Home/Catalog/XPPC-MIB

XPPC-MIB

AI MIB Summary

Standard SNMP MIB module defining data structures for XPPC-MIB.

227
Objects
Active
Status
4
Dependencies

Imported Objects

Objects

227 total
Object Name
ppc
OBJECT IDENTIFIER
.1.3.6.1.4.1.935
RFC1213-MIB
Unknown
.1.3.6.1.4.1.935
communicationLostSEVERE: Communication to the UPS has been lost. Steps to reestablish communication are in progress.
TRAP-TYPE
.1.3.6.1.4.1.935.0.1
upsOverLoadSEVERE: The UPS has sensed a load greater than 100 percent of its rated capacity.
TRAP-TYPE
.1.3.6.1.4.1.935.0.2
upsDiagnosticsFailedSEVERE: The UPS failed its internal diagnostic self-test.
TRAP-TYPE
.1.3.6.1.4.1.935.0.3
upsDischargedSEVERE: The UPS just started a runtime calibration discharge. The UPS batteries are being discharged.
TRAP-TYPE
.1.3.6.1.4.1.935.0.4
upsOnBatteryWARNING: The UPS has switched to battery backup power.
TRAP-TYPE
.1.3.6.1.4.1.935.0.5
boostOnWARNING: The UPS has enabled Boost.
TRAP-TYPE
.1.3.6.1.4.1.935.0.6
lowBatterySEVERE: The UPS batteries are low and will soon be exhausted. If utility power is not restored the UPS will put itself to 'sleep' and immediately cut power to the load.
TRAP-TYPE
.1.3.6.1.4.1.935.0.7
communicationEstablishedINFORMATION: Communication with the UPS has been established.
TRAP-TYPE
.1.3.6.1.4.1.935.0.8
powerRestoredINFORMATION: Utility power has been restored.
TRAP-TYPE
.1.3.6.1.4.1.935.0.9
upsDiagnosticsPassedINFORMATION: The UPS passed its internal self-test.
TRAP-TYPE
.1.3.6.1.4.1.935.0.10
returnFromLowBatteryINFORMATION: The UPS has returned from a low battery condition.
TRAP-TYPE
.1.3.6.1.4.1.935.0.11
upsTurnedOffWARNING: The UPS has been turned 'off' by the management station.
TRAP-TYPE
.1.3.6.1.4.1.935.0.12
upsSleepingWARNING: The UPS is entering 'sleep' mode. Power to the load will be cut off.
TRAP-TYPE
.1.3.6.1.4.1.935.0.13
upsWokeUpINFORMATION: The UPS woke up from 'sleep' mode. Power to the load has been restored.
TRAP-TYPE
.1.3.6.1.4.1.935.0.14
upsRebootStartedWARNING: The UPS has started its reboot sequence. After the specified delay the UPS will perform a reboot.
TRAP-TYPE
.1.3.6.1.4.1.935.0.15
envOverTemperatureWARNING: The environment temperature exceed the normal value.
TRAP-TYPE
.1.3.6.1.4.1.935.0.16
envTemperatureNormalINFORMATION: The environment temperature is normal.
TRAP-TYPE
.1.3.6.1.4.1.935.0.17
envOverHumidityWARNING: The environment humidity exceed the normal value.
TRAP-TYPE
.1.3.6.1.4.1.935.0.18
envHumidityNormalINFORMATION: The environment humidity is normal.
TRAP-TYPE
.1.3.6.1.4.1.935.0.19
envSmokeAbnormalWARNING: Smoke is abnormal.
TRAP-TYPE
.1.3.6.1.4.1.935.0.20
envWaterAbnormalWARNING: Water is abnormal.
TRAP-TYPE
.1.3.6.1.4.1.935.0.21
envSecurityAbnormalWARNING: Security is abnormal.
TRAP-TYPE
.1.3.6.1.4.1.935.0.22
envWaterNormalINFORMATION: Water is normal.
TRAP-TYPE
.1.3.6.1.4.1.935.0.24
envGasAbnormalWARNING: Gas Alarm
TRAP-TYPE
.1.3.6.1.4.1.935.0.26
upsTempWARNING: UPS Temperature Overrun
TRAP-TYPE
.1.3.6.1.4.1.935.0.27
upsLoadNormalWARNING: UPS Load Normal
TRAP-TYPE
.1.3.6.1.4.1.935.0.28
upsTempNormalWARNING: UPS temperature Normal
TRAP-TYPE
.1.3.6.1.4.1.935.0.29
envUnderTemperatureWARNING: The environment temperature below the normal value.
TRAP-TYPE
.1.3.6.1.4.1.935.0.30
envUnderHumidityWARNING: The environment humidity below the normal value.
TRAP-TYPE
.1.3.6.1.4.1.935.0.31
upsBypassWARNING: The UPS is entering 'bypass' mode.
TRAP-TYPE
.1.3.6.1.4.1.935.0.32
envSecurity1WARNING: Security1 Alarm.
TRAP-TYPE
.1.3.6.1.4.1.935.0.33
envSecurity2WARNING: Security2 Alarm.
TRAP-TYPE
.1.3.6.1.4.1.935.0.34
envSecurity3WARNING: Security3 Alarm.
