HUAWEI-ENVIRONMENT-MIB
AI MIB Summary
The HUAWEI-ENVIRONMENT-MIB enables SNMP-based monitoring of Huawei network device chassis health by exposing real-time metrics for temperature, voltage, current, fan speed, and digital input status. This module facilitates proactive fault detection and environmental threshold management for critical hardware components within the device's environment monitoring unit.
The MIB module defines MIB objects which include Environment Monitor Unit, Analog Environment data, Digital Environment data, Out data and Fan data Monitor management MIB interfaces.
Main OID:
hwEnvironment.1.3.6.1.4.1.2011.6.1
167
Objects
Active
Status
4
Dependencies
Imported Objects
Objects
167 total| Object Name |
|---|
hwEnvironmentThe MIB module defines MIB objects which include Environment Monitor Unit,
Analog Environment data, Digital Environment data, Out data and
Fan data Monitor management MIB interfaces. MODULE-IDENTITY .1.3.6.1.4.1.2011.6.1 |
hwEnvironmentMon OBJECT IDENTIFIER .1.3.6.1.4.1.2011.6.1.1 |
hwEnvironmentInfoTableInformation table of Environment Monitor Unit.
The Environment Monitor Unit is some kind of Environment monitoring device
and is used to monitor many kinds of Environment data.
The maximum number of Environment Monitor Units in one device node is 64.
The index of this table is hwEnvEmuIndex.
hwEnvEmuIndex is the index of one Environment Monitor Unit. SEQUENCE OF HwEnvironmentInfoEntry .1.3.6.1.4.1.2011.6.1.1.1 |
hwEnvironmentInfoEntryInformation table of Environment Monitor Unit.
The Environment Monitor Unit is some kind of Environment monitoring device
and is used to monitor many kinds of Environment data.
The maximum number of Environment Monitor Units in one device node is 64.
The index of this entry is hwEnvEmuIndex.
hwEnvEmuIndex is the index of one Environment Monitor Unit. HwEnvironmentInfoEntry .1.3.6.1.4.1.2011.6.1.1.1.1 |
hwEnvEmuIndexhwEnvEmuIndex is the index of the Environment monitoring unit,
used as the index of hwEnvironmentInfoTable.
Range: 0 - 2048ro Integer32 .1.3.6.1.4.1.2011.6.1.1.1.1.1 |
hwEnvEmuTypeType of the physical monitoring devices associated with the environment monitoring unit.
Options:
1.h302ESC(1) -Type of the physical monitoring devices is H302ESC
2.h303ESC(2) -Type of the physical monitoring devices is H303ESC
3.h4875(3) -Type of the physical monitoring devices is 4875 power monitoring frame
4.h301ESC(4) -Type of the physical monitoring devices is H301ESC
5.switch(5) -Distribute monitoring frame
6.fanEscFrame(6) -ESC monitoring fan frame
7.fanFrame(7) -monitoring fan frame
8.h4845(8) -4845 power monitoring
9.fanFCBFrame(9) -FCB monitoring fan frame
10.fanFDMUFrame(10) -FDMU monitoring fan frame
11.h304ESC(11) -provides the management function of battery
12.pwma(12) -Type of the physical monitoring devices is pwma
13.h561esc(13) -H561ESC
14.h801esc(14) -H801Esc
15.h612pwbp(15) -H612pwbp
16.pse158(16) -pse158
17.h4805(19) -h4805
18.pdu(20) -pdu
19.acrmu(21) -ac_rmu
20.acfan(22) -ac_fan
21.dcfan(23) -dc_fan
22.rmun1509(24) -rmun1509
23.onps150(25) -onps150
24.h801pmix(26) -h801pmix
25.h4875L(27) -h4875L
26.miniESC(28) -miniESC
27.h831VESC(29) -H831VESC
28.h601VESC(30) -H601VESC
29.h4830L(31) -h4830L
30.h801citx(32) -h801citx
31.h801citd(33) -h801citd
32.h831ccuh(34) -h831ccuh
33.h831pmu(35) -h831pmu
34.pwr3000(36) -a type of power named power 3000, supports 12 rectifier modules
35.tcu(37) -tcu
36.liFeBattery(38) -liFeBattery
37.transemu(39) -a type of emu for transport environment information to managment center
38.smu(40) -site monitoring unit
39.vpea(41) -vector monitoring unit
40.other(255) -otherrw Enumeration .1.3.6.1.4.1.2011.6.1.1.1.1.2 |
hwEnvBoardNameName of the environment monitoring unit.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.2011.6.1.1.1.1.3 |
hwEnvCommStateStatus of the communication between the environment monitoring unit and the device.
The environmental condition can be tested only when the communication is normal.
Options:
1.normal(1) - indicates that communication state is normal
2.shutdown(2) - indicates that communication state is shutdown
3.fault(3) - indicates that communication state is fault
4.abnormal(4) - indicates that communication state is abnormal
5.config(5) - indicates that communication state is configro Enumeration .1.3.6.1.4.1.2011.6.1.1.1.1.4 |
hwEnvRowStatusRowStatus standard operation.
