XPPC-MIB
AI MIB Summary
Standard SNMP MIB module defining data structures for XPPC-MIB.
227
Objects
Active
Status
4
Dependencies
Imported Objects
Objects
227 total| Object Name |
|---|
ppc OBJECT IDENTIFIER .1.3.6.1.4.1.935 |
RFC1213-MIB Unknown .1.3.6.1.4.1.935 |
communicationLostSEVERE: Communication to the UPS has been lost. Steps
to reestablish communication are in progress. TRAP-TYPE .1.3.6.1.4.1.935.0.1 |
upsOverLoadSEVERE: The UPS has sensed a load greater than 100 percent
of its rated capacity. TRAP-TYPE .1.3.6.1.4.1.935.0.2 |
upsDiagnosticsFailedSEVERE: The UPS failed its internal diagnostic self-test. TRAP-TYPE .1.3.6.1.4.1.935.0.3 |
upsDischargedSEVERE: The UPS just started a runtime calibration
discharge. The UPS batteries are being discharged. TRAP-TYPE .1.3.6.1.4.1.935.0.4 |
upsOnBatteryWARNING: The UPS has switched to battery backup power. TRAP-TYPE .1.3.6.1.4.1.935.0.5 |
boostOnWARNING: The UPS has enabled Boost. TRAP-TYPE .1.3.6.1.4.1.935.0.6 |
lowBatterySEVERE: The UPS batteries are low and will soon be exhausted.
If utility power is not restored the UPS will put itself
to 'sleep' and immediately cut power to the load. TRAP-TYPE .1.3.6.1.4.1.935.0.7 |
communicationEstablishedINFORMATION: Communication with the UPS has been
established. TRAP-TYPE .1.3.6.1.4.1.935.0.8 |
powerRestoredINFORMATION: Utility power has been restored. TRAP-TYPE .1.3.6.1.4.1.935.0.9 |
upsDiagnosticsPassedINFORMATION: The UPS passed its internal self-test. TRAP-TYPE .1.3.6.1.4.1.935.0.10 |
returnFromLowBatteryINFORMATION: The UPS has returned from a low battery
condition. TRAP-TYPE .1.3.6.1.4.1.935.0.11 |
upsTurnedOffWARNING: The UPS has been turned 'off' by the
management station. TRAP-TYPE .1.3.6.1.4.1.935.0.12 |
upsSleepingWARNING: The UPS is entering 'sleep' mode. Power
to the load will be cut off. TRAP-TYPE .1.3.6.1.4.1.935.0.13 |
upsWokeUpINFORMATION: The UPS woke up from 'sleep' mode. Power
to the load has been restored. TRAP-TYPE .1.3.6.1.4.1.935.0.14 |
upsRebootStartedWARNING: The UPS has started its reboot sequence. After
the specified delay the UPS will perform a reboot. TRAP-TYPE .1.3.6.1.4.1.935.0.15 |
envOverTemperatureWARNING: The environment temperature exceed the normal value. TRAP-TYPE .1.3.6.1.4.1.935.0.16 |
envTemperatureNormalINFORMATION: The environment temperature is normal. TRAP-TYPE .1.3.6.1.4.1.935.0.17 |
envOverHumidityWARNING: The environment humidity exceed the normal value. TRAP-TYPE .1.3.6.1.4.1.935.0.18 |
envHumidityNormalINFORMATION: The environment humidity is normal. TRAP-TYPE .1.3.6.1.4.1.935.0.19 |
envSmokeAbnormalWARNING: Smoke is abnormal. TRAP-TYPE .1.3.6.1.4.1.935.0.20 |
envWaterAbnormalWARNING: Water is abnormal. TRAP-TYPE .1.3.6.1.4.1.935.0.21 |
envSecurityAbnormalWARNING: Security is abnormal. TRAP-TYPE .1.3.6.1.4.1.935.0.22 |
envWaterNormalINFORMATION: Water is normal. TRAP-TYPE .1.3.6.1.4.1.935.0.24 |
envGasAbnormalWARNING: Gas Alarm TRAP-TYPE .1.3.6.1.4.1.935.0.26 |
upsTempWARNING: UPS Temperature Overrun TRAP-TYPE .1.3.6.1.4.1.935.0.27 |
upsLoadNormalWARNING: UPS Load Normal TRAP-TYPE .1.3.6.1.4.1.935.0.28 |
upsTempNormalWARNING: UPS temperature Normal TRAP-TYPE .1.3.6.1.4.1.935.0.29 |
envUnderTemperatureWARNING: The environment temperature below the normal value. TRAP-TYPE .1.3.6.1.4.1.935.0.30 |
envUnderHumidityWARNING: The environment humidity below the normal value. TRAP-TYPE .1.3.6.1.4.1.935.0.31 |
upsBypassWARNING: The UPS is entering 'bypass' mode. TRAP-TYPE .1.3.6.1.4.1.935.0.32 |
envSecurity1WARNING: Security1 Alarm. TRAP-TYPE .1.3.6.1.4.1.935.0.33 |
envSecurity2WARNING: Security2 Alarm. TRAP-TYPE .1.3.6.1.4.1.935.0.34 |
envSecurity3WARNING: Security3 Alarm. TRAP-TYPE .1.3.6.1.4.1.935.0.35 |
envSecurity4WARNING: Security4 Alarm. TRAP-TYPE .1.3.6.1.4.1.935.0.36 |
envSecurity5WARNING: Security5 Alarm. TRAP-TYPE .1.3.6.1.4.1.935.0.37 |
envSecurity6WARNING: Security6 Alarm. TRAP-TYPE .1.3.6.1.4.1.935.0.38 |
envSecurity7WARNING: Security7 Alarm. TRAP-TYPE .1.3.6.1.4.1.935.0.39 |
upsRecroterrorWARNING: Rectifier Rotation Error TRAP-TYPE .1.3.6.1.4.1.935.0.47 |
