The CYCLADES-ACS5K-PM-MIB provides SNMP management access to the Proxy for PM (Performance Monitoring) subsystem on Cyclades ACS5000 series access servers, enabling the retrieval of performance metrics and operational status for network proxy services.
This module defines objects of the Proxy for PM
Main OID:
cyACS5KPM.1.3.6.1.4.1.2925.8.5
114
Objects
Active
Status
4
Dependencies
Imported Objects
Objects
114 total| Object Name |
|---|
cyACS5KPMThis module defines objects of the Proxy for PM MODULE-IDENTITY .1.3.6.1.4.1.2925.8.5 |
cyNumberOfPMThe total number of PM's connected on the unitro Integer32 .1.3.6.1.4.1.2925.8.5.1 |
cyPMTableAllows to read information about each connected PM SEQUENCE OF CyPMEntry .1.3.6.1.4.1.2925.8.5.2 |
cyPMEntryInformation about the connected PM CyPMEntry .1.3.6.1.4.1.2925.8.5.2.1 |
cyPMSerialPortNumberThe number of the serial port when the PM is connected.ro InterfaceIndex (IF-MIB) .1.3.6.1.4.1.2925.8.5.2.1.1 |
cyPMNumberOutletsNumber of outlets.ro Integer32 .1.3.6.1.4.1.2925.8.5.2.1.2 |
cyPMNumberUnitsTotal number of PM unists that are accessed by this serial port.ro Integer32 .1.3.6.1.4.1.2925.8.5.2.1.3 |
cyPMCurrentCurrent reading for the PM.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.2925.8.5.2.1.4 |
cyPMVersionThe software version of the PM.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.2925.8.5.2.1.5 |
cyPMCommandA character string for the user to send commands to PM. He can use it to does the save command. Or to list the outlets that need to be turned off, or turned on , or cycled or locked or unlocked as a group. The command is the first word and is followed by a space and the outlet list (otulets commands). Valid commands are 'on', 'off', 'cycle', 'lock', 'unlock', 'save'.rw DisplayString .1.3.6.1.4.1.2925.8.5.2.1.7 |
cyPMUnitTableAllow operations on specific PM unit connected SEQUENCE OF CyPMUnitEntry .1.3.6.1.4.1.2925.8.5.3 |
cyPMUnitEntryAllow operations on outlet CyPMUnitEntry .1.3.6.1.4.1.2925.8.5.3.1 |
cyPMUnitNumberThe number of the PM unit in the daisy-chained mode. InterfaceIndex (IF-MIB) .1.3.6.1.4.1.2925.8.5.3.1.1 |
cyPMUnitVersionThe software version of this PM unit.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.2925.8.5.3.1.2 |
cyPMUnitOutletsNumber of outlets of this PM unit.ro Integer32 .1.3.6.1.4.1.2925.8.5.3.1.3 |
cyPMUnitFirstOutletNumber of the first outlet of this PM unit.ro Integer32 .1.3.6.1.4.1.2925.8.5.3.1.4 |
cyPMUnitCurrentCurrent of this PM unit in AMP. The value of this object is the actual current in AMP * 10. You need to translate the readed value (Ex. : value is 5, the current is 0.5 AMP.)ro Integer32 .1.3.6.1.4.1.2925.8.5.3.1.5 |
cyPMUnitMaxCurrentMaximum current of this PM unit in AMP. The value of this object is the maximum current in AMP * 10. You need to translate the readed value (Ex. : value is 5, the maximum current is 0.5 AMP.)ro Integer32 .1.3.6.1.4.1.2925.8.5.3.1.6 |
cyPMUnitSequenceIntervalSequence interval delay. Valid values are 2 to 15 (seconds).ro Integer32 .1.3.6.1.4.1.2925.8.5.3.1.9 |
cyPMUnitCycleIntervalNumber of seconds that a socket stays off before turning it back on.ro Integer32 .1.3.6.1.4.1.2925.8.5.3.1.10 |
cyPMUnitIDPDU identification.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.2925.8.5.3.1.11 |
cyPMUnitPhasesNumber of phases of this PDU unit.ro Enumeration .1.3.6.1.4.1.2925.8.5.3.1.12 |
