VERTIV-V5-MIB

AI MIB Summary

The VERTIV-V5-MIB module provides SNMP-based monitoring and management capabilities for Vertiv power and thermal infrastructure devices, including UPS systems, precision cooling units, and environmental sensors. It exposes critical operational metrics such as input/output voltage and current, battery status, temperature readings, fan speeds, and alarm states to facilitate real-time infrastructure health assessment.

The MIB for Vertiv products
Main OID:
vertiv.1.3.6.1.4.1.21239
570
Objects
Active
Status
4
Dependencies

Imported Objects

Objects

570 total
Object Name
vertivThe MIB for Vertiv products
MODULE-IDENTITY
.1.3.6.1.4.1.21239
v5
OBJECT IDENTIFIER
.1.3.6.1.4.1.21239.5
imd
OBJECT IDENTIFIER
.1.3.6.1.4.1.21239.5.2
deviceInfo
OBJECT IDENTIFIER
.1.3.6.1.4.1.21239.5.2.1
productTitleProduct namero
SnmpAdminString (SNMP-FRAMEWORK-MIB)
.1.3.6.1.4.1.21239.5.2.1.1
productVersionProduct versionro
SnmpAdminString (SNMP-FRAMEWORK-MIB)
.1.3.6.1.4.1.21239.5.2.1.2
productFriendlyNameUser-assigned namero
SnmpAdminString (SNMP-FRAMEWORK-MIB)
.1.3.6.1.4.1.21239.5.2.1.3
productMacAddressProduct's unique MAC addressro
MacAddress (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.1.4
deviceCountTotal number of devices on unitro
Integer32
.1.3.6.1.4.1.21239.5.2.1.6
temperatureUnitsCurrent units for temperature/dewpoint values: 0 = Degrees Fahrenheit 1 = Degrees Celsiusrw
Enumeration
.1.3.6.1.4.1.21239.5.2.1.7
productModelNumberProduct model number (factory-assigned)ro
SnmpAdminString (SNMP-FRAMEWORK-MIB)
.1.3.6.1.4.1.21239.5.2.1.8
productPartNumberProduct part number (factory-assigned)ro
SnmpAdminString (SNMP-FRAMEWORK-MIB)
.1.3.6.1.4.1.21239.5.2.1.9
productSerialNumberProduct serial number (factory-assigned)ro
SnmpAdminString (SNMP-FRAMEWORK-MIB)
.1.3.6.1.4.1.21239.5.2.1.10
productPlatformProduct platformro
SnmpAdminString (SNMP-FRAMEWORK-MIB)
.1.3.6.1.4.1.21239.5.2.1.11
productHostnameProduct hostnamero
SnmpAdminString (SNMP-FRAMEWORK-MIB)
.1.3.6.1.4.1.21239.5.2.1.12
productAlarmCountNumber of alarms currently trippedro
Integer32
.1.3.6.1.4.1.21239.5.2.1.13
productWarnCountNumber of warnings currently trippedro
Integer32
.1.3.6.1.4.1.21239.5.2.1.14
productManufacturerProduct manufacturerro
SnmpAdminString (SNMP-FRAMEWORK-MIB)
.1.3.6.1.4.1.21239.5.2.1.15
pdu
OBJECT IDENTIFIER
.1.3.6.1.4.1.21239.5.2.3
pduMainTablePDU general information
SEQUENCE OF PduMainEntry
.1.3.6.1.4.1.21239.5.2.3.1
pduMainEntryEntry in the pduMainTable table: each entry contains an index and other sensor details
PduMainEntry
.1.3.6.1.4.1.21239.5.2.3.1.1
pduMainIndexTable entry index value
Integer32
.1.3.6.1.4.1.21239.5.2.3.1.1.1
pduMainSerialSerial numberro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.3.1.1.2
pduMainNamePDU name (factory-assigned)ro
SnmpAdminString
.1.3.6.1.4.1.21239.5.2.3.1.1.3
pduMainLabelPDU label (user-defined)rw
SnmpAdminString
.1.3.6.1.4.1.21239.5.2.3.1.1.4
pduMainAvailDevice availability: 0 = Unavailable 1 = Available 2 = Partially Unavailablero
Gauge32
.1.3.6.1.4.1.21239.5.2.3.1.1.5
pduMeterTypeCurrent meter type: 0 = Wye 1 = Deltaro
Enumeration
.1.3.6.1.4.1.21239.5.2.3.1.1.6
pduTotalNameTotal name (factory-assigned)ro
SnmpAdminString
.1.3.6.1.4.1.21239.5.2.3.1.1.7
pduTotalLabelTotal label (user-defined)rw
SnmpAdminString
.1.3.6.1.4.1.21239.5.2.3.1.1.8
pduTotalRealPowerPDU total real powerro
Gauge32
.1.3.6.1.4.1.21239.5.2.3.1.1.9
pduTotalApparentPowerPDU total apparent powerro
Gauge32
.1.3.6.1.4.1.21239.5.2.3.1.1.10
pduTotalPowerFactorPDU total power factorro
Gauge32
.1.3.6.1.4.1.21239.5.2.3.1.1.11
pduTotalEnergyPDU total accumulated energy in watt-hoursro
Gauge32
.1.3.6.1.4.1.21239.5.2.3.1.1.12
pduPhaseTablePDU phases information
SEQUENCE OF PduPhaseEntry
.1.3.6.1.4.1.21239.5.2.3.2
pduPhaseEntryEntry in the pduPhaseTable table: each entry contains an index and other sensor details
PduPhaseEntry
.1.3.6.1.4.1.21239.5.2.3.2.1
pduPhaseIndexTable entry index value
Integer32
.1.3.6.1.4.1.21239.5.2.3.2.1.1
pduPhaseNamePDU phase name (factory-assigned)ro
SnmpAdminString
.1.3.6.1.4.1.21239.5.2.3.2.1.2
pduPhaseLabelPDU phase label (user-defined)rw
SnmpAdminString
.1.3.6.1.4.1.21239.5.2.3.2.1.3
pduPhaseVoltagePDU phase voltage in tenths of a voltro
Gauge32
.1.3.6.1.4.1.21239.5.2.3.2.1.4
pduPhaseCurrentPDU phase current reading in hundredths of an ampro
Gauge32
.1.3.6.1.4.1.21239.5.2.3.2.1.8
pduPhaseRealPowerReal power for phase in wattsro
Gauge32
.1.3.6.1.4.1.21239.5.2.3.2.1.12
pduPhaseApparentPowerApparent power for phase in volt-ampsro
Gauge32
.1.3.6.1.4.1.21239.5.2.3.2.1.13
pduPhasePowerFactorPower factor for phasero
Gauge32
.1.3.6.1.4.1.21239.5.2.3.2.1.14
pduPhaseEnergyAccumulated energy for phase in watt-hoursro
Gauge32
.1.3.6.1.4.1.21239.5.2.3.2.1.15
pduPhaseBalancePhase balance as percentro
Gauge32
.1.3.6.1.4.1.21239.5.2.3.2.1.17
pduPhaseCurrentCrestFactorCurrent crest factor for phase, in hundredthsro
Gauge32
.1.3.6.1.4.1.21239.5.2.3.2.1.19
pduBreakerTablePDU breaker information
SEQUENCE OF PduBreakerEntry
.1.3.6.1.4.1.21239.5.2.3.3
pduBreakerEntryEntry in the pduBreakerTable table: each entry contains an index and other sensor details
PduBreakerEntry
.1.3.6.1.4.1.21239.5.2.3.3.1
pduBreakerIndexTable entry index value
Integer32
.1.3.6.1.4.1.21239.5.2.3.3.1.1
pduBreakerNamePDU breaker name (factory-assigned)ro
SnmpAdminString
.1.3.6.1.4.1.21239.5.2.3.3.1.2
pduBreakerLabelPDU breaker label (user-defined)rw
SnmpAdminString
.1.3.6.1.4.1.21239.5.2.3.3.1.3
pduBreakerCurrentPDU breaker current reading in hundredths of an ampro
Gauge32
.1.3.6.1.4.1.21239.5.2.3.3.1.4
pduBreakerVoltagePDU breaker voltage in tenths of a volt. This object may not exist on all platforms, due to hardware differences.ro
Gauge32
.1.3.6.1.4.1.21239.5.2.3.3.1.8
pduBreakerRealPowerReal power for breaker in watts. This object may not exist on all platforms, due to hardware differences.ro
Gauge32
.1.3.6.1.4.1.21239.5.2.3.3.1.12
pduBreakerApparentPowerApparent power for breaker in volt-amps. This object may not exist on all platforms, due to hardware differences.ro
Gauge32
.1.3.6.1.4.1.21239.5.2.3.3.1.13
pduBreakerPowerFactorPower factor for breaker. This object may not exist on all platforms, due to hardware differences.ro
Gauge32
.1.3.6.1.4.1.21239.5.2.3.3.1.14
pduBreakerEnergyAccumulated energy for breaker in watt-hours. This object may not exist on all platforms, due to hardware differences.ro
Gauge32
.1.3.6.1.4.1.21239.5.2.3.3.1.15
pduLineTablePDU line current information
SEQUENCE OF PduLineEntry
.1.3.6.1.4.1.21239.5.2.3.4
pduLineEntryEntry in the pduLineTable table: each entry contains an index and other sensor details
PduLineEntry
.1.3.6.1.4.1.21239.5.2.3.4.1
pduLineIndexTable entry index value
Integer32
.1.3.6.1.4.1.21239.5.2.3.4.1.1
pduLineNamePDU line name (factory-assigned)ro
SnmpAdminString
.1.3.6.1.4.1.21239.5.2.3.4.1.2
pduLineLabelPDU line label (user-defined)rw
SnmpAdminString
.1.3.6.1.4.1.21239.5.2.3.4.1.3
pduLineCurrentPDU line current reading in hundredths of an ampro
Gauge32
.1.3.6.1.4.1.21239.5.2.3.4.1.4
pduOutletSwitchTableData, config and control for outlets with switching
SEQUENCE OF PduOutletSwitchEntry
.1.3.6.1.4.1.21239.5.2.3.5
pduOutletSwitchEntryEntry in the pduOutletSwitchTable table: each entry contains an index and other sensor details
PduOutletSwitchEntry
.1.3.6.1.4.1.21239.5.2.3.5.1
pduOutletSwitchIndexTable entry index value
Integer32
.1.3.6.1.4.1.21239.5.2.3.5.1.1
pduOutletSwitchNamePDU outlet name (factory-assigned)ro
SnmpAdminString
.1.3.6.1.4.1.21239.5.2.3.5.1.2
pduOutletSwitchLabelPDU outlet label (user-defined)rw
SnmpAdminString
.1.3.6.1.4.1.21239.5.2.3.5.1.3
pduOutletSwitchStateSwitch state of the outlet: 1 = Outlet is on 2 = Outlet is off 3 = Outlet is on, but will turn off after a delay 4 = Outlet is off, but will turn on after a delay 5 = Starting reboot cycle, outlet is on, but will go to the rebootOff(6) state after a delay 6 = Rebooting, outlet is off, but it will turn on after a delay 7 = Cannot get outlet statero
Enumeration
.1.3.6.1.4.1.21239.5.2.3.5.1.4
pduOutletSwitchRelayFailureTells if the outlet relay has failed. In normal operation, the value will be false(2).ro
TruthValue (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.3.5.1.5
pduOutletSwitchControlUsed for manual control of the outlet. If the outlet is in manual mode, this field can be set to one of the following values: 1 = Cancel pending operation 2 = Turn outlet on 3 = After delay (pduOutletSwitchOnDelay), turn outlet on 4 = Turn outlet off 5 = After delay (pduOutletSwitchOffDelay), turn outlet off 6 = Reboot: turn off, delay (pduOutletSwitchRebootHoldDelay), turn outlet back on 7 = After delay (pduOutletSwitchRebootDelay), reboot outlet When not in manual mode, setting this field will give an inconsistentValue error. Returns none(8) for all get requests.rw
Enumeration
.1.3.6.1.4.1.21239.5.2.3.5.1.6
pduOutletSwitchTimeToActionSeconds until an outlet state change. The value of pduOutletSwitchState tells what state the outlet will be set, after the delay.ro
Integer32
