GENSTAR
The GENSTAR MIB module facilitates SNMP-based monitoring and management of Morningstar GenStar solar charge controllers and inverters, exposing operational metrics such as battery voltage, current, state of charge, and system status via Modbus-to-SNMP translation.
Imported Objects
Objects
130 total| Object Name |
|---|
genStarMorningstar Product: GenStar
For more information on each node, check out the modbus
docs at www.morningstarcorp.com
Copyright (C) Morningstar Corporation (2019).
All Rights Reserved MODULE-IDENTITY .1.3.6.1.4.1.33333.10 |
subModelThe device's exact modelro DisplayString .1.3.6.1.4.1.33333.10.1 |
serialNumberDevice Serial Numberro DisplayString .1.3.6.1.4.1.33333.10.2 |
deviceVersionHardware and firmware versions: vHW1.HW2.FWro DisplayString .1.3.6.1.4.1.33333.10.3 |
vbtermVBTERM_F256
- Description: Battery voltage
- Modbus address: 0x0021ro DisplayString .1.3.6.1.4.1.33333.10.30 |
vloadVLOAD_F256
- Description: Load voltage
- Modbus address: 0x0023ro DisplayString .1.3.6.1.4.1.33333.10.31 |
vbsenseVBSENSE_F256
- Description: Battery sense voltage
- Modbus address: 0x0025ro DisplayString .1.3.6.1.4.1.33333.10.32 |
vCoinV_COIN_F256
- Description: Coincell battery voltage
- Modbus address: 0x0036ro DisplayString .1.3.6.1.4.1.33333.10.33 |
systemIchargeSYSTEM_ICHARGE
- Description: System charging current
- Modbus address: 0x0063ro DisplayString .1.3.6.1.4.1.33333.10.34 |
systemIloadSYSTEM_ILOAD
- Description: System load current
- Modbus address: 0x0065ro DisplayString .1.3.6.1.4.1.33333.10.35 |
tempBattTEMP_BATT
- Description: Battery temperature
- Modbus address: 0x0075ro DisplayString .1.3.6.1.4.1.33333.10.36 |
tempRtsTEMP_RTS
- Description: Remote temperature sensor temperature
- Modbus address: 0x0076ro DisplayString .1.3.6.1.4.1.33333.10.37 |
tempHeatsinkTEMP_HEATSINK
- Description: Heatsink temperature
- Modbus address: 0x0077ro DisplayString .1.3.6.1.4.1.33333.10.38 |
chargeStateCHARGE_STATE
- Description: Charge state
- Modbus address: 0x0080ro ChargeStateEnum .1.3.6.1.4.1.33333.10.39 |
vbattRefChargeVBATT_REF_CHARGE
- Description: Charging target voltage
- Modbus address: 0x00b1ro DisplayString .1.3.6.1.4.1.33333.10.40 |
battSocBATT_SOC
- Description: Battery state of charge
- Modbus address: 0x00e0ro DisplayString .1.3.6.1.4.1.33333.10.41 |
vbattMinVBATT_MIN
- Description: Minimum battery voltage
- Modbus address: 0x00e1ro DisplayString .1.3.6.1.4.1.33333.10.42 |
vbattMaxVBATT_MAX
- Description: Maximum battery voltage
- Modbus address: 0x00e2ro DisplayString .1.3.6.1.4.1.33333.10.43 |
battSocMinDailyBATT_SOC_MIN_DAILY
- Description: Minimum battery state of charge daily
- Modbus address: 0x00e9ro DisplayString .1.3.6.1.4.1.33333.10.44 |
battSocMaxDailyBATT_SOC_MAX_DAILY
- Description: Maximum battery state of charge daily
- Modbus address: 0x00earo DisplayString .1.3.6.1.4.1.33333.10.45 |
loadStateLOAD_STATE
- Description: Load state
- Modbus address: 0x0100ro LoadStateEnum .1.3.6.1.4.1.33333.10.46 |
loadFaultLOAD_FAULT
- Description: Load fault bitfield
- Modbus address: 0x0101ro LoadFaultBitfield .1.3.6.1.4.1.33333.10.47 |
loadFaultDailyLOAD_FAULT_DAILY
- Description: Load fault daily bitfield
- Modbus address: 0x0103ro LoadFaultBitfield .1.3.6.1.4.1.33333.10.48 |
faultFAULT
- Description: System fault bitfield
- Modbus address: 0x0212ro FaultBitfield .1.3.6.1.4.1.33333.10.49 |
