Home/Catalog/LIEBERT-MICRO-UPS-MIB

LIEBERT-MICRO-UPS-MIB

Detailed view of the defined objects, syntax rules, and hierarchical paths.

43
Objects
Active
Status
4
Dependencies

Imported Objects

Objects

43 total
Object Name
emerson
OBJECT IDENTIFIER
.1.3.6.1.4.1.476
RFC1155-SMI
Unknown
.1.3.6.1.4.1.476
liebertCorp
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1
liebertUps
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1
luExtensions
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1
luCore
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.1
lcUpsIdent
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.1.1
lcUpsIdentManufacturerThe UPS manufacturer.ro
DisplayString
.1.3.6.1.4.1.476.1.1.1.1.1.1
lcUpsIdentModelThe UPS Model designation.rw
DisplayString
.1.3.6.1.4.1.476.1.1.1.1.1.2
lcUpsIdentSoftwareVersionThe UPS SNMP Agent software version.ro
DisplayString
.1.3.6.1.4.1.476.1.1.1.1.1.3
lcUpsIdentSpecificA reference to MIB definitions specific to the particular UPS being managed. This object is used to locate the product-specific MIB for this device. If this information is not present, its value should be the OBJECT IDENTIFIER { 0 0 }, which is a syntactically valid object identifier, and any conformant implementation of ASN.1 and BER must be able to generate and recognize this value.ro
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.1.1.4
lcUpsAlarm
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.1.6
lcUpsAlarmsThe current number of alarm conditions.ro
Gauge
.1.3.6.1.4.1.476.1.1.1.1.6.1
lcUpsAlarmTable
SEQUENCE OF LcUpsAlarmEntry
.1.3.6.1.4.1.476.1.1.1.1.6.2
lcUpsAlarmEntry
LcUpsAlarmEntry
.1.3.6.1.4.1.476.1.1.1.1.6.2.1
lcUpsAlarmIdA unique identifier for an alarm condition. This value must remain constant between agent initializations.ro
INTEGER
.1.3.6.1.4.1.476.1.1.1.1.6.2.1.1
lcUpsAlarmDescrA reference to an alarm description object. The object referenced should not be accessible, but rather be used to provide a unique description of the alarm condition.ro
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.1.6.2.1.2
lcUpsAlarmTimeThe value of sysUpTime when the alarm condition occured.ro
TimeTicks (SNMPv2-SMI)
.1.3.6.1.4.1.476.1.1.1.1.6.2.1.3
lcUpsAlarmConditions
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.1.6.3
lcUpsAlarmLowBatteryWarning
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.1.6.3.1
lcUpsAlarmOnBattery
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.1.6.3.10
lcUpsAlarmStopNoticeIssued
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.1.6.3.11
lcUpsControl
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.1.8
lcUpsControlUnixShutdownDelaySetting this object causes the agent to instruct the UPS to perform a UNIX Shutdown in the indicated number of seconds. The agent counts down the number of seconds until the event will take place. A Unix shutdown is only valid if the UPS is on Battery. During a UNIX Shutdown, the UPS will turn off the output even if the Utility comes back on line before the shutdown time arrives. Note that different models have different clock resolutions, usually greater than 1 second. As a result, the command will only be accurate to the resolution of the UPS's clock. The command can be cancelled by setting lcUpsControlCancelCommand to the value 'cancel'.rw
INTEGER
.1.3.6.1.4.1.476.1.1.1.1.8.5
lcUpsControlUnixShutdownTrapDelayWhen 'lcUpsControlUnixShutdownDelay' reaches a value less than or equal to this object's value, an lcUpsUnixShutdownWarningTrap will be produced and this object will be reset to 0.rw
INTEGER
.1.3.6.1.4.1.476.1.1.1.1.8.6
lcUpsControlCancelCommandsSetting this variable to 'cancel' will cause the agent to issue instructions to the UPS to cancel all outstanding commands, such as lcUpsControlOutputOff, lcUpsControlOutputOn, lcUpsControlUnixShutdown.rw
Enumeration
.1.3.6.1.4.1.476.1.1.1.1.8.7
lcUpsControlRebootAgentDelaySetting this object causes the agent to reboot after the indicated number of seconds have expired. The value will count down until the event takes place. The command can be cancelled by setting lcUpsControlCancleCommand to the value cancel.rw
INTEGER
.1.3.6.1.4.1.476.1.1.1.1.8.8
lcUpsNominal
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.1.9
lcUpsNominalOutputVoltageThe nominal output voltage. (Unit of measure: volt)rw
INTEGER
.1.3.6.1.4.1.476.1.1.1.1.9.1
lcUpsNominalInputVoltageThe nominal input voltage. (Unit of measure: volt)rw
INTEGER
.1.3.6.1.4.1.476.1.1.1.1.9.2
lcUpsNominalOutputVAThe nominal Volt-Amp rating.rw
INTEGER
.1.3.6.1.4.1.476.1.1.1.1.9.3
lcUpsNominalOutputWattsThe nominal power rating. (Unit of measure: watt)rw
INTEGER
.1.3.6.1.4.1.476.1.1.1.1.9.4
lcUpsNominalOutputFreqThe nominal output frequency. (Unit of measure: Hertz)rw
INTEGER
.1.3.6.1.4.1.476.1.1.1.1.9.5
lcUpsNominalInputFreqThe nominal input frequency. (Unit of measure: Hertz)rw
INTEGER
.1.3.6.1.4.1.476.1.1.1.1.9.6
lcUpsTraps
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.1.11
lcUpsOnBatteryTrapAn lcUpsOnBatteryTrap signifies that the UPS is currently on Battery Power.
TRAP-TYPE
.1.3.6.1.4.1.476.1.1.1.1.11.0.3
lcUpsLowBatteryWarningTrapAn lcUpsLowBatteryWarningTrap signifies that the UPS has entered a Low Battery state.
TRAP-TYPE
.1.3.6.1.4.1.476.1.1.1.1.11.0.4
lcUpsAlarmTrapAn Alarm condition has occurred and is being reported in the lcUpsAlarmTable.
TRAP-TYPE
.1.3.6.1.4.1.476.1.1.1.1.11.0.11
lcUpsUnixShutdownTrapAn lcUpsUnixShutodwnTrap is sent 2 seconds before the UPS is scheduled to perform a Unix Shutdown.
TRAP-TYPE
.1.3.6.1.4.1.476.1.1.1.1.11.0.16
lcUpsUnixShutdownWarningTrapAn lcUpsUnixShutdownWarningTrap is sent when the lcUpsControlUnixShudownDelay reaches the value of lcUpsControlUnixShutdownTrapDelay.
TRAP-TYPE
.1.3.6.1.4.1.476.1.1.1.1.11.0.17
luExternal
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.1.6
luExperimental
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.2
luPrivate
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.1.3

