HUAWEI-POWER-MIB
AI MIB Summary
The HUAWEI-POWER-MIB module enables SNMP-based monitoring of power supply unit status, input/output voltage levels, current draw, and temperature metrics on Huawei networking hardware. It facilitates granular fault detection and capacity planning by exposing real-time power consumption and redundancy state data for network devices.
This MIB is used for defining Power Monitor management MIB objects.
Main OID:
hwPower.1.3.6.1.4.1.2011.6.2
261
Objects
Active
Status
5
Dependencies
Imported Objects
Objects
261 total| Object Name |
|---|
hwPowerThis MIB is used for defining Power Monitor management MIB objects. MODULE-IDENTITY .1.3.6.1.4.1.2011.6.2 |
hwPowerMonObjects OBJECT IDENTIFIER .1.3.6.1.4.1.2011.6.2.1 |
hwPowerSysInfoTablePower basic information table. The indexes of this table are hwEnvEmuIndex
and hwPowerIndex. hwEnvEmuIndex comes from hwEnvironmentInfoTable and is
the index of the monitoring unit. hwPowerIndex is the index of the power
supply monitored by the monitoring unit. SEQUENCE OF HwPowerSysInfoEntry .1.3.6.1.4.1.2011.6.2.1.1 |
hwPowerSysInfoEntryPower basic information table. The indexes of this entry are hwEnvEmuIndex
and hwPowerIndex. hwEnvEmuIndex comes from hwEnvironmentInfoTable and is
the index of the monitoring unit. hwPowerIndex is the index of the power
supply monitored by the monitoring unit. HwPowerSysInfoEntry .1.3.6.1.4.1.2011.6.2.1.1.1 |
hwPowerIndexIndex of the power supply monitored by the monitoring unitro Integer32 .1.3.6.1.4.1.2011.6.2.1.1.1.1 |
hwPowerTypeType of the Power emu device.
Options:
1.power4875(1) - Type of the Power emu device is power4875
2.power4810(2) - Type of the Power emu device is power4810
3.power48100(3) - Type of the Power emu device is power48100
4.power4850(4) - Type of the Power emu device is power4850
5.power48240(5) - Type of the Power emu device is power48240
6.power48120(6) - Type of the Power emu device is power48120
7.power48300(7) - Type of the Power emu device is power48300
8.power48240SinglePhase(8) - Type of the Power emu device is power48240SinglePhase
9.universalPower(9) - Type of the Power emu device is universalPower
10.power4845(10) - Type of the Power emu device is power4845
11.rpower(11) - Type of the Power emu device is rpower
12.power4805(15) - Type of the Power emu device is power4805
13.power4820(16) - Type of the Power emu device is power4820
14.onps(17) - Type of the Power emu device is onps
15.power4875l(18) - Type of the Power emu device is power4875l
16.psma(100) - Type of the Power emu device is psma
17.perm-al175nt(101) - Type of the Power emu device is perm-al175nt
18.mcs1800(102) - Type of the Power emu device is mcs1800
19.mcs1800A(103) - Type of the Power emu device is mcs1800A
20.mcs3000(104) - Type of the Power emu device is mcs3000
21.sm40sm60(105) - Type of the Power emu device is sm40sm60
22.scu(106) - Type of the Power emu device is scu
23.eltek(107) - Type of the Power emu device is eltek
24.dk04(108) - Type of the Power emu device is dk04
25.dk04C(109) - Type of the Power emu device is dk04C
26.dpc(110) - Type of the Power emu device is dpc
27.power4830(120) - Type of the Power emu device is power4830
28.h831pmua(121) - Type of the Power emu device is h831pmua
29.power3000(122) - Type of the Power emu device is power3000
30.liFeBattery(123) - Type of the Power emu device is LiFeBattery
31.etp4830(125), - Type of SMU Power emu device is etp4830
32.etp4890(126), - Type of SMU Power emu device is etp4890
33.other(255) - other Power Typerw Enumeration .1.3.6.1.4.1.2011.6.2.1.1.1.2 |
hwPowerNamePower name.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.2011.6.2.1.1.1.3 |
hwPowerStatePower board status:
Refers to the status of communication between the internal monitor board
of the power device and the external upper board.
Options:
1.normal(1) - indicates the normal state
2.fault(2) - indicates the faulty state
3.protecting(3)- indicates that the backup power supply works in the protection state
4.switched(4) - indicates that the main power supply is faulty, and is protected by backup power supply
5.invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormalro Enumeration .1.3.6.1.4.1.2011.6.2.1.1.1.4 |
hwPowerRowStatusRowStatus standard operation. The values 1 and 2 are supported currently.
1 indicates the activation status, and 2 indicates the non-activation status.rw RowStatus (SNMPv2-TC) .1.3.6.1.4.1.2011.6.2.1.1.1.5 |
hwPowerControlModeControl mode of the power monitor module.
Options:
1.manualControl(1) - control by manual, the remote mode
2.autoControl(2) - auto control mode, the default is auto control mode
3.invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormalrw Enumeration .1.3.6.1.4.1.2011.6.2.1.1.1.6 |
hwPowerRemoteFrameIDApply for remote power system.
It is the frame ID that the remote unit exists inrw Integer32 .1.3.6.1.4.1.2011.6.2.1.1.1.7 |
hwPowerProtectApply for remote power system.
It is used to enable or disable N+1 protection function.
Options:
1.protect(1) - enables the N+1 protection function
2.undoProtect(2) - disables the N+1 protection functionrw Enumeration .1.3.6.1.4.1.2011.6.2.1.1.1.8 |
hwPowerVersionVersion of powerro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.2011.6.2.1.1.1.9 |
hwPowerSupplyStatePower supply modes.
Options:
1.ac(1) - indicates the AC power supply
2.battery(2) - indicates power supply by the batteriesro Enumeration .1.3.6.1.4.1.2011.6.2.1.1.1.10 |
hwACInputTableAC input table. Through this table,
AC input monitoring parameters of 4875 power supply, 4845 power supply,
4810 power supply, 48100 power supply, and 48240 power supply can
be set and queried.
The indexes of this table are hwEnvEmuIndex, hwPowerIndex, and hwACLoopIndex.
hwEnvEmuIndex is the index of the monitoring unit.
hwPowerIndex is the index of the power supply monitored by the monitoring unit.
hwACLoopIndex is the index of the AC input power supply monitored by the monitoring unit. SEQUENCE OF HwACInputEntry .1.3.6.1.4.1.2011.6.2.1.2 |
hwACInputEntryAC input table. Through this table,
AC input monitoring parameters of 4875 power supply, 4845 power supply,
4810 power supply, 48100 power supply, and 48240 power supply can
be set and queried.
The indexes of this entry are hwEnvEmuIndex, hwPowerIndex, and hwACLoopIndex.
hwEnvEmuIndex is the index of the monitoring unit.
hwPowerIndex is the index of the power supply monitored by the monitoring unit.
hwACLoopIndex is the index of the AC input power supply monitored by the monitoring unit. HwACInputEntry .1.3.6.1.4.1.2011.6.2.1.2.1 |
hwACLoopIndexInput loop index. There are two channels of AC current input,
which are the backup for each other.ro Integer32 .1.3.6.1.4.1.2011.6.2.1.2.1.1 |
hwACPowerStateStatus of power supply.
Options:
1.normal(1) - indicates that the power supply is normal
2.offline(2) - indicates that the power supply is offline
3.exceedVoltage(3) - indicates that the power supply is overvoltage
4.belowVoltage(4) - indicates that the power supply is undervoltage
5.backup(5) - indicates that the power supply is not supported currently
6.invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormalro Enumeration .1.3.6.1.4.1.2011.6.2.1.2.1.2 |
hwACVoltAAC Inuput voltage A.
