EPPC-MIB
AI MIB Summary
Standard SNMP MIB module defining data structures for EPPC-MIB.
294
Objects
Active
Status
5
Dependencies
Imported Objects
Objects
294 total| Object Name |
|---|
ppc OBJECT IDENTIFIER .1.3.6.1.4.1.935 |
SNMPv2-TC Unknown .1.3.6.1.4.1.935 |
device OBJECT IDENTIFIER .1.3.6.1.4.1.935.10 |
upsAgent OBJECT IDENTIFIER .1.3.6.1.4.1.935.10.1 |
upsE OBJECT IDENTIFIER .1.3.6.1.4.1.935.10.1.1 |
upsEIdentity OBJECT IDENTIFIER .1.3.6.1.4.1.935.10.1.1.1 |
upsEIdentityManufacturerThe name of the UPS manufacturer.ro DisplayString ( SIZE ( 0 .. 31 ) ) .1.3.6.1.4.1.935.10.1.1.1.1 |
upsEIdentityModelThe UPS Model designation.ro DisplayString ( SIZE ( 0 .. 63 ) ) .1.3.6.1.4.1.935.10.1.1.1.2 |
upsEIdentityUPSFirmwareVerisonThe UPS firmware/software version(s).ro DisplayString ( SIZE ( 0 .. 31 ) ) .1.3.6.1.4.1.935.10.1.1.1.3 |
upsEIndentityUPSSerialNumberoptional.
Most UPS don't supply the value of UPS serial No.ro DisplayString ( SIZE ( 0 .. 31 ) ) .1.3.6.1.4.1.935.10.1.1.1.4 |
upsEIdentityDescriptionA string to identify the UPS. This object should be
set by the administrator.rw DisplayString ( SIZE ( 0 .. 63 ) ) .1.3.6.1.4.1.935.10.1.1.1.5 |
upsEIdentityAgentSoftwareVerisonThe Network Management Card software/firmware version.
This variable may or may not have the same value as
upsEIdentGroupUPSSoftwareVersion in some implementations.ro DisplayString ( SIZE ( 0 .. 31 ) ) .1.3.6.1.4.1.935.10.1.1.1.6 |
upsEIdentityAttachedDevicesA string identifying the devices attached to the output(s)
of the UPS. This object should be set by the administratorrw DisplayString ( SIZE ( 0 .. 63 ) ) .1.3.6.1.4.1.935.10.1.1.1.7 |
upsESystemSummary OBJECT IDENTIFIER .1.3.6.1.4.1.935.10.1.1.2 |
upsESystemStatusThe indication of UPS system status.ro Enumeration .1.3.6.1.4.1.935.10.1.1.2.1 |
upsESystemTemperatureThe temperature of UPS presented in 0.1 degree.ro INTEGER .1.3.6.1.4.1.935.10.1.1.2.2 |
upsESystemWarningCodeThe warning code of UPS. Please refer the warning table
of 'Q6' for details.ro DisplayString ( SIZE ( 0 .. 15 ) ) .1.3.6.1.4.1.935.10.1.1.2.3 |
upsESystemFaultCodeThe fault code of UPS.Please refer the fault code
of 'Q6' for details.ro DisplayString ( SIZE ( 0 .. 15 ) ) .1.3.6.1.4.1.935.10.1.1.2.4 |
upsESystemConfigInputVoltageThe magnitude of the nominal input voltage presented in 0.1 V. On those
systems which support read-write access to this object, if there is an
attempt to set this variable to a value that is not supported,
the request must be rejected and the agent shall respond with an
appropriate error message, i.e., badValue for SNMPv1, or
inconsistentValue for SNMPv2.ro NonNegativeInteger (UPS-MIB) .1.3.6.1.4.1.935.10.1.1.2.5 |
upsESystemConfigInputFrequenceThe nominal input frequency presented in 0.1 Hz. On those systems which support
read-write access to this object, if there is an attempt to
set this variable to a value that is not supported, the request
must be rejected and the agent shall respond with an appropriate
error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.ro NonNegativeInteger (UPS-MIB) .1.3.6.1.4.1.935.10.1.1.2.6 |
upsESystemConfigOutputVoltageThe magnitude of the nominal output voltage presented in 0.1V. On those systems
which support read-write access to this object, if there is an
attempt to set this variable to a value that is not supported,
the request must be rejected and the agent shall respond with an
appropriate error message, i.e., badValue for SNMPv1, or
inconsistentValue for SNMPv2ro NonNegativeInteger (UPS-MIB) .1.3.6.1.4.1.935.10.1.1.2.7 |
upsESystemConfigOutputFrequencyThe nominal output frequency presented in 0.1Hz. On those systems which support
read-write access to this object, if there is an attempt to set
this variable to a value that is not supported, the request must
be rejected and the agent shall respond with an appropriate error
message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.ro NonNegativeInteger (UPS-MIB) .1.3.6.1.4.1.935.10.1.1.2.8 |
upsESystemConfigOutputVAThe magnitude of the nominal Volt-Amp rating presented in VA.ro NonNegativeInteger (UPS-MIB) .1.3.6.1.4.1.935.10.1.1.2.9 |
upsESystemConfigOutputPowerThe magnitude of the nominal true power rating presented in W .ro NonNegativeInteger (UPS-MIB) .1.3.6.1.4.1.935.10.1.1.2.10 |
upsESystemConfigOutputLoadHighSetPointThe maximum output load allowed before the load is too high for
UPS operationrw NonNegativeInteger (UPS-MIB) .1.3.6.1.4.1.935.10.1.1.2.11 |
upsESystemConfigOverTemperatureSetPointThe maximum temperature allowed before the UPS
operation temperature is too high, presented in 0.1 degree.rw NonNegativeInteger (UPS-MIB) .1.3.6.1.4.1.935.10.1.1.2.12 |
upsESystemInputSourceNumThe present external source of input power.ro INTEGER .1.3.6.1.4.1.935.10.1.1.2.13 |
upsESystemInputLineBadsThe number of times the Input was out of tolerance in voltage or frequency.
Its value should be initialized 0 after agent restarting.ro Counter .1.3.6.1.4.1.935.10.1.1.2.14 |
upsESystemInputNumPhasesThe number of input phase utilized is this device, serves as the table index.