TRAP-TYPE
.1.3.6.1.4.1.935.0.35
envSecurity4WARNING: Security4 Alarm.
TRAP-TYPE
.1.3.6.1.4.1.935.0.36
envSecurity5WARNING: Security5 Alarm.
TRAP-TYPE
.1.3.6.1.4.1.935.0.37
envSecurity6WARNING: Security6 Alarm.
TRAP-TYPE
.1.3.6.1.4.1.935.0.38
envSecurity7WARNING: Security7 Alarm.
TRAP-TYPE
.1.3.6.1.4.1.935.0.39
upsRecroterrorWARNING: Rectifier Rotation Error
TRAP-TYPE
.1.3.6.1.4.1.935.0.47
upsBypassFreFailWARNING: Bypass Frequency Fail
TRAP-TYPE
.1.3.6.1.4.1.935.0.48
upsBypassacnormalWARNING: Bypass AC Normal
TRAP-TYPE
.1.3.6.1.4.1.935.0.49
upsBypassacabnormalWARNING: Bypass AC Abnormal
TRAP-TYPE
.1.3.6.1.4.1.935.0.50
upsTestWARNING: UPS Test
TRAP-TYPE
.1.3.6.1.4.1.935.0.51
upsScheduleShutdownWARNING: UPS Schedule Shutdown
TRAP-TYPE
.1.3.6.1.4.1.935.0.52
upsBypassReturnThe UPS return from Bypass Mode
TRAP-TYPE
.1.3.6.1.4.1.935.0.53
upsShortCircuitShutdownThe UPS Short Circuit Shutdown
TRAP-TYPE
.1.3.6.1.4.1.935.0.54
upsInverterOutputFailShutdownThe UPS Inverter Output Fail Shutdown
TRAP-TYPE
.1.3.6.1.4.1.935.0.55
upsBypassBreadkerOnShutdownThe UPS Manual Bypass Breaker on Shutdown
TRAP-TYPE
.1.3.6.1.4.1.935.0.56
upsHighDCShutdownThe UPS High DC Shutdown
TRAP-TYPE
.1.3.6.1.4.1.935.0.57
upsEmergencyStopThe UPS Emergency Stop
TRAP-TYPE
.1.3.6.1.4.1.935.0.58
upsInverterModeThe UPS Static Switch in Inverter Mode
TRAP-TYPE
.1.3.6.1.4.1.935.0.59
upsBypassModeThe UPS Static Switch in Bypass Mode
TRAP-TYPE
.1.3.6.1.4.1.935.0.60
upsOverTemperatureShutdownThe UPS Over Temperature Shutdown
TRAP-TYPE
.1.3.6.1.4.1.935.0.61
upsOverLoadShutdownThe UPS Overload Shutdown
TRAP-TYPE
.1.3.6.1.4.1.935.0.62
upsCapacityUnderrunThe UPS Capacity Underrun
TRAP-TYPE
.1.3.6.1.4.1.935.0.63
upsCapacityNormalThe UPS Capacity Normal
TRAP-TYPE
.1.3.6.1.4.1.935.0.64
upsLowBatteryShutdownThe UPS Low Battery Shutdown
TRAP-TYPE
.1.3.6.1.4.1.935.0.67
products
OBJECT IDENTIFIER
.1.3.6.1.4.1.935.1
hardware
OBJECT IDENTIFIER
.1.3.6.1.4.1.935.1.1
ups
OBJECT IDENTIFIER
.1.3.6.1.4.1.935.1.1.1
upsIdentp
OBJECT IDENTIFIER
.1.3.6.1.4.1.935.1.1.1.1
upsBaseIdent
OBJECT IDENTIFIER
.1.3.6.1.4.1.935.1.1.1.1.1
upsBaseIdentModelThe UPS model name (e.g. 'Intelligent 8000E 900VA').ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.935.1.1.1.1.1.1
upsBaseIdentUpsNameAn 8 byte ID string identifying the UPS. This object can be set by the administrator.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.935.1.1.1.1.1.2
upsSmartIdent
OBJECT IDENTIFIER
.1.3.6.1.4.1.935.1.1.1.1.2
upsSmartIdentFirmwareRevisionThe firmware revision of the UPS system.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.935.1.1.1.1.2.1
upsSmartIdentDateOfManufactureThe date when the UPS was manufactured in mm/dd/yy format.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.935.1.1.1.1.2.2
upsSmartIdentUpsSerialNumberAn 8-character string identifying the serial number of the UPS internal microprocessor. This number is set at the factory. NOTE: This number does NOT correspond to the serial number on the rear of the UPS.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.935.1.1.1.1.2.3
upsSmartIdentAgentFirmwareRevisionThe firmware revision of the UPS SNMP Proxy agent.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.935.1.1.1.1.2.4
upsBatteryp
OBJECT IDENTIFIER
.1.3.6.1.4.1.935.1.1.1.2
upsBaseBattery
OBJECT IDENTIFIER
.1.3.6.1.4.1.935.1.1.1.2.1
upsBaseBatteryStatusThe status of the UPS batteries. A batteryLow(3) value indicates the UPS will be unable to sustain the current load, and its services will be lost if power is not restored. The amount of run time in reserve at the time of low battery can be configured by the upsSmartConfigLowBatteryRunTime.ro
Enumeration
.1.3.6.1.4.1.935.1.1.1.2.1.1
upsBaseBatteryTimeOnBatteryThe elapsed time in seconds since the UPS has switched to battery power.ro
INTEGER
.1.3.6.1.4.1.935.1.1.1.2.1.2
upsBaseBatteryLastReplaceDateThe date when the UPS system's batteries were last replaced in mm/dd/yy format. For UPS models, this value is originally set in the factory. When the UPS batteries are replaced, this value should be reset by the administrator.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.935.1.1.1.2.1.3
