GEIST-IMD-MIB

AI MIB Summary

The GEIST-IMD-MIB facilitates SNMP-based monitoring and management of Geist Products environmental monitoring devices, specifically tracking sensor data such as temperature, humidity, voltage, and current for rack-mounted infrastructure. It provides standardized access to alarm states and historical counter values for power distribution units (PDUs) and environmental sensors deployed in data centers.

The MIB for Geist Products
Main OID:
geist.1.3.6.1.4.1.21239
268
Objects
Active
Status
2
Dependencies

Imported Objects

Objects

268 total
Object Name
geistThe MIB for Geist Products
MODULE-IDENTITY
.1.3.6.1.4.1.21239
blackbird
OBJECT IDENTIFIER
.1.3.6.1.4.1.21239.5
imd
OBJECT IDENTIFIER
.1.3.6.1.4.1.21239.5.2
deviceInfo
OBJECT IDENTIFIER
.1.3.6.1.4.1.21239.5.2.1
productTitleProduct namero
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.1.1
productVersionProduct versionro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.1.2
productFriendlyNameUser-assigned namero
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.1.3
productMacAddressProduct's unique MAC addressro
OCTET STRING
.1.3.6.1.4.1.21239.5.2.1.4
productUrlProduct's main URL access pointro
IpAddress
.1.3.6.1.4.1.21239.5.2.1.5
deviceCountTotal number of devices on unitro
Integer32
.1.3.6.1.4.1.21239.5.2.1.6
temperatureUnitsCurrent units for temperature values. 0 = Degrees Fahrenheit, 1 = Degrees Celsiusrw
Integer32
.1.3.6.1.4.1.21239.5.2.1.7
pdu
OBJECT IDENTIFIER
.1.3.6.1.4.1.21239.5.2.3
pduMainTablePDU general information
SEQUENCE OF PduMainEntry
.1.3.6.1.4.1.21239.5.2.3.1
pduMainEntryEntry in the pduMainTable table: each entry contains an index and other sensor details
PduMainEntry
.1.3.6.1.4.1.21239.5.2.3.1.1
pduMainIndexTable entry index valuero
Integer32
.1.3.6.1.4.1.21239.5.2.3.1.1.1
pduMainSerialSerial Numberro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.3.1.1.2
pduMainNameNamero
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.3.1.1.3
pduMainLabelLabelro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.3.1.1.4
pduMainAvailDevice availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailablero
Gauge32
.1.3.6.1.4.1.21239.5.2.3.1.1.5
pduMeterTypeCurrent meter type. 0 = Wye, 1 = Deltaro
Integer32
.1.3.6.1.4.1.21239.5.2.3.1.1.6
pduTotalNameTotal Namero
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.3.1.1.7
pduTotalLabelTotal Labelro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.3.1.1.8
pduTotalRealPowerPDU Total Real Powerro
Gauge32 UNITS "watts"
.1.3.6.1.4.1.21239.5.2.3.1.1.9
pduTotalApparentPowerPDU Total Apparent Powerro
Gauge32 UNITS "volt-amps"
.1.3.6.1.4.1.21239.5.2.3.1.1.10
pduTotalPowerFactorPDU Total Power Factorro
Gauge32 UNITS "%"
.1.3.6.1.4.1.21239.5.2.3.1.1.11
pduTotalEnergyPDU Total Accumulated Energyro
Gauge32 UNITS "watt-hours"
.1.3.6.1.4.1.21239.5.2.3.1.1.12
pduPhaseTablePDU phases information
SEQUENCE OF PduPhaseEntry
.1.3.6.1.4.1.21239.5.2.3.2
pduPhaseEntryEntry in the pduPhaseTable table: each entry contains an index and other sensor details
PduPhaseEntry
.1.3.6.1.4.1.21239.5.2.3.2.1
pduPhaseIndexTable entry index valuero
Integer32
.1.3.6.1.4.1.21239.5.2.3.2.1.1
pduPhaseNamePDU Phase Namero
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.3.2.1.2
pduPhaseLabelPDU Phase Labelro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.3.2.1.3
pduPhaseVoltagePDU Phase Voltage in tenths of a voltro
Gauge32 UNITS "decivolts (rms)"
.1.3.6.1.4.1.21239.5.2.3.2.1.4
pduPhaseVoltageMaxPDU Phase Voltage (Max) in tenths of a voltro
Gauge32 UNITS "decivolts (rms)"
.1.3.6.1.4.1.21239.5.2.3.2.1.5
pduPhaseVoltageMinPDU Phase Voltage (Min) in tenths of a voltro
Gauge32 UNITS "decivolts (rms)"
.1.3.6.1.4.1.21239.5.2.3.2.1.6
pduPhaseVoltagePeakPDU Phase Voltage (Peak) in tenths of a voltro
Gauge32 UNITS "decivolts"