cyPMUnitBanksNumber of banks of this PDU unit.ro Integer32 .1.3.6.1.4.1.2925.8.5.3.1.13 |
cyPMUnitNominalVoltageNominal Voltage configured for this PDU unit, when it does not have voltage sensorro Integer32 .1.3.6.1.4.1.2925.8.5.3.1.14 |
cyPMUnitPowerPower Consumption of this PDU unit (it is estimated when PDU does not have voltage sensor).ro Integer32 .1.3.6.1.4.1.2925.8.5.3.1.15 |
cyOutletTableAllow operations on outlet SEQUENCE OF CyOutletEntry .1.3.6.1.4.1.2925.8.5.4 |
cyOutletEntryAllow operations on outlet CyOutletEntry .1.3.6.1.4.1.2925.8.5.4.1 |
cyOutletNumberThe outlet number on the PM. Zero is ALL outlets. InterfaceIndexOrZero (IF-MIB) .1.3.6.1.4.1.2925.8.5.4.1.1 |
cyOutletNameThe name given to a particular outlet Maximum size is 8 characters.rw DisplayString .1.3.6.1.4.1.2925.8.5.4.1.2 |
cyOutletServerAlias of the Server connected to this outlet .ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.2925.8.5.4.1.3 |
cyOutletPowerGetting this object will return the power state of the outlet. Valid return states are UNKNOW, OFF and ON. Setting this object will change the power state of the outlet.rw Enumeration .1.3.6.1.4.1.2925.8.5.4.1.4 |
cyOutletLockGetting this object will return the lock state of the outlet. Setting this object will change the lock state of the outlet.rw Enumeration .1.3.6.1.4.1.2925.8.5.4.1.5 |
cyOutletPUIntervalThe power unit interval of this outlet in seconds. The value of this object is the actual interval in seconds * 10. You need to translate the readed value (Ex. : value is 5, the interval is 0.5 seconds.)rw Integer32 .1.3.6.1.4.1.2925.8.5.4.1.6 |
cyOutletMinimumOnIntervalMinimum time in seconds an outlet will stay on before turning it off.ro Integer32 .1.3.6.1.4.1.2925.8.5.4.1.7 |
cyOutletMinimumOffIntervalMinimum time in seconds an outlet will stay off before turning it on.ro Integer32 .1.3.6.1.4.1.2925.8.5.4.1.8 |
cyOutletWakeupStateOutlet state after a cold boot. It can be set to on or off.ro Integer32 .1.3.6.1.4.1.2925.8.5.4.1.9 |
cyOutletPduIDPDU identification.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.2925.8.5.4.1.10 |
cyOutletPduNumberThe number of the PDU unit in the daisy-chained mode. Integer32 .1.3.6.1.4.1.2925.8.5.4.1.11 |
cyPMElecPduTableAllow operations on elecmon element of the PDUs SEQUENCE OF CyPMElecPduTableEntry .1.3.6.1.4.1.2925.8.5.5 |
cyPMElecPduTableEntryeach entry has the information about the elecmon element of the PDUs. CyPMElecPduTableEntry .1.3.6.1.4.1.2925.8.5.5.1 |
cyPMElecPduTablePortNumberSerial Port number where the PDU is connected.ro InterfaceIndex (IF-MIB) .1.3.6.1.4.1.2925.8.5.5.1.1 |
cyPMElecPduTablePduNumberThe number of the PDU unit in the daisy-chained modero InterfaceIndex (IF-MIB) .1.3.6.1.4.1.2925.8.5.5.1.2 |
cyPMElecPduTableCurrentValueActual value of current in the element (A x 10).ro Integer32 .1.3.6.1.4.1.2925.8.5.5.1.3 |
cyPMElecPduTableCurrentMaxMaximum detected value of current in the element (A x 10). Write operation accepts only 0 for reset action.rw Integer32 .1.3.6.1.4.1.2925.8.5.5.1.4 |
cyPMElecPduTablePowerValueActual value of power in the element (W x 10).ro Integer32 .1.3.6.1.4.1.2925.8.5.5.1.5 |
cyPMElecPduTablePowerMaxMaximum value of power in the element (W x 10). Write operation accepts only 0 for reset action.rw Integer32 .1.3.6.1.4.1.2925.8.5.5.1.6 |