The creation and deletion operations are supported currently.rw RowStatus (SNMPv2-TC) .1.3.6.1.4.1.2011.6.1.1.1.1.5 |
hwEnvVersionVersion information of the environment monitoring unit.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.2011.6.1.1.1.1.6 |
hwEnvFrameIdID of the shelf housing the environment monitoring unit.rw Integer32 .1.3.6.1.4.1.2011.6.1.1.1.1.7 |
hwEnvAdminStatusThe management status of the monitoring unit.
Options:
1.noOperation(1) -no any operation
2.reset(2) -reset the monitoring board
3.manage(3) -manage the monitoring unit
4.unmanage(4) -undo manage the monitoring unit
5.clearsmokealarm(5) -clear the smoke alarm for miniEscrw Enumeration .1.3.6.1.4.1.2011.6.1.1.1.1.8 |
hwEnvSlaveNodeIdID of the slave object that the environment monitoring unit belongs to.
The environment monitoring unit uses the slave object ID to communicate
with the upstream equipment.rw Integer32 .1.3.6.1.4.1.2011.6.1.1.1.1.9 |
hwEnvComTypeThe serial communication protocol type between the monitoring unit
and the upstream equipment. The protocol types used are as follows:
Options:
1.unknown(1) -The protocol types is unknown
2.serialRS485(2) -The protocol types is serialRS485
3.serialRS232(3) -The protocol types is serialRS232
4.serialRS422(4) -The protocol types is serialRS422rw Enumeration .1.3.6.1.4.1.2011.6.1.1.1.1.10 |
hwEnvCLEICodeEnvironment CLEI Code.ro OCTET STRING .1.3.6.1.4.1.2011.6.1.1.1.1.11 |
hwEnvEmuPowerPower of the environment monitoring equipment associated with the
environment monitoring unit. Unit: Watt.ro Integer32 .1.3.6.1.4.1.2011.6.1.1.1.1.12 |
hwEnvEmuTypeNameName of the environment type.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.2011.6.1.1.1.1.13 |
hwAnaChannelTableInformation table of the analog parameters monitored.
The indexes of this table are hwEnvEmuIndex or hwAnaChannelIndex.
hwEnvEmuIndex is the index of the environment monitoring unit,
and hwAnaChannelIndex is the index of the analog parameter that
is monitored by a monitoring unit. SEQUENCE OF HwAnaChannelEntry .1.3.6.1.4.1.2011.6.1.1.2 |
hwAnaChannelEntryInformation table of the analog parameters monitored.
The indexes of this entry are hwEnvEmuIndex or hwAnaChannelIndex.
hwEnvEmuIndex is the index of the environment monitoring unit,
and hwAnaChannelIndex is the index of the analog parameter that
is monitored by a monitoring unit. HwAnaChannelEntry .1.3.6.1.4.1.2011.6.1.1.2.1 |
hwAnaChannelIndexIndex of the analog parameter that is monitored by the monitoring unit.
Range: 0 - 255ro Integer32 .1.3.6.1.4.1.2011.6.1.1.2.1.1 |
hwAnaNameName of the analog parameter that is monitored by a monitoring unit.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.2011.6.1.1.2.1.2 |
hwAnaTypeThis object indicates the type of the sensor that is used to test the
Analog parameter.
Options:
1.invalid(-1) -there is no valid sensor
2.voltage(1) -voltage sensor currently
3.current(2) -current sensor currentlyrw Enumeration .1.3.6.1.4.1.2011.6.1.1.2.1.3 |
hwAnaMeasureTypeThis object indicates the unit of the analog parameter that is tested.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.2011.6.1.1.2.1.4 |
hwAnaWorkHighHigh limit of the analog normal workrw Integer32 .1.3.6.1.4.1.2011.6.1.1.2.1.5 |
hwAnaWorkLowLow limit of the analog normal workrw Integer32 .1.3.6.1.4.1.2011.6.1.1.2.1.6 |
hwAnaAlmHighHigh limit of the analog alarm. The alarm is produced
when the measurement value is higher than this valuerw Integer32 .1.3.6.1.4.1.2011.6.1.1.2.1.7 |
hwAnaAlmLowThe low limit of the analog alarm. The alarm is produced
when the measurement value is lower than this value.rw Integer32 .1.3.6.1.4.1.2011.6.1.1.2.1.8 |
hwAnaCurrentValueThe actual measurement value of the present analog.
Unit: milliro Integer32 UNITS "milli" .1.3.6.1.4.1.2011.6.1.1.2.1.9 |
hwAnaAlarmStateThe status of the present monitored.
Options:
1.normal(1) -indicates that the measurement value is lower than the set high
limit of the alarm, and higher than the low limit
2.overWorkHigh(2) -indicates that the measurement value is higher than the high limit of the alarm
3.belowWorkLow(3) -indicates that the measurement value is lower than the low limit of the alarm
4.abnormal(4) -indicates that the measurement value is outside the scope of limit of the alarm
5.invalid(-1) -indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormalro Enumeration .1.3.6.1.4.1.2011.6.1.1.2.1.10 |
hwAnaRowStatusRowStatus standard operation. The values 1 and 2 are supported currently.