.1.3.6.1.4.1.21239.5.2.3.2.1.7
pduPhaseCurrentPDU Phase Current reading in hundreths of an ampro
Gauge32 UNITS "centiamps (rms)"
.1.3.6.1.4.1.21239.5.2.3.2.1.8
pduPhaseCurrentMaxPDU Phase Current (Max) reading in hundreths of an ampro
Gauge32 UNITS "centiamps (rms)"
.1.3.6.1.4.1.21239.5.2.3.2.1.9
pduPhaseCurrentMinPDU Phase Current (Min) reading in hundreths of an ampro
Gauge32 UNITS "centiamps (rms)"
.1.3.6.1.4.1.21239.5.2.3.2.1.10
pduPhaseCurrentPeakPDU Phase Current (Peak) reading in hundreths of an ampro
Gauge32 UNITS "centiamps (rms)"
.1.3.6.1.4.1.21239.5.2.3.2.1.11
pduPhaseRealPowerPDU Phase Real Powerro
Gauge32 UNITS "watts"
.1.3.6.1.4.1.21239.5.2.3.2.1.12
pduPhaseApparentPowerPDU Phase Apparent Powerro
Gauge32 UNITS "volt-amps"
.1.3.6.1.4.1.21239.5.2.3.2.1.13
pduPhasePowerFactorPDU Phase Power Factorro
Gauge32 UNITS "%"
.1.3.6.1.4.1.21239.5.2.3.2.1.14
pduPhaseEnergyPDU Phase Accumulated Energyro
Gauge32 UNITS "watt-hours"
.1.3.6.1.4.1.21239.5.2.3.2.1.15
pduBreakerTablePDU information
SEQUENCE OF PduBreakerEntry
.1.3.6.1.4.1.21239.5.2.3.3
pduBreakerEntryEntry in the pduBreakerTable table: each entry contains an index and other sensor details
PduBreakerEntry
.1.3.6.1.4.1.21239.5.2.3.3.1
pduBreakerIndexTable entry index valuero
Integer32
.1.3.6.1.4.1.21239.5.2.3.3.1.1
pduBreakerNamePDU Breaker Namero
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.3.3.1.2
pduBreakerLabelPDU Breaker Labelro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.3.3.1.3
pduBreakerCurrentPDU Breaker Current reading in hundreths of an ampro
Gauge32 UNITS "centiamps (rms)"
.1.3.6.1.4.1.21239.5.2.3.3.1.4
pduBreakerCurrentMaxPDU Breaker Current (Max) reading in hundreths of an ampro
Gauge32 UNITS "centiamps (rms)"
.1.3.6.1.4.1.21239.5.2.3.3.1.5
pduBreakerCurrentMinPDU Breaker Current (Min) reading in hundreths of an ampro
Gauge32 UNITS "centiamps (rms)"
.1.3.6.1.4.1.21239.5.2.3.3.1.6
pduBreakerCurrentPeakPDU Breaker Current (Peak) reading in hundreths of an ampro
Gauge32 UNITS "centiamps (rms)"
.1.3.6.1.4.1.21239.5.2.3.3.1.7
pduLineTablePDU line current information
SEQUENCE OF PduLineEntry
.1.3.6.1.4.1.21239.5.2.3.4
pduLineEntryEntry in the pduLineTable table: each entry contains an index and other sensor details
PduLineEntry
.1.3.6.1.4.1.21239.5.2.3.4.1
pduLineIndexTable entry index valuero
Integer32
.1.3.6.1.4.1.21239.5.2.3.4.1.1
pduLineNamePDU Line Namero
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.3.4.1.2
pduLineLabelPDU Line Labelro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.3.4.1.3
pduLineCurrentPDU Line Current reading in hundreths of an ampro
Gauge32 UNITS "centiamps (rms)"
.1.3.6.1.4.1.21239.5.2.3.4.1.4
pduLineCurrentMaxPDU Line Current (Max) reading in hundreths of an ampro
Gauge32 UNITS "centiamps (rms)"
.1.3.6.1.4.1.21239.5.2.3.4.1.5
pduLineCurrentMinPDU Line Current (Min) reading in hundreths of an ampro
Gauge32 UNITS "centiamps (rms)"
.1.3.6.1.4.1.21239.5.2.3.4.1.6
pduLineCurrentPeakPDU Line Current (Peak) reading in hundreths of an ampro
Gauge32 UNITS "centiamps (rms)"
.1.3.6.1.4.1.21239.5.2.3.4.1.7
tempSensorTableRemote Temperature Sensor
SEQUENCE OF TempSensorEntry
.1.3.6.1.4.1.21239.5.2.4
tempSensorEntryEntry in the tempSensorTable table: each entry contains an index and other sensor details
TempSensorEntry
.1.3.6.1.4.1.21239.5.2.4.1
tempSensorIndexTable entry index valuero
Integer32
.1.3.6.1.4.1.21239.5.2.4.1.1
tempSensorSerialSerial Numberro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.4.1.2
tempSensorNameFriendly Namero
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.4.1.3
tempSensorAvailDevice availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailablero
Gauge32
.1.3.6.1.4.1.21239.5.2.4.1.4
tempSensorTempCurrent reading for Temperature in tenths of degrees. Units are given by temperatureUnits field in deviceInforo
