40.4 |
lgpConditionOutputToLoadOverLimitThe system had detected that the output to the load has exceeded the lgpPwrOutputToLoadUserOverloadLimit. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.40.5 |
lgpConditionOutputToLoadOverloadThe system has detected an output overload condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.40.6 |
lgpConditionParallelSysOverloadThe parallel system has detected an overload condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.40.7 |
lgpConditionBypassCurrentOverloadWith the load on bypass static switch, the measured output RMS current has exceeded a specified percentage of the nominal RMS current. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.40.8 |
lgpConditionBypassCurrentOverloadPhsAWith the load on bypass static switch, the measured phase A output RMS current has exceeded a specified percentage of the nominal per-phase RMS current. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.40.8.1 |
lgpConditionBypassCurrentOverloadPhsBWith the load on bypass static switch, the measured phase B output RMS current has exceeded a specified percentage of the nominal per-phase RMS current. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.40.8.2 |
lgpConditionBypassCurrentOverloadPhsCWith the load on bypass static switch, the measured phase C output RMS current has exceeded a specified percentage of the nominal per-phase RMS current. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.40.8.3 |
lgpConditionScrShortThis system has detected a Silicon Controlled Rectifier (SCR) short condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.41 |
lgpConditionSource1ScrShortThe system has detected a source 1 Silicon Controlled Rectifier (SCR) short condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.41.1 |
lgpConditionSource2ScrShortThe system has detected a source 2 Silicon Controlled Rectifier (SCR) short condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.41.2 |
lgpConditionBypassScrShortThe system has detected a Silicon Controlled Rectifier (SCR) short condition on the bypass. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.41.3 |
lgpConditionInvStaticSwScrShortThe system has detected a short across one or more inverter static switch Silicon Controlled Rectifiers (SCRs). OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.41.4 |
lgpConditionSource1NeutralScrShortThe system has detected a source 1 Silicon Controlled Rectifier (SCR) short condition on the neutral line. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.41.5 |
lgpConditionSource2NeutralScrShortThe system has detected a source 2 Silicon Controlled Rectifier (SCR) short condition on the neutral line. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.41.6 |
lgpConditionScrOpenThis system has detected a Silicon Controlled Rectifier (SCR) open condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.42 |
lgpConditionSource1ScrOpenThe system has detected a source 1 Silicon Controlled Rectifier (SCR) open condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.42.1 |
lgpConditionSource2ScrOpenThe system has detected a source 2 Silicon Controlled Rectifier (SCR) open condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.42.2 |
lgpConditionBypassScrOpenThe system has detected a Silicon Controlled Rectifier (SCR) open condition on the bypass. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.42.3 |
lgpConditionSource1NeutralScrOpenThe system has detected a source 1 Silicon Controlled Rectifier (SCR) open condition on the neutral line. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.42.4 |
lgpConditionSource2NeutralScrOpenThe system has detected a source 2 Silicon Controlled Rectifier (SCR) open condition on the neutral line. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.42.5 |
lgpConditionFanFailureThis system has detected a fan failure condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.43 |
lgpConditionFan1FailureThe system has detected a fan 1 failure condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.43.1 |
lgpConditionRedundantFanFailureA failure has occurred in a fan that cools the system's internal components and has resulted in a loss of fan redundancy. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.43.2 |
lgpConditionMultipleFanFailureMultiple fans have failed resulting in a decreased ability to cool the system's internal components. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.43.3 |
lgpConditionBlowerFanFailureThe system has detected a problem with one or more of the blower fans. These are not the system internal cooling fans. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.43.4 |
lgpConditionBottomBlowerFanFailureThe bottom environmental unit blower fan is not operating within its normal parameters. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.43.4.1 |
lgpConditionTopBlowerFanFailureThe top environmental unit blower fan is not operating within its normal parameters. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.43.4.2 |
lgpConditionCondenserFanVFDFailureThe system has detected a problem with the Variable Frequency Drive system for the condenser fan. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.43.5 |
lgpConditionFanPowerFailureThe system has detected a power failure on one or more fans. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.43.6 |
lgpConditionTransferInhibitedThe system is preventing a transfer of the load to the alternate source. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.44 |
lgpConditionAutoReTransferPrimedThe system is capable to retransfer to the preferred source. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.45 |
lgpConditionSourcesOutOfSyncThe system has detected that the input sources are not within the specified phase difference (synchronization window). OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.46 |
lgpConditionSourceFailureThis system has detected an input source failure condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.47 |
lgpConditionSource1FailureThe system has detected source 1 has failed. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.47.1 |
lgpConditionSource2FailureThe system has detected source 2 has failed. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.47.2 |
lgpConditionAutoReTransferInhibitedThe system is preventing a retransfer of the load back to the preferred source. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.48 |
lgpConditionAutoReTransferFailedThe system is failing to automatically retransfer the load back to the preferred source. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.49 |
lgpConditionFuseOpenThis system has detected an open fuse condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.50 |
lgpConditionControlFuse1OpenThe system has detected a control power fuse 1 open condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.50.1 |
lgpConditionControlFuse2OpenThe system has detected a control power fuse 2 open condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.50.2 |
lgpConditionRectifierFuseOpenThe system has detected a rectifier fuse open condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.50.3 |
lgpConditionInverterFuseOpenThe system has detected an inverter fuse open condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.50.4 |
lgpConditionOutputToLoadFuseOpenThe system has detected an output to load fuse open condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.50.5 |
lgpConditionDcCapacitorFuseOpenThe system has detected a DC capacitor fuse open condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.50.6 |
lgpConditionDisconnectThe system has detected a disconnect condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.51 |
lgpConditionSource1DisconnectOpenThe system has detected the source 1 disconnect is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.). OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.51.1 |
lgpConditionSource2DisconnectOpenThe system has detected the source 2 disconnect is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.). OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.51.2 |
lgpConditionSource1PduDisconnectOpenThe system has detected the source 1 PDU (Power Distribution Unit) disconnect is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.). OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.51.3 |
lgpConditionSource2PduDisconnectOpenThe system has detected the source 2 PDU (Power Distribution Unit) disconnect is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.). OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.51.4 |
lgpConditionOutputToLoadDisconnect1OpenThe system has detected Output to load disconnect 1 is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.). OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.51.5 |
lgpConditionOutputToLoadDisconnect2OpenThe system has detected Output to load disconnect 2 is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.). OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.51.6 |
lgpConditionSource1BypassDisconnectClosedThe system has detected the source 1 bypass disconnect is closed. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.). OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.51.7 |
lgpConditionSource2BypassDisconnectClosedThe system has detected the source 2 bypass disconnect is closed. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.). OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.51.8 |
lgpConditionOutputToLoadNeutralDisconnectOpenThe system has detected the output to load neutral disconnect is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.). OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.51.9 |
lgpConditionBatteryDisconnectOpenThe system has detected the battery disconnect is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.). OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.51.10 |
lgpConditionBatteryDiscOpenCab01The system has detected the cabinet 1 battery disconnect is open. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.51.10.1 |
lgpConditionBatteryDiscOpenCab02The system has detected the cabinet 2 battery disconnect is open. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.51.10.2 |
lgpConditionBatteryDiscOpenCab03The system has detected the cabinet 3 battery disconnect is open. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.51.10.3 |
lgpConditionBatteryDiscOpenCab04The system has detected the cabinet 4 battery disconnect is open. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.51.10.4 |
lgpConditionBatteryDiscOpenCab05The system has detected the cabinet 5 battery disconnect is open. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.51.10.5 |
lgpConditionBatteryDiscOpenCab06The system has detected the cabinet 6 battery disconnect is open. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.51.10.6 |
lgpConditionBatteryDiscOpenCab07The system has detected the cabinet 7 battery disconnect is open. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.51.10.7 |
lgpConditionBatteryDiscOpenCab08The system has detected the cabinet 8 battery disconnect is open. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.51.10.8 |
lgpConditionInputDisconnectOpenThe system has detected the input disconnect is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.). OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.51.11 |
lgpConditionOutputToLoadDisconnectOpenThe system has detected the Output to load disconnect is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.). OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.51.12 |
lgpConditionBypassDisconnectOpenThe system has detected the bypass disconnect is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.). OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.51.13 |
lgpConditionStaticSwitchDisconnectOpenThe system has detected the static switch disconnect is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.). OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.51.14 |
lgpConditionBreakerOpenFailureA breaker in the system has failed to respond to an Open signal. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.51.15 |
lgpConditionBreakerCloseFailureA breaker in the system has failed to respond to a Close signal. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.51.16 |
lgpConditionFrequencyDeviationThis system has detected a frequency deviation condition. The frequency of a source is outside of the pre-determined thresholds for a specified amount of time. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.52 |
