Home/Catalog/EES-POWER-FERRO-MIB

EES-POWER-FERRO-MIB

AI MIB Summary

The EES-POWER-FERRO-MIB facilitates SNMP-based monitoring and management of Emerson Energy Systems SMDUH (Single Module Dual Unit Hybrid) ferroresonant power supply units. This module exposes vendor-specific operational metrics, including input/output voltage levels, current status, and internal temperature sensors, to enable real-time fault detection and performance tracking within industrial power infrastructure.

Emerson Energy Systems (EES) Power MIB, For SMDUH.
Main OID:
powerMIB.1.3.6.1.4.1.6302.2.1
190
Objects
Active
Status
2
Dependencies

Imported Objects

Objects

190 total
Object Name
ees
OBJECT IDENTIFIER
.1.3.6.1.4.1.6302
_pysmi_global
OBJECT IDENTIFIER
.1.3.6.1.4.1.6302.2
powerMIBEmerson Energy Systems (EES) Power MIB, For SMDUH.
MODULE-IDENTITY
.1.3.6.1.4.1.6302.2.1
ident
OBJECT IDENTIFIER
.1.3.6.1.4.1.6302.2.1.1
identManufacturerThe name of the equipment manufacturer.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.6302.2.1.1.1
identModelThe manufacturers model designation of the power system.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.6302.2.1.1.2
identControllerFirmwareVersionThe firmware (software) version of the controller.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.6302.2.1.1.3
identNameThe name of the power plant. This object should be set by the administrator.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.6302.2.1.1.4
identSNMPCfgVerThe name of the power plant. This object should be set by the administrator.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.6302.2.1.1.5
system
OBJECT IDENTIFIER
.1.3.6.1.4.1.6302.2.1.2
systemStatusStatus of the complete plant (highest alarm). One of (1) unknown - status has not yet been defined (2) normal - there are no activated alarms (3) warning - OA, lowest level of 'abnormal' status (4) minor - A3 (5) major - MA (6) critical - CA, highest level of 'abnormal' status (7) unmanaged (8) restricted (9) testing (10) disabledro
Status
.1.3.6.1.4.1.6302.2.1.2.1
systemVoltageSystem voltage, stored as mV, including positive or negative sign. The integer 2147483647 represents invalid value.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.2
systemCurrentSystem current, stored as mA, including positive or negative sign. The integer 2147483647 represents invalid value.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.3
systemUsedCapacityUsed capacity, stored as % of the total capacity. The integer 2147483647 represents invalid value.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.4
psBattery
OBJECT IDENTIFIER
.1.3.6.1.4.1.6302.2.1.2.5
psBatteryVoltageBattery voltage, stored as mV, including positive or negative sign. The integer 2147483647 represents invalid value.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.5.1
psTotalBatteryCurrentBattery current, stored as mA, including positive or negative sign. The integer 2147483647 represents invalid value.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.5.2
psBatteryCapacityCalculated capacity, stored as % of the total capacity. The integer 2147483647 represents invalid value.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.5.3
psBatteryNominalCapacitynominal installed capacity, stored as mAh. The integer 2147483647 represents invalid value.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.5.4
psBatteryTableBattery Table.
SEQUENCE OF PSBatteryEntry
.1.3.6.1.4.1.6302.2.1.2.5.5
psBatteryEntryBattery Measurement Table Entry.