1 indicates the activation status, and 2 indicates the non-activation status.rw RowStatus (SNMPv2-TC) .1.3.6.1.4.1.2011.6.1.1.2.1.11 |
hwAnaAlarmIDAnalog alarm definition.
Options:
1.temperature(1) -temperature alarm
2.humidity(2) -humidity alarm
3.voltage(3) -voltage alarm
4.current(4) -current alarm
5.userDefinedAlarm0(100) -analog user-defined alarm 0
6.userDefinedAlarm1(101) -analog user-defined alarm 1
7.userDefinedAlarm2(102) -analog user-defined alarm 2
8.userDefinedAlarm3(103) -analog user-defined alarm 3
9.userDefinedAlarm4(104) -analog user-defined alarm 4
10.userDefinedAlarm5(105) -analog user-defined alarm 5
11.userDefinedAlarm6(106) -analog user-defined alarm 6
12.userDefinedAlarm7(107) -analog user-defined alarm 7
13.userDefinedAlarm8(108) -analog user-defined alarm 8
14.userDefinedAlarm9(109) -analog user-defined alarm 9
15.userDefinedAlarm10(110) -analog user-defined alarm 10
16.userDefinedAlarm11(111) -analog user-defined alarm 11
17.userDefinedAlarm12(112) -analog user-defined alarm 12
18.userDefinedAlarm13(113) -analog user-defined alarm 13
19.userDefinedAlarm14(114) -analog user-defined alarm 14
20.userDefinedAlarm15(115) -analog user-defined alarm 15
21.default(65535) -default analog alarmrw Enumeration .1.3.6.1.4.1.2011.6.1.1.2.1.12 |
hwDigChannelTableInformation table of the digital parameters monitored.
The indexes of this table are hwEnvEmuIndex and hwDigChannelIndex.
hwEnvEmuIndex is the index of the environment monitoring unit,
and hwDigChannelIndex is the index of the digital parameter that
is monitored by a monitoring unit. SEQUENCE OF HwDigChannelEntry .1.3.6.1.4.1.2011.6.1.1.3 |
hwDigChannelEntryInformation table of the digital parameters monitored.
The indexes of this entry are hwEnvEmuIndex and hwDigChannelIndex.
hwEnvEmuIndex is the index of the environment monitoring unit,
and hwDigChannelIndex is the index of the digital parameter that
is monitored by a monitoring unit. HwDigChannelEntry .1.3.6.1.4.1.2011.6.1.1.3.1 |
hwDigChannelIndexIndex of the digital parameter that is monitored by a monitoring unit.
Range: 0 - 255ro Integer32 .1.3.6.1.4.1.2011.6.1.1.3.1.1 |
hwDigChannelNameName of the digital parameter that is monitored by a monitoring unit.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.2011.6.1.1.3.1.2 |
hwAlmConditionAlarm conditions.
Options:
1.lowLevelAlarm(1) -refers to the alarm produced when the digital sensor detects the low level
2.highLevelAlarm(2) -refers to the alarm produced when the digital sensor detects the high level
3.invalid(-1) -indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormalrw Enumeration .1.3.6.1.4.1.2011.6.1.1.3.1.3 |
hwDigChannelStateThe status of the present monitored digital sensor
Options:
1.normal(1) -indicates that the digital sensor works normally
2.alarm(2) -indicates that the digital sensor produces the alarm signal
3.invalid(-1) -indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormalro Enumeration .1.3.6.1.4.1.2011.6.1.1.3.1.4 |
hwDigRowStatusRowStatus standard operation. The values 1 and 2 are supported currently.
1 indicates the activation status, and 2 indicates the non-activation status.rw RowStatus (SNMPv2-TC) .1.3.6.1.4.1.2011.6.1.1.3.1.5 |
hwDigAlarmIDDigital alarm definition.
