ELTEK-BC2000-DC-POWER-MIB
AI MIB Summary
The ELTEK-BC2000-DC-POWER-MIB provides SNMP access to Eltek BC2000 DC power controllers for monitoring critical power infrastructure metrics, including input/output voltages, current levels, battery status, and system alarms. This module enables granular visibility into DC power supply health and performance parameters essential for maintaining telecommunications and data center power redundancy.
SNMP access to Eltek DC Power systems through the BC2000 controller.
Main OID:
eltek.1.3.6.1.4.1.13858
384
Objects
Active
Status
3
Dependencies
Imported Objects
Objects
384 total| Object Name |
|---|
eltekSNMP access to Eltek DC Power systems through the BC2000 controller. MODULE-IDENTITY .1.3.6.1.4.1.13858 |
vpwrDcPowerSystem OBJECT IDENTIFIER .1.3.6.1.4.1.13858.2 |
vpwrSystemIdentGroup OBJECT IDENTIFIER .1.3.6.1.4.1.13858.2.1 |
vpwrIdentManufacturerThe name of the DC Power manufacturer.ro DisplayString .1.3.6.1.4.1.13858.2.1.1 |
vpwrIdentModelThe DC Power Model designation.ro DisplayString .1.3.6.1.4.1.13858.2.1.2 |
vpwrIdentControllerVersionThe hardware/firmware version(s). This variable may or may not have the same value as vpwrIdentAgentSoftwareVersion.ro DisplayString .1.3.6.1.4.1.13858.2.1.3 |
vpwrIdentAgentSoftwareVersionThe SNMP agent software version. This variable may or may not have the same value as vpwrIdentControllerVersion.ro DisplayString .1.3.6.1.4.1.13858.2.1.4 |
vpwrIdentNameA string identifying the system. This object should be set by the administrator.rw DisplayString .1.3.6.1.4.1.13858.2.1.5 |
vpwrSystemIdentTableThis table describes shelves and modules that make up the sysetm. SEQUENCE OF VpwrSystemIdentEntry .1.3.6.1.4.1.13858.2.1.6 |
vpwrSystemIdentEntryAn entry containing information applicable to a particular alarm. VpwrSystemIdentEntry .1.3.6.1.4.1.13858.2.1.6.1 |
vpwrBayIndexIdentifies shelf number that this module belongs to. The possible values are 1 through 16 limited by vpwrSystemShelfCapacity.ro PositiveInteger .1.3.6.1.4.1.13858.2.1.6.1.1 |
vpwrModuleIndexThis object identifies the module by its position in the shelf. Module numbering is left to right starting with module 1. So, the module in the first slot has an index of 1, the next module is 2 and so on.ro PositiveInteger .1.3.6.1.4.1.13858.2.1.6.1.2 |
vpwrModuleOIDIt indicates the type of the module by specifiying its OIDro OBJECT IDENTIFIER .1.3.6.1.4.1.13858.2.1.6.1.3 |
vpwrModuleCurrentThe meaning of this object depends upon the module type which is indicated by vpwrModuleOID as follows - Current for Rectifier module in centiamps. - Not Applicable for LVD modulero INTEGER .1.3.6.1.4.1.13858.2.1.6.1.4 |
vpwrModuleOperStatusThis object indicates current over all status of the module.ro Enumeration .1.3.6.1.4.1.13858.2.1.6.1.5 |
vpwrModuleCapacityThe meaning of this object depends upon the module type which is indicated by vpwrModuleOID as follows - Capacity for Rectifier module. - Not Applicable for LVD modulero INTEGER .1.3.6.1.4.1.13858.2.1.6.1.6 |
vpwrSystemConfigGroup OBJECT IDENTIFIER .1.3.6.1.4.1.13858.2.2 |
vpwrSystemTempCompensationThis parameter enables/disables temperature compensation.rw Enumeration .1.3.6.1.4.1.13858.2.2.1 |
vpwrSystemTempCompStartTemperatureThe temperature at which temperature compensation becomes active.rw INTEGER .1.3.6.1.4.1.13858.2.2.2 |
vpwrSystemTempCompStopVoltageWhen temperature compensation is active, vpwrSystemTempCompStopVoltage is the limit to which float voltage will be reduced. For example, to set this voltage to 51.75 volts enter a value of 5175.rw INTEGER UNITS " *.01 Volts" .1.3.6.1.4.1.13858.2.2.3 |
vpwrSystemTempCompensationSlopeThe rate at which float voltage is changed, within the specified limits, when temperature compensation is active.rw INTEGER .1.3.6.1.4.1.13858.2.2.4 |
vpwrSystemThermalSenseTypeThis parameter selects the temperature sensing point for temperature compensation (in)activation.rw Enumeration .1.3.6.1.4.1.13858.2.2.5 |
vpwrSystemHVAlarmSetpointSystem High voltage alarm voltage setting.rw INTEGER UNITS " *.01 Volts" .1.3.6.1.4.1.13858.2.2.6 |
vpwrSystemBDAlarmSetpointSystem Battery Discharge voltage setting.rw INTEGER UNITS " *.01 Volts" .1.3.6.1.4.1.13858.2.2.7 |
vpwrSystemInternalTempLThresholdTemperature value at which temperature compensation inactive (clear) trap would be sent if temperature compensation was active when this value is reached.rw INTEGER UNITS "degrees Centigrade" .1.3.6.1.4.1.13858.2.2.8 |
vpwrSystemInternalTempUThresholdTemperature value at which temperature compensation active (set) trap would be sent.rw INTEGER UNITS "degrees Centigrade" .1.3.6.1.4.1.13858.2.2.9 |
vpwrSystemParameterGroup OBJECT IDENTIFIER .1.3.6.1.4.1.13858.2.3 |
vpwrSystemShelfCapacityIt describes the maximum number of shelves that can/are controlled by the controller. Each shelf is uniquely numbered in the range from 1 to vpwrShelfCapacity.ro INTEGER .1.3.6.1.4.1.13858.2.3.1 |
vpwrSystemVoltageThe current system voltage.ro INTEGER UNITS " *.01 Volts" .1.3.6.1.4.1.13858.2.3.2 |
vpwrSystemCurrentThe current system current.ro INTEGER UNITS " Amperes" .1.3.6.1.4.1.13858.2.3.3 |
vpwrSystemControllerStateCurrent System state as shown on the enhanced display.ro Enumeration .1.3.6.1.4.1.13858.2.3.4 |
vpwrSystemInternalTemperatureThe current controller internal temperature.ro INTEGER UNITS "degrees Centigrade" .1.3.6.1.4.1.13858.2.3.5 |
vpwrSystemTempCompensationStateActive or Inactive. Applicable only if temperature compensation is enabled. This means that the controller is temperature compensating the float voltage.ro Enumeration .1.3.6.1.4.1.13858.2.3.6 |
vpwrSystemTypeThis parameter describes the type of the system being managed. This object is set by Eltek Valere Inc.ro Enumeration .1.3.6.1.4.1.13858.2.3.7 |
vpwrSystemCumulativeUpTimeThis parameter describes the cumulative runtime in seconds of the Eltek Valere controller.ro Gauge .1.3.6.1.4.1.13858.2.3.8 |
