DellrPDU-MIB
Detailed view of the defined objects, syntax rules, and hierarchical paths.
282
Objects
Active
Status
4
Dependencies
Imported Objects
Objects
282 total| Object Name |
|---|
dell OBJECT IDENTIFIER .1.3.6.1.4.1.674 |
RFC1213-MIB Unknown .1.3.6.1.4.1.674 |
pdu OBJECT IDENTIFIER .1.3.6.1.4.1.674.10903 |
pdusub OBJECT IDENTIFIER .1.3.6.1.4.1.674.10903.200 |
software OBJECT IDENTIFIER .1.3.6.1.4.1.674.10903.200.1 |
hardware OBJECT IDENTIFIER .1.3.6.1.4.1.674.10903.200.2 |
productID OBJECT IDENTIFIER .1.3.6.1.4.1.674.10903.200.2.100 |
productIDDisplayNameName of this product for display purposes.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.674.10903.200.2.100.1 |
productIDDescriptionA short description of this product.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.674.10903.200.2.100.2 |
productIDVendorThe name of the product manufacturer.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.674.10903.200.2.100.3 |
productIDVersionThe hardware version of this product.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.674.10903.200.2.100.4 |
productIDBuildNumberThe software build number of the product populating the MIB.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.674.10903.200.2.100.5 |
productIDURLThe URL of the Web-based application to manage this device, should
the device provide one.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.674.10903.200.2.100.6 |
productIDDeviceNetworkNameOperating system-specific computer name if product SNMP service is
hosted.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.674.10903.200.2.100.7 |
productStatus OBJECT IDENTIFIER .1.3.6.1.4.1.674.10903.200.2.110 |
productStatusGlobalStatusThe current status of the product. This is a summary of the status
for the entire product including any metered devices. The SNMP
monitor performs a get to retrieve additional data when this status
is abnormal. Valid values 1: Other 2: Unknown 3: OK 4: Non-critical
5: Critical 6: Non-recoverable.ro RpduOtherToNonrecoverableType .1.3.6.1.4.1.674.10903.200.2.110.1 |
productStatusLastGlobalStatusThe status before the current status which induced an initiative to
issue a global status change trap.ro RpduOtherToNonrecoverableType .1.3.6.1.4.1.674.10903.200.2.110.2 |
productStatusTimeStampThe last time that the SNMP table geometries changed or attribute
data was significantly updated. Management applications use this OID
to trigger a refresh of data acquired from the MIB. This time should
be a relative timestamp, for example, the value of MIB II SysUpTime
when the values are updated.ro INTEGER .1.3.6.1.4.1.674.10903.200.2.110.3 |
productStatusRESERVED1RESERVEDro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.674.10903.200.2.110.4 |
productStatusRESERVED2RESERVEDro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.674.10903.200.2.110.5 |
productStatusRESERVED3RESERVEDro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.674.10903.200.2.110.6 |
rPDU OBJECT IDENTIFIER .1.3.6.1.4.1.674.10903.200.2.200 |
rPDUIdentD OBJECT IDENTIFIER .1.3.6.1.4.1.674.10903.200.2.200.100 |
rPDUIdentTableSizeThe number of connected Rack PDUs.ro INTEGER .1.3.6.1.4.1.674.10903.200.2.200.100.1 |
rPDUIdentTableA table of Rack PDU identification data. SEQUENCE OF RPDUIdentEntry .1.3.6.1.4.1.674.10903.200.2.200.100.2 |
rPDUIdentEntryIdentification data from the Rack PDU being queried. RPDUIdentEntry .1.3.6.1.4.1.674.10903.200.2.200.100.2.1 |
rPDUIdentIndexThe index to the Rack PDU identification table entry.ro INTEGER .1.3.6.1.4.1.674.10903.200.2.200.100.2.1.1 |
rPDUIdentNameDA user-defined string identifying the Rack PDU.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.674.10903.200.2.200.100.2.1.2 |
rPDUIdentLocationA user-defined string identifying the location of the Rack PDU.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.674.10903.200.2.200.100.2.1.3 |
rPDUIdentHardwareRevDThe Rack PDU hardware version.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.674.10903.200.2.200.100.2.1.4 |
rPDUIdentFirmwareRevDThe Rack PDU firmware version.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.674.10903.200.2.200.100.2.1.5 |
rPDUIdentDateOfManufactureDThe date the Rack PDU was manufactured in mm/dd/yyyy format.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.674.10903.200.2.200.100.2.1.6 |
rPDUIdentModelNumberDThe Rack PDU model number.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.674.10903.200.2.200.100.2.1.7 |
rPDUIdentSerialNumberDThe Rack PDU serial number.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.674.10903.200.2.200.100.2.1.8 |
rPDUDevice OBJECT IDENTIFIER .1.3.6.1.4.1.674.10903.200.2.200.110 |
rPDUDeviceTableSizeThe number of connected Rack PDUs.ro INTEGER .1.3.6.1.4.1.674.10903.200.2.200.110.1 |
rPDUDeviceStatusTableA table of Rack PDU status information. SEQUENCE OF RPDUDeviceStatusEntry .1.3.6.1.4.1.674.10903.200.2.200.110.2 |
rPDUDeviceStatusEntryStatus information from the Rack PDU being queried. RPDUDeviceStatusEntry .1.3.6.1.4.1.674.10903.200.2.200.110.2.1 |
rPDUDeviceStatusIndexThe index to the Rack PDU status table entry.ro INTEGER .1.3.6.1.4.1.674.10903.200.2.200.110.2.1.1 |
rPDUDeviceStatusNameA user-defined string identifying the Rack PDU.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.674.10903.200.2.200.110.2.1.2 |
rPDUDeviceStatusPowerThe power consumption of the Rack PDU load in 1/100 of KWatts.ro INTEGER .1.3.6.1.4.1.674.10903.200.2.200.110.2.1.3 |
rPDUDeviceStatusEnergyA user resettable energy meter measuring Rack PDU load energy
consumption in tenths of kilowatt-hours.ro INTEGER .1.3.6.1.4.1.674.10903.200.2.200.110.2.1.4 |
rPDUDeviceStatusCommandPendingIndicates whether the device is processing a pending command.
If the commandPendingUnknown (3) value is returned, all devices
receiving power from the Rack PDU should be shut down.
