Argus-MIB
The Argus-MIB facilitates SNMP monitoring of SM-series system controllers, specifically exposing the `dcPwrSysDevice` information block to track DC power system status and device health metrics.
Imported Objects
Objects
217 total| Object Name |
|---|
argusThis MIB defines the information block(s) available in system controllers as defined by the following list: - dcPwrSysDevice: the SM-series of controllers MODULE-IDENTITY .1.3.6.1.4.1.7309 |
dcpower OBJECT IDENTIFIER .1.3.6.1.4.1.7309.4 |
dcPwrSysDevice OBJECT IDENTIFIER .1.3.6.1.4.1.7309.4.1 |
dcPwrSysVariable OBJECT IDENTIFIER .1.3.6.1.4.1.7309.4.1.1 |
dcPwrSysChargeVoltsBattery Charge Voltage. The integer value represent a two digit fix decimal (Value = real voltage * 100) in Voltro INTEGER (-1000000000..1000000000) .1.3.6.1.4.1.7309.4.1.1.1 |
dcPwrSysDischargeVoltsBattery Discharge Voltage. The integer value represent a two digit fix decimal (Value = real voltage * 100) in Voltro INTEGER (-1000000000..1000000000) .1.3.6.1.4.1.7309.4.1.1.2 |
dcPwrSysChargeAmpsBattery Charge Current. The integer value represent a two digit fix decimal (Value = real current * 100) in Ampro INTEGER (-1000000000..1000000000) .1.3.6.1.4.1.7309.4.1.1.3 |
dcPwrSysDischargeAmpsBattery Discharge Current. The integer value represent a two digit fix decimal (Value = real current * 100) in Ampro INTEGER (-1000000000..1000000000) .1.3.6.1.4.1.7309.4.1.1.4 |
dcPwrSysMajorAlarmMajor Alarmro INTEGER .1.3.6.1.4.1.7309.4.1.1.5 |
dcPwrSysMinorAlarmMinor Alarmro INTEGER .1.3.6.1.4.1.7309.4.1.1.6 |
dcPwrSysString OBJECT IDENTIFIER .1.3.6.1.4.1.7309.4.1.2 |
dcPwrSysSiteNameSite Namero DisplayString .1.3.6.1.4.1.7309.4.1.2.1 |
dcPwrSysSiteCitySite Cityro DisplayString .1.3.6.1.4.1.7309.4.1.2.2 |
dcPwrSysSiteRegionSite Regionro DisplayString .1.3.6.1.4.1.7309.4.1.2.3 |
dcPwrSysSiteCountrySite Countryro DisplayString .1.3.6.1.4.1.7309.4.1.2.4 |
dcPwrSysContactNameContact Namero DisplayString .1.3.6.1.4.1.7309.4.1.2.5 |
dcPwrSysPhoneNumberPhone Numberro DisplayString .1.3.6.1.4.1.7309.4.1.2.6 |
dcPwrSysSiteNumberSite Numberro DisplayString .1.3.6.1.4.1.7309.4.1.2.7 |
dcPwrSysSystemTypeThe type of system being monitored by the agentro DisplayString .1.3.6.1.4.1.7309.4.1.2.8 |
dcPwrSysSystemSerialThe serial number of the monitored systemro DisplayString .1.3.6.1.4.1.7309.4.1.2.9 |
dcPwrSysSystemNumberThe number of the monitored systemro DisplayString .1.3.6.1.4.1.7309.4.1.2.10 |
dcPwrSysSoftwareVersionThe version of software running on the monitored systemro DisplayString .1.3.6.1.4.1.7309.4.1.2.11 |
dcPwrSysSoftwareTimestampThe time stamp of the software running on the monitored systemro DisplayString .1.3.6.1.4.1.7309.4.1.2.12 |
dcPwrSysTraps OBJECT IDENTIFIER .1.3.6.1.4.1.7309.4.1.3 |
dcPwrSysTrap OBJECT IDENTIFIER .1.3.6.1.4.1.7309.4.1.3.0 |
dcPwrSysAlarmActiveTrapA trap issued when one of the alarms on the DC power system controller became active NOTIFICATION-TYPE .1.3.6.1.4.1.7309.4.1.3.0.1 |
dcPwrSysAlarmClearedTrapA trap issued when one of the active alarms on the DC power system controller is cleared NOTIFICATION-TYPE .1.3.6.1.4.1.7309.4.1.3.0.2 |
dcPwrSysRelayTrapA trap issued from a change in state in one of the relays on the DC power system controller NOTIFICATION-TYPE .1.3.6.1.4.1.7309.4.1.3.0.3 |
dcPwrSysComOKTrapA trap to indicate that communications with a DC power system controller has been established. NOTIFICATION-TYPE .1.3.6.1.4.1.7309.4.1.3.0.4 |
dcPwrSysComErrTrapA trap to indicate that communications with a DC power system controller has been lost. NOTIFICATION-TYPE .1.3.6.1.4.1.7309.4.1.3.0.5 |
dcPwrSysAgentStartupTrapA trap to indicate that the agent software has started up. NOTIFICATION-TYPE .1.3.6.1.4.1.7309.4.1.3.0.6 |
dcPwrSysAgentShutdownTrapA trap to indicate that the agent software has shutdown. NOTIFICATION-TYPE .1.3.6.1.4.1.7309.4.1.3.0.7 |
dcPwrSysMajorAlarmActiveTrapA trap issued as a summary of DC power system status. It is sent when the system goes into in Major Alarm NOTIFICATION-TYPE .1.3.6.1.4.1.7309.4.1.3.0.8 |
dcPwrSysMajorAlarmClearedTrapA trap issued as a summary of DC power system status. It is sent when the system comes out of Major Alarm NOTIFICATION-TYPE .1.3.6.1.4.1.7309.4.1.3.0.9 |
