VALERE-DC-POWER-MIB
AI MIB Summary
The VALERE-DC-POWER-MIB facilitates the monitoring and management of Valere DC power systems, specifically retrieving inventory data for rectifiers and modules while tracking power-related trap events. It enables the collection of hardware status metrics for power supply units and associated ringers within telecommunications or data center power infrastructure.
MIB Version 0.8 Need description here. History Add table to retrieve module inventory info MIB Version 0.7 Dec 1, 05 Fixed HP Openview error Fixed warnings generated by MG-SOFT Add table to retrieve rectifier inventory info MIB Version 0.6 Feb 10, 2004 Added additional traps. Defined Ringers and other modules. Feb 08, 2003 Changed vpwrTrapDestinationTable to vpwrTrapTable Corrected entry for vpwrTrapTable to be VpwrTrapTableEntry This fixes errors generated by MG-SOFT mib compiler. Oct 30, 2002 initial release - version 0.4
Main OID:
vpwrDcPowerMgt.1.3.6.1.4.1.13858
293
Objects
Active
Status
4
Dependencies
Imported Objects
Objects
293 total| Object Name |
|---|
vpwrDcPowerMgtMIB Version 0.8
Need description here.
History
Add table to retrieve module inventory info
MIB Version 0.7
Dec 1, 05
Fixed HP Openview error
Fixed warnings generated by MG-SOFT
Add table to retrieve rectifier inventory info
MIB Version 0.6
Feb 10, 2004 Added additional traps.
Defined Ringers and other modules.
Feb 08, 2003 Changed vpwrTrapDestinationTable to vpwrTrapTable
Corrected entry for vpwrTrapTable to be VpwrTrapTableEntry
This fixes errors generated by MG-SOFT mib compiler.
Oct 30, 2002 initial release - version 0.4 MODULE-IDENTITY .1.3.6.1.4.1.13858 |
vpwrDcPowerProducts OBJECT IDENTIFIER .1.3.6.1.4.1.13858.1 |
vpwrDcPowerSystem OBJECT IDENTIFIER .1.3.6.1.4.1.13858.2 |
vpwrSystemIdentGroup OBJECT IDENTIFIER .1.3.6.1.4.1.13858.2.1 |
vpwrIdentManufacturerThe name of the DC Power manufacturer.ro DisplayString .1.3.6.1.4.1.13858.2.1.1 |
vpwrIdentModelThe DC Power Model designation.ro DisplayString .1.3.6.1.4.1.13858.2.1.2 |
vpwrIdentControllerVersionThe hardware/firmware version(s). This variable
may or may not have the same value as
vpwrIdentAgentSoftwareVersion.ro DisplayString .1.3.6.1.4.1.13858.2.1.3 |
vpwrIdentAgentSoftwareVersionThe SNMP agent software version. This variable may or
may not have the same value as
vpwrIdentControllerFirmwareVersion.ro DisplayString .1.3.6.1.4.1.13858.2.1.4 |
vpwrIdentNameA string identifying the system. This object should be
set by the administrator.rw DisplayString .1.3.6.1.4.1.13858.2.1.5 |
vpwrSystemIdentTableThis table describes shelves and modules
that make up the sysetm. SEQUENCE OF VpwrSystemIdentEntry .1.3.6.1.4.1.13858.2.1.6 |
vpwrSystemIdentEntryAn entry containing information applicable to a
particular alarm. VpwrSystemIdentEntry .1.3.6.1.4.1.13858.2.1.6.1 |
vpwrBayIndexIdentifies Bay number that this module belongs to.
The possible values are 1 through 16 limited by vpwrSystemShelfCapacity.ro PositiveInteger .1.3.6.1.4.1.13858.2.1.6.1.1 |
vpwrModuleIndexThis object identifies the module by its position in the shelf.
Module numbering is left to right starting with module 1. So, the
module in the first slot has an index of 1, the next module is 2 and
so on.ro PositiveInteger .1.3.6.1.4.1.13858.2.1.6.1.2 |
vpwrModuleOIDIt indicates the type of the module by specifiying its OIDro OBJECT IDENTIFIER .1.3.6.1.4.1.13858.2.1.6.1.3 |
vpwrModuleCurrentThe meaning of this object depends upon the module type
which is indicated by vpwrModuleOID as follows
- Current for Rectifier module.
- Not Applicable for LVD modulero INTEGER .1.3.6.1.4.1.13858.2.1.6.1.4 |
vpwrModuleOperStatusThis object indicates current over all status of the module.ro Enumeration .1.3.6.1.4.1.13858.2.1.6.1.5 |
vpwrModuleCapacityThe meaning of this object depends upon the module type
which is indicated by vpwrModuleOID as follows
- Capacity for Rectifier module.
- Not Applicable for LVD modulero INTEGER .1.3.6.1.4.1.13858.2.1.6.1.6 |
vpwrSystemConfigGroup OBJECT IDENTIFIER .1.3.6.1.4.1.13858.2.2 |
vpwrSystemTempCompensationThis parameter enables/disables temperature compensation.rw Enumeration .1.3.6.1.4.1.13858.2.2.1 |
vpwrSystemTempCompStartTemperatureThe temperature at which temperature compensation becomes
active.rw INTEGER (25 .. 60) UNITS "degrees Centigrade" .1.3.6.1.4.1.13858.2.2.2 |
vpwrSystemTempCompStopVoltageWhen temperature compensation is active, vpwrSystemTempCompStopVoltage is the
limit to which float voltage will be reduced.