The Rack PDU's power should then be cycled to clear this condition.ro Enumeration .1.3.6.1.4.1.674.10903.200.2.200.110.2.1.5 |
rPDUDeviceStatusLoadStateIndicates the present load status of the Rack PDU Device being
queried.ro RpduLowNormalNearOverloadType .1.3.6.1.4.1.674.10903.200.2.200.110.2.1.6 |
rPDUDeviceConfigTableA table of Rack PDU configuration data. SEQUENCE OF RPDUDeviceConfigEntry .1.3.6.1.4.1.674.10903.200.2.200.110.3 |
rPDUDeviceConfigEntryConfiguration data from the Rack PDU being queried. RPDUDeviceConfigEntry .1.3.6.1.4.1.674.10903.200.2.200.110.3.1 |
rPDUDeviceConfigIndexThe index to the Rack PDU table entry.ro INTEGER .1.3.6.1.4.1.674.10903.200.2.200.110.3.1.1 |
rPDUDeviceConfigNameA user-defined string identifying the Rack PDU.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.674.10903.200.2.200.110.3.1.2 |
rPDUDeviceConfigLocationThe Location of the Rack PDU.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.674.10903.200.2.200.110.3.1.3 |
rPDUDeviceConfigColdstartDelayThe amount of delay, measured in seconds, between when power is
provided to the Rack PDU and when the Rack PDU provides basic
master power to the outlets.rw INTEGER .1.3.6.1.4.1.674.10903.200.2.200.110.3.1.4 |
rPDUDeviceCfgLowLoadPwrThreshThe user-defined low power draw alarm threshold, measured in tenths
of kilowatts.rw INTEGER .1.3.6.1.4.1.674.10903.200.2.200.110.3.1.5 |
rPDUDeviceCfgNerOvloadPwrThreshThe user-defined near power overload threshold, measured in tenths
of kilowatts.rw INTEGER .1.3.6.1.4.1.674.10903.200.2.200.110.3.1.6 |
rPDUDeviceCfgOverloadPwrThreshThe user-defined power overload threshold, measured in tenths of
kilowatts.rw INTEGER .1.3.6.1.4.1.674.10903.200.2.200.110.3.1.7 |
rPDUDeviceConfigPowerHeadroomThe amount of input power that is available to the connected
devices in hundredths of kilowatt-hours.ro INTEGER .1.3.6.1.4.1.674.10903.200.2.200.110.3.1.8 |
rPDUDeviceConfigPeakPowerThe highest input power level recorded by the connected
devices in hundredths of kilowatt-hours.ro INTEGER .1.3.6.1.4.1.674.10903.200.2.200.110.3.1.9 |
rPDUDeviceCfgPeakPwrStartTimeThe time, in hh:mm:ss, when the device started recording the highest
input power level.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.674.10903.200.2.200.110.3.1.10 |
rPDUDeviceConfigPeakPwrCapTimeThe time, in hh:mm:ss, when the highest input power level was
recorded by the device.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.674.10903.200.2.200.110.3.1.11 |
rPDUDeviceCfgPeakPowerHeadroomThe highest level of input power that is available to the connected
devices in hundredths of kilowatt-hours.ro INTEGER .1.3.6.1.4.1.674.10903.200.2.200.110.3.1.12 |
rPDUDeviceCfgEnergyStartTimeThe time, in hh:mm:ss, when the device started recording the input
energy level.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.674.10903.200.2.200.110.3.1.13 |
rPDUDevicePropertiesTableA table of Rack PDU properties. SEQUENCE OF RPDUDevicePropertiesEntry .1.3.6.1.4.1.674.10903.200.2.200.110.4 |
rPDUDevicePropertiesEntryProperties of the Rack PDU being queried. RPDUDevicePropertiesEntry .1.3.6.1.4.1.674.10903.200.2.200.110.4.1 |
rPDUDevicePropertiesIndexThe index to the Rack PDU properties table entry.ro INTEGER .1.3.6.1.4.1.674.10903.200.2.200.110.4.1.1 |
rPDUDevicePropertiesNameA user-defined string identifying the Rack PDU.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.674.10903.200.2.200.110.4.1.2 |
rPDUDevicePropertiesNumOutletsThe number of outlets on the Rack PDU.ro INTEGER .1.3.6.1.4.1.674.10903.200.2.200.110.4.1.3 |
rPDUDevicePropertiesNumSwdOutsThe number of switched outlets on the Rack PDU.ro INTEGER .1.3.6.1.4.1.674.10903.200.2.200.110.4.1.4 |
rPDUDevicePropertiesNumMtrdOutsThe number of metered outlets on the Rack PDU.ro INTEGER .1.3.6.1.4.1.674.10903.200.2.200.110.4.1.5 |
rPDUDevicePropertiesNumPhasesThe number of phases present in the Rack PDU.ro INTEGER .1.3.6.1.4.1.674.10903.200.2.200.110.4.1.6 |
rPDUDevicePropertiesNumBreakersThe number of breakers present in the Rack PDU.ro INTEGER .1.3.6.1.4.1.674.10903.200.2.200.110.4.1.7 |
rPDUDevicePropertiesMaxCurntRtgThe maximum current rating, measured in Amps, for the Rack PDU.ro INTEGER .1.3.6.1.4.1.674.10903.200.2.200.110.4.1.8 |
rPDUDevicePropertiesOutlayoutThe phase wiring for the Rack PDU outlets. PhaseToNeutral and
PhaseToPhase: outlets wired consecutively; PhaseToNeutralGrouped
and PhaseToPhaseGrouped: groups of outlets wired consecutively.ro Enumeration .1.3.6.1.4.1.674.10903.200.2.200.110.4.1.9 |
rPDUDeviceControlTableA table of Rack PDU control data. SEQUENCE OF RPDUDeviceControlEntry .1.3.6.1.4.1.674.10903.200.2.200.110.5 |
rPDUDeviceControlEntryControl data from the Rack PDU being queried. RPDUDeviceControlEntry .1.3.6.1.4.1.674.10903.200.2.200.110.5.1 |
rPDUDeviceControlIndexThe index to the Rack PDU control table entry.ro INTEGER .1.3.6.1.4.1.674.10903.200.2.200.110.5.1.1 |
rPDUDeviceControlNameA user-defined string identifying the Rack PDU.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.674.10903.200.2.200.110.5.1.2 |
rPDUDeviceControlCommandSetting this OID to turnAllOnNow (1) will turn all outlets on
immediately. Setting this OID to turnAllOnSequence (2) will turn
all outlets on as defined by each outlet's sPDUOutletPowerOnTime
OID value. Setting this OID to turnAllOff (3) will turn all outlets
off immediately. Setting this OID to rebootAllNow (4) will reboot
all outlets immediately. Setting this OID to rebootAllSequence (5)
reboots all outlets, with power returned to the outlets in the
sequence defined by each outlet's rPDUOutSwitchedCfgPowerOnTime
OID value. Setting this OID to rebootAllSequence (5) will cause a
turnAllOffSequence to be performed. Once all outlets are off, the
Rack PDU will then delay the rPDUOutSwtchedCfgRebootDuration
OID time, and then perform a turnAllOnSequence. Setting this OID
to turnAllOffSequence (7) will turn all outlets off as defined by
each outlet's rPDUOutSwitchedCfgPowerOffTime OID value.
