Home/Catalog/TRISTAR-MPPT-600V

TRISTAR-MPPT-600V

AI MIB Summary

The TRISTAR-MPPT-600V MIB module enables SNMP-based monitoring and management of Morningstar TriStar-MPPT-600V solar charge controllers, specifically exposing photovoltaic input/output parameters such as array voltage, current, power, and MPPT tracking status. It facilitates the collection of real-time telemetry and operational counters required for remote system diagnostics and performance verification of the 600V DC solar charging infrastructure.

Morningstar Product: TriStar-MPPT-600V Device Type: 9 Device Model: 0 Meterbus Type: 9 Copyright (C) Morningstar Corporation (2019). All Rights Reserved
Main OID:
tristarmppt600v.1.3.6.1.4.1.33333.7
35
Objects
Active
Status
5
Dependencies

Imported Objects

Objects

35 total
Object Name
tristarmppt600vMorningstar Product: TriStar-MPPT-600V Device Type: 9 Device Model: 0 Meterbus Type: 9 Copyright (C) Morningstar Corporation (2019). All Rights Reserved
MODULE-IDENTITY
.1.3.6.1.4.1.33333.7
subModelThe device's exact modelro
DisplayString
.1.3.6.1.4.1.33333.7.1
serialNumberDevice Serial Numberro
DisplayString
.1.3.6.1.4.1.33333.7.2
deviceVersionHardware and firmware versions: vHW1.HW2.FWro
DisplayString
.1.3.6.1.4.1.33333.7.3
arrayVoltageArray Voltage - Description: Array Voltage - Scaling Factor: 1.0 - Units: V - Range: [-10, 650] - Modbus address: 0x001bro
DisplayString
.1.3.6.1.4.1.33333.7.30
arrayCurrentArray Current - Description: Array Current - Scaling Factor: 1.0 - Units: A - Range: [-10, 80] - Modbus address: 0x001dro
DisplayString
.1.3.6.1.4.1.33333.7.31
inputPowerInput Power - Description: Input Power - Scaling Factor: 1.0 - Units: W - Range: [-4000, 4000] - Modbus address: 0x003bro
DisplayString
.1.3.6.1.4.1.33333.7.32
arrayPmaxLastSweepArray Pmax(last sweep) - Description: Pmax (last sweep) - Scaling Factor: 1.0 - Units: W - Range: [-10, 5000] - Modbus address: 0x003cro
DisplayString
.1.3.6.1.4.1.33333.7.33
arrayVmpLastSweepArray Vmp (last sweep) - Description: Vmp (last sweep) - Scaling Factor: 1.0 - Units: V - Range: [-10, 650.0] - Modbus address: 0x003dro
DisplayString
.1.3.6.1.4.1.33333.7.34
arrayVocLastSweepArray Voc (last sweep) - Description: Voc (last sweep) - Scaling Factor: 1.0 - Units: V - Range: [-10, 650.0] - Modbus address: 0x003ero
DisplayString
.1.3.6.1.4.1.33333.7.35
batteryVoltageBattery Voltage - Description: Battery voltage - Scaling Factor: 1.0 - Units: V - Range: [-10, 80] - Modbus address: 0x0018ro
DisplayString
.1.3.6.1.4.1.33333.7.36
batteryVoltageSlowBattery Voltage(slow) - Description: Battery voltage(slow) - Scaling Factor: 1.0 - Units: V - Range: [-10, 80] - Modbus address: 0x0026ro
DisplayString
.1.3.6.1.4.1.33333.7.37
batteryTerminalVoltageBattery Terminal Voltage - Description: Battery Terminal Voltage - Scaling Factor: 1.0 - Units: V - Range: [-10, 80] - Modbus address: 0x0019ro
DisplayString
.1.3.6.1.4.1.33333.7.38
batterySenseVoltageBattery Sense Voltage - Description: Battery Sense Voltage - Scaling Factor: 1.0 - Units: V - Range: [-10, 80] - Modbus address: 0x001aro
DisplayString
.1.3.6.1.4.1.33333.7.39
minBatteryVoltageSlowMin. Battery Voltage(slow) - Description: Min. Battery voltage - Scaling Factor: 1.0 - Units: V - Range: [-10, 650.0] - Modbus address: 0x0028ro
DisplayString
.1.3.6.1.4.1.33333.7.40
maxBatteryVoltageSlowMax. Battery Voltage(slow) - Description: Max. Battery voltage - Scaling Factor: 1.0 - Units: V - Range: [-10, 650.0] - Modbus address: 0x0029ro
DisplayString
.1.3.6.1.4.1.33333.7.41
batteryCurrentBattery Current - Description: Battery Current - Scaling Factor: 1.0 - Units: A - Range: [-10, 80] - Modbus address: 0x001cro
DisplayString
.1.3.6.1.4.1.33333.7.42
batteryCurrentSlowBattery Current(slow) - Description: Battery current(slow) - Scaling Factor: 1.0 - Units: A - Range: [-10, 80.0] - Modbus address: 0x0027ro
DisplayString
.1.3.6.1.4.1.33333.7.43
outputPowerOutput Power - Description: Output Power - Scaling Factor: 1.0 - Units: W - Range: [-10, 4000] - Modbus address: 0x003aro
DisplayString
.1.3.6.1.4.1.33333.7.44
targetRegulationVoltageTarget Regulation Voltage - Description: Target Voltage - Scaling Factor: 1.0 - Units: V - Range: [-10, 650.0] - Modbus address: 0x0033ro
DisplayString
.1.3.6.1.4.1.33333.7.45
chargeStateCharge State - Description: Charge State - Modbus address: 0x0032ro
ChargeStateEnum
.1.3.6.1.4.1.33333.7.46
rtsTemperatureRTS Temperature - Description: RTS Temp - Scaling Factor: 1.0 - Units: C - Range: [-40, 80] - Modbus address: 0x0024ro
DisplayString
.1.3.6.1.4.1.33333.7.47
batteryTemperatureBattery Temperature - Description: Batt. Temp - Scaling Factor: 1.0 - Units: C - Range: [-40, 80] - Modbus address: 0x0025ro
DisplayString
.1.3.6.1.4.1.33333.7.48
heatsinkTemperatureHeatsink Temperature - Description: HS Temp - Scaling Factor: 1.0 - Units: C - Range: [-40, 80] - Modbus address: 0x0023ro
DisplayString
.1.3.6.1.4.1.33333.7.49
ahChargeResetableAh Charge Resetable - Description: Ah Charge Resetable - Scaling Factor: 1.0 - Units: Ah - Range: [0.0, 5000] - Modbus addresses: H=0x0034 L=0x0035ro
DisplayString
.1.3.6.1.4.1.33333.7.50
ahChargeTotalAh Charge Total - Description: Ah Charge Total - Scaling Factor: 1.0 - Units: Ah - Range: [0.0, 5000] - Modbus addresses: H=0x0036 L=0x0037ro
DisplayString
.1.3.6.1.4.1.33333.7.51
kwhChargeResetablekWh Charge Resetable - Description: kWh Charge Resetable - Scaling Factor: 1.0 - Units: kWh - Range: [0.0, 65535.0] - Modbus address: 0x0038ro
DisplayString
.1.3.6.1.4.1.33333.7.52
kwhChargeTotalkWh Charge Total - Description: kWh Charge Total - Scaling Factor: 1.0 - Units: kWh - Range: [0.0, 65535.0] - Modbus address: 0x0039ro
DisplayString
.1.3.6.1.4.1.33333.7.53
ledStateLED State - Description: Control Mode - Modbus address: 0x0031ro
LedStateEnum
.1.3.6.1.4.1.33333.7.54
faultsFaults - Description: Faults - Modbus addresses: H=0x002c L=0x002dro
FaultsBitfield
.1.3.6.1.4.1.33333.7.55
faultsDailyFaults Daily - Description: Faults Daily - Modbus addresses: H=0x0049 L=0x004aro
FaultsDailyBitfield
.1.3.6.1.4.1.33333.7.56
alarmsAlarms - Description: Alarms - Modbus addresses: H=0x002e L=0x002fro
AlarmsBitfield
.1.3.6.1.4.1.33333.7.57
alarmsDailyAlarms Daily - Description: Alarms - Modbus addresses: H=0x004b L=0x004cro
AlarmsDailyBitfield
.1.3.6.1.4.1.33333.7.58
hourmeterHourmeter - Description: Hourmeter - Scaling Factor: 1.0 - Units: hrs - Range: [0.0, 50000.0] - Modbus addresses: H=0x002a L=0x002bro
Unsigned32
.1.3.6.1.4.1.33333.7.59
settingsSwitchesSettings Switches - Description: Settings Switches - Modbus address: 0x0030ro
SettingsSwitchesEnum
.1.3.6.1.4.1.33333.7.60