Integer32(-40..200) UNITS "0.1 Degrees"
.1.3.6.1.4.1.21239.5.2.4.1.5
airFlowSensorTableRemote Airflow, Humidity, Temperature and Dewpoint Sensor
SEQUENCE OF AirFlowSensorEntry
.1.3.6.1.4.1.21239.5.2.5
airFlowSensorEntryEntry in the airFlowSensorTable table: each entry contains an index and other sensor details
AirFlowSensorEntry
.1.3.6.1.4.1.21239.5.2.5.1
airFlowSensorIndexTable entry index valuero
Integer32
.1.3.6.1.4.1.21239.5.2.5.1.1
airFlowSensorSerialSerial Numberro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.5.1.2
airFlowSensorNameFriendly Namero
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.5.1.3
airFlowSensorAvailDevice availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailablero
Gauge32
.1.3.6.1.4.1.21239.5.2.5.1.4
airFlowSensorTempCurrent reading for Temperature in tenths of degrees. Units are given by temperatureUnits field in deviceInforo
Integer32(-40..200) UNITS "0.1 Degrees"
.1.3.6.1.4.1.21239.5.2.5.1.5
airFlowSensorFlowAFHT3 Airflow readingro
Integer32
.1.3.6.1.4.1.21239.5.2.5.1.6
airFlowSensorHumidityAFHT3 Humidity readingro
Integer32
.1.3.6.1.4.1.21239.5.2.5.1.7
airFlowSensorDewPointCurrent reading for Dew Point in tenths of degrees. Units are given by temperatureUnits field in deviceInforo
Integer32(-40..200) UNITS "0.1 Degrees"
.1.3.6.1.4.1.21239.5.2.5.1.8
dewPointSensorTableRemote Dew Point sensor
SEQUENCE OF DewPointSensorEntry
.1.3.6.1.4.1.21239.5.2.6
dewPointSensorEntryEntry in the dewPointSensorTable table: each entry contains an index and other sensor details
DewPointSensorEntry
.1.3.6.1.4.1.21239.5.2.6.1
dewPointSensorIndexTable entry index valuero
Integer32
.1.3.6.1.4.1.21239.5.2.6.1.1
dewPointSensorSerialSerial Numberro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.6.1.2
dewPointSensorNameFriendly Namero
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.6.1.3
dewPointSensorAvailDevice availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailablero
Gauge32
.1.3.6.1.4.1.21239.5.2.6.1.4
dewPointSensorTempCurrent reading for Temperature in tenths of degrees. Units are given by temperatureUnits field in deviceInforo
Integer32(-40..200) UNITS "0.1 Degrees"
.1.3.6.1.4.1.21239.5.2.6.1.5
dewPointSensorHumidityHumidity readingro
Integer32
.1.3.6.1.4.1.21239.5.2.6.1.6
dewPointSensorDewPointCurrent reading for Dew-point in tenths of degrees. Units are given by temperatureUnits field in deviceInforo
Integer32(-40..200) UNITS "0.1 Degrees"
.1.3.6.1.4.1.21239.5.2.6.1.7
ccatSensorTableRemote CCAT sensor
SEQUENCE OF CcatSensorEntry
.1.3.6.1.4.1.21239.5.2.7
ccatSensorEntryEntry in the ccatSensorTable table: each entry contains an index and other sensor details
CcatSensorEntry
.1.3.6.1.4.1.21239.5.2.7.1
ccatSensorIndexTable entry index valuero
Integer32
.1.3.6.1.4.1.21239.5.2.7.1.1
ccatSensorSerialSerial Numberro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.7.1.2
ccatSensorNameFriendly Namero
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.7.1.3
ccatSensorAvailDevice availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailablero
Gauge32
.1.3.6.1.4.1.21239.5.2.7.1.4
ccatSensorValueCCAT sensor readingro
Integer32(-100..5000)
.1.3.6.1.4.1.21239.5.2.7.1.5
ccatSensorTypeCCAT sensor typero
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.7.1.6
ccatSensorDescriptionCCAT sensor value descriptionro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.7.1.7
t3hdSensorTableRemote Temperature x 3, Humidity and Dewpoint Sensor
SEQUENCE OF T3hdSensorEntry
.1.3.6.1.4.1.21239.5.2.8
t3hdSensorEntryEntry in the t3hdSensorTable table: each entry contains an index and other sensor details
T3hdSensorEntry
.1.3.6.1.4.1.21239.5.2.8.1
t3hdSensorIndexTable entry index valuero
Integer32
.1.3.6.1.4.1.21239.5.2.8.1.1
t3hdSensorSerialSerial Numberro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.8.1.2