Getting this OID will return the noCommand (6) value.rw Enumeration .1.3.6.1.4.1.674.10903.200.2.200.110.5.1.3 |
rPDUPhase OBJECT IDENTIFIER .1.3.6.1.4.1.674.10903.200.2.200.120 |
rPDUPhaseTableSizeThe number of connected Rack PDU phases.ro INTEGER .1.3.6.1.4.1.674.10903.200.2.200.120.1 |
rPDUPhaseStatusTableA table of Rack PDU phase status data. SEQUENCE OF RPDUPhaseStatusEntry .1.3.6.1.4.1.674.10903.200.2.200.120.2 |
rPDUPhaseStatusEntryStatus data from the currently queried Rack PDU phase. RPDUPhaseStatusEntry .1.3.6.1.4.1.674.10903.200.2.200.120.2.1 |
rPDUPhaseStatusIndexThe index to the Rack PDU phase status table entry.ro INTEGER .1.3.6.1.4.1.674.10903.200.2.200.120.2.1.1 |
rPDUPhaseStatusNumberThe numeric phase ID.ro INTEGER .1.3.6.1.4.1.674.10903.200.2.200.120.2.1.2 |
rPDUPhaseStatusLoadStateIndicates the present load status of the Rack PDU phase being
queried.ro RpduLowNormalNearOverloadType .1.3.6.1.4.1.674.10903.200.2.200.120.2.1.3 |
rPDUPhaseStatusCurrentIndicates the current draw, in tenths of Amps, of the load on
the Rack PDU phase being queried.ro INTEGER .1.3.6.1.4.1.674.10903.200.2.200.120.2.1.4 |
rPDUPhaseStatusVoltageIndicates the Voltage, in Volts, of the Rack PDU
phase being queried.ro INTEGER .1.3.6.1.4.1.674.10903.200.2.200.120.2.1.5 |
rPDUPhaseStatusPowerIndicates the load power, in hundredths of kilowatts, consumed on
the Rack PDU phase being queried.ro INTEGER .1.3.6.1.4.1.674.10903.200.2.200.120.2.1.6 |
rPDUPhaseConfigTableA table of Rack PDU phase configuration data. SEQUENCE OF RPDUPhaseConfigEntry .1.3.6.1.4.1.674.10903.200.2.200.120.3 |
rPDUPhaseConfigEntryConfiguration data from the currently queried Rack PDU phase. RPDUPhaseConfigEntry .1.3.6.1.4.1.674.10903.200.2.200.120.3.1 |
rPDUPhaseConfigIndexThe index to the Rack PDU phase configuration table entry.ro INTEGER .1.3.6.1.4.1.674.10903.200.2.200.120.3.1.1 |
rPDUPhaseConfigNumberThe numeric phase ID.ro INTEGER .1.3.6.1.4.1.674.10903.200.2.200.120.3.1.2 |
rPDUPhaseCfgOverloadRestrictionThis OID controls the behavior of a Switched Rack PDU phase
when an overload condition is possible and additional outlets
are requested to be turned on. Setting this OID to
alwaysAllowTurnON (1) will always allow the outlets on the
corresponding phase to turn on. Setting this OID to
restrictOnNearOverload (2) will not allow outlets on the
corresponding phase to turn on if the
rPDULoadConfigNearOverloadThreshold OID is exceeded. Setting
this OID to restrictOnOverload (3) will not allow outlets on the
corresponding phase to turn on if the
rPDULoadConfigOverloadThreshold OID is exceeded.rw Enumeration .1.3.6.1.4.1.674.10903.200.2.200.120.3.1.3 |
rPDUPhCfgLowLoadCurntThresholdThe user-defined threshold for low phase current load, in Amps.rw INTEGER .1.3.6.1.4.1.674.10903.200.2.200.120.3.1.4 |
rPDUPhCfgNerOverloadCurntThreshThe user-defined near phase overload warning threshold in Amps.rw INTEGER .1.3.6.1.4.1.674.10903.200.2.200.120.3.1.5 |
rPDUPhCfgOverloadCurntThresholdThe user-defined phase overload current threshold in Amps.rw INTEGER .1.3.6.1.4.1.674.10903.200.2.200.120.3.1.6 |
rPDUOutlet OBJECT IDENTIFIER .1.3.6.1.4.1.674.10903.200.2.200.130 |
rPDUOutletSwitched OBJECT IDENTIFIER .1.3.6.1.4.1.674.10903.200.2.200.130.1 |
rPDUOutletSwitchedTableSizeThe number of switched outlets on connected Rack PDUs.ro INTEGER .1.3.6.1.4.1.674.10903.200.2.200.130.1.1 |
rPDUOutletSwitchedStatusTableA table of Rack PDU switched outlet status information. SEQUENCE OF RPDUOutletSwitchedStatusEntry .1.3.6.1.4.1.674.10903.200.2.200.130.1.2 |
rPDUOutletSwitchedStatusEntryStatus information for the currently-queried Rack PDU switched
outlet. RPDUOutletSwitchedStatusEntry .1.3.6.1.4.1.674.10903.200.2.200.130.1.2.1 |
rPDUOutletSwitchedStatusIndexThe index to the Rack PDU switched outlet status information table
entry.ro INTEGER .1.3.6.1.4.1.674.10903.200.2.200.130.1.2.1.1 |
rPDUOutletSwitchedStatusNumberThe numeric switched outlet ID.ro INTEGER .1.3.6.1.4.1.674.10903.200.2.200.130.1.2.1.2 |
rPDUOutletSwitchedStatusNameThe user-defined switched outlet ID string.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.674.10903.200.2.200.130.1.2.1.3 |
rPDUOutletSwitchedStatusStateIndicates the present status of the Rack PDU switched outlet
being queried.ro Enumeration .1.3.6.1.4.1.674.10903.200.2.200.130.1.2.1.4 |
rPDUOutletSwitchedStatCmdPndingIndicates whether the device is processing a command for this
outlet. If the commandPendingUnknown (3) value is returned,
all devices receiving power from the Rack PDU should be shut down.
The Rack PDU's power should then be cycled to clear this condition.ro Enumeration .1.3.6.1.4.1.674.10903.200.2.200.130.1.2.1.5 |
rPDUOutletSwitchedStatPhLayoutPhase description of the currently-queried Rack PDU switched outlet.ro RpduOutletPhaseLayoutType .1.3.6.1.4.1.674.10903.200.2.200.130.1.2.1.6 |
rPDUOutletSwitchedConfigTableA table of Rack PDU switched outlet configuration data. SEQUENCE OF RPDUOutletSwitchedConfigEntry .1.3.6.1.4.1.674.10903.200.2.200.130.1.3 |
rPDUOutletSwitchedConfigEntryConfiguration data from the currently-queried Rack PDU switched
outlet. RPDUOutletSwitchedConfigEntry .1.3.6.1.4.1.674.10903.200.2.200.130.1.3.1 |
rPDUOutletSwitchedConfigIndexThe index to the Rack PDU switched outlet configuration table entry.ro INTEGER .1.3.6.1.4.1.674.10903.200.2.200.130.1.3.1.1 |
rPDUOutletSwitchedConfigNumberThe numeric switched outlet ID.ro INTEGER .1.3.6.1.4.1.674.10903.200.2.200.130.1.3.1.2 |
rPDUOutletSwitchedConfigNameThe user-defined switched outlet ID string.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.674.10903.200.2.200.130.1.3.1.3 |
rPDUOutSwitchedCfgPowerOnTimeThe amount of time, in seconds, between when power is provided to
the Rack PDU and when this switched outlet starts providing power.rw INTEGER .1.3.6.1.4.1.674.10903.200.2.200.130.1.3.1.4 |
rPDUOutSwitchedCfgPowerOffTimeThe amount of time, in seconds, this outlet will delay turning off.rw INTEGER .1.3.6.1.4.1.674.10903.200.2.200.130.1.3.1.5 |
rPDUOutSwtchedCfgRebootDurationAfter turning off power during a reboot sequence, the amount of
time, in seconds, to wait before turning on power to this outlet
again.rw INTEGER .1.3.6.1.4.1.674.10903.200.2.200.130.1.3.1.6 |
rPDUOutletSwitchedControlTableA table of Rack PDU switched outlet control data. SEQUENCE OF RPDUOutletSwitchedControlEntry .1.3.6.1.4.1.674.10903.200.2.200.130.1.4 |
rPDUOutletSwitchedControlEntryControl data for the currently-queried Rack PDU switched outlet. RPDUOutletSwitchedControlEntry .1.3.6.1.4.1.674.10903.200.2.200.130.1.4.1 |
rPDUOutletSwitchedControlIndexThe index to the Rack PDU switched outlet control data table entry.ro INTEGER .1.3.6.1.4.1.674.10903.200.2.200.130.1.4.1.1 |
rPDUOutletSwitchedControlNumberThe numeric switched outlet ID.ro INTEGER .1.3.6.1.4.1.674.10903.200.2.200.130.1.4.1.2 |
rPDUOutletSwitchedControlNameThe user-defined switched outlet ID string.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.674.10903.200.2.200.130.1.4.1.3 |
rPDUOutletSwitchedControlCmdGetting this variable will return the outlet state. If the outlet is
on, the outletOn (1) value will be returned. If the outlet is off,
the outletOff (2) value will be returned. If the state of the outlet
cannot be determined, the outletUnknown (4) value will be returned.