faultDailyFAULT_DAILY
- Description: System fault daily bitfield
- Modbus address: 0x0216ro FaultBitfield .1.3.6.1.4.1.33333.10.50 |
alarmALARM
- Description: Alarm bitfield
- Modbus address: 0x021aro AlarmBitfield .1.3.6.1.4.1.33333.10.51 |
alarmDailyALARM_DAILY
- Description: Alarm daily bitfield
- Modbus address: 0x021ero AlarmBitfield .1.3.6.1.4.1.33333.10.52 |
chargeFaultCHARGE_FAULT
- Description: Charge fault bitfield
- Modbus address: 0x0222ro ChargeFaultBitfield .1.3.6.1.4.1.33333.10.53 |
chargeFaultDailyCHARGE_FAULT_DAILY
- Description: Charge fault daily bitfield
- Modbus address: 0x0226ro ChargeFaultBitfield .1.3.6.1.4.1.33333.10.54 |
faultPowersupplyFAULT_POWERSUPPLY
- Description: Power Supply fault bitfield
- Modbus address: 0x0232ro FaultPowersupplyBitfield .1.3.6.1.4.1.33333.10.55 |
faultPowersupplyDailyFAULT_POWERSUPPLY_DAILY
- Description: Power Supply fault daily bitfield
- Modbus address: 0x0234ro FaultPowersupplyBitfield .1.3.6.1.4.1.33333.10.56 |
blockFaultBLOCK_FAULT
- Description: ReadyBlock subsystem fault bitfield
- Modbus address: 0x0236ro BlockFaultBitfield .1.3.6.1.4.1.33333.10.57 |
blockFaultDailyBLOCK_FAULT_DAILY
- Description: ReadyBlock subsystem fault daily bitfield
- Modbus address: 0x0238ro BlockFaultBitfield .1.3.6.1.4.1.33333.10.58 |
faultPowerstageFAULT_POWERSTAGE
- Description: Powerstage fault bitfield
- Modbus address: 0x023aro FaultPowerstageBitfield .1.3.6.1.4.1.33333.10.59 |
faultPowerstageDailyFAULT_POWERSTAGE_DAILY
- Description: Powerstage fault daily bitfield
- Modbus address: 0x023ero FaultPowerstageBitfield .1.3.6.1.4.1.33333.10.60 |
vbattMinDailyVBATT_MIN_DAILY
- Description: Minimum battery voltage daily
- Modbus address: 0x026cro DisplayString .1.3.6.1.4.1.33333.10.61 |
vbattMaxDailyVBATT_MAX_DAILY
- Description: Maximum battery voltage daily
- Modbus address: 0x026dro DisplayString .1.3.6.1.4.1.33333.10.62 |
varrayMaxDailyVARRAY_MAX_DAILY
- Description: Maximum array voltage daily
- Modbus address: 0x026ero DisplayString .1.3.6.1.4.1.33333.10.63 |
timeAbsorbDailyTIME_ABSORB_DAILY
- Description: Time battery spent in absorption daily
- Modbus address: 0x0274ro DisplayString .1.3.6.1.4.1.33333.10.64 |
timeEqDailyTIME_EQ_DAILY
- Description: Time battery spent in equalize daily
- Modbus address: 0x0276ro DisplayString .1.3.6.1.4.1.33333.10.65 |
timeFloatDailyTIME_FLOAT_DAILY
- Description: Time battery spent in float daily
- Modbus address: 0x0278ro DisplayString .1.3.6.1.4.1.33333.10.66 |
hourmeterHOURMETER
- Description: How long the control has ever been on
- Modbus address: 0x02a6ro Unsigned32 .1.3.6.1.4.1.33333.10.67 |
systemChargeKwhDailySYSTEM_CHARGE_KWH_DAILY
- Description: System charge kWh daily
- Modbus address: 0x02d0ro DisplayString .1.3.6.1.4.1.33333.10.68 |
systemChargeKwhResettable10SYSTEM_CHARGE_KWH_RESETTABLE10
- Description: System charge kWh resettable
- Scaling Factor: 0.1
- Modbus address: 0x02d2ro Unsigned32 .1.3.6.1.4.1.33333.10.69 |
systemChargeKwhTotal10SYSTEM_CHARGE_KWH_TOTAL10
- Description: System charge kWh total
- Scaling Factor: 0.1
- Modbus address: 0x02d4ro Unsigned32 .1.3.6.1.4.1.33333.10.70 |
systemChargeAhDailySYSTEM_CHARGE_AH_DAILY
- Description: System charge Ah daily
- Modbus address: 0x02d6ro DisplayString .1.3.6.1.4.1.33333.10.71 |
systemChargeAhResettable10SYSTEM_CHARGE_AH_RESETTABLE10