lgpConditionSource1FrequencyDeviationThe frequency for source 1 has been outside of the pre-determined thresholds for a specified period of time. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.52.1 |
lgpConditionSource2FrequencyDeviationThe frequency for source 2 has been outside of the pre-determined thresholds for a specified period of time. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.52.2 |
lgpConditionInputFrequencyDeviationThe frequency for the input has been outside of the pre-determined thresholds for a specified period of time. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.52.3 |
lgpConditionOutputToLoadFrequencyDeviationThe frequency for the output has been outside of the pre-determined thresholds for a specified period of time. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.52.4 |
lgpConditionBypassFrequencyDeviationThe frequency for the bypass input has been outside of the pre-determined thresholds for a specified period of time. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.52.5 |
lgpConditionOverCurrentThis system has detected an over-current condition. The current of a source has risen above a pre-determined threshold for a device, or system, defined amount of time. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.53 |
lgpConditionSource1OverCurrentThe system has detected an over current condition on source 1. The current of a source has risen above a pre-determined threshold for a device, or system, defined amount of time. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.53.1 |
lgpConditionSource2OverCurrentThe system has detected an over current condition on source 2. The current of a source has risen above a pre-determined threshold for a device, or system, defined amount of time. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.53.2 |
lgpConditionOutputToLoadOverCurrentThe system has detected the output to load is in an over-current condition. The current for the load has risen above a pre-determined threshold for a device, or system, defined amount of time. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.53.3 |
lgpConditionOutputToLoadOverCurrentPhsAThe system has detected the output to load on phase A is in an over-current condition. The current on this phase has risen above a pre-determined threshold for a device, or system, defined amount of time. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.53.3.1 |
lgpConditionOutputToLoadOverCurrentPhsBThe system has detected the output to load on phase B is in an over-current condition. The current on this phase has risen above a pre-determined threshold for a device, or system, defined amount of time. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.53.3.2 |
lgpConditionOutputToLoadOverCurrentPhsCThe system has detected the output to load on phase C is in an over-current condition. The current on this phase has risen above a pre-determined threshold for a device, or system, defined amount of time. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.53.3.3 |
lgpConditionGroundOverCurrentA ground source is experiencing an over-current condition. The current for the ground line has risen above a pre-determined threshold for a device, or system, defined amount of time. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.53.4 |
lgpConditionRectifierOverCurrentThe system has detected a rectifier over current condition. The current for the rectifier has risen above a pre-determined threshold for a device, or system, defined amount of time. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.53.5 |
lgpConditionInverterOverCurrentThe system has detected an inverter over current condition. The current for the inverter has risen above a pre-determined threshold for a device, or system, defined amount of time. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.53.6 |
lgpConditionInverterOverCurrentPhsAThe system has detected an inverter over current condition on phase A. The current for the this phase in the inverter has risen above a pre-determined threshold for a device, or system, defined amount of time. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.53.6.1 |
lgpConditionInverterOverCurrentPhsBThe system has detected an inverter over current condition on phase B. The current for the this phase in the inverter has risen above a pre-determined threshold for a device, or system, defined amount of time. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.53.6.2 |
lgpConditionInverterOverCurrentPhsCThe system has detected an inverter over current condition on phase C. The current for the this phase in the inverter has risen above a pre-determined threshold for a device, or system, defined amount of time. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.53.6.3 |
lgpConditionBatteryConverterOverCurrentThe system has detected an over current condition on the battery converter. The current of the converter has risen above a pre-determined threshold for a device, or system, defined amount of time. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.53.7 |
lgpConditionBatteryBalancerOverCurrentThe system has detected a battery balancer over current condition. The current at this point has risen above a pre-determined threshold for a device, or system, defined amount of time. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.53.8 |
lgpConditionHumidifierOverCurrentThe system has detected an over current condition on the humidifier. The current of the humidifier has risen above a pre-determined threshold for a defined amount of time. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.53.9 |
lgpConditionInputOverCurrentThere is an over current condition on the system input power. The input current has risen above a pre-determined threshold for a pre-defined amount of time. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.53.10 |
lgpConditionSource1NeutralOverCurrentThe system has detected an over current condition on the neutral line of source 1. The neutral current at source 1 has risen above a pre-determined threshold for a pre-defined amount of time. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.53.11 |
lgpConditionSource2NeutralOverCurrentThe system has detected an over current condition on the neutral line of source 2. The neutral current at source 2 has risen above a pre-determined threshold for a pre-defined amount of time. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.53.12 |
lgpConditionSensorFailureThis system has detected a sensor failure condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.54 |
lgpConditionOutputToLoadVoltageSensorFailureThe system had detected an output to load voltage sensor failure. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.54.1 |
lgpConditionSource1VoltageSensorFailureThe system had detected a source 1 voltage sensor failure. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.54.2 |
lgpConditionSource2VoltageSensorFailureThe system had detected a source 2 voltage sensor failure. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.54.3 |
lgpConditionSource1ScrSensorFailureThe system had detected a source 1 SCR (Silicon Controlled Rectifier) sensor failure. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.54.4 |
lgpConditionSource2ScrSensorFailureThe system had detected a source 2 SCR (Silicon Controlled Rectifier) sensor failure. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.54.5 |
lgpConditionSource1CurrentSensorFailureThe system has detected a source 1 current sensor failure. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.54.6 |
lgpConditionSource2CurrentSensorFailureThe system has detected a source 2 current sensor failure. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.54.7 |
lgpConditionRoomTempHumiditySensorFailureThe system has detected a device temperature and humidity sensor failure. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.54.8 |
lgpConditionGlycolTempSensorFailureThe system has detected a glycol temperature sensor failure. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.54.9 |
lgpConditionLocal1SensorFailureThe system has detected a local 1 sensor failure. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.54.10 |
lgpConditionCompressor1SensorFailureThe system has detected a compressor 1 digital scroll sensor failure condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.54.11 |
lgpConditionCompressor2SensorFailureThe system has detected a compressor 2 digital scroll sensor failure condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.54.12 |
lgpConditionSupplySensorFailureThe system has detected a supply sensor failure. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.54.13 |
lgpConditionCabinetTemperatureSensorFailureThe system has detected a cabinet temperature sensor failure. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.54.14 |
lgpConditionCabinetHumiditySensorFailureThe system has detected a cabinet humidity sensor failure. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.54.15 |
lgpConditionRoomTempSensorFailureThe system has detected a room temperature sensor failure. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.54.16 |
lgpConditionBatteryTempSensorFailureThe system has detected a battery temperature sensor failure. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.54.17 |
lgpConditionAirSensorAFailureThe system has detected a failure with air sensor A. The sensor may have been disconnected or the signal is out of range. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.54.18 |
lgpConditionAirSensorBFailureThe system has detected a failure with air sensor B. The sensor may have been disconnected or the signal is out of range. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.54.19 |
lgpConditionChilledWaterSupplySensorFailureThe system has detected a failure with the chilled water supply sensor. The sensor may have been disconnected or the signal is out of range. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.54.20 |
lgpConditionRefrigerantSupplySensorFailureThe system has detected a failure with the refrigerant supply sensor. The sensor may have been disconnected or the signal is out of range. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.54.21 |
lgpConditionFluidSupplySensorFailureThe system has detected a failure with the fluid supply sensor. The sensor may have been disconnected or the signal is out of range. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.54.22 |
lgpConditionCompressorLowPressureSensorFailureThe system has detected that a compressor low pressure transducer is disconnected or the signal is out of range. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.54.23 |
lgpConditionCompressor1LowPressureSensorFailureThe system has detected that compressor 1 low pressure transducer is disconnected or the signal is out of range. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.54.23.1 |
lgpConditionRemoteSensorFailureThe system has detected that a remote sensor is disconnected or the signal is out of range. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.54.24 |
lgpConditionAirSupplyTempSensorFailureThe system has detected that the supply air temperature sensor is disconnected or the signal is out of range. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.54.25 |
lgpConditionAirReturnTempSensorFailureThe system has detected that the return air temperature sensor is disconnected or the signal is out of range. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.54.26 |
lgpConditionCompressorHighPressureSensorFailureThe system has detected that a compressor high pressure transducer is disconnected or the signal is out of range. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.54.27 |
lgpConditionInternalCommunicationFailureThis system has detected an internal communication failure condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.55 |
lgpConditionExternalCommunicationFailureThis system has detected an external communication failure condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.56 |
lgpConditionSourceGateDriveFailureThis system has detected a source gate drive failure condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.57 |
lgpConditionSource1GateDriveFailureThe system has detected a source 1 gate drive failure. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.57.1 |
lgpConditionSource2GateDriveFailureThe system has detected a source 2 gate drive failure. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.57.2 |