If the outletUnknown condition should occur, all devices receiving
power from the PDU should be shut down. The PDU's power should then
be cycled to clear this condition. Setting this variable to
outletOn (1) will turn the outlet on. Setting this variable to
outletOff (2) will turn the outlet off. Setting this variable to
outletReboot (3) will reboot the outlet. Setting this variable to
outletOnWithDelay (5) will turn the outlet on after the
rPDUOutSwitchedCfgPowerOnTime OID has elapsed. Setting this
variable to outletOffWithDelay (6) will turn the outlet off after
the rPDUOutSwitchedCfgPowerOffTime OID has elapsed. Setting
this variable to outletRebootWithDelay (7) will turn the outlet off
after the rPDUOutSwitchedCfgPowerOffTime OID has elapsed,
wait the rPDUOutSwtchedCfgRebootDuration OID time, then turn
the outlet back on.rw Enumeration .1.3.6.1.4.1.674.10903.200.2.200.130.1.4.1.4 |
rPDUOutletMetered OBJECT IDENTIFIER .1.3.6.1.4.1.674.10903.200.2.200.130.2 |
rPDUOutletMeteredTableSizeThe number of metered outlets on connected Rack PDUs.ro INTEGER .1.3.6.1.4.1.674.10903.200.2.200.130.2.1 |
rPDUOutletMeteredStatusTableA table of Rack PDU metered outlet status data. SEQUENCE OF RPDUOutletMeteredStatusEntry .1.3.6.1.4.1.674.10903.200.2.200.130.2.2 |
rPDUOutletMeteredStatusEntryStatus data from the currently-queried Rack PDU metered outlet. RPDUOutletMeteredStatusEntry .1.3.6.1.4.1.674.10903.200.2.200.130.2.2.1 |
rPDUOutletMeteredStatusIndexThe index to the Rack PDU metered status table entry.ro INTEGER .1.3.6.1.4.1.674.10903.200.2.200.130.2.2.1.1 |
rPDUOutletMeteredStatusNumberThe numeric metered outlet ID.ro INTEGER .1.3.6.1.4.1.674.10903.200.2.200.130.2.2.1.2 |
rPDUOutletMeteredStatusNameThe user-defined metered outlet ID string.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.674.10903.200.2.200.130.2.2.1.3 |
rPDUOutletMeteredStatusLayoutPhase description of currently queried Rack PDU metered outlet.ro RpduOutletPhaseLayoutType .1.3.6.1.4.1.674.10903.200.2.200.130.2.2.1.4 |
rPDUOutMeteredStatPowerRatingThe power rating for the currently queried Rack PDU metered outlet.ro INTEGER .1.3.6.1.4.1.674.10903.200.2.200.130.2.2.1.5 |
rPDUOutletMeteredStatusCurrentIndicates the current draw, in Amps, of the load on the Rack PDU
outlet being queried.ro INTEGER .1.3.6.1.4.1.674.10903.200.2.200.130.2.2.1.6 |
rPDUOutletMeteredStatusEnergyA user resettable energy meter measuring Rack PDU load energy
consumption in kilowatt-hours.ro INTEGER .1.3.6.1.4.1.674.10903.200.2.200.130.2.2.1.7 |
rPDUOutletMeteredStatusPowerIndicates the power draw of the load on the Rack PDU outlet being
queried.ro INTEGER .1.3.6.1.4.1.674.10903.200.2.200.130.2.2.1.8 |
rPDUOutletMeteredStatPeakPowerThe highest power level recorded by the currently queried Rack PDU
metered outlet, in kilowatts.ro INTEGER .1.3.6.1.4.1.674.10903.200.2.200.130.2.2.1.9 |
rPDUOutMeteredStatPeakPwrTimeIndicates the date and time that peak power consumption occuredro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.674.10903.200.2.200.130.2.2.1.10 |
rPDUOutMeteredStatusLoadStateIndicates the present load status of the Rack PDU Outlet being
queried.ro RpduLowNormalNearOverloadType .1.3.6.1.4.1.674.10903.200.2.200.130.2.2.1.11 |
rPDUOutletMeteredConfigTableA table of Rack PDU metered outlet configuration data. SEQUENCE OF RPDUOutletMeteredConfigEntry .1.3.6.1.4.1.674.10903.200.2.200.130.2.4 |
rPDUOutletMeteredConfigEntryConfiguration data from the currently queried Rack PDU metered
outlet. RPDUOutletMeteredConfigEntry .1.3.6.1.4.1.674.10903.200.2.200.130.2.4.1 |
rPDUOutletMeteredConfigIndexThe index to the Rack PDU metered outlet configuration table entry.ro INTEGER .1.3.6.1.4.1.674.10903.200.2.200.130.2.4.1.1 |
rPDUOutletMeteredConfigNumberThe numeric switched outlet ID.ro INTEGER .1.3.6.1.4.1.674.10903.200.2.200.130.2.4.1.2 |
rPDUOutletMeteredConfigNameThe user-defined metered outlet ID string.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.674.10903.200.2.200.130.2.4.1.3 |
rPDUOutMtredCfgLowLdCurntThreshThe user-defined low load outlet current threshold, in Amps.rw INTEGER .1.3.6.1.4.1.674.10903.200.2.200.130.2.4.1.4 |
rPDUOutMtrdCfgNrOvdCurntThreshThe user-defined near outlet overload warning threshold, in Amps.rw INTEGER .1.3.6.1.4.1.674.10903.200.2.200.130.2.4.1.5 |
rPDUOutMtredCfgOvrldCurntThreshThe user-defined outlet overload current threshold, in Amps.rw INTEGER .1.3.6.1.4.1.674.10903.200.2.200.130.2.4.1.6 |
rPDUOutMeteredEnergyStartTimeThe time, in hh:mm:ss, when the currently queried Rack PDU metered
outlet started recording the input energy level.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.674.10903.200.2.200.130.2.5 |
rPDUOutMeteredPeakPwrStartTimeThe time, in hh:mm:ss, when the currently queried Rack PDU metered
outlet started recording the highest level of input power that is
available to the connected device.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.674.10903.200.2.200.130.2.6 |
rPDUPowerSupply OBJECT IDENTIFIER .1.3.6.1.4.1.674.10903.200.2.200.140 |
rPDUPowerSupplyAlarmDGetting this OID will return the status of the power supply alarm.ro Enumeration .1.3.6.1.4.1.674.10903.200.2.200.140.1 |
rPDUPowerSupplyVoltageThe voltage provided by the power supply in tenths of volts.ro INTEGER .1.3.6.1.4.1.674.10903.200.2.200.140.2 |
rPDUSensor OBJECT IDENTIFIER .1.3.6.1.4.1.674.10903.200.2.200.150 |
rPDUSensorStatus OBJECT IDENTIFIER .1.3.6.1.4.1.674.10903.200.2.200.150.1 |
rPDUSensorStatusTableSizeThe number of connected temperature sensors.ro INTEGER .1.3.6.1.4.1.674.10903.200.2.200.150.1.1 |
rPDUSensorStatusTableA table of temperature sensor status data. SEQUENCE OF RPDUSensorStatusEntry .1.3.6.1.4.1.674.10903.200.2.200.150.1.2 |
rPDUSensorStatusEntryStatus information from the temperature sensor being queried. RPDUSensorStatusEntry .1.3.6.1.4.1.674.10903.200.2.200.150.1.2.1 |