dcPwrSysMinorAlarmActiveTrapA trap issued as a summary of DC power system status. It is sent when the system goes into in Minor Alarm NOTIFICATION-TYPE .1.3.6.1.4.1.7309.4.1.3.0.10 |
dcPwrSysMinorAlarmClearedTrapA trap issued as a summary of DC power system status. It is sent when the system comes out of Minor Alarm NOTIFICATION-TYPE .1.3.6.1.4.1.7309.4.1.3.0.11 |
dcPwrSysOutputsTbl OBJECT IDENTIFIER .1.3.6.1.4.1.7309.4.1.4 |
dcPwrSysRelayTbl OBJECT IDENTIFIER .1.3.6.1.4.1.7309.4.1.4.1 |
dcPwrSysRelayCountNumber of relay variables in system controller relay tablero INTEGER .1.3.6.1.4.1.7309.4.1.4.1.1 |
dcPwrSysRelayTableA table of DC power system controller rectifier relay output variables SEQUENCE OF DcPwrSysRelayEntry .1.3.6.1.4.1.7309.4.1.4.1.2 |
dcPwrSysRelayEntryAn entry into the DC power system controller relay output group DcPwrSysRelayEntry .1.3.6.1.4.1.7309.4.1.4.1.2.1 |
dcPwrSysRelayIndexThe index of the relay variable in the power system controller relay output groupro INTEGER .1.3.6.1.4.1.7309.4.1.4.1.2.1.1 |
dcPwrSysRelayNameThe description of the relay variable as reported by the DC power system controller relay output groupro DisplayString .1.3.6.1.4.1.7309.4.1.4.1.2.1.2 |
dcPwrSysRelayIntegerValueThe integer value of the relay variable as reported by the DC power system controller relay output groupro INTEGER (-1000000000..1000000000) .1.3.6.1.4.1.7309.4.1.4.1.2.1.3 |
dcPwrSysRelayStringValueThe string value of the relay variable as reported by the DC power system controller relay output groupro DisplayString .1.3.6.1.4.1.7309.4.1.4.1.2.1.4 |
dcPwrSysRelaySeverityThe integer value of relay severity level of the extra variable as reported by the DC power system controller relay output groupro INTEGER .1.3.6.1.4.1.7309.4.1.4.1.2.1.5 |
dcPwrSysAnalogOpTbl OBJECT IDENTIFIER .1.3.6.1.4.1.7309.4.1.4.2 |
dcPwrSysAnalogOpCountNumber of analog output variables in system controller analog output tablero INTEGER .1.3.6.1.4.1.7309.4.1.4.2.1 |
dcPwrSysAnalogOpTableA table of DC power system controller analog output variables SEQUENCE OF DcPwrSysAnalogOpEntry .1.3.6.1.4.1.7309.4.1.4.2.2 |
dcPwrSysAnalogOpEntryAn entry into the DC power system controller analog output group DcPwrSysAnalogOpEntry .1.3.6.1.4.1.7309.4.1.4.2.2.1 |
dcPwrSysAnalogOpIndexThe index of the analog variable in the power system controller analog output groupro INTEGER .1.3.6.1.4.1.7309.4.1.4.2.2.1.1 |
dcPwrSysAnalogOpNameThe description of the analog variable as reported by the DC power system controller analog output groupro DisplayString .1.3.6.1.4.1.7309.4.1.4.2.2.1.2 |
dcPwrSysAnalogOpIntegerValueThe integer value of the analog variable as reported by the DC power system controller analog output groupro INTEGER (-1000000000..1000000000) .1.3.6.1.4.1.7309.4.1.4.2.2.1.3 |
dcPwrSysAnalogOpStringValueThe string value of the analog variable as reported by the DC power system controller analog output groupro DisplayString .1.3.6.1.4.1.7309.4.1.4.2.2.1.4 |
dcPwrSysAnalogOpSeverityThe integer value of analog severity level of the extra variable as reported by the DC power system controller analog output groupro INTEGER .1.3.6.1.4.1.7309.4.1.4.2.2.1.5 |
dcPwrSysAlrmsTbl OBJECT IDENTIFIER .1.3.6.1.4.1.7309.4.1.5 |
dcPwrSysRectAlrmTbl OBJECT IDENTIFIER .1.3.6.1.4.1.7309.4.1.5.1 |
dcPwrSysRectAlrmCountNumber of rectifier alarm variables in system controller alarm tablero INTEGER .1.3.6.1.4.1.7309.4.1.5.1.1 |
dcPwrSysRectAlrmTableA table of DC power system controller rectifier alarm variables SEQUENCE OF DcPwrSysRectAlrmEntry .1.3.6.1.4.1.7309.4.1.5.1.2 |
dcPwrSysRectAlrmEntryAn entry into the DC power system controller rectifier alarm group DcPwrSysRectAlrmEntry .1.3.6.1.4.1.7309.4.1.5.1.2.1 |
dcPwrSysRectAlrmIndexThe index of the alarm variable in the DC power system controller table rectifier alarm groupro INTEGER .1.3.6.1.4.1.7309.4.1.5.1.2.1.1 |
dcPwrSysRectAlrmNameThe description of the alarm variable as reported by the DC power system controller rectifier alarm groupro DisplayString .1.3.6.1.4.1.7309.4.1.5.1.2.1.2 |
dcPwrSysRectAlrmIntegerValueThe integer value of the alarm variable as reported by the DC power system controller rectifier alarm groupro INTEGER (-1000000000..1000000000) .1.3.6.1.4.1.7309.4.1.5.1.2.1.3 |
