TRIPPLITE-MIB

AI MIB Summary

The TRIPPLITE-MIB module enables SNMP-based remote monitoring of Tripplite PowerAlert-managed Uninterruptible Power Supply (UPS) units and power distribution equipment, exposing critical metrics such as battery status, load capacity, input/output voltage, and temperature sensors.

This MIB module defines MIB objects which provide mechanisms for remote management capabilities of Tripplite PowerAlert and related software.
Main OID:
tripplite.1.3.6.1.4.1.850
350
Objects
Active
Status
5
Dependencies

Imported Objects

Objects

350 total
Object Name
trippliteThis MIB module defines MIB objects which provide mechanisms for remote management capabilities of Tripplite PowerAlert and related software.
MODULE-IDENTITY
.1.3.6.1.4.1.850
trippUPS
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.1
tlV11TrapsPrefix
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.1.0
tlV11upsCriticalUPS Critical Alarm.obsolete
NOTIFICATION-TYPE
.1.3.6.1.4.1.850.1.0.100
tlV11upsWarningUPS Warning.obsolete
NOTIFICATION-TYPE
.1.3.6.1.4.1.850.1.0.101
tlV11upsInformationUPS Information.obsolete
NOTIFICATION-TYPE
.1.3.6.1.4.1.850.1.0.102
tlV11upsAlarmClearedUPS Alarm Cleared.obsolete
NOTIFICATION-TYPE
.1.3.6.1.4.1.850.1.0.103
tlV11upsAgentStartedAgent started.obsolete
NOTIFICATION-TYPE
.1.3.6.1.4.1.850.1.0.104
tlV11upsAgentStoppedAgent stopped.obsolete
NOTIFICATION-TYPE
.1.3.6.1.4.1.850.1.0.105
trippUpsReceptacles
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.1.1
upsReceptaclesNumReceptaclesThe number of available receptacles in this device. This variable indicates the number of rows in the receptacle table.roobsolete
NonNegativeInteger (UPS-MIB)
.1.3.6.1.4.1.850.1.1.1
upsReceptacleTableA list of receptacle table entries. The number of entries is given by the value of upsReceptaclesNumReceptacles.obsolete
SEQUENCE OF UpsReceptacleEntry
.1.3.6.1.4.1.850.1.1.2
upsReceptacleEntryAn entry containing information applicable to a particular receptacle.obsolete
UpsReceptacleEntry
.1.3.6.1.4.1.850.1.1.2.1
upsReceptacleIndexThe receptacle identifier.roobsolete
PositiveInteger (UPS-MIB)
.1.3.6.1.4.1.850.1.1.2.1.1
upsReceptacleTypeThe type of receptacle.roobsolete
Enumeration
.1.3.6.1.4.1.850.1.1.2.1.2
upsReceptacleStatusThe status of receptacle.roobsolete
Enumeration
.1.3.6.1.4.1.850.1.1.2.1.3
upsReceptacleControlSetting this object to 'on' will turn on the receptacle. Setting this object to 'off' will turn off the receptacle. Setting this object to 'cycle' will turn off and then turn on the receptacle. This action will only take place if the receptacle is controllable (upsReceptacleType = controllableBatteryProtected(3)).rwobsolete
Enumeration
.1.3.6.1.4.1.850.1.1.2.1.4
trippUpsTrapInfo
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.1.2
upsTrapCodeA numeric code identifiying the condition that caused the trap to be sent. If the trap number is 104 (upsAgentStarted) or 105 (upsAgentStopped), this code will indicate whether the SNMP agent is software (1) or hardware (2).rodeprecated
INTEGER
.1.3.6.1.4.1.850.1.2.1
upsTrapDescriptionThe description of the trap.rodeprecated
DisplayString
.1.3.6.1.4.1.850.1.2.2
trippUpsEnvironment
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.1.3
upsEnvTemperatureThe ambient temperature of the EnviroSense unit (1/10 Deg C).roobsolete
Integer32
.1.3.6.1.4.1.850.1.3.1
upsEnvHumidityThe ambient humidity of the EnviroSense unit (% Humidity).roobsolete
INTEGER
.1.3.6.1.4.1.850.1.3.2
trippUpsContacts
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.1.4
upsContactTableA table of contacts attached to the EnviroSense unit.obsolete
SEQUENCE OF UpsContactEntry
.1.3.6.1.4.1.850.1.4.1
upsContactEntryAn entry containing information applicable to a particular contact.obsolete
UpsContactEntry
.1.3.6.1.4.1.850.1.4.1.1
upsContactIndexThe contact identifier.roobsolete
PositiveInteger (UPS-MIB)
.1.3.6.1.4.1.850.1.4.1.1.1
upsContactNameThe contact name.rwobsolete
DisplayString
.1.3.6.1.4.1.850.1.4.1.1.2
upsContactStatusThe current status of the contact.roobsolete
Enumeration
.1.3.6.1.4.1.850.1.4.1.1.3
upsContactConfigThe default configuration of the contact.rwobsolete
Enumeration
.1.3.6.1.4.1.850.1.4.1.1.4
tlEnumerations
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.2
tlOperatingSystems
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.2.1
hpux9
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.2.1.1
sunos4
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.2.1.2