- Description: System charge Ah resettable
- Scaling Factor: 0.1
- Modbus address: 0x02d8ro Unsigned32 .1.3.6.1.4.1.33333.10.72 |
systemChargeAhTotal10SYSTEM_CHARGE_AH_TOTAL10
- Description: System charge Ah total
- Scaling Factor: 0.1
- Modbus address: 0x02daro Unsigned32 .1.3.6.1.4.1.33333.10.73 |
systemBattAhDailySYSTEM_BATT_AH_DAILY
- Description: System battery Ah daily
- Modbus address: 0x02dcro DisplayString .1.3.6.1.4.1.33333.10.74 |
systemBattAhResettable10SYSTEM_BATT_AH_RESETTABLE10
- Description: System battery Ah resettable
- Scaling Factor: 0.1
- Modbus address: 0x02dero Integer32 .1.3.6.1.4.1.33333.10.75 |
systemBattAhTotal10SYSTEM_BATT_AH_TOTAL10
- Description: System battery Ah total
- Scaling Factor: 0.1
- Modbus address: 0x02e0ro Integer32 .1.3.6.1.4.1.33333.10.76 |
systemLoadAhDailySYSTEM_LOAD_AH_DAILY
- Description: System load Ah daily
- Modbus address: 0x02e2ro DisplayString .1.3.6.1.4.1.33333.10.77 |
systemLoadAhResettable10SYSTEM_LOAD_AH_RESETTABLE10
- Description: System load Ah resettable
- Scaling Factor: 0.1
- Modbus address: 0x02e4ro Unsigned32 .1.3.6.1.4.1.33333.10.78 |
systemLoadAhTotal10SYSTEM_LOAD_AH_TOTAL10
- Description: System load Ah total
- Scaling Factor: 0.1
- Modbus address: 0x02e6ro Unsigned32 .1.3.6.1.4.1.33333.10.79 |
internalChargeKwhDailyINTERNAL_CHARGE_KWH_DAILY
- Description: Internal charge kWh daily
- Modbus address: 0x02e8ro DisplayString .1.3.6.1.4.1.33333.10.80 |
internalChargeKwhResettable10INTERNAL_CHARGE_KWH_RESETTABLE10
- Description: Internal charge kWh resettable
- Scaling Factor: 0.1
- Modbus address: 0x02earo Unsigned32 .1.3.6.1.4.1.33333.10.81 |
internalChargeKwhTotal10INTERNAL_CHARGE_KWH_TOTAL10
- Description: Internal charge kWh total
- Scaling Factor: 0.1
- Modbus address: 0x02ecro Unsigned32 .1.3.6.1.4.1.33333.10.82 |
internalChargeAhDailyINTERNAL_CHARGE_AH_DAILY
- Description: Internal charge Ah daily
- Modbus address: 0x02eero DisplayString .1.3.6.1.4.1.33333.10.83 |
internalChargeAhResettable10INTERNAL_CHARGE_AH_RESETTABLE10
- Description: Internal charge Ah resettable
- Scaling Factor: 0.1
- Modbus address: 0x02f0ro Unsigned32 .1.3.6.1.4.1.33333.10.84 |
internalChargeAhTotal10INTERNAL_CHARGE_AH_TOTAL10
- Description: Internal charge Ah total
- Scaling Factor: 0.1
- Modbus address: 0x02f2ro Unsigned32 .1.3.6.1.4.1.33333.10.85 |
internalBattAhDailyINTERNAL_BATT_AH_DAILY
- Description: Internal battery Ah daily
- Modbus address: 0x02f4ro DisplayString .1.3.6.1.4.1.33333.10.86 |
internalBattAhResettable10INTERNAL_BATT_AH_RESETTABLE10
- Description: Internal battery Ah resettable
- Scaling Factor: 0.1
- Modbus address: 0x02f6ro Integer32 .1.3.6.1.4.1.33333.10.87 |
internalBattAhTotal10INTERNAL_BATT_AH_TOTAL10
- Description: Internal battery Ah total
- Scaling Factor: 0.1
- Modbus address: 0x02f8ro Integer32 .1.3.6.1.4.1.33333.10.88 |
load0AhDailyLOAD0_AH_DAILY
- Description: Internal (load0) Ah daily
- Modbus address: 0x02faro DisplayString .1.3.6.1.4.1.33333.10.89 |
load0AhResettable10LOAD0_AH_RESETTABLE10
- Description: Internal (load0) Ah resettable
- Scaling Factor: 0.1
- Modbus address: 0x02fcro Unsigned32 .1.3.6.1.4.1.33333.10.90 |
load0AhTotal10LOAD0_AH_TOTAL10
- Description: Internal (load0) Ah total
- Scaling Factor: 0.1
- Modbus address: 0x02fero Unsigned32 .1.3.6.1.4.1.33333.10.91 |
