LMS-MIB
Standard SNMP MIB module defining data structures for LMS-MIB.
Imported Objects
Objects
115 total| Object Name |
|---|
emersonESNA OBJECT IDENTIFIER .1.3.6.1.4.1.885 |
IMPORTS Unknown .1.3.6.1.4.1.885 |
lms OBJECT IDENTIFIER .1.3.6.1.4.1.885.2 |
lmsSystem OBJECT IDENTIFIER .1.3.6.1.4.1.885.2.1 |
lmsCounts OBJECT IDENTIFIER .1.3.6.1.4.1.885.2.2 |
binaryChannelNumberThe number of Binary channels in the system.ro INTEGER .1.3.6.1.4.1.885.2.2.1 |
analogChannelNumberThe number of Analog channels in the system.ro INTEGER .1.3.6.1.4.1.885.2.2.2 |
relayChannelNumberThe number of Relay channels in the system.ro INTEGER .1.3.6.1.4.1.885.2.2.3 |
ledChannelNumberThe number of LED channels in the system.ro INTEGER .1.3.6.1.4.1.885.2.2.4 |
energyChannelNumberThe number of Energy Management channels in the system.ro INTEGER .1.3.6.1.4.1.885.2.2.5 |
functionChannelNumberThe number of Function channels in the system.ro INTEGER .1.3.6.1.4.1.885.2.2.6 |
lmsChannels OBJECT IDENTIFIER .1.3.6.1.4.1.885.2.3 |
lmsBinaryChannelTableThe table listing for the Binary channel information SEQUENCE OF MarconiLMSBinaryChannelEntry .1.3.6.1.4.1.885.2.3.1 |
lmsBinaryChannelEntryAn entry containing information about a individual Binary channel. MarconiLMSBinaryChannelEntry .1.3.6.1.4.1.885.2.3.1.1 |
binaryChannelIndexThe Binary channel numberro DisplayString .1.3.6.1.4.1.885.2.3.1.1.1 |
binaryChannelNameThe Binary channel namerw DisplayString .1.3.6.1.4.1.885.2.3.1.1.2 |
binaryChannelStatusThe Binary channel state (CC=voltage applied)ro DisplayString .1.3.6.1.4.1.885.2.3.1.1.3 |
binaryChannelAlarmStatusThe Binary channel alarm statusro DisplayString .1.3.6.1.4.1.885.2.3.1.1.4 |
binaryChannelAlarmClassThe Binary channel alarm classro DisplayString .1.3.6.1.4.1.885.2.3.1.1.5 |
lmsAnalogChannelTableThe table listing for the Analog channel information SEQUENCE OF MarconiLMSAnalogChannelEntry .1.3.6.1.4.1.885.2.3.2 |
lmsAnalogChannelEntryAn entry containing information about an individual Analog channel. MarconiLMSAnalogChannelEntry .1.3.6.1.4.1.885.2.3.2.1 |
analogChannelIndexThe Analog channel numberro DisplayString .1.3.6.1.4.1.885.2.3.2.1.1 |
analogChannelNameThe Analog channel namerw DisplayString .1.3.6.1.4.1.885.2.3.2.1.2 |
analogChannelValueThe Analog channel readingro DisplayString .1.3.6.1.4.1.885.2.3.2.1.3 |
analogChannelUnitsThe Analog channel reading units of measurementro DisplayString .1.3.6.1.4.1.885.2.3.2.1.4 |
analogChannelLimit1The Analog channel limit number one valuero DisplayString .1.3.6.1.4.1.885.2.3.2.1.5 |
analogChannelLimit2The Analog channel limit number two valuero DisplayString .1.3.6.1.4.1.885.2.3.2.1.6 |
analogChannelLimit3The Analog channel limit number three valuero DisplayString .1.3.6.1.4.1.885.2.3.2.1.7 |
analogChannelLimit4The Analog channel limit number four valuero DisplayString .1.3.6.1.4.1.885.2.3.2.1.8 |
analogChannelAlarmThe Analog channel alarm statusro INTEGER .1.3.6.1.4.1.885.2.3.2.1.9 |
lmsRelayChannelTableThe table listing for the Relay channel information SEQUENCE OF MarconiLMSRelayChannelEntry .1.3.6.1.4.1.885.2.3.3 |