Options:
1.acvoltage(1) -ac voltage alarm
2.acswitch(2) -ac switch alarm
3.batteryvoltage(3) -battery voltage alarm
4.batteryfuse(4) -battery fuse alarm
5.loadfuse(5) -load fuse alarm
6.rectifier(6) -rectifier alarm
7.dcpower(7) -dc power alarm
8.cupboarddoor(8) -cupboard alarm
9.roomdoor(9) -room door alarm
10.window(10) -window alarm
11.thief(11) -thief alarm
12.wiring(12) -wiring alarm
13.fan(13) -fan alarm
14.fire(14) -fire alarm
15.fog(15) -fog alarm
16.water(16) -water alarm
17.diesel(17) -diesel alarm
18.smell(18) -smell alarm
19.aircondition(19) -air-condition alarm
20.arrester(20) -arrester alarm
21.dcvoltage(21) -dc voltage
22.outputswitch(22) -output swith
23.userDefinedAlarm0(100) -digital user-defined alarm 0
24.userDefinedAlarm1(101) -digital user-defined alarm 1
25.userDefinedAlarm2(102) -digital user-defined alarm 2
26.userDefinedAlarm3(103) -digital user-defined alarm 3
27.userDefinedAlarm4(104) -digital user-defined alarm 4
28.userDefinedAlarm5(105) -digital user-defined alarm 5
29.userDefinedAlarm6(106) -digital user-defined alarm 6
30.userDefinedAlarm7(107) -digital user-defined alarm 7
31.userDefinedAlarm8(108) -digital user-defined alarm 8
32.userDefinedAlarm9(109) -digital user-defined alarm 9
33.userDefinedAlarm10(110) -digital user-defined alarm 10
34.userDefinedAlarm11(111) -digital user-defined alarm 11
35.userDefinedAlarm12(112) -digital user-defined alarm 12
36.userDefinedAlarm13(113) -digital user-defined alarm 13
37.userDefinedAlarm14(114) -digital user-defined alarm 14
38.userDefinedAlarm15(115) -digital user-defined alarm 15
39.userDefinedAlarm16(116) -digital user-defined alarm 16
40.userDefinedAlarm17(117) -digital user-defined alarm 17
41.userDefinedAlarm18(118) -digital user-defined alarm 18
42.userDefinedAlarm19(119) -digital user-defined alarm 19
43.userDefinedAlarm20(120) -digital user-defined alarm 20
44.userDefinedAlarm21(121) -digital user-defined alarm 21
45.userDefinedAlarm22(122) -digital user-defined alarm 22
46.userDefinedAlarm23(123) -digital user-defined alarm 23
47.userDefinedAlarm24(124) -digital user-defined alarm 24
48.userDefinedAlarm25(125) -digital user-defined alarm 25
49.userDefinedAlarm26(126) -digital user-defined alarm 26
50.userDefinedAlarm27(127) -digital user-defined alarm 27
51.userDefinedAlarm28(128) -digital user-defined alarm 28
52.userDefinedAlarm29(129) -digital user-defined alarm 29
53.userDefinedAlarm30(130) -digital user-defined alarm 30
54.userDefinedAlarm31(131) -digital user-defined alarm 31
55.default(65535) -digital alarmrw Enumeration .1.3.6.1.4.1.2011.6.1.1.3.1.6 |
hwControlOutTableMonitored digital out table.
This table indicates information about whether digital parameter is monitored.
The indexes of this table are hwEnvEmuIndex and hwControlOutIndex.
hwEnvEmuIndex is the index of the monitoring unit,
and hwControlOutIndex is the index of the digital out table monitored in the monitoring unit. SEQUENCE OF HwControlOutEntry .1.3.6.1.4.1.2011.6.1.1.4 |
hwControlOutEntryMonitored digital out table.
This table indicates information about whether digital parameter is monitored.
The indexes of this entry are hwEnvEmuIndex and hwControlOutIndex.
hwEnvEmuIndex is the index of the monitoring unit,
and hwControlOutIndex is the index of the digital out table monitored in the monitoring unit. HwControlOutEntry .1.3.6.1.4.1.2011.6.1.1.4.1 |
hwControlOutIndexIndex of the digital out table monitored in the monitoring unit
Range: 0 - 255ro Integer32 .1.3.6.1.4.1.2011.6.1.1.4.1.1 |
hwControlOutNameName of the monitored digital out tablerw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.2011.6.1.1.4.1.2 |
hwControlOutAdminStatusControl Out administration: executes the on/off operation.
Options:
1. on(1) - trun on
2. off(2) - trun offrw Enumeration .1.3.6.1.4.1.2011.6.1.1.4.1.3 |
hwControlOutRowStatusRowStatus standard operation. The values 1 and 2 are supported currently.
1 indicates the activation status, and 2 indicates the non-activation status.rw RowStatus (SNMPv2-TC) .1.3.6.1.4.1.2011.6.1.1.4.1.4 |
hwFanTableInformation table of fan monitoring.
The index of this table is hwEnvEmuIndex that comes from hwEnvironmentInfoTable.
hwEnvEmuIndex is the index of the monitoring unit whose monitoring type is fan. SEQUENCE OF HwFanEntry .1.3.6.1.4.1.2011.6.1.1.5 |
hwFanEntryInformation table of fan monitoring.
The index of this entry is hwEnvEmuIndex that comes from hwEnvironmentInfoTable.
hwEnvEmuIndex is the index of the monitoring unit whose monitoring type is fan. HwFanEntry .1.3.6.1.4.1.2011.6.1.1.5.1 |
hwFanNameFan namerw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.2011.6.1.1.5.1.1 |
hwFanControlModeThe fan control modes of the fan frame.
Options:
1.manual(1) -indicates that the fan is always on, and the fan speed can be manually adjusted
2.emuAuto(2) -indicates that the fan is in the automatic mode, and can be automatically
controlled depending on the temperature of the fan
3.fixed(3) -indicates that the fan is in the fixed mode, and adjusting its speed is not allowed
4.mainboardAuto(4) -indicates that the fan is in the automatic mode, and can be automatically
controlled depending on the temperature of the boards in the framerw Enumeration .1.3.6.1.4.1.2011.6.1.1.5.1.2 |
hwFanControlStateFor ESC fan, all should be checked to turn on the fan,
while all should not be checked to turn off the fan.