t3hdSensorNameFriendly Namero
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.8.1.3
t3hdSensorAvailDevice availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailablero
Gauge32
.1.3.6.1.4.1.21239.5.2.8.1.4
t3hdSensorIntNameT3HD Sensor Internal Friendly Namero
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.8.1.5
t3hdSensorIntTempCurrent reading for Internal Temperature in 0.1 degrees. Units are given by temperatureUnits field in deviceInforo
Integer32(-40..200) UNITS "0.1 Degrees"
.1.3.6.1.4.1.21239.5.2.8.1.6
t3hdSensorIntHumidityT3HD Sensor Internal Humidityro
Integer32
.1.3.6.1.4.1.21239.5.2.8.1.7
t3hdSensorIntDewPointCurrent reading for Internal DewPoint in 0.1 degrees. Units are given by temperatureUnits field in deviceInforo
Integer32(-40..200) UNITS "0.1 Degrees"
.1.3.6.1.4.1.21239.5.2.8.1.8
t3hdSensorExtAAvailT3HD External A status: 0 = Unavailable, 1 = Availablero
Gauge32
.1.3.6.1.4.1.21239.5.2.8.1.9
t3hdSensorExtANameT3HD External A Friendly Namero
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.8.1.10
t3hdSensorExtATempCurrent reading for External Temperature A in 0.1 degrees. Units are given by temperatureUnits field in deviceInforo
Integer32(-40..200) UNITS "0.1 Degrees"
.1.3.6.1.4.1.21239.5.2.8.1.11
t3hdSensorExtBAvailT3HD External B status: 0 = Unavailable, 1 = Availablero
Gauge32
.1.3.6.1.4.1.21239.5.2.8.1.12
t3hdSensorExtBNameT3HD External B Friendly Namero
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.8.1.13
t3hdSensorExtBTempCurrent reading for External Temperature B in 0.1 degrees. Units are given by temperatureUnits field in deviceInforo
Integer32(-40..200) UNITS "0.1 Degrees"
.1.3.6.1.4.1.21239.5.2.8.1.14
thdSensorTableRemote Temperature, Humidity and Dewpoint Sensor
SEQUENCE OF ThdSensorEntry
.1.3.6.1.4.1.21239.5.2.9
thdSensorEntryEntry in the thdSensorTable table: each entry contains an index and other sensor details
ThdSensorEntry
.1.3.6.1.4.1.21239.5.2.9.1
thdSensorIndexTable entry index valuero
Integer32
.1.3.6.1.4.1.21239.5.2.9.1.1
thdSensorSerialSerial Numberro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.9.1.2
thdSensorNameFriendly Namero
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.9.1.3
thdSensorAvailDevice availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailablero
Gauge32
.1.3.6.1.4.1.21239.5.2.9.1.4
thdSensorTempCurrent reading for Temperature in 0.1 degrees. Units are given by temperatureUnits field in deviceInforo
Integer32(-40..200) UNITS "0.1 Degrees"
.1.3.6.1.4.1.21239.5.2.9.1.5
thdSensorHumidityTHD Sensor Humidityro
Integer32
.1.3.6.1.4.1.21239.5.2.9.1.6
thdSensorDewPointCurrent reading for DewPoint in 0.1 degrees. Units are given by temperatureUnits field in deviceInforo
Integer32(-40..200) UNITS "0.1 Degrees"
.1.3.6.1.4.1.21239.5.2.9.1.7
rpmSensorTableRemote Power Manager Sensor
SEQUENCE OF RpmSensorEntry
.1.3.6.1.4.1.21239.5.2.10
rpmSensorEntryEntry in the rpmSensorTable table: each entry contains an index and other sensor details
RpmSensorEntry
.1.3.6.1.4.1.21239.5.2.10.1
rpmSensorIndexTable entry index valuero
Integer32
.1.3.6.1.4.1.21239.5.2.10.1.1
rpmSensorSerialSerial Numberro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.10.1.2
rpmSensorNameFriendly Namero
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.10.1.3
rpmSensorAvailDevice availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailablero
Gauge32
.1.3.6.1.4.1.21239.5.2.10.1.4
rpmSensorEnergyRPM Sensor Accumulated Energyro
Gauge32 UNITS "kWh"
.1.3.6.1.4.1.21239.5.2.10.1.5
rpmSensorVoltageRPM Sensor Voltagero
Gauge32 UNITS "Volts (rms)"
.1.3.6.1.4.1.21239.5.2.10.1.6
rpmSensorVoltageMaxRPM Sensor Voltage (Max)ro
Gauge32 UNITS "Volts (rms)"
.1.3.6.1.4.1.21239.5.2.10.1.7
rpmSensorVoltageMinRPM Sensor Voltage (Min)ro
Gauge32 UNITS "Volts (rms)"
.1.3.6.1.4.1.21239.5.2.10.1.8