lmsRelayChannelEntryAn entry containing information about an individual Relay channel. MarconiLMSRelayChannelEntry .1.3.6.1.4.1.885.2.3.3.1 |
relayChannelIndexThe Relay channel numberro DisplayString .1.3.6.1.4.1.885.2.3.3.1.1 |
relayChannelNameThe Relay channel namerw DisplayString .1.3.6.1.4.1.885.2.3.3.1.2 |
relayChannelStatusThe Relay channel status (On, Forced, Programmed)rw DisplayString .1.3.6.1.4.1.885.2.3.3.1.3 |
relayChannelAlarmStatusThe Relay channel alarm statusrw DisplayString .1.3.6.1.4.1.885.2.3.3.1.4 |
relayChannelAlarmClassThe Relay channel alarm classrw DisplayString .1.3.6.1.4.1.885.2.3.3.1.5 |
lmsLEDChannelTableThe table listing for the LED channel information SEQUENCE OF MarconiLMSLEDChannelEntry .1.3.6.1.4.1.885.2.3.4 |
lmsLEDChannelEntryAn entry containing information about an individual LED channel. MarconiLMSLEDChannelEntry .1.3.6.1.4.1.885.2.3.4.1 |
ledChannelIndexThe LED channel numberro DisplayString .1.3.6.1.4.1.885.2.3.4.1.1 |
ledChannelNameThe LED channel namerw DisplayString .1.3.6.1.4.1.885.2.3.4.1.2 |
ledChannelStatusThe LED channel status (On, Forced, Programmed)rw DisplayString .1.3.6.1.4.1.885.2.3.4.1.3 |
ledChannelAlarmStatusThe LED channel alarm statusrw DisplayString .1.3.6.1.4.1.885.2.3.4.1.4 |
ledChannelAlarmClassThe LED channel alarm classrw DisplayString .1.3.6.1.4.1.885.2.3.4.1.5 |
lmsEnergyChannelTableThe table listing for the Energy Management channel information SEQUENCE OF MarconiLMSEnergyChannelEntry .1.3.6.1.4.1.885.2.3.5 |
lmsEnergyChannelEntryAn entry containing information about an individual Energy Management channel. MarconiLMSEnergyChannelEntry .1.3.6.1.4.1.885.2.3.5.1 |
energyChannelIndexThe Energy Management channel numberro DisplayString .1.3.6.1.4.1.885.2.3.5.1.1 |
energyChannelNameThe Energy Management channel namerw DisplayString .1.3.6.1.4.1.885.2.3.5.1.2 |
energyCapacityThe rated capacity of the rectifier associated with the Energy Management channelro DisplayString .1.3.6.1.4.1.885.2.3.5.1.3 |
energyShuntThe current load on the rectifier associated with the Energy Management channelro DisplayString .1.3.6.1.4.1.885.2.3.5.1.4 |
energyRFAThe current operational status of the rectifier associated with the Energy Management channelro INTEGER .1.3.6.1.4.1.885.2.3.5.1.5 |
energyTRThe current control status of the rectifier associated with the Energy Management channelro INTEGER .1.3.6.1.4.1.885.2.3.5.1.6 |
lmsFunctionChannelTableThe table entry for a Function channel Alarm SEQUENCE OF MarconiLMSFunctionChannelEntry .1.3.6.1.4.1.885.2.3.6 |
lmsFunctionChannelEntryAn entry containing the information returned by a Function channel Trap MarconiLMSFunctionChannelEntry .1.3.6.1.4.1.885.2.3.6.1 |
functionChannelIndexThe Function channel numberro DisplayString .1.3.6.1.4.1.885.2.3.6.1.1 |
functionChannelNameThe Function channel namerw DisplayString .1.3.6.1.4.1.885.2.3.6.1.2 |
functionChannelValueThe Function channel readingro DisplayString .1.3.6.1.4.1.885.2.3.6.1.3 |
functionChannelUnitsThe Function channel reading units of measurementro DisplayString .1.3.6.1.4.1.885.2.3.6.1.4 |
functionChannelLimit1The Function channel limit number one valuero DisplayString .1.3.6.1.4.1.885.2.3.6.1.5 |