PSBatteryEntry
.1.3.6.1.4.1.6302.2.1.2.5.5.1
psBatteryIndexAutomatically generated index object.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.5.5.1.1
psBatteryCurrentBattery current in Amps.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.5.5.1.2
psBatteryNameBattery shunt name.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.6302.2.1.2.5.5.1.3
psInput
OBJECT IDENTIFIER
.1.3.6.1.4.1.6302.2.1.2.6
psInputLineAVoltageThe AC line A voltage, stored as mV. The integer 2147483647 represents invalid value.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.6.1
psInputLineBVoltageThe AC line B voltage, stored as mV. The integer 2147483647 represents invalid value.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.6.2
psInputLineCVoltageThe AC line C voltage, stored as mV. The integer 2147483647 represents invalid value.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.6.3
psTemperature
OBJECT IDENTIFIER
.1.3.6.1.4.1.6302.2.1.2.7
psTemperature1The first route temperature, stored as 0.001 Celsius degree. The integer 2147483647 represents invalid value.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.7.1
psTemperature2The second route temperature, stored as 0.001 Celsius degree. The integer 2147483647 represents invalid value..ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.7.2
psTemperatureTableTemperature Measurement Table.
SEQUENCE OF PSTemperatureEntry
.1.3.6.1.4.1.6302.2.1.2.7.3
psTemperatureEntryTemperature Measurement Table Entry.
PSTemperatureEntry
.1.3.6.1.4.1.6302.2.1.2.7.3.1
psTemperatureIndexTemperature Probe Numberro
Integer32
.1.3.6.1.4.1.6302.2.1.2.7.3.1.1
psTemperatureMeasurementTemperature Value In Centigrade.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.7.3.1.2
psTemperatureNameConfigured Temperature Probe Name.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.6302.2.1.2.7.3.1.3
psTemperatureTypeTemperature Probe Typero
Enumeration
.1.3.6.1.4.1.6302.2.1.2.7.3.1.4
psTemperatureAlarmStatusTemperature Probe Alarm Statusro
Enumeration
.1.3.6.1.4.1.6302.2.1.2.7.3.1.5
psStatusCommunicationThe status of communication with the Power System. interrupt(3) indicates some errors occurred between Power System and agent.ro
Enumeration
.1.3.6.1.4.1.6302.2.1.2.8
psStatusBatteryModeThe status of battery modes, FloatCharging(2), ShortTest(3), BoostChargingForTest(4), ManualTesting(5), PlanTesting(6), ACFailTesting(7), ACFail(8), ManualBoostCharging(9), AutoBoostCharging(10), CyclicBoostCharging(11), MasterBoostCharging(12), MasterBateryTesting(13).ro
Enumeration
.1.3.6.1.4.1.6302.2.1.2.9
psSMNumber
OBJECT IDENTIFIER
.1.3.6.1.4.1.6302.2.1.2.10
psSMACNumberThe number of SM AC module.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.10.1
psSMBATNumberThe number of SM BAT module.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.10.2
psSMIONumberThe number of SM IO module.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.10.3
psRectifier
OBJECT IDENTIFIER
.1.3.6.1.4.1.6302.2.1.2.11
numberOfInstalledRectifiersnumber of rectifiers, stored as integer. The integer 2147483647 represents invalid value.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.11.1
numberOfRectifiersCommunicatingnumber of rectifiers communicating, stored as integer. The integer 2147483647 represents invalid value.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.11.2
rectifiersUsedCapacityUsed capacity, stored as % of the total capacity. The integer 2147483647 represents invalid value.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.11.3
psRectifierTableTable holding information about indivual rectifiers.
SEQUENCE OF PSRectifierEntry
.1.3.6.1.4.1.6302.2.1.2.11.4
psRectifierEntryAn entry (conceptual row) in the rectifierInfoTable.
PSRectifierEntry
.1.3.6.1.4.1.6302.2.1.2.11.4.1
psRectifierIndexAutomatically generated index object.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.11.4.1.1
psRectifierProductNumberRectifier Product Number.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.6302.2.1.2.11.4.1.2
psRectifierHWVersionRectifier Hardware Revision.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.6302.2.1.2.11.4.1.3
psRectifierSWVersionRectifier Software Revision.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.6302.2.1.2.11.4.1.4
psRectifierSerialNumberRectifier Serial Number.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.6302.2.1.2.11.4.1.5
psRectifierCurrentRectifier Current.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.11.4.1.6
psRectifierIdentRectifier physical location identifier.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.6302.2.1.2.11.4.1.7
psRectifierFailThe type of alarm change. One of (1) activated (2) deactivatedro
StatusChange
.1.3.6.1.4.1.6302.2.1.2.11.4.1.8
psDistribution
OBJECT IDENTIFIER
.1.3.6.1.4.1.6302.2.1.2.12
psTotalLoadCurrentTotal Load current, stored as integer. The integer 2147483647 represents invalid value.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.12.1
psDistributionLoadTableDistribution Table.