Options:
1.fan1(0) -indicates that the first fan needs to be opened
2.fan2(1) -indicates that the second fan needs to be opened
3.fan3(2) -indicates that the third fan needs to be opened
4.fan4(3) -indicates that the fourth fan needs to be opened
5.fan5(4) -indicates that the fifth fan needs to be opened
6.fan6(5) -indicates that the sixth fan needs to be openedrw Bits .1.3.6.1.4.1.2011.6.1.1.5.1.3 |
hwESCFanTempAutoOnThe fan temperature set, in unit of centigrade.
The MIB object only functions for the fan monitoring board of ESC and
is not applicable to the type of fan monitoring board.
Only when the fan control mode of the fan frame is hwFanControl =auto (3),
the temperature control mode will take effect.
When detecting the environment temperature higher than the set value,
the fan will be on (or increase its rotation).rw Integer32 .1.3.6.1.4.1.2011.6.1.1.5.1.4 |
hwESCFanTempAutoOffThe fan temperature set, in unit of centigrade.
The MIB object only functions for the fan monitoring board of ESC and
is not applicable to the type of fan monitoring board.
Only when the fan control mode of the fan frame is hwFanControl =auto (3),
the temperature control mode will take effect.
When detecting the environment temperature is lower than the set value,
the fan will be turned off (decrease its rotation).rw Integer32 .1.3.6.1.4.1.2011.6.1.1.5.1.5 |
hwFanRowStatusRowStatus standard operation.rw RowStatus (SNMPv2-TC) .1.3.6.1.4.1.2011.6.1.1.5.1.6 |
hwCurrentTempThe present temperature value, in unit of cent-centigradero Integer32 .1.3.6.1.4.1.2011.6.1.1.5.1.7 |
hwFanSpeedModeThe adjusting rotation mode of the fan.
Options:
1.continue(1) -continuous control
2.discontinue(2) -discrete control
3.percent(3) -duty ratio control
4.invalid(-1) -indicates that the device can not get the value, e.g. the EMU does not support
this operation, or the EMU state is abnormalrw Enumeration .1.3.6.1.4.1.2011.6.1.1.5.1.8 |
hwFanSpeedWhen hwFanSpeedMode is the continue mode, 0 indicates the present wind speed +1, while 1 indicates the present wind speed -1.
When hwFanSpeedMode is discontinuous, 0 indicates fixed high speed, while 1 indicates fixed low speed.
When hwFanSpeedMode is percent, the value delivered by the main control is the percent value, ranging from 35 to 100, used to initialize the rotation of fan for various device main controls.
invalid(-1) indicates that the fan tray does not work normally. For example, the fan tray is disconnected from the control board, or some of the fans in the fan tray are blocked.rw Integer32 .1.3.6.1.4.1.2011.6.1.1.5.1.9 |
hwFanTypeDescriptionFan Type Description. The values 1 and 2 are supported currently.
1 indicates the activation status, and 2 indicates the non-activation status.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.2011.6.1.1.5.1.10 |
hwTcuTableInformation table of temperature control unit.
The index of this table is hwEnvEmuIndex that comes from hwEnvironmentInfoTable.
hwEnvEmuIndex is the index of the monitoring unit whose monitoring type is temperature control unit. SEQUENCE OF HwTcuEntry .1.3.6.1.4.1.2011.6.1.1.6 |
hwTcuEntryInformation table of temperature control unit.
The index of this entry is hwEnvEmuIndex that comes from hwEnvironmentInfoTable.
hwEnvEmuIndex is the index of the monitoring unit whose monitoring type is temperature control unit. HwTcuEntry .1.3.6.1.4.1.2011.6.1.1.6.1 |
hwTcuHeatExchangerTypeHeat Exchanger Type Description.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.2011.6.1.1.6.1.1 |
hwTcuExternalFanRevThe rev of Heat Exchanger outer fan, in unit of RMP (rotate per minite)ro Integer32 .1.3.6.1.4.1.2011.6.1.1.6.1.2 |
hwTcuInternalFanRevThe rev of Heat Exchanger inner fan, in unit of RMP (rotate per minite)ro Integer32 .1.3.6.1.4.1.2011.6.1.1.6.1.3 |
hwTcuStartHeatTempThe temperature of Heat Exchanger starts to heat up, in unit of Celsiusrw Integer32 .1.3.6.1.4.1.2011.6.1.1.6.1.4 |
hwTcuStopHeatTempThe temperature of Heat Exchanger stops heating, in unit of Celsiusrw Integer32 .1.3.6.1.4.1.2011.6.1.1.6.1.5 |
snmpTrapsDef OBJECT IDENTIFIER .1.3.6.1.4.1.2011.6.1.2 |
emmsnmpTraps OBJECT IDENTIFIER .1.3.6.1.4.1.2011.6.1.2.0 |
envCommAlarmThe communication alarm of environment monitoring board,
reporting the environment monitoring unit ID.