upsBypassFreFailWARNING: Bypass Frequency Fail TRAP-TYPE .1.3.6.1.4.1.935.0.48 |
upsBypassacnormalWARNING: Bypass AC Normal TRAP-TYPE .1.3.6.1.4.1.935.0.49 |
upsBypassacabnormalWARNING: Bypass AC Abnormal TRAP-TYPE .1.3.6.1.4.1.935.0.50 |
upsTestWARNING: UPS Test TRAP-TYPE .1.3.6.1.4.1.935.0.51 |
upsScheduleShutdownWARNING: UPS Schedule Shutdown TRAP-TYPE .1.3.6.1.4.1.935.0.52 |
upsBypassReturnThe UPS return from Bypass Mode TRAP-TYPE .1.3.6.1.4.1.935.0.53 |
upsShortCircuitShutdownThe UPS Short Circuit Shutdown TRAP-TYPE .1.3.6.1.4.1.935.0.54 |
upsInverterOutputFailShutdownThe UPS Inverter Output Fail Shutdown TRAP-TYPE .1.3.6.1.4.1.935.0.55 |
upsBypassBreadkerOnShutdownThe UPS Manual Bypass Breaker on Shutdown TRAP-TYPE .1.3.6.1.4.1.935.0.56 |
upsHighDCShutdownThe UPS High DC Shutdown TRAP-TYPE .1.3.6.1.4.1.935.0.57 |
upsEmergencyStopThe UPS Emergency Stop TRAP-TYPE .1.3.6.1.4.1.935.0.58 |
upsInverterModeThe UPS Static Switch in Inverter Mode TRAP-TYPE .1.3.6.1.4.1.935.0.59 |
upsBypassModeThe UPS Static Switch in Bypass Mode TRAP-TYPE .1.3.6.1.4.1.935.0.60 |
upsOverTemperatureShutdownThe UPS Over Temperature Shutdown TRAP-TYPE .1.3.6.1.4.1.935.0.61 |
upsOverLoadShutdownThe UPS Overload Shutdown TRAP-TYPE .1.3.6.1.4.1.935.0.62 |
upsCapacityUnderrunThe UPS Capacity Underrun TRAP-TYPE .1.3.6.1.4.1.935.0.63 |
upsCapacityNormalThe UPS Capacity Normal TRAP-TYPE .1.3.6.1.4.1.935.0.64 |
upsLowBatteryShutdownThe UPS Low Battery Shutdown TRAP-TYPE .1.3.6.1.4.1.935.0.67 |
products OBJECT IDENTIFIER .1.3.6.1.4.1.935.1 |
hardware OBJECT IDENTIFIER .1.3.6.1.4.1.935.1.1 |
ups OBJECT IDENTIFIER .1.3.6.1.4.1.935.1.1.1 |
upsIdentp OBJECT IDENTIFIER .1.3.6.1.4.1.935.1.1.1.1 |
upsBaseIdent OBJECT IDENTIFIER .1.3.6.1.4.1.935.1.1.1.1.1 |
upsBaseIdentModelThe UPS model name (e.g. 'Intelligent 8000E 900VA').ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.935.1.1.1.1.1.1 |
upsBaseIdentUpsNameAn 8 byte ID string identifying the UPS. This object
can be set by the administrator.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.935.1.1.1.1.1.2 |
upsSmartIdent OBJECT IDENTIFIER .1.3.6.1.4.1.935.1.1.1.1.2 |
upsSmartIdentFirmwareRevisionThe firmware revision of the UPS system.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.935.1.1.1.1.2.1 |
upsSmartIdentDateOfManufactureThe date when the UPS was manufactured in mm/dd/yy format.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.935.1.1.1.1.2.2 |
upsSmartIdentUpsSerialNumberAn 8-character string identifying the serial number of
the UPS internal microprocessor. This number is set at
the factory. NOTE: This number does NOT correspond to
the serial number on the rear of the UPS.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.935.1.1.1.1.2.3 |
upsSmartIdentAgentFirmwareRevisionThe firmware revision of the UPS SNMP Proxy agent.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.935.1.1.1.1.2.4 |
upsBatteryp OBJECT IDENTIFIER .1.3.6.1.4.1.935.1.1.1.2 |
upsBaseBattery OBJECT IDENTIFIER .1.3.6.1.4.1.935.1.1.1.2.1 |
upsBaseBatteryStatusThe status of the UPS batteries. A batteryLow(3)
value indicates the UPS will be unable to sustain the
current load, and its services will be lost if power is
not restored. The amount of run time in reserve at the
time of low battery can be configured by the
upsSmartConfigLowBatteryRunTime.ro Enumeration .1.3.6.1.4.1.935.1.1.1.2.1.1 |
upsBaseBatteryTimeOnBatteryThe elapsed time in seconds since the UPS has switched
to battery power.ro INTEGER .1.3.6.1.4.1.935.1.1.1.2.1.2 |
upsBaseBatteryLastReplaceDateThe date when the UPS system's batteries were last replaced
in mm/dd/yy format. For UPS models, this value is originally
set in the factory. When the UPS batteries are replaced,
this value should be reset by the administrator.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.935.1.1.1.2.1.3 |
upsSmartBattery OBJECT IDENTIFIER .1.3.6.1.4.1.935.1.1.1.2.2 |
upsSmartBatteryCapacityThe remaining battery capacity expressed in
percent of full capacity.ro INTEGER .1.3.6.1.4.1.935.1.1.1.2.2.1 |