vpwrSystemBatteryRemainingTimeThis parameter describes the remaining battery capacity based upon installed battery capacity and plant load. This number would change as the SOC parameters of the batteries changes.ro PositiveInteger UNITS "Hours" .1.3.6.1.4.1.13858.2.3.9 |
vpwrSystemPanelIdentGroup OBJECT IDENTIFIER .1.3.6.1.4.1.13858.2.4 |
vpwrPanelStatusTableThis table describes shelves and modules that make up the panels. SEQUENCE OF VpwrPanelStatusEntrySEQ .1.3.6.1.4.1.13858.2.4.1 |
vpwrPanelStatusAn entry containing information applicable to a particular panel making up the system. VpwrPanelStatusEntrySEQ .1.3.6.1.4.1.13858.2.4.1.1 |
vpwrPanelStatusIndexIdentifies panel number that this module belongs to. The possible values are 1 through 8, starting from the top.ro PositiveInteger .1.3.6.1.4.1.13858.2.4.1.1.1 |
vpwrPanelStatusModuleIndexThis object identifies the module within the panel. The orentation of modules within the panel is mappable.ro PositiveInteger .1.3.6.1.4.1.13858.2.4.1.1.2 |
vpwrPanelStatusModuleOIDThe module OID.ro OBJECT IDENTIFIER .1.3.6.1.4.1.13858.2.4.1.1.3 |
vpwrPanelStatusModuleCurrentThe current measured by the device (if applicable). LVD current reported in deciAmps.ro INTEGER .1.3.6.1.4.1.13858.2.4.1.1.4 |
vpwrpanelStatusModuleOperStatusThis object indicates current over all status of the module.ro Enumeration .1.3.6.1.4.1.13858.2.4.1.1.5 |
vpwrPanelStatusModuleCapacityThe maximum capacity of the module (if applicable).ro INTEGER .1.3.6.1.4.1.13858.2.4.1.1.6 |
vpwrPanelIdentTableThis table describes shelves and modules that make up the panels. SEQUENCE OF VpwrPanelIdentEntrySEQ .1.3.6.1.4.1.13858.2.4.2 |
vpwrPanelIdentEntryAn entry containing information applicable to a particular panel making up the system. VpwrPanelIdentEntrySEQ .1.3.6.1.4.1.13858.2.4.2.1 |
vpwrPanelIndexIdentifies panel number that this module belongs to. The possible values are 1 through 8, starting from the top.ro PositiveInteger .1.3.6.1.4.1.13858.2.4.2.1.1 |
vpwrPanelModuleIndexThis object identifies the module within the panel. The orentation of modules within the panel is mappable.ro PositiveInteger .1.3.6.1.4.1.13858.2.4.2.1.2 |
vpwrPanelModuleSerNumThe module serial number.ro OBJECT IDENTIFIER .1.3.6.1.4.1.13858.2.4.2.1.3 |
vpwrPanelModuleModelNameThe model name of the device.ro OBJECT IDENTIFIER .1.3.6.1.4.1.13858.2.4.2.1.4 |
vpwrPanelModuleFWVerThe module firmware version.ro OBJECT IDENTIFIER .1.3.6.1.4.1.13858.2.4.2.1.5 |
vpwrPanelModuleTestDateThe manufacturing test date.ro INTEGER .1.3.6.1.4.1.13858.2.4.2.1.6 |
vpwrSystemHistoryGroup OBJECT IDENTIFIER .1.3.6.1.4.1.13858.2.5 |
vpwrSysHistAlarmTableThis table provides a list of most recent alarms. SEQUENCE OF VpwrSysHistAlarmEntry .1.3.6.1.4.1.13858.2.5.1 |
vpwrSysHistAlarmEntryAn entry describing an alarm. VpwrSysHistAlarmEntry .1.3.6.1.4.1.13858.2.5.1.1 |
vpwrSysHistAlarmIndexAlarm index.ro PositiveInteger .1.3.6.1.4.1.13858.2.5.1.1.1 |
vpwrSysHistAlarmDescriptionAlarm description including time stamp.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.13858.2.5.1.1.2 |
vpwrSystemAlarmGroup OBJECT IDENTIFIER .1.3.6.1.4.1.13858.2.6 |
vpwrSystemAlarmMajorIndicates a Major Alarm exists on the system.ro INTEGER .1.3.6.1.4.1.13858.2.6.1 |
vpwrSystemAlarmMinorIndicates a Minor Alarm exists on the system.ro INTEGER .1.3.6.1.4.1.13858.2.6.2 |
vpwrSystemACFailAlarmOne or more rectifiers have reported AC failure. If system is configured to report rectifier communication failure as AC fail this alarm will report.ro INTEGER .1.3.6.1.4.1.13858.2.6.3 |
vpwrSystemHighVoltageWarningAlarmSystem has exceeded High Voltage Warning Setpoint. Check for high voltage on system bus.ro INTEGER .1.3.6.1.4.1.13858.2.6.4 |
vpwrSystemHighVoltageShutdownAlarmOne or more rectifiers have shut down due to high voltage present on output. Check bus voltage and reseat rectifiers that have indicated this problem.ro INTEGER .1.3.6.1.4.1.13858.2.6.5 |
vpwrSystemBatteryonDischargeAlarmSystem voltage has currently dropped below the alarm setpoint. This may be due to battery testing or AC failure.ro Enumeration .1.3.6.1.4.1.13858.2.6.6 |
vpwrSystemLowVoltageWarningAlarmSystem Voltage has dropped below setpoint for Low Voltage Alarm. This may occur during battery testing or AC failurero Enumeration .1.3.6.1.4.1.13858.2.6.7 |
vpwrSystemLVDOpenAlarmOne or more contactors have opened. This occurs normally during system power on. If it occurs during operation this may indicate system is operating below LVD disconnect voltage.ro Gauge .1.3.6.1.4.1.13858.2.6.8 |
vpwrSystemDistributionAlarmOne or more distribution alarm inputs are reporting an error condition. Check source of alarm and correct issue.ro PositiveInteger .1.3.6.1.4.1.13858.2.6.9 |
vpwrSystemAuxiliaryAlarmOne or more Auxliary alarm inputs are reporting an error condition. Check source of alarm and correct issue.ro PositiveInteger .1.3.6.1.4.1.13858.2.6.10 |
vpwrSystemRedundantCapAlarmThe system load has exceeded the requirements for redundancy. This may be a temporary system overload condition or caused by a rectifier alarm.ro PositiveInteger .1.3.6.1.4.1.13858.2.6.11 |
vpwrSystemRectIShareAlarmOne or more rectifiers are reporting a mismatch in current. This may be due to mismatched rectifier models or one or more rectifiers not current sharingro PositiveInteger .1.3.6.1.4.1.13858.2.6.12 |
vpwrSystemSnglRectAlarmro PositiveInteger .1.3.6.1.4.1.13858.2.6.13 |
vpwrSystemMultRectAlarmro PositiveInteger .1.3.6.1.4.1.13858.2.6.14 |
vpwrSystemModlCommAlarmro PositiveInteger -- .1.3.6.1.4.1.13858.2.6.15 |
vpwrSystemOverTempAlarmro PositiveInteger .1.3.6.1.4.1.13858.2.6.16 |
vpwrSystemThermRAAlarmThermal Runaway has occurred on system. Check temperature inputs.ro PositiveInteger .1.3.6.1.4.1.13858.2.6.17 |
vpwrSystemBDTAlarmSystem has entered Battery Discharge Test modero PositiveInteger .1.3.6.1.4.1.13858.2.6.18 |
vpwrSystemRectUVAlarmRectifier output has dropped 1V below Low Voltage Alarm setpointro PositiveInteger .1.3.6.1.4.1.13858.2.6.19 |