adcIloadF1sDispfilADC_ILOAD_F_1S_DISPFIL
- Description: Load current, slow filtered
- Modbus address: 0x0f30ro DisplayString .1.3.6.1.4.1.33333.10.92 |
powerOutDispfilPOWER_OUT_DISPFIL
- Description: Charging power out of control to battery, slow filtered
- Modbus address: 0x0f31ro DisplayString .1.3.6.1.4.1.33333.10.93 |
systemIbattDispfilSYSTEM_IBATT_DISPFIL
- Description: System battery current, slow filtered
- Modbus address: 0x0f33ro DisplayString .1.3.6.1.4.1.33333.10.94 |
adcVarrayFSlowShadowDispfilADC_VARRAY_F_SLOW_SHADOW_DISPFIL
- Description: Array voltage, slow filtered
- Modbus address: 0x0f34ro DisplayString .1.3.6.1.4.1.33333.10.95 |
adcIarrayFSlowShadowDispfilADC_IARRAY_F_SLOW_SHADOW_DISPFIL
- Description: Array current, slow filtered
- Modbus address: 0x0f35ro DisplayString .1.3.6.1.4.1.33333.10.96 |
echargevBattRefLimitEchargevBattRefLimit
- Description: Maximum regulator voltage; 0==disable
- Modbus address: 0x1000rw DisplayString .1.3.6.1.4.1.33333.10.97 |
echargevAbsorbEchargevAbsorb
- Description: Absorption voltage target
- Modbus address: 0x1002rw DisplayString .1.3.6.1.4.1.33333.10.98 |
echargeiBattAbsorbTermEchargeiBattAbsorbTerm
- Description: Absorption end-amps; The net battery current that will terminate absorption (based on timer)
- Modbus address: 0x1004rw DisplayString .1.3.6.1.4.1.33333.10.99 |
echargetIBattAbsorbTermEchargetIBattAbsorbTerm
- Description: Absorption end-amps time; Absorption termination will occur when the net battery current is below the end-amps threshold for this long
- Modbus address: 0x1008rw Unsigned32 .1.3.6.1.4.1.33333.10.100 |
echargevFloatExitEchargevFloatExit
- Description: Voltage trip to exit float prematurely
- Modbus address: 0x100crw DisplayString .1.3.6.1.4.1.33333.10.101 |
echargevFloatCancelEchargevFloatCancel
- Description: Voltage trip to cancel float
- Modbus address: 0x100erw DisplayString .1.3.6.1.4.1.33333.10.102 |
echargevAbsorptionExtEchargevAbsorptionExt
- Description: Absorption extension threshold
- Modbus address: 0x1010rw DisplayString .1.3.6.1.4.1.33333.10.103 |
echargetAbsorptionExtEchargetAbsorptionExt
- Description: Time to spend in Absorption extension
- Modbus address: 0x1012rw Unsigned32 .1.3.6.1.4.1.33333.10.104 |
echargevEqualizeEchargevEqualize
- Description: Equalize voltage target; 0==disable
- Modbus address: 0x1015rw DisplayString .1.3.6.1.4.1.33333.10.105 |
echargeiEqualizeLimitEchargeiEqualizeLimit
- Description: Equalize max current limit; 0==disable
- Modbus address: 0x1017rw DisplayString .1.3.6.1.4.1.33333.10.106 |
echargevHVD25EchargevHVD25
- Description: High voltage disconnect voltage (25C)
- Modbus address: 0x101drw DisplayString .1.3.6.1.4.1.33333.10.107 |
echargevHVREchargevHVR
- Description: High voltage reconnect voltage
- Modbus address: 0x101frw DisplayString .1.3.6.1.4.1.33333.10.108 |
echargetAbsorptionEchargetAbsorption
- Description: Time to spend in Absorption
- Modbus address: 0x1021rw Unsigned32 .1.3.6.1.4.1.33333.10.109 |
echargetEqualizeEchargetEqualize
- Description: Time to spend equalizing
- Modbus address: 0x1022rw Unsigned32 .1.3.6.1.4.1.33333.10.110 |
echargetEqualizeCalendarEchargetEqualizeCalendar
- Description: Interval between auto-equalize cycles
- Modbus address: 0x1023rw Unsigned32 .1.3.6.1.4.1.33333.10.111 |
echargetEqualizeTOEchargetEqualizeTO
- Description: Equalize timeout
