LIEBERT-GP-NOTIFICATIONS-MIB
AI MIB Summary
The LIEBERT-GP-NOTIFICATIONS-MIB defines the SNMP trap and notification structures for Liebert GP series precision power and cooling equipment, enabling the transmission of real-time alarm and status events regarding environmental conditions, power supply health, and system faults. This module facilitates immediate alerting for critical infrastructure failures, such as temperature thresholds, fan failures, or UPS battery depletion, within Liebert-managed data center environments.
The MIB module used to register Liebert SNMP OIDs.
Copyright 2000-2008 Liebert Corporation. All rights reserved. Reproduction of this document is authorized on the condition that the forgoing copyright notice is included.
This Specification is supplied 'AS IS' and Liebert Corporation makes no warranty, either express or implied, as to the use, operation, condition, or performance of the Specification.
Main OID:
liebertGlobalProductsNotificationsModule.1.3.6.1.4.1.476.1.42.1.4.1
29
Objects
Active
Status
4
Dependencies
Imported Objects
Objects
29 total| Object Name |
|---|
liebertGlobalProductsNotificationsModuleThe MIB module used to register Liebert SNMP OIDs.
Copyright 2000-2008 Liebert Corporation. All rights reserved.
Reproduction of this document is authorized on the condition
that the forgoing copyright notice is included.
This Specification is supplied 'AS IS' and Liebert Corporation
makes no warranty, either express or implied, as to the use,
operation, condition, or performance of the Specification. MODULE-IDENTITY .1.3.6.1.4.1.476.1.42.1.4.1 |
lgpEventNotificationsNotifications for Liebert Global Products. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.3.0 |
lgpEventConditionEntryAddedThis notification is sent each time a condition is inserted into the
conditions table. NOTIFICATION-TYPE .1.3.6.1.4.1.476.1.42.3.3.0.1 |
lgpEventConditionEntryRemovedThis notification is sent each time a condition is removed from the
conditions table. NOTIFICATION-TYPE .1.3.6.1.4.1.476.1.42.3.3.0.2 |
lgpEventLowBatteryWarningThe battery's remaining charge is less than or equal to the agent's
configured low threshold 'lgpPwrConfigLowBatteryWarningTime'. NOTIFICATION-TYPE .1.3.6.1.4.1.476.1.42.3.3.0.3 |
lgpEventLoadTransferedToBypassThe device has transferred the load to the bypass source. NOTIFICATION-TYPE .1.3.6.1.4.1.476.1.42.3.3.0.4 |
lgpEventInternalFaultThe device has reported an internal fault. NOTIFICATION-TYPE .1.3.6.1.4.1.476.1.42.3.3.0.5 |
lgpEventBatteryTestFailedThe device has reported a battery self-test failure. NOTIFICATION-TYPE .1.3.6.1.4.1.476.1.42.3.3.0.6 |
lgpEventOutputOverloadThe device has reported an output overload condition. NOTIFICATION-TYPE .1.3.6.1.4.1.476.1.42.3.3.0.7 |
lgpEventEstablishedPowerRedundancyThe device has transitioned to the user defined redundant state. NOTIFICATION-TYPE .1.3.6.1.4.1.476.1.42.3.3.0.8 |
lgpEventLostPowerRedundancyThe device as transitioned to a non-redundant power state as defined
by the user configured threshold. NOTIFICATION-TYPE .1.3.6.1.4.1.476.1.42.3.3.0.9 |
lgpEventPowerModuleFailureDevice power module failure. NOTIFICATION-TYPE .1.3.6.1.4.1.476.1.42.3.3.0.10 |
lgpEventBatteryModuleFailureDevice battery module failure. NOTIFICATION-TYPE .1.3.6.1.4.1.476.1.42.3.3.0.11 |
lgpEventControlModuleFailureDevice control module failure. NOTIFICATION-TYPE .1.3.6.1.4.1.476.1.42.3.3.0.12 |
lgpEventPowerModuleWarningDevice power module warning. NOTIFICATION-TYPE .1.3.6.1.4.1.476.1.42.3.3.0.13 |
lgpEventBatteryModuleWarningDevice battery module warning. NOTIFICATION-TYPE .1.3.6.1.4.1.476.1.42.3.3.0.14 |
lgpEventControlModuleWarningDevice control module warning. NOTIFICATION-TYPE .1.3.6.1.4.1.476.1.42.3.3.0.15 |
lgpEventAgentFirmwareUpdateSuccessfulThe firmware update to the agent card has completed successfully.