vpwrSystemMultRectUVAlarmro PositiveInteger .1.3.6.1.4.1.13858.2.6.20 |
vpwrSystemSnglRngrAlarmro PositiveInteger .1.3.6.1.4.1.13858.2.6.21 |
vpwrSystemMultRngrAlarmro PositiveInteger .1.3.6.1.4.1.13858.2.6.22 |
vpwrSystemTempProbeAlarmTemp probe input missing or failedro PositiveInteger .1.3.6.1.4.1.13858.2.6.23 |
vpwrSystemRngrCommAlarmRinger Module has stopped communicating with Controller.ro PositiveInteger .1.3.6.1.4.1.13858.2.6.24 |
vpwrSystemDistPMCommAlarmOne or more distribution alarm modules, TRIOs, or PM modules has stopped communicating with Controller.ro PositiveInteger .1.3.6.1.4.1.13858.2.6.25 |
vpwrSystemRectILimitAlarmRectifier has reached current limit setpoint.ro PositiveInteger .1.3.6.1.4.1.13858.2.6.26 |
vpwrSystemMultRectILimitAlarmro PositiveInteger .1.3.6.1.4.1.13858.2.6.27 |
vpwrSystemUnmappedI2CCANAlarmRecheck all I2C and CAN dip switch settings. One or more devices in conflict.ro PositiveInteger .1.3.6.1.4.1.13858.2.6.28 |
vpwrSystemConfigErrAlarmRecheck all I2C and CAN dip switch settings. One or more devices in conflict.ro PositiveInteger .1.3.6.1.4.1.13858.2.6.29 |
vpwrSystemDispFWAlarmro PositiveInteger .1.3.6.1.4.1.13858.2.6.30 |
vpwrSystemUndefinedAlarmro PositiveInteger .1.3.6.1.4.1.13858.2.6.31 |
vpwrDcPowerRectifier OBJECT IDENTIFIER .1.3.6.1.4.1.13858.3 |
vpwrRectifierConfigGroup OBJECT IDENTIFIER .1.3.6.1.4.1.13858.3.1 |
vpwrRectifierFVSetpointSystem Float Voltage settingrw INTEGER UNITS " *.01 Volts" .1.3.6.1.4.1.13858.3.1.1 |
vpwrRectifierHVSDSetpointSystem High Voltage Shutdown voltage settingrw INTEGER UNITS " *.01 Volts" .1.3.6.1.4.1.13858.3.1.2 |
vpwrRectifierCurrentLimitAdminStateThis parameter allows enabling or rectifier current limitrw Enumeration .1.3.6.1.4.1.13858.3.1.3 |
vpwrRectifierCurrentLimitRectifier current limit setpointrw INTEGER .1.3.6.1.4.1.13858.3.1.4 |
vpwrRectifierFallbackAdminStateEnables Rectifier to use Fallback Voltage when it loses communication with the controller. This applies to all rectifiers.rw GenericEnableDisableTC .1.3.6.1.4.1.13858.3.1.5 |
vpwrRectifierFallbackVoltageFallback Voltage setpoint to use when rectifier loses communication with the controller. This applies to all rectifiers.rw INTEGER UNITS " *.01 Volts" .1.3.6.1.4.1.13858.3.1.6 |
vpwrRectifierAlarmGroup OBJECT IDENTIFIER .1.3.6.1.4.1.13858.3.2 |
vpwrRectAlarmDCFail OBJECT IDENTIFIER .1.3.6.1.4.1.13858.3.2.1 |
vpwrRectAlarmBoostFail OBJECT IDENTIFIER .1.3.6.1.4.1.13858.3.2.2 |
vpwrRectAlarmACFail OBJECT IDENTIFIER .1.3.6.1.4.1.13858.3.2.3 |
vpwrRectAlarmHVSD OBJECT IDENTIFIER .1.3.6.1.4.1.13858.3.2.4 |
vpwrRectAlarmFanFail OBJECT IDENTIFIER .1.3.6.1.4.1.13858.3.2.5 |
vpwrRectAlarmAmbTemp OBJECT IDENTIFIER .1.3.6.1.4.1.13858.3.2.6 |
vpwrRectAlarmIntTemp OBJECT IDENTIFIER .1.3.6.1.4.1.13858.3.2.7 |
vpwrRectAlarmIShare OBJECT IDENTIFIER .1.3.6.1.4.1.13858.3.2.8 |
vpwrRectAlarmUV OBJECT IDENTIFIER .1.3.6.1.4.1.13858.3.2.9 |
vpwrRectAlarmLowVoltage OBJECT IDENTIFIER .1.3.6.1.4.1.13858.3.2.10 |
vpwrRectAlarmReserved OBJECT IDENTIFIER .1.3.6.1.4.1.13858.3.2.11 |
vpwrRectAlarmDCEnable OBJECT IDENTIFIER .1.3.6.1.4.1.13858.3.2.12 |
vpwrRectAlarmRemoteShutdown OBJECT IDENTIFIER .1.3.6.1.4.1.13858.3.2.13 |
vpwrRectAlarmModDisableShutdown OBJECT IDENTIFIER .1.3.6.1.4.1.13858.3.2.14 |
vpwrRectAlarmShortPinShutdown OBJECT IDENTIFIER .1.3.6.1.4.1.13858.3.2.15 |
vpwrRectAlarmBoostComm OBJECT IDENTIFIER .1.3.6.1.4.1.13858.3.2.16 |
vpwrDcPowerLvd OBJECT IDENTIFIER .1.3.6.1.4.1.13858.4 |
vpwrLvdConfigGroup OBJECT IDENTIFIER .1.3.6.1.4.1.13858.4.1 |
vpwrLvdWarningSetpointLVD Warning voltage setpoint.rw INTEGER UNITS " * .01 Volts" .1.3.6.1.4.1.13858.4.1.1 |
vpwrLvdDisconnectSetpointLVD disconnect voltage setpoint.rw INTEGER UNITS " *.01 Volts" .1.3.6.1.4.1.13858.4.1.2 |
vpwrLvdReconnectSetpointLVD Reconnect voltage setpoint.rw INTEGER UNITS " *.01 Volts" .1.3.6.1.4.1.13858.4.1.3 |
vpwrLvdReconnectDelayTimerThe delay time, in seconds, before LVD is reconnectedro INTEGER .1.3.6.1.4.1.13858.4.1.4 |
vpwrLvd2DisconnectSetpointLVD disconnect voltage setpoint.rw INTEGER UNITS " *.01 Volts" .1.3.6.1.4.1.13858.4.1.7 |
vpwrLvd2ReconnectSetpointLVD Reconnect voltage setpoint.rw INTEGER UNITS " *.01 Volts" .1.3.6.1.4.1.13858.4.1.8 |
vpwrLvd2ReconnectDelayTimerThe delay time, in seconds, before LVD is reconnectedro INTEGER .1.3.6.1.4.1.13858.4.1.9 |
vpwrLvd3DisconnectSetpointLVD disconnect voltage setpoint.rw INTEGER UNITS " *.01 Volts" .1.3.6.1.4.1.13858.4.1.11 |
vpwrLvd3ReconnectSetpointLVD Reconnect voltage setpoint.rw INTEGER UNITS " *.01 Volts" .1.3.6.1.4.1.13858.4.1.12 |
vpwrLvd3ReconnectDelayTimerThe delay time, in seconds, before LVD is reconnectedro INTEGER .1.3.6.1.4.1.13858.4.1.13 |
vpwrLvd4DisconnectSetpointLVD disconnect voltage setpoint.rw INTEGER UNITS " *.01 Volts" .1.3.6.1.4.1.13858.4.1.15 |
vpwrLvd4ReconnectSetpointLVD Reconnect voltage setpoint.rw INTEGER UNITS " *.01 Volts" .1.3.6.1.4.1.13858.4.1.16 |
vpwrLvd4ReconnectDelayTimerThe delay time, in seconds, before LVD is reconnectedro INTEGER .1.3.6.1.4.1.13858.4.1.17 |
vpwrDCPowerLampTestLamp Test for modulesrw Enumeration .1.3.6.1.4.1.13858.5 |
vpwrDcPowerModuleIdent OBJECT IDENTIFIER .1.3.6.1.4.1.13858.6 |
vpwrDcPowerModuleIdentTableThis table describes power modules that make up the system. SEQUENCE OF DCPowerModuleIdentEntrySEQ .1.3.6.1.4.1.13858.6.1 |
vpwrDcPowerModuleIdentEntryAn entry containing information applicable to a power module. DCPowerModuleIdentEntrySEQ .1.3.6.1.4.1.13858.6.1.1 |
vpwrBayIndex1Identifies shelf number that this module belongs to. The possible values are 1 through 2, starting from the top.ro PositiveInteger .1.3.6.1.4.1.13858.6.1.1.1 |
vpwrDCModuleIndexThis object identifies the module within the shelf.ro PositiveInteger .1.3.6.1.4.1.13858.6.1.1.2 |
vpwrModuleSerialNumberSerial Number of the modulero DisplayString (SNMPv2-TC) .1.3.6.1.4.1.13858.6.1.1.3 |