Unit: mVro MeasuresRange UNITS "mV" .1.3.6.1.4.1.2011.6.2.1.2.1.3 |
hwACCurrentAAC input Current A.
Unit: mAro MeasuresRange UNITS "mA" .1.3.6.1.4.1.2011.6.2.1.2.1.4 |
hwACVoltBAC input voltage B.
Unit: mvro MeasuresRange UNITS "mV" .1.3.6.1.4.1.2011.6.2.1.2.1.5 |
hwACCurrentBAC input current B.
Unit: mAro MeasuresRange UNITS "mA" .1.3.6.1.4.1.2011.6.2.1.2.1.6 |
hwACVoltCAC input voltage C.
Unit: mVro MeasuresRange UNITS "mV" .1.3.6.1.4.1.2011.6.2.1.2.1.7 |
hwACCurrentCAC input current C.
Unit: mAro MeasuresRange UNITS "mA" .1.3.6.1.4.1.2011.6.2.1.2.1.8 |
hwACVoltageHighAC input over-voltage alarm threshold.
Unit: mVrw MeasuresRange UNITS "mV" .1.3.6.1.4.1.2011.6.2.1.2.1.9 |
hwACVoltageLowAC input under-voltage alarm threshold.
Unit: mVrw MeasuresRange UNITS "mV" .1.3.6.1.4.1.2011.6.2.1.2.1.10 |
hwACRowStatusOnly the add operation, delete operation, and status query operation are supported.rw RowStatus (SNMPv2-TC) .1.3.6.1.4.1.2011.6.2.1.2.1.11 |
hwACVoltageAStatePhase AB/A of AC input state.
Options:
1. normal(0) - indicates that the Phase AB/A of AC input state is normal
2. belowVoltage(1) - indicates that the Phase AB/A of AC input state is belowVoltage
3. exceedVoltage(2) - indicates that the Phase AB/A of AC input state is exceedVoltage
4. missing-phase(3) - indicates that the Phase AB/A of AC input state is missing-phasero Enumeration .1.3.6.1.4.1.2011.6.2.1.2.1.12 |
hwACVoltageBStatePhase BC/B of AC input state.
Options:
1. normal(0) - indicates that the Phase BC/B of AC input state is normal
2. belowVoltage(1) - indicates that the Phase BC/B of AC input state is belowVoltage
3. exceedVoltage(2) - indicates that the Phase BC/B of AC input state is exceedVoltage
4. missing-phase(3) - indicates that the Phase BC/B of AC input state is missing-phasero Enumeration .1.3.6.1.4.1.2011.6.2.1.2.1.13 |
hwACVoltageCStatePhase CA/C of AC input state.
Options:
1. normal(0) - indicates that the Phase CA/C of AC input state is normal
2. belowVoltage(1) - indicates that the Phase CA/C of AC input state is belowVoltage
3. exceedVoltage(2) - indicates that the Phase CA/C of AC input state is exceedVoltage
4. missing-phase(3) - indicates that the Phase CA/C of AC input state is missing-phasero Enumeration .1.3.6.1.4.1.2011.6.2.1.2.1.14 |
hwDCOutTableDC output table. Through this table,
DC output monitoring parameters of 4875 power supply, 4845 power supply,
4810 power supply, 482400 power supply, and 48100 power supply can
be set and queried.
The indexes of this table are hwEnvEmuIndex and hwPowerIndex.
hwEnvEmuIndex, which comes from hwEnvironmentInfoTable,
is the index of the monitored unit.
hwPowerIndex is the index of the power supply monitored by the monitoring unit. SEQUENCE OF HwDCOutEntry .1.3.6.1.4.1.2011.6.2.1.3 |
hwDCOutEntryDC output table. Through this table,
DC output monitoring parameters of 4875 power supply, 4845 power supply,
4810 power supply, 482400 power supply, and 48100 power supply can
be set and queried.
The indexes of this entry are hwEnvEmuIndex and hwPowerIndex.
hwEnvEmuIndex, which comes from hwEnvironmentInfoTable,
is the index of the monitored unit.
hwPowerIndex is the index of the power supply monitored by the monitoring unit. HwDCOutEntry .1.3.6.1.4.1.2011.6.2.1.3.1 |
hwDCVoltageOutDC voltage output.
Unit: mVro MeasuresRange UNITS "mV" .1.3.6.1.4.1.2011.6.2.1.3.1.1 |
hwDCCurrentOutDC current output.
Unit: mAro MeasuresRange UNITS "mA" .1.3.6.1.4.1.2011.6.2.1.3.1.2 |
hwDCVoltageOutHighOutput DC exceed-voltage alarm point.
Default: 58000
Unit: mVrw MeasuresRange UNITS "mV" .1.3.6.1.4.1.2011.6.2.1.3.1.3 |
hwDCVoltageOutLowOutput DC below-voltage alarm point . Default value is 45V.
Unit: mVrw MeasuresRange UNITS "mV" .1.3.6.1.4.1.2011.6.2.1.3.1.4 |
hwDCVoltageOutStateDC output voltage status.
Options:
1. normal(1) - indicates that the DC output voltage state is normal
2. exceedVoltage(2) - indicates that the DC output voltage state is exceedVoltage
3. belowVoltage(3) - indicates that the DC output voltage state is belowVoltage
4.invalid(-1) - indicates that device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormalrodeprecated Enumeration .1.3.6.1.4.1.2011.6.2.1.3.1.5 |
hwDCCurrentOutHighOutput DC exceed-current alarm point .
Unit: mArw MeasuresRange UNITS "mA" .1.3.6.1.4.1.2011.6.2.1.3.1.6 |
hwDCCurrentOutLowOutput below-current alarm point .
Unit: mArw MeasuresRange UNITS "mA" .1.3.6.1.4.1.2011.6.2.1.3.1.7 |
hwDCCurrentOutStateDC output current status.
Options:
1.normal(1) - indicates that the DC output current state is normal
2.exceedVoltage(2) - indicates that the DC output current state is exceedVoltage
3.belowVoltage(3) - indicates that the DC output current state is belowVoltage
4.invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormalrodeprecated Enumeration .1.3.6.1.4.1.2011.6.2.1.3.1.8 |
hwDCOutRowStatusRowStatus standard operationrw RowStatus (SNMPv2-TC) .1.3.6.1.4.1.2011.6.2.1.3.1.9 |
hwDCOutLoadCurrentTotal load current of DC output .
Unit: mAro MeasuresRange UNITS "mA" .1.3.6.1.4.1.2011.6.2.1.3.1.10 |
hwDCOutLoadTmpHighThe off protection point under the load temperature, by default,
it is 65 degrees centigrade.
Unit: 0.01 degreerw MeasuresRange UNITS "0.01 degree" .1.3.6.1.4.1.2011.6.2.1.3.1.11 |
hwDCOutRunStateDC output running status.
Options:
1.battery1ChargeCurOver(0) - indicates battery 1 charge over-current
2.battery2ChargeCurOver(1) - indicates battery 2 charge over-current
3.batteryVoltageOver(2) - indicates output over-voltage
4.batteryVoltageLack(3) - indicates battery lack-voltage
5.loadOff(4) - indicates load off twice
6.batteryOff(5) - indictes battery protection (off once)
7.communicationFailure(6) - indicates that the communication fails
8.dcOutManual(7) - indicates DC by manualro Bits .1.3.6.1.4.1.2011.6.2.1.3.1.12 |
hwDCCommunicationStateDC communication status.