cyPMElecPduTableVoltageValueActual value of voltage in the element (V).When element does not have voltage sensor, it returns 0.ro Integer32 .1.3.6.1.4.1.2925.8.5.5.1.7 |
cyPMElecPduTableVoltageMaxMaximum value of voltage in the element (V). When element does not have voltage sensor, it returns 0. Write operation accepts only 0 for reset action.rw Integer32 .1.3.6.1.4.1.2925.8.5.5.1.8 |
cyPMElecPduTablePowerFactorValueActual value of power factor in the element (Pf x 10). When element does not have power factor sensor, returns 0.ro Integer32 .1.3.6.1.4.1.2925.8.5.5.1.9 |
cyPMElecPduTablePowerFactorMaxMaximum value of power factor in the element (Pf x 10). When element does not have power factor sensor, returns 0. Write operation accepts only 0 for reset action.rw Integer32 .1.3.6.1.4.1.2925.8.5.5.1.10 |
cyPMElecPduTablePowerTypeThis PDU unit's Power sensor type.ro Enumeration .1.3.6.1.4.1.2925.8.5.5.1.11 |
cyPMElecPduTableVoltageTypeThis PDU unit's has voltage sensor type.ro Enumeration .1.3.6.1.4.1.2925.8.5.5.1.12 |
cyPMElecPduTablePowerFactorTypeThis PDU unit's Power Factor sensor type.ro Enumeration .1.3.6.1.4.1.2925.8.5.5.1.13 |
cyPMElecPhaseTableAllow operations on elecmon element for phases SEQUENCE OF CyPMElecPhaseTableEntry .1.3.6.1.4.1.2925.8.5.6 |
cyPMElecPhaseTableEntryeach entry has the information about the elecmon for phase. CyPMElecPhaseTableEntry .1.3.6.1.4.1.2925.8.5.6.1 |
cyPMElecPhaseTablePortNumberSerial Port number where the PDU is connected.ro InterfaceIndex (IF-MIB) .1.3.6.1.4.1.2925.8.5.6.1.1 |
cyPMElecPhaseTablePduNumberThe number of the PDU unit in the daisy-chained modero InterfaceIndex (IF-MIB) .1.3.6.1.4.1.2925.8.5.6.1.2 |
cyPMElecPhaseTableIndexindex of the phase in the PDU. Index can be 1,2 or 3.ro InterfaceIndex (IF-MIB) .1.3.6.1.4.1.2925.8.5.6.1.3 |
cyPMElecPhaseTableNameSys-name of the phase.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.2925.8.5.6.1.4 |
cyPMElecPhaseTableCurrentValueActual value of current in the phase (A x 10).ro Integer32 .1.3.6.1.4.1.2925.8.5.6.1.5 |
cyPMElecPhaseTableCurrentMaxMaximum detected value of current in the phase (A x 10). Write operation accepts only 0 for reset action.rw Integer32 .1.3.6.1.4.1.2925.8.5.6.1.6 |
cyPMElecPhaseTablePowerValueActual value of power in the phase (W x 10).ro Integer32 .1.3.6.1.4.1.2925.8.5.6.1.7 |
cyPMElecPhaseTablePowerMaxMaximum value of power in the phase (W x 10).Write operation accepts only 0 for reset action.rw Integer32 .1.3.6.1.4.1.2925.8.5.6.1.8 |
cyPMElecPhaseTableVoltageValueActual value of voltage in the phase (V).When phase does not have voltage sensor, it returns 0.ro Integer32 .1.3.6.1.4.1.2925.8.5.6.1.9 |
cyPMElecPhaseTableVoltageMaxMaximum value of voltage in the phase (V). When phase does not have voltage sensor, it returns 0. Write operation accepts only 0 for reset action.rw Integer32 .1.3.6.1.4.1.2925.8.5.6.1.10 |
cyPMElecPhaseTablePowerFactorValueActual value of power factor in the phase (Pf x 10). When phase does not have power factor sensor, returns 0.ro Integer32 .1.3.6.1.4.1.2925.8.5.6.1.11 |
cyPMElecPhaseTablePowerFactorMaxMaximum value of power factor in the phase (Pf x 10). When phase does not have power factor sensor, returns 0.Write operation accepts only 0 for reset action.rw Integer32 .1.3.6.1.4.1.2925.8.5.6.1.12 |
cyPMElecPhaseTablePowerTypeThe type of Power sensor for this elecmonro Enumeration .1.3.6.1.4.1.2925.8.5.6.1.13 |
