EES-POWER-MIB
The EES-POWER-MIB module enables SNMP-based monitoring and management of Emerson Energy Systems power distribution units and related electrical infrastructure, specifically exposing metrics for voltage, current, power consumption, frequency, and device status.
Imported Objects
Objects
40 total| Object Name |
|---|
ees OBJECT IDENTIFIER .1.3.6.1.4.1.6302 |
_pysmi_global OBJECT IDENTIFIER .1.3.6.1.4.1.6302.2 |
powerMIBEmerson Energy Systems (EES) Power MIB, revision B. MODULE-IDENTITY .1.3.6.1.4.1.6302.2.1 |
ident OBJECT IDENTIFIER .1.3.6.1.4.1.6302.2.1.1 |
identManufacturerThe name of the equipment manufacturer.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.6302.2.1.1.1 |
identModelThe manufacturers model designation of the power system.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.6302.2.1.1.2 |
identControllerFirmwareVersionThe firmware (software) version of the controller.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.6302.2.1.1.3 |
identNameThe name of the power plant. This object should be set by the administrator.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.6302.2.1.1.4 |
system OBJECT IDENTIFIER .1.3.6.1.4.1.6302.2.1.2 |
systemStatusStatus of the complete plant (highest alarm). One of (1) unknown - status has not yet been defined (2) normal - there are no activated alarms (3) observation - OA, lowest level of 'abnormal' status (4) warning - A3 (5) minor - MA (6) major - CA, highest level of 'abnormal' status (7) unmanaged (8) restricted (9) testing (10) disabledro Status .1.3.6.1.4.1.6302.2.1.2.1 |
systemVoltageSystem voltage, stored as mV, including positive or negative sign. The integer 2147483647 represents invalid value.ro Integer32 .1.3.6.1.4.1.6302.2.1.2.2 |
systemCurrentSystem current, stored as mA, including positive or negative sign. The integer 2147483647 represents invalid value.ro Integer32 .1.3.6.1.4.1.6302.2.1.2.3 |
systemUsedCapacityUsed capacity, stored as % of the total capacity. The integer 2147483647 represents invalid value.ro Integer32 .1.3.6.1.4.1.6302.2.1.2.4 |
psBattery OBJECT IDENTIFIER .1.3.6.1.4.1.6302.2.1.2.5 |
psBatteryVoltageBattery voltage, stored as mV, including positive or negative sign. The integer 2147483647 represents invalid value.ro Integer32 .1.3.6.1.4.1.6302.2.1.2.5.1 |
psBatteryCurrentBattery current, stored as mA, including positive or negative sign. The integer 2147483647 represents invalid value.ro Integer32 .1.3.6.1.4.1.6302.2.1.2.5.2 |
psInput OBJECT IDENTIFIER .1.3.6.1.4.1.6302.2.1.2.6 |
psInputLineAVoltageThe AC line A voltage, stored as mV. The integer 2147483647 represents invalid value.ro Integer32 .1.3.6.1.4.1.6302.2.1.2.6.1 |
psInputLineBVoltageThe AC line B voltage, stored as mV. The integer 2147483647 represents invalid value.ro Integer32 .1.3.6.1.4.1.6302.2.1.2.6.2 |
psInputLineCVoltageThe AC line C voltage, stored as mV. The integer 2147483647 represents invalid value.ro Integer32 .1.3.6.1.4.1.6302.2.1.2.6.3 |
psTemperature OBJECT IDENTIFIER .1.3.6.1.4.1.6302.2.1.2.7 |
psTemperature1The first route temperature, stored as 0.001 Celsius degree. The integer 2147483647 represents invalid value.ro Integer32 .1.3.6.1.4.1.6302.2.1.2.7.1 |