rpmSensorVoltagePeakRPM Sensor Voltage (Peak)ro
Gauge32 UNITS "Volts"
.1.3.6.1.4.1.21239.5.2.10.1.9
rpmSensorCurrentRPM Sensor Current reading in deciAmpsro
Gauge32 UNITS "0.1 Amps (rms)"
.1.3.6.1.4.1.21239.5.2.10.1.10
rpmSensorRealPowerRPM Sensor Real Powerro
Gauge32 UNITS "Watts"
.1.3.6.1.4.1.21239.5.2.10.1.11
rpmSensorApparentPowerRPM Sensor Apparent Powerro
Gauge32 UNITS "Volt-Amps"
.1.3.6.1.4.1.21239.5.2.10.1.12
rpmSensorPowerFactorRPM Sensor Power Factorro
Gauge32 UNITS "%"
.1.3.6.1.4.1.21239.5.2.10.1.13
rpmSensorOutlet1RPM Sensor Outlet 1 State: 0 = off, 1 = onro
Gauge32
.1.3.6.1.4.1.21239.5.2.10.1.14
rpmSensorOutlet2RPM Sensor Outlet 2 State: 0 = off, 1 = onro
Gauge32
.1.3.6.1.4.1.21239.5.2.10.1.15
a2dSensorTableAnalog Measurement Sensor (Voltage, Current, or Dry Contact)
SEQUENCE OF A2DSensorEntry
.1.3.6.1.4.1.21239.5.2.11
a2DSensorEntryEntry in the a2dSensorTable table: each entry contains an index and other sensor details
A2DSensorEntry
.1.3.6.1.4.1.21239.5.2.11.1
a2dSensorIndexTable entry index valuero
Integer32
.1.3.6.1.4.1.21239.5.2.11.1.1
a2dSensorSerialSerial Numberro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.11.1.2
a2dSensorNameFriendly Namero
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.21239.5.2.11.1.3
a2dSensorAvailDevice availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailablero
Gauge32
.1.3.6.1.4.1.21239.5.2.11.1.4
a2dSensorValueCurrent analog measurement reading within either a user defined or preset range depending on device mode.ro
Integer32(-1000000..1000000)
.1.3.6.1.4.1.21239.5.2.11.1.5
trap
OBJECT IDENTIFIER
.1.3.6.1.4.1.21239.5.2.32767
trapPrefix
OBJECT IDENTIFIER
.1.3.6.1.4.1.21239.5.2.32767.0
internalTestNOTIFYTest SNMP Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10101
pduMainAvailNOTIFYDevice availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10305
pduTotalRealPowerNOTIFYPDU Total Real Power Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10309
pduTotalApparentPowerNOTIFYPDU Total Apparent Power Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10310
pduTotalPowerFactorNOTIFYPDU Total Power Factor Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10311
pduTotalEnergyNOTIFYPDU Total Accumulated Energy Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10312
pduPhaseVoltageNOTIFYPDU Phase Voltage in tenths of a volt Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10324
pduPhaseVoltageMaxNOTIFYPDU Phase Voltage (Max) in tenths of a volt Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10325
pduPhaseVoltageMinNOTIFYPDU Phase Voltage (Min) in tenths of a volt Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10326
pduPhaseVoltagePeakNOTIFYPDU Phase Voltage (Peak) in tenths of a volt Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10327
pduPhaseCurrentNOTIFYPDU Phase Current Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10328
pduPhaseCurrentMaxNOTIFYPDU Phase Current (Max) Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10329
pduPhaseCurrentMinNOTIFYPDU Phase Current (Min) Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10330
pduPhaseCurrentPeakNOTIFYPDU Phase Current (Peak) Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10331
pduPhaseRealPowerNOTIFYPDU Phase Real Power Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10332
pduPhaseApparentPowerNOTIFYPDU Phase Apparent Power Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10333
pduPhasePowerFactorNOTIFYPDU Phase Power Factor Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10334
pduPhaseEnergyNOTIFYPDU Phase Accumulated Energy Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10335
pduBreakerCurrentNOTIFYPDU Breaker Current Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10354
pduBreakerCurrentMaxNOTIFYPDU Breaker Current (Max) Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10355