More MIBs from Liebert

Browse all LiebertMIBs →
LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB

The LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB enables SNMP-based monitoring and management of Liebert GP series power and environmental control units, specifically exposing configurable alarm thresholds and conditional logic states for critical infrastructure parameters. This module facilitates the retrieval of dynamic condition variables and event triggers to automate fault detection and response within data center power distribution and cooling systems.

727 objects→
LIEBERT-GP-CONDITIONS-MIB

The LIEBERT-GP-CONDITIONS-MIB defines the Liebert-specific Object Identifiers required to monitor environmental conditions and operational states of Liebert GP series power and cooling infrastructure. This module enables the retrieval of critical telemetry data, including temperature, humidity, and alarm status, from Liebert network management agents via the SNMP protocol.

639 objects→
LIEBERT-GP-ENVIRONMENTAL-MIB

The LIEBERT-GP-ENVIRONMENTAL-MIB enables SNMP-based monitoring of Liebert GP-series precision cooling units and environmental control systems, specifically exposing metrics for temperature, humidity, airflow, and alarm states. This module facilitates the collection of critical facility infrastructure data required for data center thermal management and environmental fault detection.

295 objects→
LIEBERT-UPS-MIB

Standard SNMP MIB module defining data structures for LIEBERT-UPS-MIB.

278 objects→
LIEBERT-GP-POWER-MIB

The LIEBERT-GP-POWER-MIB enables SNMP monitoring of Liebert GP-series power distribution units and UPS systems, exposing critical metrics such as input/output voltage, current, frequency, load percentage, battery status, and alarm conditions. This module facilitates real-time telemetry collection for power infrastructure health assessment and fault detection within data center environments.

258 objects→
LIEBERT-GP-PDU-MIB

SNMP MIB module

245 objects→