lgpConditionDisconnectFailureThis system has detected a disconnect failure condition. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.). OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.58 |
lgpConditionOutputToLoadNeutralDisconnectFailureThe system has detected the output to load neutral disconnect has failed. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.). OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.58.1 |
lgpConditionSource1DisconnectShuntTripFailureThe system has detected a shunt trip failure of a disconnecting device on source 1. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.). OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.58.2 |
lgpConditionSource2DisconnectShuntTripFailureThe system has detected a shunt trip failure of a disconnecting device on source 2. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.). OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.58.3 |
lgpConditionInverterDisconnectFailureThe system has detected an inverter disconnect failure. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.). OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.58.4 |
lgpConditionBatteryDisconnectFailureThe system has detected a battery disconnect failure. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.). OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.58.5 |
lgpConditionRectifierDisconnectFailureThe system has detected a rectifier disconnect failure. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.). OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.58.6 |
lgpConditionOverTemperatureThis system has detected an over temperature condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.59 |
lgpConditionHeatSink1OverTemperatureThe system has detected a heat sink 1 over temperature condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.59.1 |
lgpConditionAmbient1OverTemperatureThe system has detected an ambient over temperature condition at location 1. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.59.2 |
lgpConditionSystemOverTemperatureThe system or a component of the system has detected an over temperature condition. The temperature measurement has risen above a pre-determined threshold for a device, or system, defined amount of time. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.59.3 |
lgpConditionTransformerOverTemperatureThe transformer is experiencing an over temperature condition. The transformer's temperature has exceeded a pre-determined threshold for a device, or system, defined amount of time. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.59.4 |
lgpConditionBatteryOverTemperatureThe battery is experiencing an over temperature condition. The battery's temperature has exceeded a pre-determined threshold for a device, or system, defined amount of time. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.59.5 |
lgpConditionRectifierOverTemperatureThe system has detected a rectifier over temperature condition. The rectifier's temperature has exceeded a pre-determined threshold for a device, or system, defined amount of time. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.59.6 |
lgpConditionInverterOverTemperatureThe system has detected an inverter over temperature condition. The inverter's temperature has exceeded a pre-determined threshold for a device, or system, defined amount of time. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.59.7 |
lgpConditionRectifierInductorOverTemperatureThe system has detected a rectifier inductor over temperature condition. The rectifier's inductor temperature has exceeded a pre-determined threshold for a device, or system, defined amount of time. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.59.8 |
lgpConditionInverterInductorOverTemperatureThe system has detected an inverter inductor over temperature condition. The inverter's inductor temperature has exceeded a pre-determined threshold for a device, or system, defined amount of time. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.59.9 |
lgpConditionBatteryConverterOverTemperatureThe system has detected a battery converter over temperature condition. The battery converter's temperature has exceeded a pre-determined threshold for a device, or system, defined amount of time. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.59.10 |
lgpConditionBatteryBalancerInductorOverTemperatureThe system has detected a battery balancer Inductor over temperature condition. The battery balancer Inductor's temperature has exceeded a pre-determined threshold for a specified amount of time. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.59.11 |
lgpConditionChilledWaterOverTemperatureThe system has detected a chilled water over temperature condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.59.12 |
lgpConditionElectricHeatersOverTemperatureThe system has detected an electric heater over temperature condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.59.13 |
lgpConditionInletAirOverTemperatureThe system has detected an inlet air over temperature condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.59.14 |
lgpConditionSystemOverTempWarningThe system or a component of the system has detected an over temperature condition. The temperature measurement has risen above a normal operating range for a device, or system, defined amount of time. The system is still operational but a threshold has been exceeded. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.59.15 |
lgpConditionHighTemperatureBattStringThe system has detected a high temperature on a battery string. The temperature has exceeded a specified temperature threshold. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.59.16 |
lgpConditionLoadOnAlternateSourceThe system has detected that the load is being supplied by the alternate source. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.60 |
lgpConditionPhaseRotationErrorThis system has detected a phase rotation error condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.61 |
lgpConditionSource1PhaseRotationErrorThe system has detected a phase rotation error on source 1. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.61.1 |
lgpConditionSource2PhaseRotationErrorThe system has detected a phase rotation error on source 2. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.61.2 |
lgpConditionBypassPhaseRotationErrorThe system has detected a phase rotation error on the bypass. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.61.3 |
lgpConditionInputPhaseRotationErrorThe system has detected a phase rotation error on the input. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.61.4 |
lgpConditionControlModuleFailureThis system has detected a control module failure condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.62 |
lgpConditionControlModule1FailureThe system has detected a control module 1 failure. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.62.1 |
lgpConditionHistoryLogFullThe system has detected the history log is full. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.63 |
lgpConditionConfigurationModifiedThe system has detected the configuration has been modified. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.64 |
lgpConditionPasswordModifiedThe system has detected the password has been modified. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.65 |
lgpConditionTimeModifiedThe system has detected the time has been modified. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.66 |
lgpConditionDateModifiedThe system has detected the date has been modified. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.67 |
lgpConditionEventLogClearedThe system has detected the event log has been cleared. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.68 |
lgpConditionHistoryLogClearedThe system has detected the history log has been cleared. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.69 |
lgpConditionUtilityFailureThe system has detected a utility failure. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.70 |
lgpConditionBatteryTestInProgressThe system is performing a battery test at this time. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.71 |
lgpConditionLoadOnBatteryThe system load is being supported by the battery. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.72 |
lgpConditionReplaceBatteryThe system has detected the batteries are due to be replaced. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.74 |
lgpConditionUpsShutdownPendingThe system is in a shutdown pending condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.75 |
lgpConditionBatteryChargerFailedThe system has detected the battery charger has failed. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.76 |
lgpConditionBypassVoltageUnqualifiedThe system has detected the bypass voltage is unqualified. The voltage measurement is outside a pre-determined threshold range for a specified amount of time. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.77 |
lgpConditionCheckAirFilterThe system has detected it is time to check the air filter. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.78 |
lgpConditionBrownOutThe system has detected a brown out condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.79 |
lgpConditionMultipleTransferLockoutThe system has locked out transfers to bypass. Too many transfers have occurred over a specified amount of time. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.80 |
lgpConditionBypassPhaseLostThe system has detected one or more bypass phases are missing. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.81 |
lgpConditionMaintenceBypassInhibitedThe system is preventing a transfer of the load to maintenance bypass. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.82 |
lgpConditionLoadLockedOnBypassAn error has been detected requiring the system to be put into a 'locked on bypass' state. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.83 |
lgpConditionOutputToLoadShortThe system has detected an output to load short circuit condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.84 |
lgpConditionEmergencyTransferToInverterThe system has detected an emergency transfer of the load to inverter. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.85 |
lgpConditonEmergencyPowerOffThe system has detected an Emergency Power Off (EPO) condition. An external EPO switch has cut off the power source to the system. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.86 |
lgpConditionInverterBackFeedThe system has detected an inverter back-feed condition. The inverter is feeding power through the bypass back to the input. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.87 |
lgpConditionDcGroundFaultThe system has detected a DC ground fault. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.88 |
lgpConditionDcGroundFaultPosGround fault current has been detected in the positive DC link to ground. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.88.1 |
lgpConditionDcGroundFaultNegGround fault current has been detected in the negative DC link to ground. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.88.2 |
lgpConditionStaticTransferSwitchInhibitedThe system is preventing the use of the static transfer switch. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.89 |
lgpConditionBatteryLogFullWarningThe system has detected the battery log is approaching the maximum record limit. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.90 |
lgpConditionInputCurrentUnbalancedThe system has detected an unbalanced input current condition. The currents of input phases are out of tolerance. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.91 |
lgpConditionSelfTestFailedThe system has detected a self-test failure. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.92 |
lgpConditionInverterOutOfSynchronizationThe system has detected an Inverter out of sync condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.93 |
lgpConditionModuleAlarmThis system has detected an alarm within the multi-module system. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.94 |
lgpConditioniModuleUnit1AlarmThe multi-module system has detected an alarm condition on unit 1. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.94.1 |
lgpConditioniModuleUnit2AlarmThe multi-module system has detected an alarm condition on unit 2. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.94.2 |
lgpConditioniModuleUnit3AlarmThe multi-module system has detected an alarm condition on unit 3. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.94.3 |
lgpConditioniModuleUnit4AlarmThe multi-module system has detected an alarm condition on unit 4. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.94.4 |
