VERTIV-V5-MIB
AI MIB Summary
The VERTIV-V5-MIB module provides SNMP-based monitoring and management capabilities for Vertiv power and thermal infrastructure devices, including UPS systems, precision cooling units, and environmental sensors. It exposes critical operational metrics such as input/output voltage and current, battery status, temperature readings, fan speeds, and alarm states to facilitate real-time infrastructure health assessment.
The MIB for Vertiv products
Main OID:
vertiv.1.3.6.1.4.1.21239
570
Objects
Active
Status
4
Dependencies
Imported Objects
Objects
570 total| Object Name |
|---|
vertivThe MIB for Vertiv products MODULE-IDENTITY .1.3.6.1.4.1.21239 |
v5 OBJECT IDENTIFIER .1.3.6.1.4.1.21239.5 |
imd OBJECT IDENTIFIER .1.3.6.1.4.1.21239.5.2 |
deviceInfo OBJECT IDENTIFIER .1.3.6.1.4.1.21239.5.2.1 |
productTitleProduct namero SnmpAdminString (SNMP-FRAMEWORK-MIB) .1.3.6.1.4.1.21239.5.2.1.1 |
productVersionProduct versionro SnmpAdminString (SNMP-FRAMEWORK-MIB) .1.3.6.1.4.1.21239.5.2.1.2 |
productFriendlyNameUser-assigned namero SnmpAdminString (SNMP-FRAMEWORK-MIB) .1.3.6.1.4.1.21239.5.2.1.3 |
productMacAddressProduct's unique MAC addressro MacAddress (SNMPv2-TC) .1.3.6.1.4.1.21239.5.2.1.4 |
deviceCountTotal number of devices on unitro Integer32 .1.3.6.1.4.1.21239.5.2.1.6 |
temperatureUnitsCurrent units for temperature/dewpoint values: 0 = Degrees Fahrenheit 1 = Degrees Celsiusrw Enumeration .1.3.6.1.4.1.21239.5.2.1.7 |
productModelNumberProduct model number (factory-assigned)ro SnmpAdminString (SNMP-FRAMEWORK-MIB) .1.3.6.1.4.1.21239.5.2.1.8 |
productPartNumberProduct part number (factory-assigned)ro SnmpAdminString (SNMP-FRAMEWORK-MIB) .1.3.6.1.4.1.21239.5.2.1.9 |
productSerialNumberProduct serial number (factory-assigned)ro SnmpAdminString (SNMP-FRAMEWORK-MIB) .1.3.6.1.4.1.21239.5.2.1.10 |
productPlatformProduct platformro SnmpAdminString (SNMP-FRAMEWORK-MIB) .1.3.6.1.4.1.21239.5.2.1.11 |
productHostnameProduct hostnamero SnmpAdminString (SNMP-FRAMEWORK-MIB) .1.3.6.1.4.1.21239.5.2.1.12 |
productAlarmCountNumber of alarms currently trippedro Integer32 .1.3.6.1.4.1.21239.5.2.1.13 |
productWarnCountNumber of warnings currently trippedro Integer32 .1.3.6.1.4.1.21239.5.2.1.14 |
productManufacturerProduct manufacturerro SnmpAdminString (SNMP-FRAMEWORK-MIB) .1.3.6.1.4.1.21239.5.2.1.15 |
pdu OBJECT IDENTIFIER .1.3.6.1.4.1.21239.5.2.3 |
pduMainTablePDU general information SEQUENCE OF PduMainEntry .1.3.6.1.4.1.21239.5.2.3.1 |
pduMainEntryEntry in the pduMainTable table: each entry contains an index and other sensor details PduMainEntry .1.3.6.1.4.1.21239.5.2.3.1.1 |
pduMainIndexTable entry index value Integer32 .1.3.6.1.4.1.21239.5.2.3.1.1.1 |
pduMainSerialSerial numberro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.21239.5.2.3.1.1.2 |
pduMainNamePDU name (factory-assigned)ro SnmpAdminString .1.3.6.1.4.1.21239.5.2.3.1.1.3 |
pduMainLabelPDU label (user-defined)rw SnmpAdminString .1.3.6.1.4.1.21239.5.2.3.1.1.4 |
pduMainAvailDevice availability: 0 = Unavailable 1 = Available 2 = Partially Unavailablero Gauge32 .1.3.6.1.4.1.21239.5.2.3.1.1.5 |
pduMeterTypeCurrent meter type: 0 = Wye 1 = Deltaro Enumeration .1.3.6.1.4.1.21239.5.2.3.1.1.6 |
pduTotalNameTotal name (factory-assigned)ro SnmpAdminString .1.3.6.1.4.1.21239.5.2.3.1.1.7 |
pduTotalLabelTotal label (user-defined)rw SnmpAdminString .1.3.6.1.4.1.21239.5.2.3.1.1.8 |
pduTotalRealPowerPDU total real powerro Gauge32 .1.3.6.1.4.1.21239.5.2.3.1.1.9 |
pduTotalApparentPowerPDU total apparent powerro Gauge32 .1.3.6.1.4.1.21239.5.2.3.1.1.10 |
pduTotalPowerFactorPDU total power factorro Gauge32 .1.3.6.1.4.1.21239.5.2.3.1.1.11 |
pduTotalEnergyPDU total accumulated energy in watt-hoursro Gauge32 .1.3.6.1.4.1.21239.5.2.3.1.1.12 |
pduPhaseTablePDU phases information SEQUENCE OF PduPhaseEntry .1.3.6.1.4.1.21239.5.2.3.2 |
pduPhaseEntryEntry in the pduPhaseTable table: each entry contains an index and other sensor details PduPhaseEntry .1.3.6.1.4.1.21239.5.2.3.2.1 |
pduPhaseIndexTable entry index value Integer32 .1.3.6.1.4.1.21239.5.2.3.2.1.1 |
pduPhaseNamePDU phase name (factory-assigned)ro SnmpAdminString .1.3.6.1.4.1.21239.5.2.3.2.1.2 |
pduPhaseLabelPDU phase label (user-defined)rw SnmpAdminString .1.3.6.1.4.1.21239.5.2.3.2.1.3 |
pduPhaseVoltagePDU phase voltage in tenths of a voltro Gauge32 .1.3.6.1.4.1.21239.5.2.3.2.1.4 |
pduPhaseCurrentPDU phase current reading in hundredths of an ampro Gauge32 .1.3.6.1.4.1.21239.5.2.3.2.1.8 |
pduPhaseRealPowerReal power for phase in wattsro Gauge32 .1.3.6.1.4.1.21239.5.2.3.2.1.12 |
pduPhaseApparentPowerApparent power for phase in volt-ampsro Gauge32 .1.3.6.1.4.1.21239.5.2.3.2.1.13 |
pduPhasePowerFactorPower factor for phasero Gauge32 .1.3.6.1.4.1.21239.5.2.3.2.1.14 |
pduPhaseEnergyAccumulated energy for phase in watt-hoursro Gauge32 .1.3.6.1.4.1.21239.5.2.3.2.1.15 |
pduPhaseBalancePhase balance as percentro Gauge32 .1.3.6.1.4.1.21239.5.2.3.2.1.17 |
pduPhaseCurrentCrestFactorCurrent crest factor for phase, in hundredthsro Gauge32 .1.3.6.1.4.1.21239.5.2.3.2.1.19 |
pduBreakerTablePDU breaker information SEQUENCE OF PduBreakerEntry .1.3.6.1.4.1.21239.5.2.3.3 |
pduBreakerEntryEntry in the pduBreakerTable table: each entry contains an index and other sensor details PduBreakerEntry .1.3.6.1.4.1.21239.5.2.3.3.1 |
pduBreakerIndexTable entry index value Integer32 .1.3.6.1.4.1.21239.5.2.3.3.1.1 |
pduBreakerNamePDU breaker name (factory-assigned)ro SnmpAdminString .1.3.6.1.4.1.21239.5.2.3.3.1.2 |
pduBreakerLabelPDU breaker label (user-defined)rw SnmpAdminString .1.3.6.1.4.1.21239.5.2.3.3.1.3 |
pduBreakerCurrentPDU breaker current reading in hundredths of an ampro Gauge32 .1.3.6.1.4.1.21239.5.2.3.3.1.4 |
pduBreakerVoltagePDU breaker voltage in tenths of a volt. This object may not exist on all platforms, due to hardware differences.ro Gauge32 .1.3.6.1.4.1.21239.5.2.3.3.1.8 |
pduBreakerRealPowerReal power for breaker in watts. This object may not exist on all platforms, due to hardware differences.ro Gauge32 .1.3.6.1.4.1.21239.5.2.3.3.1.12 |
pduBreakerApparentPowerApparent power for breaker in volt-amps. This object may not exist on all platforms, due to hardware differences.ro Gauge32 .1.3.6.1.4.1.21239.5.2.3.3.1.13 |
pduBreakerPowerFactorPower factor for breaker. This object may not exist on all platforms, due to hardware differences.ro Gauge32 .1.3.6.1.4.1.21239.5.2.3.3.1.14 |
pduBreakerEnergyAccumulated energy for breaker in watt-hours. This object may not exist on all platforms, due to hardware differences.ro Gauge32 .1.3.6.1.4.1.21239.5.2.3.3.1.15 |
pduLineTablePDU line current information SEQUENCE OF PduLineEntry .1.3.6.1.4.1.21239.5.2.3.4 |
pduLineEntryEntry in the pduLineTable table: each entry contains an index and other sensor details PduLineEntry .1.3.6.1.4.1.21239.5.2.3.4.1 |
pduLineIndexTable entry index value Integer32 .1.3.6.1.4.1.21239.5.2.3.4.1.1 |
pduLineNamePDU line name (factory-assigned)ro SnmpAdminString .1.3.6.1.4.1.21239.5.2.3.4.1.2 |
pduLineLabelPDU line label (user-defined)rw SnmpAdminString .1.3.6.1.4.1.21239.5.2.3.4.1.3 |
pduLineCurrentPDU line current reading in hundredths of an ampro Gauge32 .1.3.6.1.4.1.21239.5.2.3.4.1.4 |
pduOutletSwitchTableData, config and control for outlets with switching SEQUENCE OF PduOutletSwitchEntry .1.3.6.1.4.1.21239.5.2.3.5 |
pduOutletSwitchEntryEntry in the pduOutletSwitchTable table: each entry contains an index and other sensor details PduOutletSwitchEntry .1.3.6.1.4.1.21239.5.2.3.5.1 |
pduOutletSwitchIndexTable entry index value Integer32 .1.3.6.1.4.1.21239.5.2.3.5.1.1 |
pduOutletSwitchNamePDU outlet name (factory-assigned)ro SnmpAdminString .1.3.6.1.4.1.21239.5.2.3.5.1.2 |
pduOutletSwitchLabelPDU outlet label (user-defined)rw SnmpAdminString .1.3.6.1.4.1.21239.5.2.3.5.1.3 |
pduOutletSwitchStateSwitch state of the outlet: 1 = Outlet is on 2 = Outlet is off 3 = Outlet is on, but will turn off after a delay 4 = Outlet is off, but will turn on after a delay 5 = Starting reboot cycle, outlet is on, but will go to the rebootOff(6) state after a delay 6 = Rebooting, outlet is off, but it will turn on after a delay 7 = Cannot get outlet statero Enumeration .1.3.6.1.4.1.21239.5.2.3.5.1.4 |
pduOutletSwitchRelayFailureTells if the outlet relay has failed. In normal operation, the value will be false(2).ro TruthValue (SNMPv2-TC) .1.3.6.1.4.1.21239.5.2.3.5.1.5 |
pduOutletSwitchControlUsed for manual control of the outlet. If the outlet is in manual mode, this field can be set to one of the following values: 1 = Cancel pending operation 2 = Turn outlet on 3 = After delay (pduOutletSwitchOnDelay), turn outlet on 4 = Turn outlet off 5 = After delay (pduOutletSwitchOffDelay), turn outlet off 6 = Reboot: turn off, delay (pduOutletSwitchRebootHoldDelay), turn outlet back on 7 = After delay (pduOutletSwitchRebootDelay), reboot outlet When not in manual mode, setting this field will give an inconsistentValue error. Returns none(8) for all get requests.rw Enumeration .1.3.6.1.4.1.21239.5.2.3.5.1.6 |