This trap message is reported when the communication between the emu and control board is fault. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.1.2.0.1 |
envCommAlarmResumeThe communication alarm recovery of the environment monitoring,
reporting the environment monitoring unit ID.
This trap message is reported when the communication between the emu and control board resumes. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.1.2.0.2 |
anaFaultAlarmThe alarm recovery of the analog exception,
reporting the environment monitoring unit ID.
This trap message is reported when there is an analog exception in emu. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.1.2.0.3 |
anaFaultAlarmResumeThe alarm recovery of the analog exception,
reporting the environment monitoring unit ID.
This trap message is reported when the analog exception recovery in emu. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.1.2.0.4 |
anaTooHighAlarmThe alarm of too high an analog, reporting the environment
monitoring unit ID and the channel ID of the analog sensor.
This trap message is reported when an analog value is too high. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.1.2.0.5 |
anaTooHighAlarmResumeThe alarm of too high analog resume,
reporting the environment monitoring unit ID.
This trap message is reported when an analog value
returns to normal range from the high value. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.1.2.0.6 |
anaTooLowAlarmThe alarm of too low an analog, reporting the environment
monitoring unit ID and the channel ID of the analog sensor.
This trap message is reported when an analog value is too low. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.1.2.0.7 |
anaTooLowAlarmResumeThe alarm of too low an analog, reporting the
environment monitoring unit ID.
This trap message is reported when an analog value
returns to normal range from the low value. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.1.2.0.8 |
controlAlarmThe control alarm, reporting the environment monitoring unit ID.
This trap message is reported when emu control operation fails. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.1.2.0.9 |
controlAlarmResumeThe control alarm, reporting the environment monitoring unit ID.
This trap message is reported when emu control operation resumes. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.1.2.0.10 |
digtalMeasureAlarmThe digital measure alarm, reporting the environment
monitoring unit ID and the channel ID of the digital sensor.
This trap message is reported when emu measure operation fails. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.1.2.0.11 |
digtaleasureAlarmResumeThe digital measure alarm recovery, reporting the environment
monitoring unit ID and the channel ID of the digital sensor.
This trap message is reported when emu measure operation resumes. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.1.2.0.12 |
fanExistsAlarmFan nonexistance alarm.
This trap message is reported when there is no fan device connected to control board. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.1.2.0.13 |
fanExistsAlarmResumeFan nonexistance alarm recovery.
This trap message is reported when there is a fan device connected to control board. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.1.2.0.14 |
fanRunStateAlarmFan running status alarm.
This trap message is reported when the fan run state gets abnormal. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.1.2.0.15 |
envConformance OBJECT IDENTIFIER .1.3.6.1.4.1.2011.6.1.3 |
envCompliances OBJECT IDENTIFIER .1.3.6.1.4.1.2011.6.1.3.1 |
envGroups OBJECT IDENTIFIER .1.3.6.1.4.1.2011.6.1.3.2 |
hwEnvironTraps OBJECT IDENTIFIER .1.3.6.1.4.1.2011.6.1.4 |
hwEnvironCommonTraps OBJECT IDENTIFIER .1.3.6.1.4.1.2011.6.1.4.1 |
hwEnvironCommonTrapsPrefix OBJECT IDENTIFIER .1.3.6.1.4.1.2011.6.1.4.1.0 |
hwEmmEmuAutofindTrapThe agent generates this trap when a new
EMU autofind. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.1.4.1.0.1 |
hwEnvironAlarmTraps OBJECT IDENTIFIER .1.3.6.1.4.1.2011.6.1.4.2 |
hwEnvironEmuAlarmTraps OBJECT IDENTIFIER .1.3.6.1.4.1.2011.6.1.4.2.1 |
hwEnvironEmuAlarmTrapsPrefix OBJECT IDENTIFIER .1.3.6.1.4.1.2011.6.1.4.2.1.0 |
hwEmmEmufailTrapThe agent generates this trap when the
communication of the EMU with the host
is abnormal. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.1.4.2.1.0.1 |
hwEmmEmuRecoverTrapThe agent generates this trap when the
communication of the EMU with the host
recovers. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.1.4.2.1.0.2 |
hwEmmEmuHardwareFaultTrapThe agent generates this trap when the
a Hardware exception occurs. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.1.4.2.1.0.3 |
hwEmmEmuHardwareRecoverTrapThe agent generates this trap when the
a Hardware exception Recover NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.1.4.2.1.0.4 |
hwEmmEmuAutofindFailTrapThe agent generates this trap when the
emu autofind fail. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.1.4.2.1.0.5 |
hwEmmEmuFanStateTrapThe agent generates this trap when
the fan is not configured or fails. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.1.4.2.1.0.6 |
hwEnvironAnaAlarmTraps OBJECT IDENTIFIER .1.3.6.1.4.1.2011.6.1.4.2.2 |
hwEnvironAnaAlarmTrapsPrefix OBJECT IDENTIFIER .1.3.6.1.4.1.2011.6.1.4.2.2.0 |
hwEmmAnaUnnamedFaultTrapThe agent generates this trap when an unnamed