dcPwrSysRectAlrmStringValueThe string value of the alarm variable as reported by the DC power system controller rectifier alarm groupro DisplayString .1.3.6.1.4.1.7309.4.1.5.1.2.1.4 |
dcPwrSysRectAlrmSeverityThe integer value of alarm severity level of the extra variable as reported by the DC power system controller rectifier alarm groupro INTEGER .1.3.6.1.4.1.7309.4.1.5.1.2.1.5 |
dcPwrSysDigAlrmTbl OBJECT IDENTIFIER .1.3.6.1.4.1.7309.4.1.5.2 |
dcPwrSysDigAlrmCountNumber of digital alarm variables in system controller alarm tablero INTEGER .1.3.6.1.4.1.7309.4.1.5.2.1 |
dcPwrSysDigAlrmTableA table of DC power system controller digital alarm variables SEQUENCE OF DcPwrSysDigAlrmEntry .1.3.6.1.4.1.7309.4.1.5.2.2 |
dcPwrSysDigAlrmEntryAn entry into the DC power system controller digital alarm group DcPwrSysDigAlrmEntry .1.3.6.1.4.1.7309.4.1.5.2.2.1 |
dcPwrSysDigAlrmIndexThe index of the alarm variable in the DC power system controller table digital alarm groupro INTEGER .1.3.6.1.4.1.7309.4.1.5.2.2.1.1 |
dcPwrSysDigAlrmNameThe description of the alarm variable as reported by the DC power system controller digital alarm groupro DisplayString .1.3.6.1.4.1.7309.4.1.5.2.2.1.2 |
dcPwrSysDigAlrmIntegerValueThe integer value of the alarm variable as reported by the DC power system controller digital alarm groupro INTEGER (-1000000000..1000000000) .1.3.6.1.4.1.7309.4.1.5.2.2.1.3 |
dcPwrSysDigAlrmStringValueThe string value of the alarm variable as reported by the DC power system controller digital alarm groupro DisplayString .1.3.6.1.4.1.7309.4.1.5.2.2.1.4 |
dcPwrSysDigAlrmSeverityThe integer value of alarm severity level of the extra variable as reported by the DC power system controller digital alarm groupro INTEGER .1.3.6.1.4.1.7309.4.1.5.2.2.1.5 |
dcPwrSysCurrAlrmTbl OBJECT IDENTIFIER .1.3.6.1.4.1.7309.4.1.5.3 |
dcPwrSysCurrAlrmCountNumber of current alarm variables in system controller alarm tablero INTEGER .1.3.6.1.4.1.7309.4.1.5.3.1 |
dcPwrSysCurrAlrmTableA table of DC power system controller current alarm variables SEQUENCE OF DcPwrSysCurrAlrmEntry .1.3.6.1.4.1.7309.4.1.5.3.2 |
dcPwrSysCurrAlrmEntryAn entry into the DC power system controller current alarm group DcPwrSysCurrAlrmEntry .1.3.6.1.4.1.7309.4.1.5.3.2.1 |
dcPwrSysCurrAlrmIndexThe index of the alarm variable in the DC power system controller table current alarm groupro INTEGER .1.3.6.1.4.1.7309.4.1.5.3.2.1.1 |
dcPwrSysCurrAlrmNameThe description of the alarm variable as reported by the DC power system controller current alarm groupro DisplayString .1.3.6.1.4.1.7309.4.1.5.3.2.1.2 |
dcPwrSysCurrAlrmIntegerValueThe integer value of the alarm variable as reported by the DC power system controller current alarm groupro INTEGER (-1000000000..1000000000) .1.3.6.1.4.1.7309.4.1.5.3.2.1.3 |
dcPwrSysCurrAlrmStringValueThe string value of the alarm variable as reported by the DC power system controller current alarm groupro DisplayString .1.3.6.1.4.1.7309.4.1.5.3.2.1.4 |
dcPwrSysCurrAlrmSeverityThe integer value of alarm severity level of the extra variable as reported by the DC power system controller current alarm groupro INTEGER .1.3.6.1.4.1.7309.4.1.5.3.2.1.5 |
dcPwrSysVoltAlrmTbl OBJECT IDENTIFIER .1.3.6.1.4.1.7309.4.1.5.4 |
dcPwrSysVoltAlrmCountNumber of voltage alarm variables in system controller alarm tablero INTEGER .1.3.6.1.4.1.7309.4.1.5.4.1 |
dcPwrSysVoltAlrmTableA table of DC power system controller voltage alarm variables SEQUENCE OF DcPwrSysVoltAlrmEntry .1.3.6.1.4.1.7309.4.1.5.4.2 |
dcPwrSysVoltAlrmEntryAn entry into the DC power system controller voltage alarm group DcPwrSysVoltAlrmEntry .1.3.6.1.4.1.7309.4.1.5.4.2.1 |
dcPwrSysVoltAlrmIndexThe index of the alarm variable in the DC power system controller table voltage alarm groupro INTEGER .1.3.6.1.4.1.7309.4.1.5.4.2.1.1 |
dcPwrSysVoltAlrmNameThe description of the alarm variable as reported by the DC power system controller voltage alarm groupro DisplayString .1.3.6.1.4.1.7309.4.1.5.4.2.1.2 |
dcPwrSysVoltAlrmIntegerValueThe integer value of the alarm variable as reported by the DC power system controller voltage alarm groupro INTEGER (-1000000000..1000000000) .1.3.6.1.4.1.7309.4.1.5.4.2.1.3 |