.1.3.6.1.4.1.21239.5.2.3.5.1.7
pduOutletSwitchOnDelaySeconds to wait before powering on the outlet, during onAfterDelay(3) operation. Changing this value has no effect on pending actions.rw
Integer32
.1.3.6.1.4.1.21239.5.2.3.5.1.8
pduOutletSwitchOffDelaySeconds to wait before powering off the outlet, during offAfterDelay(5) operation. Changing this value has no effect on pending actions.rw
Integer32
.1.3.6.1.4.1.21239.5.2.3.5.1.9
pduOutletSwitchRebootDelaySeconds to wait before powering off the outlet, during rebootAfterDelay(7) operation. Changing this value has no effect on pending actions. See pduOutletSwitchControl for more info.rw
Integer32
.1.3.6.1.4.1.21239.5.2.3.5.1.10
pduOutletSwitchRebootHoldDelaySeconds to hold the outlet off, before powering on the outlet, during rebootAfterDelay(7) operation. Changing this value has no effect on pending actions. See pduOutletSwitchControl for more info.rw
Integer32
.1.3.6.1.4.1.21239.5.2.3.5.1.11
pduOutletSwitchPoaActionThe outlet is set to this state during power-up. The action can be have one the following values: 1 = Outlet will be turned on 2 = Outlet will stay off 3 = Outlet will be set to last known staterw
Enumeration
.1.3.6.1.4.1.21239.5.2.3.5.1.12
pduOutletSwitchPoaDelaySeconds to wait before setting the outlet to the pduOutletSwitchPoaAction state. The delay starts at power-up.rw
Integer32
.1.3.6.1.4.1.21239.5.2.3.5.1.13
pduOutletMeterTableMetering data for outlets that support this feature
SEQUENCE OF PduOutletMeterEntry
.1.3.6.1.4.1.21239.5.2.3.6
pduOutletMeterEntryEntry in the pduOutletMeterTable table: each entry contains an index and other sensor details
PduOutletMeterEntry
.1.3.6.1.4.1.21239.5.2.3.6.1
pduOutletMeterIndexTable entry index value
Integer32
.1.3.6.1.4.1.21239.5.2.3.6.1.1
pduOutletMeterNamePDU outlet name (factory-assigned)ro
SnmpAdminString
.1.3.6.1.4.1.21239.5.2.3.6.1.2
pduOutletMeterLabelPDU outlet label (user-defined)rw
SnmpAdminString
.1.3.6.1.4.1.21239.5.2.3.6.1.3
pduOutletMeterVoltagePDU outlet voltage in tenths of a voltro
Gauge32
.1.3.6.1.4.1.21239.5.2.3.6.1.4
pduOutletMeterCurrentPDU outlet current reading in hundredths of an ampro
Gauge32
.1.3.6.1.4.1.21239.5.2.3.6.1.8
pduOutletMeterRealPowerReal power for outlet in wattsro
Gauge32
.1.3.6.1.4.1.21239.5.2.3.6.1.12
pduOutletMeterApparentPowerApparent power for outlet in volt-ampsro
Gauge32
.1.3.6.1.4.1.21239.5.2.3.6.1.13
pduOutletMeterPowerFactorPower factor for outletro
Gauge32
.1.3.6.1.4.1.21239.5.2.3.6.1.14
pduOutletMeterEnergyAccumulated energy for outlet in watt-hoursro
Gauge32
.1.3.6.1.4.1.21239.5.2.3.6.1.15
pduOutletMeterResetUsed to reset energy. If read, the value is none(8). It can be set to resetEnergy(1), which sets outlet energy to 0rw
Enumeration
.1.3.6.1.4.1.21239.5.2.3.6.1.16
pduOutletCurrentCrestFactorCurrent crest factor for outlet, in hundredthsro
Gauge32
.1.3.6.1.4.1.21239.5.2.3.6.1.19
tempSensorTableRemote Temperature (RT) sensor
SEQUENCE OF TempSensorEntry
.1.3.6.1.4.1.21239.5.2.4
tempSensorEntryEntry in the tempSensorTable table: each entry contains an index and other sensor details
TempSensorEntry
.1.3.6.1.4.1.21239.5.2.4.1
tempSensorIndexTable entry index value
Integer32
.1.3.6.1.4.1.21239.5.2.4.1.1
tempSensorSerialSerial numberro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.4.1.2
tempSensorLabelUser-defined labelrw
SnmpAdminString
.1.3.6.1.4.1.21239.5.2.4.1.3
tempSensorAvailDevice availability: 0 = Unavailable 1 = Available 2 = Partially Unavailablero
Gauge32
.1.3.6.1.4.1.21239.5.2.4.1.4
tempSensorTempTemperature in tenths of a degree. Units are given by temperatureUnits field in deviceInfo.ro
Integer32(-400..2540) UNITS "decidegrees"
.1.3.6.1.4.1.21239.5.2.4.1.5
airFlowSensorTableRemote Airflow, Humidity, Temperature and Dewpoint (AFHT3) Sensor
SEQUENCE OF AirFlowSensorEntry
.1.3.6.1.4.1.21239.5.2.5
airFlowSensorEntryEntry in the airFlowSensorTable table: each entry contains an index and other sensor details
AirFlowSensorEntry
.1.3.6.1.4.1.21239.5.2.5.1
airFlowSensorIndexTable entry index value
Integer32
.1.3.6.1.4.1.21239.5.2.5.1.1
airFlowSensorSerialSerial numberro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.5.1.2
airFlowSensorLabelUser-defined labelrw
SnmpAdminString
.1.3.6.1.4.1.21239.5.2.5.1.3
airFlowSensorAvailDevice availability: 0 = Unavailable 1 = Available 2 = Partially Unavailablero
Gauge32
.1.3.6.1.4.1.21239.5.2.5.1.4
airFlowSensorTempTemperature reading in tenths of a degree. Units are given by temperatureUnits field in deviceInfo.ro
Integer32(-400..2540) UNITS "decidegrees"
.1.3.6.1.4.1.21239.5.2.5.1.5
airFlowSensorFlowAirflow reading. Still air will be less than 20, while rushing air will be around 100.ro
Integer32
.1.3.6.1.4.1.21239.5.2.5.1.6
airFlowSensorHumidityHumidity readingro
Integer32
.1.3.6.1.4.1.21239.5.2.5.1.7
airFlowSensorDewPointDewpoint reading in tenths of a degree. Units are given by temperatureUnits field in deviceInfo.ro
Integer32(-400..2540) UNITS "decidegrees"
.1.3.6.1.4.1.21239.5.2.5.1.8
t3hdSensorTableRemote Temperature x 3, Humidity and Dewpoint Sensor
SEQUENCE OF T3hdSensorEntry
.1.3.6.1.4.1.21239.5.2.8
t3hdSensorEntryEntry in the t3hdSensorTable table: each entry contains an index and other sensor details
T3hdSensorEntry
.1.3.6.1.4.1.21239.5.2.8.1
t3hdSensorIndexTable entry index value
Integer32
.1.3.6.1.4.1.21239.5.2.8.1.1
t3hdSensorSerialSerial numberro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.8.1.2
t3hdSensorLabelUser-defined labelrw
SnmpAdminString
.1.3.6.1.4.1.21239.5.2.8.1.3
t3hdSensorAvailDevice availability: 0 = Unavailable 1 = Available 2 = Partially Unavailablero
Gauge32
.1.3.6.1.4.1.21239.5.2.8.1.4
t3hdSensorIntLabelInternal label (user-defined)rw
SnmpAdminString
.1.3.6.1.4.1.21239.5.2.8.1.5
t3hdSensorIntTempInternal temperature in tenths of a degree. Units are given by temperatureUnits field in deviceInfo.ro
Integer32(-400..2540) UNITS "decidegrees"
.1.3.6.1.4.1.21239.5.2.8.1.6
t3hdSensorIntHumidityInternal humidityro
Integer32
.1.3.6.1.4.1.21239.5.2.8.1.7
t3hdSensorIntDewPointInternal dewpoint in tenths of a degree. Units are given by temperatureUnits field in deviceInfo.ro
Integer32(-400..2540) UNITS "decidegrees"
.1.3.6.1.4.1.21239.5.2.8.1.8
t3hdSensorExtAAvailExternal A status: 0 = Unavailable 1 = Availablero
Gauge32
.1.3.6.1.4.1.21239.5.2.8.1.9
t3hdSensorExtALabelExternal A label (user-defined)rw
SnmpAdminString
.1.3.6.1.4.1.21239.5.2.8.1.10
t3hdSensorExtATempExternal A temperature in tenths of a degree. Units are given by temperatureUnits field in deviceInfo.ro
Integer32(-400..2540) UNITS "decidegrees"
.1.3.6.1.4.1.21239.5.2.8.1.11
t3hdSensorExtBAvailExternal B status: 0 = Unavailable 1 = Availablero
Gauge32
.1.3.6.1.4.1.21239.5.2.8.1.12
t3hdSensorExtBLabelExternal B label (user-defined)rw
SnmpAdminString
.1.3.6.1.4.1.21239.5.2.8.1.13
t3hdSensorExtBTempExternal B temperature in tenths of a degree. Units are given by temperatureUnits field in deviceInfo.ro
Integer32(-400..2540) UNITS "decidegrees"
.1.3.6.1.4.1.21239.5.2.8.1.14
thdSensorTableRemote Temperature, Humidity, and Dewpoint (THD) Sensor
SEQUENCE OF ThdSensorEntry
.1.3.6.1.4.1.21239.5.2.9
thdSensorEntryEntry in the thdSensorTable table: each entry contains an index and other sensor details
ThdSensorEntry
.1.3.6.1.4.1.21239.5.2.9.1
thdSensorIndexTable entry index value
Integer32
.1.3.6.1.4.1.21239.5.2.9.1.1
thdSensorSerialSerial numberro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.9.1.2
thdSensorLabelUser-defined labelrw
SnmpAdminString
.1.3.6.1.4.1.21239.5.2.9.1.3
thdSensorAvailDevice availability: 0 = Unavailable 1 = Available 2 = Partially Unavailablero
Gauge32
.1.3.6.1.4.1.21239.5.2.9.1.4
thdSensorTempTemperature value in tenths of a degree. Units are given by temperatureUnits field in deviceInfo.ro
Integer32(-400..2540) UNITS "decidegrees"
.1.3.6.1.4.1.21239.5.2.9.1.5
thdSensorHumidityHumidity valuero
Integer32
.1.3.6.1.4.1.21239.5.2.9.1.6
thdSensorDewPointDewpoint value in tenths of a degree. Units are given by temperatureUnits field in deviceInfo.ro
Integer32(-400..2540) UNITS "decidegrees"
.1.3.6.1.4.1.21239.5.2.9.1.7
a2dSensorTableAnalog measurement (A2D) sensor (voltage, current, or dry-contact)
SEQUENCE OF A2dSensorEntry
.1.3.6.1.4.1.21239.5.2.11
a2dSensorEntryEntry in the a2dSensorTable table: each entry contains an index and other sensor details
A2dSensorEntry
.1.3.6.1.4.1.21239.5.2.11.1
a2dSensorIndexTable entry index value
Integer32
.1.3.6.1.4.1.21239.5.2.11.1.1
a2dSensorSerialSerial numberro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.11.1.2
a2dSensorLabelUser-defined labelrw
SnmpAdminString
.1.3.6.1.4.1.21239.5.2.11.1.3
a2dSensorAvailDevice availability: 0 = Unavailable 1 = Available 2 = Partially Unavailablero
Gauge32
.1.3.6.1.4.1.21239.5.2.11.1.4
a2dSensorValueAnalog measurement value, within either a user-defined or preset range, depending on a2dSensorMode.ro
Integer32(-1000000..1000000)
.1.3.6.1.4.1.21239.5.2.11.1.5
a2dSensorDisplayValueFor current/voltage modes, the analog value is given as a string. In binary modes, the value is either a2dSensorLowLabel or a2dSensorHighLabel, based on a2dSensorValue.ro