solaris
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.2.1.3
osf
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.2.1.4
ultrix
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.2.1.5
hpux10
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.2.1.6
netbsd1
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.2.1.7
freebsd
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.2.1.8
irix
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.2.1.9
linux
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.2.1.10
bsdi
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.2.1.11
openbsd
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.2.1.12
win32
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.2.1.13
hpux11
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.2.1.14
win9x
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.2.1.50
winnt
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.2.1.51
solspark
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.2.1.52
solintel
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.2.1.53
aix
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.2.1.54
sco
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.2.1.55
osx
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.2.1.56
unknown
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.2.1.255
tlConformance
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.20
tlCompliances
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.20.1
tlGroups
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.20.2
tlSubsetGroups
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.20.2.1
tlBasicGroups
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.20.2.2
tlFullGroups
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.20.2.3
tlUpsFullGroups
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.20.2.3.100
tlUpsFullIdentGroupThe tlUpsFullIdentGroup defines objects which are common to the Ident group of fully compliant Tripplite UPS's
Unknown
.1.3.6.1.4.1.850.20.2.3.100.1
tlUpsFullBatteryGroupThe tlUpsFullBatteryGroup defines objects which are common to the Battery group of fully compliant Tripplite UPS's
Unknown
.1.3.6.1.4.1.850.20.2.3.100.2
tlUpsFullAlarmGroup
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.20.2.3.100.6
tlUpsFullAlarmObjsGroupThe tlUpsFullAlarmObjsGroup defines objects which are common to the Alarm group of fully compliant Tripplite UPS's
Unknown
.1.3.6.1.4.1.850.20.2.3.100.6.1
tlUpsFullTestGroupThe tlUpsFullTestGroup defines objects which are common to the Test group of fully compliant Tripplite UPS's
Unknown
.1.3.6.1.4.1.850.20.2.3.100.7
tlUpsFullControlGroupThe tlUpsFullControlGroup defines objects which are common to the Control group of fully compliant Tripplite UPS's
Unknown
.1.3.6.1.4.1.850.20.2.3.100.8
tlUpsFullConfigGroupThe tlUpsFullConfigGroup defines objects which are common to the Config group of fully compliant Tripplite UPS's
Unknown
.1.3.6.1.4.1.850.20.2.3.100.9
tlUpsFullOutletGroupThe tlUpsFullOutletGroup defines objects which are common to the Outlet group of fully compliant Tripplite UPS's
Unknown
.1.3.6.1.4.1.850.20.2.3.100.10
tlV11Groups
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.20.2.4
tlDeprecatedV11GroupThe tlDeprecatedV11Group defines objects which were used by Sinetica SNMP cards on Tripplite UPSs and PowerAlert version 11. These objects are currently only used when tlEngineLegacySNMPSupport == true.obsolete
Unknown
.1.3.6.1.4.1.850.20.2.4.1
tlDeprecatedV11NotificationsGroupThe tlDeprecatedV11NotificationsGroup defines PowerAlert version 11 notifications. These notifications are being deprecated, but may still be used when tlEngineLegacySNMPSupport = true.obsolete
Unknown
.1.3.6.1.4.1.850.20.2.4.2
tlObsoleteV11GroupThe tlObsoleteV11Group defines objects which were used by Sinetica SNMP cards on Tripplite UPSs. Most of these objects are obsolete.obsolete
Unknown
.1.3.6.1.4.1.850.20.2.4.3
tlPowerAlert
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.90
tlPASystem
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.90.1
tlPAContacts
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.90.1.1
tlPAEmailContacts
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.90.1.1.1
tlPANumberOfEmailContactsThe number email contacts currently defined.ro
NonNegativeInteger (UPS-MIB)
.1.3.6.1.4.1.850.90.1.1.1.1
tlPAEmailContactsTableA list email contact entries. The number of entries is given by the value of tlPANumberOfEmailContacts.