pduOutletSwitchTimeToActionSeconds until an outlet state change. The value of pduOutletSwitchState tells what state the outlet will be set, after the delay.ro Integer32 .1.3.6.1.4.1.21239.5.2.3.5.1.7 |
pduOutletSwitchOnDelaySeconds to wait before powering on the outlet, during onAfterDelay(3) operation. Changing this value has no effect on pending actions.rw Integer32 .1.3.6.1.4.1.21239.5.2.3.5.1.8 |
pduOutletSwitchOffDelaySeconds to wait before powering off the outlet, during offAfterDelay(5) operation. Changing this value has no effect on pending actions.rw Integer32 .1.3.6.1.4.1.21239.5.2.3.5.1.9 |
pduOutletSwitchRebootDelaySeconds to wait before powering off the outlet, during rebootAfterDelay(7) operation. Changing this value has no effect on pending actions. See pduOutletSwitchControl for more info.rw Integer32 .1.3.6.1.4.1.21239.5.2.3.5.1.10 |
pduOutletSwitchRebootHoldDelaySeconds to hold the outlet off, before powering on the outlet, during rebootAfterDelay(7) operation. Changing this value has no effect on pending actions. See pduOutletSwitchControl for more info.rw Integer32 .1.3.6.1.4.1.21239.5.2.3.5.1.11 |
pduOutletSwitchPoaActionThe outlet is set to this state during power-up. The action can be have one the following values: 1 = Outlet will be turned on 2 = Outlet will stay off 3 = Outlet will be set to last known staterw Enumeration .1.3.6.1.4.1.21239.5.2.3.5.1.12 |
pduOutletSwitchPoaDelaySeconds to wait before setting the outlet to the pduOutletSwitchPoaAction state. The delay starts at power-up.rw Integer32 .1.3.6.1.4.1.21239.5.2.3.5.1.13 |
pduOutletMeterTableMetering data for outlets that support this feature SEQUENCE OF PduOutletMeterEntry .1.3.6.1.4.1.21239.5.2.3.6 |
pduOutletMeterEntryEntry in the pduOutletMeterTable table: each entry contains an index and other sensor details PduOutletMeterEntry .1.3.6.1.4.1.21239.5.2.3.6.1 |
pduOutletMeterIndexTable entry index value Integer32 .1.3.6.1.4.1.21239.5.2.3.6.1.1 |
pduOutletMeterNamePDU outlet name (factory-assigned)ro SnmpAdminString .1.3.6.1.4.1.21239.5.2.3.6.1.2 |
pduOutletMeterLabelPDU outlet label (user-defined)rw SnmpAdminString .1.3.6.1.4.1.21239.5.2.3.6.1.3 |
pduOutletMeterVoltagePDU outlet voltage in tenths of a voltro Gauge32 .1.3.6.1.4.1.21239.5.2.3.6.1.4 |
pduOutletMeterCurrentPDU outlet current reading in hundredths of an ampro Gauge32 .1.3.6.1.4.1.21239.5.2.3.6.1.8 |
pduOutletMeterRealPowerReal power for outlet in wattsro Gauge32 .1.3.6.1.4.1.21239.5.2.3.6.1.12 |
pduOutletMeterApparentPowerApparent power for outlet in volt-ampsro Gauge32 .1.3.6.1.4.1.21239.5.2.3.6.1.13 |
pduOutletMeterPowerFactorPower factor for outletro Gauge32 .1.3.6.1.4.1.21239.5.2.3.6.1.14 |
pduOutletMeterEnergyAccumulated energy for outlet in watt-hoursro Gauge32 .1.3.6.1.4.1.21239.5.2.3.6.1.15 |
pduOutletMeterResetUsed to reset energy. If read, the value is none(8). It can be set to resetEnergy(1), which sets outlet energy to 0rw Enumeration .1.3.6.1.4.1.21239.5.2.3.6.1.16 |
pduOutletCurrentCrestFactorCurrent crest factor for outlet, in hundredthsro Gauge32 .1.3.6.1.4.1.21239.5.2.3.6.1.19 |
tempSensorTableRemote Temperature (RT) sensor SEQUENCE OF TempSensorEntry .1.3.6.1.4.1.21239.5.2.4 |
tempSensorEntryEntry in the tempSensorTable table: each entry contains an index and other sensor details TempSensorEntry .1.3.6.1.4.1.21239.5.2.4.1 |
tempSensorIndexTable entry index value Integer32 .1.3.6.1.4.1.21239.5.2.4.1.1 |
tempSensorSerialSerial numberro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.21239.5.2.4.1.2 |
tempSensorLabelUser-defined labelrw SnmpAdminString .1.3.6.1.4.1.21239.5.2.4.1.3 |
tempSensorAvailDevice availability: 0 = Unavailable 1 = Available 2 = Partially Unavailablero Gauge32 .1.3.6.1.4.1.21239.5.2.4.1.4 |
tempSensorTempTemperature in tenths of a degree. Units are given by temperatureUnits field in deviceInfo.ro Integer32(-400..2540) UNITS "decidegrees" .1.3.6.1.4.1.21239.5.2.4.1.5 |
airFlowSensorTableRemote Airflow, Humidity, Temperature and Dewpoint (AFHT3) Sensor SEQUENCE OF AirFlowSensorEntry .1.3.6.1.4.1.21239.5.2.5 |
airFlowSensorEntryEntry in the airFlowSensorTable table: each entry contains an index and other sensor details AirFlowSensorEntry .1.3.6.1.4.1.21239.5.2.5.1 |
airFlowSensorIndexTable entry index value Integer32 .1.3.6.1.4.1.21239.5.2.5.1.1 |
airFlowSensorSerialSerial numberro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.21239.5.2.5.1.2 |
airFlowSensorLabelUser-defined labelrw SnmpAdminString .1.3.6.1.4.1.21239.5.2.5.1.3 |
airFlowSensorAvailDevice availability: 0 = Unavailable 1 = Available 2 = Partially Unavailablero Gauge32 .1.3.6.1.4.1.21239.5.2.5.1.4 |
airFlowSensorTempTemperature reading in tenths of a degree. Units are given by temperatureUnits field in deviceInfo.ro Integer32(-400..2540) UNITS "decidegrees" .1.3.6.1.4.1.21239.5.2.5.1.5 |
airFlowSensorFlowAirflow reading. Still air will be less than 20, while rushing air will be around 100.ro Integer32 .1.3.6.1.4.1.21239.5.2.5.1.6 |
airFlowSensorHumidityHumidity readingro Integer32 .1.3.6.1.4.1.21239.5.2.5.1.7 |
airFlowSensorDewPointDewpoint reading in tenths of a degree. Units are given by temperatureUnits field in deviceInfo.ro Integer32(-400..2540) UNITS "decidegrees" .1.3.6.1.4.1.21239.5.2.5.1.8 |
t3hdSensorTableRemote Temperature x 3, Humidity and Dewpoint Sensor SEQUENCE OF T3hdSensorEntry .1.3.6.1.4.1.21239.5.2.8 |
t3hdSensorEntryEntry in the t3hdSensorTable table: each entry contains an index and other sensor details T3hdSensorEntry .1.3.6.1.4.1.21239.5.2.8.1 |
t3hdSensorIndexTable entry index value Integer32 .1.3.6.1.4.1.21239.5.2.8.1.1 |
t3hdSensorSerialSerial numberro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.21239.5.2.8.1.2 |
t3hdSensorLabelUser-defined labelrw SnmpAdminString .1.3.6.1.4.1.21239.5.2.8.1.3 |
t3hdSensorAvailDevice availability: 0 = Unavailable 1 = Available 2 = Partially Unavailablero Gauge32 .1.3.6.1.4.1.21239.5.2.8.1.4 |
t3hdSensorIntLabelInternal label (user-defined)rw SnmpAdminString .1.3.6.1.4.1.21239.5.2.8.1.5 |
t3hdSensorIntTempInternal temperature in tenths of a degree. Units are given by temperatureUnits field in deviceInfo.ro Integer32(-400..2540) UNITS "decidegrees" .1.3.6.1.4.1.21239.5.2.8.1.6 |
t3hdSensorIntHumidityInternal humidityro Integer32 .1.3.6.1.4.1.21239.5.2.8.1.7 |
t3hdSensorIntDewPointInternal dewpoint in tenths of a degree. Units are given by temperatureUnits field in deviceInfo.ro Integer32(-400..2540) UNITS "decidegrees" .1.3.6.1.4.1.21239.5.2.8.1.8 |
t3hdSensorExtAAvailExternal A status: 0 = Unavailable 1 = Availablero Gauge32 .1.3.6.1.4.1.21239.5.2.8.1.9 |
t3hdSensorExtALabelExternal A label (user-defined)rw SnmpAdminString .1.3.6.1.4.1.21239.5.2.8.1.10 |
t3hdSensorExtATempExternal A temperature in tenths of a degree. Units are given by temperatureUnits field in deviceInfo.ro Integer32(-400..2540) UNITS "decidegrees" .1.3.6.1.4.1.21239.5.2.8.1.11 |
t3hdSensorExtBAvailExternal B status: 0 = Unavailable 1 = Availablero Gauge32 .1.3.6.1.4.1.21239.5.2.8.1.12 |
t3hdSensorExtBLabelExternal B label (user-defined)rw SnmpAdminString .1.3.6.1.4.1.21239.5.2.8.1.13 |
t3hdSensorExtBTempExternal B temperature in tenths of a degree. Units are given by temperatureUnits field in deviceInfo.ro Integer32(-400..2540) UNITS "decidegrees" .1.3.6.1.4.1.21239.5.2.8.1.14 |
thdSensorTableRemote Temperature, Humidity, and Dewpoint (THD) Sensor SEQUENCE OF ThdSensorEntry .1.3.6.1.4.1.21239.5.2.9 |
thdSensorEntryEntry in the thdSensorTable table: each entry contains an index and other sensor details ThdSensorEntry .1.3.6.1.4.1.21239.5.2.9.1 |
thdSensorIndexTable entry index value Integer32 .1.3.6.1.4.1.21239.5.2.9.1.1 |
thdSensorSerialSerial numberro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.21239.5.2.9.1.2 |
thdSensorLabelUser-defined labelrw SnmpAdminString .1.3.6.1.4.1.21239.5.2.9.1.3 |
thdSensorAvailDevice availability: 0 = Unavailable 1 = Available 2 = Partially Unavailablero Gauge32 .1.3.6.1.4.1.21239.5.2.9.1.4 |
thdSensorTempTemperature value in tenths of a degree. Units are given by temperatureUnits field in deviceInfo.ro Integer32(-400..2540) UNITS "decidegrees" .1.3.6.1.4.1.21239.5.2.9.1.5 |
thdSensorHumidityHumidity valuero Integer32 .1.3.6.1.4.1.21239.5.2.9.1.6 |
thdSensorDewPointDewpoint value in tenths of a degree. Units are given by temperatureUnits field in deviceInfo.ro Integer32(-400..2540) UNITS "decidegrees" .1.3.6.1.4.1.21239.5.2.9.1.7 |
a2dSensorTableAnalog measurement (A2D) sensor (voltage, current, or dry-contact) SEQUENCE OF A2dSensorEntry .1.3.6.1.4.1.21239.5.2.11 |
a2dSensorEntryEntry in the a2dSensorTable table: each entry contains an index and other sensor details A2dSensorEntry .1.3.6.1.4.1.21239.5.2.11.1 |
a2dSensorIndexTable entry index value Integer32 .1.3.6.1.4.1.21239.5.2.11.1.1 |
a2dSensorSerialSerial numberro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.21239.5.2.11.1.2 |
a2dSensorLabelUser-defined labelrw SnmpAdminString .1.3.6.1.4.1.21239.5.2.11.1.3 |
a2dSensorAvailDevice availability: 0 = Unavailable 1 = Available 2 = Partially Unavailablero Gauge32 .1.3.6.1.4.1.21239.5.2.11.1.4 |