This element has been relocated to lgpAgentFirmwareUpdateSuccessful
in the LIEBERT-GP-AGENT-MIB document. NOTIFICATION-TYPE .1.3.6.1.4.1.476.1.42.3.3.0.16 |
lgpEventAgentFirmwareCorruptThe firmware update to the agent card has failed and the firmware is
now corrupt.
This element has been relocated to lgpAgentFirmwareCorrupt
in the LIEBERT-GP-AGENT-MIB document. NOTIFICATION-TYPE .1.3.6.1.4.1.476.1.42.3.3.0.17 |
lgpEventConfigModifiedConfiguration for the referenced PDU has been modified. NOTIFICATION-TYPE .1.3.6.1.4.1.476.1.42.3.3.0.18 |
lgpEventModuleAddedA hot-swappable module has been added to the object specified by the
lgpEventParmTableRef and lgpEventParmTableRowRef. NOTIFICATION-TYPE .1.3.6.1.4.1.476.1.42.3.3.0.19 |
lgpEventModuleRemovedA hot-swappable module has been removed from the object specified by
the lgpEventParmTableRef and lgpEventParmTableRowRef. NOTIFICATION-TYPE .1.3.6.1.4.1.476.1.42.3.3.0.20 |
lgpEventRcpPowerStateChangeOnReceptacle's power state has been changed from OFF to ON. NOTIFICATION-TYPE .1.3.6.1.4.1.476.1.42.3.3.0.21 |
lgpEventRcpPowerStateChangeOffReceptacle's power state has been changed from ON to OFF. NOTIFICATION-TYPE .1.3.6.1.4.1.476.1.42.3.3.0.22 |
lgpEventRcpLoadAddedThe receptacle's load started drawing power. This notification
is asserted when the receptacle power is ON and the associated load
was previously not drawing power but is now drawing power.
This event is not asserted as a result of turning the
receptacle power ON. NOTIFICATION-TYPE .1.3.6.1.4.1.476.1.42.3.3.0.23 |
lgpEventRcpLoadRemovedThe receptacle's load stopped drawing power. This notification
is asserted when the receptacle power is ON and the associated load
was previously drawing power but is now no longer drawing power.
This event is not asserted as a result of turning the
receptacle power OFF. NOTIFICATION-TYPE .1.3.6.1.4.1.476.1.42.3.3.0.24 |
lgpEventParametersThis sub tree describes various parameters/data that are carried
in the payload of some notifications. OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.3.10 |
lgpEventParmTableRefThis object will be included as a varbind in some
lgpEventNotifications. It is a reference to a table object in
the MIB. The value of this object will be the OID of a table
that the object that the notification applies to is defined.
The notification containing this object will also contain
a varbind 'lgpEventParmTableRowRef' that will specify which
instance (row) in the table the object is defined in.
Example:
NOTIFICATION: lgpEventConditionEntryAdded
varbind: lgpConditionId 6
varbind: lgpConditionDescr lgpConditionRcpBranchBreakerOpen
varbind: lgpConditionTime 393884848
varbind: lgpEventParmTableRef lgpPduRbTable
varbind: lgpEventParmTableRowRef lgpPduRbEntryId.1.4
In the above example the breaker opened for a Receptacle branch.
The specific receptacle branch is specified by the additional
varbind (lgpEventParmTableRowRef). In this case the notification
is for the 4th receptacle branch on the 1st PDU in the PDU cluster.ro OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.3.10.5 |
lgpEventParmTableRowRefThis is a reference to the intersection of a row and column (cell)
in the table specified by the companion varbind
(lgpEventParmTableRef) in this notification. The row in the
table where this cell exists represents the object that this
notification applies to.
Example:
NOTIFICATION: lgpEventRcpPowerStateChangeOff
varbind: sysUpTime 393885975
varbind: lgpEventParmTableRef lgpPduRcpTable
varbind: lgpEventParmTableRowRef lgpPduRcpEntryId.2.4.5
In the above example the power state changed for a Receptacle.
The table containing the definition of the receptacle
(lgpPduRcpTable) is given by the varbind (lgpEventParmTableRef)
The specific receptacle is specified by the varbind
(lgpEventParmTableRowRef). In this case the notification
is for the 5th receptacle on the 4th receptacle branch on the
2nd PDU in the PDU cluster.
If one wanted to retrieve the user assigned label for this
receptacle the OID would be: lgpPduRcpEntryUsrLabel.2.4.5ro OBJECT IDENTIFIER .1.3.6.1.4.1.476.1.42.3.3.10.6 |