rPDUSensorStatusIndexThe index to the status data table entry.ro INTEGER .1.3.6.1.4.1.674.10903.200.2.200.150.1.2.1.1 |
rPDUSensorStatusNameThe user-defined sensor ID string.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.674.10903.200.2.200.150.1.2.1.2 |
rPDUSensorStatusTypeThe type of the sensor.ro Enumeration .1.3.6.1.4.1.674.10903.200.2.200.150.1.2.1.3 |
rPDUSensorTemp OBJECT IDENTIFIER .1.3.6.1.4.1.674.10903.200.2.200.150.2 |
rPDUSensorTempTableSizeThe number of connected temperature sensors.ro INTEGER .1.3.6.1.4.1.674.10903.200.2.200.150.2.1 |
rPDUSensorTempStatusTableA table of temperature sensor status data. SEQUENCE OF RPDUSensorTempStatusEntry .1.3.6.1.4.1.674.10903.200.2.200.150.2.2 |
rPDUSensorTempStatusEntryStatus information from the temperature sensor being queried. RPDUSensorTempStatusEntry .1.3.6.1.4.1.674.10903.200.2.200.150.2.2.1 |
rPDUSensorTempStatusIndexThe index to the temperature status data table entry.ro INTEGER .1.3.6.1.4.1.674.10903.200.2.200.150.2.2.1.1 |
rPDUSensorTempStatusNameThe user-defined temperature-humidity sensor ID string.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.674.10903.200.2.200.150.2.2.1.2 |
rPDUSensorTempStatusCommStatusThe communications status of the sensor.ro RpduCommNoneOKLostType .1.3.6.1.4.1.674.10903.200.2.200.150.2.2.1.3 |
rPDUSensorTempStatusTempFThe sensor temperature reading in tenths of degrees Fahrenheit.ro INTEGER .1.3.6.1.4.1.674.10903.200.2.200.150.2.2.1.4 |
rPDUSensorTempStatusTempCThe sensor temperature reading in tenths of degrees Celsius.ro INTEGER .1.3.6.1.4.1.674.10903.200.2.200.150.2.2.1.5 |
rPDUSensorTempStatusAlarmStatusThe alarm status of the sensor.ro RpduNotPBMinLowNrmlOHiMaxType .1.3.6.1.4.1.674.10903.200.2.200.150.2.2.1.6 |
rPDUSensorTempConfigTableA table of temperature-humidity sensor configuration data. SEQUENCE OF RPDUSensorTempConfigEntry .1.3.6.1.4.1.674.10903.200.2.200.150.2.3 |
rPDUSensorTempConfigEntryConfiguration data from the temperature-humidity sensor being
queried. RPDUSensorTempConfigEntry .1.3.6.1.4.1.674.10903.200.2.200.150.2.3.1 |
rPDUSensorTempConfigIndexThe index to the temperature-humidity sensor configuration data
table entry.ro INTEGER .1.3.6.1.4.1.674.10903.200.2.200.150.2.3.1.1 |
rPDUSensorTempConfigNameThe user-defined temperature-humidity sensor ID string.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.674.10903.200.2.200.150.2.3.1.2 |
rPDUSensorTempCfgTempMaxThreshFThe sensor maximum temperature alarm threshold in Fahrenheit.rw INTEGER .1.3.6.1.4.1.674.10903.200.2.200.150.2.3.1.3 |
rPDUSnsorTempCfgTempHighThreshFThe sensor high temperature warning alarm threshold in Fahrenheit.rw INTEGER .1.3.6.1.4.1.674.10903.200.2.200.150.2.3.1.4 |
rPDUSnsorTempCfgTempHysteresisFThe sensor temperature hysteresis setting in Fahrenheit.rw INTEGER .1.3.6.1.4.1.674.10903.200.2.200.150.2.3.1.5 |
rPDUSensorTempCfgTempMaxThreshCThe sensor maximum temperature alarm threshold in Celsius.rw INTEGER .1.3.6.1.4.1.674.10903.200.2.200.150.2.3.1.6 |
rPDUSnsorTempCfgTempHighThreshCThe sensor high temperature warning alarm threshold in Celsius.rw INTEGER .1.3.6.1.4.1.674.10903.200.2.200.150.2.3.1.7 |
rPDUSnsorTempCfgTempHysteresisCThe sensor temperature hysteresis setting in Celsius.rw INTEGER .1.3.6.1.4.1.674.10903.200.2.200.150.2.3.1.8 |
rPDUSnsorTempCfgAlarmGenerationIndicates whether the Temp Alarm Generation is enabled.rw RpduEnableDisableType .1.3.6.1.4.1.674.10903.200.2.200.150.2.3.1.9 |
rPDUSensorHumidity OBJECT IDENTIFIER .1.3.6.1.4.1.674.10903.200.2.200.150.3 |
rPDUSensorHumidityTableSizeThe number of connected temperature-humidity sensors.ro INTEGER .1.3.6.1.4.1.674.10903.200.2.200.150.3.1 |
rPDUSensorHumidityStatusTableA table of temperature-humidity sensor status data. SEQUENCE OF RPDUSensorHumidityStatusEntry .1.3.6.1.4.1.674.10903.200.2.200.150.3.2 |
rPDUSensorHumidityStatusEntryStatus information from the temperature-humidity sensor being
queried. RPDUSensorHumidityStatusEntry .1.3.6.1.4.1.674.10903.200.2.200.150.3.2.1 |
rPDUSensorHumidityStatusIndexThe index to the temperature-humidity status data table entry.ro INTEGER .1.3.6.1.4.1.674.10903.200.2.200.150.3.2.1.1 |
rPDUSensorHumidityStatusNameThe user-defined temperature-humidity sensor ID string.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.674.10903.200.2.200.150.3.2.1.2 |
rPDUSnsorHumidityStatCommStatusThe communications status of the sensor.ro RpduCommNoneOKLostType .1.3.6.1.4.1.674.10903.200.2.200.150.3.2.1.3 |
rPDUSnsorHumStatRelativeHumdityThe sensor humidity reading in percent relative humidity.ro INTEGER .1.3.6.1.4.1.674.10903.200.2.200.150.3.2.1.4 |
rPDUSnsorHumStatusAlarmStatusThe alarm status of the sensor.ro RpduNotPBMinLowNrmlOHiMaxType .1.3.6.1.4.1.674.10903.200.2.200.150.3.2.1.5 |
rPDUSensorHumidityConfigTableA table of temperature-humidity sensor configuration data. SEQUENCE OF RPDUSensorHumidityConfigEntry .1.3.6.1.4.1.674.10903.200.2.200.150.3.3 |
rPDUSensorHumidityConfigEntryConfiguration data from the temperature-humidity sensor being
queried. RPDUSensorHumidityConfigEntry .1.3.6.1.4.1.674.10903.200.2.200.150.3.3.1 |
rPDUSensorHumidityConfigIndexThe index to the temperature-humidity sensor configuration data
table entry.ro INTEGER .1.3.6.1.4.1.674.10903.200.2.200.150.3.3.1.1 |
rPDUSensorHumidityConfigNameThe user-defined temperature-humidity sensor ID string.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.674.10903.200.2.200.150.3.3.1.2 |
rPDUSnsorHumCfgHumdityLowThreshThe sensor low humidity warning alarm threshold in percent relative
humidity.rw INTEGER .1.3.6.1.4.1.674.10903.200.2.200.150.3.3.1.3 |
rPDUSnsorHumCfgHumdityMinThreshThe sensor minimum humidity alarm threshold in percent relative
humidity.rw INTEGER .1.3.6.1.4.1.674.10903.200.2.200.150.3.3.1.4 |
rPDUSnsorHumCfgHumdtyHysteresisThe sensor humidity hysteresis setting in percent relative humidity.rw INTEGER .1.3.6.1.4.1.674.10903.200.2.200.150.3.3.1.5 |