dcPwrSysVoltAlrmStringValueThe string value of the alarm variable as reported by the DC power system controller voltage alarm groupro DisplayString .1.3.6.1.4.1.7309.4.1.5.4.2.1.4 |
dcPwrSysVoltAlrmSeverityThe integer value of alarm severity level of the extra variable as reported by the DC power system controller voltage alarm groupro INTEGER .1.3.6.1.4.1.7309.4.1.5.4.2.1.5 |
dcPwrSysBattAlrmTbl OBJECT IDENTIFIER .1.3.6.1.4.1.7309.4.1.5.5 |
dcPwrSysBattAlrmCountNumber of battery alarm variables in system controller alarm tablero INTEGER .1.3.6.1.4.1.7309.4.1.5.5.1 |
dcPwrSysBattAlrmTableA table of DC power system controller battery alarm variables SEQUENCE OF DcPwrSysBattAlrmEntry .1.3.6.1.4.1.7309.4.1.5.5.2 |
dcPwrSysBattAlrmEntryAn entry into the DC power system controller battery alarm group DcPwrSysBattAlrmEntry .1.3.6.1.4.1.7309.4.1.5.5.2.1 |
dcPwrSysBattAlrmIndexThe index of the alarm variable in the DC power system controller table battery alarm groupro INTEGER .1.3.6.1.4.1.7309.4.1.5.5.2.1.1 |
dcPwrSysBattAlrmNameThe description of the alarm variable as reported by the DC power system controller battery alarm groupro DisplayString .1.3.6.1.4.1.7309.4.1.5.5.2.1.2 |
dcPwrSysBattAlrmIntegerValueThe integer value of the alarm variable as reported by the DC power system controller battery alarm groupro INTEGER (-1000000000..1000000000) .1.3.6.1.4.1.7309.4.1.5.5.2.1.3 |
dcPwrSysBattAlrmStringValueThe string value of the alarm variable as reported by the DC power system controller battery alarm groupro DisplayString .1.3.6.1.4.1.7309.4.1.5.5.2.1.4 |
dcPwrSysBattAlrmSeverityThe integer value of alarm severity level of the extra variable as reported by the DC power system controller battery alarm groupro INTEGER .1.3.6.1.4.1.7309.4.1.5.5.2.1.5 |
dcPwrSysTempAlrmTbl OBJECT IDENTIFIER .1.3.6.1.4.1.7309.4.1.5.6 |
dcPwrSysTempAlrmCountNumber of temperature alarm variables in system controller alarm tablero INTEGER .1.3.6.1.4.1.7309.4.1.5.6.1 |
dcPwrSysTempAlrmTableA table of DC power system controller temperature alarm variables SEQUENCE OF DcPwrSysTempAlrmEntry .1.3.6.1.4.1.7309.4.1.5.6.2 |
dcPwrSysTempAlrmEntryAn entry into the DC power system controller temperature alarm group DcPwrSysTempAlrmEntry .1.3.6.1.4.1.7309.4.1.5.6.2.1 |
dcPwrSysTempAlrmIndexThe index of the alarm variable in the DC power system controller table temperature alarm groupro INTEGER .1.3.6.1.4.1.7309.4.1.5.6.2.1.1 |
dcPwrSysTempAlrmNameThe description of the alarm variable as reported by the DC power system controller temperature alarm groupro DisplayString .1.3.6.1.4.1.7309.4.1.5.6.2.1.2 |
dcPwrSysTempAlrmIntegerValueThe integer value of the alarm variable as reported by the DC power system controller temperature alarm groupro INTEGER (-1000000000..1000000000) .1.3.6.1.4.1.7309.4.1.5.6.2.1.3 |
dcPwrSysTempAlrmStringValueThe string value of the alarm variable as reported by the DC power system controller temperature alarm groupro DisplayString .1.3.6.1.4.1.7309.4.1.5.6.2.1.4 |
dcPwrSysTempAlrmSeverityThe integer value of alarm severity level of the extra variable as reported by the DC power system controller temperature alarm groupro INTEGER .1.3.6.1.4.1.7309.4.1.5.6.2.1.5 |
dcPwrSysCustomAlrmTbl OBJECT IDENTIFIER .1.3.6.1.4.1.7309.4.1.5.7 |
dcPwrSysCustomAlrmCountNumber of custom alarm variables in system controller alarm tablero INTEGER .1.3.6.1.4.1.7309.4.1.5.7.1 |
dcPwrSysCustomAlrmTableA table of DC power system controller custom alarm variables SEQUENCE OF DcPwrSysCustomAlrmEntry .1.3.6.1.4.1.7309.4.1.5.7.2 |
dcPwrSysCustomAlrmEntryAn entry into the DC power system controller custom alarm group DcPwrSysCustomAlrmEntry .1.3.6.1.4.1.7309.4.1.5.7.2.1 |
dcPwrSysCustomAlrmIndexThe index of the alarm variable in the DC power system controller table custom alarm groupro INTEGER .1.3.6.1.4.1.7309.4.1.5.7.2.1.1 |
dcPwrSysCustomAlrmNameThe description of the alarm variable as reported by the DC power system controller custom alarm groupro DisplayString .1.3.6.1.4.1.7309.4.1.5.7.2.1.2 |