upsSmartBatteryVoltageThe current battery voltage expressed in 1/10 VDC.ro INTEGER .1.3.6.1.4.1.935.1.1.1.2.2.2 |
upsSmartBatteryTemperatureThe current internal UPS temperature expressed in tenths of
a Celsius degree.ro INTEGER .1.3.6.1.4.1.935.1.1.1.2.2.3 |
upsSmartBatteryRunTimeRemainingThe UPS battery run time remaining before battery
exhaustion, in seconds.ro INTEGER .1.3.6.1.4.1.935.1.1.1.2.2.4 |
upsSmartBatteryReplaceIndicatorIndicates whether the UPS batteries need replacing.ro Enumeration .1.3.6.1.4.1.935.1.1.1.2.2.5 |
upsSmartBatteryFullChargeVoltageThe fully charged battery voltage of the battery system
used in the UPS, expressed in tenths of a volt.ro INTEGER .1.3.6.1.4.1.935.1.1.1.2.2.6 |
upsSmartBatteryCurrentThe current battery current expressed in percent of
maximum current.ro INTEGER .1.3.6.1.4.1.935.1.1.1.2.2.7 |
upsInputp OBJECT IDENTIFIER .1.3.6.1.4.1.935.1.1.1.3 |
upsBaseInput OBJECT IDENTIFIER .1.3.6.1.4.1.935.1.1.1.3.1 |
upsBaseInputPhaseThe current AC input phase.ro INTEGER .1.3.6.1.4.1.935.1.1.1.3.1.1 |
upsSmartInput OBJECT IDENTIFIER .1.3.6.1.4.1.935.1.1.1.3.2 |
upsSmartInputLineVoltageThe current utility line voltage in 1/10 VAC.ro INTEGER .1.3.6.1.4.1.935.1.1.1.3.2.1 |
upsSmartInputMaxLineVoltageThe maximum utility line voltage in 1/10 VAC over the
previous 1 minute period.ro INTEGER .1.3.6.1.4.1.935.1.1.1.3.2.2 |
upsSmartInputMinLineVoltageThe minimum utility line voltage in 1/10 VAC over the
previous 1 minute period.ro INTEGER .1.3.6.1.4.1.935.1.1.1.3.2.3 |
upsSmartInputFrequencyThe current input frequency to the UPS system in 1/10 Hz.ro INTEGER .1.3.6.1.4.1.935.1.1.1.3.2.4 |
upsSmartInputLineFailCauseThe reason for the occurrence of the last transfer
to UPS battery power. The variable is set to
noTransfer(1) if there is no transfer yet. The variable
is set to highLineVoltage(2) if the transfer to battery is
caused by an over voltage greater than the high transfer
voltage. The variable is set to brownout(3) if the duration
of the outage is greater than five seconds and the line
voltage is between 40 percent of the rated output voltage and
the low transfer voltage. The variable is set to blackout(4)
if the duration of the outage is greater than five seconds and
the line voltage is between 40 percent of the rated output voltage
and ground. The variable is set to smallMomentarySag(5)
if the duration of the outage is less than five seconds and
the line voltage is between 40 percent of the rated output voltage
and the low transfer voltage. The variable is set to
deepMomentarySag(6) if the duration of the outage is less
than five seconds and the line voltage is between 40 percent of the
rated output voltage and ground.ro Enumeration .1.3.6.1.4.1.935.1.1.1.3.2.5 |
upsOutputp OBJECT IDENTIFIER .1.3.6.1.4.1.935.1.1.1.4 |
upsBaseOutput OBJECT IDENTIFIER .1.3.6.1.4.1.935.1.1.1.4.1 |
upsBaseOutputStatusThe current state of the UPS. If the UPS is unable
to determine the state of the UPS this variable is set
to unknown(1).ro Enumeration .1.3.6.1.4.1.935.1.1.1.4.1.1 |
upsBaseOutputPhaseThe current output phase.ro INTEGER .1.3.6.1.4.1.935.1.1.1.4.1.2 |
upsSmartOutput OBJECT IDENTIFIER .1.3.6.1.4.1.935.1.1.1.4.2 |
upsSmartOutputVoltageThe output voltage of the UPS system in 1/10 VAC.ro INTEGER .1.3.6.1.4.1.935.1.1.1.4.2.1 |
upsSmartOutputFrequencyThe current output frequency of the UPS system in 1/10 Hz.ro INTEGER .1.3.6.1.4.1.935.1.1.1.4.2.2 |
upsSmartOutputLoadThe current UPS load expressed in percent
of rated capacity.ro INTEGER .1.3.6.1.4.1.935.1.1.1.4.2.3 |
upsConfigp OBJECT IDENTIFIER .1.3.6.1.4.1.935.1.1.1.5 |
upsBaseConfig OBJECT IDENTIFIER .1.3.6.1.4.1.935.1.1.1.5.1 |
upsBaseConfigNumDevicesThe number of devices that are plugged into the UPS.ro INTEGER .1.3.6.1.4.1.935.1.1.1.5.1.1 |
upsBaseConfigDeviceTableA list of devices that are plugged into the UPS. The
number of entries is given by the value of
upsBaseConfigNumDevices. SEQUENCE OF UpsBaseConfigDeviceEntry .1.3.6.1.4.1.935.1.1.1.5.1.2 |
upsBaseConfigDeviceEntryThe devices plugged in to the UPS. UpsBaseConfigDeviceEntry .1.3.6.1.4.1.935.1.1.1.5.1.2.1 |