This value indicate the device initialized feature.ro PositiveInteger ( 1 .. 3 ) .1.3.6.1.4.1.935.10.1.1.2.15 |
upsESystemInputTableA list of input table entries. The number of entries is given by the
value of upsESystemInputNumPhase. SEQUENCE OF UpsSystemInputEntry .1.3.6.1.4.1.935.10.1.1.2.16 |
upsESystemInputEntryAn entry containing information applicable to a particular input line. UpsSystemInputEntry .1.3.6.1.4.1.935.10.1.1.2.16.1 |
upsESystemInputPhaseThe number of the phase. Serves as index for input table PositiveInteger( 1 .. 3 ) .1.3.6.1.4.1.935.10.1.1.2.16.1.1 |
upsESystemInputFrequencyThe measured input frquency from the UPS meters in 0.1Hz.ro NonNegativeInteger (UPS-MIB) .1.3.6.1.4.1.935.10.1.1.2.16.1.2 |
upsESystemInputVoltageThe measured input voltage from the UPS meters in 0.1 voltsro NonNegativeInteger (UPS-MIB) .1.3.6.1.4.1.935.10.1.1.2.16.1.3 |
upsESystemInputCurrentThe measured input mandatory from the UPS meters in 0.1 amps.ro NonNegativeInteger (UPS-MIB) .1.3.6.1.4.1.935.10.1.1.2.16.1.4 |
upsESystemInputWattsThe measured input real power in watts.ro NonNegativeInteger (UPS-MIB) .1.3.6.1.4.1.935.10.1.1.2.16.1.5 |
upsESystemOutputNumPhaseThe number of metered output phases, serves as the table index.
This value indicate the device initialized feature.ro PositiveInteger ( 1 .. 3 ) .1.3.6.1.4.1.935.10.1.1.2.17 |
upsESystemOutputTableA list of output table entries. The number of entries is given
by the value of upsESystemOutputNumPhase. SEQUENCE OF UpsSystemOutputEntry .1.3.6.1.4.1.935.10.1.1.2.18 |
upsESystemOutputEntryAn entry containing information applicable to a particular line. UpsSystemOutputEntry .1.3.6.1.4.1.935.10.1.1.2.18.1 |
upsESystemOutputPhaseThe number of the phase. Serves as index for output table PositiveInteger ( 1 .. 3 ) .1.3.6.1.4.1.935.10.1.1.2.18.1.1 |
upsESystemOutputFrequencyThe measured output frequency from the UPS meters in 0.1Hz.ro NonNegativeInteger (UPS-MIB) .1.3.6.1.4.1.935.10.1.1.2.18.1.2 |
upsESystemOutputVoltageThe measured output voltage from the UPS meters in 0.1 voltsro NonNegativeInteger (UPS-MIB) .1.3.6.1.4.1.935.10.1.1.2.18.1.3 |
upsESystemOutputCurrentThe measured output mandatory from the UPS meters in 0.1 amps.ro NonNegativeInteger (UPS-MIB) .1.3.6.1.4.1.935.10.1.1.2.18.1.4 |
upsESystemOutputWattsThe measured output real power in watts.ro NonNegativeInteger (UPS-MIB) .1.3.6.1.4.1.935.10.1.1.2.18.1.5 |
upsESystemOutputVAThe measured output real complex power in VA.ro NonNegativeInteger (UPS-MIB) .1.3.6.1.4.1.935.10.1.1.2.18.1.6 |
upsESystemOutputLoadThe UPS output load in percent of rated capacity.ro NonNegativeInteger (UPS-MIB) .1.3.6.1.4.1.935.10.1.1.2.18.1.7 |
upsESystemBypassNumPhaseThe number of bypass phases, serves as the table index.
This value indicate the device initialized featurero PositiveInteger ( 1 .. 3 ) .1.3.6.1.4.1.935.10.1.1.2.19 |
upsESystemBypassTableA list of bypass table entries. The number of entries is given by the
value of upsESystemBypassNumPhase. SEQUENCE OF UpsSystemBypassEntry .1.3.6.1.4.1.935.10.1.1.2.20 |
upsESystemBypassEntryAn entry containing information applicable to a particular line. UpsSystemBypassEntry .1.3.6.1.4.1.935.10.1.1.2.20.1 |
upsESystemBypassPhaseThe number of the phase. Serves as index for bypass table PositiveInteger ( 1 .. 3 ) .1.3.6.1.4.1.935.10.1.1.2.20.1.1 |
upsESystemBypassFrequencyThe measured bypass frequency from the UPS meters in 0.1 Hz.ro NonNegativeInteger (UPS-MIB) .1.3.6.1.4.1.935.10.1.1.2.20.1.2 |
upsESystemBypassVoltageThe measured bypass voltage from the UPS meters in 0.1 voltsro NonNegativeInteger (UPS-MIB) .1.3.6.1.4.1.935.10.1.1.2.20.1.3 |
upsESystemBypassCurrentThe measured bypass mandatory from the UPS meters in 0.1 ampsro NonNegativeInteger (UPS-MIB) .1.3.6.1.4.1.935.10.1.1.2.20.1.4 |
upsESystemBypassWattsThe measured input real power in watts.ro NonNegativeInteger (UPS-MIB) .1.3.6.1.4.1.935.10.1.1.2.20.1.5 |
upsESystemConfigBelowCapacityLimitThe UPS batteries capacity(%) limit for shutdownrw NonNegativeInteger (UPS-MIB) .1.3.6.1.4.1.935.10.1.1.2.21 |
upsESystemConfigBelowRemainTimeLimitThe UPS batteries backup time(minute) limit for shutdownrw NonNegativeInteger (UPS-MIB) .1.3.6.1.4.1.935.10.1.1.2.22 |
upsEBatterySystem OBJECT IDENTIFIER .1.3.6.1.4.1.935.10.1.1.3 |
upsEBatteryStatusThe status of UPS battery, a value of batteryLow indicates
that the battery-low status bit has been set from device.