SEQUENCE OF TlPAEmailContactEntry
.1.3.6.1.4.1.850.90.1.1.1.2
tlPAEmailContactEntryAn entry containing email contacts information.
TlPAEmailContactEntry
.1.3.6.1.4.1.850.90.1.1.1.2.1
tlPAEmailContactIndexThis is the index number of the email contact.ro
PositiveInteger (UPS-MIB)
.1.3.6.1.4.1.850.90.1.1.1.2.1.1
tlPAEmailContactRowStatusThe row status for the tlPAEmailContactTable rowrw
RowStatus (SNMPv2-TC)
.1.3.6.1.4.1.850.90.1.1.1.2.1.2
tlPAEmailContactNameThe name of the email contact.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.850.90.1.1.1.2.1.3
tlPAEmailContactAddressThe address of the email contact.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.850.90.1.1.1.2.1.4
tlPASnmpContacts
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.90.1.1.2
tlPANumberOfSnmpContactsThe number SNMP contacts currently defined.ro
NonNegativeInteger (UPS-MIB)
.1.3.6.1.4.1.850.90.1.1.2.1
tlPASnmpContactsTableA list SNMP contact entries. The number of entries is given by the value of tlPANumberOfSnmpContacts.
SEQUENCE OF TlPASnmpContactEntry
.1.3.6.1.4.1.850.90.1.1.2.2
tlPASnmpContactEntryAn entry containing SNMP contacts information.
TlPASnmpContactEntry
.1.3.6.1.4.1.850.90.1.1.2.2.1
tlPASnmpContactIndexThis is the index number of this SNMP contact.ro
PositiveInteger (UPS-MIB)
.1.3.6.1.4.1.850.90.1.1.2.2.1.1
tlPASnmpContactRowStatusThe row status for the tlPASnmpContactTable rowrw
RowStatus (SNMPv2-TC)
.1.3.6.1.4.1.850.90.1.1.2.2.1.2
tlPASnmpContactNameThe name of the SNMP contact.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.850.90.1.1.2.2.1.3
tlPASnmpContactIpAddressThe IP address of the SNMP contact.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.850.90.1.1.2.2.1.4
tlPASnmpContactPortThe port of the SNMP contact.rw
PositiveInteger (UPS-MIB)
.1.3.6.1.4.1.850.90.1.1.2.2.1.5
tlPASnmpContactSnmpVersionThe SNMP contact version to use for sending traps.rw
Enumeration
.1.3.6.1.4.1.850.90.1.1.2.2.1.6
tlPASnmpContactSecurityNameThe SNMP contact security name.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.850.90.1.1.2.2.1.7
tlPASnmpContactPrivPasswordThe SNMP contact priv password to use for sending V3 traps.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.850.90.1.1.2.2.1.8
tlPASnmpContactAuthPasswordThe SNMP contact auth password to use for sending V3 traps.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.850.90.1.1.2.2.1.9
tlUPS
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.100
tlUpsObjects
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.100.1
tlUpsIdent
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.100.1.1
tlUpsIdentUpsSoftwareChecksumA checksum for the UPS software.ro
Integer32
.1.3.6.1.4.1.850.100.1.1.1
tlUpsIdentSerialNumSerial number for the UPS.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.850.100.1.1.2
tlUpsIdentIDA user-supplied ID for the UPS.rw
Integer32
.1.3.6.1.4.1.850.100.1.1.3
tlUpsSnmpCardSerialNumSerial number for the UPS.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.850.100.1.1.4
tlUpsSelectedDeviceIDThe device ID selected to be used for retrieving data for this mib. As the snmp web card has only one device, this is read only for itrw