indexOfDeviceThe index of the device that is plugged into the UPS.ro INTEGER .1.3.6.1.4.1.935.1.1.1.5.1.2.1.1 |
nameOfDeviceThe name/description of the device plugged into the UPS.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.935.1.1.1.5.1.2.1.2 |
vaRatingOfDeviceThe volt-amp rating of the device plugged into the UPS.rw INTEGER .1.3.6.1.4.1.935.1.1.1.5.1.2.1.3 |
deviceAcceptAn entry is added if yes, the entry is deleted if no.rw Enumeration .1.3.6.1.4.1.935.1.1.1.5.1.2.1.4 |
upsSmartConfig OBJECT IDENTIFIER .1.3.6.1.4.1.935.1.1.1.5.2 |
upsSmartConfigRatedOutputVoltageThe nominal output voltage from the UPS in 1/10 VAC.
Possible values are 1000, 1200, 2080, 2200, 2250, 2300
and 2400.
NOTE: Only units that are 2200, 2250, 2300 and 2400 can
be changed. Allowable values are 2200, 2250, 2300 and
2400.
For these adjustable units, if a value other than
a supported value is provided in a set request, the
UPS interprets it as the next lower acceptable value.
If the provided value is lower than the lowest acceptable
value, the lowest acceptable value is used.rw INTEGER .1.3.6.1.4.1.935.1.1.1.5.2.1 |
upsSmartConfigHighTransferVoltThe maximum line voltage in 1/10 VAC allowed before the
UPS system transfers to battery backup.
Allowed value depend on the UPS used:
120 Volt units allow settings of 1290, 1320, 1350, 1380.
100 Volt units allow settings of 1080, 1100, 1120, 1140.
230 Volt units allow settings of 2530, 2640, 2710, 2800.
208 Volt units allow settings of 2240, 2290, 2340, 2390.
If a value other than a supported value is provided in a
set request, the UPS interprets it as the next lower
acceptable value. If the provided value is lower than
the lowest acceptable value, the lowest acceptable
value is used.rw INTEGER .1.3.6.1.4.1.935.1.1.1.5.2.2 |
upsSmartConfigLowTransferVoltThe minimum line voltage in 1/10 VAC allowed before the
UPS system transfers to battery backup.
Allowable values depend on the UPS used:
120 Volt units allow settings of 970, 1000, 1030, 1060.
100 Volt units allow settings of 810, 830, 850, 870.
230 Volt units allow settings of 1880, 1960, 2040, 2080.
208 Volt units allow settings of 1680, 1720, 1770, 1820.
If a value other than a supported value is provided in a
set request, the UPS interprets it as a the next higher
acceptable value. If the provided value is higher than
the highest acceptable value, the highest acceptable
value is used.rw INTEGER .1.3.6.1.4.1.935.1.1.1.5.2.3 |
upsSmartConfigAlarmA flag indicating how the UPS should handle audible line fail
alarms.rw Enumeration .1.3.6.1.4.1.935.1.1.1.5.2.4 |
upsSmartConfigAlarmTimerThe time in seconds after initial line failure at which the
UPS begins emitting audible alarms (beeping). This timer is
observerd only if the value of extControlAlarm is timed(2).
Allowed values are 0 or 30 seconds.
If a value other than a supported value is provided in a
set request, the UPS interprets it as a the next lower
acceptable value. If the provided value is lower than
the lowest acceptable value, the lowest acceptable
value is used.rw INTEGER .1.3.6.1.4.1.935.1.1.1.5.2.5 |
upsSmartConfigMinReturnCapacityThe minimum battery capacity as a percent of full capacity
required before the UPS will return from a low battery
shutdown condition. In other words, the UPS will not
re-energize the output until the battery capacity is equal
to this value. Allowed values are 0, 10, 25, or 90 percent.
If a value other than a supported value is provided in a
set request, the UPS interprets it as a the next higher
acceptable value. If the provided value is higher than
the highest acceptable value, the highest acceptable
value is used.rw INTEGER .1.3.6.1.4.1.935.1.1.1.5.2.6 |
upsSmartConfigSensitivityThe sensitivity of the UPS to utility line abnormalities
or noises.rw Enumeration .1.3.6.1.4.1.935.1.1.1.5.2.7 |
upsSmartConfigLowBatteryRunTimeThe desired run time in seconds once the low battery
condition is reached. Allowed values are 120, 300, 420,
or 600 seconds. During this time the UPS will produce a
constant warning tone which can not be disabled.