SnmpAdminString
.1.3.6.1.4.1.21239.5.2.11.1.6
a2dSensorModeBinary modes have two states represented by the values 0 (low) or 1 (high). These correspond to a2dSensorLowLabel and a2dSensorHighLabel. Current and voltage modes provide a scaled value from a2dSensorMin to a2dSensorMax. Analog modes: 1 = Door (binary) 2 = Power failure (binary) 3 = Flood (binary) 4 = Water-sensing cable leak (binary) 5 = Water-sensing cable fault (binary) 6 = Smoke alarm (binary) 7 = Isolated voltage negative ground (voltage) 8 = Isolated voltage positive ground (voltage) 9 = Custom voltage (voltage) 10 = Custom binary (binary) 11 = Custom current (current)rw
Enumeration
.1.3.6.1.4.1.21239.5.2.11.1.7
a2dSensorUnitsThe units for the analog value. If a2dSensorMode is customVoltage(9) or customCurrent(11), then this field has a user-defined value. Otherwise, the value is fixed, based on mode.rw
SnmpAdminString
.1.3.6.1.4.1.21239.5.2.11.1.8
a2dSensorMinMinimum analog value, given as an integer. The analog measurement is scaled to the range a2dSensorMin to a2dSensorMax. If a2dSensorMode is customVoltage(9) or customCurrent(11), then this field has a user- defined value. Otherwise, the value is fixed, based on mode.rw
Integer32(-1000000..1000000)
.1.3.6.1.4.1.21239.5.2.11.1.9
a2dSensorMaxMaximum analog value, given as an integer. The analog measurement is scaled to the range a2dSensorMin to a2dSensorMax. If a2dSensorMode is customVoltage(9) or customCurrent(11), then this field has a user- defined value. Otherwise, the value is fixed, based on mode.rw
Integer32(-1000000..1000000)
.1.3.6.1.4.1.21239.5.2.11.1.10
a2dSensorLowLabelLabel for 0 (low) binary value. This field is only applicable if a2dSensorMode is one of the binary modes. If a2dSensorMode is customBinary(10), then this field is user-defined. Otherwise, it has a pre-defined value based on the mode.rw
SnmpAdminString
.1.3.6.1.4.1.21239.5.2.11.1.11
a2dSensorHighLabelLabel for 1 (high) binary value. The field is only applicable if a2dSensorMode is one of the binary modes. If a2dSensorMode is customBinary(10), then this field is user-defined. Otherwise, it has a pre-defined value based on the mode.rw
SnmpAdminString
.1.3.6.1.4.1.21239.5.2.11.1.12
a2dSensorAnalogLabelLabel for the analog measurementrw
SnmpAdminString
.1.3.6.1.4.1.21239.5.2.11.1.13
humiditySensorTableRemote humidity sensor
SEQUENCE OF HumiditySensorEntry
.1.3.6.1.4.1.21239.5.2.12
humiditySensorEntryEntry in the humiditySensorTable table: each entry contains an index and other sensor details
HumiditySensorEntry
.1.3.6.1.4.1.21239.5.2.12.1
humiditySensorIndexTable entry index value
Integer32
.1.3.6.1.4.1.21239.5.2.12.1.1
humiditySensorSerialSerial numberro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.12.1.2
humiditySensorLabelUser-defined labelrw
SnmpAdminString
.1.3.6.1.4.1.21239.5.2.12.1.3
humiditySensorAvailDevice availability: 0 = Unavailable 1 = Available 2 = Partially Unavailablero
Gauge32
.1.3.6.1.4.1.21239.5.2.12.1.4
humiditySensorValueHumidity valuero
Integer32
.1.3.6.1.4.1.21239.5.2.12.1.5
sn2dSensorTable2 Door Switch Sensor (SN-2D)
SEQUENCE OF Sn2dSensorEntry
.1.3.6.1.4.1.21239.5.2.13
sn2dSensorEntryEntry in the sn2dSensorTable table: each entry contains an index and other sensor details
Sn2dSensorEntry
.1.3.6.1.4.1.21239.5.2.13.1
sn2dSensorIndexTable entry index value
Integer32
.1.3.6.1.4.1.21239.5.2.13.1.1
sn2dSensorSerialSerial numberro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.13.1.2
sn2dSensorLabelUser-defined labelrw
SnmpAdminString
.1.3.6.1.4.1.21239.5.2.13.1.3
sn2dSensorAvailDevice availability: 0 = Unavailable 1 = Available 2 = Partially Unavailablero
Gauge32
.1.3.6.1.4.1.21239.5.2.13.1.4
sn2dSensorDoor1LabelDoor switch 1 labelrw
SnmpAdminString
.1.3.6.1.4.1.21239.5.2.13.1.5
sn2dSensorDoor1StateDoor switch 1 state: 1 = open 2 = closedro
Enumeration
.1.3.6.1.4.1.21239.5.2.13.1.6
sn2dSensorDoor1DisplayStateDoor switch 1 state given as a stringro
SnmpAdminString
.1.3.6.1.4.1.21239.5.2.13.1.7
sn2dSensorDoor2LabelDoor switch 2 labelrw
SnmpAdminString
.1.3.6.1.4.1.21239.5.2.13.1.8
sn2dSensorDoor2StateDoor switch 2 state: 1 = open 2 = closedro
Enumeration
.1.3.6.1.4.1.21239.5.2.13.1.9
sn2dSensorDoor2DisplayStateDoor switch 2 state given as a stringro
SnmpAdminString
.1.3.6.1.4.1.21239.5.2.13.1.10
cooling
OBJECT IDENTIFIER
.1.3.6.1.4.1.21239.5.2.30
vrc
OBJECT IDENTIFIER
.1.3.6.1.4.1.21239.5.2.30.1
vrcMainTableTable that contains general VRC information
SEQUENCE OF VrcMainEntry
.1.3.6.1.4.1.21239.5.2.30.1.1
vrcMainEntryEntry in the vrcMainTable: each entry represents a VRC device
VrcMainEntry
.1.3.6.1.4.1.21239.5.2.30.1.1.1
vrcMainIndexUnique id for each entry in the table
Integer32
.1.3.6.1.4.1.21239.5.2.30.1.1.1.1
vrcMainSerialSerial numberro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.30.1.1.1.2
vrcMainNameVRC name (factory-assigned)ro
SnmpAdminString
.1.3.6.1.4.1.21239.5.2.30.1.1.1.3
vrcMainLabelVRC label (user-defined)rw
SnmpAdminString
.1.3.6.1.4.1.21239.5.2.30.1.1.1.4
vrcMainAvailDevice availability: 0 = Unavailable 1 = Available 2 = Partially Unavailablero
Gauge32
.1.3.6.1.4.1.21239.5.2.30.1.1.1.5
vrcMainPtTableTable that contains general VRC status
SEQUENCE OF VrcMainPtEntry
.1.3.6.1.4.1.21239.5.2.30.1.2
vrcMainPtEntryEntry in the vrcMainPtTable: each entry contains status data for a VRC device
VrcMainPtEntry
.1.3.6.1.4.1.21239.5.2.30.1.2.1
vrcMainPtIndexUnique id for each entry in the table
Integer32
.1.3.6.1.4.1.21239.5.2.30.1.2.1.1
vrcMainPtRunStateVRC run state: 1 = on 2 = offro
Enumeration
.1.3.6.1.4.1.21239.5.2.30.1.2.1.2
vrcMainPtEevOpenedEev opened value (percent)ro
Integer32
.1.3.6.1.4.1.21239.5.2.30.1.2.1.3
vrcMainPtAlarmNumbersAlarm numbers valuero
Integer32(-32768..32767)
.1.3.6.1.4.1.21239.5.2.30.1.2.1.4
vrcMainPtHistoryAlarmNumbersHistory alarm numbers valuero
Integer32(-32768..32767)
.1.3.6.1.4.1.21239.5.2.30.1.2.1.5
vrcMainPtHpAbnRecordCntHp Abnormal record countro
Integer32(-32768..32767)
.1.3.6.1.4.1.21239.5.2.30.1.2.1.6
vrcMainPtMonitorBaudrateMonitor baud rate: 1 = error 2 = 1200 3 = 2400 4 = 4800 5 = 9600 6 = 19200ro
Enumeration
.1.3.6.1.4.1.21239.5.2.30.1.2.1.7
vrcMainPtMonitorAddressMonitor addressro
Integer32
.1.3.6.1.4.1.21239.5.2.30.1.2.1.8
vrcMainPtLpLp statusro
TruthValue (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.30.1.2.1.9
vrcMainPtFilterMaintRemindFilter maintenance reminder statusro
TruthValue (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.30.1.2.1.10
vrcMainPtCoolingFlagCooling flagro
TruthValue (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.30.1.2.1.11
vrcMainPtFirstOnFlagFirst on flagro
TruthValue (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.30.1.2.1.12
vrcMainPtNewAlarmFlagNew alarm flagro
TruthValue (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.30.1.2.1.13
vrcMainPtComAlarmOutStateCommon alarm output statero
TruthValue (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.30.1.2.1.14
vrcMainPtHighWaterInputHigh water inputro
TruthValue (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.30.1.2.1.15
vrcMainPtHighWaterAlarmHigh water alarm statusro
TruthValue (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.30.1.2.1.16
vrcMainPtWaterUnderFloorAlarmWater under floor alarm statusro
TruthValue (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.30.1.2.1.17
vrcMainPtSwShutDownStatusSoftware shutdown statusro
TruthValue (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.30.1.2.1.18
vrcMainPtRemoteShutdownRemote shutdown statusro
TruthValue (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.30.1.2.1.19
vrcMainPtRemoteShutDownFlagRemote shutdown flagro
TruthValue (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.30.1.2.1.20
vrcMainPtRemoteShutDownAlarmRemote shutdown alarm statusro
TruthValue (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.30.1.2.1.21
vrcMainPtHmiShutDownFlagHmi shutdown flagro
TruthValue (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.30.1.2.1.22
vrcMainPtLpAlarmLow pressure alarm statusro
TruthValue (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.30.1.2.1.23
vrcMainPtHpAlarmHigh pressure alarm statusro
TruthValue (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.30.1.2.1.24
vrcMainPtLpFreqAlarmLow pressure frequently alarm statusro
TruthValue (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.30.1.2.1.25
vrcMainPtHpFreqAlarmHigh pressure frequently alarm statusro
TruthValue (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.30.1.2.1.26
vrcMainPtLpSensorFailAlarmLow pressure sensor failure alarm statusro
TruthValue (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.30.1.2.1.27
vrcMainPtHpSensorFailAlarmHigh pressure sensor failure alarm statusro
TruthValue (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.30.1.2.1.28
vrcMainPtEevCommFailAlarmEev communication failure alarm statusro
TruthValue (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.30.1.2.1.29
vrcMainCfgTableTable that contains general VRC configuration