Integer32
.1.3.6.1.4.1.850.100.1.1.5
tlUpsLocationThe device location string.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.850.100.1.1.6
tlUpsBattery
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.100.1.2
tlUpsBatteryAgeThe age of the battery in years. This is equal to the current date minus tlConfigBattReplDate.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.850.100.1.2.1
tlUpsTemperatureFThe temperature of the battery, in Farenheight degrees. This is calculated from upsBatteryTemperature, which is in Celsius degrees.ro
Integer32
.1.3.6.1.4.1.850.100.1.2.2
tlUpsInput
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.100.1.3
tlUpsInputNumVoltagesThe number of input voltages. Phase to phase or phase to neutral. This variable indicates the number of rows in the input table.ro
NonNegativeInteger (UPS-MIB)
.1.3.6.1.4.1.850.100.1.3.1
tlUpsInputVoltageTableA list of voltage input table entries. The number of entries is given by the value of tlUpsInputNumVoltages.
SEQUENCE OF TlUpsInputVoltageEntry
.1.3.6.1.4.1.850.100.1.3.2
tlUpsInputVoltageEntryAn entry containing information applicable to a particular input voltage.
TlUpsInputVoltageEntry
.1.3.6.1.4.1.850.100.1.3.2.1
tlUpsInputVoltageIndexThe input voltage identifier.
PositiveInteger (UPS-MIB)
.1.3.6.1.4.1.850.100.1.3.2.1.1
tlUpsInputVoltageTypeWhether voltage measured is phase to phase or phase to neutral.ro
Enumeration
.1.3.6.1.4.1.850.100.1.3.2.1.2
tlUpsInputVoltageThe magnitude of the present input voltage. A value of 6553 indicates Unknown.ro
NonNegativeInteger UNITS "RMS Volts"
.1.3.6.1.4.1.850.100.1.3.2.1.3
tlUpsOutput
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.100.1.4
tlUpsOutputPowerTotalThe power capacity of the device.ro
PositiveInteger (UPS-MIB)
.1.3.6.1.4.1.850.100.1.4.5
tlUpsOutputCircuitsThe number of output circuits. This variable indicates the number of rows in the output circuit table.ro
NonNegativeInteger (UPS-MIB)
.1.3.6.1.4.1.850.100.1.4.6
tlUpsOutputCircuitTableA list of output currents table entries. The number of entries is given by the value of tlUpsOutputNumCircuits.
SEQUENCE OF TlUpsOutputCircuitEntry
.1.3.6.1.4.1.850.100.1.4.7
tlUpsOutputCircuitEntryAn entry containing information applicable to a particular output circuit.
TlUpsOutputCircuitEntry
.1.3.6.1.4.1.850.100.1.4.7.1
tlUpsOutputCircuitIndexThe output circuit identifier.
PositiveInteger (UPS-MIB)
.1.3.6.1.4.1.850.100.1.4.7.1.1
tlUpsOutputCircuitStatusWhether the breaker is open or closed.ro
Enumeration
.1.3.6.1.4.1.850.100.1.4.7.1.2
tlUpsOutputCircuitLoadCurrentThe magnitude of the present output current in tenths of an amp. A value of 65534 indicates Unknown.ro
NonNegativeInteger UNITS "Tenths of Amperes"
.1.3.6.1.4.1.850.100.1.4.7.1.3
tlUpsAlarm
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.100.1.6
tlUpsAlarmsPresentThe present number of active alarm conditions.ro
Gauge32
.1.3.6.1.4.1.850.100.1.6.1
tlUpsAlarmTableA list of alarm table entries.
SEQUENCE OF TlUpsAlarmEntry
.1.3.6.1.4.1.850.100.1.6.2
tlUpsAlarmEntryAn entry containing information applicable to a particular alarm.