If a value other than a supported value is provided in a
set request, the UPS interprets it as a the next higher
acceptable value. If the provided value is higher than
the highest acceptable value, the highest acceptable
value is used.rw INTEGER .1.3.6.1.4.1.935.1.1.1.5.2.8 |
upsSmartConfigReturnDelayThe delay in seconds after utility line power returns
before the UPS will turn on. This value is also used
when the UPS comes out of a reboot and before the UPS
wakes up from 'sleep' mode. Allowed values are 0, 60,
180 and 300 seconds.
If a value other than a supported value is provided in a
set request, the UPS interprets it as a the next higher
acceptable value. If the provided value is higher than
the highest acceptable value, the highest acceptable
value is used.rw INTEGER .1.3.6.1.4.1.935.1.1.1.5.2.9 |
upsSmartConfigShutoffDelayThe delay in seconds the UPS remains on after being told
to turn off. Allowed values are 12, 18, 24, 30, 36, 42,
48, 54, 60, 120, 180, 240, 300, 360, 420, 480, 540, and
600 seconds.
If a value other than a supported value is provided in a
set request, the UPS interprets it as next higher acceptable
value. If the provided value is higher than the highest
acceptable value, the highest acceptable value is used.rw INTEGER .1.3.6.1.4.1.935.1.1.1.5.2.10 |
upsSmartConfigUpsSleepTimeThe time in minutes for the UPS to go to 'sleep' when
instructed. When in sleep mode, the UPS will not provide
output power regardless of the input line state. Once the
specified time has elapsed, output power will be restored.
This is a configuration setting. The UPS will not go to
sleep until told to do so by the manager from a management
station.
Any input value is allowed, however the UPS only recognizes
0 - 9999 minutes in one minute increments.
If the provided value is higher than the highest acceptable
value, the highest acceptable value is used.rw INTEGER .1.3.6.1.4.1.935.1.1.1.5.2.11 |
upsSmartConfigSetEEPROMDefaultsWRITE: Resets the UPS EEPROM variables to default values.
READ: returns 0rw Enumeration .1.3.6.1.4.1.935.1.1.1.5.2.12 |
upsControlp OBJECT IDENTIFIER .1.3.6.1.4.1.935.1.1.1.6 |
upsBaseControl OBJECT IDENTIFIER .1.3.6.1.4.1.935.1.1.1.6.1 |
upsBaseControlConserveBatterySetting this variable to turnUpsOffToConserveBattery(2)
causes a UPS on battery to be put into 'sleep' mode immediately.
The (10) means suspending time(10 minutes) before turn off UPS.
UPS will turn back on when utility power is restored.
Attempting to turn off a UPS that is not on battery will
result in a badValue error.
Setting this value to noTurnOffUps(1) has no
effect.
The value noTurnOffUps(1) will always be returned
when the variable is read.rw Enumeration .1.3.6.1.4.1.935.1.1.1.6.1.1 |
upsSmartControl OBJECT IDENTIFIER .1.3.6.1.4.1.935.1.1.1.6.2 |
upsSmartControlUpsOffSetting this variable to turnUpsOff(2) causes
the UPS to shut off. When in this state, the UPS
will not provide output power regardless of the input
line state. The on/off switch on the UPS
must be toggled for the UPS to return to operation.
Setting this value to noTurnUpsOff(1) has no
effect.
The value noTurnUpsOff(1) will always be returned
when the variable is read.rw Enumeration .1.3.6.1.4.1.935.1.1.1.6.2.1 |
upsSmartControlRebootUpsSetting this variable to rebootUps(2) causes the
UPS to shut off and turn back on.
Setting this value to noRebootUps(1) has no effect.
The value noRebootUps(1) will always be returned
when the variable is read.rw Enumeration .1.3.6.1.4.1.935.1.1.1.6.2.2 |
upsSmartControlUpsSleepSetting this variable to putUpsToSleep(2) causes
the UPS to go to sleep for the time specified by
upsSmartConfigUpsSleepTime.
When in sleep mode, the UPS will not provide output
power regardless of the input line state. Once the
specified time has elapsed, output power will be
restored.
Setting this value to noPutUpsToSleep(1) has no
effect.
The value noPutUpsToSleep(1) will always be returned
when the variable is read.rw Enumeration .1.3.6.1.4.1.935.1.1.1.6.2.3 |
upsSmartControlSimulatePowerFailSetting this variable to simulatePowerFailure(2) causes
the UPS switch to battery power.
Setting this value to noSimulatePowerFailure(1) has no
effect.
The value noSimulatePowerFailure(1) will always be returned
when the variable is read.rw Enumeration .1.3.6.1.4.1.935.1.1.1.6.2.4 |
upsSmartControlFlashAndBeepUPS to identify itself by lighting all indicators
and beeping.
Setting this variable to FlashAndBeep(2) causes
the UPS lights all panel indicators and beeps.
Setting this value to noFlashAndBeep(1) has no
effect.