A value of batteryDepleted indicates that the UPS will be
unable to sustain the present load when and if the utility
power is lost (including the possibility that the utility
power is mandatoryly absent and the UPS is unable to sustain
the output)ro Enumeration .1.3.6.1.4.1.935.10.1.1.3.1 |
upsESecondsOnBatteryIf the unit is on battery power, the elapsed time
since the UPS last switched to battery power, or the
time since the network management subsystem was last
restarted, whichever is less. 0 shall be returned
if the unit is not on battery powerro NonNegativeInteger (UPS-MIB) .1.3.6.1.4.1.935.10.1.1.3.2 |
upsEBatteryEstimatedMinutesRemainingAn estimate of the time to battery charge depletion
under the present load conditions if the utility power
is off and remains off, or if it were to be lost and
remain off.ro PositiveInteger (UPS-MIB) .1.3.6.1.4.1.935.10.1.1.3.3 |
upsEBatteryEstimatedChargeRemainingAn estimate of the battery charge remaining expressed
as a percent of full chargero Integer32 ( 0 .. 100 ) .1.3.6.1.4.1.935.10.1.1.3.4 |
upsEPositiveBatteryVoltageThe magnitude of the present positive battery voltage in 0.1 Volt DCro NonNegativeInteger (UPS-MIB) .1.3.6.1.4.1.935.10.1.1.3.5 |
upsENegativeBatteryVoltageThe magnitude of the present negative battery voltage in 0.1 Volt DCro NonNegativeInteger (UPS-MIB) .1.3.6.1.4.1.935.10.1.1.3.6 |
upsEBatteryCellNumberThis object indicate the cell number of each set.ro NonNegativeInteger (UPS-MIB) .1.3.6.1.4.1.935.10.1.1.3.7 |
upsEBatteryTemperatureThe ambient temperature at or near the UPS Battery
casing in 0.1 degree.ro INTEGER .1.3.6.1.4.1.935.10.1.1.3.8 |
upsEBatteryLastReplacedDateThe date when the Batteries in this UPS were last replaced.
The format should be DD/MM/YYYY.ro DisplayString ( SIZE ( 10 .. 10 ) ) .1.3.6.1.4.1.935.10.1.1.3.9 |
upsEBatteryABMStatusThe status of ABM.ro Enumeration .1.3.6.1.4.1.935.10.1.1.3.10 |
upsEChargerModulesNumThe number of charger modules inserted to UPS systems. served
as the index of the upsEChargerModulesTable.
The default value 0 indicate that the UPS system don't have
separate charger module.ro NonNegativeInteger ( 0 .. 32 ) .1.3.6.1.4.1.935.10.1.1.3.11 |
upsEChargerModulesTableA list of charger modules entries. The number of entries is given
by the value of upsEchargerModulesNum. SEQUENCE OF UpsChargerModulesEntry .1.3.6.1.4.1.935.10.1.1.3.12 |
upsEChargerModulesEntryAn entry containing information applicable to a particular charger module. UpsChargerModulesEntry .1.3.6.1.4.1.935.10.1.1.3.12.1 |
chargerModulesNumThe number of charger modules. Serves as index for charger module table PositiveInteger ( 1 .. 32 ) .1.3.6.1.4.1.935.10.1.1.3.12.1.1 |
chargerModulesAddressCharger Modules' address.ro NonNegativeInteger (UPS-MIB) .1.3.6.1.4.1.935.10.1.1.3.12.1.2 |
positiveChargeVotlageThe measured positive charger voltage from the UPS meters in 0.1 voltsro NonNegativeInteger (UPS-MIB) .1.3.6.1.4.1.935.10.1.1.3.12.1.3 |
negativeChargeVoltageThe measured nepositive charger voltage from the UPS meters in 0.1 voltsro NonNegativeInteger (UPS-MIB) .1.3.6.1.4.1.935.10.1.1.3.12.1.4 |
positiveChargeCurrentThe measured positive charger mandatory from the UPS meters in in 0.1 amps.ro NonNegativeInteger (UPS-MIB) .1.3.6.1.4.1.935.10.1.1.3.12.1.5 |
negativeChargeCurrentThe measured nepositive charger mandatory from the UPS meters in 0.1 amps.ro NonNegativeInteger (UPS-MIB) .1.3.6.1.4.1.935.10.1.1.3.12.1.6 |
chargerModulesTemperatureThe measured charger temperature from the UPS meters in 0.1 degree.ro INTEGER .1.3.6.1.4.1.935.10.1.1.3.12.1.7 |
chargerModulesModeThe working mode of charger modules.ro Enumeration .1.3.6.1.4.1.935.10.1.1.3.12.1.8 |
upsEPowerConverterSystem OBJECT IDENTIFIER .1.3.6.1.4.1.935.10.1.1.4 |
upsEUPSModulesNumThe number of UPS modules inserted to UPS systems.
served as the index of the upsEModulesTable.
the default value 0 indicate that the UPS system do not
have separate UPS module.ro NonNegativeInteger ( 0 .. 32 ) .1.3.6.1.4.1.935.10.1.1.4.1 |
upsEModulesTableA list of UPS modules entries. The number of entries is
given by the value of upsEModulesNum. SEQUENCE OF UpsModulesEntry .1.3.6.1.4.1.935.10.1.1.4.2 |
upsEModulesEntryAn entry containing information applicable to a particular upsE module. UpsModulesEntry .1.3.6.1.4.1.935.10.1.1.4.2.1 |
upsEModulesNumThe number of UPS modules. Serves as index for UPS module table PositiveInteger ( 1 .. 32 ) .1.3.6.1.4.1.935.10.1.1.4.2.1.1 |
upsEModuleAddressthe address of UPS modules.ro INTEGER .1.3.6.1.4.1.935.10.1.1.4.2.1.2 |
upsEModulePositiveBusVoltThe measured positive upsE module voltage from the UPS meters in 0.1 voltsro NonNegativeInteger (UPS-MIB) .1.3.6.1.4.1.935.10.1.1.4.2.1.3 |
upsEModuleNegativeBusVoltThe measured nepositive upsE module voltage from the UPS meters in 0.1 voltsro NonNegativeInteger (UPS-MIB) .1.3.6.1.4.1.935.10.1.1.4.2.1.4 |
upsEModuleTemperatureThe measured upsE module temperature from the UPS meters in 0.1 degree.ro INTEGER .1.3.6.1.4.1.935.10.1.1.4.2.1.5 |
upsEModuleWorkingModeThe working mode of UPS modules.ro Enumeration .1.3.6.1.4.1.935.10.1.1.4.2.1.6 |
upsEModuleOutputCurrentRThe measured upsE module output mandatory from the UPS meters in 0.1 A.ro NonNegativeInteger (UPS-MIB) .1.3.6.1.4.1.935.10.1.1.4.2.1.7 |
upsEModuleOutputWattRThe measured upsE module output watts from the UPS meters in watts.ro NonNegativeInteger (UPS-MIB) .1.3.6.1.4.1.935.10.1.1.4.2.1.8 |
upsEModuleOutputLoadRThe output load of UPS modules in %.ro INTEGER .1.3.6.1.4.1.935.10.1.1.4.2.1.9 |
upsEModuleWarningCodeThe warning code of ups modules.Please refer the warning table of 'QU,XX' for details.ro DisplayString ( SIZE ( 0 .. 15 ) ) .1.3.6.1.4.1.935.10.1.1.4.2.1.10 |
upsEModuleFaultCodeThe fault code of ups modules.Please refer command 'QU,XX' for details.ro DisplayString ( SIZE ( 0 .. 15 ) ) .1.3.6.1.4.1.935.10.1.1.4.2.1.11 |
upsEModuleTrapStatethe values indicate the unrestored traps.
