ALPHA-INVERTER-SYS-MIB
AI MIB Summary
The ALPHA-INVERTER-SYS-MIB enables SNMP-based monitoring of a single Cordex HP inverter system, exposing a flat data structure of operational parameters from the controller. This module facilitates the collection of critical inverter status and performance metrics for centralized network management and fault detection.
This MIB provides a flat list of data points available from the Cordex HP controller to present information of one Inverter System.
Main OID:
inverterSystem.1.3.6.1.4.1.7309.5.3.3
60
Objects
Active
Status
3
Dependencies
Imported Objects
Objects
60 total| Object Name |
|---|
inverterSystemThis MIB provides a flat list of data points available from the Cordex HP controller to present information of one Inverter System. MODULE-IDENTITY .1.3.6.1.4.1.7309.5.3.3 |
invTotalAcOutputPowerVaThe total output power summed from all the phases (VA).ro ScaledNumber (ALPHA-RESOURCE-MIB) .1.3.6.1.4.1.7309.5.3.3.1 |
invSysAverageLoadingOfInstalledPowerVaThe average output loading of all phases (% VA).ro ScaledNumber (ALPHA-RESOURCE-MIB) .1.3.6.1.4.1.7309.5.3.3.2 |
invSysAverageDcInputToOutputPowerRatioThe percentage of the output that is taken from the DC input (%).ro ScaledNumber (ALPHA-RESOURCE-MIB) .1.3.6.1.4.1.7309.5.3.3.3 |
invSysSystemModeThe mode of the system. See manual for decoding the number.ro ScaledNumber (ALPHA-RESOURCE-MIB) .1.3.6.1.4.1.7309.5.3.3.4 |
invSysPhase1OutputPowerVaThe total output power from the phase 1 (VA).ro ScaledNumber (ALPHA-RESOURCE-MIB) .1.3.6.1.4.1.7309.5.3.3.5 |
invSysPhase2OutputPowerVaThe total output power from phase 2 (VA).ro ScaledNumber (ALPHA-RESOURCE-MIB) .1.3.6.1.4.1.7309.5.3.3.6 |
invSysPhase3OutputPowerVaThe total output power from the phase 3 (VA).ro ScaledNumber (ALPHA-RESOURCE-MIB) .1.3.6.1.4.1.7309.5.3.3.7 |
invSysAverageOutputVoltageMeasuredThe average output voltage of all the phases (V).ro ScaledNumber (ALPHA-RESOURCE-MIB) .1.3.6.1.4.1.7309.5.3.3.8 |
invSysEnabledDisconnectsThe number of disconnects that are enabled.ro ScaledNumber (ALPHA-RESOURCE-MIB) .1.3.6.1.4.1.7309.5.3.3.9 |
invSysActivatedDisconnectsThe number of disconnects that are active.ro ScaledNumber (ALPHA-RESOURCE-MIB) .1.3.6.1.4.1.7309.5.3.3.10 |
invSysTotalDCInputCurrentTotal DC input current for the inverter system (A).ro ScaledNumber (ALPHA-RESOURCE-MIB) .1.3.6.1.4.1.7309.5.3.3.11 |
invSysAverageDcInputVoltageAverage DC input voltage reading for the inverter system (V).ro ScaledNumber (ALPHA-RESOURCE-MIB) .1.3.6.1.4.1.7309.5.3.3.12 |
invSysTotalDcInputPowerTotal DC input power reading for the inverter system (W).ro ScaledNumber (ALPHA-RESOURCE-MIB) .1.3.6.1.4.1.7309.5.3.3.13 |
invSysSystemOnBypassTrue when the bypass switch is on. The AC input from the grid is fed to the AC load directly.ro ScaledNumber (ALPHA-RESOURCE-MIB) .1.3.6.1.4.1.7309.5.3.3.14 |
invSysTotalAcInputPowerVaTotal AC input power reading of the Inverter System (VA).ro ScaledNumber (ALPHA-RESOURCE-MIB) .1.3.6.1.4.1.7309.5.3.3.18 |