The value noFlashAndBeep(1) will always be returned
when the variable is read.rw Enumeration .1.3.6.1.4.1.935.1.1.1.6.2.5 |
upsSmartControlTurnOnUpsLoadSetting this variable to upsSmartControlTurnOnUpsLoad(2)
causes the UPS switch back to utility power if utility
power is present.
Setting this value to noUpsSmartControlTurnOnUpsLoad(1)
has no effect.
The value noUpsSmartControlTurnOnUpsLoad(1) will always
be returned when the variable is read.rw Enumeration .1.3.6.1.4.1.935.1.1.1.6.2.6 |
upsTestp OBJECT IDENTIFIER .1.3.6.1.4.1.935.1.1.1.7 |
upsBaseTest OBJECT IDENTIFIER .1.3.6.1.4.1.935.1.1.1.7.1 |
upsSmartTest OBJECT IDENTIFIER .1.3.6.1.4.1.935.1.1.1.7.2 |
upsSmartTestDiagnosticScheduleThe UPS system's automatic battery test schedule.rw Enumeration .1.3.6.1.4.1.935.1.1.1.7.2.1 |
upsSmartTestDiagnosticsSetting this variable to testDiagnostics(2) causes
the UPS to perform a diagnostic self test.
Setting this value to noTestDiagnostics(1) has no
effect.
The value noTestDiagnostics(1) will always be returned
when the variable is read.rw Enumeration .1.3.6.1.4.1.935.1.1.1.7.2.2 |
upsSmartTestDiagnosticsResultsThe results of the last UPS diagnostics test performed.ro Enumeration .1.3.6.1.4.1.935.1.1.1.7.2.3 |
upsSmartTestLastDiagnosticsDateThe date the last UPS diagnostics test was performed in
mm/dd/yy format.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.935.1.1.1.7.2.4 |
upsSmartTestIndicatorsSetting this variable to testIndicators(2) causes
the UPS to perform a front panel indicator (lights) test.
Setting this value to noTestIndicators(1) has no effect.
The value noTestIndicators(1) will always be returned
when the variable is read.rw Enumeration .1.3.6.1.4.1.935.1.1.1.7.2.5 |
upsSmartTestRuntimeCalibrationSetting this variable to performCalibration(2) causes
the UPS to discharge to calibrate the UPS.
The test will only start if the battery capacity is 100 percent.
The test runs until capacity is less than 25 percent.
Setting this variable to cancelCurrentCalibration(3)
after setting performCalibration(2) will cancel the
current discharge.
Setting this variable to noPerformCalibration(1)
will have no effect.
The value noPerformCalibration(1) will always be returned
when the variable is read.
The result of the calibration will be saved in
upsSmartTestCalibrationResult.rw Enumeration .1.3.6.1.4.1.935.1.1.1.7.2.6 |
upsSmartTestCalibrationResultsThe results of the last runtime calibration.
Value ok(1) means a successful runtime calibration.
Value invalidTest(2) indicates last calibration did
not take place since the battery capacity was below
100 percent.
Value calibrationInProgress(3) means a calibration
is occurring now.ro Enumeration .1.3.6.1.4.1.935.1.1.1.7.2.7 |
upsSmartTestCalibrationDateThe date the last UPS runtime calibration was
performed in mm/dd/yy format.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.935.1.1.1.7.2.8 |
upsThreePhase OBJECT IDENTIFIER .1.3.6.1.4.1.935.1.1.1.8 |
upsThreePhaseBatteryGrp OBJECT IDENTIFIER .1.3.6.1.4.1.935.1.1.1.8.1 |
upsThreePhaseBatteryVoltageBattery Voltagero INTEGER .1.3.6.1.4.1.935.1.1.1.8.1.1 |
upsThreePhaseBatteryCapacityPercentageBattery Capacity Percentagero INTEGER .1.3.6.1.4.1.935.1.1.1.8.1.2 |
upsThreePhaseBatteryTimeRemainBattery Time Remain (unit is Minute)ro INTEGER .1.3.6.1.4.1.935.1.1.1.8.1.3 |
upsThreePhaseBatteryCurrentBattery Electric Currentro INTEGER .1.3.6.1.4.1.935.1.1.1.8.1.4 |
upsThreePhaseBatteryTemperatureBattery Temperaturero INTEGER .1.3.6.1.4.1.935.1.1.1.8.1.5 |
upsThreePhaseInputGrp OBJECT IDENTIFIER .1.3.6.1.4.1.935.1.1.1.8.2 |