upsSmartBattery
OBJECT IDENTIFIER
.1.3.6.1.4.1.935.1.1.1.2.2
upsSmartBatteryCapacityThe remaining battery capacity expressed in percent of full capacity.ro
INTEGER
.1.3.6.1.4.1.935.1.1.1.2.2.1
upsSmartBatteryVoltageThe current battery voltage expressed in 1/10 VDC.ro
INTEGER
.1.3.6.1.4.1.935.1.1.1.2.2.2
upsSmartBatteryTemperatureThe current internal UPS temperature expressed in tenths of a Celsius degree.ro
INTEGER
.1.3.6.1.4.1.935.1.1.1.2.2.3
upsSmartBatteryRunTimeRemainingThe UPS battery run time remaining before battery exhaustion, in seconds.ro
INTEGER
.1.3.6.1.4.1.935.1.1.1.2.2.4
upsSmartBatteryReplaceIndicatorIndicates whether the UPS batteries need replacing.ro
Enumeration
.1.3.6.1.4.1.935.1.1.1.2.2.5
upsSmartBatteryFullChargeVoltageThe fully charged battery voltage of the battery system used in the UPS, expressed in tenths of a volt.ro
INTEGER
.1.3.6.1.4.1.935.1.1.1.2.2.6
upsSmartBatteryCurrentThe current battery current expressed in percent of maximum current.ro
INTEGER
.1.3.6.1.4.1.935.1.1.1.2.2.7
upsInputp
OBJECT IDENTIFIER
.1.3.6.1.4.1.935.1.1.1.3
upsBaseInput
OBJECT IDENTIFIER
.1.3.6.1.4.1.935.1.1.1.3.1
upsBaseInputPhaseThe current AC input phase.ro
INTEGER
.1.3.6.1.4.1.935.1.1.1.3.1.1
upsSmartInput
OBJECT IDENTIFIER
.1.3.6.1.4.1.935.1.1.1.3.2
upsSmartInputLineVoltageThe current utility line voltage in 1/10 VAC.ro
INTEGER
.1.3.6.1.4.1.935.1.1.1.3.2.1
upsSmartInputMaxLineVoltageThe maximum utility line voltage in 1/10 VAC over the previous 1 minute period.ro
INTEGER
.1.3.6.1.4.1.935.1.1.1.3.2.2
upsSmartInputMinLineVoltageThe minimum utility line voltage in 1/10 VAC over the previous 1 minute period.ro
INTEGER
.1.3.6.1.4.1.935.1.1.1.3.2.3
upsSmartInputFrequencyThe current input frequency to the UPS system in 1/10 Hz.ro
INTEGER
.1.3.6.1.4.1.935.1.1.1.3.2.4
upsSmartInputLineFailCauseThe reason for the occurrence of the last transfer to UPS battery power. The variable is set to noTransfer(1) if there is no transfer yet. The variable is set to highLineVoltage(2) if the transfer to battery is caused by an over voltage greater than the high transfer voltage. The variable is set to brownout(3) if the duration of the outage is greater than five seconds and the line voltage is between 40 percent of the rated output voltage and the low transfer voltage. The variable is set to blackout(4) if the duration of the outage is greater than five seconds and the line voltage is between 40 percent of the rated output voltage and ground. The variable is set to smallMomentarySag(5) if the duration of the outage is less than five seconds and the line voltage is between 40 percent of the rated output voltage and the low transfer voltage. The variable is set to deepMomentarySag(6) if the duration of the outage is less than five seconds and the line voltage is between 40 percent of the rated output voltage and ground.ro
Enumeration
.1.3.6.1.4.1.935.1.1.1.3.2.5
upsOutputp
OBJECT IDENTIFIER
.1.3.6.1.4.1.935.1.1.1.4
upsBaseOutput
OBJECT IDENTIFIER
.1.3.6.1.4.1.935.1.1.1.4.1
upsBaseOutputStatusThe current state of the UPS. If the UPS is unable to determine the state of the UPS this variable is set to unknown(1).ro
Enumeration
.1.3.6.1.4.1.935.1.1.1.4.1.1
upsBaseOutputPhaseThe current output phase.ro
INTEGER
.1.3.6.1.4.1.935.1.1.1.4.1.2
upsSmartOutput
OBJECT IDENTIFIER
.1.3.6.1.4.1.935.1.1.1.4.2
upsSmartOutputVoltageThe output voltage of the UPS system in 1/10 VAC.ro
INTEGER
.1.3.6.1.4.1.935.1.1.1.4.2.1
upsSmartOutputFrequencyThe current output frequency of the UPS system in 1/10 Hz.ro
INTEGER
.1.3.6.1.4.1.935.1.1.1.4.2.2
upsSmartOutputLoadThe current UPS load expressed in percent of rated capacity.ro
INTEGER
.1.3.6.1.4.1.935.1.1.1.4.2.3
upsConfigp
OBJECT IDENTIFIER
.1.3.6.1.4.1.935.1.1.1.5
upsBaseConfig
OBJECT IDENTIFIER
.1.3.6.1.4.1.935.1.1.1.5.1
upsBaseConfigNumDevicesThe number of devices that are plugged into the UPS.ro
INTEGER
.1.3.6.1.4.1.935.1.1.1.5.1.1
upsBaseConfigDeviceTableA list of devices that are plugged into the UPS. The number of entries is given by the value of upsBaseConfigNumDevices.