phaseGroup OBJECT IDENTIFIER .1.3.6.1.4.1.7309.5.3.3.80 |
invSysAcPhaseCountro Integer32 .1.3.6.1.4.1.7309.5.3.3.80.1 |
invSysAcPhaseTable SEQUENCE OF InvSysAcPhaseEntry .1.3.6.1.4.1.7309.5.3.3.80.2 |
invSysAcPhaseEntry InvSysAcPhaseEntry .1.3.6.1.4.1.7309.5.3.3.80.2.1 |
invSysAcPhaseAcOutputPowerVaThe power of the AC output (VA).ro ScaledNumber (ALPHA-RESOURCE-MIB) .1.3.6.1.4.1.7309.5.3.3.80.2.1.1 |
invSysAcPhaseOutputVoltageMeasuredThe output voltage of the phase or inverter (V).ro ScaledNumber (ALPHA-RESOURCE-MIB) .1.3.6.1.4.1.7309.5.3.3.80.2.1.2 |
invSysAcPhaseOutputCurrentThe output current of the phase or inverter (A).ro ScaledNumber (ALPHA-RESOURCE-MIB) .1.3.6.1.4.1.7309.5.3.3.80.2.1.3 |
invSysAcPhaseFrequencyFrequency to which the inverters will lock (Hz).ro ScaledNumber (ALPHA-RESOURCE-MIB) .1.3.6.1.4.1.7309.5.3.3.80.2.1.4 |
invSysAcPhaseLoadingOfInstalledPowerVaThe ratio of output load to installed power (%VA).ro ScaledNumber (ALPHA-RESOURCE-MIB) .1.3.6.1.4.1.7309.5.3.3.80.2.1.5 |
invSysAcPhaseNumberOfModulesOnThe number of inverters that are On and can deliver power.ro ScaledNumber (ALPHA-RESOURCE-MIB) .1.3.6.1.4.1.7309.5.3.3.80.2.1.6 |
invSysAcPhaseLoadingOfInstalledPowerWattsThe ratio of output load to installed power (% W).ro ScaledNumber (ALPHA-RESOURCE-MIB) .1.3.6.1.4.1.7309.5.3.3.80.2.1.7 |
invSysAcPhaseDcInputToOutputPowerRatioMeasuredThe measured percentage of DC input power to output power(%). Under light or no load this value will not computed accurately.ro ScaledNumber (ALPHA-RESOURCE-MIB) .1.3.6.1.4.1.7309.5.3.3.80.2.1.8 |
invSysAcPhaseAcInputPowerWattsThe power drawn by the AC input (W).ro ScaledNumber (ALPHA-RESOURCE-MIB) .1.3.6.1.4.1.7309.5.3.3.80.2.1.9 |
invSysAcPhaseAcInputPowerVaThe power drawn by the AC input (VA).ro ScaledNumber (ALPHA-RESOURCE-MIB) .1.3.6.1.4.1.7309.5.3.3.80.2.1.10 |
invSysAcPhaseAcOutputPowerWattsThe power of the AC output (W).ro ScaledNumber (ALPHA-RESOURCE-MIB) .1.3.6.1.4.1.7309.5.3.3.80.2.1.11 |
invSysAcPhaseDCInputPowerWattsThe power drawn by the DC input (W).ro ScaledNumber (ALPHA-RESOURCE-MIB) .1.3.6.1.4.1.7309.5.3.3.80.2.1.12 |
invSysAcPhaseNumberOfRedundantModulesMeasuredNumber of inverters currently unneeded by the load.ro ScaledNumber (ALPHA-RESOURCE-MIB) .1.3.6.1.4.1.7309.5.3.3.80.2.1.13 |
invSysAcPhaseNumberOfModulesDetectedThe number of inverters assigned to this phase that the T2S has detected.ro ScaledNumber (ALPHA-RESOURCE-MIB) .1.3.6.1.4.1.7309.5.3.3.80.2.1.14 |
invSysAcPhaseNumberOfModulesOffThe number of inverters that are manually turned off.ro ScaledNumber (ALPHA-RESOURCE-MIB) .1.3.6.1.4.1.7309.5.3.3.80.2.1.15 |
invSysAcPhaseNumberOfModulesFailedThe number of inverters that have failed and cannot deliver power.ro ScaledNumber (ALPHA-RESOURCE-MIB) .1.3.6.1.4.1.7309.5.3.3.80.2.1.16 |
acInputGroup OBJECT IDENTIFIER .1.3.6.1.4.1.7309.5.3.3.81 |
invSysAcInputCountro Integer32 .1.3.6.1.4.1.7309.5.3.3.81.1 |