For example, to set this voltage to 51.75 volts enter a value of 5175.rw INTEGER UNITS " *.01 Volts" .1.3.6.1.4.1.13858.2.2.3 |
vpwrSystemTempCompensationSlopeThe rate at which float voltage is changed, within the specified limits,
when temperature compensation is active.rw INTEGER (0 .. 250) UNITS " milli-Volts per degrees Centigrade" .1.3.6.1.4.1.13858.2.2.4 |
vpwrSystemThermalSenseTypeThis parameter selects the temperature sensing point for temperature
compensation (in)activation.rw Enumeration .1.3.6.1.4.1.13858.2.2.5 |
vpwrSystemHVAlarmSetpointSystem High voltage alarm voltage setting.rw INTEGER UNITS " *.01 Volts" .1.3.6.1.4.1.13858.2.2.6 |
vpwrSystemBDAlarmSetpointSystem Battery Discharge voltage setting.rw INTEGER UNITS " *.01 Volts" .1.3.6.1.4.1.13858.2.2.7 |
vpwrSystemInternalTempLThresholdTemperature value at which temperature compensation inactive (clear)
trap would be sent if temperature compensation was active when this
value is reached.rw INTEGER UNITS "degrees Centigrade" .1.3.6.1.4.1.13858.2.2.8 |
vpwrSystemInternalTempUThresholdTemperature value at which temperature compensation active (set) trap
would be sent.rw INTEGER UNITS "degrees Centigrade" .1.3.6.1.4.1.13858.2.2.9 |
vpwrSystemParameterGroup OBJECT IDENTIFIER .1.3.6.1.4.1.13858.2.3 |
vpwrSystemShelfCapacityIt describes the maximum number of shelves that can/are controlled
by the controller. Each shelf is uniquely numbered in the range
from 1 to vpwrShelfCapacity.ro INTEGER (1 .. 16) .1.3.6.1.4.1.13858.2.3.1 |
vpwrSystemVoltageThe current system voltage.ro INTEGER UNITS " *.01 Volts" .1.3.6.1.4.1.13858.2.3.2 |
vpwrSystemCurrentThe current system current.ro INTEGER UNITS " Amperes" .1.3.6.1.4.1.13858.2.3.3 |
vpwrSystemControllerStateCurrent System state as shown on the enhanced display.ro Enumeration .1.3.6.1.4.1.13858.2.3.4 |
vpwrSystemInternalTemperatureThe current controller internal temperature.ro INTEGER UNITS "degrees Centigrade" .1.3.6.1.4.1.13858.2.3.5 |
vpwrSystemTempCompensationStateActive or Inactive. Applicable only if temperature compensation is enabled.
This means that the controller is temperature compensating the float voltage.ro Enumeration .1.3.6.1.4.1.13858.2.3.6 |
vpwrSystemTypeThis parameter describes the type of the system being managed.
This object is set by Valere Power Inc.ro Enumeration .1.3.6.1.4.1.13858.2.3.7 |
vpwrSystemPanelIdentGroup OBJECT IDENTIFIER .1.3.6.1.4.1.13858.2.4 |
vpwrPanelIdentTableThis table describes shelves and modules
that make up the panels. SEQUENCE OF VpwrPanelIdentEntry .1.3.6.1.4.1.13858.2.4.1 |
vpwrPanelIdentEntryAn entry containing information applicable to a
particular panel making up the system. VpwrPanelIdentEntry .1.3.6.1.4.1.13858.2.4.1.1 |
vpwrPanelBayIndexIdentifies bay number that this module belongs to.
The possible values are 1 through 16, starting from the top.ro PositiveInteger .1.3.6.1.4.1.13858.2.4.1.1.1 |
vpwrPanelModuleIndexThis object identifies the module within the panel.
The orentation of modules within the panel is mappable.ro PositiveInteger .1.3.6.1.4.1.13858.2.4.1.1.2 |
vpwrPanelModuleOIDIt indicates the type of the module by specifiying its OIDro OBJECT IDENTIFIER .1.3.6.1.4.1.13858.2.4.1.1.3 |
vpwrPanelModuleCurrentThis is the Current of the first shunt of the module.ro INTEGER .1.3.6.1.4.1.13858.2.4.1.1.4 |
vpwrPanelModuleOperStatusThis object indicates over all status of the module.ro Enumeration .1.3.6.1.4.1.13858.2.4.1.1.5 |
vpwrPanelModuleCapacityThis is the overall Capacity of the module and is for reference only.ro INTEGER .1.3.6.1.4.1.13858.2.4.1.1.6 |
vpwrSystemBayctrlIdentGroup OBJECT IDENTIFIER .1.3.6.1.4.1.13858.2.5 |
vpwrBayctrlIdentTableThis table describes bay controllers
that make up the system. SEQUENCE OF VpwrBayctrlIdentEntry .1.3.6.1.4.1.13858.2.5.1 |
vpwrBayctrlIdentEntryAn entry containing information applicable to a
particular bay controller making up the system. VpwrBayctrlIdentEntry .1.3.6.1.4.1.13858.2.5.1.1 |
vpwrBayctrlIndexIdentifies bay number that this module belongs to.
The possible values are 0 through 15, starting from the top.ro PositiveInteger .1.3.6.1.4.1.13858.2.5.1.1.1 |
vpwrBayctrlOIDIt indicates the type of the module by specifiying its OIDro OBJECT IDENTIFIER .1.3.6.1.4.1.13858.2.5.1.1.2 |
vpwrBayctrlCurrentThis is the total output Current of the bayro INTEGER .1.3.6.1.4.1.13858.2.5.1.1.3 |
vpwrBayctrlOperStatusThis object indicates over all status of the bayro Enumeration .1.3.6.1.4.1.13858.2.5.1.1.4 |
vpwrBayctrlCapacityThis is the overall Capacity of the bay and is for reference only.ro INTEGER .1.3.6.1.4.1.13858.2.5.1.1.5 |