SEQUENCE OF PSDistributionLoadEntry
.1.3.6.1.4.1.6302.2.1.2.12.2
psDistributionLoadEntryDistribution Measurement Table Entry.
PSDistributionLoadEntry
.1.3.6.1.4.1.6302.2.1.2.12.2.1
psDistributionLoadIndexAutomatically generated index object.
Integer32
.1.3.6.1.4.1.6302.2.1.2.12.2.1.1
psDistributionLoadCurrentDistribution current in Amps.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.12.2.1.2
psDistributionLoadNameDistribution name.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.6302.2.1.2.12.2.1.3
psDistributionGeneralTableDistribution Table.
SEQUENCE OF PSDistributionGeneralEntry
.1.3.6.1.4.1.6302.2.1.2.12.3
psDistributionGeneralEntryDistribution Measurement Table Entry.
PSDistributionGeneralEntry
.1.3.6.1.4.1.6302.2.1.2.12.3.1
psDistributionGeneralIndexAutomatically generated index object.
Integer32
.1.3.6.1.4.1.6302.2.1.2.12.3.1.1
psDistributionGeneralCurrentDistribution current in Amps.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.12.3.1.2
psDistributionGeneralNameDistribution name.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.6302.2.1.2.12.3.1.3
psConverter
OBJECT IDENTIFIER
.1.3.6.1.4.1.6302.2.1.2.13
numberOfInstalledConvertersnumber of converters, stored as integer. The integer 2147483647 represents invalid value.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.13.1
numberOfConvertersCommunicatingnumber of converters communicating, stored as integer. The integer 2147483647 represents invalid value.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.13.2
convertersUsedCapacityUsed capacity, stored as % of the total capacity. The integer 2147483647 represents invalid value.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.13.3
psConverterVoltageConverter voltage in mV. The integer 2147483647 represents invalid value.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.13.4
psTotalConverterCurrentTotal Converter current in Amps. The integer 2147483647 represents invalid value.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.13.5
psConverterTableTable holding information about indivual converters.
SEQUENCE OF PSConverterEntry
.1.3.6.1.4.1.6302.2.1.2.13.6
psConverterEntryAn entry (conceptual row) in the ConverterInfoTable.
PSConverterEntry
.1.3.6.1.4.1.6302.2.1.2.13.6.1
psConverterIndexAutomatically generated index object.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.13.6.1.1
psConverterProductNumberConverter Product Number.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.6302.2.1.2.13.6.1.2
psConverterHWVersionConverter Hardware Revision.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.6302.2.1.2.13.6.1.3
psConverterSWVersionConverter Software Revision.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.6302.2.1.2.13.6.1.4
psConverterSerialNumberConverter Serial Number.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.6302.2.1.2.13.6.1.5
psConverterCurrentConverter Current.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.13.6.1.6
psConverterIdentConverter physical location identifier.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.6302.2.1.2.13.6.1.7
psConverterFailThe type of alarm change. One of (1) activated (2) deactivatedro
StatusChange
.1.3.6.1.4.1.6302.2.1.2.13.6.1.8
psControl
OBJECT IDENTIFIER
.1.3.6.1.4.1.6302.2.1.2.14
controlBatteryTestControl battery test, start(1), stop (0).rw
Integer32
.1.3.6.1.4.1.6302.2.1.2.14.1
controlRelay8Control relay8, close(1), open(0).rw
Integer32
.1.3.6.1.4.1.6302.2.1.2.14.2
controlRelay7Control relay7, close(1), open(0).rw
Integer32
.1.3.6.1.4.1.6302.2.1.2.14.3
controlRelay6Control relay6, close(1), open(0).rw
Integer32
.1.3.6.1.4.1.6302.2.1.2.14.4
controlRelayTestControl Relay test, start(1), stop (0).rw
Integer32
.1.3.6.1.4.1.6302.2.1.2.14.5
psEquipmentSignalTableTable of indexed equipment signal values.