vpwrModuleModelNumberModel Number of the module.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.13858.6.1.1.4 |
vpwrModuleFwVersionFirmware version of the module.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.13858.6.1.1.5 |
vpwrModuleTestDateDate when the module was last tested.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.13858.6.1.1.6 |
vpwrModuleOperHoursCumulative Operating Hours.ro Counter32 .1.3.6.1.4.1.13858.6.1.1.7 |
vpwrDcPowerBatteryGroup OBJECT IDENTIFIER .1.3.6.1.4.1.13858.7 |
vpwrBatteryTempGroup OBJECT IDENTIFIER .1.3.6.1.4.1.13858.7.1 |
vpwrBatteryTempTableThis table describes battery temperature probes. SEQUENCE OF VpwrBatteryTempEntry .1.3.6.1.4.1.13858.7.1.1 |
vpwrBatteryTempEntryAn entry containing information applicable to a particular temperature probe. VpwrBatteryTempEntry .1.3.6.1.4.1.13858.7.1.1.1 |
vpwrBatteryTempIndexIndex into temperature tablero INTEGER .1.3.6.1.4.1.13858.7.1.1.1.1 |
vpwrBatteryTempNameA string identifying probe location.rw DisplayString .1.3.6.1.4.1.13858.7.1.1.1.2 |
vpwrBatteryTempCurrent temperature as recorded by the probe.ro SysInputValue UNITS "degrees Celsius" .1.3.6.1.4.1.13858.7.1.1.1.3 |
vpwrBatteryTempLThresholdTemperature value at which a clear trap would be sent. All three battery temperature must be at or below this value to trigger this trap.rw INTEGER UNITS "degrees Celsius" .1.3.6.1.4.1.13858.7.1.2 |
vpwrBatteryTempUThresholdTemperature value at which a set trap would be sent. Any one of the three battery temperatures at or exceeding this limit would trigger the trap.rw INTEGER UNITS "degrees Celsius" .1.3.6.1.4.1.13858.7.1.3 |
batteryTempCompensationThis parameter enables/disables temperature compensation.rw Enumeration .1.3.6.1.4.1.13858.7.1.4 |
batteryTempCompHighStartTemperatureThe temperature at which temperature compensation becomes active.rw INTEGER .1.3.6.1.4.1.13858.7.1.5 |
batteryTempCompHighStopVoltageWhen temperature compensation is active, batteryTempCompHighStopVoltage is the limit to which float voltage will be reduced. For example, to set this voltage to 51.75 volts enter a value of 5175.rw INTEGER UNITS " *.01 Volts" .1.3.6.1.4.1.13858.7.1.6 |
batteryTempCompHighSlopeThe rate at which float voltage is changed, within the specified limits, when temperature compensation is active.rw INTEGER .1.3.6.1.4.1.13858.7.1.7 |
batteryTempCompLowStartTemperatureThe temperature at which temperature compensation becomes active.rw INTEGER UNITS "degrees Celsius" .1.3.6.1.4.1.13858.7.1.8 |
batteryTempCompLowStopVoltageWhen temperature compensation is active, batteryTempCompLowStopVoltage is the limit to which float voltage will be reduced. For example, to set this voltage to 51.75 volts enter a value of 5175.rw INTEGER UNITS " *.01 Volts" .1.3.6.1.4.1.13858.7.1.9 |
batteryTempCompLowSlopeThe rate at which float voltage is changed, within the specified limits, when temperature compensation is active.rw INTEGER .1.3.6.1.4.1.13858.7.1.10 |
batteryTempCompRunawayTemperatureThe temperature at which system voltage will be set to batteryTempCompRunawayStopVoltage.rw INTEGER .1.3.6.1.4.1.13858.7.1.11 |
batteryTempCompRunawayStopVoltageWhen temperature compensation is enabled, float voltage will be reduced to batteryTempCompRunawayStopVoltage if temperature reaches batteryTempCompRunawayTemperature.rw INTEGER UNITS " *.01 Volts" .1.3.6.1.4.1.13858.7.1.12 |
batteryTempCompSenseSourceThis parameter selects the temperature sensing point for temperature compensation (in)activation.rw Enumeration .1.3.6.1.4.1.13858.7.1.13 |
batteryTempCompRunawayStateThis parameter selects the temperature sensing point for temperature compensation (in)activation.ro Enumeration .1.3.6.1.4.1.13858.7.1.14 |
vpwrBatteryCurrentGroup OBJECT IDENTIFIER .1.3.6.1.4.1.13858.7.2 |
vpwrBatteryCurrentLimitAdminStateThis parameter allows enabling or disabling battery current limit.rw Enumeration .1.3.6.1.4.1.13858.7.2.1 |
vpwrBatteryCurrentLimitrw INTEGER .1.3.6.1.4.1.13858.7.2.2 |
vpwrBatteryCurrentBattery currentro INTEGER UNITS "Ampere" .1.3.6.1.4.1.13858.7.2.3 |
vpwrBatteryBoostGroup OBJECT IDENTIFIER .1.3.6.1.4.1.13858.7.3 |
vpwrBoostAdminStateThis parameter allows enabling or disabling boost.rw Enumeration .1.3.6.1.4.1.13858.7.3.1 |
vpwrBoostVoltagerw INTEGER UNITS " *.01 Volts" .1.3.6.1.4.1.13858.7.3.2 |
vpwrBoostDurationNumber of seconds for boost.rw INTEGER .1.3.6.1.4.1.13858.7.3.3 |
vpwrBoostOperStateThis parameter allows starting or stopping boost if it is enabled.rw Enumeration .1.3.6.1.4.1.13858.7.3.4 |
vpwrBatteryDischargeTestGroup OBJECT IDENTIFIER .1.3.6.1.4.1.13858.7.4 |
vpwrBDTAdminStateEnable / Disable Battery Discharge Test execution.rw Enumeration .1.3.6.1.4.1.13858.7.4.1 |
vpwrBDTDurationBDT Duration Setpoint.ro INTEGER .1.3.6.1.4.1.13858.7.4.2 |
vpwrBDTAlarmVoltageBDT Alarm Voltage Setpoint.rw INTEGER UNITS " *.01 Volts" .1.3.6.1.4.1.13858.7.4.3 |
vpwrBDTAbortVoltageBDT Abort Voltage Setpoint.rw INTEGER UNITS " *.01 Volts" .1.3.6.1.4.1.13858.7.4.4 |
vpwrBDTAlarmCoefficientDeprecated. Always returns 1ro INTEGER UNITS "None" .1.3.6.1.4.1.13858.7.4.5 |
vpwrBDTOperStateStart/Stop Battery Discharge Test execution.ro Enumeration .1.3.6.1.4.1.13858.7.4.6 |
vpwrBDTClearAlarmClears any active BDT alarm.ro Enumeration .1.3.6.1.4.1.13858.7.4.7 |
vpwrBDTActualTimeActual BDT runtime in minutes.ro INTEGER UNITS "minutes" .1.3.6.1.4.1.13858.7.4.8 |
vpwrBDTAlarmDelayDelay, in minutes, before checking and raising BDT alarm. Test: Plant Voltage <= BDTAlarmVoltagero INTEGER UNITS "minutes" .1.3.6.1.4.1.13858.7.4.9 |
vpwrBDTResultResults of BDT.ro BDTResultTC .1.3.6.1.4.1.13858.7.4.10 |
vpwrBDTAutoAdminStateEnable /Disable Battery Discharge Test data collection upon detecting AC Fail condition.rw Enumeration .1.3.6.1.4.1.13858.7.4.11 |
vpwrBDTHistTableThis table provides results of past BDT test. SEQUENCE OF VpwrBDTHistEntry .1.3.6.1.4.1.13858.7.4.12 |
vpwrBDTHistEntryAn entry containing information applicable to a particular BDT History. VpwrBDTHistEntry .1.3.6.1.4.1.13858.7.4.12.1 |