pduBreakerCurrentMinNOTIFYPDU Breaker Current (Min) Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10356
pduBreakerCurrentPeakNOTIFYPDU Breaker Current (Peak) Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10357
pduLineCurrentNOTIFYPDU Line Current Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10374
pduLineCurrentMaxNOTIFYPDU Line Current (Max) Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10375
pduLineCurrentMinNOTIFYPDU Line Current (Min) Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10376
pduLineCurrentPeakNOTIFYPDU Line Current (Peak) Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10377
tempSensorAvailNOTIFYDevice availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10404
tempSensorTempNOTIFYRemote Temperature Sensor Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10405
airFlowSensorAvailNOTIFYDevice availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10504
airFlowSensorTempNOTIFYAFHT3 Sensor Temperature Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10505
airFlowSensorFlowNOTIFYAFHT3 Airflow reading Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10506
airFlowSensorHumidityNOTIFYAFHT3 Humidity reading Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10507
airFlowSensorDewPointNOTIFYAFHT3 Sensor Dew Point Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10508
dewPointSensorAvailNOTIFYDevice availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10604
dewPointSensorTempNOTIFYRemote Dew Point Sensor Temperature Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10605
dewPointSensorHumidityNOTIFYHumidity reading Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10606
dewPointSensorDewPointNOTIFYRemote Dew Point Sensor Dew Point Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10607
ccatSensorAvailNOTIFYDevice availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10704
ccatSensorValueNOTIFYCCAT sensor reading Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10705
t3hdSensorAvailNOTIFYDevice availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10804
t3hdSensorIntTempNOTIFYT3HD Sensor Temperature Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10806
t3hdSensorIntHumidityNOTIFYT3HD Sensor Internal Humidity Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10807
t3hdSensorIntDewPointNOTIFYT3HD Sensor Dew Point Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10808
t3hdSensorExtATempNOTIFYT3HD Sensor External A Temperature Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10811
t3hdSensorExtBTempNOTIFYT3HD Sensor External B Temperature Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10814
thdSensorAvailNOTIFYDevice availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10904
thdSensorTempNOTIFYTHD Sensor Temperature Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10905
thdSensorHumidityNOTIFYTHD Sensor Humidity Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10906
thdSensorDewPointNOTIFYTHD Sensor Dew Point Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.10907
rpmSensorAvailNOTIFYDevice availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.11004
rpmSensorEnergyNOTIFYRPM Sensor Accumulated Energy Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.11005
rpmSensorVoltageNOTIFYRPM Sensor Voltage Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.11006
rpmSensorVoltageMaxNOTIFYRPM Sensor Voltage (Max) Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.11007
rpmSensorVoltageMinNOTIFYRPM Sensor Voltage (Min) Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.11008
rpmSensorVoltagePeakNOTIFYRPM Sensor Voltage (Peak) Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.11009
rpmSensorCurrentNOTIFYRPM Sensor Current Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.11010