a2dSensorValueAnalog measurement value, within either a user-defined or preset range, depending on a2dSensorMode.ro Integer32(-1000000..1000000) .1.3.6.1.4.1.21239.5.2.11.1.5 |
a2dSensorDisplayValueFor current/voltage modes, the analog value is given as a string. In binary modes, the value is either a2dSensorLowLabel or a2dSensorHighLabel, based on a2dSensorValue.ro SnmpAdminString .1.3.6.1.4.1.21239.5.2.11.1.6 |
a2dSensorModeBinary modes have two states represented by the values 0 (low) or 1 (high). These correspond to a2dSensorLowLabel and a2dSensorHighLabel. Current and voltage modes provide a scaled value from a2dSensorMin to a2dSensorMax. Analog modes: 1 = Door (binary) 2 = Power failure (binary) 3 = Flood (binary) 4 = Water-sensing cable leak (binary) 5 = Water-sensing cable fault (binary) 6 = Smoke alarm (binary) 7 = Isolated voltage negative ground (voltage) 8 = Isolated voltage positive ground (voltage) 9 = Custom voltage (voltage) 10 = Custom binary (binary) 11 = Custom current (current)rw Enumeration .1.3.6.1.4.1.21239.5.2.11.1.7 |
a2dSensorUnitsThe units for the analog value. If a2dSensorMode is customVoltage(9) or customCurrent(11), then this field has a user-defined value. Otherwise, the value is fixed, based on mode.rw SnmpAdminString .1.3.6.1.4.1.21239.5.2.11.1.8 |
a2dSensorMinMinimum analog value, given as an integer. The analog measurement is scaled to the range a2dSensorMin to a2dSensorMax. If a2dSensorMode is customVoltage(9) or customCurrent(11), then this field has a user- defined value. Otherwise, the value is fixed, based on mode.rw Integer32(-1000000..1000000) .1.3.6.1.4.1.21239.5.2.11.1.9 |
a2dSensorMaxMaximum analog value, given as an integer. The analog measurement is scaled to the range a2dSensorMin to a2dSensorMax. If a2dSensorMode is customVoltage(9) or customCurrent(11), then this field has a user- defined value. Otherwise, the value is fixed, based on mode.rw Integer32(-1000000..1000000) .1.3.6.1.4.1.21239.5.2.11.1.10 |
a2dSensorLowLabelLabel for 0 (low) binary value. This field is only applicable if a2dSensorMode is one of the binary modes. If a2dSensorMode is customBinary(10), then this field is user-defined. Otherwise, it has a pre-defined value based on the mode.rw SnmpAdminString .1.3.6.1.4.1.21239.5.2.11.1.11 |
a2dSensorHighLabelLabel for 1 (high) binary value. The field is only applicable if a2dSensorMode is one of the binary modes. If a2dSensorMode is customBinary(10), then this field is user-defined. Otherwise, it has a pre-defined value based on the mode.rw SnmpAdminString .1.3.6.1.4.1.21239.5.2.11.1.12 |
a2dSensorAnalogLabelLabel for the analog measurementrw SnmpAdminString .1.3.6.1.4.1.21239.5.2.11.1.13 |
humiditySensorTableRemote humidity sensor SEQUENCE OF HumiditySensorEntry .1.3.6.1.4.1.21239.5.2.12 |
humiditySensorEntryEntry in the humiditySensorTable table: each entry contains an index and other sensor details HumiditySensorEntry .1.3.6.1.4.1.21239.5.2.12.1 |
humiditySensorIndexTable entry index value Integer32 .1.3.6.1.4.1.21239.5.2.12.1.1 |
humiditySensorSerialSerial numberro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.21239.5.2.12.1.2 |
humiditySensorLabelUser-defined labelrw SnmpAdminString .1.3.6.1.4.1.21239.5.2.12.1.3 |
humiditySensorAvailDevice availability: 0 = Unavailable 1 = Available 2 = Partially Unavailablero Gauge32 .1.3.6.1.4.1.21239.5.2.12.1.4 |
humiditySensorValueHumidity valuero Integer32 .1.3.6.1.4.1.21239.5.2.12.1.5 |
sn2dSensorTable2 Door Switch Sensor (SN-2D) SEQUENCE OF Sn2dSensorEntry .1.3.6.1.4.1.21239.5.2.13 |
sn2dSensorEntryEntry in the sn2dSensorTable table: each entry contains an index and other sensor details Sn2dSensorEntry .1.3.6.1.4.1.21239.5.2.13.1 |
sn2dSensorIndexTable entry index value Integer32 .1.3.6.1.4.1.21239.5.2.13.1.1 |
sn2dSensorSerialSerial numberro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.21239.5.2.13.1.2 |
sn2dSensorLabelUser-defined labelrw SnmpAdminString .1.3.6.1.4.1.21239.5.2.13.1.3 |
sn2dSensorAvailDevice availability: 0 = Unavailable 1 = Available 2 = Partially Unavailablero Gauge32 .1.3.6.1.4.1.21239.5.2.13.1.4 |
sn2dSensorDoor1LabelDoor switch 1 labelrw SnmpAdminString .1.3.6.1.4.1.21239.5.2.13.1.5 |
sn2dSensorDoor1StateDoor switch 1 state: 1 = open 2 = closedro Enumeration .1.3.6.1.4.1.21239.5.2.13.1.6 |
sn2dSensorDoor1DisplayStateDoor switch 1 state given as a stringro SnmpAdminString .1.3.6.1.4.1.21239.5.2.13.1.7 |
sn2dSensorDoor2LabelDoor switch 2 labelrw SnmpAdminString .1.3.6.1.4.1.21239.5.2.13.1.8 |
sn2dSensorDoor2StateDoor switch 2 state: 1 = open 2 = closedro Enumeration .1.3.6.1.4.1.21239.5.2.13.1.9 |
sn2dSensorDoor2DisplayStateDoor switch 2 state given as a stringro SnmpAdminString .1.3.6.1.4.1.21239.5.2.13.1.10 |
cooling OBJECT IDENTIFIER .1.3.6.1.4.1.21239.5.2.30 |
vrc OBJECT IDENTIFIER .1.3.6.1.4.1.21239.5.2.30.1 |
vrcMainTableTable that contains general VRC information SEQUENCE OF VrcMainEntry .1.3.6.1.4.1.21239.5.2.30.1.1 |
vrcMainEntryEntry in the vrcMainTable: each entry represents a VRC device VrcMainEntry .1.3.6.1.4.1.21239.5.2.30.1.1.1 |
vrcMainIndexUnique id for each entry in the table Integer32 .1.3.6.1.4.1.21239.5.2.30.1.1.1.1 |
vrcMainSerialSerial numberro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.21239.5.2.30.1.1.1.2 |
vrcMainNameVRC name (factory-assigned)ro SnmpAdminString .1.3.6.1.4.1.21239.5.2.30.1.1.1.3 |
vrcMainLabelVRC label (user-defined)rw SnmpAdminString .1.3.6.1.4.1.21239.5.2.30.1.1.1.4 |
vrcMainAvailDevice availability: 0 = Unavailable 1 = Available 2 = Partially Unavailablero Gauge32 .1.3.6.1.4.1.21239.5.2.30.1.1.1.5 |
vrcMainPtTableTable that contains general VRC status SEQUENCE OF VrcMainPtEntry .1.3.6.1.4.1.21239.5.2.30.1.2 |
vrcMainPtEntryEntry in the vrcMainPtTable: each entry contains status data for a VRC device VrcMainPtEntry .1.3.6.1.4.1.21239.5.2.30.1.2.1 |
vrcMainPtIndexUnique id for each entry in the table Integer32 .1.3.6.1.4.1.21239.5.2.30.1.2.1.1 |
vrcMainPtRunStateVRC run state: 1 = on 2 = offro Enumeration .1.3.6.1.4.1.21239.5.2.30.1.2.1.2 |
vrcMainPtEevOpenedEev opened value (percent)ro Integer32 .1.3.6.1.4.1.21239.5.2.30.1.2.1.3 |
vrcMainPtAlarmNumbersAlarm numbers valuero Integer32(-32768..32767) .1.3.6.1.4.1.21239.5.2.30.1.2.1.4 |
vrcMainPtHistoryAlarmNumbersHistory alarm numbers valuero Integer32(-32768..32767) .1.3.6.1.4.1.21239.5.2.30.1.2.1.5 |
vrcMainPtHpAbnRecordCntHp Abnormal record countro Integer32(-32768..32767) .1.3.6.1.4.1.21239.5.2.30.1.2.1.6 |
vrcMainPtMonitorBaudrateMonitor baud rate: 1 = error 2 = 1200 3 = 2400 4 = 4800 5 = 9600 6 = 19200ro Enumeration .1.3.6.1.4.1.21239.5.2.30.1.2.1.7 |
vrcMainPtMonitorAddressMonitor addressro Integer32 .1.3.6.1.4.1.21239.5.2.30.1.2.1.8 |
vrcMainPtLpLp statusro TruthValue (SNMPv2-TC) .1.3.6.1.4.1.21239.5.2.30.1.2.1.9 |
vrcMainPtFilterMaintRemindFilter maintenance reminder statusro TruthValue (SNMPv2-TC) .1.3.6.1.4.1.21239.5.2.30.1.2.1.10 |
vrcMainPtCoolingFlagCooling flagro TruthValue (SNMPv2-TC) .1.3.6.1.4.1.21239.5.2.30.1.2.1.11 |
vrcMainPtFirstOnFlagFirst on flagro TruthValue (SNMPv2-TC) .1.3.6.1.4.1.21239.5.2.30.1.2.1.12 |
vrcMainPtNewAlarmFlagNew alarm flagro TruthValue (SNMPv2-TC) .1.3.6.1.4.1.21239.5.2.30.1.2.1.13 |
vrcMainPtComAlarmOutStateCommon alarm output statero TruthValue (SNMPv2-TC) .1.3.6.1.4.1.21239.5.2.30.1.2.1.14 |
vrcMainPtHighWaterInputHigh water inputro TruthValue (SNMPv2-TC) .1.3.6.1.4.1.21239.5.2.30.1.2.1.15 |
vrcMainPtHighWaterAlarmHigh water alarm statusro TruthValue (SNMPv2-TC) .1.3.6.1.4.1.21239.5.2.30.1.2.1.16 |
vrcMainPtWaterUnderFloorAlarmWater under floor alarm statusro TruthValue (SNMPv2-TC) .1.3.6.1.4.1.21239.5.2.30.1.2.1.17 |
vrcMainPtSwShutDownStatusSoftware shutdown statusro TruthValue (SNMPv2-TC) .1.3.6.1.4.1.21239.5.2.30.1.2.1.18 |
vrcMainPtRemoteShutdownRemote shutdown statusro TruthValue (SNMPv2-TC) .1.3.6.1.4.1.21239.5.2.30.1.2.1.19 |
vrcMainPtRemoteShutDownFlagRemote shutdown flagro TruthValue (SNMPv2-TC) .1.3.6.1.4.1.21239.5.2.30.1.2.1.20 |
vrcMainPtRemoteShutDownAlarmRemote shutdown alarm statusro TruthValue (SNMPv2-TC) .1.3.6.1.4.1.21239.5.2.30.1.2.1.21 |
vrcMainPtHmiShutDownFlagHmi shutdown flagro TruthValue (SNMPv2-TC) .1.3.6.1.4.1.21239.5.2.30.1.2.1.22 |
vrcMainPtLpAlarmLow pressure alarm statusro TruthValue (SNMPv2-TC) .1.3.6.1.4.1.21239.5.2.30.1.2.1.23 |
vrcMainPtHpAlarmHigh pressure alarm statusro TruthValue (SNMPv2-TC) .1.3.6.1.4.1.21239.5.2.30.1.2.1.24 |
vrcMainPtLpFreqAlarmLow pressure frequently alarm statusro TruthValue (SNMPv2-TC) .1.3.6.1.4.1.21239.5.2.30.1.2.1.25 |
vrcMainPtHpFreqAlarmHigh pressure frequently alarm statusro TruthValue (SNMPv2-TC) .1.3.6.1.4.1.21239.5.2.30.1.2.1.26 |
vrcMainPtLpSensorFailAlarmLow pressure sensor failure alarm statusro TruthValue (SNMPv2-TC) .1.3.6.1.4.1.21239.5.2.30.1.2.1.27 |
vrcMainPtHpSensorFailAlarmHigh pressure sensor failure alarm statusro TruthValue (SNMPv2-TC) .1.3.6.1.4.1.21239.5.2.30.1.2.1.28 |
vrcMainPtEevCommFailAlarmEev communication failure alarm statusro TruthValue (SNMPv2-TC) .1.3.6.1.4.1.21239.5.2.30.1.2.1.29 |