lgpConditioniModuleUnit5AlarmThe multi-module system has detected an alarm condition on unit 5. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.94.5 |
lgpConditioniModuleUnit6AlarmThe multi-module system has detected an alarm condition on unit 6. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.94.6 |
lgpConditioniModuleUnit7AlarmThe multi-module system has detected an alarm condition on unit 7. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.94.7 |
lgpConditioniModuleUnit8AlarmThe multi-module system has detected an alarm condition on unit 8. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.94.8 |
lgpConditionActiveModuleAlarmThe system has detected an active alarm in one, or more, of the sub-modules of the multi-module system. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.95 |
lgpConditionControlFailureThis system has detected a control failure condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.96 |
lgpConditionMainControlFailureThe system has detected a main control failure condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.96.1 |
lgpConditionRedundantControlFailureThe system has detected a redundant control failure condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.96.2 |
lgpConditionParallelSysControlFailureThe parallel system has detected a control failure condition with one of the controls. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.96.3 |
lgpConditionMainControlCommFailureOne or more communications failures have occurred in the main control. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.96.4 |
lgpConditionControlBoardFailureThe system has detected a control board failure. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.96.5 |
lgpConditionHumidifierControlBdFailureHumidifier control board is required to be connected, but no signal is detected. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.96.5.1 |
lgpConditionControlWarningThis system has detected a control warning conditions. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.97 |
lgpConditionMainControlWarningThe system has detected a main control warning condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.97.1 |
lgpConditionRedundantControlWarningThe system has detected a redundant control warning condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.97.2 |
lgpConditionUserInterfaceFailureThe system has detected a user interface control failure condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.98 |
lgpConditionLostPowerRedundancyThe system has detected the number of redundant power modules has fallen below the minimum redundant power module setting. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.99 |
lgpConditionPowerModuleFailureThe system has detected a power module failure condition in the system. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.100 |
lgpConditionBatteryModuleFailureThe system has detected a battery module failure condition in the system. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.101 |
lgpConditionOutputToLoadOffThe system has detected that there is no power being supplied to the load. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.102 |
lgpConditionSystemOffThe system is off. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.103 |
lgpConditionRectifierStartupFailureThe system has detected a rectifier under voltage start-up failure condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.104 |
lgpConditionRectifierFaultThe system has detected a rectifier fault condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.105 |
lgpConditionInverterShutdownLowDcThe system has shutdown the inverter due to a DC bus under voltage. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.106 |
lgpConditionInverterFaultThe system has detected an inverter fault condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.107 |
lgpConditionInverterDcOffsetOverrunThe system has detected an over run of the inverter DC offset voltage. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.108 |
lgpConditionParallelSysLowBatteryWarningThe parallel system has detected a low battery warning condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.109 |
lgpConditionParallelSysLoadShareFaultThe parallel system has detected a load share fault condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.110 |
lgpConditionBatteryFaultThe system has detected a battery fault condition. The battery conductors are either reversed or disconnected. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.111 |
lgpConditionBatteryConverterFailureThe system has detected a battery converter failure condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.112 |
lgpConditionBatteryBalancerFaultThe system has detected a battery balancer fault condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.113 |
lgpConditionpsUpsOperationFaultThe system has detected an operation fault. The UPS attempted to transfer to maintenance bypass without following the proper sequence.deprecated OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.114 |
lgpConditionOutputToLoadOnJointModeThe system load is being supported by both the battery and rectifier. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.115 |
lgpConditionInputNeutralLostThe system had detected the main input neutral is disconnected. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.116 |
lgpConditionLowBatteryWarningThe battery's remaining charge is less than or equal to the configured low threshold. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.117 |
lgpConditionInternalFaultThe system has detected an internal fault. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.118 |
lgpConditionBatteryTestFailedThe system has detected a battery self-test failure. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.119 |
lgpConditionPowerModuleWarningThe system has detected an alarm condition on one, or more, power modules. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.120 |
lgpConditionBatteryModuleWarningThe system has detected an alarm condition on one, or more, battery modules. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.121 |
lgpConditionControlModuleWarningThe system has detected a control module warning. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.122 |
lgpConditionUpsOperationFaultThe system has detected an operation fault. The UPS attempted to transfer to maintenance bypass without following the proper sequence. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.123 |
lgpConditionActiveAlarmThe system has detected an alarm condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.124 |
lgpConditionRectifierCommunicationFailureThe system has detected an internal communication failure condition with the rectifier. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.125 |
lgpConditionInverterCommunicationFailureThe system has detected an internal communication failure condition with the inverter. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.126 |
lgpConditionParallelSysConnectionFaultThe parallel system has detected a connection fault. One or more of the devices are not properly connected. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.127 |
lgpConditionParallelSysCommunicationFailureThe parallel system has detected a communication failure. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.128 |
lgpConditionLostBatteryRedundancyThe system has detected the number of redundant battery modules has fallen below the configured redundant battery module threshold. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.129 |
lgpConditionCompPumpDownFailureThe system has detected that a compressor has failed to pump down. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.130 |
lgpConditionComp1PumpDownFailureThe system has detected that compressor 1 has failed to pump down. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.130.1 |
lgpConditionComp2PumpDownFailureThe system has detected that compressor 2 has failed to pump down. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.130.2 |
lgpConditionChilledWaterLowWaterFlowThe system has detected a chilled water low water flow condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.131 |
lgpConditionChilledWaterLowWaterFlowCircuit2The system has detected a chilled water low water flow condition for circuit 2. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.131.2 |
lgpConditionAirFilterCloggedThe system has detected a air filter clogged condition.deprecated OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.132 |
lgpConditionHumidifierFailureThe system has detected a humidifier failure condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.133 |
lgpConditionRunHoursExceededThe system has detected a pre-determined run hours threshold has been exceeded. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.134 |
lgpConditionUnitRunHrsExceededThe system has detected the system run hours has exceeded the pre-determined threshold. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.134.1 |
lgpConditionComp1RunHrsExceededThe system has detected the compressor 1 run hours has exceeded the pre-determined threshold. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.134.2 |
lgpConditionComp2RunHrsExceededThe system has detected the compressor 2 run hours has exceeded the pre-determined threshold. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.134.3 |
lgpConditionFreeCoolRunHrsExceededThe system has detected the free cooling run hours has exceeded the pre-determined threshold. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.134.4 |
lgpConditionElectricalHeater1RunHrsExceededThe system has detected the electrical heater's run hours have exceeded the pre-determined threshold. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.134.5 |
lgpConditionElectricalHeater2RunHrsExceededThe system has detected the electrical heater's run hours have exceeded the pre-determined limit. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.134.6 |
lgpConditionElectricalHeater3RunHrsExceededThe system has detected the electrical heater's run hours have exceeded the pre-determined limit. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.134.7 |
lgpConditionHotWaterRunHrsExceededThe system has detected the hot water run hours have exceeded the pre-determined threshold. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.134.8 |
lgpConditionHotGasRunHrsExceededThe system has detected the hot gas run hours have exceeded the pre-determined threshold. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.134.9 |
lgpConditionHumidifierRunHrsExceededThe system has detected the humidifier run hours have exceeded the pre-determined threshold. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.134.10 |
lgpConditionDehumidiferRunHrsExceededThe system has detected the dehumidifier run hours have exceeded the pre-determined threshold. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.134.11 |
lgpConditionFanRunHrsExceededThe system has detected the unit blower fan run hours have exceeded the pre-determined threshold. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.134.12 |
lgpConditionCommWarningThe system has detected a loss of communications with another module. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.135 |
lgpConditionCommWarningUnit1The system has detected a loss of communications with unit 1. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.135.1 |
lgpConditionCommWarningUnit2The system has detected a loss of communications with unit 2. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.135.2 |
lgpConditionCommWarningUnit3The system has detected a loss of communications with unit 3. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.135.3 |
lgpConditionCommWarningUnit4The system has detected a loss of communications with unit 4. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.135.4 |
lgpConditionCommWarningUnit5The system has detected a loss of communications with unit 5. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.135.5 |
lgpConditionCommWarningUnit6The system has detected a loss of communications with unit 6. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.135.6 |
lgpConditionCommWarningUnit7The system has detected a loss of communications with unit 7. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.135.7 |
lgpConditionCommWarningUnit8The system has detected a loss of communications with unit 8. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.135.8 |