dcPwrSysCustomAlrmIntegerValueThe integer value of the alarm variable as reported by the DC power system controller custom alarm groupro INTEGER (-1000000000..1000000000) .1.3.6.1.4.1.7309.4.1.5.7.2.1.3 |
dcPwrSysCustomAlrmStringValueThe string value of the alarm variable as reported by the DC power system controller custom alarm groupro DisplayString .1.3.6.1.4.1.7309.4.1.5.7.2.1.4 |
dcPwrSysCustomAlrmSeverityThe integer value of alarm severity level of the extra variable as reported by the DC power system controller custom alarm groupro INTEGER .1.3.6.1.4.1.7309.4.1.5.7.2.1.5 |
dcPwrSysMiscAlrmTbl OBJECT IDENTIFIER .1.3.6.1.4.1.7309.4.1.5.8 |
dcPwrSysMiscAlrmCountNumber of misc alarm variables in system controller alarm tablero INTEGER .1.3.6.1.4.1.7309.4.1.5.8.1 |
dcPwrSysMiscAlrmTableA table of DC power system controller misc alarm variables SEQUENCE OF DcPwrSysMiscAlrmEntry .1.3.6.1.4.1.7309.4.1.5.8.2 |
dcPwrSysMiscAlrmEntryAn entry into the DC power system controller misc alarm group DcPwrSysMiscAlrmEntry .1.3.6.1.4.1.7309.4.1.5.8.2.1 |
dcPwrSysMiscAlrmIndexThe index of the alarm variable in the DC power system controller table misc alarm groupro INTEGER .1.3.6.1.4.1.7309.4.1.5.8.2.1.1 |
dcPwrSysMiscAlrmNameThe description of the alarm variable as reported by the DC power system controller misc alarm groupro DisplayString .1.3.6.1.4.1.7309.4.1.5.8.2.1.2 |
dcPwrSysMiscAlrmIntegerValueThe integer value of the alarm variable as reported by the DC power system controller misc alarm groupro INTEGER (-1000000000..1000000000) .1.3.6.1.4.1.7309.4.1.5.8.2.1.3 |
dcPwrSysMiscAlrmStringValueThe string value of the alarm variable as reported by the DC power system controller misc alarm groupro DisplayString .1.3.6.1.4.1.7309.4.1.5.8.2.1.4 |
dcPwrSysMiscAlrmSeverityThe integer value of alarm severity level of the extra variable as reported by the DC power system controller misc alarm groupro INTEGER .1.3.6.1.4.1.7309.4.1.5.8.2.1.5 |
dcPwrSysCtrlAlrmTbl OBJECT IDENTIFIER .1.3.6.1.4.1.7309.4.1.5.9 |
dcPwrSysCtrlAlrmCountNumber of control alarm variables in system controller alarm tablero INTEGER .1.3.6.1.4.1.7309.4.1.5.9.1 |
dcPwrSysCtrlAlrmTableA table of DC power system controller control alarm variables SEQUENCE OF DcPwrSysCtrlAlrmEntry .1.3.6.1.4.1.7309.4.1.5.9.2 |
dcPwrSysCtrlAlrmEntryAn entry into the DC power system controller control alarm group DcPwrSysCtrlAlrmEntry .1.3.6.1.4.1.7309.4.1.5.9.2.1 |
dcPwrSysCtrlAlrmIndexThe index of the alarm variable in the DC power system controller table control alarm groupro INTEGER .1.3.6.1.4.1.7309.4.1.5.9.2.1.1 |
dcPwrSysCtrlAlrmNameThe description of the alarm variable as reported by the DC power system controller control alarm groupro DisplayString .1.3.6.1.4.1.7309.4.1.5.9.2.1.2 |
dcPwrSysCtrlAlrmIntegerValueThe integer value of the alarm variable as reported by the DC power system controller control alarm groupro INTEGER (-1000000000..1000000000) .1.3.6.1.4.1.7309.4.1.5.9.2.1.3 |
dcPwrSysCtrlAlrmStringValueThe string value of the alarm variable as reported by the DC power system controller control alarm groupro DisplayString .1.3.6.1.4.1.7309.4.1.5.9.2.1.4 |
dcPwrSysCtrlAlrmSeverityThe integer value of alarm severity level of the extra variable as reported by the DC power system controller control alarm groupro INTEGER .1.3.6.1.4.1.7309.4.1.5.9.2.1.5 |
dcPwrSysAdioAlrmTbl OBJECT IDENTIFIER .1.3.6.1.4.1.7309.4.1.5.10 |
dcPwrSysAdioAlrmCountNumber of control alarm variables in Adio alarm tablero INTEGER .1.3.6.1.4.1.7309.4.1.5.10.1 |
dcPwrSysAdioAlrmTableA table of DC power system controller Adio alarm variables SEQUENCE OF DcPwrSysAdioAlrmEntry .1.3.6.1.4.1.7309.4.1.5.10.2 |
dcPwrSysAdioAlrmEntryAn entry into the DC power system controller Adio alarm group DcPwrSysAdioAlrmEntry .1.3.6.1.4.1.7309.4.1.5.10.2.1 |
dcPwrSysAdioAlrmIndexThe index of the alarm variable in the DC power system controller table Adio alarm groupro INTEGER .1.3.6.1.4.1.7309.4.1.5.10.2.1.1 |
dcPwrSysAdioAlrmNameThe description of the alarm variable as reported by the DC power system controller Adio alarm groupro DisplayString .1.3.6.1.4.1.7309.4.1.5.10.2.1.2 |
dcPwrSysAdioAlrmIntegerValueThe integer value of the alarm variable as reported by the DC power system controller Adio alarm groupro INTEGER (-1000000000..1000000000) .1.3.6.1.4.1.7309.4.1.5.10.2.1.3 |