vpwrDcPowerRectifier OBJECT IDENTIFIER .1.3.6.1.4.1.13858.3 |
vpwrRectifierConfigGroup OBJECT IDENTIFIER .1.3.6.1.4.1.13858.3.1 |
vpwrRectifierFVSetpointSystem Float Voltage settingrw INTEGER UNITS " *.01 Volts" .1.3.6.1.4.1.13858.3.1.1 |
vpwrRectifierHVSDSetpointSystem High Voltage Shutdown voltage settingrw INTEGER UNITS " *.01 Volts" .1.3.6.1.4.1.13858.3.1.2 |
vpwrRectifierCurrentLimitAdminStateThis parameter allows enabling or disabling boost.rw Enumeration .1.3.6.1.4.1.13858.3.1.3 |
vpwrRectifierCurrentLimitRectifier current limit setpointrw INTEGER (5 .. 200) UNITS "Amperes" .1.3.6.1.4.1.13858.3.1.4 |
vpwrRectifierAlarmGroup OBJECT IDENTIFIER .1.3.6.1.4.1.13858.3.2 |
vpwrRectAlarmDCFail OBJECT IDENTIFIER .1.3.6.1.4.1.13858.3.2.1 |
vpwrRectAlarmBoostFail OBJECT IDENTIFIER .1.3.6.1.4.1.13858.3.2.2 |
vpwrRectAlarmACFail OBJECT IDENTIFIER .1.3.6.1.4.1.13858.3.2.3 |
vpwrRectAlarmHVSD OBJECT IDENTIFIER .1.3.6.1.4.1.13858.3.2.4 |
vpwrRectAlarmFanFail OBJECT IDENTIFIER .1.3.6.1.4.1.13858.3.2.5 |
vpwrRectAlarmAmbTemp OBJECT IDENTIFIER .1.3.6.1.4.1.13858.3.2.6 |
vpwrRectAlarmIntTemp OBJECT IDENTIFIER .1.3.6.1.4.1.13858.3.2.7 |
vpwrRectAlarmIShare OBJECT IDENTIFIER .1.3.6.1.4.1.13858.3.2.8 |
vpwrRectAlarmUV OBJECT IDENTIFIER .1.3.6.1.4.1.13858.3.2.9 |
vpwrRectAlarmLowVoltage OBJECT IDENTIFIER .1.3.6.1.4.1.13858.3.2.10 |
vpwrRectAlarmReserved OBJECT IDENTIFIER .1.3.6.1.4.1.13858.3.2.11 |
vpwrRectAlarmDCEnable OBJECT IDENTIFIER .1.3.6.1.4.1.13858.3.2.12 |
vpwrRectAlarmRemoteShutdown OBJECT IDENTIFIER .1.3.6.1.4.1.13858.3.2.13 |
vpwrRectAlarmModDisableShutdown OBJECT IDENTIFIER .1.3.6.1.4.1.13858.3.2.14 |
vpwrRectAlarmShortPinShutdown OBJECT IDENTIFIER .1.3.6.1.4.1.13858.3.2.15 |
vpwrRectAlarmBoostComm OBJECT IDENTIFIER .1.3.6.1.4.1.13858.3.2.16 |
vpwrRectifierTestGroup OBJECT IDENTIFIER .1.3.6.1.4.1.13858.3.3 |
vpwrDcPowerLvd OBJECT IDENTIFIER .1.3.6.1.4.1.13858.4 |
vpwrLvdConfigGroup OBJECT IDENTIFIER .1.3.6.1.4.1.13858.4.1 |
vpwrLvdWarningSetpointLVD Warning voltage setpoint.rw INTEGER UNITS " * .01 Volts" .1.3.6.1.4.1.13858.4.1.1 |
vpwrLvdDisconnectSetpointLVD disconnect voltage setpoint.rw INTEGER UNITS " *.01 Volts" .1.3.6.1.4.1.13858.4.1.2 |
vpwrLvdReconnectSetpointLVD Reconnect voltage setpoint.rw INTEGER UNITS " *.01 Volts" .1.3.6.1.4.1.13858.4.1.3 |
vpwrLvdReconnectDelayTimerThe delay time, in seconds, before LVD is reconnectedrw INTEGER .1.3.6.1.4.1.13858.4.1.4 |
vpwrLvdContactorConfigTableThis table describes shelves and modules
that make up the sysetm. SEQUENCE OF VpwrLvdContactorConfigEntry .1.3.6.1.4.1.13858.4.1.5 |
vpwrLvdContactorConfigEntryAn entry containing information applicable to a
particular module making up the system. VpwrLvdContactorConfigEntry .1.3.6.1.4.1.13858.4.1.5.1 |
vpwrLvdContactorIndexcontactor indexro PositiveInteger UNITS " None" .1.3.6.1.4.1.13858.4.1.5.1.1 |
vpwrLvdContactorWarningSetpointLVD Warning voltage setpoint.rw PositiveInteger UNITS " * .01 Volts" .1.3.6.1.4.1.13858.4.1.5.1.2 |
vpwrLvdContactorDisconnectSetpointLVD disconnect voltage setpoint.rw PositiveInteger UNITS " *.01 Volts" .1.3.6.1.4.1.13858.4.1.5.1.3 |
vpwrLvdContactorReconnectSetpointLVD Reconnect voltage setpoint.rw PositiveInteger UNITS " *.01 Volts" .1.3.6.1.4.1.13858.4.1.5.1.4 |
vpwrLvdContactorReconnectDelayTimerThe delay time, in seconds, before LVD is reconnectedrw PositiveInteger .1.3.6.1.4.1.13858.4.1.5.1.5 |
vpwrLvdContactorStateThe delay time, in seconds, before LVD is reconnectedrw Enumeration .1.3.6.1.4.1.13858.4.1.5.1.6 |
vpwrLvdAlarmGroup OBJECT IDENTIFIER .1.3.6.1.4.1.13858.4.2 |
vpwrLvdAlarmContactorOpenContactor open OBJECT IDENTIFIER .1.3.6.1.4.1.13858.4.2.1 |
vpwrLvdAlarmCBOpenCircuit Breaker open OBJECT IDENTIFIER .1.3.6.1.4.1.13858.4.2.2 |
vpwrTrapLvdFuseOpenFuse open OBJECT IDENTIFIER .1.3.6.1.4.1.13858.4.2.3 |
vpwrLvdAlarmWarningPlant Voltage below warning threshold OBJECT IDENTIFIER .1.3.6.1.4.1.13858.4.2.4 |
vpwrLvdTestGroup OBJECT IDENTIFIER .1.3.6.1.4.1.13858.4.3 |
vpwrDcPowerTest OBJECT IDENTIFIER .1.3.6.1.4.1.13858.5 |
vpwrDcPowerModuleIdent OBJECT IDENTIFIER .1.3.6.1.4.1.13858.6 |
vpwrModuleIdentTableThis table describes shelves and modules
that make up the sysetm. SEQUENCE OF VpwrModuleIdentEntry .1.3.6.1.4.1.13858.6.1 |
vpwrModuleIdentEntryAn entry containing information applicable to a
particular Module. VpwrModuleIdentEntry .1.3.6.1.4.1.13858.6.1.1 |
vpwrModuleSerialNumberSerial Number of the modulero DisplayString (SNMPv2-TC) .1.3.6.1.4.1.13858.6.1.1.1 |