SEQUENCE OF UpsBaseConfigDeviceEntry
.1.3.6.1.4.1.935.1.1.1.5.1.2
upsBaseConfigDeviceEntryThe devices plugged in to the UPS.
UpsBaseConfigDeviceEntry
.1.3.6.1.4.1.935.1.1.1.5.1.2.1
indexOfDeviceThe index of the device that is plugged into the UPS.ro
INTEGER
.1.3.6.1.4.1.935.1.1.1.5.1.2.1.1
nameOfDeviceThe name/description of the device plugged into the UPS.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.935.1.1.1.5.1.2.1.2
vaRatingOfDeviceThe volt-amp rating of the device plugged into the UPS.rw
INTEGER
.1.3.6.1.4.1.935.1.1.1.5.1.2.1.3
deviceAcceptAn entry is added if yes, the entry is deleted if no.rw
Enumeration
.1.3.6.1.4.1.935.1.1.1.5.1.2.1.4
upsSmartConfig
OBJECT IDENTIFIER
.1.3.6.1.4.1.935.1.1.1.5.2
upsSmartConfigRatedOutputVoltageThe nominal output voltage from the UPS in 1/10 VAC. Possible values are 1000, 1200, 2080, 2200, 2250, 2300 and 2400. NOTE: Only units that are 2200, 2250, 2300 and 2400 can be changed. Allowable values are 2200, 2250, 2300 and 2400. For these adjustable units, if a value other than a supported value is provided in a set request, the UPS interprets it as the next lower acceptable value. If the provided value is lower than the lowest acceptable value, the lowest acceptable value is used.rw
INTEGER
.1.3.6.1.4.1.935.1.1.1.5.2.1
upsSmartConfigHighTransferVoltThe maximum line voltage in 1/10 VAC allowed before the UPS system transfers to battery backup. Allowed value depend on the UPS used: 120 Volt units allow settings of 1290, 1320, 1350, 1380. 100 Volt units allow settings of 1080, 1100, 1120, 1140. 230 Volt units allow settings of 2530, 2640, 2710, 2800. 208 Volt units allow settings of 2240, 2290, 2340, 2390. If a value other than a supported value is provided in a set request, the UPS interprets it as the next lower acceptable value. If the provided value is lower than the lowest acceptable value, the lowest acceptable value is used.rw
INTEGER
.1.3.6.1.4.1.935.1.1.1.5.2.2
upsSmartConfigLowTransferVoltThe minimum line voltage in 1/10 VAC allowed before the UPS system transfers to battery backup. Allowable values depend on the UPS used: 120 Volt units allow settings of 970, 1000, 1030, 1060. 100 Volt units allow settings of 810, 830, 850, 870. 230 Volt units allow settings of 1880, 1960, 2040, 2080. 208 Volt units allow settings of 1680, 1720, 1770, 1820. If a value other than a supported value is provided in a set request, the UPS interprets it as a the next higher acceptable value. If the provided value is higher than the highest acceptable value, the highest acceptable value is used.rw
INTEGER
.1.3.6.1.4.1.935.1.1.1.5.2.3
upsSmartConfigAlarmA flag indicating how the UPS should handle audible line fail alarms.rw
Enumeration
.1.3.6.1.4.1.935.1.1.1.5.2.4
upsSmartConfigAlarmTimerThe time in seconds after initial line failure at which the UPS begins emitting audible alarms (beeping). This timer is observerd only if the value of extControlAlarm is timed(2). Allowed values are 0 or 30 seconds. If a value other than a supported value is provided in a set request, the UPS interprets it as a the next lower acceptable value. If the provided value is lower than the lowest acceptable value, the lowest acceptable value is used.rw
INTEGER
.1.3.6.1.4.1.935.1.1.1.5.2.5
upsSmartConfigMinReturnCapacityThe minimum battery capacity as a percent of full capacity required before the UPS will return from a low battery shutdown condition. In other words, the UPS will not re-energize the output until the battery capacity is equal to this value. Allowed values are 0, 10, 25, or 90 percent. If a value other than a supported value is provided in a set request, the UPS interprets it as a the next higher acceptable value. If the provided value is higher than the highest acceptable value, the highest acceptable value is used.rw
INTEGER
.1.3.6.1.4.1.935.1.1.1.5.2.6
