LIEBERT-MICRO-UPS-MIB
Detailed view of the defined objects, syntax rules, and hierarchical paths.
43
Objects
Active
Status
4
Dependencies
Imported Objects
Objects
43 total| Object Name |
|---|
emerson OBJECT IDENTIFIER .1.3.6.1.4.1.476 |
RFC1155-SMI Unknown .1.3.6.1.4.1.476 |
liebertCorp OBJECT IDENTIFIER .1.3.6.1.4.1.476.1 |
liebertUps OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.1 |
luExtensions OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.1.1 |
luCore OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.1.1.1 |
lcUpsIdent OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.1.1.1.1 |
lcUpsIdentManufacturerThe UPS manufacturer.ro DisplayString .1.3.6.1.4.1.476.1.1.1.1.1.1 |
lcUpsIdentModelThe UPS Model designation.rw DisplayString .1.3.6.1.4.1.476.1.1.1.1.1.2 |
lcUpsIdentSoftwareVersionThe UPS SNMP Agent software version.ro DisplayString .1.3.6.1.4.1.476.1.1.1.1.1.3 |
lcUpsIdentSpecificA reference to MIB definitions specific to the
particular UPS being managed. This object is
used to locate the product-specific MIB for this
device.
If this information is not present, its value
should be the OBJECT IDENTIFIER { 0 0 },
which is a syntactically valid object identifier,
and any conformant implementation of ASN.1 and BER
must be able to generate and recognize this
value.ro OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.1.1.1.1.4 |
lcUpsAlarm OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.1.1.1.6 |
lcUpsAlarmsThe current number of alarm conditions.ro Gauge .1.3.6.1.4.1.476.1.1.1.1.6.1 |
lcUpsAlarmTable SEQUENCE OF LcUpsAlarmEntry .1.3.6.1.4.1.476.1.1.1.1.6.2 |
lcUpsAlarmEntry LcUpsAlarmEntry .1.3.6.1.4.1.476.1.1.1.1.6.2.1 |
lcUpsAlarmIdA unique identifier for an alarm condition. This
value must remain constant between agent
initializations.ro INTEGER .1.3.6.1.4.1.476.1.1.1.1.6.2.1.1 |
lcUpsAlarmDescrA reference to an alarm description object. The
object referenced should not be accessible, but
rather be used to provide a unique description of
the alarm condition.ro OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.1.1.1.6.2.1.2 |
lcUpsAlarmTimeThe value of sysUpTime when the alarm condition
occured.ro TimeTicks (SNMPv2-SMI) .1.3.6.1.4.1.476.1.1.1.1.6.2.1.3 |
lcUpsAlarmConditions OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.1.1.1.6.3 |
lcUpsAlarmLowBatteryWarning OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.1.1.1.6.3.1 |
lcUpsAlarmOnBattery OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.1.1.1.6.3.10 |
lcUpsAlarmStopNoticeIssued OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.1.1.1.6.3.11 |
lcUpsControl OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.1.1.1.8 |
lcUpsControlUnixShutdownDelaySetting this object causes the agent to instruct
the UPS to perform a UNIX Shutdown in the indicated
number of seconds. The agent counts down the number
of seconds until the event will take place. A Unix
shutdown is only valid if the UPS is on Battery.
During a UNIX Shutdown, the UPS will turn off the
output even if the Utility comes back on line before
the shutdown time arrives. Note that different models
have different clock resolutions, usually greater
than 1 second. As a result, the command will only
be accurate to the resolution of the UPS's clock.
The command can be cancelled by setting
lcUpsControlCancelCommand to the value 'cancel'.rw INTEGER .1.3.6.1.4.1.476.1.1.1.1.8.5 |
lcUpsControlUnixShutdownTrapDelayWhen 'lcUpsControlUnixShutdownDelay' reaches a value
less than or equal to this object's value, an
lcUpsUnixShutdownWarningTrap will be produced and
this object will be reset to 0.rw INTEGER .1.3.6.1.4.1.476.1.1.1.1.8.6 |
lcUpsControlCancelCommandsSetting this variable to 'cancel' will cause the
agent to issue instructions to the UPS to cancel all
outstanding commands, such as lcUpsControlOutputOff,
lcUpsControlOutputOn, lcUpsControlUnixShutdown.rw Enumeration .1.3.6.1.4.1.476.1.1.1.1.8.7 |
lcUpsControlRebootAgentDelaySetting this object causes the agent to reboot after
the indicated number of seconds have expired. The
value will count down until the event takes place.
The command can be cancelled by setting
lcUpsControlCancleCommand to the value cancel.rw INTEGER .1.3.6.1.4.1.476.1.1.1.1.8.8 |
lcUpsNominal OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.1.1.1.9 |
lcUpsNominalOutputVoltageThe nominal output voltage. (Unit of measure:
volt)rw INTEGER .1.3.6.1.4.1.476.1.1.1.1.9.1 |
lcUpsNominalInputVoltageThe nominal input voltage. (Unit of measure:
volt)rw INTEGER .1.3.6.1.4.1.476.1.1.1.1.9.2 |
lcUpsNominalOutputVAThe nominal Volt-Amp rating.rw INTEGER .1.3.6.1.4.1.476.1.1.1.1.9.3 |
lcUpsNominalOutputWattsThe nominal power rating. (Unit of measure:
watt)rw INTEGER .1.3.6.1.4.1.476.1.1.1.1.9.4 |
lcUpsNominalOutputFreqThe nominal output frequency. (Unit of measure:
Hertz)rw INTEGER .1.3.6.1.4.1.476.1.1.1.1.9.5 |
lcUpsNominalInputFreqThe nominal input frequency. (Unit of measure:
Hertz)rw INTEGER .1.3.6.1.4.1.476.1.1.1.1.9.6 |
lcUpsTraps OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.1.1.1.11 |
lcUpsOnBatteryTrapAn lcUpsOnBatteryTrap signifies that the
UPS is currently on Battery Power. TRAP-TYPE .1.3.6.1.4.1.476.1.1.1.1.11.0.3 |
lcUpsLowBatteryWarningTrapAn lcUpsLowBatteryWarningTrap signifies that the
UPS has entered a Low Battery state. TRAP-TYPE .1.3.6.1.4.1.476.1.1.1.1.11.0.4 |
lcUpsAlarmTrapAn Alarm condition has occurred and is being reported
in the lcUpsAlarmTable. TRAP-TYPE .1.3.6.1.4.1.476.1.1.1.1.11.0.11 |
lcUpsUnixShutdownTrapAn lcUpsUnixShutodwnTrap is sent 2 seconds before
the UPS is scheduled to perform a Unix Shutdown. TRAP-TYPE .1.3.6.1.4.1.476.1.1.1.1.11.0.16 |
lcUpsUnixShutdownWarningTrapAn lcUpsUnixShutdownWarningTrap is sent when the
lcUpsControlUnixShudownDelay reaches the value of
lcUpsControlUnixShutdownTrapDelay. TRAP-TYPE .1.3.6.1.4.1.476.1.1.1.1.11.0.17 |
luExternal OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.1.1.6 |
luExperimental OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.1.2 |
luPrivate OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.1.3 |