vpwrModuleModelNumberModel Number of the module.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.13858.6.1.1.2 |
vpwrModuleFwVersionFirmware version of the module.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.13858.6.1.1.3 |
vpwrModuleTestDateDate when the module was last tested.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.13858.6.1.1.4 |
vpwrModuleOperHoursCumulative Operating Hours.ro Counter32 .1.3.6.1.4.1.13858.6.1.1.5 |
vpwrPanelModuleIdentTableThis table describes shelves and modules
that make up the sysetm. SEQUENCE OF VpwrPanelModuleIdentEntry .1.3.6.1.4.1.13858.6.2 |
vpwrPanelModuleIdentEntryAn entry containing information applicable to a
particular alarm. VpwrPanelModuleIdentEntry .1.3.6.1.4.1.13858.6.2.1 |
vpwrPanelModuleSerialNumberSerial Number of the modulero DisplayString (SNMPv2-TC) .1.3.6.1.4.1.13858.6.2.1.1 |
vpwrPanelModuleModelNumberModel Number of the module.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.13858.6.2.1.2 |
vpwrPanelModuleFwVersionFirmware version of the module.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.13858.6.2.1.3 |
vpwrPanelModuleTestDateDate when the module was last tested.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.13858.6.2.1.4 |
vpwrPanelModuleOperHoursCumulative Operating Hours.ro Counter32 .1.3.6.1.4.1.13858.6.2.1.5 |
vpwrBayctrlModuleIdentTableThis table describes bay controllers that make up the sysetm. SEQUENCE OF VpwrBayctrlModuleIdentEntry .1.3.6.1.4.1.13858.6.3 |
vpwrBayctrlModuleIdentEntryAn entry containing information applicable to a particular bay controller. VpwrBayctrlModuleIdentEntry .1.3.6.1.4.1.13858.6.3.1 |
vpwrBayctrlSerialNumberSerial Number of the bay controllerro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.13858.6.3.1.1 |
vpwrBayctrlModelNumberModel Number of the bay controller.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.13858.6.3.1.2 |
vpwrBayctrlFwVersionFirmware version of the bay controller.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.13858.6.3.1.3 |
vpwrBayctrlTestDateDate when the bayctrl was last tested.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.13858.6.3.1.4 |
vpwrBayctrlOperHoursCumulative Operating Hours.ro Counter32 .1.3.6.1.4.1.13858.6.3.1.5 |
vpwrDcPowerBatteryGroup OBJECT IDENTIFIER .1.3.6.1.4.1.13858.7 |
vpwrBatteryTempGroup OBJECT IDENTIFIER .1.3.6.1.4.1.13858.7.1 |
vpwrBatteryTempTableThis table describes battery temperature probes. SEQUENCE OF VpwrBatteryTempEntry .1.3.6.1.4.1.13858.7.1.1 |
vpwrBatteryTempEntryAn entry containing information applicable to a
particular temperature probe. VpwrBatteryTempEntry .1.3.6.1.4.1.13858.7.1.1.1 |
vpwrBatteryTempIndexIndex into temperature tablero INTEGER .1.3.6.1.4.1.13858.7.1.1.1.1 |
vpwrBatteryTempNameA string identifying probe location.rw DisplayString .1.3.6.1.4.1.13858.7.1.1.1.2 |
vpwrBatteryTempCurrent temperature as recorded by the probe.ro INTEGER UNITS "degrees Centigrade" .1.3.6.1.4.1.13858.7.1.1.1.3 |
vpwrBatteryTempLThresholdTemperature value at which a clear trap would be sent.
All three battery temperature must be at or below this value
to trigger this trap.rw INTEGER UNITS "degrees Centigrade" .1.3.6.1.4.1.13858.7.1.2 |
vpwrBatteryTempUThresholdTemperature value at which a set trap would be sent.
Any one of the three battery temperatures at or exceeding this limit
would trigger the trap.rw INTEGER UNITS "degrees Centigrade" .1.3.6.1.4.1.13858.7.1.3 |
batteryTempCompensationThis parameter enables/disables temperature compensation.rw Enumeration .1.3.6.1.4.1.13858.7.1.4 |
batteryTempCompHighStartTemperatureThe temperature at which temperature compensation becomes
active.rw INTEGER (25 .. 60) UNITS "degrees Centigrade" .1.3.6.1.4.1.13858.7.1.5 |
batteryTempCompHighStopVoltageWhen temperature compensation is active, batteryTempCompHighStopVoltage is the
limit to which float voltage will be reduced.
For example, to set this voltage to 51.75 volts enter a value of 5175.rw INTEGER UNITS " *.01 Volts" .1.3.6.1.4.1.13858.7.1.6 |
batteryTempCompHighSlopeThe rate at which float voltage is changed, within the specified limits,
when temperature compensation is active.rw INTEGER (0 .. 250) UNITS " milli-Volts per degrees Centigrade" .1.3.6.1.4.1.13858.7.1.7 |
batteryTempCompLowStartTemperatureThe temperature at which temperature compensation becomes
active.rw INTEGER UNITS "degrees Centigrade" .1.3.6.1.4.1.13858.7.1.8 |
batteryTempCompLowStopVoltageWhen temperature compensation is active, batteryTempCompLowStopVoltage is the
limit to which float voltage will be reduced.