rPDUSnsorHumCfgAlarmGenerationIndicates whether the Humidity Alarm Generation is enabled.rw RpduEnableDisableType .1.3.6.1.4.1.674.10903.200.2.200.150.3.3.1.6 |
rPDUSensorDiscrete OBJECT IDENTIFIER .1.3.6.1.4.1.674.10903.200.2.200.150.4 |
rPDUSensorDiscreteTableSizeThe number of connected discrete sensors.ro INTEGER .1.3.6.1.4.1.674.10903.200.2.200.150.4.1 |
rPDUSensorDiscreteStatusTableA table of discrete sensor status data. SEQUENCE OF RPDUSensorDiscreteStatusEntry .1.3.6.1.4.1.674.10903.200.2.200.150.4.2 |
rPDUSensorDiscreteStatusEntryStatus information from the discrete sensor being queried. RPDUSensorDiscreteStatusEntry .1.3.6.1.4.1.674.10903.200.2.200.150.4.2.1 |
rPDUSensorDiscreteStatusIndexThe index to the discrete sensor status data table entry.ro INTEGER .1.3.6.1.4.1.674.10903.200.2.200.150.4.2.1.1 |
rPDUSensorDiscreteStatusNameThe user-defined discrete sensor ID string.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.674.10903.200.2.200.150.4.2.1.2 |
rPDUSnsorDiscreteStatCurntStateThe current state of the discrete sensor, open, closed, or unknown.ro Enumeration .1.3.6.1.4.1.674.10903.200.2.200.150.4.2.1.3 |
rPDUSnsorDiscreteStatAlarmStateIndicates the alarm status of the discrete sensor input.ro RpduNormalAlarmType .1.3.6.1.4.1.674.10903.200.2.200.150.4.2.1.4 |
rPDUSensorDiscreteConfigTableA table of discrete sensor configuration data. SEQUENCE OF RPDUSensorDiscreteConfigEntry .1.3.6.1.4.1.674.10903.200.2.200.150.4.3 |
rPDUSensorDiscreteConfigEntryConfiguration data from the discrete sensor being queried. RPDUSensorDiscreteConfigEntry .1.3.6.1.4.1.674.10903.200.2.200.150.4.3.1 |
rPDUSensorDiscreteConfigIndexThe index to the discrete sensor configuration data table entry.ro INTEGER .1.3.6.1.4.1.674.10903.200.2.200.150.4.3.1.1 |
rPDUSensorDiscreteConfigNameThe user-defined discrete sensor ID string.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.674.10903.200.2.200.150.4.3.1.2 |
rPDUSnsorDiscreteCfgNormalStateIndicates the normal state of the discrete input contact.rw Enumeration .1.3.6.1.4.1.674.10903.200.2.200.150.4.3.1.3 |
rPDUSnsorDiscrteAlarmGenerationIndicates whether Discrete Alarm Generation is enabled.rw RpduEnableDisableType .1.3.6.1.4.1.674.10903.200.2.200.150.4.3.1.4 |
mtrapargsD OBJECT IDENTIFIER .1.3.6.1.4.1.674.10903.200.2.200.160 |
contactNumberThis OID allows traps to be sent with an integer argument that
may not be defined in the MIB. A get of this OID will return 0.ro INTEGER .1.3.6.1.4.1.674.10903.200.2.200.160.1 |
outletNumberThis OID allows traps to be sent with an integer argument that
may not be defined in the MIB. A get of this OID will return 0.ro INTEGER .1.3.6.1.4.1.674.10903.200.2.200.160.2 |
mtrapargsStringThis OID allows traps to be sent with an octet string argument
that may not be defined in the MIB. A get of this OID will return
a NULL string.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.674.10903.200.2.200.160.3 |
phaseNumberThis OID allows traps to be sent with an integer argument that
may not be defined in the MIB. A get of this OID will return 0.ro INTEGER .1.3.6.1.4.1.674.10903.200.2.200.160.4 |
sensorNumberThis OID allows traps to be sent with an integer argument that
may not be defined in the MIB. A get of this OID will return 0.ro INTEGER .1.3.6.1.4.1.674.10903.200.2.200.160.5 |
deviceNameDThis OID allows traps to be sent with an octet string argument
that may not be defined in the MIB. A get of this OID will return
a NULL string.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.674.10903.200.2.200.160.6 |
serialNumberThis OID allows traps to be sent with an octet string argument that
may not be defined in the MIB. A get of this OID will return a NULL
string.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.674.10903.200.2.200.160.7 |
testTrapargsIntegerThis OID allows traps to be sent with an integer argument that
may not be defined in the MIB. A get of this OID will return 0.ro INTEGER .1.3.6.1.4.1.674.10903.200.2.200.160.8 |
events OBJECT IDENTIFIER .1.3.6.1.4.1.674.10903.200.2.200.500 |
deviceCommunicationLostClearedINFORMATIONAL: Lost communication with device
has been re-established.
The first argument is the serial number.
The second argument is the device name. TRAP-TYPE .1.3.6.1.4.1.674.10903.200.2.200.500.0.1 |
deviceCommunicationLostSetCRITICAL: Lost communication with device.
The first argument is the serial number.
The second argument is the device name. TRAP-TYPE .1.3.6.1.4.1.674.10903.200.2.200.500.0.2 |
componentCommLostClearedINFORMATIONAL: Lost communication with an on board component
has been re-established.
The first argument is the serial number.
The second argument is the device name. TRAP-TYPE .1.3.6.1.4.1.674.10903.200.2.200.500.0.3 |
componentCommLostSetCRITICAL: Lost communication with an on board component.
The first argument is the serial number.
The second argument is the device name. TRAP-TYPE .1.3.6.1.4.1.674.10903.200.2.200.500.0.4 |
cANBusOffClearedINFORMATIONAL: CAN bus off condition was cleared.
The first argument is the serial number.
The second argument is the device name. TRAP-TYPE .1.3.6.1.4.1.674.10903.200.2.200.500.0.5 |
canBusOffSetMINOR: CAN bus off condition was set.
The first argument is the serial number.
The second argument is the device name. TRAP-TYPE .1.3.6.1.4.1.674.10903.200.2.200.500.0.6 |
powerSupplyFailureClearedINFORMATIONAL: Unit's power supply voltage is no longer out of
tolerance.
The first argument is the serial number.
The second argument is the device name. TRAP-TYPE .1.3.6.1.4.1.674.10903.200.2.200.500.0.7 |
powerSupplyFailureSetCRITICAL: Unit's power supply voltage is out of tolerance.
The first argument is the serial number.
The second argument is the device name. TRAP-TYPE .1.3.6.1.4.1.674.10903.200.2.200.500.0.8 |
keypadButtonStuckClearedINFORMATIONAL: Keypad button stuck has been cleared.