analog alarm occurs. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.1.4.2.2.0.1 |
hwEmmAnaUnnamedRecoverTrapThe agent generates this trap when an unnamed
analog alarm recovers. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.1.4.2.2.0.2 |
hwEmmAnaTempFaultTrapThe agent generates this trap when the analog
temperature alarm occurs. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.1.4.2.2.0.3 |
hwEmmAnaTempRecoverTrapThe agent generates this trap when the analog
temperature alarm recovers. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.1.4.2.2.0.4 |
hwEmmAnaHumyFaultTrapThe agent generates this trap when the analog
humidity alarm occurs. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.1.4.2.2.0.5 |
hwEmmAnaHumyRecoverTrapThe agent generates this trap when the analog
humidity alarm recovers. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.1.4.2.2.0.6 |
hwEmmAnaVoltFaultTrapThe agent generates this trap when the analog
voltage alarm occurs. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.1.4.2.2.0.7 |
hwEmmAnaVoltRecoverTrapThe agent generates this trap when the analog
voltage alarm recovers. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.1.4.2.2.0.8 |
hwEmmAnaCurrentFaultTrapThe agent generates this trap when the analog
current alarm occurs. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.1.4.2.2.0.9 |
hwEmmAnaCurrentRecoverTrapThe agent generates this trap when the analog
current alarm recovers. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.1.4.2.2.0.10 |
hwEnvironDigAlarmTraps OBJECT IDENTIFIER .1.3.6.1.4.1.2011.6.1.4.2.3 |
hwEnvironDigAlarmTrapsPrefix OBJECT IDENTIFIER .1.3.6.1.4.1.2011.6.1.4.2.3.0 |
hwEmmDigFanBlockFaultTrapThe agent generates this trap when the
fan is blocked. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.1.4.2.3.0.1 |
hwEmmDigFanBlockRecoverTrapThe agent generates this trap when the
fan is recovered from block. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.1.4.2.3.0.2 |
hwEmmDigFanTempHighFaultTrapThe agent generates this trap when the
temperature of fan is too high. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.1.4.2.3.0.3 |
hwEmmDigFanTempHighRecoverTrapThe agent generates this trap when the
temperature of fan recover from too high. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.1.4.2.3.0.4 |
hwEmmDigUnnamedFaultTrapThe agent generates this trap when a
unnamed digital fault occurs. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.1.4.2.3.0.5 |
hwEmmDigUnnamedRecoverTrapThe agent generates this trap when a
unnamed digital recovers. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.1.4.2.3.0.6 |
hwEmmDigOutputswitchFaultTrapThe agent generates this trap when Output
switch digital fault occurs. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.1.4.2.3.0.7 |
hwEmmDigOutputswitchRecoverTrapThe agent generates this trap when Output
switch digital recovers. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.1.4.2.3.0.8 |
hwEmmDigAcvolFaultTrapThe agent generates this trap when
The AC voltage is out of the normal
range. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.1.4.2.3.0.11 |
hwEmmDigAcvolRecoverTrapThe agent generates this trap when
The AC voltage recovers to the
normal range. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.1.4.2.3.0.12 |
hwEmmDigAcswitchFaultTrapThe agent generates this trap when
The AC switch is out of the normal
range. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.1.4.2.3.0.13 |
hwEmmDigAcswitchRecoverTrapThe agent generates this trap when
The AC switch recovers to the
normal range. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.1.4.2.3.0.14 |
hwEmmDigBattvolFaultTrapThe agent generates this trap when
The batt vol is out of the normal
range. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.1.4.2.3.0.15 |
hwEmmDigBattvolRecoverTrapThe agent generates this trap when
The batt vol recovers to the
normal range. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.1.4.2.3.0.16 |
hwEmmDigBattfuseFaultTrapThe agent generates this trap when
The battery fuse is out of the normal
range. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.1.4.2.3.0.17 |
hwEmmDigBattfuseRecoverTrapThe agent generates this trap when
The battery fuse recovers to the
normal range. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.1.4.2.3.0.18 |
hwEmmDigLoadfuseFaultTrapThe agent generates this trap when
The load fuse is out of the normal
range. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.1.4.2.3.0.19 |
hwEmmDigLoadfuseRecoverTrapThe agent generates this trap when
The load fuse recovers to the
normal range. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.1.4.2.3.0.20 |
hwEmmDigRectifierFaultTrapThe agent generates this trap when
The Rectifier is out of the normal
range. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.1.4.2.3.0.21 |
hwEmmDigRectifierRecoverTrapThe agent generates this trap when
The Rectifier recovers to the
normal range. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.1.4.2.3.0.22 |
hwEmmDigDcpowerFaultTrapThe agent generates this trap when
The dc-power is out of the normal
range. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.1.4.2.3.0.23 |
hwEmmDigDcpowerRecoverTrapThe agent generates this trap when
The dc-power recovers to the
normal range. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.1.4.2.3.0.24 |
hwEmmDigRoomdoorFaultTrapThe agent generates this trap when