For example, to set this voltage to 51.75 volts enter a value of 5175.rw INTEGER UNITS " *.01 Volts" .1.3.6.1.4.1.13858.7.1.9 |
batteryTempCompLowSlopeThe rate at which float voltage is changed, within the specified limits,
when temperature compensation is active.rw INTEGER (0 .. 250) UNITS " milli-Volts per degrees Centigrade" .1.3.6.1.4.1.13858.7.1.10 |
batteryTempCompRunawayTemperatureThe temperature at which system voltage will be set to
batteryTempCompRunawayStopVoltage.rw INTEGER (25 .. 60) UNITS "degrees Centigrade" .1.3.6.1.4.1.13858.7.1.11 |
batteryTempCompRunawayStopVoltageWhen temperature compensation is enabled, float voltage will be reduced to
batteryTempCompRunawayStopVoltage if temperature
reaches batteryTempCompRunawayTemperature.rw INTEGER UNITS " *.01 Volts" .1.3.6.1.4.1.13858.7.1.12 |
batteryTempCompSenseSourceThis parameter selects the temperature sensing point for temperature
compensation (in)activation.rw Enumeration .1.3.6.1.4.1.13858.7.1.13 |
batteryTempCompRunawayStateThis parameter selects the temperature sensing point for temperature
compensation (in)activation.ro Enumeration .1.3.6.1.4.1.13858.7.1.14 |
thermalProbeTableThis table describes battery temperature probes. SEQUENCE OF ThermalProbeEntry .1.3.6.1.4.1.13858.7.1.15 |
thermalProbeEntryAn entry containing information applicable to a
particular temperature probe. ThermalProbeEntry .1.3.6.1.4.1.13858.7.1.15.1 |
thermalProbeStateState of thermal probe.ro Enumeration .1.3.6.1.4.1.13858.7.1.15.1.1 |
vpwrBatteryCurrentGroup OBJECT IDENTIFIER .1.3.6.1.4.1.13858.7.2 |
vpwrBatteryCurrentLimitAdminStateThis parameter allows enabling or disabling battery current limit.rw Enumeration .1.3.6.1.4.1.13858.7.2.1 |
vpwrBattetyCurrentLimitValuerw INTEGER (5 .. 40) UNITS "Ampere" .1.3.6.1.4.1.13858.7.2.2 |
vpwrBattetyCurrentValuero INTEGER (5 .. 40) UNITS "Ampere" .1.3.6.1.4.1.13858.7.2.3 |
vpwrBatteryBoostGroup OBJECT IDENTIFIER .1.3.6.1.4.1.13858.7.3 |
vpwrBoostAdminStateThis parameter allows enabling or disabling boost.rw Enumeration .1.3.6.1.4.1.13858.7.3.1 |
vpwrBoostVoltagerw INTEGER (7000 .. 11000) UNITS " *.01 Volts" .1.3.6.1.4.1.13858.7.3.2 |
vpwrBoostDurationrw INTEGER (0 .. 100 ) UNITS "Hours" .1.3.6.1.4.1.13858.7.3.3 |
vpwrBoostOperStateThis parameter allows starting or stoping boost if it is enabled.rw Enumeration .1.3.6.1.4.1.13858.7.3.4 |
vpwrBatteryDischargeTestGroup OBJECT IDENTIFIER .1.3.6.1.4.1.13858.7.4 |
vpwrBDTAdminStateEnable /Disable Battery Discharge Test execution.rw Enumeration .1.3.6.1.4.1.13858.7.4.1 |
vpwrBDTDurationrw INTEGER (17 .. 50) UNITS "Minutes" .1.3.6.1.4.1.13858.7.4.2 |
vpwrBDTAlarmVoltagerw INTEGER (7000 .. 11000) UNITS " *.01 Volts" .1.3.6.1.4.1.13858.7.4.3 |
vpwrBDTAbortVoltagerw INTEGER (0 .. 5600 ) UNITS " *.01 Volts" .1.3.6.1.4.1.13858.7.4.4 |
vpwrBDTAlarmCoefficientrw INTEGER (0 .. 1 ) UNITS "None" .1.3.6.1.4.1.13858.7.4.5 |
vpwrBDTOperStateStart/Stop Battery Discharge Test execution.rw Enumeration .1.3.6.1.4.1.13858.7.4.6 |
vpwrBDTClearAlarmClears any active bdt alarm.rw Enumeration .1.3.6.1.4.1.13858.7.4.7 |
vpwrDcPowerAlarmGroup OBJECT IDENTIFIER .1.3.6.1.4.1.13858.8 |
vpwrAlarmsPresentThe present number of active alarm conditions.ro Gauge32 .1.3.6.1.4.1.13858.8.1 |
vpwrAlarmTableA list of alarm table entries. The table contains
zero, one, or many rows at any moment, depending upon
the number of alarm conditions in effect. The table
is initially empty at agent startup. The agent
creates a row in the table each time a condition is
detected and deletes that row when that condition no
longer pertains.
The vpwrAlarmIndex, for each type of module starts at 1
and is limited by the total number of alarams that can be
generated by the module.
Alarms are named by an AutonomousType (OBJECT
IDENTIFIER), vpwrAlarmDescr, to allow a single table to
reflect alarms for different type of modules.
The number of rows in the table at any given time is
reflected by the value of vpwrAlarmsPresent. SEQUENCE OF VpwrAlarmEntry .1.3.6.1.4.1.13858.8.2 |
vpwrAlarmEntryAn entry containing information applicable to a
particular alarm. VpwrAlarmEntry .1.3.6.1.4.1.13858.8.2.1 |
vpwrAlarmIndexIdentifies the alarm associated with the module.
It is unique on per module type basis. For example,
multiple rectifiers can have the same alarm and therefore same
vpwrAlarmIndex active at any one time.ro PositiveInteger .1.3.6.1.4.1.13858.8.2.1.1 |
vpwrAlarmDescrA reference to an alarm description object. The
object referenced should not be accessible, but rather
be used to provide a unique description of the alarm
condition.ro AutonomousType (SNMPv2-TC) .1.3.6.1.4.1.13858.8.2.1.2 |
vpwrAlarmTimeThe value of sysUpTime when the alarm condition was
detected.ro TimeStamp (SNMPv2-TC) .1.3.6.1.4.1.13858.8.2.1.3 |
sysRelayConfigTableThis table describes battery temperature probes. SEQUENCE OF SysRelayConfigEntry .1.3.6.1.4.1.13858.8.3 |
sysRelayConfigEntryAn entry containing information applicable to a
particular temperature probe. SysRelayConfigEntry .1.3.6.1.4.1.13858.8.3.1 |
sysRelayIndexIndex into temperature tablero INTEGER .1.3.6.1.4.1.13858.8.3.1.1 |
sysRelayDefaultNameA string identifying probe location.ro DisplayString .1.3.6.1.4.1.13858.8.3.1.2 |
sysRelayCustomNameA string identifying probe location.rw DisplayString .1.3.6.1.4.1.13858.8.3.1.3 |
sysRelayAlarmSeverityCurrent temperature as recorded by the probe.rw Enumeration .1.3.6.1.4.1.13858.8.3.1.4 |
sysAlarmConfigTableThis table describes battery temperature probes. SEQUENCE OF SysAlarmConfigEntry .1.3.6.1.4.1.13858.8.4 |
sysAlarmConfigEntryAn entry containing information applicable to a
particular temperature probe. SysAlarmConfigEntry .1.3.6.1.4.1.13858.8.4.1 |
sysAlarmIndexIndex into temperature tablero INTEGER .1.3.6.1.4.1.13858.8.4.1.1 |
sysAlarmDefaultNameA string identifying probe location.ro DisplayString .1.3.6.1.4.1.13858.8.4.1.2 |
sysAlarmCustomNameA string identifying probe location.rw DisplayString .1.3.6.1.4.1.13858.8.4.1.3 |
sysAlarmSeverityAlarm Severity as denoted by Major and Minor Alarm Maskrw Enumeration .1.3.6.1.4.1.13858.8.4.1.4 |
sysAlarmToRelayMappingNo additional mapping = 0
Map to Relay A = 1
Map to Relay B = 2
Map to Relay C = 4
Map to Relay D = 8
Map to Relay E = 16
Map to Relay F = 32
Map to Relay A and B = (1 + 2) and so on
The major/minor classification of alarms automatically
associates it with Major/Minor relay. Assigning a null
mapping here does not override sysRelayAlarmSeverity for
the alarm.