SEQUENCE OF VrcMainCfgEntry
.1.3.6.1.4.1.21239.5.2.30.1.3
vrcMainCfgEntryEntry in the vrcMainCfgTable: each entry contains general config fields for a VRC device
VrcMainCfgEntry
.1.3.6.1.4.1.21239.5.2.30.1.3.1
vrcMainCfgIndexUnique id for each entry in the table
Integer32
.1.3.6.1.4.1.21239.5.2.30.1.3.1.1
vrcMainCfgModelSelectModel Selection: 1 = TMM-Local 220V 50/60HZ 2 = TMM-Global 208/230V 50/60HZ 3 = TMM-Global 120V 50/60HZ 4 = SC 220V 50/60HZ 5 = 0U 220V 50/60HZ 6 = SS 208/230V 50/60HZ 7 = SS 120V 50/60HZrw
Enumeration
.1.3.6.1.4.1.21239.5.2.30.1.3.1.2
vrcMainCfgSystemTimeYearSystem time - yearrw
Integer32
.1.3.6.1.4.1.21239.5.2.30.1.3.1.3
vrcMainCfgSystemTimeMonthSystem time - monthrw
Integer32
.1.3.6.1.4.1.21239.5.2.30.1.3.1.4
vrcMainCfgSystemTimeDaySystem time - dayrw
Integer32
.1.3.6.1.4.1.21239.5.2.30.1.3.1.5
vrcMainCfgSystemTimeHourSystem time - hourrw
Integer32
.1.3.6.1.4.1.21239.5.2.30.1.3.1.6
vrcMainCfgSystemTimeMinSystem time - minutesrw
Integer32
.1.3.6.1.4.1.21239.5.2.30.1.3.1.7
vrcMainCfgSystemTimeSecSystem time - secondsrw
Integer32
.1.3.6.1.4.1.21239.5.2.30.1.3.1.8
vrcMainCfgEevShtSettingMinMin Eev sht in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The settable range is determined by the current temperature units. Celsius: 50 to 200 Fahrenheit: 90 to 359rw
Integer32 UNITS "decidegrees"
.1.3.6.1.4.1.21239.5.2.30.1.3.1.9
vrcMainCfgEevShtSettingMaxMax Eev sht in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The settable range is determined by the current temperature units. Celsius: 50 to 200 Fahrenheit: 90 to 359rw
Integer32 UNITS "decidegrees"
.1.3.6.1.4.1.21239.5.2.30.1.3.1.10
vrcMainCfgEevValveCloseShtEev valve close sht in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The settable range is determined by the current temperature units. Celsius: 0 to 100 Fahrenheit: 0 to 179rw
Integer32 UNITS "decidegrees"
.1.3.6.1.4.1.21239.5.2.30.1.3.1.11
vrcMainCfgEevMopPressSettingEev mop pressure setting in tenths of a bar.rw
Integer32
.1.3.6.1.4.1.21239.5.2.30.1.3.1.12
vrcMainCfgLpdtLow pressure dt in secondsrw
Integer32
.1.3.6.1.4.1.21239.5.2.30.1.3.1.13
vrcMainCfgDeadBandDead band in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The settable range is determined by the current temperature units. Celsius: 0 to 20 Fahrenheit: 0 to 35rw
Integer32 UNITS "decidegrees"
.1.3.6.1.4.1.21239.5.2.30.1.3.1.14
vrcMainCfgOnOffSwitchOn-off switchrw
TruthValue (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.30.1.3.1.15
vrcMainCfgVacuumStateVacuum staterw
TruthValue (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.30.1.3.1.16
vrcMainCfgControlModeControl mode: 1 = supply 2 = returnrw
Enumeration
.1.3.6.1.4.1.21239.5.2.30.1.3.1.17
vrcMainCfgManualRunEnableManual run enablerw
TruthValue (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.30.1.3.1.18
vrcMainCfgRemShutdownInputRemote shutdown inputrw
TruthValue (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.30.1.3.1.19
vrcMainCfgMonitorShutDownFlagMonitor shutdown flagrw
TruthValue (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.30.1.3.1.20
vrcMainCfgFirstOnPasswordFirst on password valuerw
Integer32(-32768..32767)
.1.3.6.1.4.1.21239.5.2.30.1.3.1.21
vrcMainCfgFilterMaintSettingFilter maintenance settingrw
TruthValue (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.30.1.3.1.22
vrcMainCfgFilterMaintRemindTimeTime between filter maintenance reminders in daysrw
Integer32
.1.3.6.1.4.1.21239.5.2.30.1.3.1.23
vrcMainCfgFilterMaintRemindCtrlFilter maintenance reminder: 1 = close 2 = suspend 3 = openrw
Enumeration
.1.3.6.1.4.1.21239.5.2.30.1.3.1.24
vrcMainCfgCommonAlarmOutputDirCommon alarm output directionrw
TruthValue (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.30.1.3.1.25
vrcMainCfgHpAbnAlarmSettingAbnormal high pressure alarm value in tenths of a barrw
Integer32
.1.3.6.1.4.1.21239.5.2.30.1.3.1.26
vrcMainCfgLpAlarmCtrlLow pressure alarm control: 2 = suspend 3 = openrw
Enumeration
.1.3.6.1.4.1.21239.5.2.30.1.3.1.27
vrcMainCfgHpAlarmCtrlHigh pressure alarm control: 2 = suspend 3 = openrw
Enumeration
.1.3.6.1.4.1.21239.5.2.30.1.3.1.28
vrcMainCfgLpFreqAlarmCtrlLow pressure frequently alarm control: 2 = suspend 3 = openrw
Enumeration
.1.3.6.1.4.1.21239.5.2.30.1.3.1.29
vrcMainCfgHpFreqAlarmCtrlHigh pressure frequently alarm control: 2 = suspend 3 = openrw
Enumeration
.1.3.6.1.4.1.21239.5.2.30.1.3.1.30
vrcMainCfgLpSensorFailAlarmCtrlLow pressure sensor failure alarm control: 2 = suspend 3 = openrw
Enumeration
.1.3.6.1.4.1.21239.5.2.30.1.3.1.31
vrcMainCfgHpSensorFailAlarmCtrlHigh pressure sensor failure alarm control: 2 = suspend 3 = openrw
Enumeration
.1.3.6.1.4.1.21239.5.2.30.1.3.1.32
vrcMainCfgHighWaterAlarmCtrlHigh water alarm control: 1 = close 2 = suspend 3 = openrw
Enumeration
.1.3.6.1.4.1.21239.5.2.30.1.3.1.33
vrcMainCfgRemShutdownAlarmCtrlRemote shutdown alarm control: 2 = suspend 3 = openrw
Enumeration
.1.3.6.1.4.1.21239.5.2.30.1.3.1.34
vrcMainCfgEevCommFailAlarmCtrlEev communication failure alarm: 2 = suspend 3 = openrw
Enumeration
.1.3.6.1.4.1.21239.5.2.30.1.3.1.35
vrcOutFanPtTableTable that contains VRC out-fan status
SEQUENCE OF VrcOutFanPtEntry
.1.3.6.1.4.1.21239.5.2.30.1.4
vrcOutFanPtEntryEntry in the vrcOutFanPtTable: each entry represents data for a VRC out-fan
VrcOutFanPtEntry
.1.3.6.1.4.1.21239.5.2.30.1.4.1
vrcOutFanPtIndexUnique id for each entry in the table
Integer32
.1.3.6.1.4.1.21239.5.2.30.1.4.1.1
vrcOutFanPtNameOut-fan name (factory-assigned)ro
SnmpAdminString
.1.3.6.1.4.1.21239.5.2.30.1.4.1.2
vrcOutFanPtSpeedFan speed (percent)ro
Integer32
.1.3.6.1.4.1.21239.5.2.30.1.4.1.3
vrcOutFanCfgTableTable used for VRC out-fan configuration
SEQUENCE OF VrcOutFanCfgEntry
.1.3.6.1.4.1.21239.5.2.30.1.5
vrcOutFanCfgEntryEntry in the vrcOutFanCfgTable: each entry contains config fields for a VRC out-fan
VrcOutFanCfgEntry
.1.3.6.1.4.1.21239.5.2.30.1.5.1
vrcOutFanCfgIndexUnique id for each entry in the table
Integer32
.1.3.6.1.4.1.21239.5.2.30.1.5.1.1
vrcOutFanCfgStartPressOut-fan start pressure in tenths of a barrw
Integer32
.1.3.6.1.4.1.21239.5.2.30.1.5.1.2
vrcOutFanCfgPressSettingOut-fan pressure setting in tenths of a barrw
Integer32
.1.3.6.1.4.1.21239.5.2.30.1.5.1.3
vrcOutFanCfgMinPowerVoltageMin out-fan voltage (percent)rw
Integer32
.1.3.6.1.4.1.21239.5.2.30.1.5.1.4
vrcOutFanCfgMaxPowerVoltageMax out-fan voltage (percent)rw
Integer32
.1.3.6.1.4.1.21239.5.2.30.1.5.1.5
vrcOutFanCfgSpeedOut-fan speed (percent)rw
Integer32
.1.3.6.1.4.1.21239.5.2.30.1.5.1.6
vrcInFanPtTableTable that contains VRC in-fan status
SEQUENCE OF VrcInFanPtEntry
.1.3.6.1.4.1.21239.5.2.30.1.6
vrcInFanPtEntryEntry in the vrcInFanPtTable: each entry represents data for a VRC in- fan
VrcInFanPtEntry
.1.3.6.1.4.1.21239.5.2.30.1.6.1
vrcInFanPtIndexUnique id for each entry in the table
Integer32
.1.3.6.1.4.1.21239.5.2.30.1.6.1.1
vrcInFanPtNameIn-fan name (factory-assigned)ro
SnmpAdminString
.1.3.6.1.4.1.21239.5.2.30.1.6.1.2
vrcInFanPtRunTimeHoursIn-fan run time in hoursro
Integer32(-32768..32767) UNITS "hours"
.1.3.6.1.4.1.21239.5.2.30.1.6.1.3
vrcInFanPtStartStopCountIn-fan start/stop countro
Integer32(-32768..32767)
.1.3.6.1.4.1.21239.5.2.30.1.6.1.4
vrcInFanCfgTableTable used for VRC in-fan configuration
SEQUENCE OF VrcInFanCfgEntry
.1.3.6.1.4.1.21239.5.2.30.1.7
vrcInFanCfgEntryEntry in the vrcInFanCfgTable: each entry contains config fields for a VRC in-fan
VrcInFanCfgEntry
.1.3.6.1.4.1.21239.5.2.30.1.7.1
vrcInFanCfgIndexUnique id for each entry in the table
Integer32
.1.3.6.1.4.1.21239.5.2.30.1.7.1.1
vrcInFanCfgOutputStatusIn-fan output statusrw
TruthValue (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.30.1.7.1.2
vrcInFanCfgLowSpeedStepIn-fan low speed step in tenths of a percent per secondrw
Integer32
.1.3.6.1.4.1.21239.5.2.30.1.7.1.3
vrcInFanCfgHighSpeedStepIn-fan high speed step in tenths of a percent per secondrw
Integer32
.1.3.6.1.4.1.21239.5.2.30.1.7.1.4
vrcInFanCfgMinSpeedMin in-fan speed (percent)rw
Integer32
.1.3.6.1.4.1.21239.5.2.30.1.7.1.5
vrcInFanCfgStandardSpeedStandard in-fan speed (percent)rw
Integer32
.1.3.6.1.4.1.21239.5.2.30.1.7.1.6
vrcInFanCfgMinCfcMin in-fan cfc (percent)rw
Integer32
.1.3.6.1.4.1.21239.5.2.30.1.7.1.7
vrcInFanCfgStandardCfcStandard in-fan cfc (percent)rw
Integer32
.1.3.6.1.4.1.21239.5.2.30.1.7.1.8
vrcInFanCfgStartDelayIn-fan start delay in secondsrw
Integer32
.1.3.6.1.4.1.21239.5.2.30.1.7.1.9
vrcInFanCfgStopDelayIn-fan stop delay in secondsrw
Integer32
.1.3.6.1.4.1.21239.5.2.30.1.7.1.10
vrcInFanCfgReduceSpeedDelayIn-fan reduce speed delay in secondsrw
Integer32
.1.3.6.1.4.1.21239.5.2.30.1.7.1.11
vrcInFanCfgJumpBand1In-fan jump band 1 in tenths of a percentrw
Integer32
.1.3.6.1.4.1.21239.5.2.30.1.7.1.12
vrcInFanCfgJumpBand2In-fan jump band 2 in tenths of a percentrw
Integer32
.1.3.6.1.4.1.21239.5.2.30.1.7.1.13
vrcInFanCfgJumpBand3In-fan jump band 3 in tenths of a percentrw
Integer32
.1.3.6.1.4.1.21239.5.2.30.1.7.1.14
vrcInFanCfgJumpBand4In-fan jump band 4 in tenths of a percentrw
Integer32
.1.3.6.1.4.1.21239.5.2.30.1.7.1.15