lgpConditionCommWarningUnit9The system has detected a loss of communications with unit 9. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.135.9 |
lgpConditionCommWarningUnit10The system has detected a loss of communications with unit 10. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.135.10 |
lgpConditionCommWarningUnit11The system has detected a loss of communications with unit 11. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.135.11 |
lgpConditionCommWarningUnit12The system has detected a loss of communications with unit 12. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.135.12 |
lgpConditionCommWarningUnit13The system has detected a loss of communications with unit 13. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.135.13 |
lgpConditionCommWarningUnit14The system has detected a loss of communications with unit 14. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.135.14 |
lgpConditionCommWarningUnit15The system has detected a loss of communications with unit 15. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.135.15 |
lgpConditionCommWarningUnit16The system has detected a loss of communications with unit 16. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.135.16 |
lgpConditionUnitOnThe unit is on. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.136 |
lgpConditionUnitOffThe unit is off. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.137 |
lgpConditionSleepModeOffThe system sleep mode operation has been turned off. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.138 |
lgpConditionPowerOnThe system power is on. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.139 |
lgpConditionSystemOnStanbyThe system is on standby. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.140 |
lgpConditionPowerOffThe system power is off. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.141 |
lgpConditionHighTemperatureGroupThe system has detected a high temperature condition. This group contains various high temperature conditions. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.142 |
lgpConditionHighTemperatureSensor1The temperature has exceeded the high temperature threshold for sensor 1. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.142.1 |
lgpConditionHighTemperatureDigitalScroll1The system has detected a high temperature event on Digital Scroll Compressor 1. The temperature has exceeded a specified temperature threshold. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.142.2 |
lgpConditionHighTemperatureDigitalScroll2The system has detected a high temperature event on Digital Scroll Compressor 2. The temperature has exceeded a specified temperature threshold. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.142.3 |
lgpConditionHighTemperatureUser1The temperature has exceeded the high temperature threshold for user configured temperature sensor 1. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.142.4 |
lgpConditionHighTemperatureInternalThe system has detected a high internal temperature condition. The temperature has exceeded a specified temperature threshold. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.142.5 |
lgpConditionHighTemperatureExternalAirSensorAThe temperature has exceeded the high temperature threshold for external air sensor A. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.142.6 |
lgpConditionHighTemperatureExternalAirSensorBThe temperature has exceeded the high temperature threshold for external air sensor B. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.142.7 |
lgpConditionHighTemperatureRefrigerantSupplyThe temperature has exceeded the high temperature threshold for the refrigerant supply. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.142.8 |
lgpConditionHighTemperatureFluidSupplyThe temperature has exceeded the high temperature threshold for the fluid supply. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.142.9 |
lgpConditionHighTemperatureSupplyAirThe temperature has exceeded the high temperature threshold for the supply air. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.142.10 |
lgpConditionHighTemperatureReturnAirThe temperature has exceeded the high temperature threshold for the return air. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.142.11 |
lgpConditionLowTemperatureGroupThe system has detected a low temperature condition. This group contains various low temperature conditions. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.143 |
lgpConditionLowTemperatureSensor1The temperature is below the low temperature threshold for sensor 1. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.143.1 |
lgpConditionLowTemperatureInternalThe system has detected a low internal temperature condition. The temperature is below a specified temperature threshold. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.143.2 |
lgpConditionLowTemperatureExternalAirSensorAThe temperature is below the low temperature threshold for external air sensor A. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.143.3 |
lgpConditionLowTemperatureExternalAirSensorBThe temperature is below the low temperature threshold for external air sensor B. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.143.4 |
lgpConditionLowTemperatureRefrigerantSupplyThe temperature is below the low temperature threshold for the refrigerant supply. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.143.5 |
lgpConditionLowTemperatureFluidSupplyThe temperature is below the low temperature threshold for the fluid supply. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.143.6 |
lgpConditionLowTemperatureSupplyAirThe temperature is below the low temperature threshold for the supply air. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.143.7 |
lgpConditionHighHumidityGroupThe system has detected a high humidity condition. This group contains various high humidity conditions. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.144 |
lgpConditionHighHumiditySensor1The humidity has exceeded the high humidity threshold for sensor 1. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.144.1 |
lgpConditionHighHumidityReturnAirThe humidity has exceeded the high humidity threshold for the return air. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.144.2 |
lgpConditionLowHumidityGroupThe system has detected a low humidity condition. This group contains various high humidity conditions. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.145 |
lgpConditionLowHumiditySensor1The humidity is below the low humidity threshold for sensor 1. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.145.1 |
lgpConditionLowHumidityReturnAirThe humidity is below the low humidity threshold for the return air. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.145.2 |
lgpConditionPeerNetworkNoMasterThe system is unable to communicate with the master on the peer to peer network. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.146 |
lgpConditionNoOnOffPermissionsThe system lacks the permissions to execute the on/off operation. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.147 |
lgpConditionPeerNetworkFailureThe system has detected a communication failure on the peer to peer network. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.148 |
lgpConditionUnitDisabledThe unit is disabled. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.149 |
lgpConditionUnitShutdownThe system has shutdown. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.150 |
lgpConditionPeerNetworkDiscoveredThe system has established communications on the peer to peer network. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.151 |
lgpConditionLossOfWaterFlowThe system has detected a loss of water flow condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.152 |
lgpConditionCondensatePumpHighWaterThe system has detected high water in the condensate pump. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.153 |
lgpConditionGeneralAlarmThe system has detected a general alarm condition. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.154 |
lgpConditionProductSpecificThe system has detected a product specific condition. This condition is not currently available via the agent card. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.155 |
lgpConditionReheatLockoutThe system has locked out the electrical reheat operation for a specified amount of time. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.156 |
lgpConditionHumidifierLockoutThe system has locked out the humidifier operation for a specified amount of time. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.157 |
lgpConditionCompressorsLockoutThe system has locked out compressor operation for a specified amount of time. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.158 |
lgpConditionCallServiceThe system has detected a condition that requires a service representative be contacted. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.159 |
lgpConditionLowMemoryGroupThis group contains various low memory conditions. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.160 |
lgpConditionLowMemory1The system has detected a low memory condition. The control board is low in memory resources. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.160.1 |
lgpConditionMemoryFailureGroupThis group contains various memory device failure conditions. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.161 |
lgpConditionMemory1FailureThe system has detected a memory 1 module failure. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.161.1 |
lgpConditionMemory2FailureThe system has detected a memory 2 module failure. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.161.2 |
lgpConditionUnitCodeErrorGroupThis group contains various memory device failure conditions. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.162 |
lgpConditionUnitCodeNotConfiguredThe system has detected the unit code is not configured. The unit code must be configured before system start-up. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.162.1 |
lgpConditionUnitCode01OutOfRangeThe system has detected a unit code error. This digit of the unit code value is out of range. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.162.2 |
lgpConditionUnitCode02OutOfRangeThe system has detected a unit code error. This digit of the unit code value is out of range. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.162.3 |
lgpConditionUnitCode03OutOfRangeThe system has detected a unit code error. This digit of the unit code value is out of range. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.162.4 |
lgpConditionUnitCode04OutOfRangeThe system has detected a unit code error. This digit of the unit code value is out of range. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.162.5 |
lgpConditionUnitCode05OutOfRangeThe system has detected a unit code error. This digit of the unit code value is out of range. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.162.6 |
lgpConditionUnitCode06OutOfRangeThe system has detected a unit code error. This digit of the unit code value is out of range. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.162.7 |
lgpConditionUnitCode07OutOfRangeThe system has detected a unit code error. This digit of the unit code value is out of range. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.162.8 |
lgpConditionUnitCode08OutOfRangeThe system has detected a unit code error. This digit of the unit code value is out of range. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.162.9 |
lgpConditionUnitCode09OutOfRangeThe system has detected a unit code error. This digit of the unit code value is out of range. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.162.10 |
lgpConditionUnitCode10OutOfRangeThe system has detected a unit code error. This digit of the unit code value is out of range. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.162.11 |
lgpConditionUnitCode11OutOfRangeThe system has detected a unit code error. This digit of the unit code value is out of range. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.162.12 |
lgpConditionUnitCode12OutOfRangeThe system has detected a unit code error. This digit of the unit code value is out of range. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.162.13 |
lgpConditionUnitCode13OutOfRangeThe system has detected a unit code error. This digit of the unit code value is out of range. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.162.14 |
