Home/Catalog/LIEBERT-GP-NOTIFICATIONS-MIB

LIEBERT-GP-NOTIFICATIONS-MIB

AI MIB Summary

The LIEBERT-GP-NOTIFICATIONS-MIB defines the SNMP trap and notification structures for Liebert GP series precision power and cooling equipment, enabling the transmission of real-time alarm and status events regarding environmental conditions, power supply health, and system faults. This module facilitates immediate alerting for critical infrastructure failures, such as temperature thresholds, fan failures, or UPS battery depletion, within Liebert-managed data center environments.

The MIB module used to register Liebert SNMP OIDs. Copyright 2000-2008 Liebert Corporation. All rights reserved. Reproduction of this document is authorized on the condition that the forgoing copyright notice is included. This Specification is supplied 'AS IS' and Liebert Corporation makes no warranty, either express or implied, as to the use, operation, condition, or performance of the Specification.
Main OID:
liebertGlobalProductsNotificationsModule.1.3.6.1.4.1.476.1.42.1.4.1
29
Objects
Active
Status
4
Dependencies

Imported Objects

Objects

29 total
Object Name
liebertGlobalProductsNotificationsModuleThe MIB module used to register Liebert SNMP OIDs. Copyright 2000-2008 Liebert Corporation. All rights reserved. Reproduction of this document is authorized on the condition that the forgoing copyright notice is included. This Specification is supplied 'AS IS' and Liebert Corporation makes no warranty, either express or implied, as to the use, operation, condition, or performance of the Specification.
MODULE-IDENTITY
.1.3.6.1.4.1.476.1.42.1.4.1
lgpEventNotificationsNotifications for Liebert Global Products.
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.3.0
lgpEventConditionEntryAddedThis notification is sent each time a condition is inserted into the conditions table.
NOTIFICATION-TYPE
.1.3.6.1.4.1.476.1.42.3.3.0.1
lgpEventConditionEntryRemovedThis notification is sent each time a condition is removed from the conditions table.
NOTIFICATION-TYPE
.1.3.6.1.4.1.476.1.42.3.3.0.2
lgpEventLowBatteryWarningThe battery's remaining charge is less than or equal to the agent's configured low threshold 'lgpPwrConfigLowBatteryWarningTime'.
NOTIFICATION-TYPE
.1.3.6.1.4.1.476.1.42.3.3.0.3
lgpEventLoadTransferedToBypassThe device has transferred the load to the bypass source.
NOTIFICATION-TYPE
.1.3.6.1.4.1.476.1.42.3.3.0.4
lgpEventInternalFaultThe device has reported an internal fault.
NOTIFICATION-TYPE
.1.3.6.1.4.1.476.1.42.3.3.0.5
lgpEventBatteryTestFailedThe device has reported a battery self-test failure.
NOTIFICATION-TYPE
.1.3.6.1.4.1.476.1.42.3.3.0.6
lgpEventOutputOverloadThe device has reported an output overload condition.
NOTIFICATION-TYPE
.1.3.6.1.4.1.476.1.42.3.3.0.7
lgpEventEstablishedPowerRedundancyThe device has transitioned to the user defined redundant state.
NOTIFICATION-TYPE
.1.3.6.1.4.1.476.1.42.3.3.0.8
lgpEventLostPowerRedundancyThe device as transitioned to a non-redundant power state as defined by the user configured threshold.
NOTIFICATION-TYPE
.1.3.6.1.4.1.476.1.42.3.3.0.9
lgpEventPowerModuleFailureDevice power module failure.
NOTIFICATION-TYPE
.1.3.6.1.4.1.476.1.42.3.3.0.10
lgpEventBatteryModuleFailureDevice battery module failure.
NOTIFICATION-TYPE
.1.3.6.1.4.1.476.1.42.3.3.0.11
lgpEventControlModuleFailureDevice control module failure.
NOTIFICATION-TYPE
.1.3.6.1.4.1.476.1.42.3.3.0.12
lgpEventPowerModuleWarningDevice power module warning.
NOTIFICATION-TYPE
.1.3.6.1.4.1.476.1.42.3.3.0.13
lgpEventBatteryModuleWarningDevice battery module warning.
NOTIFICATION-TYPE
.1.3.6.1.4.1.476.1.42.3.3.0.14
lgpEventControlModuleWarningDevice control module warning.
NOTIFICATION-TYPE
.1.3.6.1.4.1.476.1.42.3.3.0.15
lgpEventAgentFirmwareUpdateSuccessfulThe firmware update to the agent card has completed successfully. This element has been relocated to lgpAgentFirmwareUpdateSuccessful in the LIEBERT-GP-AGENT-MIB document.