vpwrBDTHistIndexBDT History index.ro PositiveInteger .1.3.6.1.4.1.13858.7.4.12.1.1 |
vpwrBDTHistDateTimeBDT run date as yr-mm-dd hh:mmro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.13858.7.4.12.1.2 |
vpwrBDTHistDurationBDT duration at the time this test was run.ro PositiveInteger UNITS "Minutes" .1.3.6.1.4.1.13858.7.4.12.1.3 |
vpwrBDTHistAlarmVoltageBDT Alarm Voltage setpoint when this test was run.rw PositiveInteger UNITS " *.01 Volts" .1.3.6.1.4.1.13858.7.4.12.1.4 |
vpwrBDTHistAbortVoltageBDT Abort Voltage setpoint when this test was run.ro PositiveInteger UNITS " *.01 Volts" .1.3.6.1.4.1.13858.7.4.12.1.5 |
vpwrBDTHistStartMethodHow Battery Discharge Test was started.ro BDTStartSourceTC .1.3.6.1.4.1.13858.7.4.12.1.6 |
vpwrBDTHistResultResults of BDT.ro BDTResultTC .1.3.6.1.4.1.13858.7.4.12.1.7 |
vpwrBDTHistActualTimeActual BDT runtime in minutes.ro PositiveInteger UNITS "minutes" .1.3.6.1.4.1.13858.7.4.12.1.8 |
vpwrBDTHistStartVoltagePlant Voltage at the time the BDT was started.ro PositiveInteger UNITS " *.01 Volts" .1.3.6.1.4.1.13858.7.4.12.1.9 |
vpwrBDTHistEndVoltagePlant Voltage at the time the BDT was completed.ro PositiveInteger UNITS " *.01 Volts" .1.3.6.1.4.1.13858.7.4.12.1.10 |
vpwrBDTSchedTableThis table provides the list of the 12 BDTs that can be scheduled. Need to set date(month and day) and time (hh and minutes) when the test should be started. SEQUENCE OF VpwrBDTSchedEntry .1.3.6.1.4.1.13858.7.4.13 |
vpwrBDTSchedEntryAn entry describing an alarm. VpwrBDTSchedEntry .1.3.6.1.4.1.13858.7.4.13.1 |
vpwrBDTSchedIndexBDT Sched index.ro PositiveInteger .1.3.6.1.4.1.13858.7.4.13.1.1 |
vpwrBDTSchedDay1 to 28,29,30 or 31 depending upon the monthrw PositiveInteger .1.3.6.1.4.1.13858.7.4.13.1.2 |
vpwrBDTSchedMonthrange 1 to 12rw PositiveInteger .1.3.6.1.4.1.13858.7.4.13.1.3 |
vpwrBDTSchedHourrange 0 to 23rw PositiveInteger .1.3.6.1.4.1.13858.7.4.13.1.4 |
vpwrBDTSchedMinuterange 0 to 59rw PositiveInteger .1.3.6.1.4.1.13858.7.4.13.1.5 |
vpwrDcPowerAlarmGroup OBJECT IDENTIFIER .1.3.6.1.4.1.13858.8 |
vpwrAlarmsPresentThe present number of active alarm conditions.ro Gauge32 .1.3.6.1.4.1.13858.8.1 |
vpwrAlarmTableA list of alarm table entries. The table contains zero, one, or multiple rows at any time depending upon the number of alarm conditions in effect. The table is initially empty at agent startup. The agent creates a row in the table each time a condition is detected and deletes that row when that condition no longer exists. The vpwrAlarmIndex, for each type of module starts at 1 and is limited by the total number of alarms that can be generated by the module. Alarms are named by an AutonomousType (OBJECT IDENTIFIER), vpwrAlarmDescr, to allow a single table to reflect alarms for different types of modules. The number of rows in the table at any given time is reflected by the value of vpwrAlarmsPresent. SEQUENCE OF VpwrAlarmEntrySEQ .1.3.6.1.4.1.13858.8.2 |
vpwrAlarmEntryAn entry containing information applicable to a particular alarm. VpwrAlarmEntrySEQ .1.3.6.1.4.1.13858.8.2.1 |
vpwrAlarmIndexIdentifies the alarm associated with the module. It is unique on per module type basis. For example, multiple rectifiers can have the same alarm and therefore same vpwrAlarmIndex active at any one time.ro PositiveInteger .1.3.6.1.4.1.13858.8.2.1.1 |
vpwrAlarmDescrA reference to an alarm description object. The object referenced should not be accessible, but rather be used to provide a unique description of the alarm condition.ro AutonomousType (SNMPv2-TC) .1.3.6.1.4.1.13858.8.2.1.2 |
vpwrAlarmTimeThe value of sysUpTime when the alarm condition was detected.ro TimeStamp (SNMPv2-TC) .1.3.6.1.4.1.13858.8.2.1.3 |
sysAlarmConfigTableThis table describes system alarm configuration and current status. SEQUENCE OF SysAlarmConfigEntry .1.3.6.1.4.1.13858.8.3 |
sysAlarmConfigEntryAn entry containing information applicable to a particular system alarm. SysAlarmConfigEntry .1.3.6.1.4.1.13858.8.3.1 |
sysAlarmIndexIndex into system alarm tablero INTEGER .1.3.6.1.4.1.13858.8.3.1.1 |
sysAlarmDefaultNameDefault alarm name.ro DisplayString .1.3.6.1.4.1.13858.8.3.1.2 |
sysAlarmCustomNameA custom alarm name.rw DisplayString .1.3.6.1.4.1.13858.8.3.1.3 |
sysAlarmSeverityAlarm Severity as denoted by Major and Minor Alarm Maskrw Enumeration .1.3.6.1.4.1.13858.8.3.1.4 |
sysAlarmToRelayMappingNo additional mapping = 0 Map to Relay A = 1 Map to Relay B = 2 Map to Relay C = 4 Map to Relay D = 8 Map to Relay E = 16 Map to Relay F = 32 Map to Relay A and B = (1 + 2) and so on The major/minor classification of alarms automatically associates it with Major/Minor relay. Assigning a null mapping here does not override vpwrPMRelayAlarmSeverity for the alarm. It should be used to define mapping to additional relays.rw DisplayString .1.3.6.1.4.1.13858.8.3.1.5 |
sysAlarmOperStatusIndicates current alarm statusro Enumeration .1.3.6.1.4.1.13858.8.3.1.6 |
sysAlarmComFailStateEnable/Disable generation of comm fail alarm.rw Enumeration .1.3.6.1.4.1.13858.8.4 |
sysAlarmIShareStateEnable/Disable generation of current share alarm.rw Enumeration .1.3.6.1.4.1.13858.8.5 |
sysAlarmRedundancyStateEnable/Disable generation of redundancy alarm.rw Enumeration .1.3.6.1.4.1.13858.8.6 |
sysAlarmComFailToACFailStateEnable/Disable generation of ACF upon Com Failrw Enumeration .1.3.6.1.4.1.13858.8.7 |
vpwrDcPowerSnmpConfig OBJECT IDENTIFIER .1.3.6.1.4.1.13858.9 |
vpwrTrapTableA list of possible trap destinations depending upon the criticality of the trap. SEQUENCE OF VpwrTrapEntry .1.3.6.1.4.1.13858.9.1 |
vpwrTrapEntryAn entry containing information applicable to a particular trap destination. VpwrTrapEntry .1.3.6.1.4.1.13858.9.1.1 |
vpwrTrapIpIndexTrap Entry Indexro INTEGER .1.3.6.1.4.1.13858.9.1.1.1 |
vpwrTrapIpAddressTrap destination IP Addressrw IpAddress .1.3.6.1.4.1.13858.9.1.1.2 |
vpwrTrapCriticalityCriticality of traps sent to this IP Addressrw INTEGER .1.3.6.1.4.1.13858.9.1.1.3 |