vrcMainCfgTableTable that contains general VRC configuration SEQUENCE OF VrcMainCfgEntry .1.3.6.1.4.1.21239.5.2.30.1.3 |
vrcMainCfgEntryEntry in the vrcMainCfgTable: each entry contains general config fields for a VRC device VrcMainCfgEntry .1.3.6.1.4.1.21239.5.2.30.1.3.1 |
vrcMainCfgIndexUnique id for each entry in the table Integer32 .1.3.6.1.4.1.21239.5.2.30.1.3.1.1 |
vrcMainCfgModelSelectModel Selection: 1 = TMM-Local 220V 50/60HZ 2 = TMM-Global 208/230V 50/60HZ 3 = TMM-Global 120V 50/60HZ 4 = SC 220V 50/60HZ 5 = 0U 220V 50/60HZ 6 = SS 208/230V 50/60HZ 7 = SS 120V 50/60HZrw Enumeration .1.3.6.1.4.1.21239.5.2.30.1.3.1.2 |
vrcMainCfgSystemTimeYearSystem time - yearrw Integer32 .1.3.6.1.4.1.21239.5.2.30.1.3.1.3 |
vrcMainCfgSystemTimeMonthSystem time - monthrw Integer32 .1.3.6.1.4.1.21239.5.2.30.1.3.1.4 |
vrcMainCfgSystemTimeDaySystem time - dayrw Integer32 .1.3.6.1.4.1.21239.5.2.30.1.3.1.5 |
vrcMainCfgSystemTimeHourSystem time - hourrw Integer32 .1.3.6.1.4.1.21239.5.2.30.1.3.1.6 |
vrcMainCfgSystemTimeMinSystem time - minutesrw Integer32 .1.3.6.1.4.1.21239.5.2.30.1.3.1.7 |
vrcMainCfgSystemTimeSecSystem time - secondsrw Integer32 .1.3.6.1.4.1.21239.5.2.30.1.3.1.8 |
vrcMainCfgEevShtSettingMinMin Eev sht in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The settable range is determined by the current temperature units. Celsius: 50 to 200 Fahrenheit: 90 to 359rw Integer32 UNITS "decidegrees" .1.3.6.1.4.1.21239.5.2.30.1.3.1.9 |
vrcMainCfgEevShtSettingMaxMax Eev sht in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The settable range is determined by the current temperature units. Celsius: 50 to 200 Fahrenheit: 90 to 359rw Integer32 UNITS "decidegrees" .1.3.6.1.4.1.21239.5.2.30.1.3.1.10 |
vrcMainCfgEevValveCloseShtEev valve close sht in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The settable range is determined by the current temperature units. Celsius: 0 to 100 Fahrenheit: 0 to 179rw Integer32 UNITS "decidegrees" .1.3.6.1.4.1.21239.5.2.30.1.3.1.11 |
vrcMainCfgEevMopPressSettingEev mop pressure setting in tenths of a bar.rw Integer32 .1.3.6.1.4.1.21239.5.2.30.1.3.1.12 |
vrcMainCfgLpdtLow pressure dt in secondsrw Integer32 .1.3.6.1.4.1.21239.5.2.30.1.3.1.13 |
vrcMainCfgDeadBandDead band in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The settable range is determined by the current temperature units. Celsius: 0 to 20 Fahrenheit: 0 to 35rw Integer32 UNITS "decidegrees" .1.3.6.1.4.1.21239.5.2.30.1.3.1.14 |
vrcMainCfgOnOffSwitchOn-off switchrw TruthValue (SNMPv2-TC) .1.3.6.1.4.1.21239.5.2.30.1.3.1.15 |
vrcMainCfgVacuumStateVacuum staterw TruthValue (SNMPv2-TC) .1.3.6.1.4.1.21239.5.2.30.1.3.1.16 |
vrcMainCfgControlModeControl mode: 1 = supply 2 = returnrw Enumeration .1.3.6.1.4.1.21239.5.2.30.1.3.1.17 |
vrcMainCfgManualRunEnableManual run enablerw TruthValue (SNMPv2-TC) .1.3.6.1.4.1.21239.5.2.30.1.3.1.18 |
vrcMainCfgRemShutdownInputRemote shutdown inputrw TruthValue (SNMPv2-TC) .1.3.6.1.4.1.21239.5.2.30.1.3.1.19 |
vrcMainCfgMonitorShutDownFlagMonitor shutdown flagrw TruthValue (SNMPv2-TC) .1.3.6.1.4.1.21239.5.2.30.1.3.1.20 |
vrcMainCfgFirstOnPasswordFirst on password valuerw Integer32(-32768..32767) .1.3.6.1.4.1.21239.5.2.30.1.3.1.21 |
vrcMainCfgFilterMaintSettingFilter maintenance settingrw TruthValue (SNMPv2-TC) .1.3.6.1.4.1.21239.5.2.30.1.3.1.22 |
vrcMainCfgFilterMaintRemindTimeTime between filter maintenance reminders in daysrw Integer32 .1.3.6.1.4.1.21239.5.2.30.1.3.1.23 |
vrcMainCfgFilterMaintRemindCtrlFilter maintenance reminder: 1 = close 2 = suspend 3 = openrw Enumeration .1.3.6.1.4.1.21239.5.2.30.1.3.1.24 |
vrcMainCfgCommonAlarmOutputDirCommon alarm output directionrw TruthValue (SNMPv2-TC) .1.3.6.1.4.1.21239.5.2.30.1.3.1.25 |
vrcMainCfgHpAbnAlarmSettingAbnormal high pressure alarm value in tenths of a barrw Integer32 .1.3.6.1.4.1.21239.5.2.30.1.3.1.26 |
vrcMainCfgLpAlarmCtrlLow pressure alarm control: 2 = suspend 3 = openrw Enumeration .1.3.6.1.4.1.21239.5.2.30.1.3.1.27 |
vrcMainCfgHpAlarmCtrlHigh pressure alarm control: 2 = suspend 3 = openrw Enumeration .1.3.6.1.4.1.21239.5.2.30.1.3.1.28 |
vrcMainCfgLpFreqAlarmCtrlLow pressure frequently alarm control: 2 = suspend 3 = openrw Enumeration .1.3.6.1.4.1.21239.5.2.30.1.3.1.29 |
vrcMainCfgHpFreqAlarmCtrlHigh pressure frequently alarm control: 2 = suspend 3 = openrw Enumeration .1.3.6.1.4.1.21239.5.2.30.1.3.1.30 |
vrcMainCfgLpSensorFailAlarmCtrlLow pressure sensor failure alarm control: 2 = suspend 3 = openrw Enumeration .1.3.6.1.4.1.21239.5.2.30.1.3.1.31 |
vrcMainCfgHpSensorFailAlarmCtrlHigh pressure sensor failure alarm control: 2 = suspend 3 = openrw Enumeration .1.3.6.1.4.1.21239.5.2.30.1.3.1.32 |
vrcMainCfgHighWaterAlarmCtrlHigh water alarm control: 1 = close 2 = suspend 3 = openrw Enumeration .1.3.6.1.4.1.21239.5.2.30.1.3.1.33 |
vrcMainCfgRemShutdownAlarmCtrlRemote shutdown alarm control: 2 = suspend 3 = openrw Enumeration .1.3.6.1.4.1.21239.5.2.30.1.3.1.34 |
vrcMainCfgEevCommFailAlarmCtrlEev communication failure alarm: 2 = suspend 3 = openrw Enumeration .1.3.6.1.4.1.21239.5.2.30.1.3.1.35 |
vrcOutFanPtTableTable that contains VRC out-fan status SEQUENCE OF VrcOutFanPtEntry .1.3.6.1.4.1.21239.5.2.30.1.4 |
vrcOutFanPtEntryEntry in the vrcOutFanPtTable: each entry represents data for a VRC out-fan VrcOutFanPtEntry .1.3.6.1.4.1.21239.5.2.30.1.4.1 |
vrcOutFanPtIndexUnique id for each entry in the table Integer32 .1.3.6.1.4.1.21239.5.2.30.1.4.1.1 |
vrcOutFanPtNameOut-fan name (factory-assigned)ro SnmpAdminString .1.3.6.1.4.1.21239.5.2.30.1.4.1.2 |
vrcOutFanPtSpeedFan speed (percent)ro Integer32 .1.3.6.1.4.1.21239.5.2.30.1.4.1.3 |
vrcOutFanCfgTableTable used for VRC out-fan configuration SEQUENCE OF VrcOutFanCfgEntry .1.3.6.1.4.1.21239.5.2.30.1.5 |
vrcOutFanCfgEntryEntry in the vrcOutFanCfgTable: each entry contains config fields for a VRC out-fan VrcOutFanCfgEntry .1.3.6.1.4.1.21239.5.2.30.1.5.1 |
vrcOutFanCfgIndexUnique id for each entry in the table Integer32 .1.3.6.1.4.1.21239.5.2.30.1.5.1.1 |
vrcOutFanCfgStartPressOut-fan start pressure in tenths of a barrw Integer32 .1.3.6.1.4.1.21239.5.2.30.1.5.1.2 |
vrcOutFanCfgPressSettingOut-fan pressure setting in tenths of a barrw Integer32 .1.3.6.1.4.1.21239.5.2.30.1.5.1.3 |
vrcOutFanCfgMinPowerVoltageMin out-fan voltage (percent)rw Integer32 .1.3.6.1.4.1.21239.5.2.30.1.5.1.4 |
vrcOutFanCfgMaxPowerVoltageMax out-fan voltage (percent)rw Integer32 .1.3.6.1.4.1.21239.5.2.30.1.5.1.5 |
vrcOutFanCfgSpeedOut-fan speed (percent)rw Integer32 .1.3.6.1.4.1.21239.5.2.30.1.5.1.6 |
vrcInFanPtTableTable that contains VRC in-fan status SEQUENCE OF VrcInFanPtEntry .1.3.6.1.4.1.21239.5.2.30.1.6 |
vrcInFanPtEntryEntry in the vrcInFanPtTable: each entry represents data for a VRC in- fan VrcInFanPtEntry .1.3.6.1.4.1.21239.5.2.30.1.6.1 |
vrcInFanPtIndexUnique id for each entry in the table Integer32 .1.3.6.1.4.1.21239.5.2.30.1.6.1.1 |
vrcInFanPtNameIn-fan name (factory-assigned)ro SnmpAdminString .1.3.6.1.4.1.21239.5.2.30.1.6.1.2 |
vrcInFanPtRunTimeHoursIn-fan run time in hoursro Integer32(-32768..32767) UNITS "hours" .1.3.6.1.4.1.21239.5.2.30.1.6.1.3 |
vrcInFanPtStartStopCountIn-fan start/stop countro Integer32(-32768..32767) .1.3.6.1.4.1.21239.5.2.30.1.6.1.4 |
vrcInFanCfgTableTable used for VRC in-fan configuration SEQUENCE OF VrcInFanCfgEntry .1.3.6.1.4.1.21239.5.2.30.1.7 |
vrcInFanCfgEntryEntry in the vrcInFanCfgTable: each entry contains config fields for a VRC in-fan VrcInFanCfgEntry .1.3.6.1.4.1.21239.5.2.30.1.7.1 |
vrcInFanCfgIndexUnique id for each entry in the table Integer32 .1.3.6.1.4.1.21239.5.2.30.1.7.1.1 |
vrcInFanCfgOutputStatusIn-fan output statusrw TruthValue (SNMPv2-TC) .1.3.6.1.4.1.21239.5.2.30.1.7.1.2 |
vrcInFanCfgLowSpeedStepIn-fan low speed step in tenths of a percent per secondrw Integer32 .1.3.6.1.4.1.21239.5.2.30.1.7.1.3 |
vrcInFanCfgHighSpeedStepIn-fan high speed step in tenths of a percent per secondrw Integer32 .1.3.6.1.4.1.21239.5.2.30.1.7.1.4 |
vrcInFanCfgMinSpeedMin in-fan speed (percent)rw Integer32 .1.3.6.1.4.1.21239.5.2.30.1.7.1.5 |
vrcInFanCfgStandardSpeedStandard in-fan speed (percent)rw Integer32 .1.3.6.1.4.1.21239.5.2.30.1.7.1.6 |
vrcInFanCfgMinCfcMin in-fan cfc (percent)rw Integer32 .1.3.6.1.4.1.21239.5.2.30.1.7.1.7 |
vrcInFanCfgStandardCfcStandard in-fan cfc (percent)rw Integer32 .1.3.6.1.4.1.21239.5.2.30.1.7.1.8 |
vrcInFanCfgStartDelayIn-fan start delay in secondsrw Integer32 .1.3.6.1.4.1.21239.5.2.30.1.7.1.9 |
vrcInFanCfgStopDelayIn-fan stop delay in secondsrw Integer32 .1.3.6.1.4.1.21239.5.2.30.1.7.1.10 |
vrcInFanCfgReduceSpeedDelayIn-fan reduce speed delay in secondsrw Integer32 .1.3.6.1.4.1.21239.5.2.30.1.7.1.11 |
vrcInFanCfgJumpBand1In-fan jump band 1 in tenths of a percentrw Integer32 .1.3.6.1.4.1.21239.5.2.30.1.7.1.12 |
vrcInFanCfgJumpBand2In-fan jump band 2 in tenths of a percentrw Integer32 .1.3.6.1.4.1.21239.5.2.30.1.7.1.13 |
vrcInFanCfgJumpBand3In-fan jump band 3 in tenths of a percentrw Integer32 .1.3.6.1.4.1.21239.5.2.30.1.7.1.14 |
vrcInFanCfgJumpBand4In-fan jump band 4 in tenths of a percentrw Integer32 .1.3.6.1.4.1.21239.5.2.30.1.7.1.15 |