Options:
1.normal(0) - indicates that the DC communication state is normal
2.fault(1) - indicates that the DC communication state is faultro Enumeration .1.3.6.1.4.1.2011.6.2.1.3.1.13 |
hwLoadinfoTableLoad information table. Through this table, the load parameter can be set and queried.
The indexes of this table are hwEnvEmuIndex, hwPowerIndex, and hwLoadIndex.
hwEnvEmuIndex, which comes from hwEnvironmentInfoTable, is the index of the monitored unit.
hwPowerIndex is the index of the power supply monitored by the monitoring unit.
hwLoadIndex is the index of the monitored load. SEQUENCE OF HwLoadinfoEntry .1.3.6.1.4.1.2011.6.2.1.4 |
hwLoadinfoEntryLoad information table. Through this table, the load parameter can be set and queried.
The indexes of this entry are hwEnvEmuIndex, hwPowerIndex, and hwLoadIndex.
hwEnvEmuIndex, which comes from hwEnvironmentInfoTable, is the index of the monitored unit.
hwPowerIndex is the index of the power supply monitored by the monitoring unit.
hwLoadIndex is the index of the monitored load. HwLoadinfoEntry .1.3.6.1.4.1.2011.6.2.1.4.1 |
hwLoadIndexLoop index: usually each DC output loop corresponds to a load.ro Integer32 .1.3.6.1.4.1.2011.6.2.1.4.1.1 |
hwLoadInfoAdminStateLoad operation.
Options:
1. on(1) - indicates that the Load is enabled
2. off(2) - indicates that the Load is disabled
3. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormalrw Enumeration .1.3.6.1.4.1.2011.6.2.1.4.1.2 |
hwLoadInfoOperStatusStatus of power supply.
Options:
1. normal(1) - indicates that the state of power supply is normal
2. abnormal(2) - indicates that the state of power supply is abnormal
3. stop(3) - indicates that the state of power supply is stopping power supply
4. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormalro Enumeration .1.3.6.1.4.1.2011.6.2.1.4.1.3 |
hwLoadCurrentPresent current .
Unit: mAro MeasuresRange UNITS "mA" .1.3.6.1.4.1.2011.6.2.1.4.1.4 |
hwLoadVoltagePresent voltage .
Unit: mVro MeasuresRange UNITS "mV" .1.3.6.1.4.1.2011.6.2.1.4.1.5 |
hwLoadVoltageHighOff voltage (Stop external voltage), in unit of mV,
When DC output voltage exceeds the value, the load will be automatically cut off.
Default: 43500
Unit: mVrw MeasuresRange UNITS "mV" .1.3.6.1.4.1.2011.6.2.1.4.1.6 |
hwLoadLoadNameLoad name: usually each DC output loop corresponds to a load.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.2011.6.2.1.4.1.7 |
hwLoadInfoRowStatusRowStatus standard operationrw RowStatus (SNMPv2-TC) .1.3.6.1.4.1.2011.6.2.1.4.1.8 |
hwLoadFuseStateLoad fuse state, including the auxiliary load fuse.
Options:
1. on(1) - indicates that the fuse is connected
2. off(2) - indicates that the fuse is disconnected
3. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormalro Enumeration .1.3.6.1.4.1.2011.6.2.1.4.1.9 |
hwLoadHoreIndexload hore indexrw Integer32 .1.3.6.1.4.1.2011.6.2.1.4.1.10 |
hwRectifierTableRectifier module table.
Through this table, the status information of the rectifier module
can be set and queried.
The indexes of this table are hwEnvEmuIndex, hwPowerIndex, and hwRectifierIndex.
hwEnvEmuIndex, which comes from hwEnvironmentInfoTable,
is the index of the monitored unit.
hwPowerIndex is the index of the power supply monitored by the monitoring unit.
hwRectifierIndex is the index of the monitored rectifier module under the power supply. SEQUENCE OF HwRectifierEntry .1.3.6.1.4.1.2011.6.2.1.5 |
hwRectifierEntryRectifier module table.
Through this table, the status information of the rectifier module
can be set and queried.
The indexes of this entry are hwEnvEmuIndex, hwPowerIndex, and hwRectifierIndex.
hwEnvEmuIndex, which comes from hwEnvironmentInfoTable,
is the index of the monitored unit.
hwPowerIndex is the index of the power supply monitored by the monitoring unit.
hwRectifierIndex is the index of the monitored rectifier module under the power supply. HwRectifierEntry .1.3.6.1.4.1.2011.6.2.1.5.1 |
hwRectifierIndexRectifier Module index. There are multiple rectifier
modules to a power source.ro Integer32 .1.3.6.1.4.1.2011.6.2.1.5.1.1 |
hwRectifierAdminStateSwitch operation of rectifier module.
Options:
1.on(1) - indicates that the Rectifier module is enabled
2.off(2) - indicates that the Rectifier module is disabled
3.invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormalrw Enumeration .1.3.6.1.4.1.2011.6.2.1.5.1.2 |
hwRectifierOperStatePresent state, 5 and 6 respectively indicates the on/off state of the 48100 power device.
Options:
1. normal(1) - indicates that the Rectifier operation state is normal
2. fault(2) - indicates that the Rectifier operation state is fault
3. protect(3) - indicates that the Rectifier operation state is protect
4. communicationFailure(4) - indicates that the Rectifier operation state is communicationFailure
5. on(5) - indicates that the Rectifier operation state is on
6. off(6) - indicates that the Rectifier operation state is off
7. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormalro Enumeration .1.3.6.1.4.1.2011.6.2.1.5.1.3 |
hwRectifierVoltageOutput voltage .
Unit: mVro MeasuresRange UNITS "mV" .1.3.6.1.4.1.2011.6.2.1.5.1.4 |
hwRectifierCurrentOutput current .
Unit: mAro MeasuresRange UNITS "mA" .1.3.6.1.4.1.2011.6.2.1.5.1.5 |
hwRectifierRowStatusRowStatus standard operationrw RowStatus (SNMPv2-TC) .1.3.6.1.4.1.2011.6.2.1.5.1.6 |
hwRectifierCurrentLimitcurrent limit switchrw TruthValue (SNMPv2-TC) .1.3.6.1.4.1.2011.6.2.1.5.1.7 |
hwRectifierRunStateRunning state of rectifier module.
Options:
1.rectifierOn(0) - indicates that the module is on
2.averageCharge(1) - indicates that the module is being averagely charged.
3.output(2) - indicates that the module has output
4. isLimit(3) - indicates the current limit switchro Bits .1.3.6.1.4.1.2011.6.2.1.5.1.8 |
hwRectifierChargeStateCharging state of rectifier.
Options:
1. float(0) - indicates that the Charge state of Rectifier is float
2. average(1) - indicates that the Charge state of Rectifier is average
3. test(2) - indicates that the Charge state of Rectifier is testro Enumeration .1.3.6.1.4.1.2011.6.2.1.5.1.9 |
hwBatteryGroup OBJECT IDENTIFIER .1.3.6.1.4.1.2011.6.2.1.6 |
hwBatteryGroupTableBasic information table of battery group.
The indexes of this table are hwEnvEmuIndex and hwPowerIndex.
hwEnvEmuIndex is the index of the monitored unit,
and hwPowerIndex is the index of the power supply monitored by the monitoring unit. SEQUENCE OF HwBatteryGroupEntry .1.3.6.1.4.1.2011.6.2.1.6.1 |
hwBatteryGroupEntryBasic information table of battery group.