The first argument is the serial number.
The second argument is the device name. TRAP-TYPE .1.3.6.1.4.1.674.10903.200.2.200.500.0.9 |
keypadButtonStuckSetMINOR: Keypad button stuck has been set.
The first argument is the serial number.
The second argument is the device name. TRAP-TYPE .1.3.6.1.4.1.674.10903.200.2.200.500.0.10 |
dryContactAbnormalClearedINFORMATIONAL: Dry Contact is no longer in an abnormal state.
The first argument is the serial number.
The second argument is the device name.
The third argument is the contact number. TRAP-TYPE .1.3.6.1.4.1.674.10903.200.2.200.500.0.11 |
dryContactAbnormalSetCRITICAL: Dry Contact has moved to an abnormal state.
The first argument is the serial number.
The second argument is the device name.
The third argument is the contact number. TRAP-TYPE .1.3.6.1.4.1.674.10903.200.2.200.500.0.12 |
deviceLowLoadClearedINFORMATIONAL: Device load is no longer below the 'Low Load'
threshold value.
The first argument is the serial number.
The second argument is the device name. TRAP-TYPE .1.3.6.1.4.1.674.10903.200.2.200.500.0.13 |
deviceLowLoadSetMINOR: Device load has fallen below the 'Low Load' threshold
value.
The first argument is the serial number.
The second argument is the device name. TRAP-TYPE .1.3.6.1.4.1.674.10903.200.2.200.500.0.14 |
deviceNearOverLoadClearedINFORMATIONAL: Device load no longer exceeds the 'Near Over Load'
threshold value.
The first argument is the serial number.
The second argument is the device name. TRAP-TYPE .1.3.6.1.4.1.674.10903.200.2.200.500.0.15 |
deviceNearOverLoadSetMINOR: Device load has exceeded the 'Near Over Load' threshold
value.
The first argument is the serial number.
The second argument is the device name. TRAP-TYPE .1.3.6.1.4.1.674.10903.200.2.200.500.0.16 |
deviceOverLoadClearedINFORMATIONAL: Device load no longer exceeds the 'Over Load'
threshold value.
The first argument is the serial number.
The second argument is the device name. TRAP-TYPE .1.3.6.1.4.1.674.10903.200.2.200.500.0.17 |
deviceOverLoadSetCRITICAL: Device load has exceeded the 'Over Load' threshold
value.
The first argument is the serial number.
The second argument is the device name. TRAP-TYPE .1.3.6.1.4.1.674.10903.200.2.200.500.0.18 |
phaseLowLoadClearedINFORMATIONAL: Phase load is no longer below the 'Low Load'
threshold value.
The first argument is the serial number.
The second argument is the device name.
The third argument is the phase number. TRAP-TYPE .1.3.6.1.4.1.674.10903.200.2.200.500.0.19 |
phaseLowLoadSetMINOR: Phase load has fallen below the 'Low Load' threshold
value.
The first argument is the serial number.
The second argument is the device name.
The third argument is the phase number. TRAP-TYPE .1.3.6.1.4.1.674.10903.200.2.200.500.0.20 |
phaseNearOverLoadClearedINFORMATIONAL: Phase load no longer exceeds the 'Near Over Load'
threshold value.
The first argument is the serial number.
The second argument is the device name.
The third argument is the phase number. TRAP-TYPE .1.3.6.1.4.1.674.10903.200.2.200.500.0.21 |
phaseNearOverLoadSetMINOR: Phase load has exceeded the 'Near Over Load' threshold
value.
The first argument is the serial number.
The second argument is the device name.
The third argument is the phase number. TRAP-TYPE .1.3.6.1.4.1.674.10903.200.2.200.500.0.22 |
phaseOverLoadClearedINFORMATIONAL: Phase load no longer exceeds the 'Over Load'
threshold value.
The first argument is the serial number.
The second argument is the device name.
The third argument is the phase number. TRAP-TYPE .1.3.6.1.4.1.674.10903.200.2.200.500.0.23 |
phaseOverLoadSetCRITICAL: Phase load has exceeded the 'Over Load' threshold
value.
The first argument is the serial number.
The second argument is the device name.
The third argument is the phase number. TRAP-TYPE .1.3.6.1.4.1.674.10903.200.2.200.500.0.24 |
outletLowLoadClearedINFORMATIONAL: Outlet load is no longer below the 'Low Load'
threshold value.
The first argument is the serial number.
The second argument is the device name.
The third argument is the outlet number. TRAP-TYPE .1.3.6.1.4.1.674.10903.200.2.200.500.0.25 |
outletLowLoadSetMINOR: Outlet load had fallen below the 'Low Load' threshold
value.
The first argument is the serial number.
The second argument is the device name.
The third argument is the outlet number. TRAP-TYPE .1.3.6.1.4.1.674.10903.200.2.200.500.0.26 |
outletNearOverLoadClearedINFORMATIONAL: Outlet load no longer exceeds the 'Near Over Load'
threshold value.
The first argument is the serial number.
The second argument is the device name.
The third argument is the outlet number. TRAP-TYPE .1.3.6.1.4.1.674.10903.200.2.200.500.0.27 |
outletNearOverLoadSetMINOR: Outlet load has exceeded the 'Near Over Load' threshold
value.
The first argument is the serial number.
The second argument is the device name.
The third argument is the outlet number. TRAP-TYPE .1.3.6.1.4.1.674.10903.200.2.200.500.0.28 |
outletOverLoadClearedINFORMATIONAL: Outlet load no longer exceeds the 'Over Load'
threshold value.
The first argument is the serial number.
The second argument is the device name.
The third argument is the outlet number. TRAP-TYPE .1.3.6.1.4.1.674.10903.200.2.200.500.0.29 |
outletOverLoadSetCRITICAL: Outlet load has exceeded the 'Over Load' threshold
value.
The first argument is the serial number.
The second argument is the device name.
The third argument is the outlet number. TRAP-TYPE .1.3.6.1.4.1.674.10903.200.2.200.500.0.30 |
sensorDisconnectedClearedINFORMATIONAL: Sensor disconnected condition cleared.
The first argument is the serial number.
The second argument is the device name.
The third argument is the sensor number. TRAP-TYPE .1.3.6.1.4.1.674.10903.200.2.200.500.0.31 |
sensorDisconnectedSetMINOR: Sensor disconnected condition set.
The first argument is the serial number.
The second argument is the device name.
The third argument is the sensor number. TRAP-TYPE .1.3.6.1.4.1.674.10903.200.2.200.500.0.32 |
sensorTypeIndeterminateClearedINFORMATIONAL: Sensor type indeterminate condition cleared.
The first argument is the serial number.
The second argument is the device name.
The third argument is the sensor number. TRAP-TYPE .1.3.6.1.4.1.674.10903.200.2.200.500.0.33 |
sensorTypeIndeterminateSetMINOR: Sensor type indeterminate condition set.
The first argument is the serial number.
The second argument is the device name.
The third argument is the sensor number. TRAP-TYPE .1.3.6.1.4.1.674.10903.200.2.200.500.0.34 |
sensorTypeUnsupportedClearedINFORMATIONAL: Sensor type unsupported condition cleared.
The first argument is the serial number.
The second argument is the device name.
The third argument is the sensor number. TRAP-TYPE .1.3.6.1.4.1.674.10903.200.2.200.500.0.35 |
sensorTypeUnsupportedSetMINOR: Sensor type unsupported condition set.