SEQUENCE OF EquipmentSignalTableEntry
.1.3.6.1.4.1.6302.2.1.2.15
equipmentSignalTableEntryAn entry (conceptual row) in the psEquipment Signal Table.
EquipmentSignalTableEntry
.1.3.6.1.4.1.6302.2.1.2.15.1
psEquipmentSignalTableEntryIndexThe unique sequence number of this equipment signal.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.15.1.1
psEquipmentSignalValueIndexed equipment signal value.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.15.1.2
psSMDUHCurrent
OBJECT IDENTIFIER
.1.3.6.1.4.1.6302.2.1.2.16
numberOfInstalledSMDUHnumber of SMDHU units, stored as integer. The integer 2147483647 represents invalid value.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.16.1
psSMDUH1VoltageSMDUH1 Voltage.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.16.2
psSMDUH2VoltageSMDUH2 Voltage.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.16.3
psSMDUH3VoltageSMDUH3 Voltage.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.16.4
psSMDUH4VoltageSMDUH4 Voltage.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.16.5
psSMDUH5VoltageSMDUH5 Voltage.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.16.6
psSMDUH6VoltageSMDUH6 Voltage.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.16.7
psSMDUH7VoltageSMDUH7 Voltage.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.16.8
psSMDUH8VoltageSMDU8 Voltage.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.16.9
psSMDUHCurrentTableTable holding information about SMDUH currents.
SEQUENCE OF PSSMDUHEntry
.1.3.6.1.4.1.6302.2.1.2.16.10
psSMDUHCurrentEntryAn entry (conceptual row) in the SMDUHTable.
PSSMDUHEntry
.1.3.6.1.4.1.6302.2.1.2.16.10.1
psSMDUHCurrentIndexAutomatically generated index object.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.16.10.1.1
psSMDUHCurrent1SMDUH Current 1.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.16.10.1.2
psSMDUHCurrent2SMDUH Current 2.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.16.10.1.3
psSMDUHCurrent3SMDUH Current 3.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.16.10.1.4
psSMDUHCurrent4SMDUH Current 4.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.16.10.1.5
psSMDUHCurrent5SMDUH Current 5.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.16.10.1.6
psSMDUHCurrent6SMDUH Current 6.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.16.10.1.7
psSMDUHCurrent7SMDUH Current 7.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.16.10.1.8
psSMDUHCurrent8SMDUH Current 8.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.16.10.1.9
psSMDUHCurrent9SMDUH Current 9.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.16.10.1.10
psSMDUHCurrent10SMDUH Current 10.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.16.10.1.11
psSMDUHCurrent11SMDUH Current 11.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.16.10.1.12
psSMDUHCurrent12SMDUH Current 12.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.16.10.1.13
psSMDUHCurrent13SMDUH Current 13.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.16.10.1.14
psSMDUHCurrent14SMDUH Current 14.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.16.10.1.15
psSMDUHCurrent15SMDUH Current 15.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.16.10.1.16
psSMDUHCurrent16SMDUH Current 16.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.16.10.1.17
psSMDUHCurrent17SMDUH Current 17.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.16.10.1.18
psSMDUHCurrent18SMDUH Current 18.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.16.10.1.19
psSMDUHCurrent19SMDUH Current 19.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.16.10.1.20
psSMDUHCurrent20SMDUH Current 20.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.16.10.1.21
psSMDUHPower
OBJECT IDENTIFIER
.1.3.6.1.4.1.6302.2.1.2.17
psSMDUHPowerTableTable holding information about SMDUH power.