For example, after AC fail, so the value of upsETrapState should be '1'.
And then the AC restore, the value of upsEModuleTrapState
should change to empty.ro DisplayString ( SIZE ( 0 .. 127 ) ) .1.3.6.1.4.1.935.10.1.1.4.2.1.12 |
upsEModuleConfigOutputVAThe magnitude of the nominal Volt-Amp rating presented in VA.ro NonNegativeInteger (UPS-MIB) .1.3.6.1.4.1.935.10.1.1.4.2.1.13 |
upsEModuleOutputCurrentSThe measured upsE module output mandatory from the UPS meters in 0.1 A.ro NonNegativeInteger (UPS-MIB) .1.3.6.1.4.1.935.10.1.1.4.2.1.14 |
upsEModuleOutputCurrentTThe measured upsE module output mandatory from the UPS meters in 0.1 A.ro NonNegativeInteger (UPS-MIB) .1.3.6.1.4.1.935.10.1.1.4.2.1.15 |
upsEModuleOutputWattSThe measured upsE module output watts from the UPS meters in watts.ro NonNegativeInteger (UPS-MIB) .1.3.6.1.4.1.935.10.1.1.4.2.1.16 |
upsEModuleOutputWattTThe measured upsE module output watts from the UPS meters in watts.ro NonNegativeInteger (UPS-MIB) .1.3.6.1.4.1.935.10.1.1.4.2.1.17 |
upsEModuleOutputLoadSThe output load of UPS modules in %.ro INTEGER .1.3.6.1.4.1.935.10.1.1.4.2.1.18 |
upsEModuleOutputLoadTThe output load of UPS modules in %.ro INTEGER .1.3.6.1.4.1.935.10.1.1.4.2.1.19 |
upsEModuleOutputVARThe magnitude of the nominal Volt-Amp rating presented in VA.ro NonNegativeInteger (UPS-MIB) .1.3.6.1.4.1.935.10.1.1.4.2.1.20 |
upsEModuleOutputVASThe magnitude of the nominal Volt-Amp rating presented in VA.ro NonNegativeInteger (UPS-MIB) .1.3.6.1.4.1.935.10.1.1.4.2.1.21 |
upsEModuleOutputVATThe magnitude of the nominal Volt-Amp rating presented in VA.ro NonNegativeInteger (UPS-MIB) .1.3.6.1.4.1.935.10.1.1.4.2.1.22 |
upsELoadSegment OBJECT IDENTIFIER .1.3.6.1.4.1.935.10.1.1.5 |
upsELoadSegment1OffDelaySetting this object will shutdown the UPS Load Segment output after the indicated number of seconds, or less.
Setting this object to 0 will cause the shutdown to occur immediately. Setting this object to -1 will
abort the countdown. Read this object will get countdown value of the Load Segment.rw INTEGER .1.3.6.1.4.1.935.10.1.1.5.1 |
upsELoadSegment1OnDelaySetting this object will start the Load segment output after the indicated number of seconds,
including starting the UPS, if necessary. Setting this object to 0 will cause the startup
to occur immediately. Setting this object to -1 will abort the countdown.rw INTEGER .1.3.6.1.4.1.935.10.1.1.5.2 |
upsELoadSegment1AutoOffTimerThe load segment turns automatically off after the delay while the unit operates on battery,
but the shutdown is cancelled if the utility return before the delay has expired.rw INTEGER .1.3.6.1.4.1.935.10.1.1.5.3 |
upsELoadSegment1AutoOnTimerThe load segment is automatically turned on after a selected delay
if it has been shutdown due to on battery.rw INTEGER .1.3.6.1.4.1.935.10.1.1.5.4 |
upsELoadSegment1StateLoad segment output state.ro Enumeration .1.3.6.1.4.1.935.10.1.1.5.5 |
upsELoadSegment2OffDelaySetting this object will shutdown the UPS Load Segment output after the indicated number of seconds, or less.
Setting this object to 0 will cause the shutdown to occur immediately. Setting this object to -1 will
abort the countdown. Read this object will get countdown value of the Load Segment.rw INTEGER .1.3.6.1.4.1.935.10.1.1.5.6 |
upsELoadSegment2OnDelaySetting this object will start the Load segment output after the indicated number of seconds,
including starting the UPS, if necessary. Setting this object to 0 will cause the startup
to occur immediately. Setting this object to -1 will abort the countdown.rw INTEGER .1.3.6.1.4.1.935.10.1.1.5.7 |
upsELoadSegment2AutoOffTimerThe load segment turns automatically off after the delay while the unit operates on battery,
but the shutdown is cancelled if the utility return before the delay has expired.rw INTEGER .1.3.6.1.4.1.935.10.1.1.5.8 |
upsELoadSegment2AutoOnTimerThe load segment is automatically turned on after a selected delay
if it has been shutdown due to on battery.rw INTEGER .1.3.6.1.4.1.935.10.1.1.5.9 |
upsELoadSegment2StateLoad segment output state.ro Enumeration .1.3.6.1.4.1.935.10.1.1.5.10 |
upsEEnvironment OBJECT IDENTIFIER .1.3.6.1.4.1.935.10.1.1.6 |
upsEEnvironmentTemperature OBJECT IDENTIFIER .1.3.6.1.4.1.935.10.1.1.6.1 |
upsEEnvironmentCurrentTemperatureThe measurement of temperature sensor, in 0.1 degreero INTEGER .1.3.6.1.4.1.935.10.1.1.6.1.1 |
upsEEnvironmentTemperatureHighSetPointThe set point for high temperature warning, in 0.1 degrees.