upsSmartConfigSensitivityThe sensitivity of the UPS to utility line abnormalities or noises.rw
Enumeration
.1.3.6.1.4.1.935.1.1.1.5.2.7
upsSmartConfigLowBatteryRunTimeThe desired run time in seconds once the low battery condition is reached. Allowed values are 120, 300, 420, or 600 seconds. During this time the UPS will produce a constant warning tone which can not be disabled. If a value other than a supported value is provided in a set request, the UPS interprets it as a the next higher acceptable value. If the provided value is higher than the highest acceptable value, the highest acceptable value is used.rw
INTEGER
.1.3.6.1.4.1.935.1.1.1.5.2.8
upsSmartConfigReturnDelayThe delay in seconds after utility line power returns before the UPS will turn on. This value is also used when the UPS comes out of a reboot and before the UPS wakes up from 'sleep' mode. Allowed values are 0, 60, 180 and 300 seconds. If a value other than a supported value is provided in a set request, the UPS interprets it as a the next higher acceptable value. If the provided value is higher than the highest acceptable value, the highest acceptable value is used.rw
INTEGER
.1.3.6.1.4.1.935.1.1.1.5.2.9
upsSmartConfigShutoffDelayThe delay in seconds the UPS remains on after being told to turn off. Allowed values are 12, 18, 24, 30, 36, 42, 48, 54, 60, 120, 180, 240, 300, 360, 420, 480, 540, and 600 seconds. If a value other than a supported value is provided in a set request, the UPS interprets it as next higher acceptable value. If the provided value is higher than the highest acceptable value, the highest acceptable value is used.rw
INTEGER
.1.3.6.1.4.1.935.1.1.1.5.2.10
upsSmartConfigUpsSleepTimeThe time in minutes for the UPS to go to 'sleep' when instructed. When in sleep mode, the UPS will not provide output power regardless of the input line state. Once the specified time has elapsed, output power will be restored. This is a configuration setting. The UPS will not go to sleep until told to do so by the manager from a management station. Any input value is allowed, however the UPS only recognizes 0 - 9999 minutes in one minute increments. If the provided value is higher than the highest acceptable value, the highest acceptable value is used.rw
INTEGER
.1.3.6.1.4.1.935.1.1.1.5.2.11
upsSmartConfigSetEEPROMDefaultsWRITE: Resets the UPS EEPROM variables to default values. READ: returns 0rw
Enumeration
.1.3.6.1.4.1.935.1.1.1.5.2.12
upsControlp
OBJECT IDENTIFIER
.1.3.6.1.4.1.935.1.1.1.6
upsBaseControl
OBJECT IDENTIFIER
.1.3.6.1.4.1.935.1.1.1.6.1
upsBaseControlConserveBatterySetting this variable to turnUpsOffToConserveBattery(2) causes a UPS on battery to be put into 'sleep' mode immediately. The (10) means suspending time(10 minutes) before turn off UPS. UPS will turn back on when utility power is restored. Attempting to turn off a UPS that is not on battery will result in a badValue error. Setting this value to noTurnOffUps(1) has no effect. The value noTurnOffUps(1) will always be returned when the variable is read.rw
Enumeration
.1.3.6.1.4.1.935.1.1.1.6.1.1
upsSmartControl
OBJECT IDENTIFIER
.1.3.6.1.4.1.935.1.1.1.6.2
upsSmartControlUpsOffSetting this variable to turnUpsOff(2) causes the UPS to shut off. When in this state, the UPS will not provide output power regardless of the input line state. The on/off switch on the UPS must be toggled for the UPS to return to operation. Setting this value to noTurnUpsOff(1) has no effect. The value noTurnUpsOff(1) will always be returned when the variable is read.rw
Enumeration
.1.3.6.1.4.1.935.1.1.1.6.2.1
upsSmartControlRebootUpsSetting this variable to rebootUps(2) causes the UPS to shut off and turn back on. Setting this value to noRebootUps(1) has no effect. The value noRebootUps(1) will always be returned when the variable is read.rw
Enumeration
.1.3.6.1.4.1.935.1.1.1.6.2.2