dcPwrSysAdioAlrmStringValueThe string value of the alarm variable as reported by the DC power system controller Adio alarm groupro DisplayString .1.3.6.1.4.1.7309.4.1.5.10.2.1.4 |
dcPwrSysAdioAlrmSeverityThe integer value of alarm severity level of the extra variable as reported by the DC Adio system controller control alarm groupro INTEGER .1.3.6.1.4.1.7309.4.1.5.10.2.1.5 |
dcPwrSysConvAlrmTbl OBJECT IDENTIFIER .1.3.6.1.4.1.7309.4.1.5.11 |
dcPwrSysConvAlrmCountNumber of Converter alarm variables in system controller alarm tablero INTEGER .1.3.6.1.4.1.7309.4.1.5.11.1 |
dcPwrSysConvAlrmTableA table of DC power system controller Converter alarm variables SEQUENCE OF DcPwrSysConvAlrmEntry .1.3.6.1.4.1.7309.4.1.5.11.2 |
dcPwrSysConvAlrmEntryAn entry into the DC power system controller Converter alarm group DcPwrSysConvAlrmEntry .1.3.6.1.4.1.7309.4.1.5.11.2.1 |
dcPwrSysConvAlrmIndexThe index of the alarm variable in the DC power system controller table Converter alarm groupro INTEGER .1.3.6.1.4.1.7309.4.1.5.11.2.1.1 |
dcPwrSysConvAlrmNameThe description of the alarm variable as reported by the DC power system controller Converter alarm groupro DisplayString .1.3.6.1.4.1.7309.4.1.5.11.2.1.2 |
dcPwrSysConvAlrmIntegerValueThe integer value of the alarm variable as reported by the DC power system controller Converter alarm groupro INTEGER (-1000000000..1000000000) .1.3.6.1.4.1.7309.4.1.5.11.2.1.3 |
dcPwrSysConvAlrmStringValueThe string value of the alarm variable as reported by the DC power system controller Converter alarm groupro DisplayString .1.3.6.1.4.1.7309.4.1.5.11.2.1.4 |
dcPwrSysConvAlrmSeverityThe integer value of alarm severity level of the extra variable as reported by the DC power system controller Converter alarm groupro INTEGER .1.3.6.1.4.1.7309.4.1.5.11.2.1.5 |
dcPwrSysInputsTbl OBJECT IDENTIFIER .1.3.6.1.4.1.7309.4.1.6 |
dcPwrSysDigIpTbl OBJECT IDENTIFIER .1.3.6.1.4.1.7309.4.1.6.1 |
dcPwrSysDigIpCountNumber of digital input variables in system controller digital input tablero INTEGER .1.3.6.1.4.1.7309.4.1.6.1.1 |
dcPwrSysDigIpTableA table of DC power system controller digital input variables SEQUENCE OF DcPwrSysDigIpEntry .1.3.6.1.4.1.7309.4.1.6.1.2 |
dcPwrSysDigIpEntryAn entry into the DC power system controller digital input group DcPwrSysDigIpEntry .1.3.6.1.4.1.7309.4.1.6.1.2.1 |
dcPwrSysDigIpIndexThe index of the digital input variable in the DC power system controller table digital input groupro INTEGER .1.3.6.1.4.1.7309.4.1.6.1.2.1.1 |
dcPwrSysDigIpNameThe description of the digital input variable as reported by the DC power system controller digital input groupro DisplayString .1.3.6.1.4.1.7309.4.1.6.1.2.1.2 |
dcPwrSysDigIpIntegerValueThe integer value of the digital input variable as reported by the DC power system controller digital input groupro INTEGER (-1000000000..1000000000) .1.3.6.1.4.1.7309.4.1.6.1.2.1.3 |
dcPwrSysDigIpStringValueThe string value of the digital input variable as reported by the DC power system controller digital input groupro DisplayString .1.3.6.1.4.1.7309.4.1.6.1.2.1.4 |
dcPwrSysCntrlrIpTbl OBJECT IDENTIFIER .1.3.6.1.4.1.7309.4.1.6.2 |
dcPwrSysCntrlrIpCountNumber of controller input variables in system controller controller input tablero INTEGER .1.3.6.1.4.1.7309.4.1.6.2.1 |
dcPwrSysCntrlrIpTableA table of DC power system controller controller input variables SEQUENCE OF DcPwrSysCntrlrIpEntry .1.3.6.1.4.1.7309.4.1.6.2.2 |
dcPwrSysCntrlrIpEntryAn entry into the DC power system controller controller input group DcPwrSysCntrlrIpEntry .1.3.6.1.4.1.7309.4.1.6.2.2.1 |
dcPwrSysCntrlrIpIndexThe index of the controller input variable in the DC power system controller table controller input groupro INTEGER .1.3.6.1.4.1.7309.4.1.6.2.2.1.1 |
dcPwrSysCntrlrIpNameThe description of the controller input variable as reported by the DC power system controller controller input groupro DisplayString .1.3.6.1.4.1.7309.4.1.6.2.2.1.2 |
dcPwrSysCntrlrIpIntegerValueThe integer value of the controller input variable as reported by the DC power system controller controller input groupro INTEGER (-1000000000..1000000000) .1.3.6.1.4.1.7309.4.1.6.2.2.1.3 |