vrcInFanCfgJumpBand5In-fan jump band 5 in tenths of a percentrw
Integer32
.1.3.6.1.4.1.21239.5.2.30.1.7.1.16
vrcInFanCfgJumpFreq1In-fan jump frequency 1 in tenths of a percentrw
Integer32
.1.3.6.1.4.1.21239.5.2.30.1.7.1.17
vrcInFanCfgJumpFreq2In-fan jump frequency 2 in tenths of a percentrw
Integer32
.1.3.6.1.4.1.21239.5.2.30.1.7.1.18
vrcInFanCfgJumpFreq3In-fan jump frequency 3 in tenths of a percentrw
Integer32
.1.3.6.1.4.1.21239.5.2.30.1.7.1.19
vrcInFanCfgJumpFreq4In-fan jump frequency 4 in tenths of a percentrw
Integer32
.1.3.6.1.4.1.21239.5.2.30.1.7.1.20
vrcInFanCfgJumpFreq5In-fan jump frequency 5 in tenths of a percentrw
Integer32
.1.3.6.1.4.1.21239.5.2.30.1.7.1.21
vrcInFanCfgTempPIn-fan temperature P in tenths of a degree. Units are given by temperatureUnits field in deviceInfo.rw
Integer32
.1.3.6.1.4.1.21239.5.2.30.1.7.1.22
vrcInFanCfgTempIIn-fan temperature I in secondsrw
Integer32
.1.3.6.1.4.1.21239.5.2.30.1.7.1.23
vrcInFanCfgTempDIn-fan temperature D in secondsrw
Integer32
.1.3.6.1.4.1.21239.5.2.30.1.7.1.24
vrcCompPtTableTable that contains VRC compressor status
SEQUENCE OF VrcCompPtEntry
.1.3.6.1.4.1.21239.5.2.30.1.8
vrcCompPtEntryEntry in the vrcCompPtTable: each entry represents data for a VRC compressor
VrcCompPtEntry
.1.3.6.1.4.1.21239.5.2.30.1.8.1
vrcCompPtIndexUnique id for each entry in the table
Integer32
.1.3.6.1.4.1.21239.5.2.30.1.8.1.1
vrcCompPtNameCompressor name (factory-assigned)ro
SnmpAdminString
.1.3.6.1.4.1.21239.5.2.30.1.8.1.2
vrcCompPtCapacityCompressor capacity value (percent)ro
Integer32
.1.3.6.1.4.1.21239.5.2.30.1.8.1.3
vrcCompPtRunTimeHoursCompressor run time in hoursro
Integer32(-32768..32767) UNITS "hours"
.1.3.6.1.4.1.21239.5.2.30.1.8.1.4
vrcCompPtStartStopCountCompressor start/stop countro
Integer32(-32768..32767)
.1.3.6.1.4.1.21239.5.2.30.1.8.1.5
vrcCompPtDriverFaultU00Compressor driver fault alarm U00 statero
TruthValue (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.30.1.8.1.6
vrcCompPtDriverFaultU01Compressor driver fault alarm U01 statero
TruthValue (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.30.1.8.1.7
vrcCompPtDriverFaultU02Compressor driver fault alarm U02 statero
TruthValue (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.30.1.8.1.8
vrcCompPtDriverFaultU03Compressor driver fault alarm U03 statero
TruthValue (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.30.1.8.1.9
vrcCompPtDriverFaultU04Compressor driver fault alarm U04 statero
TruthValue (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.30.1.8.1.10
vrcCompPtDriverFaultU05Compressor driver fault alarm U05 statero
TruthValue (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.30.1.8.1.11
vrcCompPtDriverFaultU06Compressor driver fault alarm U06 statero
TruthValue (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.30.1.8.1.12
vrcCompPtDriverFaultU07Compressor driver fault alarm U07 statero
TruthValue (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.30.1.8.1.13
vrcCompPtDriverFaultU08Compressor driver fault alarm U08 statero
TruthValue (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.30.1.8.1.14
vrcCompPtDriverFaultU09Compressor driver fault alarm U09 statero
TruthValue (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.30.1.8.1.15
vrcCompPtDriverFaultU10Compressor driver fault alarm U10 statero
TruthValue (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.30.1.8.1.16
vrcCompPtDriverFaultU11Compressor driver fault alarm U11 statero
TruthValue (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.30.1.8.1.17
vrcCompPtDriverFaultU12Compressor driver fault alarm U12 statero
TruthValue (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.30.1.8.1.18
vrcCompPtDriverFaultU13Compressor driver fault alarm U13 statero
TruthValue (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.30.1.8.1.19
vrcCompPtDriverFaultU14Compressor driver fault alarm U14 statero
TruthValue (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.30.1.8.1.20
vrcCompPtDriverFaultU15Compressor driver fault alarm U15 statero
TruthValue (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.30.1.8.1.21
vrcCompPtDriverCommFailAlarmCompressor driver communication failure alarm statero
TruthValue (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.30.1.8.1.22
vrcCompPtFaultLockAlarmCompressor fault lock alarm statero
TruthValue (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.30.1.8.1.23
vrcCompCfgTableTable used for VRC compressor configuration
SEQUENCE OF VrcCompCfgEntry
.1.3.6.1.4.1.21239.5.2.30.1.9
vrcCompCfgEntryEntry in the vrcCompCfgTable: each entry contains config fields for a VRC compressor
VrcCompCfgEntry
.1.3.6.1.4.1.21239.5.2.30.1.9.1
vrcCompCfgIndexUnique id for each entry in the table
Integer32
.1.3.6.1.4.1.21239.5.2.30.1.9.1.1
vrcCompCfgOutputStatusCompressor output statusrw
TruthValue (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.30.1.9.1.2
vrcCompCfgOutputDeadBandCompressor output dead band in tenths of a percentrw
Integer32
.1.3.6.1.4.1.21239.5.2.30.1.9.1.3
vrcCompCfgCapacityOutputValueCompressor capacity output (percent)rw
Integer32
.1.3.6.1.4.1.21239.5.2.30.1.9.1.4
vrcCompCfgMinCapacityCompressor min capacity (percent)rw
Integer32
.1.3.6.1.4.1.21239.5.2.30.1.9.1.5
vrcCompCfgStartCapacityCompressor start capacity (percent)rw
Integer32
.1.3.6.1.4.1.21239.5.2.30.1.9.1.6
vrcCompCfgStandardCapacityCompressor standard capacity (percent)rw
Integer32
.1.3.6.1.4.1.21239.5.2.30.1.9.1.7
vrcCompCfgStartCfcCompressor start cfc (percent)rw
Integer32
.1.3.6.1.4.1.21239.5.2.30.1.9.1.8
vrcCompCfgStopCfcCompressor stop cfc (percent)rw
Integer32(-200..-50) UNITS "%"
.1.3.6.1.4.1.21239.5.2.30.1.9.1.9
vrcCompCfgMinRunTimeCompressor min run time in minutesrw
Integer32
.1.3.6.1.4.1.21239.5.2.30.1.9.1.10
vrcCompCfgMinStopTimeCompressor min stop time in minutesrw
Integer32
.1.3.6.1.4.1.21239.5.2.30.1.9.1.11
vrcCompCfgJumpBand1Compressor jump band 1 in tenths of a percentrw
Integer32
.1.3.6.1.4.1.21239.5.2.30.1.9.1.12
vrcCompCfgJumpBand2Compressor jump band 2 in tenths of a percentrw
Integer32
.1.3.6.1.4.1.21239.5.2.30.1.9.1.13
vrcCompCfgJumpBand3Compressor jump band 3 in tenths of a percentrw
Integer32
.1.3.6.1.4.1.21239.5.2.30.1.9.1.14
vrcCompCfgJumpBand4Compressor jump band 4 in tenths of a percentrw
Integer32
.1.3.6.1.4.1.21239.5.2.30.1.9.1.15
vrcCompCfgJumpBand5Compressor jump band 5 in tenths of a percentrw
Integer32
.1.3.6.1.4.1.21239.5.2.30.1.9.1.16
vrcCompCfgJumpFreq1Compressor jump frequency 1 in tenths of a percentrw
Integer32
.1.3.6.1.4.1.21239.5.2.30.1.9.1.17
vrcCompCfgJumpFreq2Compressor jump frequency 2 in tenths of a percentrw
Integer32
.1.3.6.1.4.1.21239.5.2.30.1.9.1.18
vrcCompCfgJumpFreq3Compressor jump frequency 3 in tenths of a percentrw
Integer32
.1.3.6.1.4.1.21239.5.2.30.1.9.1.19
vrcCompCfgJumpFreq4Compressor jump frequency 4 in tenths of a percentrw
Integer32
.1.3.6.1.4.1.21239.5.2.30.1.9.1.20
vrcCompCfgJumpFreq5Compressor jump frequency 5 in tenths of a percentrw
Integer32
.1.3.6.1.4.1.21239.5.2.30.1.9.1.21
vrcCompCfgTempPCompressor temperature P in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The settable range is determined by the current temperature units. Celsius: 10 to 150 Fahrenheit: 18 to 269rw
Integer32 UNITS "decidegrees"
.1.3.6.1.4.1.21239.5.2.30.1.9.1.22
vrcCompCfgTempICompressor temperature I in secondsrw
Integer32
.1.3.6.1.4.1.21239.5.2.30.1.9.1.23
vrcCompCfgTempDCompressor temperature D in secondsrw
Integer32
.1.3.6.1.4.1.21239.5.2.30.1.9.1.24
vrcCompCfgDriverFaultAlmCtrlCompressor driver fault alarm control: 2 = suspend 3 = openrw
Enumeration
.1.3.6.1.4.1.21239.5.2.30.1.9.1.25
vrcCompCfgDriverCommFailAlmCtrlCompressor driver communication failure alarm control: 2 = suspend 3 = openrw
Enumeration
.1.3.6.1.4.1.21239.5.2.30.1.9.1.26
vrcCompCfgFaultLockAlmCtrlCompressor fault lock alarm control: 2 = suspend 3 = openrw
Enumeration
.1.3.6.1.4.1.21239.5.2.30.1.9.1.27
vrcReturnPtTableTable that contains VRC return status
SEQUENCE OF VrcReturnPtEntry
.1.3.6.1.4.1.21239.5.2.30.1.10
vrcReturnPtEntryEntry in the vrcReturnPtTable: each entry represents return data for a VRC
VrcReturnPtEntry
.1.3.6.1.4.1.21239.5.2.30.1.10.1
vrcReturnPtIndexUnique id for each entry in the table
Integer32
.1.3.6.1.4.1.21239.5.2.30.1.10.1.1
vrcReturnPtNameReturn name (factory-assigned)ro
SnmpAdminString
.1.3.6.1.4.1.21239.5.2.30.1.10.1.2
vrcReturnPtTempReturn temperature value in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The range is determined by the current temperature units. Celsius: -400 to 1000 Fahrenheit: -400 to 2120ro
Integer32 UNITS "decidegrees"
.1.3.6.1.4.1.21239.5.2.30.1.10.1.3
vrcReturnPtHighTempAlarmReturn high temperature alarm statero
TruthValue (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.30.1.10.1.4
vrcReturnPtTempSensorFailAlarmReturn temperature sensor failure alarm statero
TruthValue (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.30.1.10.1.5
vrcReturnCfgTableTable used for VRC return configuration
SEQUENCE OF VrcReturnCfgEntry
.1.3.6.1.4.1.21239.5.2.30.1.11