NOTIFICATION-TYPE
.1.3.6.1.4.1.476.1.42.3.3.0.16
lgpEventAgentFirmwareCorruptThe firmware update to the agent card has failed and the firmware is now corrupt. This element has been relocated to lgpAgentFirmwareCorrupt in the LIEBERT-GP-AGENT-MIB document.
NOTIFICATION-TYPE
.1.3.6.1.4.1.476.1.42.3.3.0.17
lgpEventConfigModifiedConfiguration for the referenced PDU has been modified.
NOTIFICATION-TYPE
.1.3.6.1.4.1.476.1.42.3.3.0.18
lgpEventModuleAddedA hot-swappable module has been added to the object specified by the lgpEventParmTableRef and lgpEventParmTableRowRef.
NOTIFICATION-TYPE
.1.3.6.1.4.1.476.1.42.3.3.0.19
lgpEventModuleRemovedA hot-swappable module has been removed from the object specified by the lgpEventParmTableRef and lgpEventParmTableRowRef.
NOTIFICATION-TYPE
.1.3.6.1.4.1.476.1.42.3.3.0.20
lgpEventRcpPowerStateChangeOnReceptacle's power state has been changed from OFF to ON.
NOTIFICATION-TYPE
.1.3.6.1.4.1.476.1.42.3.3.0.21
lgpEventRcpPowerStateChangeOffReceptacle's power state has been changed from ON to OFF.
NOTIFICATION-TYPE
.1.3.6.1.4.1.476.1.42.3.3.0.22
lgpEventRcpLoadAddedThe receptacle's load started drawing power. This notification is asserted when the receptacle power is ON and the associated load was previously not drawing power but is now drawing power. This event is not asserted as a result of turning the receptacle power ON.
NOTIFICATION-TYPE
.1.3.6.1.4.1.476.1.42.3.3.0.23
lgpEventRcpLoadRemovedThe receptacle's load stopped drawing power. This notification is asserted when the receptacle power is ON and the associated load was previously drawing power but is now no longer drawing power. This event is not asserted as a result of turning the receptacle power OFF.
NOTIFICATION-TYPE
.1.3.6.1.4.1.476.1.42.3.3.0.24
lgpEventParametersThis sub tree describes various parameters/data that are carried in the payload of some notifications.
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.3.10
lgpEventParmTableRefThis object will be included as a varbind in some lgpEventNotifications. It is a reference to a table object in the MIB. The value of this object will be the OID of a table that the object that the notification applies to is defined. The notification containing this object will also contain a varbind 'lgpEventParmTableRowRef' that will specify which instance (row) in the table the object is defined in. Example: NOTIFICATION: lgpEventConditionEntryAdded varbind: lgpConditionId 6 varbind: lgpConditionDescr lgpConditionRcpBranchBreakerOpen varbind: lgpConditionTime 393884848 varbind: lgpEventParmTableRef lgpPduRbTable varbind: lgpEventParmTableRowRef lgpPduRbEntryId.1.4 In the above example the breaker opened for a Receptacle branch. The specific receptacle branch is specified by the additional varbind (lgpEventParmTableRowRef). In this case the notification is for the 4th receptacle branch on the 1st PDU in the PDU cluster.ro
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.3.10.5
lgpEventParmTableRowRefThis is a reference to the intersection of a row and column (cell) in the table specified by the companion varbind (lgpEventParmTableRef) in this notification. The row in the table where this cell exists represents the object that this notification applies to. Example: NOTIFICATION: lgpEventRcpPowerStateChangeOff varbind: sysUpTime 393885975 varbind: lgpEventParmTableRef lgpPduRcpTable varbind: lgpEventParmTableRowRef lgpPduRcpEntryId.2.4.5 In the above example the power state changed for a Receptacle. The table containing the definition of the receptacle (lgpPduRcpTable) is given by the varbind (lgpEventParmTableRef) The specific receptacle is specified by the varbind (lgpEventParmTableRowRef). In this case the notification is for the 5th receptacle on the 4th receptacle branch on the 2nd PDU in the PDU cluster. If one wanted to retrieve the user assigned label for this receptacle the OID would be: lgpPduRcpEntryUsrLabel.2.4.5ro
OBJECT IDENTIFIER
.1.3.6.1.4.1.476.1.42.3.3.10.6