vpwrReadCommunityStringThis allows setting password to be able to do Get operationsrw DisplayString .1.3.6.1.4.1.13858.9.2 |
vpwrWriteCommunityStringThis allows setting password to be able to do Get and Set operations. The read-access is not allowed in the actual implementation.rw DisplayString .1.3.6.1.4.1.13858.9.3 |
vpwrTrapCommunityStringThis allows setting community string required for the trap to be accepted at the destination.rw DisplayString .1.3.6.1.4.1.13858.9.4 |
vpwrTrapVersionThis allows setting the version of trap message sent from the systemrw INTEGER .1.3.6.1.4.1.13858.9.5 |
vpwrDcPowerTraps OBJECT IDENTIFIER .1.3.6.1.4.1.13858.10 |
vpwrTrapPowerMajorAlarmMajor Alarm NOTIFICATION-TYPE .1.3.6.1.4.1.13858.10.1 |
vpwrTrapPowerMinorAlarmMinor Alarm NOTIFICATION-TYPE .1.3.6.1.4.1.13858.10.2 |
vpwrTrapACFAlarmAC Fail Alarm NOTIFICATION-TYPE .1.3.6.1.4.1.13858.10.3 |
vpwrTrapHVAlarmHigh Voltage Warning Alarm NOTIFICATION-TYPE .1.3.6.1.4.1.13858.10.4 |
vpwrTrapHVSDAlarmHigh Voltage Shutdown Alarm NOTIFICATION-TYPE .1.3.6.1.4.1.13858.10.5 |
vpwrTrapBDAlarmBattery on Discharge Alarm NOTIFICATION-TYPE .1.3.6.1.4.1.13858.10.6 |
vpwrTrapLVDWarningAlarmLVD Warning Alarm NOTIFICATION-TYPE .1.3.6.1.4.1.13858.10.7 |
vpwrTrapLVDOpenAlarmLVD Open Alarm NOTIFICATION-TYPE .1.3.6.1.4.1.13858.10.8 |
vpwrTrapDistAlarmDistribution Open Alarm NOTIFICATION-TYPE .1.3.6.1.4.1.13858.10.9 |
vpwrTrapAuxAlarmAuxiliary System Alarm NOTIFICATION-TYPE .1.3.6.1.4.1.13858.10.10 |
vpwrTrapSystemRedundancyAlarmSystem Redundant Capacity Alarm NOTIFICATION-TYPE .1.3.6.1.4.1.13858.10.11 |
vpwrTrapIShareAlarmRectifier Current Share Alarm NOTIFICATION-TYPE .1.3.6.1.4.1.13858.10.12 |
vpwrTrapModuleFailAlarmSingle Rectifier Fail Alarm NOTIFICATION-TYPE .1.3.6.1.4.1.13858.10.13 |
vpwrTrapMultipleModuleFailAlarmMultiple Rectifier Fail Alarm NOTIFICATION-TYPE .1.3.6.1.4.1.13858.10.14 |
vpwrTrapModuleCommAlarmPower Module Communication Alarm NOTIFICATION-TYPE .1.3.6.1.4.1.13858.10.15 |
vpwrTrapSystemOverTemperatureAlarmSystem Over Temperature Alarm NOTIFICATION-TYPE .1.3.6.1.4.1.13858.10.16 |
vpwrTrapSystemOKSYSTEM OK - No Active Alarms NOTIFICATION-TYPE .1.3.6.1.4.1.13858.10.17 |
vpwrTrapModuleInsertedA new module has been inserted into the system NOTIFICATION-TYPE .1.3.6.1.4.1.13858.10.18 |
vpwrTrapModuleRemovedA module has been removed from the system NOTIFICATION-TYPE .1.3.6.1.4.1.13858.10.19 |
vpwrTrapThermalCompActiveThermal compensation has become active NOTIFICATION-TYPE .1.3.6.1.4.1.13858.10.20 |
vpwrTrapThermalCompInactiveThermal compensation has been de-activated NOTIFICATION-TYPE .1.3.6.1.4.1.13858.10.21 |
vpwrTrapInternalTempAlarmSet!!! NOT VALID FOR BC2000 CONTROLLER !!! Internal Temperature upper threshold exceeded NOTIFICATION-TYPE .1.3.6.1.4.1.13858.10.22 |
vpwrTrapInternalTempAlarmCleared!!! NOT VALID FOR BC2000 CONTROLLER !!! Internal Temperature within limits NOTIFICATION-TYPE .1.3.6.1.4.1.13858.10.23 |
vpwrTrapBatteryTempAlarmSet!!! NOT VALID FOR BC2000 CONTROLLER !!! At least one Battery Temperature exceeded upper threshold NOTIFICATION-TYPE .1.3.6.1.4.1.13858.10.24 |
vpwrTrapBatteryTempAlarmCleared!!! NOT VALID FOR BC2000 CONTROLLER !!! All Battery Temperatures within limits NOTIFICATION-TYPE .1.3.6.1.4.1.13858.10.25 |
vpwrTrapLoginFail!!! NOT VALID FOR BC2000 CONTROLLER !!! Admin login failed due to wrong username/password NOTIFICATION-TYPE .1.3.6.1.4.1.13858.10.26 |
vpwrTrapLoginSuccess!!! NOT VALID FOR BC2000 CONTROLLER !!! Admin login successful NOTIFICATION-TYPE .1.3.6.1.4.1.13858.10.27 |
vpwrTrapLogout!!! NOT VALID FOR BC2000 CONTROLLER !!! Admin logout NOTIFICATION-TYPE .1.3.6.1.4.1.13858.10.28 |
vpwrTrapAdminPwdChange!!! NOT VALID FOR BC2000 CONTROLLER !!! Config change submitted with invalid access NOTIFICATION-TYPE .1.3.6.1.4.1.13858.10.29 |
vpwrTrapIllegalConfigSubmit!!! NOT VALID FOR BC2000 CONTROLLER !!! Config change submitted with invalid access NOTIFICATION-TYPE .1.3.6.1.4.1.13858.10.30 |
vpwrTrapCfgChange!!! NOT VALID FOR BC2000 CONTROLLER !!! Config change submitted NOTIFICATION-TYPE .1.3.6.1.4.1.13858.10.31 |
vpwrTrapClearEventHistory!!! NOT VALID FOR BC2000 CONTROLLER !!! Clear Event history buffer clear request NOTIFICATION-TYPE .1.3.6.1.4.1.13858.10.32 |
vpwrTrapSwDownloadNoReboot!!! NOT VALID FOR BC2000 CONTROLLER !!! System software upgrade without reboot NOTIFICATION-TYPE .1.3.6.1.4.1.13858.10.33 |
vpwrTrapSwDownloadAndReboot!!! NOT VALID FOR BC2000 CONTROLLER !!! System reboot due to software upgrade NOTIFICATION-TYPE .1.3.6.1.4.1.13858.10.34 |
vpwrTrapSystemClockChange!!! NOT VALID FOR BC2000 CONTROLLER !!! System clock updated NOTIFICATION-TYPE .1.3.6.1.4.1.13858.10.35 |
vpwrTrapModuleAlarm!!! NOT VALID FOR BC2000 CONTROLLER !!! Module Alarm NOTIFICATION-TYPE .1.3.6.1.4.1.13858.10.36 |
vpwrTrapOIDChange!!! NOT VALID FOR BC2000 CONTROLLER !!! Change in OID NOTIFICATION-TYPE .1.3.6.1.4.1.13858.10.37 |
vpwrTrapThermalRunawayThermal Runaway Alarm NOTIFICATION-TYPE .1.3.6.1.4.1.13858.10.38 |
vpwrTrapBatteryDischargeTestAlarmSystem Voltage dropped to BDT Alarm Setpoint NOTIFICATION-TYPE .1.3.6.1.4.1.13858.10.39 |
vpwrTrapBayUnnameAlarm!!! NOT VALID FOR BC2000 CONTROLLER !!! Unassigned Bay Fail Alarm NOTIFICATION-TYPE .1.3.6.1.4.1.13858.10.40 |
vpwrTrapPMComFailAlarm!!! NOT VALID FOR BC2000 CONTROLLER !!! PM Communication Fail Alarm NOTIFICATION-TYPE .1.3.6.1.4.1.13858.10.41 |
vpwrTrapFuseOverloadAlarm!!! NOT VALID FOR BC2000 CONTROLLER !!! Fuse Overload Alarm NOTIFICATION-TYPE .1.3.6.1.4.1.13858.10.42 |
vpwrTrapPeripheralAlarm!!! NOT VALID FOR BC2000 CONTROLLER !!! Peripheral Alarm. NOTIFICATION-TYPE .1.3.6.1.4.1.13858.10.43 |
vpwrTrapThermalProbeAlarmThermal Probe Missing Alarm NOTIFICATION-TYPE .1.3.6.1.4.1.13858.10.44 |
vpwrTrapBayCommAlarm!!! NOT VALID FOR BC2000 CONTROLLER !!! Bay Communication Alarm NOTIFICATION-TYPE .1.3.6.1.4.1.13858.10.45 |
vpwrTrapDistributionCommAlarmDistribution Communication Alarm NOTIFICATION-TYPE .1.3.6.1.4.1.13858.10.46 |