This value must be greater than upsEEnvironmentTemperatureLowSetPoint,
and the least significant digit must be zero.rw INTEGER .1.3.6.1.4.1.935.10.1.1.6.1.2 |
upsEEnvironmentTemperatureHighStatusTo enable/disable high set point check with sensor temperature.rw Enumeration .1.3.6.1.4.1.935.10.1.1.6.1.3 |
upsEEnvironmentTemperatureLowSetPointThe set point for low temperature warning, in 0.1 degrees.
This value must be less than upsEEnvironmentTemperatureHighSetPoint,
and the least significant digit must be zero.rw INTEGER .1.3.6.1.4.1.935.10.1.1.6.1.4 |
upsEEnvironmentTemperatureLowStatusTo enable/disable low set point check with sensor temperature.rw Enumeration .1.3.6.1.4.1.935.10.1.1.6.1.5 |
upsEEnvironmentTemperatureOffsetThe offset to calibrate temperature of EMD, in 0.1 degreesrw INTEGER .1.3.6.1.4.1.935.10.1.1.6.1.6 |
upsEEnvironmentHumidity OBJECT IDENTIFIER .1.3.6.1.4.1.935.10.1.1.6.2 |
upsEEnvironmentCurrentHumidityThe measurement of sensor humidity present in %.ro INTEGER .1.3.6.1.4.1.935.10.1.1.6.2.1 |
upsEEnvironmentHumidityHighSetPointThe set point for high humidity warning, in %.
This value must be greater than upsEEnvironmentHumidityLowSetPoint.rw INTEGER .1.3.6.1.4.1.935.10.1.1.6.2.2 |
upsEEnvironmentHumidityHighStatusTo enable/disable high set point check with emd humidity.rw Enumeration .1.3.6.1.4.1.935.10.1.1.6.2.3 |
upsEEnvironmentHumidityLowSetPointThe set point for low humidity warning, in %.
This value must be less than upsEEnvironmentHumidityHighSetPoint.rw INTEGER .1.3.6.1.4.1.935.10.1.1.6.2.4 |
upsEEnvironmentHumidityLowStatusTo enable/disable high set point check with emd humidity.rw Enumeration .1.3.6.1.4.1.935.10.1.1.6.2.5 |
upsEEnvironmentHumidityOffsetThe offset to calibrate humidity of EMD, in %.rw INTEGER .1.3.6.1.4.1.935.10.1.1.6.2.6 |
upsEEnvironmentContactsNumThe number of environment contacts, serves as the table index.ro NonNegativeInteger (UPS-MIB) .1.3.6.1.4.1.935.10.1.1.6.3 |
upsEEnvironmentContactTableA list of contacts table entries. The number of entries is given by the
value of upsEEnvironmentContactsNum SEQUENCE OF UpsEEnvironmentContactEntry .1.3.6.1.4.1.935.10.1.1.6.4 |
upsEEnvironmentContactEntryAn entry containing information applicable to a particular contact UpsEEnvironmentContactEntry .1.3.6.1.4.1.935.10.1.1.6.4.1 |
upsEEnvironmentContactIndexThe number of environment contacts. Serves as index for environment contact table PositiveInteger (UPS-MIB) .1.3.6.1.4.1.935.10.1.1.6.4.1.1 |
upsEEnvironmentContactTypeoperation typerw Enumeration .1.3.6.1.4.1.935.10.1.1.6.4.1.2 |
upsEEnvironmentContactStateThe mandatory status.ro Enumeration .1.3.6.1.4.1.935.10.1.1.6.4.1.3 |
upsEEnvironmentContactDescriptionDescription of environment contact.rw DisplayString ( SIZE ( 0 .. 31 ) ) .1.3.6.1.4.1.935.10.1.1.6.4.1.4 |
upsEBatteryTest OBJECT IDENTIFIER .1.3.6.1.4.1.935.10.1.1.7 |
upsEBatteryTestStartThis object specify the battery test type and initiate battery test.