The Roomdoor is out of the normal
range. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.1.4.2.3.0.25 |
hwEmmDigRoomdoorRecoverTrapThe agent generates this trap when
The Roomdoor recovers to the
normal range. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.1.4.2.3.0.26 |
hwEmmDigTheftFaultTrapThe agent generates this trap when
The Roomdoor is out of the normal
range. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.1.4.2.3.0.27 |
hwEmmDigTheftRecoverTrapThe agent generates this trap when
The Roomdoor recovers to the
normal range. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.1.4.2.3.0.28 |
hwEmmDigWiringFaultTrapThe agent generates this trap when
The WIRING is out of the normal
range. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.1.4.2.3.0.29 |
hwEmmDigWiringRecoverTrapThe agent generates this trap when
The WIRING recovers to the
normal range. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.1.4.2.3.0.30 |
hwEmmDigFanFaultTrapThe agent generates this trap when
The FAN is out of the normal
range. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.1.4.2.3.0.31 |
hwEmmDigFanRecoverTrapThe agent generates this trap when
The FAN recovers to the normal
range. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.1.4.2.3.0.32 |
hwEmmDigFireFaultTrapThe agent generates this trap when
The Fire is out of the normal
range. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.1.4.2.3.0.33 |
hwEmmDigFireRecoverTrapThe agent generates this trap when
The Fire recovers to the normal
range. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.1.4.2.3.0.34 |
hwEmmDigFogFaultTrapThe agent generates this trap when
The Fog is out of the normal
range. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.1.4.2.3.0.35 |
hwEmmDigFogRecoverTrapThe agent generates this trap when
The Fog recovers to the normal
range. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.1.4.2.3.0.36 |
hwEmmDigWaterFaultTrapThe agent generates this trap when
The Water is out of the normal
range. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.1.4.2.3.0.37 |
hwEmmDigWaterRecoverTrapThe agent generates this trap when
The Water recovers to the normal
range. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.1.4.2.3.0.38 |
hwEmmDigDieselFaultTrapThe agent generates this trap when
The Diesel is out of the normal
range. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.1.4.2.3.0.39 |
hwEmmDigDieselRecoverTrapThe agent generates this trap when
The Diesel recovers to the normal
range. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.1.4.2.3.0.40 |
hwEmmDigSmellFaultTrapThe agent generates this trap when
The Smell is out of the normal
range. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.1.4.2.3.0.41 |
hwEmmDigSmellRecoverTrapThe agent generates this trap when
The Smell recovers to the normal
range. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.1.4.2.3.0.42 |
hwEmmDigAirconditionFaultTrapThe agent generates this trap when
The Air condition is out of the normal
range. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.1.4.2.3.0.43 |
hwEmmDigAirconditionRecoverTrapThe agent generates this trap when
The Air condition recovers to the normal
range. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.1.4.2.3.0.44 |
hwEmmDigArrsterFaultTrapThe agent generates this trap when
The arrester is out of the normal
range. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.1.4.2.3.0.45 |
hwEmmDigArrsterRecoverTrapThe agent generates this trap when
The arrester recovers to the normal
range. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.1.4.2.3.0.46 |
hwEmmDigDcvolFaultTrapThe agent generates this trap when
The DC VOL is out of the normal
range. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.1.4.2.3.0.47 |
hwEmmDigDcvolRecoverTrapThe agent generates this trap when
The DC VOL recovers to the normal
range. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.1.4.2.3.0.48 |
hwEmmFanCriticalBlockFaultTrapThe agent generates this trap when more
than two fans are blocked. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.1.4.2.3.0.49 |
hwEmmFanCriticalBlockRecoverTrapThe agent generates this trap when the
critical multi-fan blocking recovers. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.1.4.2.3.0.50 |
hwEmmDigitalSwitchOpenTrapThe agent generates this trap when the
48V input switch is closed. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.1.4.2.3.0.51 |
hwEmmDigitalSwitchCloseTrapThe agent generates this trap when the
48V input switch is opened. NOTIFICATION-TYPE .1.3.6.1.4.1.2011.6.1.4.2.3.0.52 |
hwEmmTrapVbOids OBJECT IDENTIFIER .1.3.6.1.4.1.2011.6.1.5 |
hwFanStatusThe status of the fan.
Options:
1.notconfig(1) -The status of the fan is notconfig
2.failure(2) -The status of the fan is failro Enumeration .1.3.6.1.4.1.2011.6.1.5.1 |
hwFailureCauseThe reason of the auto-finding failure:
Options:
1.fullemu(1) -No enough EMU IDs are available
2.shelfnotsupport(2) -The EMU does not support the auto discovery function
3.emunotsupportautofind(3) -The shelf does not support the EMU of this typero Enumeration .1.3.6.1.4.1.2011.6.1.5.2 |
hwEnvAutofindNodeIdThe NodeId of the auto-found EMU.ro Integer32 .1.3.6.1.4.1.2011.6.1.5.3 |
hwEnvAutofindEmuTypeThe type of the auto-found EMU.ro OCTET STRING .1.3.6.1.4.1.2011.6.1.5.4 |
hwEnvAutofindBoardNameThe board name of the auto-found EMU.ro OCTET STRING .1.3.6.1.4.1.2011.6.1.5.5 |