vrcReturnCfgEntryEntry in the vrcReturnCfgTable: each entry contains config fields for VRC return
VrcReturnCfgEntry
.1.3.6.1.4.1.21239.5.2.30.1.11.1
vrcReturnCfgIndexUnique id for each entry in the table
Integer32
.1.3.6.1.4.1.21239.5.2.30.1.11.1.1
vrcReturnCfgOilCycleReturn oil cycle in tenths of an hourrw
Integer32
.1.3.6.1.4.1.21239.5.2.30.1.11.1.2
vrcReturnCfgOilRunCapacityReturn Oil run capacity (percent)rw
Integer32
.1.3.6.1.4.1.21239.5.2.30.1.11.1.3
vrcReturnCfgOilRunTimeReturn oil run time in minutesrw
Integer32
.1.3.6.1.4.1.21239.5.2.30.1.11.1.4
vrcReturnCfgTempCalValueReturn temperature calibration value in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The settable range is determined by the current temperature units. Celsius: -100 to 100 Fahrenheit: -179 to 179rw
Integer32 UNITS "decidegrees"
.1.3.6.1.4.1.21239.5.2.30.1.11.1.5
vrcReturnCfgTempSettingReturn temperature setting in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The settable range is determined by the current temperature units. Celsius: 250 to 350 Fahrenheit: 770 to 949rw
Integer32 UNITS "decidegrees"
.1.3.6.1.4.1.21239.5.2.30.1.11.1.6
vrcReturnCfgHighTempAlarmValueReturn high temperature alarm value in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The settable range is determined by the current temperature units. Celsius: 300 to 450 Fahrenheit: 860 to 1129rw
Integer32 UNITS "decidegrees"
.1.3.6.1.4.1.21239.5.2.30.1.11.1.7
vrcReturnCfgHighTempAlarmCtrlReturn high temperature alarm control: 1 = close 2 = suspend 3 = openrw
Enumeration
.1.3.6.1.4.1.21239.5.2.30.1.11.1.8
vrcReturnCfgTempSensFailAlmCtrlReturn temperature sensor failure alarm control: 1 = close 2 = suspend 3 = openrw
Enumeration
.1.3.6.1.4.1.21239.5.2.30.1.11.1.9
vrcSupplyPtTableTable that contains VRC supply status
SEQUENCE OF VrcSupplyPtEntry
.1.3.6.1.4.1.21239.5.2.30.1.12
vrcSupplyPtEntryEntry in the vrcSupplyPtTable: each entry represents supply data for a VRC
VrcSupplyPtEntry
.1.3.6.1.4.1.21239.5.2.30.1.12.1
vrcSupplyPtIndexUnique id for each entry in the table
Integer32
.1.3.6.1.4.1.21239.5.2.30.1.12.1.1
vrcSupplyPtNameSupply name (factory-assigned)ro
SnmpAdminString
.1.3.6.1.4.1.21239.5.2.30.1.12.1.2
vrcSupplyPtTempSupply temperature value in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The range is determined by the current temperature units. Celsius: -400 to 1000 Fahrenheit: -400 to 2120ro
Integer32 UNITS "decidegrees"
.1.3.6.1.4.1.21239.5.2.30.1.12.1.3
vrcSupplyPtLowTempAlarmSupply low temperature alarm statero
TruthValue (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.30.1.12.1.4
vrcSupplyPtHighTempAlarmSupply high temperature alarm statero
TruthValue (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.30.1.12.1.5
vrcSupplyPtTempSensorFailAlarmSupply temperature sensor failure alarm statero
TruthValue (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.30.1.12.1.6
vrcSupplyCfgTableTable used for VRC supply configuration
SEQUENCE OF VrcSupplyCfgEntry
.1.3.6.1.4.1.21239.5.2.30.1.13
vrcSupplyCfgEntryEntry in the vrcSupplyCfgTable: each entry contains config fields for a VRC supply
VrcSupplyCfgEntry
.1.3.6.1.4.1.21239.5.2.30.1.13.1
vrcSupplyCfgIndexUnique id for each entry in the table
Integer32
.1.3.6.1.4.1.21239.5.2.30.1.13.1.1
vrcSupplyCfgTempCalValueSupply temperature calibration value in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The settable range is determined by the current temperature units. Celsius: -100 to 100 Fahrenheit: -179 to 179rw
Integer32 UNITS "decidegrees"
.1.3.6.1.4.1.21239.5.2.30.1.13.1.2
vrcSupplyCfgTempSettingSupply temperature setting in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The settable range is determined by the current temperature units. Celsius: 130 to 280 Fahrenheit: 554 to 823rw
Integer32 UNITS "decidegrees"
.1.3.6.1.4.1.21239.5.2.30.1.13.1.3
vrcSupplyCfgLowTempAlarmValueSupply low temperature alarm value in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The settable range is determined by the current temperature units. Celsius: 50 to 200 Fahrenheit: 410 to 679rw
Integer32 UNITS "decidegrees"
.1.3.6.1.4.1.21239.5.2.30.1.13.1.4
vrcSupplyCfgHighTempAlarmValueSupply high temperature alarm value in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The settable range is determined by the current temperature units. Celsius: 200 to 350 Fahrenheit: 680 to 949rw
Integer32 UNITS "decidegrees"
.1.3.6.1.4.1.21239.5.2.30.1.13.1.5
vrcSupplyCfgLowTempAlmCtrlSupply low temperature alarm control: 1 = close 2 = suspend 3 = openrw
Enumeration
.1.3.6.1.4.1.21239.5.2.30.1.13.1.6
vrcSupplyCfgHighTempAlmCtrlSupply high temperature alarm control: 1 = close 2 = suspend 3 = openrw
Enumeration
.1.3.6.1.4.1.21239.5.2.30.1.13.1.7
vrcSupplyCfgTempSensFailAlmCtrlSupply temperature sensor failure alarm control: 1 = close 2 = suspend 3 = openrw
Enumeration
.1.3.6.1.4.1.21239.5.2.30.1.13.1.8
vrcPowerPtTableTable that contains VRC power status
SEQUENCE OF VrcPowerPtEntry
.1.3.6.1.4.1.21239.5.2.30.1.14
vrcPowerPtEntryEntry in the vrcPowerPtTable: each entry represents power data for a VRC
VrcPowerPtEntry
.1.3.6.1.4.1.21239.5.2.30.1.14.1
vrcPowerPtIndexUnique id for each entry in the table
Integer32
.1.3.6.1.4.1.21239.5.2.30.1.14.1.1
vrcPowerPtNamePower name (factory-assigned)ro
SnmpAdminString
.1.3.6.1.4.1.21239.5.2.30.1.14.1.2
vrcPowerPtVoltagePower voltage measurement in tenths of a voltro
Integer32(-32768..32767) UNITS "decivolts"
.1.3.6.1.4.1.21239.5.2.30.1.14.1.3
vrcPowerPtFrequencyPower frequency measurement in tenths of hertzro
Integer32(-32768..32767) UNITS "decihertz"
.1.3.6.1.4.1.21239.5.2.30.1.14.1.4
vrcPowerPtLowVoltageAlarmPower low voltage alarm statero
TruthValue (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.30.1.14.1.5
vrcPowerPtHighVoltageAlarmPower high voltage alarm statero
TruthValue (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.30.1.14.1.6
vrcPowerPtLossOfPhasePowerAlarmPhase power loss alarm statero
TruthValue (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.30.1.14.1.7
vrcPowerPtLossOfPowerAlarmPower loss alarm statero
TruthValue (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.30.1.14.1.8
vrcPowerPtFrequencyErrorAlarmPower frequency error alarm statero
TruthValue (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.30.1.14.1.9
vrcPowerCfgTableTable used for VRC power configuration
SEQUENCE OF VrcPowerCfgEntry
.1.3.6.1.4.1.21239.5.2.30.1.15
vrcPowerCfgEntryEntry in the vrcPowerCfgTable: each entry contains config fields for VRC power
VrcPowerCfgEntry
.1.3.6.1.4.1.21239.5.2.30.1.15.1
vrcPowerCfgIndexUnique id for each entry in the table
Integer32
.1.3.6.1.4.1.21239.5.2.30.1.15.1.1
vrcPowerCfgLowVoltageSettingPower low voltage setting in voltsrw
Integer32
.1.3.6.1.4.1.21239.5.2.30.1.15.1.2
vrcPowerCfgHighVoltageSettingPower high voltage setting in voltsrw
Integer32
.1.3.6.1.4.1.21239.5.2.30.1.15.1.3
vrcPowerCfgLowVoltageAlarmCtrlPower low voltage alarm control: 1 = close 2 = suspend 3 = openrw
Enumeration
.1.3.6.1.4.1.21239.5.2.30.1.15.1.4
vrcPowerCfgHighVoltageAlarmCtrlPower high voltage alarm control: 1 = close 2 = suspend 3 = openrw
Enumeration
.1.3.6.1.4.1.21239.5.2.30.1.15.1.5
vrcPowerCfgLossOfPowerAlarmCtrlPower loss alarm control: 1 = close 2 = suspend 3 = openrw
Enumeration
.1.3.6.1.4.1.21239.5.2.30.1.15.1.6
vrcPowerCfgFreqErrorAlarmCtrlPower frequency error alarm control: 1 = close 2 = suspend 3 = openrw
Enumeration
.1.3.6.1.4.1.21239.5.2.30.1.15.1.7
vrcOutdoorPtTableTable that contains VRC outdoor status
SEQUENCE OF VrcOutdoorPtEntry
.1.3.6.1.4.1.21239.5.2.30.1.16
vrcOutdoorPtEntryEntry in the vrcOutdoorPtTable: each entry represents data for a VRC outdoor
VrcOutdoorPtEntry
.1.3.6.1.4.1.21239.5.2.30.1.16.1
vrcOutdoorPtIndexUnique id for each entry in the table
Integer32
.1.3.6.1.4.1.21239.5.2.30.1.16.1.1
vrcOutdoorPtNameOutdoor name (factory-assigned)ro
SnmpAdminString
.1.3.6.1.4.1.21239.5.2.30.1.16.1.2
vrcOutdoorPtTempOutdoor temperature value in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The range is determined by the current temperature units. Celsius: -400 to 1000 Fahrenheit: -400 to 2120ro
Integer32 UNITS "decidegrees"
.1.3.6.1.4.1.21239.5.2.30.1.16.1.3
vrcDischPtTableTable that contains VRC discharge status
SEQUENCE OF VrcDischPtEntry
.1.3.6.1.4.1.21239.5.2.30.1.18
vrcDischPtEntryEntry in the vrcDischPtTable: each entry represents discharge data for a VRC
VrcDischPtEntry
.1.3.6.1.4.1.21239.5.2.30.1.18.1
vrcDischPtIndexUnique id for each entry in the table
Integer32
.1.3.6.1.4.1.21239.5.2.30.1.18.1.1
vrcDischPtNameDischarge name (factory-assigned)ro
SnmpAdminString
.1.3.6.1.4.1.21239.5.2.30.1.18.1.2
vrcDischPtTempDischarge temperature value in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The range is determined by the current temperature units. Celsius: -400 to 1560 Fahrenheit: -400 to 3128rw
Integer32 UNITS "decidegrees"
.1.3.6.1.4.1.21239.5.2.30.1.18.1.3
vrcDischPtPressureDischarge air pressure value in tenths of a barrw
Integer32
.1.3.6.1.4.1.21239.5.2.30.1.18.1.4