vrcInFanCfgJumpBand5In-fan jump band 5 in tenths of a percentrw Integer32 .1.3.6.1.4.1.21239.5.2.30.1.7.1.16 |
vrcInFanCfgJumpFreq1In-fan jump frequency 1 in tenths of a percentrw Integer32 .1.3.6.1.4.1.21239.5.2.30.1.7.1.17 |
vrcInFanCfgJumpFreq2In-fan jump frequency 2 in tenths of a percentrw Integer32 .1.3.6.1.4.1.21239.5.2.30.1.7.1.18 |
vrcInFanCfgJumpFreq3In-fan jump frequency 3 in tenths of a percentrw Integer32 .1.3.6.1.4.1.21239.5.2.30.1.7.1.19 |
vrcInFanCfgJumpFreq4In-fan jump frequency 4 in tenths of a percentrw Integer32 .1.3.6.1.4.1.21239.5.2.30.1.7.1.20 |
vrcInFanCfgJumpFreq5In-fan jump frequency 5 in tenths of a percentrw Integer32 .1.3.6.1.4.1.21239.5.2.30.1.7.1.21 |
vrcInFanCfgTempPIn-fan temperature P in tenths of a degree. Units are given by temperatureUnits field in deviceInfo.rw Integer32 .1.3.6.1.4.1.21239.5.2.30.1.7.1.22 |
vrcInFanCfgTempIIn-fan temperature I in secondsrw Integer32 .1.3.6.1.4.1.21239.5.2.30.1.7.1.23 |
vrcInFanCfgTempDIn-fan temperature D in secondsrw Integer32 .1.3.6.1.4.1.21239.5.2.30.1.7.1.24 |
vrcCompPtTableTable that contains VRC compressor status SEQUENCE OF VrcCompPtEntry .1.3.6.1.4.1.21239.5.2.30.1.8 |
vrcCompPtEntryEntry in the vrcCompPtTable: each entry represents data for a VRC compressor VrcCompPtEntry .1.3.6.1.4.1.21239.5.2.30.1.8.1 |
vrcCompPtIndexUnique id for each entry in the table Integer32 .1.3.6.1.4.1.21239.5.2.30.1.8.1.1 |
vrcCompPtNameCompressor name (factory-assigned)ro SnmpAdminString .1.3.6.1.4.1.21239.5.2.30.1.8.1.2 |
vrcCompPtCapacityCompressor capacity value (percent)ro Integer32 .1.3.6.1.4.1.21239.5.2.30.1.8.1.3 |
vrcCompPtRunTimeHoursCompressor run time in hoursro Integer32(-32768..32767) UNITS "hours" .1.3.6.1.4.1.21239.5.2.30.1.8.1.4 |
vrcCompPtStartStopCountCompressor start/stop countro Integer32(-32768..32767) .1.3.6.1.4.1.21239.5.2.30.1.8.1.5 |
vrcCompPtDriverFaultU00Compressor driver fault alarm U00 statero TruthValue (SNMPv2-TC) .1.3.6.1.4.1.21239.5.2.30.1.8.1.6 |
vrcCompPtDriverFaultU01Compressor driver fault alarm U01 statero TruthValue (SNMPv2-TC) .1.3.6.1.4.1.21239.5.2.30.1.8.1.7 |
vrcCompPtDriverFaultU02Compressor driver fault alarm U02 statero TruthValue (SNMPv2-TC) .1.3.6.1.4.1.21239.5.2.30.1.8.1.8 |
vrcCompPtDriverFaultU03Compressor driver fault alarm U03 statero TruthValue (SNMPv2-TC) .1.3.6.1.4.1.21239.5.2.30.1.8.1.9 |
vrcCompPtDriverFaultU04Compressor driver fault alarm U04 statero TruthValue (SNMPv2-TC) .1.3.6.1.4.1.21239.5.2.30.1.8.1.10 |
vrcCompPtDriverFaultU05Compressor driver fault alarm U05 statero TruthValue (SNMPv2-TC) .1.3.6.1.4.1.21239.5.2.30.1.8.1.11 |
vrcCompPtDriverFaultU06Compressor driver fault alarm U06 statero TruthValue (SNMPv2-TC) .1.3.6.1.4.1.21239.5.2.30.1.8.1.12 |
vrcCompPtDriverFaultU07Compressor driver fault alarm U07 statero TruthValue (SNMPv2-TC) .1.3.6.1.4.1.21239.5.2.30.1.8.1.13 |
vrcCompPtDriverFaultU08Compressor driver fault alarm U08 statero TruthValue (SNMPv2-TC) .1.3.6.1.4.1.21239.5.2.30.1.8.1.14 |
vrcCompPtDriverFaultU09Compressor driver fault alarm U09 statero TruthValue (SNMPv2-TC) .1.3.6.1.4.1.21239.5.2.30.1.8.1.15 |
vrcCompPtDriverFaultU10Compressor driver fault alarm U10 statero TruthValue (SNMPv2-TC) .1.3.6.1.4.1.21239.5.2.30.1.8.1.16 |
vrcCompPtDriverFaultU11Compressor driver fault alarm U11 statero TruthValue (SNMPv2-TC) .1.3.6.1.4.1.21239.5.2.30.1.8.1.17 |
vrcCompPtDriverFaultU12Compressor driver fault alarm U12 statero TruthValue (SNMPv2-TC) .1.3.6.1.4.1.21239.5.2.30.1.8.1.18 |
vrcCompPtDriverFaultU13Compressor driver fault alarm U13 statero TruthValue (SNMPv2-TC) .1.3.6.1.4.1.21239.5.2.30.1.8.1.19 |
vrcCompPtDriverFaultU14Compressor driver fault alarm U14 statero TruthValue (SNMPv2-TC) .1.3.6.1.4.1.21239.5.2.30.1.8.1.20 |
vrcCompPtDriverFaultU15Compressor driver fault alarm U15 statero TruthValue (SNMPv2-TC) .1.3.6.1.4.1.21239.5.2.30.1.8.1.21 |
vrcCompPtDriverCommFailAlarmCompressor driver communication failure alarm statero TruthValue (SNMPv2-TC) .1.3.6.1.4.1.21239.5.2.30.1.8.1.22 |
vrcCompPtFaultLockAlarmCompressor fault lock alarm statero TruthValue (SNMPv2-TC) .1.3.6.1.4.1.21239.5.2.30.1.8.1.23 |
vrcCompCfgTableTable used for VRC compressor configuration SEQUENCE OF VrcCompCfgEntry .1.3.6.1.4.1.21239.5.2.30.1.9 |
vrcCompCfgEntryEntry in the vrcCompCfgTable: each entry contains config fields for a VRC compressor VrcCompCfgEntry .1.3.6.1.4.1.21239.5.2.30.1.9.1 |
vrcCompCfgIndexUnique id for each entry in the table Integer32 .1.3.6.1.4.1.21239.5.2.30.1.9.1.1 |
vrcCompCfgOutputStatusCompressor output statusrw TruthValue (SNMPv2-TC) .1.3.6.1.4.1.21239.5.2.30.1.9.1.2 |
vrcCompCfgOutputDeadBandCompressor output dead band in tenths of a percentrw Integer32 .1.3.6.1.4.1.21239.5.2.30.1.9.1.3 |
vrcCompCfgCapacityOutputValueCompressor capacity output (percent)rw Integer32 .1.3.6.1.4.1.21239.5.2.30.1.9.1.4 |
vrcCompCfgMinCapacityCompressor min capacity (percent)rw Integer32 .1.3.6.1.4.1.21239.5.2.30.1.9.1.5 |
vrcCompCfgStartCapacityCompressor start capacity (percent)rw Integer32 .1.3.6.1.4.1.21239.5.2.30.1.9.1.6 |
vrcCompCfgStandardCapacityCompressor standard capacity (percent)rw Integer32 .1.3.6.1.4.1.21239.5.2.30.1.9.1.7 |
vrcCompCfgStartCfcCompressor start cfc (percent)rw Integer32 .1.3.6.1.4.1.21239.5.2.30.1.9.1.8 |
vrcCompCfgStopCfcCompressor stop cfc (percent)rw Integer32(-200..-50) UNITS "%" .1.3.6.1.4.1.21239.5.2.30.1.9.1.9 |
vrcCompCfgMinRunTimeCompressor min run time in minutesrw Integer32 .1.3.6.1.4.1.21239.5.2.30.1.9.1.10 |
vrcCompCfgMinStopTimeCompressor min stop time in minutesrw Integer32 .1.3.6.1.4.1.21239.5.2.30.1.9.1.11 |
vrcCompCfgJumpBand1Compressor jump band 1 in tenths of a percentrw Integer32 .1.3.6.1.4.1.21239.5.2.30.1.9.1.12 |
vrcCompCfgJumpBand2Compressor jump band 2 in tenths of a percentrw Integer32 .1.3.6.1.4.1.21239.5.2.30.1.9.1.13 |
vrcCompCfgJumpBand3Compressor jump band 3 in tenths of a percentrw Integer32 .1.3.6.1.4.1.21239.5.2.30.1.9.1.14 |
vrcCompCfgJumpBand4Compressor jump band 4 in tenths of a percentrw Integer32 .1.3.6.1.4.1.21239.5.2.30.1.9.1.15 |
vrcCompCfgJumpBand5Compressor jump band 5 in tenths of a percentrw Integer32 .1.3.6.1.4.1.21239.5.2.30.1.9.1.16 |
vrcCompCfgJumpFreq1Compressor jump frequency 1 in tenths of a percentrw Integer32 .1.3.6.1.4.1.21239.5.2.30.1.9.1.17 |
vrcCompCfgJumpFreq2Compressor jump frequency 2 in tenths of a percentrw Integer32 .1.3.6.1.4.1.21239.5.2.30.1.9.1.18 |
vrcCompCfgJumpFreq3Compressor jump frequency 3 in tenths of a percentrw Integer32 .1.3.6.1.4.1.21239.5.2.30.1.9.1.19 |
vrcCompCfgJumpFreq4Compressor jump frequency 4 in tenths of a percentrw Integer32 .1.3.6.1.4.1.21239.5.2.30.1.9.1.20 |
vrcCompCfgJumpFreq5Compressor jump frequency 5 in tenths of a percentrw Integer32 .1.3.6.1.4.1.21239.5.2.30.1.9.1.21 |
vrcCompCfgTempPCompressor temperature P in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The settable range is determined by the current temperature units. Celsius: 10 to 150 Fahrenheit: 18 to 269rw Integer32 UNITS "decidegrees" .1.3.6.1.4.1.21239.5.2.30.1.9.1.22 |
vrcCompCfgTempICompressor temperature I in secondsrw Integer32 .1.3.6.1.4.1.21239.5.2.30.1.9.1.23 |
vrcCompCfgTempDCompressor temperature D in secondsrw Integer32 .1.3.6.1.4.1.21239.5.2.30.1.9.1.24 |
vrcCompCfgDriverFaultAlmCtrlCompressor driver fault alarm control: 2 = suspend 3 = openrw Enumeration .1.3.6.1.4.1.21239.5.2.30.1.9.1.25 |
vrcCompCfgDriverCommFailAlmCtrlCompressor driver communication failure alarm control: 2 = suspend 3 = openrw Enumeration .1.3.6.1.4.1.21239.5.2.30.1.9.1.26 |
vrcCompCfgFaultLockAlmCtrlCompressor fault lock alarm control: 2 = suspend 3 = openrw Enumeration .1.3.6.1.4.1.21239.5.2.30.1.9.1.27 |
vrcReturnPtTableTable that contains VRC return status SEQUENCE OF VrcReturnPtEntry .1.3.6.1.4.1.21239.5.2.30.1.10 |
vrcReturnPtEntryEntry in the vrcReturnPtTable: each entry represents return data for a VRC VrcReturnPtEntry .1.3.6.1.4.1.21239.5.2.30.1.10.1 |
vrcReturnPtIndexUnique id for each entry in the table Integer32 .1.3.6.1.4.1.21239.5.2.30.1.10.1.1 |
vrcReturnPtNameReturn name (factory-assigned)ro SnmpAdminString .1.3.6.1.4.1.21239.5.2.30.1.10.1.2 |
vrcReturnPtTempReturn temperature value in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The range is determined by the current temperature units. Celsius: -400 to 1000 Fahrenheit: -400 to 2120ro Integer32 UNITS "decidegrees" .1.3.6.1.4.1.21239.5.2.30.1.10.1.3 |
vrcReturnPtHighTempAlarmReturn high temperature alarm statero TruthValue (SNMPv2-TC) .1.3.6.1.4.1.21239.5.2.30.1.10.1.4 |
vrcReturnPtTempSensorFailAlarmReturn temperature sensor failure alarm statero TruthValue (SNMPv2-TC) .1.3.6.1.4.1.21239.5.2.30.1.10.1.5 |
vrcReturnCfgTableTable used for VRC return configuration SEQUENCE OF VrcReturnCfgEntry .1.3.6.1.4.1.21239.5.2.30.1.11 |
vrcReturnCfgEntryEntry in the vrcReturnCfgTable: each entry contains config fields for VRC return VrcReturnCfgEntry .1.3.6.1.4.1.21239.5.2.30.1.11.1 |
vrcReturnCfgIndexUnique id for each entry in the table Integer32 .1.3.6.1.4.1.21239.5.2.30.1.11.1.1 |