The indexes of this entry are hwEnvEmuIndex and hwPowerIndex.
hwEnvEmuIndex is the index of the monitored unit,
and hwPowerIndex is the index of the power supply monitored by the monitoring unit. HwBatteryGroupEntry .1.3.6.1.4.1.2011.6.2.1.6.1.1 |
hwBatteryGroupCapacityTotal capacity of the present battery group.
Unit: Ahro Integer32 .1.3.6.1.4.1.2011.6.2.1.6.1.1.1 |
hwBatteryGroupCapcaityRemainTotal remain capacity of the present battery group .
invalid(-1) indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal.
Unit: Ahro Integer32 (-1..100) .1.3.6.1.4.1.2011.6.2.1.6.1.1.2 |
hwBatteryGroupsNumber of battery grouprw Integer32 .1.3.6.1.4.1.2011.6.2.1.6.1.1.3 |
hwBatteryGroupVoltageLowWhen the voltage of the battery group is lower than the value set,
the battery group will no longer supply power. Its unit is mV.
Default: 43000
Unit: mVrw MeasuresRange UNITS "mV" .1.3.6.1.4.1.2011.6.2.1.6.1.1.4 |
hwBatteryGroupChargeLimitCharge limit point quotient, the product of which and the max capacity
of the battery group is the max charge current allowed.
Default: 15
Unit: percentrw MeasuresRange UNITS "percent" .1.3.6.1.4.1.2011.6.2.1.6.1.1.5 |
hwBatteryGroupRowStatusRowStatus standard operationrw RowStatus (SNMPv2-TC) .1.3.6.1.4.1.2011.6.2.1.6.1.1.6 |
hwBatteryGroupOperStatusThe State of the battery supply which was connected with Power EMU.
To use this function,please confirm that the battery group was connected with Power EMU and the Power EMU state is Normal.
When the mains supply is abnormal, the battery group usually supplies power in an emergency.
Options:
1.on(1) - indicates that the state of the battery power supply is on
2.off(2) - indicates that the state of the battery power supply is off
3.invalid(-1) - indicates that the device can not get the value,e.g. the EMU does not support this operation, or the EMU state is abnormalro Enumeration .1.3.6.1.4.1.2011.6.2.1.6.1.1.7 |
hwBatteryGroupVoltageHighWhen the voltage of the battery group is higher than the value set, the battery group
will no longer supply power. Its unit is mV.
Default: 43000
Unit: mVrw MeasuresRange UNITS "mV" .1.3.6.1.4.1.2011.6.2.1.6.1.1.8 |
hwBatteryGroupTwiceOffVoltageThe twice off protection voltage of the battery group. Its unit is mV.
Default: 44000
Unit: mVrw MeasuresRange UNITS "mV" .1.3.6.1.4.1.2011.6.2.1.6.1.1.9 |
hwBatteryGroupProtectVoltageThe first off protection voltage of the battery,
whose default is 43V.
Default: 43000
Unit: mVrw MeasuresRange UNITS "mV" .1.3.6.1.4.1.2011.6.2.1.6.1.1.10 |
hwBatteryGroupTmpOffHighThe high temperature off protection point of the battery group,
whose default is 50 degrees centigrade.
Unit: 0.01 degreerw MeasuresRange UNITS "0.01 degree" .1.3.6.1.4.1.2011.6.2.1.6.1.1.11 |
hwBatteryInstallTimeThe installing date of battery group.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.2011.6.2.1.6.1.1.12 |
hwBatteryGroupBomCodeThe BAR code of battery.rw OCTET STRING .1.3.6.1.4.1.2011.6.2.1.6.1.1.13 |
hwChargeTableCharge management table.
Through this table, the charging parameter of the battery can be set and queried.
The indexes of this table are hwEnvEmuIndex and hwPowerIndex.
hwEnvEmuIndex is the index of the monitored unit,
and hwPowerIndex is the index of the power supply monitored by the monitoring unit. SEQUENCE OF HwChargeEntry .1.3.6.1.4.1.2011.6.2.1.6.2 |
hwChargeEntryCharge management table.
Through this table, the charging parameter of the battery can be set and queried.
The indexes of this entry are hwEnvEmuIndex and hwPowerIndex.
hwEnvEmuIndex is the index of the monitored unit,
and hwPowerIndex is the index of the power supply monitored by the monitoring unit. HwChargeEntry .1.3.6.1.4.1.2011.6.2.1.6.2.1 |
hwChargeAdminStatusCharge management mode.
Options:
1. average(1) - indicates that the charge management mode is average charge
2. float(2) - indicates that the charge management mode is float charge
3. auto(3) - indicates that the charge management mode is auto-control charge
4. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormalrw Enumeration .1.3.6.1.4.1.2011.6.2.1.6.2.1.1 |
hwChargeOperStatusCharge operation status.
Options:
1. average(1) - indicates that the charge operation state is average charge
2. float(2) - indicates that the charge operation state is float charge
3. full(3) - indicates that the charge operation state is full
4. noCharge(4) - indicates that there is no charge in operation
5. discharge(5) - indicates that there is discharge in operation
6. sleep(6) - indicates that the charge operation state is sleep
7. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormalro Enumeration .1.3.6.1.4.1.2011.6.2.1.6.2.1.2 |
hwAverageChargeVoltageVoltage value of average charge, in unit of mV.
Default: 56500
Unit: mVrw MeasuresRange UNITS "mV" .1.3.6.1.4.1.2011.6.2.1.6.2.1.3 |
hwFloatChargeVoltageVoltage value of float charge .
Default: 53500
Unit: mVrw MeasuresRange UNITS "mV" .1.3.6.1.4.1.2011.6.2.1.6.2.1.4 |
hwChargeControlRowStatusRowStatus standard operationrw RowStatus (SNMPv2-TC) .1.3.6.1.4.1.2011.6.2.1.6.2.1.5 |
hwAverageChargeTimeTiming average charge time interval, effective range is 190 days.
Default :value is 60 days
Unit: dayrw Integer32 UNITS "day" .1.3.6.1.4.1.2011.6.2.1.6.2.1.6 |
hwBatteryTmpRedeemingQuotietyTemperature redeeming quotient, used to set the co-relation
between the float charge voltage and the battery temperature.
It means How much will the float charge voltage decrease
with the increasing of every degree centigrade of the battery
temperature. The unit is mV.
Specific value is determined by the redeem feature curve of
floating charge for the battery group used.
Default value is 100mVrw Integer32 .1.3.6.1.4.1.2011.6.2.1.6.2.1.7 |
hwBatteryTableBattery group state table.
Through this table, the status parameter of a battery group can be set and queried.
The indexes of this table are hwEnvEmuIndex, hwPowerIndex, and hwBatteryIndex.
hwEnvEmuIndex is the index of the monitored unit.
hwPowerIndex is the index of the power supply monitored by the monitoring unit.
hwBatteryIndex is the index of the monitored battery group. SEQUENCE OF HwBatteryEntry .1.3.6.1.4.1.2011.6.2.1.6.3 |
hwBatteryEntryBattery group state table.
Through this table, the status parameter of a battery group can be set and queried.
The indexes of this entry are hwEnvEmuIndex, hwPowerIndex, and hwBatteryIndex.
hwEnvEmuIndex is the index of the monitored unit.
hwPowerIndex is the index of the power supply monitored by the monitoring unit.
hwBatteryIndex is the index of the monitored battery group. HwBatteryEntry .1.3.6.1.4.1.2011.6.2.1.6.3.1 |
hwBatteryIndexBattery group loop indexro Integer32 .1.3.6.1.4.1.2011.6.2.1.6.3.1.1 |
hwBatteryCapacityThe permitted max battery capacity of the battery group loop charge.