vrcDischPtHighTempAlarmDischarge high temperature alarm statero
TruthValue (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.30.1.18.1.5
vrcDischPtHighTempFreqAlarmDischarge high temperature frequently alarm statero
TruthValue (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.30.1.18.1.6
vrcDischPtTempSensorFailAlarmDischarge temperature sensor failure alarm statero
TruthValue (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.30.1.18.1.7
vrcDischCfgTableTable used for VRC discharge configuration
SEQUENCE OF VrcDischCfgEntry
.1.3.6.1.4.1.21239.5.2.30.1.19
vrcDischCfgEntryEntry in the vrcDischCfgTable: each entry contains config fields for VRC discharge
VrcDischCfgEntry
.1.3.6.1.4.1.21239.5.2.30.1.19.1
vrcDischCfgIndexUnique id for each entry in the table
Integer32
.1.3.6.1.4.1.21239.5.2.30.1.19.1.1
vrcDischCfgTempCalValueDischarge temperature calibration value in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The settable range is determined by the current temperature units. Celsius: -100 to 100 Fahrenheit: -179 to 179rw
Integer32 UNITS "decidegrees"
.1.3.6.1.4.1.21239.5.2.30.1.19.1.2
vrcDischCfgPressCalValueDischarge pressure calibration value in tenths of a barrw
Integer32(-100..100) UNITS "decibars"
.1.3.6.1.4.1.21239.5.2.30.1.19.1.3
vrcDischCfgHighTempAlmCtrlDischarge high temperature alarm control: 2 = suspend 3 = openrw
Enumeration
.1.3.6.1.4.1.21239.5.2.30.1.19.1.4
vrcDischCfgHighTempFreqAlmCtrlDischarge high temperature frequenctly alarm control: 2 = suspend 3 = openrw
Enumeration
.1.3.6.1.4.1.21239.5.2.30.1.19.1.5
vrcDischCfgTempSensFailAlmCtrlDischarge temperature sensor failure alarm control: 2 = suspend 3 = openrw
Enumeration
.1.3.6.1.4.1.21239.5.2.30.1.19.1.6
vrcSuctPtTableTable that contains VRC suction status
SEQUENCE OF VrcSuctPtEntry
.1.3.6.1.4.1.21239.5.2.30.1.20
vrcSuctPtEntryEntry in the vrcSuctPtTable: each entry represents suction data for a VRC
VrcSuctPtEntry
.1.3.6.1.4.1.21239.5.2.30.1.20.1
vrcSuctPtIndexUnique id for each entry in the table
Integer32
.1.3.6.1.4.1.21239.5.2.30.1.20.1.1
vrcSuctPtNameSuction name (factory-assigned)ro
SnmpAdminString
.1.3.6.1.4.1.21239.5.2.30.1.20.1.2
vrcSuctPtTempSuction temperature in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The range is determined by the current temperature units. Celsius: -400 to 1000 Fahrenheit: -400 to 2120ro
Integer32 UNITS "decidegrees"
.1.3.6.1.4.1.21239.5.2.30.1.20.1.3
vrcSuctPtPressureSuction air pressure in tenths of a barro
Integer32
.1.3.6.1.4.1.21239.5.2.30.1.20.1.4
vrcSuctPtSuperHeatTempSuction super heat temperature in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The range is determined by the current temperature units. Celsius: -400 to 1000 Fahrenheit: -400 to 2120ro
Integer32 UNITS "decidegrees"
.1.3.6.1.4.1.21239.5.2.30.1.20.1.5
vrcSuctPtTempSensorFailAlarmSuction temperature sensor failure alarm statero
TruthValue (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.30.1.20.1.6
vrcSuctCfgTableTable used for VRC suction configuration
SEQUENCE OF VrcSuctCfgEntry
.1.3.6.1.4.1.21239.5.2.30.1.21
vrcSuctCfgEntryEntry in the vrcSuctCfgTable: each entry contains config fields for VRC suction
VrcSuctCfgEntry
.1.3.6.1.4.1.21239.5.2.30.1.21.1
vrcSuctCfgIndexUnique id for each entry in the table
Integer32
.1.3.6.1.4.1.21239.5.2.30.1.21.1.1
vrcSuctCfgPressCalValueSuction pressure calibration value in tenths of a barrw
Integer32(-100..100) UNITS "decibars"
.1.3.6.1.4.1.21239.5.2.30.1.21.1.2
vrcSuctCfgTempSensFailAlmCtrlSuction temperature sensor failure alarm control: 2 = suspend 3 = openrw
Enumeration
.1.3.6.1.4.1.21239.5.2.30.1.21.1.3
trap
OBJECT IDENTIFIER
.1.3.6.1.4.1.21239.5.2.32767
trapPrefix
OBJECT IDENTIFIER
.1.3.6.1.4.1.21239.5.2.32767.0
internalTestNOTIFYTest SNMP Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10101
pduMainAvailNOTIFYPDU availability trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10305
pduTotalRealPowerNOTIFYPDU total real power trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10309
pduTotalApparentPowerNOTIFYPDU total apparent power trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10310
pduTotalPowerFactorNOTIFYPDU total power factor trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10311
pduTotalEnergyNOTIFYPDU total energy trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10312
pduPhaseVoltageNOTIFYPDU phase voltage trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10324
pduPhaseCurrentNOTIFYPDU phase current trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10328
pduPhaseRealPowerNOTIFYPDU phase real power trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10332
pduPhaseApparentPowerNOTIFYPDU phase apparent power trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10333
pduPhasePowerFactorNOTIFYPDU phase power factor trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10334
pduPhaseEnergyNOTIFYPDU phase energy trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10335
pduPhaseBalanceNOTIFYPDU phase balance trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10337
pduPhaseCurrentCrestFactorNOTIFYPDU phase current crest factor trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10339
pduBreakerCurrentNOTIFYPDU breaker current trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10354
pduBreakerVoltageNOTIFYPDU breaker voltage trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10358
pduBreakerRealPowerNOTIFYPDU breaker real power trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10362
pduBreakerApparentPowerNOTIFYPDU breaker apparent power trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10363
pduBreakerPowerFactorNOTIFYPDU breaker power factor trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10364
pduBreakerEnergyNOTIFYPDU breaker energy trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10365
pduLineCurrentNOTIFYPDU line current trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10374
pduOutletMeterVoltageNOTIFYPDU outlet voltage trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10385
pduOutletMeterCurrentNOTIFYPDU outlet current trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10389
pduOutletMeterRealPowerNOTIFYPDU outlet real power trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10393
pduOutletMeterApparentPowerNOTIFYPDU outlet apparent power trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10394
pduOutletMeterPowerFactorNOTIFYPDU outlet power factor trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10395
pduOutletMeterEnergyNOTIFYPDU outlet energy trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10396
pduOutletCurrentCrestFactorNOTIFYPDU outlet current crest factor trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10400
tempSensorAvailNOTIFYRT availability trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10404
tempSensorTempNOTIFYRT temperature trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10405
airFlowSensorAvailNOTIFYAFHT3 availability trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10504
airFlowSensorTempNOTIFYAFHT3 temperature trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10505
airFlowSensorFlowNOTIFYAFHT3 airflow trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10506
airFlowSensorHumidityNOTIFYAFHT3 humidity trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10507
airFlowSensorDewPointNOTIFYAFHT3 dewpoint trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10508
t3hdSensorAvailNOTIFYT3HD availability trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10804
t3hdSensorIntTempNOTIFYT3HD Internal temperature trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10806
t3hdSensorIntHumidityNOTIFYT3HD Internal humidity trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10807
t3hdSensorIntDewPointNOTIFYT3HD Internal dewpoint trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10808
t3hdSensorExtATempNOTIFYT3HD External A temperature trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10811
t3hdSensorExtBTempNOTIFYT3HD External B temperature trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10814
thdSensorAvailNOTIFYTHD availability trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10904
thdSensorTempNOTIFYTHD temperature trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10905
thdSensorHumidityNOTIFYTHD humidity trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10906
thdSensorDewPointNOTIFYTHD dewpoint trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10907
a2dSensorAvailNOTIFYA2D availability trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.11104
a2dSensorValueNOTIFYA2D measurement trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.11105
humiditySensorAvailNOTIFYRemote humidity availability trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.11204
humiditySensorValueNOTIFYRemote humidity value trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.11205
sn2dSensorAvailNOTIFYSN-2D availability trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.11304