dcPwrSysCntrlrIpStringValueThe string value of the controller input variable as reported by the DC power system controller controller input groupro DisplayString .1.3.6.1.4.1.7309.4.1.6.2.2.1.4 |
dcPwrSysRectIpTbl OBJECT IDENTIFIER .1.3.6.1.4.1.7309.4.1.6.3 |
dcPwrSysRectIpCountNumber of rectifier input variables in system controller rectifier input tablero INTEGER .1.3.6.1.4.1.7309.4.1.6.3.1 |
dcPwrSysRectIpTableA table of DC power system controller rectifier input variables SEQUENCE OF DcPwrSysRectIpEntry .1.3.6.1.4.1.7309.4.1.6.3.2 |
dcPwrSysRectIpEntryAn entry into the DC power system controller rectifier input group DcPwrSysRectIpEntry .1.3.6.1.4.1.7309.4.1.6.3.2.1 |
dcPwrSysRectIpIndexThe index of the rectifier input variable in the DC power system controller table rectifier input groupro INTEGER .1.3.6.1.4.1.7309.4.1.6.3.2.1.1 |
dcPwrSysRectIpNameThe description of the rectifier input variable as reported by the DC power system controller rectifier input groupro DisplayString .1.3.6.1.4.1.7309.4.1.6.3.2.1.2 |
dcPwrSysRectIpIntegerValueThe integer value of the rectifier input variable as reported by the DC power system controller rectifier input groupro INTEGER (-1000000000..1000000000) .1.3.6.1.4.1.7309.4.1.6.3.2.1.3 |
dcPwrSysRectIpStringValueThe string value of the rectifier input variable as reported by the DC power system controller rectifier input groupro DisplayString .1.3.6.1.4.1.7309.4.1.6.3.2.1.4 |
dcPwrSysCustomIpTbl OBJECT IDENTIFIER .1.3.6.1.4.1.7309.4.1.6.4 |
dcPwrSysCustomIpCountNumber of custom input variables in system controller custom input tablero INTEGER .1.3.6.1.4.1.7309.4.1.6.4.1 |
dcPwrSysCustomIpTableA table of DC power system controller digital custom variables SEQUENCE OF DcPwrSysCustomIpEntry .1.3.6.1.4.1.7309.4.1.6.4.2 |
dcPwrSysCustomIpEntryAn entry into the DC power system controller custom input group DcPwrSysCustomIpEntry .1.3.6.1.4.1.7309.4.1.6.4.2.1 |
dcPwrSysCustomIpIndexThe index of the custom input variable in the DC power system controller table custom input groupro INTEGER .1.3.6.1.4.1.7309.4.1.6.4.2.1.1 |
dcPwrSysCustomIpNameThe description of the custom input variable as reported by the DC power system controller custom input groupro DisplayString .1.3.6.1.4.1.7309.4.1.6.4.2.1.2 |
dcPwrSysgCustomIpIntegerValueThe integer value of the custom input variable as reported by the DC power system controller custom input groupro INTEGER (-1000000000..1000000000) .1.3.6.1.4.1.7309.4.1.6.4.2.1.3 |
dcPwrSysCustomIpStringValueThe string value of the custom input variable as reported by the DC power system controller custom input groupro DisplayString .1.3.6.1.4.1.7309.4.1.6.4.2.1.4 |
dcPwrSysConvIpTbl OBJECT IDENTIFIER .1.3.6.1.4.1.7309.4.1.6.5 |
dcPwrSysConvIpCountNumber of Converter input variables in system controller Converter input tablero INTEGER .1.3.6.1.4.1.7309.4.1.6.5.1 |
dcPwrSysConvIpTableA table of DC power system controller Converter input variables SEQUENCE OF DcPwrSysConvIpEntry .1.3.6.1.4.1.7309.4.1.6.5.2 |
dcPwrSysConvIpEntryAn entry into the DC power system controller Converter input group DcPwrSysConvIpEntry .1.3.6.1.4.1.7309.4.1.6.5.2.1 |
dcPwrSysConvIpIndexThe index of the Converter input variable in the DC power system controller table Converter input groupro INTEGER .1.3.6.1.4.1.7309.4.1.6.5.2.1.1 |
dcPwrSysConvIpNameThe description of the Converter input variable as reported by the DC power system controller Converter input groupro DisplayString .1.3.6.1.4.1.7309.4.1.6.5.2.1.2 |
dcPwrSysConvIpIntegerValueThe integer value of the Converter input variable as reported by the DC power system controller Converter input groupro INTEGER (-1000000000..1000000000) .1.3.6.1.4.1.7309.4.1.6.5.2.1.3 |
dcPwrSysConvIpStringValueThe string value of the Converter input variable as reported by the DC power system controller Converter input groupro DisplayString .1.3.6.1.4.1.7309.4.1.6.5.2.1.4 |
dcPwrSysTimerIpTbl OBJECT IDENTIFIER .1.3.6.1.4.1.7309.4.1.6.6 |
dcPwrSysTimerIpCountNumber of Timererter input variables in system controller Timererter input tablero INTEGER .1.3.6.1.4.1.7309.4.1.6.6.1 |
dcPwrSysTimerIpTableA table of DC power system controller Timererter input variables SEQUENCE OF DcPwrSysTimerIpEntry .1.3.6.1.4.1.7309.4.1.6.6.2 |