vrcReturnCfgOilCycleReturn oil cycle in tenths of an hourrw Integer32 .1.3.6.1.4.1.21239.5.2.30.1.11.1.2 |
vrcReturnCfgOilRunCapacityReturn Oil run capacity (percent)rw Integer32 .1.3.6.1.4.1.21239.5.2.30.1.11.1.3 |
vrcReturnCfgOilRunTimeReturn oil run time in minutesrw Integer32 .1.3.6.1.4.1.21239.5.2.30.1.11.1.4 |
vrcReturnCfgTempCalValueReturn temperature calibration value in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The settable range is determined by the current temperature units. Celsius: -100 to 100 Fahrenheit: -179 to 179rw Integer32 UNITS "decidegrees" .1.3.6.1.4.1.21239.5.2.30.1.11.1.5 |
vrcReturnCfgTempSettingReturn temperature setting in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The settable range is determined by the current temperature units. Celsius: 250 to 350 Fahrenheit: 770 to 949rw Integer32 UNITS "decidegrees" .1.3.6.1.4.1.21239.5.2.30.1.11.1.6 |
vrcReturnCfgHighTempAlarmValueReturn high temperature alarm value in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The settable range is determined by the current temperature units. Celsius: 300 to 450 Fahrenheit: 860 to 1129rw Integer32 UNITS "decidegrees" .1.3.6.1.4.1.21239.5.2.30.1.11.1.7 |
vrcReturnCfgHighTempAlarmCtrlReturn high temperature alarm control: 1 = close 2 = suspend 3 = openrw Enumeration .1.3.6.1.4.1.21239.5.2.30.1.11.1.8 |
vrcReturnCfgTempSensFailAlmCtrlReturn temperature sensor failure alarm control: 1 = close 2 = suspend 3 = openrw Enumeration .1.3.6.1.4.1.21239.5.2.30.1.11.1.9 |
vrcSupplyPtTableTable that contains VRC supply status SEQUENCE OF VrcSupplyPtEntry .1.3.6.1.4.1.21239.5.2.30.1.12 |
vrcSupplyPtEntryEntry in the vrcSupplyPtTable: each entry represents supply data for a VRC VrcSupplyPtEntry .1.3.6.1.4.1.21239.5.2.30.1.12.1 |
vrcSupplyPtIndexUnique id for each entry in the table Integer32 .1.3.6.1.4.1.21239.5.2.30.1.12.1.1 |
vrcSupplyPtNameSupply name (factory-assigned)ro SnmpAdminString .1.3.6.1.4.1.21239.5.2.30.1.12.1.2 |
vrcSupplyPtTempSupply temperature value in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The range is determined by the current temperature units. Celsius: -400 to 1000 Fahrenheit: -400 to 2120ro Integer32 UNITS "decidegrees" .1.3.6.1.4.1.21239.5.2.30.1.12.1.3 |
vrcSupplyPtLowTempAlarmSupply low temperature alarm statero TruthValue (SNMPv2-TC) .1.3.6.1.4.1.21239.5.2.30.1.12.1.4 |
vrcSupplyPtHighTempAlarmSupply high temperature alarm statero TruthValue (SNMPv2-TC) .1.3.6.1.4.1.21239.5.2.30.1.12.1.5 |
vrcSupplyPtTempSensorFailAlarmSupply temperature sensor failure alarm statero TruthValue (SNMPv2-TC) .1.3.6.1.4.1.21239.5.2.30.1.12.1.6 |
vrcSupplyCfgTableTable used for VRC supply configuration SEQUENCE OF VrcSupplyCfgEntry .1.3.6.1.4.1.21239.5.2.30.1.13 |
vrcSupplyCfgEntryEntry in the vrcSupplyCfgTable: each entry contains config fields for a VRC supply VrcSupplyCfgEntry .1.3.6.1.4.1.21239.5.2.30.1.13.1 |
vrcSupplyCfgIndexUnique id for each entry in the table Integer32 .1.3.6.1.4.1.21239.5.2.30.1.13.1.1 |
vrcSupplyCfgTempCalValueSupply temperature calibration value in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The settable range is determined by the current temperature units. Celsius: -100 to 100 Fahrenheit: -179 to 179rw Integer32 UNITS "decidegrees" .1.3.6.1.4.1.21239.5.2.30.1.13.1.2 |
vrcSupplyCfgTempSettingSupply temperature setting in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The settable range is determined by the current temperature units. Celsius: 130 to 280 Fahrenheit: 554 to 823rw Integer32 UNITS "decidegrees" .1.3.6.1.4.1.21239.5.2.30.1.13.1.3 |
vrcSupplyCfgLowTempAlarmValueSupply low temperature alarm value in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The settable range is determined by the current temperature units. Celsius: 50 to 200 Fahrenheit: 410 to 679rw Integer32 UNITS "decidegrees" .1.3.6.1.4.1.21239.5.2.30.1.13.1.4 |
vrcSupplyCfgHighTempAlarmValueSupply high temperature alarm value in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The settable range is determined by the current temperature units. Celsius: 200 to 350 Fahrenheit: 680 to 949rw Integer32 UNITS "decidegrees" .1.3.6.1.4.1.21239.5.2.30.1.13.1.5 |
vrcSupplyCfgLowTempAlmCtrlSupply low temperature alarm control: 1 = close 2 = suspend 3 = openrw Enumeration .1.3.6.1.4.1.21239.5.2.30.1.13.1.6 |
vrcSupplyCfgHighTempAlmCtrlSupply high temperature alarm control: 1 = close 2 = suspend 3 = openrw Enumeration .1.3.6.1.4.1.21239.5.2.30.1.13.1.7 |
vrcSupplyCfgTempSensFailAlmCtrlSupply temperature sensor failure alarm control: 1 = close 2 = suspend 3 = openrw Enumeration .1.3.6.1.4.1.21239.5.2.30.1.13.1.8 |
vrcPowerPtTableTable that contains VRC power status SEQUENCE OF VrcPowerPtEntry .1.3.6.1.4.1.21239.5.2.30.1.14 |
vrcPowerPtEntryEntry in the vrcPowerPtTable: each entry represents power data for a VRC VrcPowerPtEntry .1.3.6.1.4.1.21239.5.2.30.1.14.1 |
vrcPowerPtIndexUnique id for each entry in the table Integer32 .1.3.6.1.4.1.21239.5.2.30.1.14.1.1 |
vrcPowerPtNamePower name (factory-assigned)ro SnmpAdminString .1.3.6.1.4.1.21239.5.2.30.1.14.1.2 |
vrcPowerPtVoltagePower voltage measurement in tenths of a voltro Integer32(-32768..32767) UNITS "decivolts" .1.3.6.1.4.1.21239.5.2.30.1.14.1.3 |
vrcPowerPtFrequencyPower frequency measurement in tenths of hertzro Integer32(-32768..32767) UNITS "decihertz" .1.3.6.1.4.1.21239.5.2.30.1.14.1.4 |
vrcPowerPtLowVoltageAlarmPower low voltage alarm statero TruthValue (SNMPv2-TC) .1.3.6.1.4.1.21239.5.2.30.1.14.1.5 |
vrcPowerPtHighVoltageAlarmPower high voltage alarm statero TruthValue (SNMPv2-TC) .1.3.6.1.4.1.21239.5.2.30.1.14.1.6 |
vrcPowerPtLossOfPhasePowerAlarmPhase power loss alarm statero TruthValue (SNMPv2-TC) .1.3.6.1.4.1.21239.5.2.30.1.14.1.7 |
vrcPowerPtLossOfPowerAlarmPower loss alarm statero TruthValue (SNMPv2-TC) .1.3.6.1.4.1.21239.5.2.30.1.14.1.8 |
vrcPowerPtFrequencyErrorAlarmPower frequency error alarm statero TruthValue (SNMPv2-TC) .1.3.6.1.4.1.21239.5.2.30.1.14.1.9 |
vrcPowerCfgTableTable used for VRC power configuration SEQUENCE OF VrcPowerCfgEntry .1.3.6.1.4.1.21239.5.2.30.1.15 |
vrcPowerCfgEntryEntry in the vrcPowerCfgTable: each entry contains config fields for VRC power VrcPowerCfgEntry .1.3.6.1.4.1.21239.5.2.30.1.15.1 |
vrcPowerCfgIndexUnique id for each entry in the table Integer32 .1.3.6.1.4.1.21239.5.2.30.1.15.1.1 |
vrcPowerCfgLowVoltageSettingPower low voltage setting in voltsrw Integer32 .1.3.6.1.4.1.21239.5.2.30.1.15.1.2 |
vrcPowerCfgHighVoltageSettingPower high voltage setting in voltsrw Integer32 .1.3.6.1.4.1.21239.5.2.30.1.15.1.3 |
vrcPowerCfgLowVoltageAlarmCtrlPower low voltage alarm control: 1 = close 2 = suspend 3 = openrw Enumeration .1.3.6.1.4.1.21239.5.2.30.1.15.1.4 |
vrcPowerCfgHighVoltageAlarmCtrlPower high voltage alarm control: 1 = close 2 = suspend 3 = openrw Enumeration .1.3.6.1.4.1.21239.5.2.30.1.15.1.5 |
vrcPowerCfgLossOfPowerAlarmCtrlPower loss alarm control: 1 = close 2 = suspend 3 = openrw Enumeration .1.3.6.1.4.1.21239.5.2.30.1.15.1.6 |
vrcPowerCfgFreqErrorAlarmCtrlPower frequency error alarm control: 1 = close 2 = suspend 3 = openrw Enumeration .1.3.6.1.4.1.21239.5.2.30.1.15.1.7 |
vrcOutdoorPtTableTable that contains VRC outdoor status SEQUENCE OF VrcOutdoorPtEntry .1.3.6.1.4.1.21239.5.2.30.1.16 |
vrcOutdoorPtEntryEntry in the vrcOutdoorPtTable: each entry represents data for a VRC outdoor VrcOutdoorPtEntry .1.3.6.1.4.1.21239.5.2.30.1.16.1 |
vrcOutdoorPtIndexUnique id for each entry in the table Integer32 .1.3.6.1.4.1.21239.5.2.30.1.16.1.1 |
vrcOutdoorPtNameOutdoor name (factory-assigned)ro SnmpAdminString .1.3.6.1.4.1.21239.5.2.30.1.16.1.2 |
vrcOutdoorPtTempOutdoor temperature value in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The range is determined by the current temperature units. Celsius: -400 to 1000 Fahrenheit: -400 to 2120ro Integer32 UNITS "decidegrees" .1.3.6.1.4.1.21239.5.2.30.1.16.1.3 |
vrcDischPtTableTable that contains VRC discharge status SEQUENCE OF VrcDischPtEntry .1.3.6.1.4.1.21239.5.2.30.1.18 |
vrcDischPtEntryEntry in the vrcDischPtTable: each entry represents discharge data for a VRC VrcDischPtEntry .1.3.6.1.4.1.21239.5.2.30.1.18.1 |
vrcDischPtIndexUnique id for each entry in the table Integer32 .1.3.6.1.4.1.21239.5.2.30.1.18.1.1 |
vrcDischPtNameDischarge name (factory-assigned)ro SnmpAdminString .1.3.6.1.4.1.21239.5.2.30.1.18.1.2 |
vrcDischPtTempDischarge temperature value in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The range is determined by the current temperature units. Celsius: -400 to 1560 Fahrenheit: -400 to 3128rw Integer32 UNITS "decidegrees" .1.3.6.1.4.1.21239.5.2.30.1.18.1.3 |
vrcDischPtPressureDischarge air pressure value in tenths of a barrw Integer32 .1.3.6.1.4.1.21239.5.2.30.1.18.1.4 |
vrcDischPtHighTempAlarmDischarge high temperature alarm statero TruthValue (SNMPv2-TC) .1.3.6.1.4.1.21239.5.2.30.1.18.1.5 |
vrcDischPtHighTempFreqAlarmDischarge high temperature frequently alarm statero TruthValue (SNMPv2-TC) .1.3.6.1.4.1.21239.5.2.30.1.18.1.6 |
vrcDischPtTempSensorFailAlarmDischarge temperature sensor failure alarm statero TruthValue (SNMPv2-TC) .1.3.6.1.4.1.21239.5.2.30.1.18.1.7 |