lgpConditionUnitCode14OutOfRangeThe system has detected a unit code error. This digit of the unit code value is out of range. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.162.15 |
lgpConditionUnitCode15OutOfRangeThe system has detected a unit code error. This digit of the unit code value is out of range. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.162.16 |
lgpConditionUnitCode16OutOfRangeThe system has detected a unit code error. This digit of the unit code value is out of range. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.162.17 |
lgpConditionUnitCode17OutOfRangeThe system has detected a unit code error. This digit of the unit code value is out of range. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.162.18 |
lgpConditionUnitCode18OutOfRangeThe system has detected a unit code error. This digit of the unit code value is out of range. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.162.19 |
lgpConditionHighExternalDewPointThe system has detected a high external dew point condition. The room dew point has exceeded the specified threshold. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.163 |
lgpConditionHcbDisconnectedThe system has detected the humidifier control board is disconnected or not installed. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.164 |
lgpConditionBmsResetTimerExpiredThe BMS fan speed control reset counter has timed out. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.165 |
lgpConditionAgentFirmwareCorruptThe firmware update to the agent card has failed and the firmware is now corrupt. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.166 |
lgpConditionSystemAccessGroupThis group contains various system access conditions. An examples is an open access panel. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.175 |
lgpConditionFrontAccessOpenThe system has detected the front access panel/door is open. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.175.1 |
lgpConditionRearAccessOpenThe system has detected the rear access panel/door is open. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.175.2 |
lgpConditionsDamperFailureThis group contains various damper failure conditions. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.176 |
lgpConditionEmergencyDamperFailureThe system has detected an emergency damper failure. The damper is in the wrong position. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.176.1 |
lgpConditionRemoteShutdownA remote shutdown occurred. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.177 |
lgpConditionFireAlarmFire Alarm. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.178 |
lgpConditionHeatersOverheatedHeaters Overheated. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.179 |
lgpConditionCondenserFailureGroupThis group contains condenser failure conditions. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.180 |
lgpConditionCondenser1FailureCondenser 1 Failure. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.180.1 |
lgpConditionCondenser2FailureCondenser 2 Failure. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.180.2 |
lgpConditionCondenserTVSSFailureThe condenser Transient Voltage Surge Suppressor or Surge Protection Device has failed. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.180.3 |
lgpConditionHumidifierCyclinderWornThe system has detected the humidifier cylinder is worn. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.181 |
lgpConditionUnderCurrentThe system has detected a low current condition. The current of one or more sources in the system has fallen below a threshold for a specified amount of time. The threshold and time that triggered this condition is system dependent. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.182 |
lgpConditionHumidifierUnderCurrentThe system has detected a low current condition on the humidifier. The current of the humidifier has fallen below a pre-determined threshold for a defined amount of time. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.182.1 |
lgpConditionInputUnderCurrentThere is a low current condition on the input power source. The current of the input power source has fallen below a pre-determined threshold for a defined amount of time. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.182.2 |
lgpConditionHeatRejectorGroupThis group contains failure conditions for the heat rejection unit. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.183 |
lgpConditionHeatRejectorFanFailureThe heat rejecter fan has failed. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.183.1 |
lgpConditionHeatRejectorVoltageSuppressionFailureThe heat rejecter voltage suppression has failed and is no longer able to protect the unit from power fluctuations. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.183.2 |
lgpConditionFreeCoolLockoutThe free cooling capability has been disabled. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.184 |
lgpConditionWaterLeakSensorFailureThe sensor used to detect water leaks is not connected or has failed. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.185 |
lgpConditionNoLoadDetectedWarningThere is no load detected on the output. This can be an indication that the output is being powered by an external bypass source and has inadvertently been left on external bypass. This warning is triggered after a delay. The delay is specified by the object 'lgpPwrNoLoadWarningDelay'. The alarm is triggered when the output current falls below a certain threshold specified by the object 'lgpPwrNoLoadWarningLimit' OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.186 |
lgpConditionFirmwareGroupGrouping level for firmware related conditions. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.187 |
lgpConditionFirmwareUpdateRequiredThe firmware on the system or one or more components of the system must be updated. This typically indicates that one or more components of the system contain corrupted firmware or the firmware on one or more components are incompatible with one another. When this condition is active the system may not be able to function to its full capacity or may not be able to function at all. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.187.3 |
lgpConditionTestGroupObjects in this group of conditions are related to testing or test events. This object is never active. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.188 |
lgpConditionTest01This is a 'test' condition. It is a generic test event that can be utilized to evaluate system handling of events. Some products will support the activation of this event upon user request so that user management stations can execute end-to-end event handling tests. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.188.5 |
lgpConditionReceptacleBranchGroupGrouping level for receptacle branch conditions. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.190 |
lgpConditionRcpBranchFailureThe receptacle branch module or control system has failed. Service is required. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.190.5 |
lgpConditionRcpBranchBreakerOpenThe receptacle branch breaker is open. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.190.10 |
lgpConditionInputUnqualifiedThe input is not qualified to provide power to the system. This may be due to system input over-voltage, system input under-voltage, system input frequency out of range, or other similar issues. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.192 |
lgpConditionBypassUnavailableThis summary event is asserted when the bypass is not available. Possible causes include: Bypass Sync Error, Bypass Line Fail, Bypass Overvoltage, Bypass Undervoltage, Bypass Phase Rotation Error, or other similar causes. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.193 |
lgpConditionAutoTransferFailedThe system is failing to automatically transfer the load to the alternate source. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.194 |
lgpConditionSBSUnavailableA Static Bypass Switch (SBS) Failure has been detected. Possible causes include: SBS Phase Open, SBS SCR (Silicon Controlled Rectifier) Shorted, SBS Overload Exceeded, Bypass Power Supply Fail, Static Bypass Switch Fuse Failure, or other similar causes. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.195 |
lgpConditionSBSOverloadOn at least one phase of the static bypass switch (SBS), the power dissipation limit has been exceeded. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.196 |
lgpConditionExcessPulseParallelThe system has performed too many pulse parallel operations within the specified time interval. A pulse parallel operation is a momentary operation of the static bypass switch (SBS) in parallel with the inverter. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.197 |
lgpConditionRemoteBypassSwitchOffExtThe static bypass switch is off due to the state of an external signal. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.198 |
lgpConditionManTransferInhibitedManual transfer from inverter to bypass is inhibited. Bypass is not qualified. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.199 |
lgpConditionManReTransferInhibitedManual retransfer from bypass to inverter is inhibited. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.200 |
lgpConditionBatteryChargeErrorThe battery is not charging properly. Some reasons for this condition include, but are not limited to: battery charger failure, battery failure, etc. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.201 |
lgpConditionBatteryAutoTestInhibitedAutomatic (scheduled) battery tests are inhibited. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.202 |
lgpConditionBatteryChargeReducedExtA reduced battery charging algorithm is being used due to an external signal. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.203 |
lgpConditionBatteryCapacityLowThe battery capacity is low. Some reasons for this condition include, but are not limited to: a battery is offline, the battery age has reduced its capabilities, etc. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.204 |
lgpConditionBatteryTempImbalanceThe temperature difference between two batteries in the system exceeds the predefined threshold. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.205 |
lgpConditionBatteryEqualizeThe rectifier output voltage has been increased to equalize the battery voltage level. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.206 |
lgpConditionBatteryChargeInhibitedExtBattery charging is inhibited due to an external inhibit signal. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.207 |
lgpConditionServiceExtBatteryMonitorGroupThis group contains battery monitor service conditions. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.208 |
lgpConditionServiceExtBatteryMonitor1External battery monitor 1 indicates battery maintenance is required. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.208.1 |
lgpConditionServiceExtBatteryMonitor2External battery monitor 2 indicates battery maintenance is required. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.208.2 |
lgpConditionBatteryGroundFaultBattery system ground fault amperage exceeds the threshold. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.209 |
lgpConditionBatteryLowShutdownWith the battery breaker closed, the battery voltage has dropped below the calculated End-Of-Discharge (EOD) limit. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.210 |
lgpConditionEmergencyPowerOffLocalThe system has detected an Emergency Power Off (EPO) condition. The local EPO switch has cut off the power source to the system. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.211 |
lgpConditionOutputLowPFLaggingThe system has detected a lagging output power factor below the threshold, resulting in reduced load capacity. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.212 |
lgpConditionOutputLowPFLeadingThe system has detected a leading output power factor below the threshold, resulting in reduced load capacity. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.213 |
lgpConditionOutputToLoadFaultThe system has detected an output to load fault. This could be caused by over or under voltage, or by over or under frequency. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.214 |
lgpConditionInvRestartInhibitedExtRestart of the inverter is inhibited by an external signal. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.215 |
lgpConditionInverterShutdownOverloadThe system has shutdown the inverter due to a sustained overload. This event does not indicate if the load has been dropped or transferred to bypass. At least one phase of the inverter power dissipation limit has been exceeded. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.216 |