The first argument is the serial number.
The second argument is the device name.
The third argument is the sensor number. TRAP-TYPE .1.3.6.1.4.1.674.10903.200.2.200.500.0.36 |
maxTemperatureExceededClearedINFORMATIONAL: Sensor Temperature no longer exceeds the
'Max Temperature' threshold value.
The first argument is the serial number.
The second argument is the device name.
The third argument is the sensor number. TRAP-TYPE .1.3.6.1.4.1.674.10903.200.2.200.500.0.37 |
maxTemperatureExceededSetCRITICAL: Sensor Temperature has exceeded the 'Max Temperature'
threshold value.
The first argument is the serial number.
The second argument is the device name.
The third argument is the sensor number. TRAP-TYPE .1.3.6.1.4.1.674.10903.200.2.200.500.0.38 |
highTemperatureExceededClearedINFORMATIONAL: Sensor Temperature no longer exceeds the 'High
Temperature' threshold value.
The first argument is the serial number.
The second argument is the device name.
The third argument is the sensor number. TRAP-TYPE .1.3.6.1.4.1.674.10903.200.2.200.500.0.39 |
highTemperatureExceededSetMINOR: Sensor Temperature has exceeded the 'High Temperature'
threshold value.
The first argument is the serial number.
The second argument is the device name.
The third argument is the sensor number. TRAP-TYPE .1.3.6.1.4.1.674.10903.200.2.200.500.0.40 |
lowHumidityExceededClearedINFORMATIONAL: Sensor Humidity is no longer below the 'Low
Humidity' threshold value.
The first argument is the serial number.
The second argument is the device name.
The third argument is the sensor number. TRAP-TYPE .1.3.6.1.4.1.674.10903.200.2.200.500.0.41 |
lowHumidityExceededSetMINOR: Sensor Humidity has fallen below the 'Low Humidity'
threshold value.
The first argument is the serial number.
The second argument is the device name.
The third argument is the sensor number. TRAP-TYPE .1.3.6.1.4.1.674.10903.200.2.200.500.0.42 |
minHumidityExceededClearedINFORMATIONAL: Sensor Humidity is no longer below the 'Min
Humidity' threshold value.
The first argument is the serial number.
The second argument is the device name.
The third argument is the sensor number. TRAP-TYPE .1.3.6.1.4.1.674.10903.200.2.200.500.0.43 |
minHumidityExceededSetCRITICAL: Sensor Humidity has fallen below the 'Min Humidity'
threshold value.
The first argument is the serial number.
The second argument is the device name.
The third argument is the sensor number. TRAP-TYPE .1.3.6.1.4.1.674.10903.200.2.200.500.0.44 |
outletTurnOnINFORMATIONAL: An outlet has turned on.
The first argument is the serial number.
The second argument is the device name.
The third argument is the outlet number. TRAP-TYPE .1.3.6.1.4.1.674.10903.200.2.200.500.0.45 |
outletTurnOffINFORMATIONAL: An outlet has turned off.
The first argument is the serial number.
The second argument is the device name.
The third argument is the outlet number. TRAP-TYPE .1.3.6.1.4.1.674.10903.200.2.200.500.0.46 |
actionCancelledINFORMATIONAL: An outlet action has been cancelled.
The first argument is the serial number.
The second argument is the device name.
The third argument is the outlet number. TRAP-TYPE .1.3.6.1.4.1.674.10903.200.2.200.500.0.47 |
deviceConfigurationChangeINFORMATIONAL: A device configuration has been changed.
The first argument is the serial number.
The second argument is the device name. TRAP-TYPE .1.3.6.1.4.1.674.10903.200.2.200.500.0.48 |
sensorConfigurationChangeINFORMATIONAL: A sensor configuration has been changed.
The first argument is the serial number.
The second argument is the device name.
The third argument is the sensor number. TRAP-TYPE .1.3.6.1.4.1.674.10903.200.2.200.500.0.49 |
outletConfigurationChangeINFORMATIONAL: An outlet configuration has been changed.
The first argument is the serial number.
The second argument is the device name.
The third argument is the outlet number. TRAP-TYPE .1.3.6.1.4.1.674.10903.200.2.200.500.0.50 |
phaseConfigurationChangeINFORMATIONAL: A phase configuration has been changed.
The first argument is the serial number.
The second argument is the device name.
The third argument is the phase number. TRAP-TYPE .1.3.6.1.4.1.674.10903.200.2.200.500.0.51 |
dryContactConfigurationChangeINFORMATIONAL: A dry contact configuration has been changed.
The first argument is the serial number.
The second argument is the device name.
The third argument is the contact number. TRAP-TYPE .1.3.6.1.4.1.674.10903.200.2.200.500.0.52 |
actionInitINFORMATIONAL: An outlet action has been initialized.
The first argument is the serial number.
The second argument is the device name.
The third argument is the outlet number. TRAP-TYPE .1.3.6.1.4.1.674.10903.200.2.200.500.0.53 |
actionFailedMINOR: An outlet action has failed to complete.
The first argument is the serial number.
The second argument is the device name.
The third argument is the outlet number. TRAP-TYPE .1.3.6.1.4.1.674.10903.200.2.200.500.0.54 |
actionDeletedINFORMATIONAL: An outlet action has been deleted.
The first argument is the serial number.
The second argument is the device name.
The third argument is the outlet number. TRAP-TYPE .1.3.6.1.4.1.674.10903.200.2.200.500.0.55 |
syncCommandFailedMINOR: An outlet sync command to another unit has failed.
The first argument is the serial number.
The second argument is the device name.
The third argument is the outlet number. TRAP-TYPE .1.3.6.1.4.1.674.10903.200.2.200.500.0.56 |
mPOPicFwDownloadStartedINFORMATIONAL: MPO pic fw download started.
The first argument is the serial number.
The second argument is the device name. TRAP-TYPE .1.3.6.1.4.1.674.10903.200.2.200.500.0.57 |
mPOPicFwDownloadCompleteINFORMATIONAL: MPO pic fw download complete.
The first argument is the serial number.
The second argument is the device name. TRAP-TYPE .1.3.6.1.4.1.674.10903.200.2.200.500.0.58 |
mPOPicFwDownloadAbortedINFORMATIONAL: MPO pic fw download aborted.
The first argument is the serial number.
The second argument is the device name. TRAP-TYPE .1.3.6.1.4.1.674.10903.200.2.200.500.0.59 |
sensorCommEstablishedINFORMATIONAL: Sensor comm established.
The first argument is the serial number.
The second argument is the device name.
The third argument is the sensor number. TRAP-TYPE .1.3.6.1.4.1.674.10903.200.2.200.500.0.60 |
configChangeSNMPMINOR: The SNMP configuration has been changed. TRAP-TYPE .1.3.6.1.4.1.674.10903.200.2.200.500.0.1000 |
accessViolationConsoleMINOR: Someone attempted console login with incorrect password
three times. TRAP-TYPE .1.3.6.1.4.1.674.10903.200.2.200.500.0.1001 |
accessViolationHTTPMINOR: Someone attempted login via HTTP with incorrect password. TRAP-TYPE .1.3.6.1.4.1.674.10903.200.2.200.500.0.1002 |
dellTestTrapINFORMATIONAL: Trap used to test SNMP trap functionality.
The first argument is a place holder for test variables. TRAP-TYPE .1.3.6.1.4.1.674.10903.200.2.200.500.0.1003 |
system OBJECT IDENTIFIER .1.3.6.1.4.1.674.10903.200.3 |