Unit: Ahrw Integer32 .1.3.6.1.4.1.2011.6.2.1.6.3.1.2 |
hwBatteryLoopStateThe battery group present status.
Options:
1. on(1) - indicates that the present state of battery group is on
2. off(2) - indicates that the present state of battery group is off
3. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormalro Enumeration .1.3.6.1.4.1.2011.6.2.1.6.3.1.3 |
hwBatteryVoltageThe loop voltage of the battery group.
Unit: mVro MeasuresRange UNITS "mV" .1.3.6.1.4.1.2011.6.2.1.6.3.1.4 |
hwBatteryStateThe present state of the battery group loop.
Options:
1. charge(1) - indicates that the present state of the battery group loop is charge
2. discharge(2) - indicates that the present state of the battery group loop is discharge
3. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormalro Enumeration .1.3.6.1.4.1.2011.6.2.1.6.3.1.5 |
hwBatteryCurrentPresent current .
Unit: mAro MeasuresRange UNITS "mA" .1.3.6.1.4.1.2011.6.2.1.6.3.1.6 |
hwBatteryTemperatureThe loop temperature of the battery group.
Unit: degreero Integer32 UNITS "degree" .1.3.6.1.4.1.2011.6.2.1.6.3.1.7 |
hwBatteryRowStatusRowStatus standard operationrw RowStatus (SNMPv2-TC) .1.3.6.1.4.1.2011.6.2.1.6.3.1.8 |
hwBatteryCurrentHighThe over-current alarm point of the battery group.
Unit: mArw MeasuresRange UNITS "mA" .1.3.6.1.4.1.2011.6.2.1.6.3.1.9 |
hwBatteryFuseStateBattery fuse state.
Options:
1. on(1) - indicates that the fuse is connected
2. off(2) - indicates that the fuse is disconnected
3. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormalro Enumeration .1.3.6.1.4.1.2011.6.2.1.6.3.1.10 |
hwBatteryContactStateThe state of the battery contactor.
Options:
1. on(1) - indicates that the contactor is connected
2. off(2) - indicates that the contactor is disconnected
3. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormalro Enumeration .1.3.6.1.4.1.2011.6.2.1.6.3.1.11 |
hwBatteryRemainCapacityRemain capacity of the batteryro Integer32 .1.3.6.1.4.1.2011.6.2.1.6.3.1.12 |
hwBatteryProtectStateProtection status of the battery.
Options:
1. normal(1) - indicates that the Protection status of the battery is normal
2. overtemperature(2) - indicates that the Protection status of the battery is overtemperature
3. overCurrent(3) - indicates that the Protection status of the battery is overCurrentro Enumeration .1.3.6.1.4.1.2011.6.2.1.6.3.1.13 |
hwBatteryVoltageStateVoltage state of Battery.
Options:
1. normal(1) - indicates that Voltage state of Battery is normal
2. exceedVoltage(2) - indicates that Voltage state of Battery is exceedVoltage
3. belowVoltage(3) - indicates that Voltage state of Battery is belowVoltagero Enumeration .1.3.6.1.4.1.2011.6.2.1.6.3.1.14 |
hwBatteryHardwareStateHardware State of Battery.
Options:
1. normal(1) - indicates that the hardware state of Battery is normal
2. fault(2) - indicates that the hardware state of Battery is faultro Enumeration .1.3.6.1.4.1.2011.6.2.1.6.3.1.15 |
hwBatteryTestTableBattery test table.
The indexes of this table are hwEnvEmuIndex and hwPowerIndex.
hwEnvEmuIndex is the index of the monitored unit,
and hwPowerIndex is the index of the power supply monitored by the monitoring unit. SEQUENCE OF HwBatteryTestEntry .1.3.6.1.4.1.2011.6.2.1.6.4 |
hwBatteryTestEntryBattery test table.
The indexes of this entry are hwEnvEmuIndex and hwPowerIndex.
hwEnvEmuIndex is the index of the monitored unit,
and hwPowerIndex is the index of the power supply monitored by the monitoring unit. HwBatteryTestEntry .1.3.6.1.4.1.2011.6.2.1.6.4.1 |
hwBatteryTestAdminStatusBattery test admin status.
Options:
1. start(1) - indicates that the Battery starts testing
2. terminate(2) - indicates that the Battery terminates testing
3. enableAutoTest(3) - indicates that the Battery enables auto test function
4. disableAutoTest(4) - indicates that the Battery disables auto test function
5. timeautoTest(5) - indicates that the Battery enable timing auto test function
6. offautoTest(6) - indicates that the Battery enable off auto test function
7. timeoffautoTest(7) - indicates that the Battery enable timing+off auto testrw Enumeration .1.3.6.1.4.1.2011.6.2.1.6.4.1.1 |
hwBatteryTestAutoDischargePeriodAuto discharge test period.
Effective range is 30 -240 days.
Default: 120
Unit: dayrw Integer32 UNITS "day" .1.3.6.1.4.1.2011.6.2.1.6.4.1.2 |
hwBatteryTestResultTest result:
Options:
1. testing(1) - indicates that the Battery test is in operation
2. complete(2) - indicates that the Battery test is completed normally
3. alarmTerminated(3) - indicates that the Battery test is stopped by alarms
4. hostTerminated(4) - indicates that the Battery test is stopped by the host
5. overtimeTerminated(5) - indicates that the Battery test is stopped because of over time
6. normal(6) - indicates that the Battery test is not started
7. supplyRecoverAutotestTerminated(7) - indicates that the Battery test is stopped because of supply recoverroobsolete Enumeration .1.3.6.1.4.1.2011.6.2.1.6.4.1.3 |
hwBatteryTestStartTimeTime of starting testroobsolete DateAndTime (SNMPv2-TC) .1.3.6.1.4.1.2011.6.2.1.6.4.1.4 |
hwBatteryTestDurationBattery discharge test duration .
Effective range is 1C100 hours.
Default :value is 10 hours
Unit: hourrw Integer32 UNITS "hour" .1.3.6.1.4.1.2011.6.2.1.6.4.1.5 |
hwBatteryTestTerminateVoltageBattery discharge test end voltage.
Effective range (DC lack alarm voltage+0.5VCvoltage of floating charge).
Default: 45600
Unit: mVrw Integer32 UNITS "mV" .1.3.6.1.4.1.2011.6.2.1.6.4.1.6 |
hwBatteryTestTotalDischargeAHTotal discharge AH.
Unit: mAHroobsolete Integer32 UNITS "mAH" .1.3.6.1.4.1.2011.6.2.1.6.4.1.7 |
hwBatteryTestOperStatusBattery discharge test operate status.
Options:
1. autoTestPermit(1) - indicates that auto discharge test is enabled
2. autoTestForbid(2) - indicates that auto discharge test is disabled
3. timeautoTestPermit(3) - indicates that timing auto discharge test is enabled
4. offautoTestPermit(4) - indicates that off auto discharge test is enabled
5. timeoffautoTestPermit(5) - indicates that timing-off auto discharge test is enabledro Enumeration .1.3.6.1.4.1.2011.6.2.1.6.4.1.8 |
hwBatteryTestPhaseBattery test phase.
Options:
1. charge(1) - indicates the batter test phase is charge
2. discharge(2) - indicates the batter test phase is discharge
3. record(3) - indicates the power equipment recording test result
4. finish(4) - indicates that the discharge is complete
5.waitingfordischarge(5) - indicates that preparation is ready for discharge commandro Enumeration .1.3.6.1.4.1.2011.6.2.1.6.4.1.9 |
hwBatteryTestStartHourDischarge start time.