- Modbus address: 0x1024rw Unsigned32 .1.3.6.1.4.1.33333.10.112 |
echargevTempCompEchargevTempComp
- Description: Temperature compensation coefficient
- Modbus address: 0x1025rw DisplayString .1.3.6.1.4.1.33333.10.113 |
echargeTBattMinLimEchargeTBattMinLim
- Description: Minimum compensation temperature
- Modbus address: 0x1026rw DisplayString .1.3.6.1.4.1.33333.10.114 |
echargeTBattMaxLimEchargeTBattMaxLim
- Description: Maximum compensation temperature
- Modbus address: 0x1027rw DisplayString .1.3.6.1.4.1.33333.10.115 |
echargetemperatureFoldbackCold0EchargetemperatureFoldbackCold0
- Description: the cold temperature below which the charge controller current is 0%; NAN==disable
- Modbus address: 0x1028rw DisplayString .1.3.6.1.4.1.33333.10.116 |
echargetemperatureFoldbackCold100EchargetemperatureFoldbackCold100
- Description: the cold temperature above which the charge controller current can be 100%; NAN==disable
- Modbus address: 0x1029rw DisplayString .1.3.6.1.4.1.33333.10.117 |
echargetemperatureFoldbackHot100EchargetemperatureFoldbackHot100
- Description: the hot temperature below which the charge controller current can be 100%; NAN==disable
- Modbus address: 0x102arw DisplayString .1.3.6.1.4.1.33333.10.118 |
echargetemperatureFoldbackHot0EchargetemperatureFoldbackHot0
- Description: the hot temperature above which the charge controller current is 0%; NAN==disable
- Modbus address: 0x102brw DisplayString .1.3.6.1.4.1.33333.10.119 |
egreenModeEgreen_mode
- Description: Ethernet green mode. Enabling this attempts to save power in the Ethernet system when possible, e.g., turning off power to unused ports. 1==enable, 0==disable
- Modbus address: 0x105crw TruthValue (SNMPv2-TC) .1.3.6.1.4.1.33333.10.120 |
eBatteryTypeEBatteryType
- Description: Battery Type; See the latest revision manual on our website for battery type definitions
- Modbus address: 0x1060rw Unsigned32 .1.3.6.1.4.1.33333.10.121 |
emodbusIdEmodbus_id
- Description: This device's Modbus address (1 to 247)
- Modbus address: 0x1068rw Unsigned32 .1.3.6.1.4.1.33333.10.122 |
ebaudrateMb232Ebaudrate_mb232
- Description: Baudrate for serial Modbus; E.g., 96 means 9600 baud
- Scaling Factor: 100
- Modbus address: 0x1069rw Unsigned32 .1.3.6.1.4.1.33333.10.123 |
eload0VLVD0Eload0VLVD0
- Description: Load low voltage disconnect
- Modbus address: 0x10a0rw DisplayString .1.3.6.1.4.1.33333.10.124 |
eload0VLVREload0VLVR
- Description: Load low voltage reconnect
- Modbus address: 0x10a1rw DisplayString .1.3.6.1.4.1.33333.10.125 |
eload0vStartLVDEload0vStartLVD
- Description: Voltage at start to go straight into LVD
- Modbus address: 0x10a2rw DisplayString .1.3.6.1.4.1.33333.10.126 |
eload0HVDEload0HVD
- Description: The HVD used in the load controller
- Modbus address: 0x10a3rw DisplayString .1.3.6.1.4.1.33333.10.127 |
eload0HVREload0HVR
- Description: The HVR used in the load controller
- Modbus address: 0x10a4rw DisplayString .1.3.6.1.4.1.33333.10.128 |
eload0SOCDisconnectEload0SOCDisconnect
- Description: Load low SOC disconnect
- Modbus address: 0x10a5rw DisplayString .1.3.6.1.4.1.33333.10.129 |
eload0SOCReconnectEload0SOCReconnect
- Description: Load low SOC reconnect
- Modbus address: 0x10a6rw DisplayString .1.3.6.1.4.1.33333.10.130 |
eload0tLVDWarnEload0tLVDWarn
- Description: Load low voltage disconnect warning timer.