More MIBs from morningstar

Browse all morningstarMIBs →
C-PRODUCT-TRAP-MIB

Standard SNMP MIB module defining data structures for C-PRODUCT-TRAP-MIB.

181 objects→
GENSTAR

The GENSTAR MIB module facilitates SNMP-based monitoring and management of Morningstar GenStar solar charge controllers and inverters, exposing operational metrics such as battery voltage, current, state of charge, and system status via Modbus-to-SNMP translation.

139 objects→
PROSTAR-MPPT

The PROSTAR-MPPT MIB module enables SNMP-based monitoring and management of Morningstar Prostar Maximum Power Point Tracking (MPPT) solar charge controllers, exposing telemetry for photovoltaic array voltage, current, power output, battery bank status, and system efficiency metrics.

60 objects→
PROSTAR-PWM

The PROSTAR-PWM MIB module enables SNMP-based monitoring and management of Morningstar Prostar Pulse Width Modulation (PWM) solar charge controllers, exposing device-specific telemetry such as battery voltage, charging current, solar input status, and internal temperature. It facilitates the collection of operational state data and alarm conditions for these specific solar power management devices within a networked infrastructure.

53 objects→
SUNSAVER-MPPT

The SUNSAVER-MPPT MIB module enables SNMP-based monitoring and management of Morningstar SunSaver MPPT solar charge controllers, specifically facilitating the retrieval of photovoltaic system telemetry such as input/output voltage, current, power, and battery state-of-charge. This module supports the device's Meterbus interface (Type 5) to aggregate critical charging parameters for remote system health assessment and performance analysis.

52 objects→
TRISTAR-MPPT

The TRISTAR-MPPT MIB module enables SNMP-based monitoring and management of Morningstar TriStar-MPPT solar charge controllers, specifically exposing metrics for photovoltaic input voltage and current, battery bank status, and MPPT tracking efficiency. This module facilitates the collection of real-time operational data and alarm states required for remote system health assessment and performance analysis of solar power installations.

44 objects→