Effective range is 0 23
Default: 0
Unit: hourrw Integer32 UNITS "hour" .1.3.6.1.4.1.2011.6.2.1.6.4.1.10 |
hwBatteryTestAlarmThresholdThe battery discharge test alarm threshold in ratio of the range:1~79.rw Integer32 UNITS "percent" .1.3.6.1.4.1.2011.6.2.1.6.4.1.11 |
hwBatteryLogTestTableBattery test result table,
Through this table, the discharging test result of the battery group can be saved and queried.
The indexes of this table are hwEnvEmuIndex, hwPowerIndex, and hwBatteryLogTestIndex.
hwEnvEmuIndex is the index of the monitored unit.
hwPowerIndex is the index of the power supply monitored by the monitoring unit.
hwBatteryLogTestIndex is the index of the monitored battery. SEQUENCE OF HwBatteryLogTestEntry .1.3.6.1.4.1.2011.6.2.1.6.5 |
hwBatteryLogTestEntryBattery test result table,
Through this table, the discharging test result of the battery group can be saved and queried.
The indexes of this entry are hwEnvEmuIndex, hwPowerIndex, and hwBatteryLogTestIndex.
hwEnvEmuIndex is the index of the monitored unit.
hwPowerIndex is the index of the power supply monitored by the monitoring unit.
hwBatteryLogTestIndex is the index of the monitored battery. HwBatteryLogTestEntry .1.3.6.1.4.1.2011.6.2.1.6.5.1 |
hwBatteryLogTestIndexBattery discharge test result indexro Integer32 .1.3.6.1.4.1.2011.6.2.1.6.5.1.1 |
hwBatteryLogTestStartTimeBattery discharge test start timero DateAndTime (SNMPv2-TC) .1.3.6.1.4.1.2011.6.2.1.6.5.1.2 |
hwBatteryLogTestDischargeDurationDuration of discharge.
Unit: minutero Integer32 UNITS "minute" .1.3.6.1.4.1.2011.6.2.1.6.5.1.3 |
hwBatteryLogTestTerminateVoltageEnd voltage of battery discharge test .
Unit: mVro Integer32 UNITS "mV" .1.3.6.1.4.1.2011.6.2.1.6.5.1.4 |
hwBatteryLogTestBatteryStatusBattery status.
Options:
1. expectant(1) - indicates the batter test state is expectant
2. unexpected(2) - indicates the batter test state is unexpected
3. unknown(3) - indicates the batter test state is unknownro Enumeration .1.3.6.1.4.1.2011.6.2.1.6.5.1.5 |
hwBatteryLogTestTotalDischargeAHDischarge cumulate AH.
Unit: mAHro Integer32 UNITS "mAH" .1.3.6.1.4.1.2011.6.2.1.6.5.1.6 |
hwBatteryLogTestFinishBattery Test result.
Options:
1. testing(1) - indicates that it is during testing
2. completed(2) - indicates that the test is completed normally
3. alarmTerminated(3) - indicates that the test is stopped by alarms
4. hostTerminated(4) - indicates that the test is stopped by the host
5. overtimeTerminated(5) - indicates that the test is stopped because of over 100 hours
6. notTest(6) - indicates that the test is not startedro Enumeration .1.3.6.1.4.1.2011.6.2.1.6.5.1.7 |
hwBatteryLogTestEfficiencyThe information of battery test efficiency.ro Integer32 UNITS "percent" .1.3.6.1.4.1.2011.6.2.1.6.5.1.8 |
hwBatteryLogTestBatteryTemperatureBattery discharge test end Temperature.
Unit: 0.01 Degreero Integer32 UNITS "0.01 Degree" .1.3.6.1.4.1.2011.6.2.1.6.5.1.9 |
hwBatteryLogTestBatteryCurrentBattery discharge test average Current.
Unit: mAro Integer32 UNITS "mA" .1.3.6.1.4.1.2011.6.2.1.6.5.1.10 |
hwRemoteProvidePowerInfoTableRemote provide power basic information table.
The indexes of this table are hwEnvEmuIndex and hwPowerIndex.
hwEnvEmuIndex is the index of the monitored unit,
and hwPowerIndex is the index of the power supply monitored by the monitoring unit. SEQUENCE OF HwRemoteProvidePowerInfoEntry .1.3.6.1.4.1.2011.6.2.1.7 |
hwRemoteProvidePowerInfoEntryRemote provide power basic information table.
The indexes of this entry are hwEnvEmuIndex and hwPowerIndex.
hwEnvEmuIndex is the index of the monitored unit,
and hwPowerIndex is the index of the power supply monitored by the monitoring unit. HwRemoteProvidePowerInfoEntry .1.3.6.1.4.1.2011.6.2.1.7.1 |
hwPowerCentralStateState of the central module.
Options:
1. normal(1) - indicates the normal state
2. temOver(2) - indicates the over-temperaturero Enumeration .1.3.6.1.4.1.2011.6.2.1.7.1.1 |
hwPowerCentralDCInPutStateState of central module DC input:
Options:
1.normal(1) - indicates the normal state
2.lack(2) - indicates the voltage underflow
3.over(3) - indicates the voltage overflowro Enumeration .1.3.6.1.4.1.2011.6.2.1.7.1.2 |
hwPowerCentralDCOutputStateState of central module DC output.
Options:
1. normal(1) - indicates the normal state
2. volLack(2) - indicates the voltage underflow
3. volOver(3) - indicates the voltage overflow
4. loadOver(4) - indicates the over-loading
5. shortCircuit(5) - indicates the short circuit
6. noLoad(6) - indicates no loadro Enumeration .1.3.6.1.4.1.2011.6.2.1.7.1.3 |
hwPowerCentralDCOutputModeMode of central module DC output.
Options:
1. highVolMode(1) - indicates the high voltage output mode
2. lowVolMode(2) - indicates the low voltage output modero Enumeration .1.3.6.1.4.1.2011.6.2.1.7.1.4 |
hwPowerRemoteCommStateRemote power module communications state.
Options:
1. normal(1) - indicates the normal state
2. revfault(2) - indicates the receiving of fault
3. sendfault(3) - indicates the sending of faultrw Enumeration .1.3.6.1.4.1.2011.6.2.1.7.1.5 |
hwPowerRemoteDCInputStateState of remote module DC input.
Options:
1. normal(1) - indicates the normal state
2. lack(2) - indicates that the voltage is underflowrw Enumeration .1.3.6.1.4.1.2011.6.2.1.7.1.6 |
hwPowerRemoteLineCurStatestate of line between central and remote module.
Options:
1.normal(1) - indicates the normal state
2.cablejoining(2) - indicates the cable joining
3.curLeakage(3) - indicates the cur Leakage
4.curOver(4) - indicates the cur Overrw Enumeration .1.3.6.1.4.1.2011.6.2.1.7.1.7 |
hwPowerRemotePowerStatestate of remote UA60 power.
Options:
1. normal(1) - indicates the normal state
2. fault(2) - indicates the faulty staterw Enumeration .1.3.6.1.4.1.2011.6.2.1.7.1.8 |
hwPowerRemoteLineStateState of line U1.
Options:
1. u1state(0) - indicates the power remote line state is u1 state
2. u2state(1) - indicates the power remote line state is u2 state
3. u3state(2) - indicates the power remote line state is u3 state
4. u4state(3) - indicates the power remote line state is u4 state
5. a1state(4) - indicates the power remote line state is a1 state
6. a2state(5) - indicates the power remote line state is a2 state
7. a3state(6) - indicates the power remote line state is a3 state
8. a4state(7) - indicates the power remote line state is a4 staterw Bits .1.3.6.1.4.1.2011.6.2.1.7.1.9 |
hwPowerCentralLoadStatestate of central load.