vrcDischCfgTableTable used for VRC discharge configuration SEQUENCE OF VrcDischCfgEntry .1.3.6.1.4.1.21239.5.2.30.1.19 |
vrcDischCfgEntryEntry in the vrcDischCfgTable: each entry contains config fields for VRC discharge VrcDischCfgEntry .1.3.6.1.4.1.21239.5.2.30.1.19.1 |
vrcDischCfgIndexUnique id for each entry in the table Integer32 .1.3.6.1.4.1.21239.5.2.30.1.19.1.1 |
vrcDischCfgTempCalValueDischarge temperature calibration value in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The settable range is determined by the current temperature units. Celsius: -100 to 100 Fahrenheit: -179 to 179rw Integer32 UNITS "decidegrees" .1.3.6.1.4.1.21239.5.2.30.1.19.1.2 |
vrcDischCfgPressCalValueDischarge pressure calibration value in tenths of a barrw Integer32(-100..100) UNITS "decibars" .1.3.6.1.4.1.21239.5.2.30.1.19.1.3 |
vrcDischCfgHighTempAlmCtrlDischarge high temperature alarm control: 2 = suspend 3 = openrw Enumeration .1.3.6.1.4.1.21239.5.2.30.1.19.1.4 |
vrcDischCfgHighTempFreqAlmCtrlDischarge high temperature frequenctly alarm control: 2 = suspend 3 = openrw Enumeration .1.3.6.1.4.1.21239.5.2.30.1.19.1.5 |
vrcDischCfgTempSensFailAlmCtrlDischarge temperature sensor failure alarm control: 2 = suspend 3 = openrw Enumeration .1.3.6.1.4.1.21239.5.2.30.1.19.1.6 |
vrcSuctPtTableTable that contains VRC suction status SEQUENCE OF VrcSuctPtEntry .1.3.6.1.4.1.21239.5.2.30.1.20 |
vrcSuctPtEntryEntry in the vrcSuctPtTable: each entry represents suction data for a VRC VrcSuctPtEntry .1.3.6.1.4.1.21239.5.2.30.1.20.1 |
vrcSuctPtIndexUnique id for each entry in the table Integer32 .1.3.6.1.4.1.21239.5.2.30.1.20.1.1 |
vrcSuctPtNameSuction name (factory-assigned)ro SnmpAdminString .1.3.6.1.4.1.21239.5.2.30.1.20.1.2 |
vrcSuctPtTempSuction temperature in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The range is determined by the current temperature units. Celsius: -400 to 1000 Fahrenheit: -400 to 2120ro Integer32 UNITS "decidegrees" .1.3.6.1.4.1.21239.5.2.30.1.20.1.3 |
vrcSuctPtPressureSuction air pressure in tenths of a barro Integer32 .1.3.6.1.4.1.21239.5.2.30.1.20.1.4 |
vrcSuctPtSuperHeatTempSuction super heat temperature in tenths of a degree. Units are given by temperatureUnits field in deviceInfo. The range is determined by the current temperature units. Celsius: -400 to 1000 Fahrenheit: -400 to 2120ro Integer32 UNITS "decidegrees" .1.3.6.1.4.1.21239.5.2.30.1.20.1.5 |
vrcSuctPtTempSensorFailAlarmSuction temperature sensor failure alarm statero TruthValue (SNMPv2-TC) .1.3.6.1.4.1.21239.5.2.30.1.20.1.6 |
vrcSuctCfgTableTable used for VRC suction configuration SEQUENCE OF VrcSuctCfgEntry .1.3.6.1.4.1.21239.5.2.30.1.21 |
vrcSuctCfgEntryEntry in the vrcSuctCfgTable: each entry contains config fields for VRC suction VrcSuctCfgEntry .1.3.6.1.4.1.21239.5.2.30.1.21.1 |
vrcSuctCfgIndexUnique id for each entry in the table Integer32 .1.3.6.1.4.1.21239.5.2.30.1.21.1.1 |
vrcSuctCfgPressCalValueSuction pressure calibration value in tenths of a barrw Integer32(-100..100) UNITS "decibars" .1.3.6.1.4.1.21239.5.2.30.1.21.1.2 |
vrcSuctCfgTempSensFailAlmCtrlSuction temperature sensor failure alarm control: 2 = suspend 3 = openrw Enumeration .1.3.6.1.4.1.21239.5.2.30.1.21.1.3 |
trap OBJECT IDENTIFIER .1.3.6.1.4.1.21239.5.2.32767 |
trapPrefix OBJECT IDENTIFIER .1.3.6.1.4.1.21239.5.2.32767.0 |
internalTestNOTIFYTest SNMP Trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.10101 |
pduMainAvailNOTIFYPDU availability trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.10305 |
pduTotalRealPowerNOTIFYPDU total real power trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.10309 |
pduTotalApparentPowerNOTIFYPDU total apparent power trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.10310 |
pduTotalPowerFactorNOTIFYPDU total power factor trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.10311 |
pduTotalEnergyNOTIFYPDU total energy trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.10312 |
pduPhaseVoltageNOTIFYPDU phase voltage trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.10324 |
pduPhaseCurrentNOTIFYPDU phase current trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.10328 |
pduPhaseRealPowerNOTIFYPDU phase real power trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.10332 |
pduPhaseApparentPowerNOTIFYPDU phase apparent power trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.10333 |
pduPhasePowerFactorNOTIFYPDU phase power factor trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.10334 |
pduPhaseEnergyNOTIFYPDU phase energy trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.10335 |
pduPhaseBalanceNOTIFYPDU phase balance trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.10337 |
pduPhaseCurrentCrestFactorNOTIFYPDU phase current crest factor trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.10339 |
pduBreakerCurrentNOTIFYPDU breaker current trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.10354 |
pduBreakerVoltageNOTIFYPDU breaker voltage trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.10358 |
pduBreakerRealPowerNOTIFYPDU breaker real power trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.10362 |
pduBreakerApparentPowerNOTIFYPDU breaker apparent power trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.10363 |
pduBreakerPowerFactorNOTIFYPDU breaker power factor trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.10364 |
pduBreakerEnergyNOTIFYPDU breaker energy trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.10365 |
pduLineCurrentNOTIFYPDU line current trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.10374 |
pduOutletMeterVoltageNOTIFYPDU outlet voltage trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.10385 |
pduOutletMeterCurrentNOTIFYPDU outlet current trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.10389 |
pduOutletMeterRealPowerNOTIFYPDU outlet real power trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.10393 |
pduOutletMeterApparentPowerNOTIFYPDU outlet apparent power trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.10394 |
pduOutletMeterPowerFactorNOTIFYPDU outlet power factor trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.10395 |
pduOutletMeterEnergyNOTIFYPDU outlet energy trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.10396 |
pduOutletCurrentCrestFactorNOTIFYPDU outlet current crest factor trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.10400 |
tempSensorAvailNOTIFYRT availability trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.10404 |
tempSensorTempNOTIFYRT temperature trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.10405 |
airFlowSensorAvailNOTIFYAFHT3 availability trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.10504 |
airFlowSensorTempNOTIFYAFHT3 temperature trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.10505 |
airFlowSensorFlowNOTIFYAFHT3 airflow trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.10506 |
airFlowSensorHumidityNOTIFYAFHT3 humidity trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.10507 |
airFlowSensorDewPointNOTIFYAFHT3 dewpoint trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.10508 |
t3hdSensorAvailNOTIFYT3HD availability trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.10804 |
t3hdSensorIntTempNOTIFYT3HD Internal temperature trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.10806 |
t3hdSensorIntHumidityNOTIFYT3HD Internal humidity trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.10807 |
t3hdSensorIntDewPointNOTIFYT3HD Internal dewpoint trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.10808 |
t3hdSensorExtATempNOTIFYT3HD External A temperature trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.10811 |
t3hdSensorExtBTempNOTIFYT3HD External B temperature trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.10814 |
thdSensorAvailNOTIFYTHD availability trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.10904 |
thdSensorTempNOTIFYTHD temperature trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.10905 |
thdSensorHumidityNOTIFYTHD humidity trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.10906 |
thdSensorDewPointNOTIFYTHD dewpoint trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.10907 |
a2dSensorAvailNOTIFYA2D availability trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.11104 |
a2dSensorValueNOTIFYA2D measurement trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.11105 |
humiditySensorAvailNOTIFYRemote humidity availability trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.11204 |
humiditySensorValueNOTIFYRemote humidity value trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.11205 |
sn2dSensorAvailNOTIFYSN-2D availability trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.11304 |
sn2dSensorDoor1StateNOTIFYSN-2D Door switch 1 state trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.11306 |
sn2dSensorDoor2StateNOTIFYSN-2D Door switch 2 state trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.11309 |