vpwrTrapConverterAlarm!!! NOT VALID FOR BC2000 CONTROLLER !!! Single Converter Fail Alarm NOTIFICATION-TYPE .1.3.6.1.4.1.13858.10.47 |
vpwrTrapMultipleConvFailAlarm!!! NOT VALID FOR BC2000 CONTROLLER !!! Multiple Converter Fail Alarm NOTIFICATION-TYPE .1.3.6.1.4.1.13858.10.48 |
vpwrTrapDGUAlarm!!! For Future Use. !!! DGU Alarm NOTIFICATION-TYPE .1.3.6.1.4.1.13858.10.49 |
vpwrTrapConfigErrorAlarmConfiguration Error NOTIFICATION-TYPE .1.3.6.1.4.1.13858.10.50 |
vpwrTrapDisplayFirmwareMismatchAlarm!!! NOT VALID FOR BC2000 CONTROLLER !!! Display Firmware Mismatch NOTIFICATION-TYPE .1.3.6.1.4.1.13858.10.51 |
vpwrTrapConverterInputFailAlarm!!! NOT VALID FOR BC2000 CONTROLLER !!! Converter Input Fail Alarm NOTIFICATION-TYPE .1.3.6.1.4.1.13858.10.52 |
vpwrTrapBatteryRechgIlimitFailAlarm!!! NOT VALID FOR BC2000 CONTROLLER !!! Battery Recharge Current Limit Fail NOTIFICATION-TYPE .1.3.6.1.4.1.13858.10.53 |
vpwrTrapSystemAlivePeriodic Keepalive trap NOTIFICATION-TYPE .1.3.6.1.4.1.13858.10.54 |
vpwrTrapSystemAuxAlmSourceSource of Auxilary Alarms. Indicates the module and the aux within the module causing alarms NOTIFICATION-TYPE .1.3.6.1.4.1.13858.10.55 |
vpwrTrapSystemDistAlmSourceSource of Distribution Alarms. Indicates the module and the dist within the module causing alarms NOTIFICATION-TYPE .1.3.6.1.4.1.13858.10.56 |
vpwrTrapSystemBatCapacityAlarmPlant Load exceeds Plant Battery Current Capacity. Useful for batteries that limit maximum discharge current It will not be sent out for VRLA batteries, eg NOTIFICATION-TYPE .1.3.6.1.4.1.13858.10.58 |
vpwrTrapSystemACFClearAlarmAC Fail (ACF) Conditioned Cleared Alarm. Duration is in minutes. NOTIFICATION-TYPE .1.3.6.1.4.1.13858.10.61 |
vpwrTrapSystemACFSetAlarmACF Conditioned detected Alarm. The duration would always be zero. Msg String: ACF Alarm Set NOTIFICATION-TYPE .1.3.6.1.4.1.13858.10.62 |
vpwrTrapSystemBatCapacityLeft!!! For Future Use. !!! Battery Useful Capacity Remaining NOTIFICATION-TYPE .1.3.6.1.4.1.13858.10.64 |
vpwrTrapRectifierUVAlarmRectifier Under Voltage Alarm NOTIFICATION-TYPE .1.3.6.1.4.1.13858.10.65 |
vpwrTrapMultRectifierUVAlarm!!! For Future Use. !!! Multiple Rectifier Under Voltage Alarm NOTIFICATION-TYPE .1.3.6.1.4.1.13858.10.66 |
vpwrTrapRingerAlarmRinger Alarm NOTIFICATION-TYPE .1.3.6.1.4.1.13858.10.67 |
vpwrTrapMultRingerAlarm!!! For Future Use. !!! Multiple Ringer Alarm NOTIFICATION-TYPE .1.3.6.1.4.1.13858.10.68 |
vpwrTrapI2CCANAlarm!!! For Future Use. !!! Unmapped I2C/CAN Address Alarm One of your I2C or CAN devices has a duplicate or invalid address and can not be mapped. Please recheck all device addresses. NOTIFICATION-TYPE .1.3.6.1.4.1.13858.10.69 |
vpwrTrapRectifierIlimitAlarmRectifier Current Limit Alarm NOTIFICATION-TYPE .1.3.6.1.4.1.13858.10.70 |
vpwrTrapMultRectifierIlimitAlarm!!! For Future Use. !!! Multiple Rectifier Current Limit Alarm NOTIFICATION-TYPE .1.3.6.1.4.1.13858.10.71 |
vpwrTrapRingerCommAlarmRinger Communication Alarm NOTIFICATION-TYPE .1.3.6.1.4.1.13858.10.72 |
vpwrTrapUnassignedAlarm!!! NOT VALID FOR BC2000 CONTROLLER !!! Unassigned Alarm(Trap) - Check Web Page NOTIFICATION-TYPE .1.3.6.1.4.1.13858.10.99 |
vpwrDcPowerTrapVars OBJECT IDENTIFIER .1.3.6.1.4.1.13858.11 |
vpwrTrapsMsgStringPlace holder for trap notification message stringro DisplayString .1.3.6.1.4.1.13858.11.1 |
vpwrTrapUserIpAddressPlace holder for IP address of the user accessing the system IpAddress .1.3.6.1.4.1.13858.11.2 |
vpwrTrapAcfDurationPlace holder for duration.ro NonNegativeInteger .1.3.6.1.4.1.13858.11.3 |
vpwrAlarmingSubModuleBitMapindices of alarming sources are encoded as a bit-map e.g., source 1 and source 2 will be encoded as hex 3. source 1 and 3 will be encoded as hex 5.ro PositiveInteger .1.3.6.1.4.1.13858.11.4 |
vpwrBatteryCurrentCapacityPlace holder for total battery capacityro PositiveInteger .1.3.6.1.4.1.13858.11.5 |
vpwrAlarmingModuleIndexindex of alarming module.ro PositiveInteger .1.3.6.1.4.1.13858.11.6 |
vpwrAlarmingModuleOIDIt indicates the type of the module by specifiying its OIDro OBJECT IDENTIFIER .1.3.6.1.4.1.13858.11.7 |
vpwrAlarmingModuleBitMapindices of alarming sources are encoded as a bit-map e.g., source 1 and source 2 will be encoded as hex 3. source 1 and 3 will be encoded as hex 5. PositiveInteger .1.3.6.1.4.1.13858.11.8 |
vpwrBatteryRemainingTimePlace holder for remaining battery time at the current loadro PositiveInteger .1.3.6.1.4.1.13858.11.9 |
vpwrDcPowerRinger OBJECT IDENTIFIER .1.3.6.1.4.1.13858.12 |
vpwrRingerConfigGroup OBJECT IDENTIFIER .1.3.6.1.4.1.13858.12.1 |
vpwrRingerIndexThis parameter allows selecting ringer A or Ringer B as the active ringer.rw INTEGER .1.3.6.1.4.1.13858.12.1.1 |
vpwrRingerParameterAdminStateThis parameter allows selecting ringer A or Ringer B as the active ringer.rw Enumeration .1.3.6.1.4.1.13858.12.1.2 |
vpwrRingerParameterAcVoltageThis parameter sets the output AC voltage of the ringer.rw INTEGER .1.3.6.1.4.1.13858.12.1.3 |
vpwrRingerParameterDcVoltageThis parameter sets the DC offset value of the ringer.rw INTEGER (0..5500 ) UNITS " *.01 Volts" .1.3.6.1.4.1.13858.12.1.4 |
vpwrRingerParameterFrequencyThis parameter sets the ringer AC frequency.rw INTEGER .1.3.6.1.4.1.13858.12.1.5 |
vpwrRingerNumberPresentThe present number of ringer modules.ro Gauge32 .1.3.6.1.4.1.13858.12.1.6 |
vpwrRingerAlarmGroup OBJECT IDENTIFIER .1.3.6.1.4.1.13858.12.2 |
vpwrRingerAlarmAFailedRinger A Failed OBJECT IDENTIFIER .1.3.6.1.4.1.13858.12.2.1 |
vpwrRingerAlarmAOverTempRinger A Heatsink Over-Temperature OBJECT IDENTIFIER .1.3.6.1.4.1.13858.12.2.2 |
vpwrRingerAlarmAOverCurrentRinger A Over-Current protection OBJECT IDENTIFIER .1.3.6.1.4.1.13858.12.2.3 |
vpwrRingerAlarmBFailedRinger B Failed OBJECT IDENTIFIER .1.3.6.1.4.1.13858.12.2.4 |
vpwrRingerAlarmBOverTempRinger B Heatsink Over-Temperature OBJECT IDENTIFIER .1.3.6.1.4.1.13858.12.2.5 |
vpwrRingerAlarmBOverCurrentRinger B Over-Current protection OBJECT IDENTIFIER .1.3.6.1.4.1.13858.12.2.6 |