SEQUENCE OF PSSMDUHEntry
.1.3.6.1.4.1.6302.2.1.2.17.1
psSMDUHPowerEntryAn entry (conceptual row) in the SMDUHPowerTable.
PSSMDUHEntry
.1.3.6.1.4.1.6302.2.1.2.17.1.1
psSMDUHPowerIndexAutomatically generated index object.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.17.1.1.1
psSMDUHPower1SMDUH Power 1.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.17.1.1.2
psSMDUHPower2SMDUH Power 2.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.17.1.1.3
psSMDUHPower3SMDUH Power 3.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.17.1.1.4
psSMDUHPower4SMDUH Power 4.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.17.1.1.5
psSMDUHPower5SMDUH Power 5.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.17.1.1.6
psSMDUHPower6SMDUH Power 6.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.17.1.1.7
psSMDUHPower7SMDUH Power 7.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.17.1.1.8
psSMDUHPower8SMDUH Power 8.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.17.1.1.9
psSMDUHPower9SMDUH Power 9.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.17.1.1.10
psSMDUHPower10SMDUH Power 10.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.17.1.1.11
psSMDUHPower11SMDUH Power 11.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.17.1.1.12
psSMDUHPower12SMDUH Power 12.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.17.1.1.13
psSMDUHPower13SMDUH Power 13.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.17.1.1.14
psSMDUHPower14SMDUH Power 14.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.17.1.1.15
psSMDUHPower15SMDUH Power 15.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.17.1.1.16
psSMDUHPower16SMDUH Power 16.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.17.1.1.17
psSMDUHPower17SMDUH Power 17.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.17.1.1.18
psSMDUHPower18SMDUH Power 18.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.17.1.1.19
psSMDUHPower19SMDUH Power 19.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.17.1.1.20
psSMDUHPower20SMDUH Power 20.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.17.1.1.21
psSMDUHEnergy
OBJECT IDENTIFIER
.1.3.6.1.4.1.6302.2.1.2.18
psSMDUHEnergyTableTable holding information about SMDUH energy counters.
SEQUENCE OF PSSMDUHEntry
.1.3.6.1.4.1.6302.2.1.2.18.1
psSMDUHEnergyEntryAn entry (conceptual row) in the SMDUHEnergyTable.
PSSMDUHEntry
.1.3.6.1.4.1.6302.2.1.2.18.1.1
psSMDUHEnergyIndexAutomatically generated index object.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.18.1.1.1
psSMDUHTotalEnergy1SMDUH Total Energy 1.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.18.1.1.2
psSMDUHTotalEnergy2SMDUH Total Energy 2.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.18.1.1.3
psSMDUHTotalEnergy3SMDUH Total Energy 3.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.18.1.1.4
psSMDUHTotalEnergy4SMDUH Total Energy 4.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.18.1.1.5
psSMDUHTotalEnergy5SMDUH Total Energy 5.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.18.1.1.6
psSMDUHTotalEnergy6SMDUH Total Energy 6.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.18.1.1.7
psSMDUHTotalEnergy7SMDUH Total Energy 7.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.18.1.1.8
psSMDUHTotalEnergy8SMDUH Total Energy 8.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.18.1.1.9
psSMDUHTotalEnergy9SMDUH Total Energy 9.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.18.1.1.10
psSMDUHTotalEnergy10SMDUH Total Energy 10.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.18.1.1.11
psSMDUHTotalEnergy11SMDUH Total Energy 11.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.18.1.1.12
psSMDUHTotalEnergy12SMDUH Total Energy 12.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.18.1.1.13
psSMDUHTotalEnergy13SMDUH Total Energy 13.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.18.1.1.14
psSMDUHTotalEnergy14SMDUH Total Energy 14.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.18.1.1.15
psSMDUHTotalEnergy15SMDUH Total Energy 15.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.18.1.1.16
psSMDUHTotalEnergy16SMDUH Total Energy 16.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.18.1.1.17
psSMDUHTotalEnergy17SMDUH Total Energy 17.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.18.1.1.18
psSMDUHTotalEnergy18SMDUH Total Energy 18.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.18.1.1.19
psSMDUHTotalEnergy19SMDUH Total Energy 19.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.18.1.1.20
psSMDUHTotalEnergy20SMDUH Total Energy 20.ro
Integer32
.1.3.6.1.4.1.6302.2.1.2.18.1.1.21
alarmLastTrapNoThe sequence number of last submitted alarm trap, also last row in alarmTrapTable.ro
Counter32
.1.3.6.1.4.1.6302.2.1.3
alarmActiveAlarmTableTable holding information about the currently active alarms.