If battTestWithTime selected, the test time is refer to upsEBatteryTestSettingTime.rw Enumeration .1.3.6.1.4.1.935.10.1.1.7.1 |
upsEBatteryTestSettingTimeThe object specify the test time for battery test in seconds.rw NonNegativeInteger (UPS-MIB) .1.3.6.1.4.1.935.10.1.1.7.2 |
upsEBatteryTestResultThis object indicate the test result of battery.ro Enumeration .1.3.6.1.4.1.935.10.1.1.7.3 |
upsEBatteryTestStartTimeThe value of the time the test in progress was initiated,
or, if no test is in progress, the time the previous test
was initiated. If the value of upsETestBatteryTestResult
is noTestsInitiated(6), upsETestStartTime has the value
01/01/1970 00:00:00.ro DisplayString ( SIZE ( 19 .. 19 ) ) .1.3.6.1.4.1.935.10.1.1.7.4 |
upsEBatteryTestElapsedTimeThe amount of time in format hh:mm:ss, since the test in progress
was initiated, or, if no test is in progress, the previous
test took to complete. If the value of upsTestResultsSummary
is idle(1), upsTestElapsedTime has the value 00:00:00.ro DisplayString ( SIZE ( 11 .. 11 ) ) .1.3.6.1.4.1.935.10.1.1.7.5 |
upsEBatteryTestScheduleTableThis table describes the schedule for automatically battery
test. SEQUENCE OF UpsBatteryTestScheduleEntry .1.3.6.1.4.1.935.10.1.1.7.6 |
upsEBatteryTestScheduleEntryAn entry containing information applicable to schedule test. UpsBatteryTestScheduleEntry .1.3.6.1.4.1.935.10.1.1.7.6.1 |
upsEBatteryTestScheduleIndexThe index of battery test scheduled. PositiveInteger (UPS-MIB) .1.3.6.1.4.1.935.10.1.1.7.6.1.1 |
upsEBatteryTestScheduleDayThe weekday or specaial day on which the UPS should start battery test.rw Enumeration .1.3.6.1.4.1.935.10.1.1.7.6.1.2 |
upsEBatteryTestScheduleTimeThe time that the battery test will be initiated in hh:mm format.rw DisplayString ( SIZE ( 5 ) ) .1.3.6.1.4.1.935.10.1.1.7.6.1.3 |
upsEBatteryTestScheduleTypeThe type of battery test.rw Enumeration .1.3.6.1.4.1.935.10.1.1.7.6.1.5 |
upsEBatteryTestScheduleTestWithTimeThe battery time of setting time test in seconds.rw NonNegativeInteger (UPS-MIB) .1.3.6.1.4.1.935.10.1.1.7.6.1.6 |
upsEBatteryTestScheduleSpecialDayThe special day that the battery test will be initiated in dd/mm/yyyy format.rw DisplayString ( SIZE ( 10 ) ) .1.3.6.1.4.1.935.10.1.1.7.6.1.7 |
upsEControl OBJECT IDENTIFIER .1.3.6.1.4.1.935.10.1.1.8 |
upsEControlOutputOffDelaySetting this value to other than zero will cause the UPS
output to turn off after the number of seconds.rw NonNegativeInteger (UPS-MIB) .1.3.6.1.4.1.935.10.1.1.8.1 |
upsEControlOutputOnDelaySetting this value to other than zero will cause the
UPS output to turn on after the number of seconds.rw NonNegativeInteger (UPS-MIB) .1.3.6.1.4.1.935.10.1.1.8.2 |
upsEControlOutputOnOffControlupsEOutputOff ( 1 ) indicates the shutdown sequence,
upsEOutputOffCancel ( 2 ) indicates cancel the shutdown sequence,
upsESleep( 3 ) indicates shutdown UPS first, then switch on.rw Enumeration .1.3.6.1.4.1.935.10.1.1.8.3 |
upsEShutdownEventsTableThis table describes the parametes for shutdown process
when shutdown event occurs SEQUENCE OF UpsShutdownEventsEntry .1.3.6.1.4.1.935.10.1.1.8.4 |
upsEShutdownEventsEntryAn entry containing information applicable to a particular shutdown
event line UpsShutdownEventsEntry .1.3.6.1.4.1.935.10.1.1.8.4.1 |
upsEShutdownEventThe shutdown event identification Enumeration .1.3.6.1.4.1.935.10.1.1.8.4.1.1 |
upsEShutdownEventActionStatus of the corresponding shutdown Event.
When set to disable(), shutdown process will not start when
corresponding event occured.rw Enumeration .1.3.6.1.4.1.935.10.1.1.8.4.1.2 |
upsEShutdownwarningPeriodTimeThe Delay in seconds after the occurance of the curresponding shutdown
event, and warning message should be popped in this period.rw NonNegativeInteger (UPS-MIB) .1.3.6.1.4.1.935.10.1.1.8.4.1.3 |
upsEShutdownWarningPeriodIntervalThe frequency of sending warning messages to the connected
clients when the curresponding shutdown event occurs.
The value is in units of seconds.rw NonNegativeInteger (UPS-MIB) .1.3.6.1.4.1.935.10.1.1.8.4.1.4 |
upsEControlWeeklyScheduleTableThe table to schedule shutting down the ups by weekly SEQUENCE OF UpsControlWeeklyScheduleEntry .1.3.6.1.4.1.935.10.1.1.8.5 |
upsEControlWeeklyScheduleEntryAn entry containing information applicable to a particular line UpsControlWeeklyScheduleEntry .1.3.6.1.4.1.935.10.1.1.8.5.1 |
upsEControlWeeklyScheduleIndexthe index of schedule events. PositiveInteger (UPS-MIB) .1.3.6.1.4.1.935.10.1.1.8.5.1.1 |
upsEWeeklyScheduleShutdownDaythe weekday on which upsE shoud shutdownrw Enumeration .1.3.6.1.4.1.935.10.1.1.8.5.1.2 |
upsEWeeklyScheduleShutdownTimeThe time that the process of shutting down the UPS will be initiated
in hh:mm format.rw DisplayString ( SIZE ( 5 ) ) .1.3.6.1.4.1.935.10.1.1.8.5.1.3 |
upsEWeeklyScheduleRestartDaythe weekday on which the UPS should restart.rw Enumeration .1.3.6.1.4.1.935.10.1.1.8.5.1.4 |
upsEWeeklyScheduleRestartTimeThe time the UPS will restart in hh:mm format.rw DisplayString ( SIZE ( 5 .. 5 ) ) .1.3.6.1.4.1.935.10.1.1.8.5.1.5 |
upsEControlSpecialDayScheduleTableThe table to schedule shutting down the ups. SEQUENCE OF UpsControlSpecialDayScheduleEntry .1.3.6.1.4.1.935.10.1.1.8.6 |
upsEControlSpecialDayScheduleEntryAn entry containing information applicable to a particular line. UpsControlSpecialDayScheduleEntry .1.3.6.1.4.1.935.10.1.1.8.6.1 |
upsEControlSpecialDayScheduleIndexThe index of special day schedule. PositiveInteger (UPS-MIB) .1.3.6.1.4.1.935.10.1.1.8.6.1.1 |
upsESpecialDayScheduleShutdownDayThe special day on which UPS should shutdown with the format
of DD/MM/YYYY.rw DisplayString ( SIZE ( 10 .. 10 ) ) .1.3.6.1.4.1.935.10.1.1.8.6.1.2 |
upsESpecialDayScheduleShutdownTimeThe time that the process of shutting down the UPS will be initiated
in hh:mm format.rw DisplayString ( SIZE ( 5 .. 5 ) ) .1.3.6.1.4.1.935.10.1.1.8.6.1.3 |
upsESpecialDayScheduleRestartDayThe special day on which the UPS should restart with the format
of DD/MM/YYYY.rw DisplayString ( SIZE ( 10 .. 10 ) ) .1.3.6.1.4.1.935.10.1.1.8.6.1.4 |
upsESpecialDayScheduleRestartTimeThe time the UPS will restart in hh:mm format.rw DisplayString ( SIZE ( 5 .. 5 ) ) .1.3.6.1.4.1.935.10.1.1.8.6.1.5 |
upsESystemMasterOffDelayThe UPS output will shutdown after the indicated number of seconds, -1 indicate no action.ro INTEGER .1.3.6.1.4.1.935.10.1.1.8.7 |
upsESystemMasterOnDelayThe UPS output will start on after the indicated number of seconds, -1 indicate no action.ro INTEGER .1.3.6.1.4.1.935.10.1.1.8.8 |
upsETrapControl OBJECT IDENTIFIER .1.3.6.1.4.1.935.10.1.1.9 |
upsETrapsReceiversTableThis table list the managers'IP to send traps to. SEQUENCE OF UpsTrapsReceiversEntry .1.3.6.1.4.1.935.10.1.1.9.1 |
upsETrapsReceiversEntryAn entry containing information applicable to a particular input line. UpsTrapsReceiversEntry .1.3.6.1.4.1.935.10.1.1.9.1.1 |
upsETrapsReceiversIndexThe index to a trap receiver entry PositiveInteger (UPS-MIB) .1.3.6.1.4.1.935.10.1.1.9.1.1.1 |