It should be used to define mapping to additional relays.rw DisplayString .1.3.6.1.4.1.13858.8.4.1.5 |
sysAlarmOperStatusIndicates current alarm statusro Enumeration .1.3.6.1.4.1.13858.8.4.1.6 |
sysAuxAlarmConfigTableThis table describes battery temperature probes. SEQUENCE OF SysAuxAlarmConfigEntry .1.3.6.1.4.1.13858.8.5 |
sysAuxAlarmConfigEntryAn entry containing information applicable to a
particular temperature probe. SysAuxAlarmConfigEntry .1.3.6.1.4.1.13858.8.5.1 |
sysAuxAlarmIndexIndex into temperature tablero INTEGER .1.3.6.1.4.1.13858.8.5.1.1 |
sysAuxAlarmDefaultNameA string identifying probe location.ro DisplayString .1.3.6.1.4.1.13858.8.5.1.2 |
sysAuxAlarmCustomNameA string identifying probe location.rw DisplayString .1.3.6.1.4.1.13858.8.5.1.3 |
sysAuxAlarmSeverityAux Alarm Severityrw Enumeration .1.3.6.1.4.1.13858.8.5.1.4 |
sysAuxAlarmToRelayMappingNo additional mapping = 0
Map to Relay A = 1
Map to Relay B = 2
Map to Relay C = 4
Map to Relay D = 8
Map to Relay E = 16
Map to Relay F = 32
Map to Relay A and B = (1 + 2) and so on
The major/minor classification of alarms automatically
associates it with Major/Minor relay. Assigning a null
mapping here does not override sysRelayAlarmSeverity for
the alarm.
It should be used to define mapping to additional relays.rw DisplayString .1.3.6.1.4.1.13858.8.5.1.5 |
sysAuxAlarmPolarityCurrent temperature as recorded by the probe.rw Enumeration .1.3.6.1.4.1.13858.8.5.1.6 |
sysAuxAlarmOperStatusIndicates current alarm statusro Enumeration .1.3.6.1.4.1.13858.8.5.1.7 |
sysAlarmComFailStateEnable/Disable generation of comm fail alarm.rw Enumeration .1.3.6.1.4.1.13858.8.6 |
sysAlarmIShareStateEnable/Disable generation of current share alarm.rw Enumeration .1.3.6.1.4.1.13858.8.7 |
sysAlarmRedundancyStateEnable/Disable generation of redundancy alarm.rw Enumeration .1.3.6.1.4.1.13858.8.8 |
vpwrDcPowerSnmpConfig OBJECT IDENTIFIER .1.3.6.1.4.1.13858.9 |
vpwrTrapTableA list of possible trap destinations depending upon
the criticality of the trap. SEQUENCE OF VpwrTrapEntry .1.3.6.1.4.1.13858.9.1 |
vpwrTrapEntryAn entry containing information applicable to a
particular trap destination. VpwrTrapEntry .1.3.6.1.4.1.13858.9.1.1 |
vpwrTrapIpIndexTrap Entry Indexro INTEGER .1.3.6.1.4.1.13858.9.1.1.1 |
vpwrTrapIpAddressTrap destination IP Addressrw IpAddress .1.3.6.1.4.1.13858.9.1.1.2 |
vpwrTrapCriticalityCriticality of traps sent to this IP Addressrw INTEGER .1.3.6.1.4.1.13858.9.1.1.3 |
vpwrReadCommunityStringThis allows setting password to be able to do Get operationsrw DisplayString .1.3.6.1.4.1.13858.9.2 |
vpwrWriteCommunityStringThis allows setting password to be able to do Get and Set
operations.