SEQUENCE OF ActiveAlarmEntry
.1.3.6.1.4.1.6302.2.1.4
activeAlarmEntryAn entry (conceptual row) in the alarmTrapTable.
ActiveAlarmEntry
.1.3.6.1.4.1.6302.2.1.4.1
alarmIndexThe unique sequence number of this alarm trap.ro
Counter32
.1.3.6.1.4.1.6302.2.1.4.1.1
alarmTimeDate and time when event occured (local time), including timezone if supported by controller.ro
DateAndTime (SNMPv2-TC)
.1.3.6.1.4.1.6302.2.1.4.1.2
alarmStatusChangeThe type of alarm change. One of (1) activated (2) deactivatedro
StatusChange
.1.3.6.1.4.1.6302.2.1.4.1.3
alarmSeverityThe severity of the alarm. One of (3) warning - OA, lowest level of alarm severity (4) minor - A3 (5) major - MA (6) critical - CA, highest level of alarm severityro
Status
.1.3.6.1.4.1.6302.2.1.4.1.4
alarmDescriptionFree-text description of alarm.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.6302.2.1.4.1.5
alarmTypeAlarm type, i.e. an integer specifying the type of alarm.ro
Integer32
.1.3.6.1.4.1.6302.2.1.4.1.6
powerEvents
OBJECT IDENTIFIER
.1.3.6.1.4.1.6302.2.1.5
alarmTrapAn alarm trap is sent when an alarm occurs (activated) or returns to normal state (deactivated). Alarm traps are logged in alarmTrapTable. Variables in this trap: * alarmIndex - The unique sequence number of this alarm trap. * alarmTime - Date and time when event occured (local time), including timezone if supported by controller. * alarmStatusChange - (1) activated or (2) deactivated. * alarmSeverity - Integer describing the severity of the alarm. * alarmDescription - Free-text description of alarm. * alarmType - Integer indicating type of alarm.
NOTIFICATION-TYPE
.1.3.6.1.4.1.6302.2.1.5.1
alarmActiveTrapAn alarm trap is sent when an alarm occurs (activated) Variables in this trap * alarmTime - Date and time when event occured (local time), including timezone if supported by controller. * alarmSeverity - Integer describing the severity of the alarm. * alarmDescription - Free-text description of alarm. * alarmType - Integer indicating type of alarm.
NOTIFICATION-TYPE
.1.3.6.1.4.1.6302.2.1.5.2
alarmCeaseTrapAn alarm trap is sent when an alarm returns to normal state (clear, deactivated). Variables in this trap: * alarmTime - Date and time when event occured (local time), including timezone if supported by controller. * alarmSeverity - Integer describing the severity of the alarm. * alarmDescription - Free-text description of alarm. * alarmType - Integer indicating type of alarm.
NOTIFICATION-TYPE
.1.3.6.1.4.1.6302.2.1.5.3
EES-POWER-FERRO-MIB - SNMP MIB Reference | MIBs Explorer