upsETrapsReceiverAddressThe IP address of the manager to send a trap to.rw DisplayString ( SIZE ( 0 .. 45 ) ) .1.3.6.1.4.1.935.10.1.1.9.1.1.2 |
upsETrapReceiverCommunityStringThe community name to use in the trap when
sent to the manager.rw DisplayString ( SIZE ( 0 .. 32 ) ) .1.3.6.1.4.1.935.10.1.1.9.1.1.3 |
upsETrapTypeThe type of trap to be received by the manager.rw Enumeration .1.3.6.1.4.1.935.10.1.1.9.1.1.4 |
upsETrapsSeverityLevelThe severity level of traps to be received by this manager.rw Enumeration .1.3.6.1.4.1.935.10.1.1.9.1.1.5 |
upsETrapReceiverDescriptionDescription of trap receiversrw DisplayString ( SIZE ( 0 .. 63 ) ) .1.3.6.1.4.1.935.10.1.1.9.1.1.6 |
upsETrapStatethe values indicate the unrestored traps.
For example, after AC fail, the agent send
the trap 1(AC Fail) and trap 7(battery on) to
NMS. so the value of upsETrapState should be '1,7'.
And then the AC restore, the value of upsETrapState
should change to empty.ro DisplayString ( SIZE ( 0 .. 127 ) ) .1.3.6.1.4.1.935.10.1.1.9.2 |
upsETraps OBJECT IDENTIFIER .1.3.6.1.4.1.935.10.1.2 |
upsEPowerFailWARNING: Utility power not available. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.1 |
upsEPowerRestoredINFORMATION: Utility power has restored. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.2 |
upsELowBatterySEVERE: The UPS batteries are low and will soon be exhausted. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.3 |
upsEReturnFromLowBatteryINFORMATION: The UPS has return from a low battery condition. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.4 |
upsEFailedSEVERE: The UPS is not working fine. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.5 |
upsEOkINFORMATION: The UPS is working fine. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.6 |
upsEOnBatteryWARNING: The UPS has switched to battery backup power. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.7 |
upsENotOnBatteryINFORMATION: The UPS is not on battery power. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.8 |
upsETestInProgressINFORMATION: The testing is going on ups. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.9 |
upsETestOverINFORMATION: The testing of UPS is completed. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.10 |
upsEBypassOnINFORMATION: The UPS has enabled bypass. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.11 |
upsEOnlineINFORMATION: The UPS is not on Bypass and return to normal status. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.12 |
upsECommunicationLostSEVERE: Communication to the UPS has been lost. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.13 |
upsECommunicationEstablishedINFORMATION: Communication with the UPS has been established. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.14 |
upsEGoingShutdownWARNING: The UPS is going to shutdown output. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.15 |
upsEShutdownCancelledINFORMATION: The UPS is not going to shutdown output. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.16 |
upsEOutlet1GoingShutdownWARNING: The UPS is going to shutdown outlet1. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.17 |
upsEOutlet1ShutdownCancelledINFORMATION: The UPS is not going to shutdown outlet1. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.18 |
upsEOutlet2GoingShutdownWARNING: The UPS is going to shutdown outlet2. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.19 |
upsEOutlet2ShutdownCancelledINFORMATION: The UPS is not going to shutdown outlet2. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.20 |
upsESleepingINFORMATION: UPS has entered sleep mode and power to load has been cut off. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.21 |
upsEWokeUpINFORMATION: The UPS woke up from sleep mode and power to load has been restored. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.22 |
upsEOverTemperatureWARNING: The UPS temperature is over the setting limit. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.23 |
upsENotOverTemperatureINFORMATION: The UPS temperature is not over the setting limit. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.24 |
upsEOverLoadWARNING: The UPS load is over the setting limit. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.25 |
upsENotOverLoadINFORMATION: The UPS load is not over the setting limit. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.26 |
upsEModuleInsertedWARNING: UPS module or charger module plug-in. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.27 |
upsEModuleRemovedWARNING: UPS module or charger module unplugs. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.28 |
sensorTemperatureTooHighWARNING: Sensor Temperature over high Set point. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.29 |
sensorTemperatureNotHighINFORMATION: Sensor Temperature not over high Set point. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.30 |
sensorTemperatureTooLowWARNING: Sensor Temperature under low Set point. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.31 |
sensorTemperatureNotLowINFORMATION: Sensor Temperature not under low Set point. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.32 |
sensorHumidityTooHighWARNING: Sensor Humidity over high Set point. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.33 |
sensorHumidityNotHighINFORMATION: Sensor Humidity not over high Set point. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.34 |
sensorHumidityTooLowWARNING: Sensor Humidity under low Set point. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.35 |
sensorHumidityNotLowINFORMATION: Sensor Humidity not under low Set point. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.36 |
contactAlarm1Active} TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.37 |
concactAlarm1Normal} TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.38 |
contactAlarm2Active} TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.39 |
contactAlarm2Normal} TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.40 |
upsEInternalwarningWARNING: Internal warning. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.41 |
upsEReturnFromInternalwarningINFORMATION: Return from Internal warning. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.42 |
upsEEPOActiveWARNING: EPO Active. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.43 |
upsEReturnFromEPOActiveINFORMATION: Return from EPO Active. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.44 |
upsEModuleUnlockWARNING: Module Unlock. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.45 |
upsEReturnFromModuleUnlockINFORMATION: Return from Module Unlock. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.46 |
upsEMain1NeutrallossWARNING: Main 1 Neutral loss. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.47 |
upsEReturnFromMain1NeutrallossINFORMATION: Return from Main 1 Neutral loss. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.48 |