psTemperature2The second route temperature, stored as 0.001 Celsius degree. The integer 2147483647 represents invalid value..ro Integer32 .1.3.6.1.4.1.6302.2.1.2.7.2 |
psStatusCommunicationThe status of communication with the Power System. interrupt(3) indicates some errors occurred between Power System and agent.ro Enumeration .1.3.6.1.4.1.6302.2.1.2.8 |
psStatusBatteryModeThe status of battery modes, FloatCharging(2), ShortTest(3), BoostChargingForTest(4), ManualTesting(5), PlanTesting(6), ACFailTesting(7), ACFail(8), ManualBoostCharging(9), AutoBoostCharging(10), CyclicBoostCharging(11), MasterBoostCharging(12), MasterBateryTesting(13).ro Enumeration .1.3.6.1.4.1.6302.2.1.2.9 |
psSMNumber OBJECT IDENTIFIER .1.3.6.1.4.1.6302.2.1.2.10 |
psSMACNumberThe number of SM AC module.ro Integer32 .1.3.6.1.4.1.6302.2.1.2.10.1 |
psSMBATNumberThe number of SM BAT module.ro Integer32 .1.3.6.1.4.1.6302.2.1.2.10.2 |
psSMIONumberThe number of SM IO module.ro Integer32 .1.3.6.1.4.1.6302.2.1.2.10.3 |
alarmLastTrapNoThe sequence number of last submitted alarm trap, also last row in alarmTrapTable.ro Counter32 .1.3.6.1.4.1.6302.2.1.3 |
alarmTrapTableTable holding information about the submitted alarm traps. SEQUENCE OF AlarmTrapEntry .1.3.6.1.4.1.6302.2.1.4 |
alarmTrapEntryAn entry (conceptual row) in the alarmTrapTable. AlarmTrapEntry .1.3.6.1.4.1.6302.2.1.4.1 |
alarmTrapNoThe unique sequence number of this alarm trap.ro Counter32 .1.3.6.1.4.1.6302.2.1.4.1.1 |
alarmTimeDate and time when event occured (local time), including timezone if supported by controller.ro DateAndTime (SNMPv2-TC) .1.3.6.1.4.1.6302.2.1.4.1.2 |
alarmStatusChangeThe type of alarm change. One of (1) activated (2) deactivatedro StatusChange .1.3.6.1.4.1.6302.2.1.4.1.3 |
alarmSeverityThe severity of the alarm. One of (3) observation - OA, lowest level of alarm severity (4) warning - A3 (5) minor - MA (6) major - CA, highest level of alarm severityro Status .1.3.6.1.4.1.6302.2.1.4.1.4 |
alarmDescriptionFree-text description of alarm.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.6302.2.1.4.1.5 |
alarmTypeAlarm type, i.e. an integer specifying the type of alarm.ro Integer32 .1.3.6.1.4.1.6302.2.1.4.1.6 |
powerEvents OBJECT IDENTIFIER .1.3.6.1.4.1.6302.2.1.5 |
alarmTrapAn alarm trap is sent when an alarm occurs (activated) or returns to normal state (deactivated). Alarm traps are logged in alarmTrapTable. Variables in this trap: * alarmTrapNo - The unique sequence number of this alarm trap. * alarmTime - Date and time when event occured (local time), including timezone if supported by controller. * alarmStatusChange - (1) activated or (2) deactivated. * alarmSeverity - Integer describing the severity of the alarm. * alarmDescription - Free-text description of alarm. * alarmType - Integer indicating type of alarm. NOTIFICATION-TYPE .1.3.6.1.4.1.6302.2.1.5.1 |
More MIBs from Emerson Energy
Browse all Emerson EnergyMIBs →The EES-POWER-FERRO-MIB facilitates SNMP-based monitoring and management of Emerson Energy Systems SMDUH (Single Module Dual Unit Hybrid) ferroresonant power supply units. This module exposes vendor-specific operational metrics, including input/output voltage levels, current status, and internal temperature sensors, to enable real-time fault detection and performance tracking within industrial power infrastructure.