upsSmartControlUpsSleepSetting this variable to putUpsToSleep(2) causes the UPS to go to sleep for the time specified by upsSmartConfigUpsSleepTime. When in sleep mode, the UPS will not provide output power regardless of the input line state. Once the specified time has elapsed, output power will be restored. Setting this value to noPutUpsToSleep(1) has no effect. The value noPutUpsToSleep(1) will always be returned when the variable is read.rw
Enumeration
.1.3.6.1.4.1.935.1.1.1.6.2.3
upsSmartControlSimulatePowerFailSetting this variable to simulatePowerFailure(2) causes the UPS switch to battery power. Setting this value to noSimulatePowerFailure(1) has no effect. The value noSimulatePowerFailure(1) will always be returned when the variable is read.rw
Enumeration
.1.3.6.1.4.1.935.1.1.1.6.2.4
upsSmartControlFlashAndBeepUPS to identify itself by lighting all indicators and beeping. Setting this variable to FlashAndBeep(2) causes the UPS lights all panel indicators and beeps. Setting this value to noFlashAndBeep(1) has no effect. The value noFlashAndBeep(1) will always be returned when the variable is read.rw
Enumeration
.1.3.6.1.4.1.935.1.1.1.6.2.5
upsSmartControlTurnOnUpsLoadSetting this variable to upsSmartControlTurnOnUpsLoad(2) causes the UPS switch back to utility power if utility power is present. Setting this value to noUpsSmartControlTurnOnUpsLoad(1) has no effect. The value noUpsSmartControlTurnOnUpsLoad(1) will always be returned when the variable is read.rw
Enumeration
.1.3.6.1.4.1.935.1.1.1.6.2.6
upsTestp
OBJECT IDENTIFIER
.1.3.6.1.4.1.935.1.1.1.7
upsBaseTest
OBJECT IDENTIFIER
.1.3.6.1.4.1.935.1.1.1.7.1
upsSmartTest
OBJECT IDENTIFIER
.1.3.6.1.4.1.935.1.1.1.7.2
upsSmartTestDiagnosticScheduleThe UPS system's automatic battery test schedule.rw
Enumeration
.1.3.6.1.4.1.935.1.1.1.7.2.1
upsSmartTestDiagnosticsSetting this variable to testDiagnostics(2) causes the UPS to perform a diagnostic self test. Setting this value to noTestDiagnostics(1) has no effect. The value noTestDiagnostics(1) will always be returned when the variable is read.rw
Enumeration
.1.3.6.1.4.1.935.1.1.1.7.2.2
upsSmartTestDiagnosticsResultsThe results of the last UPS diagnostics test performed.ro
Enumeration
.1.3.6.1.4.1.935.1.1.1.7.2.3
upsSmartTestLastDiagnosticsDateThe date the last UPS diagnostics test was performed in mm/dd/yy format.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.935.1.1.1.7.2.4
upsSmartTestIndicatorsSetting this variable to testIndicators(2) causes the UPS to perform a front panel indicator (lights) test. Setting this value to noTestIndicators(1) has no effect. The value noTestIndicators(1) will always be returned when the variable is read.rw
Enumeration
.1.3.6.1.4.1.935.1.1.1.7.2.5
upsSmartTestRuntimeCalibrationSetting this variable to performCalibration(2) causes the UPS to discharge to calibrate the UPS. The test will only start if the battery capacity is 100 percent. The test runs until capacity is less than 25 percent. Setting this variable to cancelCurrentCalibration(3) after setting performCalibration(2) will cancel the current discharge. Setting this variable to noPerformCalibration(1) will have no effect. The value noPerformCalibration(1) will always be returned when the variable is read. The result of the calibration will be saved in upsSmartTestCalibrationResult.rw
Enumeration
.1.3.6.1.4.1.935.1.1.1.7.2.6
upsSmartTestCalibrationResultsThe results of the last runtime calibration. Value ok(1) means a successful runtime calibration. Value invalidTest(2) indicates last calibration did not take place since the battery capacity was below 100 percent. Value calibrationInProgress(3) means a calibration is occurring now.ro
Enumeration
.1.3.6.1.4.1.935.1.1.1.7.2.7
upsSmartTestCalibrationDateThe date the last UPS runtime calibration was performed in mm/dd/yy format.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.935.1.1.1.7.2.8
upsThreePhase
OBJECT IDENTIFIER
.1.3.6.1.4.1.935.1.1.1.8