upsEMain1phaseerrorWARNING: Main 1 phase error. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.49 |
upsEReturnFromMain1phaseerrorINFORMATION: Return from Main 1 phase error. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.50 |
upsESitefaultWARNING: Site fault. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.51 |
upsEReturnFromSitefaultINFORMATION: Return from Site fault. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.52 |
upsEBypassAbnormalWARNING: Bypass Abnormal. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.53 |
upsEReturnFromBypassAbnormalINFORMATION: Return from Bypass Abnormal. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.54 |
upsEBypassPhaseErrorWARNING: Bypass Phase Error. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.55 |
upsEReturnFromBypassPhaseErrorINFORMATION: Return from Bypass Phase Error. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.56 |
upsEBatteryOpenWARNING: Battery Open. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.57 |
upsEReturnFromBatteryOpenINFORMATION: Return from Battery Open. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.58 |
upsEBatteryOverChargeWARNING: Battery Over Charge. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.59 |
upsEReturnFromBatteryOverChargeINFORMATION: Return from Battery Over Charge. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.60 |
upsEBatteryReverseWARNING: Battery Reverse. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.61 |
upsEReturnFromBatteryReverseINFORMATION: Return from Battery Reverse. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.62 |
upsEOverloadforewarningWARNING: Overload forewarning. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.63 |
upsEReturnFromOverloadforewarningINFORMATION: Return from Overload forewarning. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.64 |
upsEOverloadWarningWARNING: Overload Warning. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.65 |
upsEReturnFromOverloadWarningINFORMATION: Return from Overload Warning. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.66 |
upsEFanLockWARNING: Fan Lock. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.67 |
upsEReturnFromFanLockINFORMATION: Return from Fan Lock. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.68 |
upsEMaintaincoverisopenWARNING: Maintain cover is open. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.69 |
upsEReturnFromMaintaincoverisopenINFORMATION: Return from Maintain cover is open. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.70 |
upsEChargerfaultWARNING: Charger fault. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.71 |
upsEReturnFromChargerfaultINFORMATION: Return from Charger fault. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.72 |
upsEModulelocationerrorWARNING: Module location error. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.73 |
upsEReturnFromModulelocationerrorINFORMATION: Return from Module location error. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.74 |
upsETurnonabnormalWARNING: Turn on abnormal. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.75 |
upsEReturnFromTurnonabnormalINFORMATION: Return from Turn on abnormal. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.76 |
upsERedundancylossWARNING: Redundancy loss. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.77 |
upsEReturnFromRedundancylossINFORMATION: Return from Redundancy loss. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.78 |
upsEHotSwapActivedWARNING: Hot Swap Active. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.79 |
upsEReturnFromHotSwapActivedINFORMATION: Return from Hot Swap Active. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.80 |
upsEBatteryInformWARNING: Battery Inform. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.81 |
upsEReturnFromBatteryInformINFORMATION: Return from Battery Inform. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.82 |
upsEInspectionInformWARNING: Inspection Inform. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.83 |
upsEReturnFromInspectionInformINFORMATION: Return from Inspection Inform. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.84 |
upsEGuaranteeInformWARNING: Guarantee Inform. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.85 |
upsEReturnFromGuaranteeInformINFORMATION: Return from Guarantee Inform. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.86 |
upsETemperatureLowWARNING: Temperature Low. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.87 |
upsEReturnFromTemperatureLowINFORMATION: Return from Temperature Low. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.88 |
upsETemperatureHighWARNING: Temperature High. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.89 |
upsEReturnFromTemperatureHighINFORMATION: Return from Temperature High. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.90 |
upsEBatteryOverTemperatureWARNING: Battery Over Temperature. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.91 |
upsEReturnFromBatteryOverTemperatureINFORMATION: Return from Battery Over Temperature. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.92 |
upsEFanMaintainInformWARNING: Fan Maintain Inform. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.93 |
upsEReturnFromFanMaintainInformINFORMATION: Return from Fan Maintain Inform. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.94 |
upsEBusCapacitanceMaintainInformWARNING: Bus Capacitance Maintain Inform. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.95 |
upsEReturnFromBusCapacitanceMaintainInformINFORMATION: Return from Bus Capacitance Maintain Inform. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.96 |
upsESystemOverCapacityWARNING: System Over Capacity. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.97 |
upsEReturnFromSystemOverCapacityINFORMATION: Return from System Over Capacity. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.98 |
upsEBelowCapacityLimitSEVERE: The UPS batteries capacity is lower than setting limit. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.123 |
upsENotBelowCapacityLimitINFORMATION: The UPS batteries capacity is not lower than setting limit. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.124 |
upsEBelowRemainTimeLimitSEVERE: The UPS batteries backup time is below the setting limit. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.125 |
upsENotBelowRemainTimeLimitINFORMATION: The UPS batteries backup time is not below the setting limit. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.126 |
upsELoadSegment1OffWARNING: Load segment 1 is off. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.127 |
upsELoadSegment1OnINFORMATION: Load segment 1 is on. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.128 |
upsELoadSegment2OffWARNING: Load segment 2 is off. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.129 |
upsELoadSegment2OnINFORMATION: Load segment 2 is on. TRAP-TYPE .1.3.6.1.4.1.935.10.1.2.0.130 |