upsThreePhaseInputFrequencyInput Frequencyro INTEGER .1.3.6.1.4.1.935.1.1.1.8.2.1 |
upsThreePhaseInputVoltageRInput VoltageRro INTEGER .1.3.6.1.4.1.935.1.1.1.8.2.2 |
upsThreePhaseInputVoltageSInput VoltageSro INTEGER .1.3.6.1.4.1.935.1.1.1.8.2.3 |
upsThreePhaseInputVoltageTInput VoltageTro INTEGER .1.3.6.1.4.1.935.1.1.1.8.2.4 |
upsThreePhaseOutputGrp OBJECT IDENTIFIER .1.3.6.1.4.1.935.1.1.1.8.3 |
upsThreePhaseOutputFrequencyOutput Frequencyro INTEGER .1.3.6.1.4.1.935.1.1.1.8.3.1 |
upsThreePhaseOutputVoltageROutput VoltageRro INTEGER .1.3.6.1.4.1.935.1.1.1.8.3.2 |
upsThreePhaseOutputVoltageSOutput VoltageSro INTEGER .1.3.6.1.4.1.935.1.1.1.8.3.3 |
upsThreePhaseOutputVoltageTOutput VoltageTro INTEGER .1.3.6.1.4.1.935.1.1.1.8.3.4 |
upsThreePhaseOutputLoadPercentageRLoad PercentageRro INTEGER .1.3.6.1.4.1.935.1.1.1.8.3.5 |
upsThreePhaseOutputLoadPercentageSLoad PercentageSro INTEGER .1.3.6.1.4.1.935.1.1.1.8.3.6 |
upsThreePhaseOutputLoadPercentageTLoad PercentageTro INTEGER .1.3.6.1.4.1.935.1.1.1.8.3.7 |
upsThreePhaseBypassGrp OBJECT IDENTIFIER .1.3.6.1.4.1.935.1.1.1.8.4 |
upsThreePhaseBypassSourceFrequencyBypass Frequencyro INTEGER .1.3.6.1.4.1.935.1.1.1.8.4.1 |
upsThreePhaseBypssSourceVoltageRBypass VoltageRro INTEGER .1.3.6.1.4.1.935.1.1.1.8.4.2 |
upsThreePhaseBypssSourceVoltageSBypass VoltageSro INTEGER .1.3.6.1.4.1.935.1.1.1.8.4.3 |
upsThreePhaseBypssSourceVoltageTBypass VoltageTro INTEGER .1.3.6.1.4.1.935.1.1.1.8.4.4 |
upsThreePhaseDCandRectifierStatusGrp OBJECT IDENTIFIER .1.3.6.1.4.1.935.1.1.1.8.5 |
upsThreePhaseDCandRectifierStatusRecRotErrorRectifier Rotation Errorro Enumeration .1.3.6.1.4.1.935.1.1.1.8.5.1 |
upsThreePhaseDCandRectifierStatusLowBatteryShutdownLow Battery Shutdownro Enumeration .1.3.6.1.4.1.935.1.1.1.8.5.2 |
upsThreePhaseDCandRectifierStatusLowBatteryLow Batteryro Enumeration .1.3.6.1.4.1.935.1.1.1.8.5.3 |
upsThreePhaseDCandRectifierStatusInAndOutIn And Putro Enumeration .1.3.6.1.4.1.935.1.1.1.8.5.4 |
upsThreePhaseDCandRectifierStatusBatteryStatusBack Statusro Enumeration .1.3.6.1.4.1.935.1.1.1.8.5.5 |
upsThreePhaseDCandRectifierStatusChargeStatusCharge Statusro Enumeration .1.3.6.1.4.1.935.1.1.1.8.5.6 |
upsThreePhaseDCandRectifierStatusRecOperatingRectifier Operatingro Enumeration .1.3.6.1.4.1.935.1.1.1.8.5.7 |
upsThreePhaseUPSStatusGrp OBJECT IDENTIFIER .1.3.6.1.4.1.935.1.1.1.8.6 |
upsThreePhaseUPSStatusBypassFreqFailBypass Statusro Enumeration .1.3.6.1.4.1.935.1.1.1.8.6.1 |
upsThreePhaseUPSStatusManualBypassBreakerBreaker Statusro Enumeration .1.3.6.1.4.1.935.1.1.1.8.6.2 |
upsThreePhaseUPSStatusACStatusAC Statusro Enumeration .1.3.6.1.4.1.935.1.1.1.8.6.3 |
upsThreePhaseUPSStaticSwitchModeSwitch Modero Enumeration .1.3.6.1.4.1.935.1.1.1.8.6.4 |
upsThreePhaseUPSStatusInverterOperatingOperatingro Enumeration .1.3.6.1.4.1.935.1.1.1.8.6.5 |
upsThreePhaseFaultStatusGrp OBJECT IDENTIFIER .1.3.6.1.4.1.935.1.1.1.8.7 |
upsThreePhaseFaultStatusEmergencyStopEmergency Stopro Enumeration .1.3.6.1.4.1.935.1.1.1.8.7.1 |
upsThreePhaseFaultStatusHighDCShutdownHigh DC Shutdownro Enumeration .1.3.6.1.4.1.935.1.1.1.8.7.2 |
upsThreePhaseFaultStatusBypassBreakerBypass Breakerro Enumeration .1.3.6.1.4.1.935.1.1.1.8.7.3 |
upsThreePhaseFaultStatusOverLoadOver Loadro Enumeration .1.3.6.1.4.1.935.1.1.1.8.7.4 |
upsThreePhaseFaultStatusInverterOutputFailOutput Failro Enumeration .1.3.6.1.4.1.935.1.1.1.8.7.5 |
upsThreePhaseFaultStatusOverTemperatureOver Temperaturero Enumeration .1.3.6.1.4.1.935.1.1.1.8.7.6 |
upsThreePhaseFaultStatusShortCircuitShort Circuitro Enumeration .1.3.6.1.4.1.935.1.1.1.8.7.7 |
upsThreePhaseRatingGrp OBJECT IDENTIFIER .1.3.6.1.4.1.935.1.1.1.8.8 |