- Modbus address: 0x10a8rw Unsigned32 .1.3.6.1.4.1.33333.10.131 |
eload0currentCompEload0currentComp
- Description: Battery resistance for LVD current compensation; this value will always be positive
- Modbus address: 0x10aarw DisplayString .1.3.6.1.4.1.33333.10.132 |
eIPAddrEIPAddr
- Description: This device's static IP address, in host (little-endian) order. Only meaningful if DHCP is disabled.
- Modbus address: 0x1110rw IpAddress .1.3.6.1.4.1.33333.10.133 |
eNetMaskENetMask
- Description: This device's static IP netmask. Only meaningful if DHCP is disabled
- Modbus address: 0x1112rw IpAddress .1.3.6.1.4.1.33333.10.134 |
eGatewayEGateway
- Description: This device's static IP gateway. Only meaningful if DHCP is disabled
- Modbus address: 0x1114rw IpAddress .1.3.6.1.4.1.33333.10.135 |
ePrimaryDNSServerEPrimaryDNSServer
- Description: This device's static IP primary DNS server to use. Only meaningful if DHCP is disabled
- Modbus address: 0x1116rw IpAddress .1.3.6.1.4.1.33333.10.136 |
eSecondaryDNSServerESecondaryDNSServer
- Description: This device's static IP secondary DNS server to use. Only meaningful if DHCP is disabled
- Modbus address: 0x1118rw IpAddress .1.3.6.1.4.1.33333.10.137 |
eIsDHCPEnabledEIsDHCPEnabled
- Description: DHCP status. If DHCP is disabled, the control will use static IP settings. 0==disabled, 1==enabled.
- Modbus address: 0x1122rw TruthValue (SNMPv2-TC) .1.3.6.1.4.1.33333.10.138 |
eHTTPPortEHTTPPort
- Description: HTTP port number
- Modbus address: 0x1125rw Unsigned32 .1.3.6.1.4.1.33333.10.139 |
eMBIPPortEMBIPPort
- Description: Modbus IP port number
- Modbus address: 0x1126rw Unsigned32 .1.3.6.1.4.1.33333.10.140 |
eModbusTcpBridgingEnabledEModbusTcpBridgingEnabled
- Description: Modbus bridging status. 0==disabled, 1==enabled.
- Modbus address: 0x1127rw TruthValue (SNMPv2-TC) .1.3.6.1.4.1.33333.10.141 |
eWirelessEnableEWirelessEnable
- Description: Wireless communications status. If enabled, the wireless radio will be turned on and will advertise for connections, etc. When this value is written, it applies immediately without requiring a reboot. 0==disabled, 1==enabled.