Options:
1. normal(1) - indicates the normal state
2. overload(2) - indicates overload
3. nonload(3) - indicates non-loadrw Enumeration .1.3.6.1.4.1.2011.6.2.1.7.1.10 |
hwACInfomationTableAC infomation table. The table is not supported.
The indexes of this table are hwEnvEmuIndex and hwPowerIndex. SEQUENCE OF HwACInfomationEntry .1.3.6.1.4.1.2011.6.2.1.8 |
hwACInfomationEntryAC infomation table. The table is not supported.
The indexes of this entry are hwEnvEmuIndex and hwPowerIndex. HwACInfomationEntry .1.3.6.1.4.1.2011.6.2.1.8.1 |
hwACInfoCommStatecommunication state of AC input module.
The node is not supported.
Options:
1. normal(0) - indicates the communication state of AC is normal
2. fault(1) - indicates the communication state of AC is faultro Enumeration .1.3.6.1.4.1.2011.6.2.1.8.1.1 |
hwACInfoThunderStateThunder's state.
The node is not supported.
Options:
1. normal(0) - indicates the state of Thunder is normal
2. fault(1) - indicates the state of Thunder is faultro Enumeration .1.3.6.1.4.1.2011.6.2.1.8.1.2 |
hwACInfoCurrentLoopCurrent AC input working loop.
The leaf is not supported.ro Integer32 .1.3.6.1.4.1.2011.6.2.1.8.1.3 |
hwACInfoMCBTriggerAC input MCB trigger state.
The leaf is not supported.
Options:
1. normal(0) - indicates the AC input MCB trigger state is normal
2. break-down(1)- indicates the AC input MCB trigger state is break-downro Enumeration .1.3.6.1.4.1.2011.6.2.1.8.1.4 |
hwACInfoFrequencyThe infomation of AC input frequency.
This leaf is not supported.
Unit: HZro Integer32 UNITS "HZ" .1.3.6.1.4.1.2011.6.2.1.8.1.5 |
hwACInfoRowStatusRowStatus standard operation
The leaf is not supported.rw RowStatus (SNMPv2-TC) .1.3.6.1.4.1.2011.6.2.1.8.1.6 |
hwPowerMibTrap OBJECT IDENTIFIER .1.3.6.1.4.1.2011.6.2.2 |
hwPowerTrapOid OBJECT IDENTIFIER .1.3.6.1.4.1.2011.6.2.2.1 |
hwPowerTrapsDefine OBJECT IDENTIFIER .1.3.6.1.4.1.2011.6.2.2.2 |
hwPowerTraps OBJECT IDENTIFIER .1.3.6.1.4.1.2011.6.2.2.2.0 |
powerConnFaultAlarmThis trap message is reported when the communication between
the power module and the monitoring board is fault. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.2.2.0.1 |
powerConnFaultAlarmResumeThis trap message is reported when the communication between
the power module and the monitoring board resumes. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.2.2.0.2 |
acInputVoltageAlarmThis trap message is reported when there is a exception of AC input voltage. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.2.2.0.3 |
acInputVoltageAlarmResumeThis trap message is reported when the state of AC input voltage resumes. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.2.2.0.4 |
acInputVoltageHighAlarmThis trap message is reported when the input voltage is too high. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.2.2.0.5 |
acInputVoltageHighAlarmResumeThis trap message is reported when the input voltage
resumes to the normal range from a high value. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.2.2.0.6 |
acInputVoltageLowAlarmThis trap message is reported when the input voltage is too low. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.2.2.0.7 |
acInputVoltageLowAlarmResumeThis trap message is reported when the input voltage
resumes to the normal range from a low value. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.2.2.0.8 |
dcOutputVoltageHighAlarmThis trap message is reported when the output voltage is too high. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.2.2.0.9 |
dcOutputVoltageHighAlarmResumeThis trap message is reported when the output voltage
resumes to the normal range from a high value. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.2.2.0.10 |
dcOutputCurrentHighAlarmThis trap message is reported when the output current is too high. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.2.2.0.11 |
dcOutputCurrentHighAlarmResumeThis trap message is reported when the output current
resumes to the normal range from a high value. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.2.2.0.12 |
dcOutputVoltageLowAlarmThis trap message is reported when the output voltage is too low. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.2.2.0.13 |
dcOutputVoltageLowAlarmResumeThis trap message is reported when the output voltage
resumes to the normal range from a low value. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.2.2.0.14 |
dcOutputCurrentLowAlarmThis trap message is reported when the output current is too low. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.2.2.0.15 |
dcOutputCurrentLowAlarmResumeThis trap message is reported when the output current
resumes to the normal range from a low value. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.2.2.0.16 |
overLoadPowerAbnormalAlarmThis trap message is reported when the state of load power is abnormal. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.2.2.0.17 |
overLoadPowerAbnormalAlarmResumeThis trap message is reported when the state of load power recovers to normal. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.2.2.0.18 |
overBattPowerOffAlarmThis trap message is reported when the battery is powered off. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.2.2.0.19 |
overBattPowerOffAlarmResumeThis trap message is reported when the battery is powered on. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.2.2.0.20 |
overLoadPowerOffAlarmThis trap message is reported when the loadpower is powered off. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.2.2.0.21 |
overLoadPowerOffAlarmResumeThis trap message is reported when the loadpower is powered on. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.2.2.0.22 |
acMainsSupplyAlarmThis trap message is reported when the AC mains supply is abnormal. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.2.2.0.23 |
acMainsSupplyAlarmResumeThis trap message is reported when the AC mains supply recovers to normal. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.2.2.0.24 |
batteryLoopAlarmThis trap message is reported when the loop of battery group disconnects. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.2.2.0.25 |
batteryLoopAlarmResumeThis trap message is reported when the loop of battery group connects. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.2.2.0.26 |
batteryFuseAlarmThis trap message is reported when the fuse of battery group disconnects. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.2.2.0.27 |
batteryFuseAlarmResumeThis trap message is reported when the fuse of battery group connects. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.2.2.0.28 |
batteryContachAlarmThis trap message is reported when the contactor of battery group disconnects. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.2.2.0.29 |
batteryContachAlarmResumeThis trap message is reported when the contactor of battery group connects. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.2.2.0.30 |
userModuleOffAlarmThis trap message is reported when the user module is powered off. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.2.2.0.31 |
userModuleOffAlarmResumeThis trap message is reported when the user module is powered on. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.2.2.0.32 |
transferModuleOffAlarmThis trap message is reported when the transfer module is powered off. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.2.2.0.33 |
transferModuleOffAlarmResumeThis trap message is reported when the transfer module is powered on. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.2.2.0.34 |
userModuleSwitchAlarmThis trap message is reported when the user module is switched off. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.2.2.0.35 |
transferModuleSwitchAlarmThis trap message is reported when the transfer module is switched off. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.2.2.0.37 |
loadFuseAlarmThis trap message is reported when the load fuse is abnormal. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.2.2.0.39 |
loadFuseAlarmResumeThis trap message is reported when the load fuse resumes. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.2.2.0.40 |
chargeCtrlStateAlarmThis trap message is reported when the control state of average or floating charge converts. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.2.2.0.41 |
chargeModeAlarmThis trap message is reported when the charge state converts. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.2.2.0.42 |
acCommFailAlarmThis trap message is reported when the AC panel communication fails. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.2.2.0.43 |
acCommFailAlarmResumeThis trap message is reported when the AC panel communication resumes. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.2.2.0.44 |
batteryChargeOverAlarmThis trap message is reported when the Over-current of battery group happens. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.2.2.0.45 |
batteryChargeOverAlarmResumeOThis trap message is reported when the Over-current of battery group resumes. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.2.2.0.46 |