rpmSensorRealPowerNOTIFYRPM Sensor Real Power Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.11011
rpmSensorApparentPowerNOTIFYRPM Sensor Apparent Power Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.11012
rpmSensorPowerFactorNOTIFYRPM Sensor Power Factor Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.11013
a2dSensorAvailNOTIFYDevice availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.11104
a2dSensorValueNOTIFYA2D Analog Sensor Measurement Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.11105
pduMainAvailCLEARDevice availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable Clear Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20305
pduTotalRealPowerCLEARPDU Total Real Power Clear Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20309
pduTotalApparentPowerCLEARPDU Total Apparent Power Clear Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20310
pduTotalPowerFactorCLEARPDU Total Power Factor Clear Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20311
pduTotalEnergyCLEARPDU Total Accumulated Energy Clear Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20312
pduPhaseVoltageCLEARPDU Phase Voltage in tenths of a volt Clear Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20324
pduPhaseVoltageMaxCLEARPDU Phase Voltage (Max) in tenths of a volt Clear Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20325
pduPhaseVoltageMinCLEARPDU Phase Voltage (Min) in tenths of a volt Clear Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20326
pduPhaseVoltagePeakCLEARPDU Phase Voltage (Peak) in tenths of a volt Clear Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20327
pduPhaseCurrentCLEARPDU Phase Current Clear Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20328
pduPhaseCurrentMaxCLEARPDU Phase Current (Max) Clear Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20329
pduPhaseCurrentMinCLEARPDU Phase Current (Min) Clear Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20330
pduPhaseCurrentPeakCLEARPDU Phase Current (Peak) Clear Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20331
pduPhaseRealPowerCLEARPDU Phase Real Power Clear Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20332
pduPhaseApparentPowerCLEARPDU Phase Apparent Power Clear Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20333
pduPhasePowerFactorCLEARPDU Phase Power Factor Clear Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20334
pduPhaseEnergyCLEARPDU Phase Accumulated Energy Clear Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20335
pduBreakerCurrentCLEARPDU Breaker Current Clear Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20354
pduBreakerCurrentMaxCLEARPDU Breaker Current (Max) Clear Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20355
pduBreakerCurrentMinCLEARPDU Breaker Current (Min) Clear Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20356
pduBreakerCurrentPeakCLEARPDU Breaker Current (Peak) Clear Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20357
pduLineCurrentCLEARPDU Line Current Clear Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20374
pduLineCurrentMaxCLEARPDU Line Current (Max) Clear Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20375
pduLineCurrentMinCLEARPDU Line Current (Min) Clear Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20376
pduLineCurrentPeakCLEARPDU Line Current (Peak) Clear Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20377
tempSensorAvailCLEARDevice availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable Clear Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20404
tempSensorTempCLEARRemote Temperature Sensor Clear Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20405
airFlowSensorAvailCLEARDevice availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable Clear Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20504