lgpConditionInverterOffExtThe inverter is off due to the state of an external signal. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.217 |
lgpConditionInputContactGroupThe system has detected an active input contact. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.218 |
lgpConditionInputContact01The system has detected that input contact 1 is active. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.218.1 |
lgpConditionInputContact02The system has detected that input contact 2 is active. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.218.2 |
lgpConditionInputContact03The system has detected that input contact 3 is active. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.218.3 |
lgpConditionInputContact04The system has detected that input contact 4 is active. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.218.4 |
lgpConditionInputContact05The system has detected that input contact 5 is active. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.218.5 |
lgpConditionInputContact06The system has detected that input contact 6 is active. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.218.6 |
lgpConditionInputContact07The system has detected that input contact 7 is active. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.218.7 |
lgpConditionInputContact08The system has detected that input contact 8 is active. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.218.8 |
lgpConditionInputContact09The system has detected that input contact 9 is active. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.218.9 |
lgpConditionInputContact10The system has detected that input contact 10 is active. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.218.10 |
lgpConditionInputContact11The system has detected that input contact 11 is active. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.218.11 |
lgpConditionInputContact12The system has detected that input contact 12 is active. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.218.12 |
lgpConditionInputContact13The system has detected that input contact 13 is active. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.218.13 |
lgpConditionInputContact14The system has detected that input contact 14 is active. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.218.14 |
lgpConditionInputContact15The system has detected that input contact 15 is active. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.218.15 |
lgpConditionInputContact16The system has detected that input contact 16 is active. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.218.16 |
lgpConditionRectifierOperInhibitedThe operation of the rectifier is inhibited by an external signal. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.219 |
lgpConditionBypassBackFeedBrkrOpenThe bypass backfeed breaker is in the open position. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.220 |
lgpConditionAutoRestartInProgressAuto restart is in progress. Becomes inactive when auto restart completes or fails. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.221 |
lgpConditionAutoRestartInhibitedExtAuto restart is inhibited due to an external signal. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.222 |
lgpConditionAutoRestartFailedAuto restart has failed. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.223 |
lgpConditionInputOnGeneratorA generator is supplying the power to the system. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.224 |
lgpConditionInputFilterCycleLockThe input filter disconnect has opened too many times within a given period of time. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.225 |
lgpConditionServiceCodeActiveThe system is in an operational mode intended for testing. In normal operating conditions, the system should not be in this state. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.226 |
lgpConditionLoadBusSyncActiveLoad Bus Sync Operation is active. This synchronizes the UPS output with the output of another UPS. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.227 |
lgpConditionLoadBusSyncInhibitedThe system has detected that conditions to perform Load Bus Sync Operation are not satisfied. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.228 |
lgpConditionControlsResetRequiredA controls reset is required because one or more critical settings have changed. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.229 |
lgpConditionEquipTempSensorFailedA temperature sensor is reporting a value outside the bounds of a properly operating sensor. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.230 |
lgpConditionInputCurrentImbalanceThe current on one input phase is much greater or lower than the average current of all the phases. This may indicate improper operation of the rectifier or input filter. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.231 |
lgpConditionPumpGroupThe system has detected an alarm with one of the pumps. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.232 |
lgpConditionPumpFlowLossThe system has detected a loss of flow with one or more pumps. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.232.1 |
lgpConditionPump1FlowLossThe system has detected a loss of flow with pump 1. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.232.1.1 |
lgpConditionPump2FlowLossThe system has detected a loss of flow with pump 2. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.232.1.2 |
lgpConditionPumpShortCycleThe system has detected a short cycling of the pumps. One or more of the pumps has been turned on and off a number of times within a specified time period. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.232.2 |
lgpConditionPumpInverterShortCycleThe system has detected a short cycling of one or more pump inverters and has temporarily locked out further pump operation to protect from thermal overload. A short cycle is defined as powering on and off a number of times over a set time period. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.232.3 |
lgpConditionPump1InverterShortCycleThe system has detected a short cycling of the inverter for pump 1 and has temporarily locked out further pump operation to protect from thermal overload. A short cycle is defined as powering on and off a number of times over a set time period. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.232.3.1 |
lgpConditionPump2InverterShortCycleThe system has detected a short cycling of the inverter for pump 2 and has temporarily locked out further pump operation to protect from thermal overload. A short cycle is defined as powering on and off a number of times over a set time period. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.232.3.2 |
lgpConditionValveGroupThe system has detected an alarm with one of the valves. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.233 |
lgpConditionChilledWaterValvePositionThe system has detected a problem with the chilled water valve position. The position of the chilled water control valve does not match an expected value. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.233.1 |
lgpConditionCondensationDetectedThe system has detected condensation. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.234 |
lgpConditionMaintenanceGroupThe system has detected a maintenance condition. This group contains various maintenance conditions. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.235 |
lgpConditionMaintenanceDueSystem is due for maintenance. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.235.1 |
lgpConditionMaintenanceCompleteThe system maintenance has been completed. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.235.2 |
lgpConditionExternalEventSignalGroupThis group contains various conditions signalled by external inputs. Each event is deactivated when the signal is inactive. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.236 |
lgpConditionExternalFireDetectFire detected, as indicated by an external input signal. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.236.1 |
lgpConditionExternalFlowLossLoss of flow is detected, as indicated by an external input signal. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.236.2 |
lgpConditionExternalReheatLockoutThe reheater is shut down and disabled by an external input signal. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.236.3 |
lgpConditionExternalOverTempA temperature has exceeded its threshold, as indicated by an external input signal. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.236.4 |
lgpConditionExternalCompLockoutThe compressor is shut down and disabled by an external input signal. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.236.5 |
lgpConditionExternalHumidifierLockoutThe humidifier is shut down and disabled by an external input signal. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.236.6 |
lgpConditionComponentShutdownGroupThis group contains conditions signaling shutdown of various system components. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.237 |
lgpConditionComponentShutdownPartialAn event has occurred requiring some system components to be shutdown and disabled. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.237.1 |
lgpConditionComponentShutdownHighPowerSupply to high power components has been shutdown. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.237.2 |
lgpConditionCondenserProblemGroupThis group contains condenser conditions. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.238 |
lgpConditionCondenser1ProblemCondenser 1 is not operating within its normal parameters. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.238.1 |
lgpConditionHumidityOutOfPropBandThe system has detected a humidity reading that remained outside of the proportional control band for an extended period of time. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.239 |
lgpConditionEnvRemoteSensorGroupThis group contains remote sensors. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.240 |
lgpConditionEnvRemoteSensor1IssueRemote sensor is disconnected or the signal is out of range. The event is deactivated when sensor signal is re-established. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.240.1 |
lgpConditionEnvRemoteSensor2IssueRemote sensor is disconnected or the signal is out of range. The event is deactivated when sensor signal is re-established. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.240.2 |
lgpConditionEnvRemoteSensor3IssueRemote sensor is disconnected or the signal is out of range. The event is deactivated when sensor signal is re-established. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.240.3 |
lgpConditionEnvRemoteSensor4IssueRemote sensor is disconnected or the signal is out of range. The event is deactivated when sensor signal is re-established. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.240.4 |
lgpConditionEnvRemoteSensor5IssueRemote sensor is disconnected or the signal is out of range. The event is deactivated when sensor signal is re-established. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.240.5 |
lgpConditionEnvRemoteSensor6IssueRemote sensor is disconnected or the signal is out of range. The event is deactivated when sensor signal is re-established. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.240.6 |
lgpConditionEnvRemoteSensor7IssueRemote sensor is disconnected or the signal is out of range. The event is deactivated when sensor signal is re-established. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.240.7 |
lgpConditionEnvRemoteSensor8IssueRemote sensor is disconnected or the signal is out of range. The event is deactivated when sensor signal is re-established. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.240.8 |
lgpConditionEnvRemoteSensor9IssueRemote sensor is disconnected or the signal is out of range. The event is deactivated when sensor signal is re-established. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.240.9 |
lgpConditionEnvRemoteSensor10IssueRemote sensor is disconnected or the signal is out of range. The event is deactivated when sensor signal is re-established. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.240.10 |
lgpConditionNeutralSnubberBoardCommFailureThe Neutral Snubber board has stopped communicating. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.241 |
lgpConditionRedundantChargerFailureThe redundant charger has failed. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.242 |