sn2dSensorDoor1StateNOTIFYSN-2D Door switch 1 state trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.11306
sn2dSensorDoor2StateNOTIFYSN-2D Door switch 2 state trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.11309
vrcMainAvailNOTIFYVRC availability trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.13001
vrcOutFanPtSpeedNOTIFYVRC out-fan speed trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.13002
vrcCompPtCapacityNOTIFYVRC compressor capacity trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.13003
vrcReturnPtTempNOTIFYVRC return temperature trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.13004
vrcSupplyPtTempNOTIFYVRC supply temperature trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.13005
vrcPowerPtVoltageNOTIFYVRC power voltage trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.13006
vrcPowerPtFrequencyNOTIFYVRC power frequency trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.13007
vrcOutdoorPtTempNOTIFYVRC outdoor temperature trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.13008
vrcDischPtTempNOTIFYVRC discharge temperature trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.13009
vrcDischPtPressureNOTIFYVRC discharge pressure trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.13010
vrcSuctPtTempNOTIFYVRC suction temperature trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.13011
vrcSuctPtPressureNOTIFYVRC suction pressure trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.13012
pduMainAvailCLEARPDU availability clear trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20305
pduTotalRealPowerCLEARPDU total real power clear trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20309
pduTotalApparentPowerCLEARPDU total apparent power clear trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20310
pduTotalPowerFactorCLEARPDU total power factor clear trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20311
pduTotalEnergyCLEARPDU total energy clear trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20312
pduPhaseVoltageCLEARPDU phase voltage clear trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20324
pduPhaseCurrentCLEARPDU phase current clear trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20328
pduPhaseRealPowerCLEARPDU phase real power clear trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20332
pduPhaseApparentPowerCLEARPDU phase apparent power clear trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20333
pduPhasePowerFactorCLEARPDU phase power factor clear trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20334
pduPhaseEnergyCLEARPDU phase energy clear trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20335
pduPhaseBalanceCLEARPDU phase balance clear trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20337
pduPhaseCurrentCrestFactorCLEARPDU phase current crest factor clear trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20339
pduBreakerCurrentCLEARPDU breaker current clear trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20354
pduBreakerVoltageCLEARPDU breaker voltage clear trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20358
pduBreakerRealPowerCLEARPDU breaker real power clear trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20362
pduBreakerApparentPowerCLEARPDU breaker apparent power clear trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20363
pduBreakerPowerFactorCLEARPDU breaker power factor clear trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20364
pduBreakerEnergyCLEARPDU breaker energy clear trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20365
pduLineCurrentCLEARPDU line current clear trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20374
pduOutletMeterVoltageCLEARPDU outlet voltage clear trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20385
pduOutletMeterCurrentCLEARPDU outlet current clear trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20389
pduOutletMeterRealPowerCLEARPDU outlet real power clear trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20393
pduOutletMeterApparentPowerCLEARPDU outlet apparent power clear trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20394
pduOutletMeterPowerFactorCLEARPDU outlet power factor clear trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20395
pduOutletMeterEnergyCLEARPDU outlet energy clear trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20396
pduOutletCurrentCrestFactorCLEARPDU outlet current crest factor clear trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20400
tempSensorAvailCLEARRT availability clear trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20404
tempSensorTempCLEARRT temperature clear trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20405
airFlowSensorAvailCLEARAFHT3 availability clear trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20504
airFlowSensorTempCLEARAFHT3 temperature clear trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20505
airFlowSensorFlowCLEARAFHT3 airflow clear trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20506
airFlowSensorHumidityCLEARAFHT3 humidity clear trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20507
airFlowSensorDewPointCLEARAFHT3 dewpoint clear trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20508
t3hdSensorAvailCLEART3HD availability clear trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20804
t3hdSensorIntTempCLEART3HD Internal temperature clear trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20806
t3hdSensorIntHumidityCLEART3HD Internal humidity clear trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20807
t3hdSensorIntDewPointCLEART3HD Internal dewpoint clear trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20808
t3hdSensorExtATempCLEART3HD External A temperature clear trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20811
t3hdSensorExtBTempCLEART3HD External B temperature clear trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20814
thdSensorAvailCLEARTHD availability clear trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20904
thdSensorTempCLEARTHD temperature clear trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20905
thdSensorHumidityCLEARTHD humidity clear trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20906
thdSensorDewPointCLEARTHD dewpoint clear trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20907
a2dSensorAvailCLEARA2D availability clear trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.21104
a2dSensorValueCLEARA2D measurement clear trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.21105
humiditySensorAvailCLEARRemote humidity availability clear trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.21204
humiditySensorValueCLEARRemote humidity value clear trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.21205
sn2dSensorAvailCLEARSN-2D availability clear trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.21304
sn2dSensorDoor1StateCLEARSN-2D Door switch 1 state clear trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.21306
sn2dSensorDoor2StateCLEARSN-2D Door switch 2 state clear trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.21309
vrcMainAvailCLEARVRC availability clear trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.23001
vrcOutFanPtSpeedCLEARVRC out-fan speed clear trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.23002
vrcCompPtCapacityCLEARVRC compressor capacity clear trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.23003
vrcReturnPtTempCLEARVRC return temperature clear trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.23004
vrcSupplyPtTempCLEARVRC supply temperature clear trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.23005
vrcPowerPtVoltageCLEARVRC power voltage clear trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.23006
vrcPowerPtFrequencyCLEARVRC power frequency clear trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.23007
vrcOutdoorPtTempCLEARVRC outdoor temperature clear trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.23008
vrcDischPtTempCLEARVRC discharge temperature clear trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.23009
vrcDischPtPressureCLEARVRC discharge pressure clear trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.23010
vrcSuctPtTempCLEARVRC suction temperature clear trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.23011
vrcSuctPtPressureCLEARVRC suction pressure clear trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.23012
trapObj
OBJECT IDENTIFIER
.1.3.6.1.4.1.21239.5.2.32767.1
trapSeverityIndicates the severity of the trap: 0 = None 1 = Warning 2 = Alarmro
Enumeration
.1.3.6.1.4.1.21239.5.2.32767.1.1
trapThreshTypeOnly sent for threshold alarms. Identifies the threshold type: 1 = Low 2 = Highro
Enumeration
.1.3.6.1.4.1.21239.5.2.32767.1.2
common
OBJECT IDENTIFIER
.1.3.6.1.4.1.21239.42
identity
OBJECT IDENTIFIER
.1.3.6.1.4.1.21239.42.1
r05Value given for sysObjectID on R-Series units
OBJECT IDENTIFIER
.1.3.6.1.4.1.21239.42.1.15
i03Value given for sysObjectID on IMD3 units
OBJECT IDENTIFIER
.1.3.6.1.4.1.21239.42.1.53