cyPMElecPhaseTableVoltageTypeThe type of Voltage sensor for this elecmonro Enumeration .1.3.6.1.4.1.2925.8.5.6.1.14 |
cyPMElecPhaseTablePowerFactorTypeThe type of Power Factor sensor for this elecmonro Enumeration .1.3.6.1.4.1.2925.8.5.6.1.15 |
cyPMElecBankTableAllow operations on elecmon element for banks SEQUENCE OF CyPMElecBankTableEntry .1.3.6.1.4.1.2925.8.5.7 |
cyPMElecBankTableEntryeach entry has the information about the elecmon for Bank. CyPMElecBankTableEntry .1.3.6.1.4.1.2925.8.5.7.1 |
cyPMElecBankTablePortNumberSerial Port number where the PDU is connected.ro InterfaceIndex (IF-MIB) .1.3.6.1.4.1.2925.8.5.7.1.1 |
cyPMElecBankTablePduNumberThe number of the PDU unit in the daisy-chained modero InterfaceIndex (IF-MIB) .1.3.6.1.4.1.2925.8.5.7.1.2 |
cyPMElecBankTableIndexindex of the Bank in the PDU. Index can be 1,2, ... number of banks of the PDU.ro InterfaceIndex (IF-MIB) .1.3.6.1.4.1.2925.8.5.7.1.3 |
cyPMElecBankTableNameSys-name of the Bank.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.2925.8.5.7.1.4 |
cyPMElecBankTableCurrentValueActual value of current in the Bank (A x 10).ro Integer32 .1.3.6.1.4.1.2925.8.5.7.1.5 |
cyPMElecBankTableCurrentMaxMaximum detected value of current in the Bank (A x 10). Write operation accepts only 0 for reset action.rw Integer32 .1.3.6.1.4.1.2925.8.5.7.1.6 |
cyPMElecBankTablePowerValueActual value of power in the Bank (W x 10).ro Integer32 .1.3.6.1.4.1.2925.8.5.7.1.7 |
cyPMElecBankTablePowerMaxMaximum value of power in the Bank (W x 10).Write operation accepts only 0 for reset action.rw Integer32 .1.3.6.1.4.1.2925.8.5.7.1.8 |
cyPMElecBankTableVoltageValueActual value of voltage in the Bank (V).When Bank does not have voltage sensor, it returns 0.ro Integer32 .1.3.6.1.4.1.2925.8.5.7.1.9 |
cyPMElecBankTableVoltageMaxMaximum value of voltage in the Bank (V). When Bank does not have voltage sensor, it returns 0. Write operation accepts only 0 for reset action.rw Integer32 .1.3.6.1.4.1.2925.8.5.7.1.10 |
cyPMElecBankTablePowerFactorValueActual value of power factor in the Bank (Pf x 10). When Bank does not have power factor sensor, returns 0.ro Integer32 .1.3.6.1.4.1.2925.8.5.7.1.11 |
cyPMElecBankTablePowerFactorMaxMaximum value of power factor in the Bank (Pf x 10). When Bank does not have power factor sensor, returns 0.Write operation accepts only 0 for reset action.rw Integer32 .1.3.6.1.4.1.2925.8.5.7.1.12 |
cyPMElecBankTablePowerTypeThe type of Power sensor for this elecmonro Enumeration .1.3.6.1.4.1.2925.8.5.7.1.13 |
cyPMElecBankTableVoltageTypeThe type of Voltage sensor for this elecmonro Enumeration .1.3.6.1.4.1.2925.8.5.7.1.14 |
cyPMElecBankTablePowerFactorTypeThe type of Power Factor sensor for this elecmonro Enumeration .1.3.6.1.4.1.2925.8.5.7.1.15 |
cyPMElecOutletTableAllow operations on elecmon element for outlets SEQUENCE OF CyPMElecOutletTableEntry .1.3.6.1.4.1.2925.8.5.8 |
cyPMElecOutletTableEntryeach entry has the information about the elecmon for Outlet. CyPMElecOutletTableEntry .1.3.6.1.4.1.2925.8.5.8.1 |
cyPMElecOutletTablePortNumberSerial Port number where the PDU is connected.ro InterfaceIndex (IF-MIB) .1.3.6.1.4.1.2925.8.5.8.1.1 |
cyPMElecOutletTablePduNumberThe number of the PDU unit in the daisy-chained modero InterfaceIndex (IF-MIB) .1.3.6.1.4.1.2925.8.5.8.1.2 |
cyPMElecOutletTableNumberoutlet number in the PDUro InterfaceIndex (IF-MIB) .1.3.6.1.4.1.2925.8.5.8.1.3 |