lgpConditionBoardInputContactorPowerFailureBoard input contactor power failure. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.243 |
lgpConditionBoard1InputContactorPowerFailureBoard1 input contactor power failure. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.243.1 |
lgpConditionBoard2InputContactorPowerFailureBoard2 input contactor power failure. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.243.2 |
lgpConditionTooManySensorsThe number of sensors installed on the device has exceeded the pre-determined limit. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.5423 |
lgpConditionDoorSwitchOpenAn open door has been detected. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.5471 |
lgpConditionContactClosureOpenAn open circuit has been detected. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.5479 |
lgpConditionContactClosureClosedA closed circuit has been detected. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.5480 |
lgpConditionSensorsNotDisplayedThe number of sensors that can be displayed (monitored) on the device has exceeded the pre-determined limit. Note this condition differs from the lgpConditionTooManySensors in that the system may currently have less than the maximum of installed sensors present but one or more of those sensors can not be displayed because the display order table (lgpPduAuxMeasOrderTable) contains entries for sensors that are not currently installed. This condition effectively prevents one or more installed sensors from being presented in the lgpPduAuxMeasTable. It is possible for both this condition and the lgpConditionTooManySensors condition to be active at the same time. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.1.6119 |
lgpConditionsPresentThe present number of conditions (rows) in the lgpConditionsTable.ro Gauge32 .1.3.6.1.4.1.476.1.42.3.2.2 |
lgpConditionsTableA list of condition table entries. The table contains zero, one, or many rows at any moment, depending upon the number of conditions in effect. The number of rows in the table is given by (lgpConditionsPresent). The table is initially empty at agent startup. The agent creates a row in the table each time a condition is detected and deletes that row subject to the following rules: Rows are removed from the table based on the following rules: 1. If a condition does not require acknowledgement (see 'lgpConditionAckReq') the condition is removed as soon as the issue clears (see 'lgpConditionCurrentState'). 2. If a condition requires acknowledgement (see 'lgpConditionAckReq') the condition is removed as soon as the issue clears (see 'lgpConditionCurrentState') AND the condition is acknowledged (see 'lgpConditionAcknowledged'). 3. If the columns 'lgpConditionCurrentState' and 'lgpConditionAcknowledged' are not present for the condition then the condition will be removed as soon as the issue causing the condition clears. The agent creates the first row with lgpConditionId equal to 1, and increments the value of 'lgpConditionId' each time a new row is created, wrapping to the first free value greater than or equal to 1 when the maximum value of lgpConditionId would otherwise be exceeded. The number of rows in the table at any given time is reflected by the value of 'lgpConditionsPresent'. SEQUENCE OF LgpConditionEntry .1.3.6.1.4.1.476.1.42.3.2.3 |
lgpConditionEntryThis entry defines the contents of the rows for the table 'lgpConditionsTable'. A row in this table cannot be created or deleted by SNMP operations on columns of the table. LgpConditionEntry .1.3.6.1.4.1.476.1.42.3.2.3.1 |
lgpConditionIdA unique identifier for a condition. This value must remain constant between agent initializations. This OID is used as an index to identify a row in the table 'lgpConditionsTable'.ro Unsigned32 .1.3.6.1.4.1.476.1.42.3.2.3.1.1 |
lgpConditionDescrA reference to a condition description object. The object referenced should not be accessible, but rather be used to provide a unique description.ro OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.3.1.2 |
lgpConditionTimeThe value of sysUpTime when the condition occurred (became active).ro TimeTicks (SNMPv2-SMI) .1.3.6.1.4.1.476.1.42.3.2.3.1.3 |
lgpConditionTableRefThis object will be included as a varbind in some rows of the table. It is a reference to a table object in the MIB. The value of this object will be the OID of a table that the object that the condition applies to is defined. The table row corresponding to this object will also contain a varbind 'lgpConditionTableRowRef' that will specify which instance (row) in the referenced table the object is defined in. Example: TABLE ROW: lgpConditionId 5 lgpConditionDescr lgpConditionRcpBranchBreakerOpen lgpConditionTime 393884848 lgpConditionTableRef lgpPduRbTable lgpConditionTableRowRef lgpPduRbEntryId.1.4 lgpConditionType alarm lgpConditionCurrentState active lgpConditionSeverity major lgpConditionAcknowledged acknowledged lgpConditionAckReq required In the above example the breaker opened for a Receptacle branch. The specific receptacle branch is specified by the additional varbind (lgpEventParmTableRowRef). In this case the notification is for the 4th receptacle branch on the 1st PDU in the cluster.ro OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.3.1.5 |
lgpConditionTableRowRefThis is a reference to the (cell) in the table specified by the companion varbind (lgpConditionTableRef) in this condition. The row in the table where this cell exists represents the object that this condition applies to. Example: TABLE ROW: lgpConditionId 5 lgpConditionDescr lgpConditionRcpBranchBreakerOpen lgpConditionTime 393884848 lgpConditionTableRef lgpPduRbTable lgpConditionTableRowRef lgpPduRbEntryId.1.4 lgpConditionType lgpConditionCurrentState active lgpConditionSeverity major lgpConditionAcknowledged acknowledged lgpConditionAckReq required The table containing the definition of the receptacle branch (lgpPduRbTable) is given by the varbind (lgpConditionTableRef) The specific receptacle branch (instance) is specified by the varbind (lgpConditionTableRowRef). In this case the condition is for the 4th receptacle branch on the 1st PDU in the PDU cluster. If one wanted to retrieve the serial number for this receptacle branch the OID would be: lgpPduRbEntrySerialNum.1.4.ro OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.3.1.6 |
lgpConditionTypeThe type of condition in this row in the table.ro Enumeration .1.3.6.1.4.1.476.1.42.3.2.3.1.10 |
lgpConditionCurrentStateIndication of the current state of the event. If the state is 'active' then the condition currently exists. If the state is 'inactive' then the condition no longer exists (i.e. the situation causing the condition has cleared or been resolved). The behavior of some devices is to remove the condition from this table when the condition clears. The behavior of other devices is to leave the condition entry in the table until the condition is acknowledged ( see lgpConditionAcknowledged and lgpConditionAckReq).ro Enumeration .1.3.6.1.4.1.476.1.42.3.2.3.1.12 |
lgpConditionSeverityThis represents the relative severity of the condition.ro Enumeration .1.3.6.1.4.1.476.1.42.3.2.3.1.14 |
lgpConditionAcknowledgedThis indicates if the condition has been acknowledged. If the value is 'notAcknowledged' then the condition has not been acknowledged. If the value is 'acknowledged' then the condition has been acknowledged. Writing a value of 'acknowledged' to this object acknowledges the condition and the value will be changed to 'acknowledged'. If the current state of the condition is 'active' (see lgpConditionCurrentState) the condition will, for all devices remain in the table regardless of the state of the 'lgpConditionAcknowledged' object. If the 'lgpConditionAckReq' is 'notRequired' or this column does not exist for the row then this object has no affect on the duration the condition stays in the lgpConditionsTable. If the 'lgpConditionAckReq' is 'required' then the condition will remain in the condition table until both the 'lgpConditionCurrentState' is 'inactive' AND 'lgpConditionAcknowledged' is 'acknowledged'.rw Enumeration .1.3.6.1.4.1.476.1.42.3.2.3.1.18 |
lgpConditionAckReqThis indicates if the corresponding condition does or does not require user acknowledgement. Conditions that require user acknowledgement will have a value of 'required'. Those conditions that do not require user acknowledgement will have a value of 'notRequired' or in some devices the column may not be present at all. If a condition requires acknowledgement it will remain in the table until both the 'lgpConditionCurrentState' and 'lgpConditionAcknowledged' are 'inactive' and 'acknowledged' respectively (see lgpConditionAcknowledged). If a condition does not require acknowledgement it will be removed from the table as soon as its 'lgpConditionCurrentState' is 'inactive'.ro Enumeration .1.3.6.1.4.1.476.1.42.3.2.3.1.19 |
lgpConditionControl OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.4 |
lgpConditionControlEventResetEvent Reset Command. This command will reset all of the device's events. On some units, when an event is activated, a 'set' field is also marked and maintained even when the event has become inactive. The 'set' field is only cleared when the user clears it and the event is no longer active. This item will clear the 'set' field for all events that are not active.rw Enumeration .1.3.6.1.4.1.476.1.42.3.2.4.1 |
lgpConditionControlEventAckEvent Acknowledge Command. This command will acknowledge all of the device's events.rw Enumeration .1.3.6.1.4.1.476.1.42.3.2.4.2 |
lgpConditionControlTableA list of condition control table entries. The table contains zero, one, or many rows at any moment, depending upon the number of conditions that are controllable by the unit. This table does not necessarily contain all conditions supported by the unit. This table only contains conditions that are end-user modifiable. SEQUENCE OF LgpConditionControlEntry .1.3.6.1.4.1.476.1.42.3.2.4.20 |
lgpConditionControlEntryThis entry defines the contents of the rows for the table 'lgpConditionControlTable'. A row in this table cannot be created or deleted by user initiated SNMP operations on columns of the table. LgpConditionControlEntry .1.3.6.1.4.1.476.1.42.3.2.4.20.1 |
lgpConditionControlIndexThis is the index indicating the nth element of the table. Unsigned32 .1.3.6.1.4.1.476.1.42.3.2.4.20.1.1 |
lgpConditionControlDescrA reference to an Object Identifier (OID) representing a unique condition. The referenced OID is used solely for identification purposes. The object identifier referenced here will be the same object identifier referenced in the lgpConditionsTable (column: lgpConditionDescr) when the condition is activated.ro OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.4.20.1.2 |
lgpConditionControlEnableStatusThe value in this column determines if the device is currently capable of generating this event. If the value is 'enabled' then the event will be generated if the condition indicated by lgpConditionControlDescr becomes active. If the value is 'disabled' the device will never generate the event. This value is stored on the managed device. Some devices do not allow write access to some entries in this column. The 'lgpConditionControlEnableCapability' column indicates whether this entry can be written.rw Enumeration .1.3.6.1.4.1.476.1.42.3.2.4.20.1.3 |
lgpConditionControlTypeThe 'type' assigned or configured for this condition. The value assigned to the condition here is displayed in the lgpConditionsTable (column: lgpConditionType). For some units this is user configurable. This value is stored on the managed device.rw Enumeration .1.3.6.1.4.1.476.1.42.3.2.4.20.1.4 |
lgpConditionControlEnableCapabilitySome devices do not allow write access to some entries in the 'lgpConditionControlEnableStatus' column. This column indicates whether the 'lgpConditionControlEnableStatus' entry for this row can be written.ro Enumeration .1.3.6.1.4.1.476.1.42.3.2.4.20.1.5 |
lgpConditionDescriptionThe ASCII text description for the condition.ro DisplayString .1.3.6.1.4.1.476.1.42.3.2.5 |
lgpNetworkNameThe network name in a node.domain.com like format. This object is intended to be used as a varbind object by other notifications that have a context of a network address. As an example the lgpAgentDnsLookupFailure trap which describes a network name that is failing or has failed to be resolved from a Domain Name Service (DNS) lookup. Refer to RFC 952 for further information.ro DisplayString .1.3.6.1.4.1.476.1.42.3.2.6 |
lgpFlexConditions OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.2.7 |