vrcMainAvailNOTIFYVRC availability trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.13001 |
vrcOutFanPtSpeedNOTIFYVRC out-fan speed trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.13002 |
vrcCompPtCapacityNOTIFYVRC compressor capacity trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.13003 |
vrcReturnPtTempNOTIFYVRC return temperature trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.13004 |
vrcSupplyPtTempNOTIFYVRC supply temperature trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.13005 |
vrcPowerPtVoltageNOTIFYVRC power voltage trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.13006 |
vrcPowerPtFrequencyNOTIFYVRC power frequency trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.13007 |
vrcOutdoorPtTempNOTIFYVRC outdoor temperature trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.13008 |
vrcDischPtTempNOTIFYVRC discharge temperature trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.13009 |
vrcDischPtPressureNOTIFYVRC discharge pressure trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.13010 |
vrcSuctPtTempNOTIFYVRC suction temperature trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.13011 |
vrcSuctPtPressureNOTIFYVRC suction pressure trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.13012 |
pduMainAvailCLEARPDU availability clear trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.20305 |
pduTotalRealPowerCLEARPDU total real power clear trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.20309 |
pduTotalApparentPowerCLEARPDU total apparent power clear trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.20310 |
pduTotalPowerFactorCLEARPDU total power factor clear trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.20311 |
pduTotalEnergyCLEARPDU total energy clear trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.20312 |
pduPhaseVoltageCLEARPDU phase voltage clear trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.20324 |
pduPhaseCurrentCLEARPDU phase current clear trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.20328 |
pduPhaseRealPowerCLEARPDU phase real power clear trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.20332 |
pduPhaseApparentPowerCLEARPDU phase apparent power clear trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.20333 |
pduPhasePowerFactorCLEARPDU phase power factor clear trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.20334 |
pduPhaseEnergyCLEARPDU phase energy clear trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.20335 |
pduPhaseBalanceCLEARPDU phase balance clear trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.20337 |
pduPhaseCurrentCrestFactorCLEARPDU phase current crest factor clear trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.20339 |
pduBreakerCurrentCLEARPDU breaker current clear trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.20354 |
pduBreakerVoltageCLEARPDU breaker voltage clear trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.20358 |
pduBreakerRealPowerCLEARPDU breaker real power clear trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.20362 |
pduBreakerApparentPowerCLEARPDU breaker apparent power clear trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.20363 |
pduBreakerPowerFactorCLEARPDU breaker power factor clear trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.20364 |
pduBreakerEnergyCLEARPDU breaker energy clear trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.20365 |
pduLineCurrentCLEARPDU line current clear trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.20374 |
pduOutletMeterVoltageCLEARPDU outlet voltage clear trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.20385 |
pduOutletMeterCurrentCLEARPDU outlet current clear trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.20389 |
pduOutletMeterRealPowerCLEARPDU outlet real power clear trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.20393 |
pduOutletMeterApparentPowerCLEARPDU outlet apparent power clear trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.20394 |
pduOutletMeterPowerFactorCLEARPDU outlet power factor clear trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.20395 |
pduOutletMeterEnergyCLEARPDU outlet energy clear trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.20396 |
pduOutletCurrentCrestFactorCLEARPDU outlet current crest factor clear trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.20400 |
tempSensorAvailCLEARRT availability clear trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.20404 |
tempSensorTempCLEARRT temperature clear trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.20405 |
airFlowSensorAvailCLEARAFHT3 availability clear trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.20504 |
airFlowSensorTempCLEARAFHT3 temperature clear trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.20505 |
airFlowSensorFlowCLEARAFHT3 airflow clear trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.20506 |
airFlowSensorHumidityCLEARAFHT3 humidity clear trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.20507 |
airFlowSensorDewPointCLEARAFHT3 dewpoint clear trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.20508 |
t3hdSensorAvailCLEART3HD availability clear trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.20804 |
t3hdSensorIntTempCLEART3HD Internal temperature clear trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.20806 |
t3hdSensorIntHumidityCLEART3HD Internal humidity clear trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.20807 |
t3hdSensorIntDewPointCLEART3HD Internal dewpoint clear trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.20808 |
t3hdSensorExtATempCLEART3HD External A temperature clear trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.20811 |
t3hdSensorExtBTempCLEART3HD External B temperature clear trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.20814 |
thdSensorAvailCLEARTHD availability clear trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.20904 |
thdSensorTempCLEARTHD temperature clear trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.20905 |
thdSensorHumidityCLEARTHD humidity clear trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.20906 |
thdSensorDewPointCLEARTHD dewpoint clear trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.20907 |
a2dSensorAvailCLEARA2D availability clear trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.21104 |
a2dSensorValueCLEARA2D measurement clear trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.21105 |
humiditySensorAvailCLEARRemote humidity availability clear trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.21204 |
humiditySensorValueCLEARRemote humidity value clear trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.21205 |
sn2dSensorAvailCLEARSN-2D availability clear trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.21304 |
sn2dSensorDoor1StateCLEARSN-2D Door switch 1 state clear trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.21306 |
sn2dSensorDoor2StateCLEARSN-2D Door switch 2 state clear trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.21309 |
vrcMainAvailCLEARVRC availability clear trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.23001 |
vrcOutFanPtSpeedCLEARVRC out-fan speed clear trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.23002 |
vrcCompPtCapacityCLEARVRC compressor capacity clear trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.23003 |
vrcReturnPtTempCLEARVRC return temperature clear trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.23004 |
vrcSupplyPtTempCLEARVRC supply temperature clear trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.23005 |
vrcPowerPtVoltageCLEARVRC power voltage clear trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.23006 |
vrcPowerPtFrequencyCLEARVRC power frequency clear trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.23007 |
vrcOutdoorPtTempCLEARVRC outdoor temperature clear trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.23008 |
vrcDischPtTempCLEARVRC discharge temperature clear trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.23009 |
vrcDischPtPressureCLEARVRC discharge pressure clear trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.23010 |
vrcSuctPtTempCLEARVRC suction temperature clear trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.23011 |
vrcSuctPtPressureCLEARVRC suction pressure clear trap NOTIFICATION-TYPE .1.3.6.1.4.1.21239.5.2.32767.0.23012 |
trapObj OBJECT IDENTIFIER .1.3.6.1.4.1.21239.5.2.32767.1 |
trapSeverityIndicates the severity of the trap: 0 = None 1 = Warning 2 = Alarmro Enumeration .1.3.6.1.4.1.21239.5.2.32767.1.1 |
trapThreshTypeOnly sent for threshold alarms. Identifies the threshold type: 1 = Low 2 = Highro Enumeration .1.3.6.1.4.1.21239.5.2.32767.1.2 |
common OBJECT IDENTIFIER .1.3.6.1.4.1.21239.42 |
identity OBJECT IDENTIFIER .1.3.6.1.4.1.21239.42.1 |
r05Value given for sysObjectID on R-Series units OBJECT IDENTIFIER .1.3.6.1.4.1.21239.42.1.15 |
i03Value given for sysObjectID on IMD3 units OBJECT IDENTIFIER .1.3.6.1.4.1.21239.42.1.53 |