airFlowSensorTempCLEARAFHT3 Sensor Temperature Clear Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20505
airFlowSensorFlowCLEARAFHT3 Airflow reading Clear Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20506
airFlowSensorHumidityCLEARAFHT3 Humidity reading Clear Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20507
airFlowSensorDewPointCLEARAFHT3 Sensor Dew Point Clear Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20508
dewPointSensorAvailCLEARDevice availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable Clear Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20604
dewPointSensorTempCLEARRemote Dew Point Sensor Temperature Clear Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20605
dewPointSensorHumidityCLEARHumidity reading Clear Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20606
dewPointSensorDewPointCLEARRemote Dew Point Sensor Dew Point Clear Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20607
ccatSensorAvailCLEARDevice availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable Clear Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20704
ccatSensorValueCLEARCCAT sensor reading Clear Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20705
t3hdSensorAvailCLEARDevice availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable Clear Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20804
t3hdSensorIntTempCLEART3HD Sensor Temperature Clear Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20806
t3hdSensorIntHumidityCLEART3HD Sensor Internal Humidity Clear Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20807
t3hdSensorIntDewPointCLEART3HD Sensor Dew Point Clear Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20808
t3hdSensorExtATempCLEART3HD Sensor External A Temperature Clear Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20811
t3hdSensorExtBTempCLEART3HD Sensor External B Temperature Clear Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20814
thdSensorAvailCLEARDevice availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable Clear Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20904
thdSensorTempCLEARTHD Sensor Temperature Clear Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20905
thdSensorHumidityCLEARTHD Sensor Humidity Clear Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20906
thdSensorDewPointCLEARTHD Sensor Dew Point Clear Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.20907
rpmSensorAvailCLEARDevice availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable Clear Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.21004
rpmSensorEnergyCLEARRPM Sensor Accumulated Energy Clear Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.21005
rpmSensorVoltageCLEARRPM Sensor Voltage Clear Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.21006
rpmSensorVoltageMaxCLEARRPM Sensor Voltage (Max) Clear Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.21007
rpmSensorVoltageMinCLEARRPM Sensor Voltage (Min) Clear Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.21008
rpmSensorVoltagePeakCLEARRPM Sensor Voltage (Peak) Clear Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.21009
rpmSensorCurrentCLEARRPM Sensor Current Clear Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.21010
rpmSensorRealPowerCLEARRPM Sensor Real Power Clear Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.21011
rpmSensorApparentPowerCLEARRPM Sensor Apparent Power Clear Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.21012
rpmSensorPowerFactorCLEARRPM Sensor Power Factor Clear Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.21013
a2dSensorAvailCLEARDevice availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable Clear Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.21104
a2dSensorValueCLEARA2D Analog Sensor Measurement Clear Trap
NOTIFICATION-TYPE
.1.3.6.1.4.1.21239.5.2.32767.0.21105