cyPMElecOutletTableNamename of the Outlet.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.2925.8.5.8.1.4 |
cyPMElecOutletTableCurrentValueActual value of current in the Outlet (A x 10).ro Integer32 .1.3.6.1.4.1.2925.8.5.8.1.5 |
cyPMElecOutletTableCurrentMaxMaximum detected value of current in the Outlet (A x 10). Write operation accepts only 0 for reset action.rw Integer32 .1.3.6.1.4.1.2925.8.5.8.1.6 |
cyPMElecOutletTablePowerValueActual value of power in the Outlet (W x 10).ro Integer32 .1.3.6.1.4.1.2925.8.5.8.1.7 |
cyPMElecOutletTablePowerMaxMaximum value of power in the Outlet (W x 10).Write operation accepts only 0 for reset action.rw Integer32 .1.3.6.1.4.1.2925.8.5.8.1.8 |
cyPMElecOutletTableVoltageValueActual value of voltage in the Outlet (V).When Outlet does not have voltage sensor, it returns 0.ro Integer32 .1.3.6.1.4.1.2925.8.5.8.1.9 |
cyPMElecOutletTableVoltageMaxMaximum value of voltage in the Outlet (V). When Outlet does not have voltage sensor, it returns 0. Write operation accepts only 0 for reset action.rw Integer32 .1.3.6.1.4.1.2925.8.5.8.1.10 |
cyPMElecOutletTablePowerFactorValueActual value of power factor in the Outlet (Pf x 10). When Outlet does not have power factor sensor, returns 0.ro Integer32 .1.3.6.1.4.1.2925.8.5.8.1.11 |
cyPMElecOutletTablePowerFactorMaxMaximum value of power factor in the Outlet (Pf x 10). When Outlet does not have power factor sensor, returns 0.Write operation accepts only 0 for reset action.rw Integer32 .1.3.6.1.4.1.2925.8.5.8.1.12 |
cyPMElecOutletTablePowerTypeThe type of Power sensor for this elecmonro Enumeration .1.3.6.1.4.1.2925.8.5.8.1.13 |
cyPMElecOutletTableVoltageTypeThe type of Voltage sensor for this elecmonro Enumeration .1.3.6.1.4.1.2925.8.5.8.1.14 |
cyPMElecOutletTablePowerFactorTypeThe type of Power Factor sensor for this elecmonro Enumeration .1.3.6.1.4.1.2925.8.5.8.1.15 |
cyPMEnvMonTableAllow operations on environmental monitors SEQUENCE OF CyPMEnvMonTableEntry .1.3.6.1.4.1.2925.8.5.9 |
cyPMEnvMonTableEntryeach entry has the information about the environmental monitors. CyPMEnvMonTableEntry .1.3.6.1.4.1.2925.8.5.9.1 |
cyPMEnvMonTablePortNumberSerial Port number where the PDU is connected.ro InterfaceIndex (IF-MIB) .1.3.6.1.4.1.2925.8.5.9.1.1 |
cyPMEnvMonTablePduNumberThe number of the PDU unit in the daisy-chained modero InterfaceIndex (IF-MIB) .1.3.6.1.4.1.2925.8.5.9.1.2 |
cyPMEnvMonTableIndexindex of the environmental monitor in the PDU.ro InterfaceIndex (IF-MIB) .1.3.6.1.4.1.2925.8.5.9.1.3 |
cyPMEnvMonTableNameName of the environmental monitor.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.2925.8.5.9.1.4 |
cyPMEnvMonTableTypeThe type of environmental monitor.ro Enumeration .1.3.6.1.4.1.2925.8.5.9.1.5 |
cyPMEnvMonTableStatusThe status of Dry-Contact/Water-level/Smoke/Motion monitors. Dry-Contact sensor: Opened(1), closed(2). Water level: Normal (1), Triggered(2). Smoke sensor: not-detected(1), detected(2). Motion sensor: not-detected(1), detected(2).ro Enumeration .1.3.6.1.4.1.2925.8.5.9.1.6 |
cyPMEnvMonTableValueActual value of Temperature/Humidity/Air-flow monitors (x 10).ro Integer32 .1.3.6.1.4.1.2925.8.5.9.1.7 |
cyPMEnvMonTableMaxValueMaximum detected value of Temperature/Humidity/Air-flow monitor (x 10). Write operation accepts only 0 for reset action.rw Integer32 .1.3.6.1.4.1.2925.8.5.9.1.8 |