The read-access is not allowed in the actual implementation.rw DisplayString .1.3.6.1.4.1.13858.9.3 |
vpwrTrapCommunityStringThis allows setting community string required for the
trap to be accepted at the destination.rw DisplayString .1.3.6.1.4.1.13858.9.4 |
vpwrDcPowerTraps OBJECT IDENTIFIER .1.3.6.1.4.1.13858.10 |
vpwrTrapPowerMajorAlarmMajor Alarm TRAP-TYPE .1.3.6.1.4.1.13858.10.0.1 |
vpwrTrapPowerMinorAlarmMinor Alarm TRAP-TYPE .1.3.6.1.4.1.13858.10.0.2 |
vpwrTrapACFAlarmAC Fail Alarm TRAP-TYPE .1.3.6.1.4.1.13858.10.0.3 |
vpwrTrapHVAlarmHigh Voltage Warning Alarm TRAP-TYPE .1.3.6.1.4.1.13858.10.0.4 |
vpwrTrapHVSDAlarmHigh Voltage Shutdown Alarm TRAP-TYPE .1.3.6.1.4.1.13858.10.0.5 |
vpwrTrapBDAlarmBattery on Discharge Alarm TRAP-TYPE .1.3.6.1.4.1.13858.10.0.6 |
vpwrTrapLVDWarningAlarmLVD Warning Alarm TRAP-TYPE .1.3.6.1.4.1.13858.10.0.7 |
vpwrTrapLVDOpenAlarmLVD Open Alarm TRAP-TYPE .1.3.6.1.4.1.13858.10.0.8 |
vpwrTrapDistAlarmDistribution Open Alarm TRAP-TYPE .1.3.6.1.4.1.13858.10.0.9 |
vpwrTrapAuxAlarmAuxiliary System Alarm TRAP-TYPE .1.3.6.1.4.1.13858.10.0.10 |
vpwrTrapSystemRedundancyAlarmSystem Redundant Capacity Alarm TRAP-TYPE .1.3.6.1.4.1.13858.10.0.11 |
vpwrTrapIShareAlarmRectifier Current Share Alarm TRAP-TYPE .1.3.6.1.4.1.13858.10.0.12 |
vpwrTrapModuleFailAlarmSingle Rectifier Fail Alarm TRAP-TYPE .1.3.6.1.4.1.13858.10.0.13 |
vpwrTrapMultipleModuleFailAlarmMultiple Rectifier Fail Alarm TRAP-TYPE .1.3.6.1.4.1.13858.10.0.14 |
vpwrTrapModuleCommAlarmModule Communication Alarm TRAP-TYPE .1.3.6.1.4.1.13858.10.0.15 |
vpwrTrapSystemOverTemperatureAlarmSystem Over Temperature Alarm TRAP-TYPE .1.3.6.1.4.1.13858.10.0.16 |
vpwrTrapSystemOKSYSTEM OK - No Active Alarms TRAP-TYPE .1.3.6.1.4.1.13858.10.0.17 |
vpwrTrapModuleInsertedA new module has been inserted into the system. TRAP-TYPE .1.3.6.1.4.1.13858.10.0.18 |
vpwrTrapModuleRemovedA module has been removed from the system. TRAP-TYPE .1.3.6.1.4.1.13858.10.0.19 |
vpwrTrapThermalCompActiveThermal compensation has become active. TRAP-TYPE .1.3.6.1.4.1.13858.10.0.20 |
vpwrTrapThermalCompInactiveThermal compensation has been de-activated. TRAP-TYPE .1.3.6.1.4.1.13858.10.0.21 |
vpwrTrapInternalTempAlarmSetInternal Temperature upper threshold exceeded. TRAP-TYPE .1.3.6.1.4.1.13858.10.0.22 |
vpwrTrapInternalTempAlarmClearedInternal Temperature within limits TRAP-TYPE .1.3.6.1.4.1.13858.10.0.23 |
vpwrTrapBatteryTempAlarmSetAt least one Battery Temperature exceeded upper threshold. TRAP-TYPE .1.3.6.1.4.1.13858.10.0.24 |
vpwrTrapBatteryTempAlarmClearedAll Battery Temperatures within limits. TRAP-TYPE .1.3.6.1.4.1.13858.10.0.25 |
vpwrTrapLoginFailAdmin login failed due to wrong username/password. TRAP-TYPE .1.3.6.1.4.1.13858.10.0.26 |
vpwrTrapLoginSuccessAdmin login successful. TRAP-TYPE .1.3.6.1.4.1.13858.10.0.27 |
vpwrTrapLogoutAdmin logout. TRAP-TYPE .1.3.6.1.4.1.13858.10.0.28 |
vpwrTrapAdminPwdChangeConfig change submitted with invalid access. TRAP-TYPE .1.3.6.1.4.1.13858.10.0.29 |
vpwrTrapIllegalConfigSubmitConfig change submitted with invalid access. TRAP-TYPE .1.3.6.1.4.1.13858.10.0.30 |
vpwrTrapCfgChangeConfig change submitted. TRAP-TYPE .1.3.6.1.4.1.13858.10.0.31 |
vpwrTrapClearEventHistoryClear Event history buffer clear request. TRAP-TYPE .1.3.6.1.4.1.13858.10.0.32 |
vpwrTrapSwDownloadNoRebootSystem software upgrade without reboot. TRAP-TYPE .1.3.6.1.4.1.13858.10.0.33 |
vpwrTrapSwDownloadAndRebootSystem reboot due to software upgrade. TRAP-TYPE .1.3.6.1.4.1.13858.10.0.34 |
vpwrTrapSystemClockChangeSystem clock updated. TRAP-TYPE .1.3.6.1.4.1.13858.10.0.35 |
vpwrTrapModuleAlarmModule Alarm. TRAP-TYPE .1.3.6.1.4.1.13858.10.0.36 |
vpwrTrapOIDChangeChange in OID. TRAP-TYPE .1.3.6.1.4.1.13858.10.0.37 |
vpwrTrapThermalRunawayThermal Runaway Alarm. TRAP-TYPE .1.3.6.1.4.1.13858.10.0.38 |
vpwrTrapBatteryDischargeTestAlarmSystem Voltage dropped to BDT Alarm Setpoint. TRAP-TYPE .1.3.6.1.4.1.13858.10.0.39 |
vpwrTrapRingerAAlarmRinger A Fail Alarm. TRAP-TYPE .1.3.6.1.4.1.13858.10.0.40 |
vpwrTrapRingerBAlarmRinger B Fail Alarm. TRAP-TYPE .1.3.6.1.4.1.13858.10.0.41 |
vpwrTrapSingleRingerAlarmSingle Ringer Fail Alarm. TRAP-TYPE .1.3.6.1.4.1.13858.10.0.42 |
vpwrTrapMultipleRingerAlarmMultiple Ringer Fail Alarm. TRAP-TYPE .1.3.6.1.4.1.13858.10.0.43 |
vpwrTrapThermalProbeAlarmThermal Probe Missing Alarm. TRAP-TYPE .1.3.6.1.4.1.13858.10.0.44 |
vpwrTrapRingerCommAlarmRinger Communication Alarm. TRAP-TYPE .1.3.6.1.4.1.13858.10.0.45 |
vpwrTrapDistributionCommAlarmDistribution Communication Alarm. TRAP-TYPE .1.3.6.1.4.1.13858.10.0.46 |
vpwrTrapConverterAlarmSingle Converter Fail Alarm. TRAP-TYPE .1.3.6.1.4.1.13858.10.0.47 |
vpwrTrapMultipleConvFailAlarmMultiple Converter Fail Alarm. TRAP-TYPE .1.3.6.1.4.1.13858.10.0.48 |
vpwrTrapUnmappedAddressAlarmUnmapped I2C Address. TRAP-TYPE .1.3.6.1.4.1.13858.10.0.49 |
vpwrTrapConfigErrorAlarmConfiguration Error. TRAP-TYPE .1.3.6.1.4.1.13858.10.0.50 |
vpwrTrapDisplayFirmwareMismatchAlarmDisplay Firmware Mismatch. TRAP-TYPE .1.3.6.1.4.1.13858.10.0.51 |
vpwrTrapConverterInputFailAlarmConverter Input Fail Alarm. TRAP-TYPE .1.3.6.1.4.1.13858.10.0.52 |
vpwrTrapBatteryRechgIlimitFailAlarmBattery Recharge Current Limit Fail. TRAP-TYPE .1.3.6.1.4.1.13858.10.0.53 |
vpwrTrapSystemAlivePeriodic Keepalive trap. TRAP-TYPE .1.3.6.1.4.1.13858.10.0.54 |
vpwrDcPowerTrapsMsgString OBJECT IDENTIFIER .1.3.6.1.4.1.13858.11 |
vpwrTrapsMsgStringPlace holder for trap notification message string DisplayString .1.3.6.1.4.1.13858.11.1 |
vpwrTrapUserIpAddressPlace holder for IP address of the user accessing the system IpAddress .1.3.6.1.4.1.13858.11.2 |
vpwrTrapEventTimeStampPlace holder for time-stamp. IpAddress .1.3.6.1.4.1.13858.11.3 |
vpwrDcPowerRinger OBJECT IDENTIFIER .1.3.6.1.4.1.13858.12 |
vpwrRingerConfigGroup OBJECT IDENTIFIER .1.3.6.1.4.1.13858.12.1 |
vpwrRingerParameterTableA list of alarm table entries. The table contains
zero, one, or many rows at any moment, depending upon
the number of alarm conditions in effect. The table
is initially empty at agent startup. The agent
creates a row in the table each time a condition is
detected and deletes that row when that condition no
longer pertains.