upsThreePhaseBatteryGrp
OBJECT IDENTIFIER
.1.3.6.1.4.1.935.1.1.1.8.1
upsThreePhaseBatteryVoltageBattery Voltagero
INTEGER
.1.3.6.1.4.1.935.1.1.1.8.1.1
upsThreePhaseBatteryCapacityPercentageBattery Capacity Percentagero
INTEGER
.1.3.6.1.4.1.935.1.1.1.8.1.2
upsThreePhaseBatteryTimeRemainBattery Time Remain (unit is Minute)ro
INTEGER
.1.3.6.1.4.1.935.1.1.1.8.1.3
upsThreePhaseBatteryCurrentBattery Electric Currentro
INTEGER
.1.3.6.1.4.1.935.1.1.1.8.1.4
upsThreePhaseBatteryTemperatureBattery Temperaturero
INTEGER
.1.3.6.1.4.1.935.1.1.1.8.1.5
upsThreePhaseInputGrp
OBJECT IDENTIFIER
.1.3.6.1.4.1.935.1.1.1.8.2
upsThreePhaseInputFrequencyInput Frequencyro
INTEGER
.1.3.6.1.4.1.935.1.1.1.8.2.1
upsThreePhaseInputVoltageRInput VoltageRro
INTEGER
.1.3.6.1.4.1.935.1.1.1.8.2.2
upsThreePhaseInputVoltageSInput VoltageSro
INTEGER
.1.3.6.1.4.1.935.1.1.1.8.2.3
upsThreePhaseInputVoltageTInput VoltageTro
INTEGER
.1.3.6.1.4.1.935.1.1.1.8.2.4
upsThreePhaseOutputGrp
OBJECT IDENTIFIER
.1.3.6.1.4.1.935.1.1.1.8.3
upsThreePhaseOutputFrequencyOutput Frequencyro
INTEGER
.1.3.6.1.4.1.935.1.1.1.8.3.1
upsThreePhaseOutputVoltageROutput VoltageRro
INTEGER
.1.3.6.1.4.1.935.1.1.1.8.3.2
upsThreePhaseOutputVoltageSOutput VoltageSro
INTEGER
.1.3.6.1.4.1.935.1.1.1.8.3.3
upsThreePhaseOutputVoltageTOutput VoltageTro
INTEGER
.1.3.6.1.4.1.935.1.1.1.8.3.4
upsThreePhaseOutputLoadPercentageRLoad PercentageRro
INTEGER
.1.3.6.1.4.1.935.1.1.1.8.3.5
upsThreePhaseOutputLoadPercentageSLoad PercentageSro
INTEGER
.1.3.6.1.4.1.935.1.1.1.8.3.6
upsThreePhaseOutputLoadPercentageTLoad PercentageTro
INTEGER
.1.3.6.1.4.1.935.1.1.1.8.3.7
upsThreePhaseBypassGrp
OBJECT IDENTIFIER
.1.3.6.1.4.1.935.1.1.1.8.4
upsThreePhaseBypassSourceFrequencyBypass Frequencyro
INTEGER
.1.3.6.1.4.1.935.1.1.1.8.4.1
upsThreePhaseBypssSourceVoltageRBypass VoltageRro
INTEGER
.1.3.6.1.4.1.935.1.1.1.8.4.2
upsThreePhaseBypssSourceVoltageSBypass VoltageSro
INTEGER
.1.3.6.1.4.1.935.1.1.1.8.4.3
upsThreePhaseBypssSourceVoltageTBypass VoltageTro
INTEGER
.1.3.6.1.4.1.935.1.1.1.8.4.4
upsThreePhaseDCandRectifierStatusGrp
OBJECT IDENTIFIER
.1.3.6.1.4.1.935.1.1.1.8.5
upsThreePhaseDCandRectifierStatusRecRotErrorRectifier Rotation Errorro
Enumeration
.1.3.6.1.4.1.935.1.1.1.8.5.1
upsThreePhaseDCandRectifierStatusLowBatteryShutdownLow Battery Shutdownro
Enumeration
.1.3.6.1.4.1.935.1.1.1.8.5.2
upsThreePhaseDCandRectifierStatusLowBatteryLow Batteryro
Enumeration
.1.3.6.1.4.1.935.1.1.1.8.5.3
upsThreePhaseDCandRectifierStatusInAndOutIn And Putro
Enumeration
.1.3.6.1.4.1.935.1.1.1.8.5.4
upsThreePhaseDCandRectifierStatusBatteryStatusBack Statusro
Enumeration
.1.3.6.1.4.1.935.1.1.1.8.5.5
upsThreePhaseDCandRectifierStatusChargeStatusCharge Statusro
Enumeration
.1.3.6.1.4.1.935.1.1.1.8.5.6
upsThreePhaseDCandRectifierStatusRecOperatingRectifier Operatingro
Enumeration
.1.3.6.1.4.1.935.1.1.1.8.5.7
upsThreePhaseUPSStatusGrp
OBJECT IDENTIFIER
.1.3.6.1.4.1.935.1.1.1.8.6
upsThreePhaseUPSStatusBypassFreqFailBypass Statusro
Enumeration
.1.3.6.1.4.1.935.1.1.1.8.6.1
upsThreePhaseUPSStatusManualBypassBreakerBreaker Statusro
Enumeration
.1.3.6.1.4.1.935.1.1.1.8.6.2
upsThreePhaseUPSStatusACStatusAC Statusro
Enumeration
.1.3.6.1.4.1.935.1.1.1.8.6.3
upsThreePhaseUPSStaticSwitchModeSwitch Modero
Enumeration
.1.3.6.1.4.1.935.1.1.1.8.6.4
upsThreePhaseUPSStatusInverterOperatingOperatingro
Enumeration
.1.3.6.1.4.1.935.1.1.1.8.6.5
upsThreePhaseFaultStatusGrp
OBJECT IDENTIFIER
.1.3.6.1.4.1.935.1.1.1.8.7
upsThreePhaseFaultStatusEmergencyStopEmergency Stopro
Enumeration
.1.3.6.1.4.1.935.1.1.1.8.7.1
upsThreePhaseFaultStatusHighDCShutdownHigh DC Shutdownro
Enumeration
.1.3.6.1.4.1.935.1.1.1.8.7.2
upsThreePhaseFaultStatusBypassBreakerBypass Breakerro
Enumeration
.1.3.6.1.4.1.935.1.1.1.8.7.3
upsThreePhaseFaultStatusOverLoadOver Loadro
Enumeration
.1.3.6.1.4.1.935.1.1.1.8.7.4
upsThreePhaseFaultStatusInverterOutputFailOutput Failro
Enumeration
.1.3.6.1.4.1.935.1.1.1.8.7.5