invSysAcInputTable SEQUENCE OF InvSysAcInputEntry .1.3.6.1.4.1.7309.5.3.3.81.2 |
invSysAcInputEntry InvSysAcInputEntry .1.3.6.1.4.1.7309.5.3.3.81.2.1 |
invSysAcInputInputVoltageThe input voltage of the inverter or group (V).ro ScaledNumber (ALPHA-RESOURCE-MIB) .1.3.6.1.4.1.7309.5.3.3.81.2.1.1 |
invSysAcInputInputCurrentThe input current of the inverter or group (A).ro ScaledNumber (ALPHA-RESOURCE-MIB) .1.3.6.1.4.1.7309.5.3.3.81.2.1.2 |
invSysAcInputFrequencyThe frequency of the input voltage and current of the inverter or group (Hz).ro ScaledNumber (ALPHA-RESOURCE-MIB) .1.3.6.1.4.1.7309.5.3.3.81.2.1.3 |
invSysAcInputAcInputPowerVaThe power drawn by the AC input (VA).ro ScaledNumber (ALPHA-RESOURCE-MIB) .1.3.6.1.4.1.7309.5.3.3.81.2.1.4 |
invSysAcInputNumberOfModulesOnThe number of inverters that are On and can deliver power.ro ScaledNumber (ALPHA-RESOURCE-MIB) .1.3.6.1.4.1.7309.5.3.3.81.2.1.5 |
invSysAcInputAcInputPowerWattsThe power drawn by the AC input (W).ro ScaledNumber (ALPHA-RESOURCE-MIB) .1.3.6.1.4.1.7309.5.3.3.81.2.1.6 |
invSysAcInputNumberOfModulesDetectedThe number of inverters assigned to this phase that the T2S has detected.ro ScaledNumber (ALPHA-RESOURCE-MIB) .1.3.6.1.4.1.7309.5.3.3.81.2.1.7 |
invSysAcInputNumberOfModulesOffThe number of inverters that are manually turned off.ro ScaledNumber (ALPHA-RESOURCE-MIB) .1.3.6.1.4.1.7309.5.3.3.81.2.1.8 |
invSysAcInputNumberOfModulesFailedThe number of inverters that have failed and cannot deliver power.ro ScaledNumber (ALPHA-RESOURCE-MIB) .1.3.6.1.4.1.7309.5.3.3.81.2.1.9 |
dcInputGroup OBJECT IDENTIFIER .1.3.6.1.4.1.7309.5.3.3.82 |
invSysDcInputCountro Integer32 .1.3.6.1.4.1.7309.5.3.3.82.1 |
invSysDcInputTable SEQUENCE OF InvSysDcInputEntry .1.3.6.1.4.1.7309.5.3.3.82.2 |
invSysDcInputEntry InvSysDcInputEntry .1.3.6.1.4.1.7309.5.3.3.82.2.1 |
invSysDcInputInputVoltageThe input voltage of the inverter or group (V).ro ScaledNumber (ALPHA-RESOURCE-MIB) .1.3.6.1.4.1.7309.5.3.3.82.2.1.1 |
invSysDcInputInputCurrentThe input current of the inverter or group (A).ro ScaledNumber (ALPHA-RESOURCE-MIB) .1.3.6.1.4.1.7309.5.3.3.82.2.1.2 |
invSysDcInputDcInputPowerWattsThe power drawn by the DC input (W).ro ScaledNumber (ALPHA-RESOURCE-MIB) .1.3.6.1.4.1.7309.5.3.3.82.2.1.3 |
invSysDcInputNumberOfModulesOnThe number of inverters that are On and can deliver power.ro ScaledNumber (ALPHA-RESOURCE-MIB) .1.3.6.1.4.1.7309.5.3.3.82.2.1.4 |
invSysDcInputNumberOfModulesOffThe number of inverters that are manually turned off.ro ScaledNumber (ALPHA-RESOURCE-MIB) .1.3.6.1.4.1.7309.5.3.3.82.2.1.5 |
invSysDcInputNumberOfModulesFailedThe number of inverters that have failed and cannot deliver power.ro ScaledNumber (ALPHA-RESOURCE-MIB) .1.3.6.1.4.1.7309.5.3.3.82.2.1.6 |
invSysDcInputNumberOfModulesDetectedThe number of inverters assigned to this phase that the T2S has detected.ro ScaledNumber (ALPHA-RESOURCE-MIB) .1.3.6.1.4.1.7309.5.3.3.82.2.1.7 |