batteryVoltageLackAlarmThis trap message is reported when the voltage of battery group lacks. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.2.2.0.47 |
batteryVoltageLackAlarmResumeThis trap message is reported when the voltage of battery group recovers from lack. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.2.2.0.48 |
loadTwiceOffAlarmThis trap message is reported when the load is powered off twice. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.2.2.0.49 |
loadTwiceOffAlarmResumeThis trap message is reported when the load recovers from powering off twice. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.2.2.0.50 |
loadOnceOffAlarmThis trap message is reported when the load is powered off once. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.2.2.0.51 |
loadOnceOffAlarmResumeThis trap message is reported when the load recovers from powering off once. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.2.2.0.52 |
acInputPowerOffAlarmThis trap message is reported when the AC input is powered off. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.2.2.0.53 |
acInputPowerOffAlarmResumeThis trap message is reported when the AC input power is powered off. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.2.2.0.54 |
acInputLoopSwtichAlarmThis trap message is reported when the AC input loop switches to another one. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.2.2.0.55 |
batteryDischargeTestStartAlarmThis trap message is reported when the battery discharge test starts. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.2.2.0.56 |
batteryDischargeTestStopAlarmThis trap message is reported when the battery discharge test stops. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.2.2.0.57 |
powerProtectAlarmThis trap message is reported when the power protection function is enbaled. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.2.2.0.58 |
powerUndoProtectAlarmThis trap message is reported when the power protection function is disabled. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.2.2.0.59 |
powerCentralOutputModeSwtichAlarmThis trap message is reported when the central output mode swtiches to another one. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.2.2.0.60 |
powerCentralTempretaureAlarmThis trap message is reported when the central tempretaure is abnormal. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.2.2.0.61 |
powerCentralInputAlarmThis trap message is reported when the central input voltage is abnormal. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.2.2.0.62 |
powerCentralOutputAlarmThis trap message is reported when the central output voltage is abnormal. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.2.2.0.63 |
powerRemoteCommFaultAlarmThis trap message is reported when the communiction between the remote and central fails. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.2.2.0.64 |
powerRemoteVoltageAlarmThis trap message is reported when the remote voltage is abnormal. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.2.2.0.65 |
powerLineAlarmThis trap message is reported when the power line is abnormal. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.2.2.0.66 |
powerRemotePowerAlarm1This trap message is reported when the remote power is abnormal. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.2.2.0.67 |
powerRemotePowerAlarm2This trap message is reported when the Line UA is abnormal. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.2.2.0.68 |
powerRemotePowerAlarm3This trap message is reported when the Central load is abnormal. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.2.2.0.69 |
powerConformance OBJECT IDENTIFIER .1.3.6.1.4.1.2011.6.2.3 |
powerCompliances OBJECT IDENTIFIER .1.3.6.1.4.1.2011.6.2.3.1 |
powerGroups OBJECT IDENTIFIER .1.3.6.1.4.1.2011.6.2.3.2 |
hwEnvironPowerTraps OBJECT IDENTIFIER .1.3.6.1.4.1.2011.6.2.4 |
hwEnvironPowerCommonTraps OBJECT IDENTIFIER .1.3.6.1.4.1.2011.6.2.4.1 |
hwEnvironPowerAlarmTraps OBJECT IDENTIFIER .1.3.6.1.4.1.2011.6.2.4.2 |
hwEnvironPowerAlarmTrapsPrefix OBJECT IDENTIFIER .1.3.6.1.4.1.2011.6.2.4.2.0 |
hwEmmPowerBattaryTestStartTrapThe agent generates this trap when the power
device battary discharge test starts. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.4.2.0.1 |
hwEmmPowerBattaryTestStopTrapThe agent generates this trap when the power
device battary discharge test ends. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.4.2.0.2 |
hwEmmPowerAcvolFaultTrapThe agent generates this trap when the power
device AC input voltage is abnormal. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.4.2.0.3 |
hwEmmPowerAcvolRecoverTrapThe agent generates this trap when the power
device AC input voltage recovers. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.4.2.0.4 |
hwEmmPowerDcvolFaultTrapThe agent generates this trap when the power
device DC output voltage is abnormal. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.4.2.0.5 |
hwEmmPowerDcvolRecoverTrapThe agent generates this trap when the power
device DC output voltage recovers. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.4.2.0.6 |
hwEmmPowerBattloopFaultTrapThe agent generates this trap when the power
device the battery loop is broken.
In this case, the function of he backup power is lost. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.4.2.0.7 |
hwEmmPowerBattloopRecoverTrapThe agent generates this trap when the power
device battery loop recovers. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.4.2.0.8 |
hwEmmPowerLoadfuseFaultTrapThe agent generates this trap when the fuse of the power device
is broken. In this case, the device is powered off. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.4.2.0.9 |
hwEmmPowerLoadfuseRecoverTrapThe agent generates this trap when the fuse of the power
device recovers. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.4.2.0.10 |
hwEmmPowerRectifierFaultTrapThe agent generates this trap when the rectifier
module of the power device is abnormal and the spully power may decrease. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.4.2.0.11 |
hwEmmPowerRectifierRecoverTrapThe agent generates this trap when the rectifier module of the
power device recovers. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.4.2.0.12 |
hwEmmDigMainsupplyFaultTrapThe agent generates this trap when the
main supply digital is faulty. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.4.2.0.13 |
hwEmmDigMainsupplyRecoverTrapThe agent generates this trap when the
main supply digital recovers. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.4.2.0.14 |
hwEmmPowerBatteryOffTrapThe agent generates this trap when the power
of battary is off. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.4.2.0.15 |
hwEmmBatt1TempFaultTrapThe agent generates this trap when the
battery group 1 temperature sensor fault
occurs. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.4.2.0.16 |
hwEmmBatt1TempRestoreTrapThe agent generates this trap when the
battery group 1 temperature sensor fault
recovers. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.4.2.0.17 |
hwEmmEnviHumFaultTrapThe agent generates this trap when the
environment humidity sensor fault occurs. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.4.2.0.18 |
hwEmmEnviHumRestoreTrapThe agent generates this trap when the
environment humidity sensor fault recovers. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.4.2.0.19 |
hwEmmEnvi1TempFaultTrapThe agent generates this trap when the
environment 1 temperature sensor fault
occurs. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.4.2.0.20 |
hwEmmEnvi1TempRestoreTrapThe agent generates this trap when the
environment 1 temperature sensor fault
recovers. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.4.2.0.21 |
hwEmmBattTemFaultTrapThe agent generates this trap when the battery
temperature out of normal range. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.4.2.0.22 |
hwEmmBattTemRecoverTrapThe agent generates this trap when the battery
temperature recovers to normal range. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.4.2.0.23 |
hwEmmPowerBatteryOffRecoverTrapThe agent generates this trap when the power
of battary recovers to on state. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.4.2.0.24 |
hwEmmPowerBatteryUnDetectTrapThe agent generates this trap when the
one or more batteries are not detected. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.4.2.0.25 |
hwEmmPowerBatteryDetectRecoverTrapThe agent generates this trap when the
batteries recover. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.4.2.0.26 |
hwPowerModuleMismatchTrapThe agent generates this trap when the
the power supply system detects mismatched power module . NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.4.2.0.27 |
hwPowerModuleRestoreTrapThe agent generates this trap when the power module recovers. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.2.4.2.0.28 |