- Modbus address: 0x112brw TruthValue (SNMPv2-TC) .1.3.6.1.4.1.33333.10.142 |
eqtrigEQTRIG
- Description: Manual equalize trigger; true==start equalize, false==stop equalize
- Modbus address: 0x0000rw TruthValue (SNMPv2-TC) .1.3.6.1.4.1.33333.10.500 |
loaddisconnectLOADDISCONNECT
- Description: Load Disconnect (refers to DC load, this shuts down inverting from the battery); true==disconnect, false==reconnect
- Modbus address: 0x0001rw TruthValue (SNMPv2-TC) .1.3.6.1.4.1.33333.10.501 |
chargedisconnectCHARGEDISCONNECT
- Description: Charge disconnect; true==stop charge, false==restart charge
- Modbus address: 0x0002rw TruthValue (SNMPv2-TC) .1.3.6.1.4.1.33333.10.502 |
clearCountersResettableCLEAR_COUNTERS_RESETTABLE
- Description: Resets all resettable counters; true==do action
- Modbus address: 0x0014rw TruthValue (SNMPv2-TC) .1.3.6.1.4.1.33333.10.503 |
clearCountersTotalCLEAR_COUNTERS_TOTAL
- Description: Reset all total counters; true==do action
- Modbus address: 0x0015rw TruthValue (SNMPv2-TC) .1.3.6.1.4.1.33333.10.504 |
clearVbminmaxCLEAR_VBMINMAX
- Description: Clear Vbatt min and max saved values; true==do action
- Modbus address: 0x0016rw TruthValue (SNMPv2-TC) .1.3.6.1.4.1.33333.10.505 |
clearFaultsCLEAR_FAULTS
- Description: Clear faults; true==do action
- Modbus address: 0x0017rw TruthValue (SNMPv2-TC) .1.3.6.1.4.1.33333.10.506 |
clearAlarmsCLEAR_ALARMS
- Description: Clear alarms; true==do action
- Modbus address: 0x0018rw TruthValue (SNMPv2-TC) .1.3.6.1.4.1.33333.10.507 |
eeUpdateEE_UPDATE
- Description: Forces eeprom update of logged variables (hourmeter/vbmin/vbmax/etc); true== do action
- Modbus address: 0x0020rw TruthValue (SNMPv2-TC) .1.3.6.1.4.1.33333.10.508 |
lvdOverrideLVD_OVERRIDE
- Description: Override low voltage disconnect; true==do action
- Modbus address: 0x0021rw TruthValue (SNMPv2-TC) .1.3.6.1.4.1.33333.10.509 |
eepromSessionApplyEEPROM_SESSION_APPLY
- Description: Applies or discards any EEPROM session changes which are pending but not yet written to EE; true==apply changes, false==discard changes. Reading this coil will return non-zero if there are pending changes to be applied, zero if not.
- Modbus address: 0x00fcrw TruthValue (SNMPv2-TC) .1.3.6.1.4.1.33333.10.510 |
resetRESET
- Description: Soft reboot. Resets the controller without power cycling; true==do action
- Modbus address: 0x00ffrw TruthValue (SNMPv2-TC) .1.3.6.1.4.1.33333.10.511 |
setOrClearSocSET_OR_CLEAR_SOC
- Description: Tells the coulomb counting algorithm to either set 100% SOC or clear it; true==set 100% SOC, false==clear SOC (SOC=NAN)
- Modbus address: 0x1104rw TruthValue (SNMPv2-TC) .1.3.6.1.4.1.33333.10.512 |
More MIBs from morningstar
Browse all morningstarMIBs →Standard SNMP MIB module defining data structures for C-PRODUCT-TRAP-MIB.
The PROSTAR-MPPT MIB module enables SNMP-based monitoring and management of Morningstar Prostar Maximum Power Point Tracking (MPPT) solar charge controllers, exposing telemetry for photovoltaic array voltage, current, power output, battery bank status, and system efficiency metrics.
The PROSTAR-PWM MIB module enables SNMP-based monitoring and management of Morningstar Prostar Pulse Width Modulation (PWM) solar charge controllers, exposing device-specific telemetry such as battery voltage, charging current, solar input status, and internal temperature. It facilitates the collection of operational state data and alarm conditions for these specific solar power management devices within a networked infrastructure.
The SUNSAVER-MPPT MIB module enables SNMP-based monitoring and management of Morningstar SunSaver MPPT solar charge controllers, specifically facilitating the retrieval of photovoltaic system telemetry such as input/output voltage, current, power, and battery state-of-charge. This module supports the device's Meterbus interface (Type 5) to aggregate critical charging parameters for remote system health assessment and performance analysis.
The TRISTAR-MPPT MIB module enables SNMP-based monitoring and management of Morningstar TriStar-MPPT solar charge controllers, specifically exposing metrics for photovoltaic input voltage and current, battery bank status, and MPPT tracking efficiency. This module facilitates the collection of real-time operational data and alarm states required for remote system health assessment and performance analysis of solar power installations.
The TRISTAR-MPPT-600V MIB module enables SNMP-based monitoring and management of Morningstar TriStar-MPPT-600V solar charge controllers, specifically exposing photovoltaic input/output parameters such as array voltage, current, power, and MPPT tracking status. It facilitates the collection of real-time telemetry and operational counters required for remote system diagnostics and performance verification of the 600V DC solar charging infrastructure.