upsThreePhaseFaultStatusOverTemperatureOver Temperaturero
Enumeration
.1.3.6.1.4.1.935.1.1.1.8.7.6
upsThreePhaseFaultStatusShortCircuitShort Circuitro
Enumeration
.1.3.6.1.4.1.935.1.1.1.8.7.7
upsThreePhaseRatingGrp
OBJECT IDENTIFIER
.1.3.6.1.4.1.935.1.1.1.8.8
upsThreePhaseRatingRectifierVoltageRectifier Voltagero
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.935.1.1.1.8.8.1
upsThreePhaseRatingRectifierFrequencyRectifier Frequencyro
INTEGER
.1.3.6.1.4.1.935.1.1.1.8.8.2
upsThreePhaseRatingBypassVoltageBypass Voltagero
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.935.1.1.1.8.8.3
upsThreePhaseRatingBypassFrequencyBypass Frequencyro
INTEGER
.1.3.6.1.4.1.935.1.1.1.8.8.4
upsThreePhaseRatingOutputVoltageOutput Voltagero
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.935.1.1.1.8.8.5
upsThreePhaseRatingOutputFrequencyOutput Frequencyro
INTEGER
.1.3.6.1.4.1.935.1.1.1.8.8.6
upsThreePhaseRatingBatteryVoltageBattery Voltagero
INTEGER
.1.3.6.1.4.1.935.1.1.1.8.8.7
upsThreePhaseRatingPowerPower Ratingro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.935.1.1.1.8.8.8
upsEnvironment
OBJECT IDENTIFIER
.1.3.6.1.4.1.935.1.1.1.9
upsEnvStatus
OBJECT IDENTIFIER
.1.3.6.1.4.1.935.1.1.1.9.1
upsEnvTemperatureThe ambient environment temperature.ro
INTEGER
.1.3.6.1.4.1.935.1.1.1.9.1.1
upsEnvHumidityThe environment humidity.ro
INTEGER
.1.3.6.1.4.1.935.1.1.1.9.1.2
upsEnvWaterWater statusro
Enumeration
.1.3.6.1.4.1.935.1.1.1.9.1.3
upsEnvSmokeSmoke statusro
Enumeration
.1.3.6.1.4.1.935.1.1.1.9.1.4
upsEnvSecurity1Security statusro
Enumeration
.1.3.6.1.4.1.935.1.1.1.9.1.5
upsEnvSecurity2Security statusro
Enumeration
.1.3.6.1.4.1.935.1.1.1.9.1.6
upsEnvSecurity3Security statusro
Enumeration
.1.3.6.1.4.1.935.1.1.1.9.1.7
upsEnvSecurity4Security statusro
Enumeration
.1.3.6.1.4.1.935.1.1.1.9.1.8
upsEnvSecurity5Security statusro
Enumeration
.1.3.6.1.4.1.935.1.1.1.9.1.9
upsEnvSecurity6Security statusro
Enumeration
.1.3.6.1.4.1.935.1.1.1.9.1.10
upsEnvSecurity7Security statusro
Enumeration
.1.3.6.1.4.1.935.1.1.1.9.1.11
upsEnvSetting
OBJECT IDENTIFIER
.1.3.6.1.4.1.935.1.1.1.9.2
upsEnvOverTemperatureAlarm dupsAlarmOverTemperature on when the environment temperature over the value.rw
INTEGER
.1.3.6.1.4.1.935.1.1.1.9.2.1
upsEnvUnderTemperatureAlarm dupsAlarmUnderTemperature on when the environment temperature below the value.rw
INTEGER
.1.3.6.1.4.1.935.1.1.1.9.2.2
upsEnvOverHumidityAlarm dupsAlarmOverHumidity on when the environment humidity over the value.rw
INTEGER
.1.3.6.1.4.1.935.1.1.1.9.2.3
upsEnvUnderHumidityAlarm dupsAlarmUnderHumidity on when the environment humidity below the value.rw
INTEGER
.1.3.6.1.4.1.935.1.1.1.9.2.4
ppcmgmt
OBJECT IDENTIFIER
.1.3.6.1.4.1.935.2
mconfig
OBJECT IDENTIFIER
.1.3.6.1.4.1.935.2.1
mconfigTrapsReceiversNumThe number of managers to send traps to.ro
INTEGER
.1.3.6.1.4.1.935.2.1.1
mconfigTrapsReceiversTableA list of managers to send traps to. The number of entries is given by the value of mconfigNumTrapReceivers
SEQUENCE OF MconfigTrapsReceiversEntry
.1.3.6.1.4.1.935.2.1.2
mconfigTrapsReceiversEntryThe managers to send traps to.
MconfigTrapsReceiversEntry
.1.3.6.1.4.1.935.2.1.2.1
trapsIndexThe index to a trap receiver entry.ro
INTEGER
.1.3.6.1.4.1.935.2.1.2.1.1
trapsReceiverAddrThe IP address of the manager to send a trap to.rw
IpAddress
.1.3.6.1.4.1.935.2.1.2.1.2
receiverCommunityStringThe community name to use in the trap when sent to the manager.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.935.2.1.2.1.3
severityLevelThe severity threshold of traps to send to the manager. traps are labeled in severity as informational(1), warning(2), severe(3). Only traps of equal or greater severity than this value are sent to the manager.rw
Enumeration
.1.3.6.1.4.1.935.2.1.2.1.4
receiverAcceptAn entry will become active if yes, and will be deleted if no.rw
Enumeration
.1.3.6.1.4.1.935.2.1.2.1.5