functionChannelLimit2The Function channel limit number two valuero DisplayString .1.3.6.1.4.1.885.2.3.6.1.6 |
functionChannelLimit3The Function channel limit number three valuero DisplayString .1.3.6.1.4.1.885.2.3.6.1.7 |
functionChannelLimit4The Function channel limit number four valuero DisplayString .1.3.6.1.4.1.885.2.3.6.1.8 |
functionChannelAlarmThe Function channel alarm statusro INTEGER .1.3.6.1.4.1.885.2.3.6.1.9 |
lmsTraps OBJECT IDENTIFIER .1.3.6.1.4.1.885.2.5 |
lmsLedAlarmTableThe table entry for a Led Alarm SEQUENCE OF MarconiLMSLedAlarmEntry .1.3.6.1.4.1.885.2.5.1 |
lmsLedAlarmEntryAn entry containing the information returned by a LED Trap MarconiLMSLedAlarmEntry .1.3.6.1.4.1.885.2.5.1.1 |
ledAlarmIndexThe LED channel numberro DisplayString .1.3.6.1.4.1.885.2.5.1.1.1 |
ledAlarmNameThe LED channel namero DisplayString .1.3.6.1.4.1.885.2.5.1.1.2 |
ledAlarmStatusThe LED channel status (On, Forced, Programmed)ro DisplayString .1.3.6.1.4.1.885.2.5.1.1.3 |
ledAlarmAlarmStatusThe LED channel alarm statusro DisplayString .1.3.6.1.4.1.885.2.5.1.1.4 |
ledAlarmClassThe LED channel alarm classro DisplayString .1.3.6.1.4.1.885.2.5.1.1.5 |
ledAlarmReportTypeThe LED channel alarm conditionro DisplayString .1.3.6.1.4.1.885.2.5.1.1.6 |
ledAlarmDurationThe length of time the LED alarm has been activero DisplayString .1.3.6.1.4.1.885.2.5.1.1.7 |
lmsAnalogAlarmTableThe table entry for an Analog channel Alarm SEQUENCE OF MarconiLMSAnalogAlarmEntry .1.3.6.1.4.1.885.2.5.10 |
lmsAnalogAlarmEntryAn entry containing the information returned by an Analog channel Trap MarconiLMSAnalogAlarmEntry .1.3.6.1.4.1.885.2.5.10.1 |
analogAlarmIndexThe Analog channel numberro DisplayString .1.3.6.1.4.1.885.2.5.10.1.1 |
analogAlarmNameThe Analog channel namero DisplayString .1.3.6.1.4.1.885.2.5.10.1.2 |
analogAlarmValueThe Analog channel readingro DisplayString .1.3.6.1.4.1.885.2.5.10.1.3 |
analogAlarmUnitsThe Analog channel reading units of measurementro DisplayString .1.3.6.1.4.1.885.2.5.10.1.4 |
analogAlarmLimitValueThe Analog channel limit valuero DisplayString .1.3.6.1.4.1.885.2.5.10.1.5 |
analogAlarmLimitTypeThe Analog channel limit typero INTEGER .1.3.6.1.4.1.885.2.5.10.1.6 |
analogAlarmLimitNameThe Analog channel limit namero DisplayString .1.3.6.1.4.1.885.2.5.10.1.7 |
analogAlarmLimitClassThe Analog channel limit conditionro DisplayString .1.3.6.1.4.1.885.2.5.10.1.8 |
analogAlarmReportTypeThe Analog channel limit conditionro DisplayString .1.3.6.1.4.1.885.2.5.10.1.9 |
analogAlarmDurationThe length of time the Analog limit has been activero DisplayString .1.3.6.1.4.1.885.2.5.10.1.10 |
lmsBinaryAlarmTableThe table entry for a Binary Alarm SEQUENCE OF MarconiLMSBinaryAlarmEntry .1.3.6.1.4.1.885.2.5.11 |
lmsBinaryAlarmEntryAn entry containing the information returned by a Binary Trap MarconiLMSBinaryAlarmEntry .1.3.6.1.4.1.885.2.5.11.1 |
binaryAlarmIndexThe Binary channel numberro DisplayString .1.3.6.1.4.1.885.2.5.11.1.1 |
binaryAlarmNameThe Binary channel namero DisplayString .1.3.6.1.4.1.885.2.5.11.1.2 |
binaryAlarmStatusThe Binary channel state (CC=voltage applied)ro DisplayString .1.3.6.1.4.1.885.2.5.11.1.3 |