vpwrRingerTestGroup OBJECT IDENTIFIER .1.3.6.1.4.1.13858.12.3 |
vpwrDcPowerDcDcConverter OBJECT IDENTIFIER .1.3.6.1.4.1.13858.13 |
vpwrDcDcConverterConfigGroup OBJECT IDENTIFIER .1.3.6.1.4.1.13858.13.1 |
vpwrDcDcConverterAlarmGroup OBJECT IDENTIFIER .1.3.6.1.4.1.13858.13.2 |
vpwrDcDcConverterTestGroup OBJECT IDENTIFIER .1.3.6.1.4.1.13858.13.3 |
vpwrDcPowerDcAcInverter OBJECT IDENTIFIER .1.3.6.1.4.1.13858.14 |
vpwrDcAcInverterConfigGroup OBJECT IDENTIFIER .1.3.6.1.4.1.13858.14.1 |
vpwrDcAcInverterAlarmGroup OBJECT IDENTIFIER .1.3.6.1.4.1.13858.14.2 |
vpwrDcAcInverterTestGroup OBJECT IDENTIFIER .1.3.6.1.4.1.13858.14.3 |
vpwrDcPowerAcLineModule OBJECT IDENTIFIER .1.3.6.1.4.1.13858.15 |
vpwrAcLineModuleConfigGroup OBJECT IDENTIFIER .1.3.6.1.4.1.13858.15.1 |
vpwrAcLineModuleAlarmGroup OBJECT IDENTIFIER .1.3.6.1.4.1.13858.15.2 |
vpwrAcLineModuleTestGroup OBJECT IDENTIFIER .1.3.6.1.4.1.13858.15.3 |
vpwrDcPowerIoModule OBJECT IDENTIFIER .1.3.6.1.4.1.13858.16 |
vpwrIoModuleConfigGroup OBJECT IDENTIFIER .1.3.6.1.4.1.13858.16.1 |
vpwrIoModuleAlarmGroup OBJECT IDENTIFIER .1.3.6.1.4.1.13858.16.2 |
vpwrIoModuleTestGroup OBJECT IDENTIFIER .1.3.6.1.4.1.13858.16.3 |
vpwrDcPowerPMModule OBJECT IDENTIFIER .1.3.6.1.4.1.13858.17 |
vpwrPMCnfgTableThis table shows the current configuration of the TRIO/PM86000/Controller inputs. SEQUENCE OF VpwrPMCnfgEntry .1.3.6.1.4.1.13858.17.1 |
vpwrPMCnfgEntryAn entry containing current configuration of the TRIO/PM86000/Controller inputs. VpwrPMCnfgEntry .1.3.6.1.4.1.13858.17.1.1 |
vpwrPMIndexThis parameter describes which TRIO/PM86000 device is being accessed.ro NonNegativeInteger .1.3.6.1.4.1.13858.17.1.1.1 |
vpwrPMDescriptionThis parameter describes the configuration of the TRIO/PM86000 device.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.13858.17.1.1.2 |
vpwrPMCnfg1This parameter gets the current configuration of the TRIO/PM86000, input 1rw VpwrPMCnfgValue .1.3.6.1.4.1.13858.17.1.1.3 |
vpwrPMCnfg2This parameter gets the current configuration of the TRIO/PM86000, input 2rw VpwrPMCnfgValue .1.3.6.1.4.1.13858.17.1.1.4 |
vpwrPMCnfg3This parameter gets the current configuration of the TRIO/PM86000, input 3rw VpwrPMCnfgValue .1.3.6.1.4.1.13858.17.1.1.5 |
vpwrPMCnfg4This parameter gets the current configuration of the TRIO/PM86000, input 4rw VpwrPMCnfgValue .1.3.6.1.4.1.13858.17.1.1.6 |
vpwrPMCnfg5This parameter gets the current configuration of the TRIO/PM86000, input 5rw VpwrPMCnfgValue .1.3.6.1.4.1.13858.17.1.1.7 |
vpwrPMCnfg6This parameter gets the current configuration of the TRIO/PM86000, input 6rw VpwrPMCnfgValue .1.3.6.1.4.1.13858.17.1.1.8 |
vpwrPMCnfg7This parameter gets the current configuration of the TRIO (PM86000), input 7rw VpwrPMCnfgValue .1.3.6.1.4.1.13858.17.1.1.9 |
vpwrPMCnfg8This parameter gets the current configuration of the TRIO/PM86000, input 8rw VpwrPMCnfgValue .1.3.6.1.4.1.13858.17.1.1.10 |
vpwrPMInputStatusTableThis table shows the current values of the TRIO/PM86000/Controller inputs. SEQUENCE OF VpwrPMInputStatusEntry .1.3.6.1.4.1.13858.17.2 |
vpwrPMInputStatusEntryAn entry containing current state of the TRIO/PM86000/Controller inputs. VpwrPMInputStatusEntry .1.3.6.1.4.1.13858.17.2.1 |
vpwrPMIndex1This parameter describes which TRIO/PM86000 device is being accessed.ro NonNegativeInteger .1.3.6.1.4.1.13858.17.2.1.1 |
vpwrPMDescription1This parameter describes the input values of the TRIO/PM86000 device.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.13858.17.2.1.2 |
vpwrPMInput1StateThis parameter gets the current state of input 1ro SysInputValue .1.3.6.1.4.1.13858.17.2.1.3 |
vpwrPMInput2StateThis parameter gets the current state of input 2ro SysInputValue .1.3.6.1.4.1.13858.17.2.1.4 |
vpwrPMInput3StateThis parameter gets the current state of input 3ro SysInputValue .1.3.6.1.4.1.13858.17.2.1.5 |
vpwrPMInput4StateThis parameter gets the current state of input 4ro SysInputValue .1.3.6.1.4.1.13858.17.2.1.6 |
vpwrPMInput5StateThis parameter gets the current state of input 5ro SysInputValue .1.3.6.1.4.1.13858.17.2.1.7 |
vpwrPMInput6StateThis parameter gets the current state of input 6ro SysInputValue .1.3.6.1.4.1.13858.17.2.1.8 |
vpwrPMInput7StateThis parameter gets the current state of input 7ro SysInputValue .1.3.6.1.4.1.13858.17.2.1.9 |
vpwrPMInput8StateThis parameter gets the current state of input 8ro SysInputValue .1.3.6.1.4.1.13858.17.2.1.10 |
vpwrPMRelayCtrlTableThis table describes/controls system relays. SEQUENCE OF VpwrPMRelayCtrlEntry .1.3.6.1.4.1.13858.17.3 |
vpwrPMRelayCtrlEntryAn entry containing current state of the relays. VpwrPMRelayCtrlEntry .1.3.6.1.4.1.13858.17.3.1 |
vpwrPMIndex2This parameter describes the TRIO/PM devicero NonNegativeInteger .1.3.6.1.4.1.13858.17.3.1.1 |
vpwrPMDescription2This parameter describes the TRIO/PM devicero DisplayString (SNMPv2-TC) .1.3.6.1.4.1.13858.17.3.1.2 |
vpwrPMRelay1StateThis parameter sets the current state of relay 1rw Enumeration .1.3.6.1.4.1.13858.17.3.1.3 |
vpwrPMRelay2StateThis parameter sets the current state of relay 2rw Enumeration .1.3.6.1.4.1.13858.17.3.1.4 |
vpwrPMRelay3StateThis parameter sets the current state of relay 3rw Enumeration .1.3.6.1.4.1.13858.17.3.1.5 |
vpwrPMRelay4StateThis parameter sets the current state of relay 4rw Enumeration .1.3.6.1.4.1.13858.17.3.1.6 |
vpwrPMRelay5StateThis parameter sets the current state of relay 5rw Enumeration .1.3.6.1.4.1.13858.17.3.1.7 |
vpwrPMRelay6StateThis parameter sets the current state of relay 6rw Enumeration .1.3.6.1.4.1.13858.17.3.1.8 |
vpwrPMModuleAlarmGroup OBJECT IDENTIFIER .1.3.6.1.4.1.13858.17.4 |
vpwrPMModuleTestGroup OBJECT IDENTIFIER .1.3.6.1.4.1.13858.17.5 |
vpwrDcPowerDistModule OBJECT IDENTIFIER .1.3.6.1.4.1.13858.18 |
vpwrDcPowerBattery OBJECT IDENTIFIER .1.3.6.1.4.1.13858.19 |
vpwrDcPowerController OBJECT IDENTIFIER .1.3.6.1.4.1.13858.20 |
vpwrDcPowerUnkModule OBJECT IDENTIFIER .1.3.6.1.4.1.13858.499 |
thirdPartyProduct OBJECT IDENTIFIER .1.3.6.1.4.1.13858.500 |