dcPwrSysTimerIpEntryAn entry into the DC power system controller Timererter input group DcPwrSysTimerIpEntry .1.3.6.1.4.1.7309.4.1.6.6.2.1 |
dcPwrSysTimerIpIndexThe index of the Timererter input variable in the DC power system controller table Timererter input groupro INTEGER .1.3.6.1.4.1.7309.4.1.6.6.2.1.1 |
dcPwrSysTimerIpNameThe description of the Timererter input variable as reported by the DC power system controller Timererter input groupro DisplayString .1.3.6.1.4.1.7309.4.1.6.6.2.1.2 |
dcPwrSysTimerIpIntegerValueThe integer value of the Timererter input variable as reported by the DC power system controller Timererter input groupro INTEGER (-1000000000..1000000000) .1.3.6.1.4.1.7309.4.1.6.6.2.1.3 |
dcPwrSysTimerIpStringValueThe string value of the Timererter input variable as reported by the DC power system controller Timererter input groupro DisplayString .1.3.6.1.4.1.7309.4.1.6.6.2.1.4 |
dcPwrSysCounterIpTbl OBJECT IDENTIFIER .1.3.6.1.4.1.7309.4.1.6.7 |
dcPwrSysCounterIpCountNumber of Countererter input variables in system controller Countererter input tablero INTEGER .1.3.6.1.4.1.7309.4.1.6.7.1 |
dcPwrSysCounterIpTableA table of DC power system controller Countererter input variables SEQUENCE OF DcPwrSysCounterIpEntry .1.3.6.1.4.1.7309.4.1.6.7.2 |
dcPwrSysCounterIpEntryAn entry into the DC power system controller Countererter input group DcPwrSysCounterIpEntry .1.3.6.1.4.1.7309.4.1.6.7.2.1 |
dcPwrSysCounterIpIndexThe index of the Countererter input variable in the DC power system controller table Countererter input groupro INTEGER .1.3.6.1.4.1.7309.4.1.6.7.2.1.1 |
dcPwrSysCounterIpNameThe description of the Countererter input variable as reported by the DC power system controller Countererter input groupro DisplayString .1.3.6.1.4.1.7309.4.1.6.7.2.1.2 |
dcPwrSysCounterIpIntegerValueThe integer value of the Countererter input variable as reported by the DC power system controller Countererter input groupro INTEGER (-1000000000..1000000000) .1.3.6.1.4.1.7309.4.1.6.7.2.1.3 |
dcPwrSysCounterIpStringValueThe string value of the Countererter input variable as reported by the DC power system controller Countererter input groupro DisplayString .1.3.6.1.4.1.7309.4.1.6.7.2.1.4 |
dcPwrExternalControls OBJECT IDENTIFIER .1.3.6.1.4.1.7309.4.1.8 |
dcPwrSysResyncAlarmsSend/Resend all active alarms that were previously sent through SNMP notification.rw INTEGER .1.3.6.1.4.1.7309.4.1.8.1 |
dcPwrVarbindNameReference OBJECT IDENTIFIER .1.3.6.1.4.1.7309.4.1.9 |
dcPwrSysAlarmTriggerValuero INTEGER .1.3.6.1.4.1.7309.4.1.9.1 |
dcPwrSysTimeStampro DisplayString .1.3.6.1.4.1.7309.4.1.9.2 |
More MIBs from Alpha
Browse all AlphaMIBs →The SITE-MONITORING-MIB structures SNMP OIDs to categorize and organize management data for Alpha Innovations hardware based on specific design center architectures. This module facilitates the monitoring of site-specific operational metrics and device states within the vendor's proprietary network infrastructure.
AlphaPowerSystem-MIB facilitates SNMP monitoring of DC power system devices within Cordex series controllers, specifically exposing the `dcPwrSysDevice` information block for tracking power subsystem status and operational parameters.
SNMP MIB module
The ALPHA-RESOURCE-MIB provides standardized SNMP access to hardware resource utilization metrics, such as CPU load, memory consumption, and storage capacity, within system controllers. This module enables network management systems to monitor critical performance thresholds and capacity planning data for ALPHA vendor infrastructure.
The Argus-Power-System-MIB facilitates SNMP monitoring of CXC-series RMU controllers, specifically exposing the `upsDevice` information block to track Uninterruptible Power Supply (UPS) status, battery conditions, and power system health metrics.
The ALPHA-INVERTER-SYS-MIB enables SNMP-based monitoring of a single Cordex HP inverter system, exposing a flat data structure of operational parameters from the controller. This module facilitates the collection of critical inverter status and performance metrics for centralized network management and fault detection.