binaryAlarmAlarmStatusThe Binary channel alarm statusro DisplayString .1.3.6.1.4.1.885.2.5.11.1.4 |
binaryAlarmClassThe Binary channel alarm classro DisplayString .1.3.6.1.4.1.885.2.5.11.1.5 |
binaryAlarmReportTypeThe Binary channel alarm conditionro DisplayString .1.3.6.1.4.1.885.2.5.11.1.6 |
binaryAlarmDurationThe length of time the Binary alarm has been activero DisplayString .1.3.6.1.4.1.885.2.5.11.1.7 |
lmsFunctionAlarmTableThe table entry for a Function channel Alarm SEQUENCE OF MarconiLMSFunctionAlarmEntry .1.3.6.1.4.1.885.2.5.12 |
lmsFunctionAlarmEntryAn entry containing the information returned by a Function channel Trap MarconiLMSFunctionAlarmEntry .1.3.6.1.4.1.885.2.5.12.1 |
functionAlarmIndexThe Function channel numberro DisplayString .1.3.6.1.4.1.885.2.5.12.1.1 |
functionAlarmNameThe Function channel namero DisplayString .1.3.6.1.4.1.885.2.5.12.1.2 |
functionAlarmValueThe Function channel readingro DisplayString .1.3.6.1.4.1.885.2.5.12.1.3 |
functionAlarmUnitsThe Function channel reading units of measurementro DisplayString .1.3.6.1.4.1.885.2.5.12.1.4 |
functionAlarmLimitValueThe Function channel limit valuero DisplayString .1.3.6.1.4.1.885.2.5.12.1.5 |
functionAlarmLimitTypeThe Function channel limit valuero INTEGER .1.3.6.1.4.1.885.2.5.12.1.6 |
functionAlarmLimitNameThe Function channel limit namero DisplayString .1.3.6.1.4.1.885.2.5.12.1.7 |
functionAlarmLimitClassThe Function channel alarm classro DisplayString .1.3.6.1.4.1.885.2.5.12.1.8 |
functionAlarmReportTypeThe Function channel limit conditionro DisplayString .1.3.6.1.4.1.885.2.5.12.1.9 |
functionAlarmDurationThe length of time the Function limit has been activero DisplayString .1.3.6.1.4.1.885.2.5.12.1.10 |
lmsRelayAlarmTableThe table entry for a Relay Alarm SEQUENCE OF MarconiLMSRelayAlarmEntry .1.3.6.1.4.1.885.2.5.13 |
lmsRelayAlarmEntryAn entry containing the information returned by a Relay Trap MarconiLMSRelayAlarmEntry .1.3.6.1.4.1.885.2.5.13.1 |
relayAlarmIndexThe Relay channel numberro DisplayString .1.3.6.1.4.1.885.2.5.13.1.1 |
relayAlarmNameThe Relay channel namero DisplayString .1.3.6.1.4.1.885.2.5.13.1.2 |
relayAlarmStatusThe Relay channel status (On, Forced, Programmed)ro DisplayString .1.3.6.1.4.1.885.2.5.13.1.3 |
relayAlarmAlarmStatusThe Relay channel alarm statusro DisplayString .1.3.6.1.4.1.885.2.5.13.1.4 |
relayAlarmClassThe Relay channel alarm classro DisplayString .1.3.6.1.4.1.885.2.5.13.1.5 |
relayAlarmReportTypeThe Relay channel alarm conditionro DisplayString .1.3.6.1.4.1.885.2.5.13.1.6 |
relayAlarmDurationThe length of time the Relay alarm has been activero DisplayString .1.3.6.1.4.1.885.2.5.13.1.7 |
More MIBs from Emerson Energy
Browse all Emerson EnergyMIBs →The EES-POWER-FERRO-MIB facilitates SNMP-based monitoring and management of Emerson Energy Systems SMDUH (Single Module Dual Unit Hybrid) ferroresonant power supply units. This module exposes vendor-specific operational metrics, including input/output voltage levels, current status, and internal temperature sensors, to enable real-time fault detection and performance tracking within industrial power infrastructure.