upsThreePhaseRatingRectifierVoltageRectifier Voltagero DisplayString (SNMPv2-TC) .1.3.6.1.4.1.935.1.1.1.8.8.1 |
upsThreePhaseRatingRectifierFrequencyRectifier Frequencyro INTEGER .1.3.6.1.4.1.935.1.1.1.8.8.2 |
upsThreePhaseRatingBypassVoltageBypass Voltagero DisplayString (SNMPv2-TC) .1.3.6.1.4.1.935.1.1.1.8.8.3 |
upsThreePhaseRatingBypassFrequencyBypass Frequencyro INTEGER .1.3.6.1.4.1.935.1.1.1.8.8.4 |
upsThreePhaseRatingOutputVoltageOutput Voltagero DisplayString (SNMPv2-TC) .1.3.6.1.4.1.935.1.1.1.8.8.5 |
upsThreePhaseRatingOutputFrequencyOutput Frequencyro INTEGER .1.3.6.1.4.1.935.1.1.1.8.8.6 |
upsThreePhaseRatingBatteryVoltageBattery Voltagero INTEGER .1.3.6.1.4.1.935.1.1.1.8.8.7 |
upsThreePhaseRatingPowerPower Ratingro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.935.1.1.1.8.8.8 |
upsEnvironment OBJECT IDENTIFIER .1.3.6.1.4.1.935.1.1.1.9 |
upsEnvStatus OBJECT IDENTIFIER .1.3.6.1.4.1.935.1.1.1.9.1 |
upsEnvTemperatureThe ambient environment temperature.ro INTEGER .1.3.6.1.4.1.935.1.1.1.9.1.1 |
upsEnvHumidityThe environment humidity.ro INTEGER .1.3.6.1.4.1.935.1.1.1.9.1.2 |
upsEnvWaterWater statusro Enumeration .1.3.6.1.4.1.935.1.1.1.9.1.3 |
upsEnvSmokeSmoke statusro Enumeration .1.3.6.1.4.1.935.1.1.1.9.1.4 |
upsEnvSecurity1Security statusro Enumeration .1.3.6.1.4.1.935.1.1.1.9.1.5 |
upsEnvSecurity2Security statusro Enumeration .1.3.6.1.4.1.935.1.1.1.9.1.6 |
upsEnvSecurity3Security statusro Enumeration .1.3.6.1.4.1.935.1.1.1.9.1.7 |
upsEnvSecurity4Security statusro Enumeration .1.3.6.1.4.1.935.1.1.1.9.1.8 |
upsEnvSecurity5Security statusro Enumeration .1.3.6.1.4.1.935.1.1.1.9.1.9 |
upsEnvSecurity6Security statusro Enumeration .1.3.6.1.4.1.935.1.1.1.9.1.10 |
upsEnvSecurity7Security statusro Enumeration .1.3.6.1.4.1.935.1.1.1.9.1.11 |
upsEnvSetting OBJECT IDENTIFIER .1.3.6.1.4.1.935.1.1.1.9.2 |
upsEnvOverTemperatureAlarm dupsAlarmOverTemperature on when the environment
temperature over the value.rw INTEGER .1.3.6.1.4.1.935.1.1.1.9.2.1 |
upsEnvUnderTemperatureAlarm dupsAlarmUnderTemperature on when the environment
temperature below the value.rw INTEGER .1.3.6.1.4.1.935.1.1.1.9.2.2 |
upsEnvOverHumidityAlarm dupsAlarmOverHumidity on when the environment
humidity over the value.rw INTEGER .1.3.6.1.4.1.935.1.1.1.9.2.3 |
upsEnvUnderHumidityAlarm dupsAlarmUnderHumidity on when the environment
humidity below the value.rw INTEGER .1.3.6.1.4.1.935.1.1.1.9.2.4 |
ppcmgmt OBJECT IDENTIFIER .1.3.6.1.4.1.935.2 |
mconfig OBJECT IDENTIFIER .1.3.6.1.4.1.935.2.1 |
mconfigTrapsReceiversNumThe number of managers to send traps to.ro INTEGER .1.3.6.1.4.1.935.2.1.1 |
mconfigTrapsReceiversTableA list of managers to send traps to. The number of
entries is given by the value of mconfigNumTrapReceivers SEQUENCE OF MconfigTrapsReceiversEntry .1.3.6.1.4.1.935.2.1.2 |
mconfigTrapsReceiversEntryThe managers to send traps to. MconfigTrapsReceiversEntry .1.3.6.1.4.1.935.2.1.2.1 |
trapsIndexThe index to a trap receiver entry.ro INTEGER .1.3.6.1.4.1.935.2.1.2.1.1 |
trapsReceiverAddrThe IP address of the manager to send a trap to.rw IpAddress .1.3.6.1.4.1.935.2.1.2.1.2 |
receiverCommunityStringThe community name to use in the trap when
sent to the manager.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.935.2.1.2.1.3 |
severityLevelThe severity threshold of traps to send to the manager.
traps are labeled in severity as informational(1), warning(2),
severe(3). Only traps of equal or greater severity than
this value are sent to the manager.rw Enumeration .1.3.6.1.4.1.935.2.1.2.1.4 |
receiverAcceptAn entry will become active if yes, and will
be deleted if no.rw Enumeration .1.3.6.1.4.1.935.2.1.2.1.5 |