The vpwrAlarmIndex, for each type of module starts at 1
and is limited by the total number of alarams that can be
generated by the module.
Alarms are named by an AutonomousType (OBJECT
IDENTIFIER), vpwrAlarmDescr, to allow a single table to
reflect alarms for different type of modules.
The number of rows in the table at any given time is
reflected by the value of vpwrAlarmsPresent. SEQUENCE OF VpwrRingerParameterEntry .1.3.6.1.4.1.13858.12.1.1 |
vpwrRingerParameterEntryAn entry containing information applicable to a
particular alarm. VpwrRingerParameterEntry .1.3.6.1.4.1.13858.12.1.1.1 |
vpwrRingerIndexThis parameter allows selecting ringer A or Ringer B as the active ringer.ro INTEGER .1.3.6.1.4.1.13858.12.1.1.1.1 |
vpwrRingerParameterAdminStateThis parameter allows selecting ringer A or Ringer B as the active ringer.rw Enumeration .1.3.6.1.4.1.13858.12.1.1.1.2 |
vpwrRingerParameterAcVoltagerw INTEGER (7000 .. 11000) UNITS " *.01 Volts" .1.3.6.1.4.1.13858.12.1.1.1.3 |
vpwrRingerParameterDcVoltagerw INTEGER (0 .. 5600 ) UNITS " *.01 Volts" .1.3.6.1.4.1.13858.12.1.1.1.4 |
vpwrRingerParameterFrequencyrw INTEGER (17 .. 50) UNITS " Hz" .1.3.6.1.4.1.13858.12.1.1.1.5 |
vpwrRingerNumberPresentThe present number of active alarm conditions.ro Gauge32 .1.3.6.1.4.1.13858.12.1.2 |
vpwrRingerAlarmGroup OBJECT IDENTIFIER .1.3.6.1.4.1.13858.12.2 |
vpwrRingerAlarmaAFailedRinger A Failed OBJECT IDENTIFIER .1.3.6.1.4.1.13858.12.2.1 |
vpwrRingerAlarmAOTempRinger A Heatsink Over-Temperature OBJECT IDENTIFIER .1.3.6.1.4.1.13858.12.2.2 |
vpwrRingerAlarmAOCurrentRinger A Over-Current protection OBJECT IDENTIFIER .1.3.6.1.4.1.13858.12.2.3 |
vpwrRingerAlarmaBFailedRinger A Failed OBJECT IDENTIFIER .1.3.6.1.4.1.13858.12.2.4 |
vpwrRingerAlarmBOverTempRinger A Heatsink Over-Temperature OBJECT IDENTIFIER .1.3.6.1.4.1.13858.12.2.5 |
vpwrRingerAlarmBOverCurrentRinger A Over-Current protection OBJECT IDENTIFIER .1.3.6.1.4.1.13858.12.2.6 |
vpwrRingerTestGroup OBJECT IDENTIFIER .1.3.6.1.4.1.13858.12.3 |
vpwrDcPowerDcDcConverter OBJECT IDENTIFIER .1.3.6.1.4.1.13858.13 |
vpwrDcDcConverterConfigGroup OBJECT IDENTIFIER .1.3.6.1.4.1.13858.13.1 |
vpwrDcDcConverterAlarmGroup OBJECT IDENTIFIER .1.3.6.1.4.1.13858.13.2 |
vpwrDcDcConverterTestGroup OBJECT IDENTIFIER .1.3.6.1.4.1.13858.13.3 |
vpwrDcPowerDcAcInverter OBJECT IDENTIFIER .1.3.6.1.4.1.13858.14 |
vpwrDcAcInverterConfigGroup OBJECT IDENTIFIER .1.3.6.1.4.1.13858.14.1 |
vpwrDcAcInverterAlarmGroup OBJECT IDENTIFIER .1.3.6.1.4.1.13858.14.2 |
vpwrDcAcInverterTestGroup OBJECT IDENTIFIER .1.3.6.1.4.1.13858.14.3 |
vpwrDcPowerBayController OBJECT IDENTIFIER .1.3.6.1.4.1.13858.15 |
vpwrDcPowerIoModule OBJECT IDENTIFIER .1.3.6.1.4.1.13858.16 |
vpwrIoModuleConfigGroup OBJECT IDENTIFIER .1.3.6.1.4.1.13858.16.1 |
vpwrIoModuleAlarmGroup OBJECT IDENTIFIER .1.3.6.1.4.1.13858.16.2 |
vpwrIoModuleTestGroup OBJECT IDENTIFIER .1.3.6.1.4.1.13858.16.3 |
vpwrDcPowerDist OBJECT IDENTIFIER .1.3.6.1.4.1.13858.17 |
vpwrDcPowerTrio OBJECT IDENTIFIER .1.3.6.1.4.1.13858.18 |