TlUpsAlarmEntry
.1.3.6.1.4.1.850.100.1.6.2.1
tlUpsAlarmIdA unique identifier for an alarm condition.ro
PositiveInteger (UPS-MIB)
.1.3.6.1.4.1.850.100.1.6.2.1.1
tlUpsAlarmDescrA description of the alarm condition.ro
AutonomousType (SNMPv2-TC)
.1.3.6.1.4.1.850.100.1.6.2.1.2
tlUpsAlarmTimeThe value of sysUpTime when the alarm condition was detected.ro
TimeStamp (SNMPv2-TC)
.1.3.6.1.4.1.850.100.1.6.2.1.3
tlUpsAlarmDetailA textual description of the alarm condition.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.850.100.1.6.2.1.4
tlUpsAlarmDeviceIdA numeric identifier for the device on which the alarm is active.ro
PositiveInteger (UPS-MIB)
.1.3.6.1.4.1.850.100.1.6.2.1.5
tlUpsAlarmDeviceNameA string identifier for the device on which the alarm is active.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.850.100.1.6.2.1.6
tlUpsAlarmLocationThe location of the device on which the alarm is active.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.850.100.1.6.2.1.7
tlUpsAlarmGroupThe category/group of this alarm.ro
Enumeration
.1.3.6.1.4.1.850.100.1.6.2.1.8
tlUpsAlarmIpThe originating IP address associated with this alarm.ro
IpAddress
.1.3.6.1.4.1.850.100.1.6.2.1.9
tlUpsAlarmMacThe originating mac address associated with this alarm.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.850.100.1.6.2.1.10
tlUpsWellKnownAlarms
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.100.1.6.3
tlUpsAlarmPrimaryPowerOutageThe primary power source is not present.
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.100.1.6.3.1
tlUpsAlarmSecondaryPowerOutageThe secondary power source is not present.
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.100.1.6.3.2
tlUpsAlarmLoadLevelAboveThresholdThe load level is above the designated threshold.
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.100.1.6.3.3
tlUpsAlarmOutputCurrentChangedThe output current changed from its last known value.
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.100.1.6.3.4
tlUpsAlarmBatteryAgeAboveThresholdOne or more batteries have been determined to require replacement.
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.100.1.6.3.5
tlUpsAlarmLoadOffThe load is off.
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.100.1.6.3.6
tlUpsAlarmUserDefinedA user-defined event is in alarm.
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.100.1.6.3.7
tlUpsAlarmBatteryBadOne or more batteries have been determined to require replacement.
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.100.1.6.3.8
tlUpsAlarmOnBatteryThe UPS is drawing power from the batteries.
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.100.1.6.3.9
tlUpsAlarmLowBatteryThe remaining battery run-time is less than or equal to upsConfigLowBattTime.
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.100.1.6.3.10
tlUpsAlarmDepletedBatteryThe UPS will be unable to sustain the present load when and if the utility power is lost.
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.100.1.6.3.11
tlUpsAlarmTempBadA temperature is out of tolerance.
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.100.1.6.3.12
tlUpsAlarmInputBadAn input condition is out of tolerance.
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.100.1.6.3.13
tlUpsAlarmOutputBadAn output condition (other than OutputOverload) is out of tolerance.
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.100.1.6.3.14
tlUpsAlarmOutputOverloadThe output load exceeds the UPS output capacity.
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.100.1.6.3.15
tlUpsAlarmOnBypassThe Bypass is presently engaged on the UPS.
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.100.1.6.3.16
tlUpsAlarmBypassBadThe Bypass is out of tolerance.
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.100.1.6.3.17
tlUpsAlarmOutputOffAsRequestedThe UPS has shutdown as requested, i.e., the output is off.
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.100.1.6.3.18
tlUpsAlarmUpsOffAsRequestedThe entire UPS has shutdown as commanded.
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.100.1.6.3.19
tlUpsAlarmChargerFailedAn uncorrected problem has been detected within the UPS charger subsystem.
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.100.1.6.3.20
tlUpsAlarmUpsOutputOffThe output of the UPS is in the off state.
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.100.1.6.3.21
tlUpsAlarmUpsSystemOffThe UPS system is in the off state.
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.100.1.6.3.22
tlUpsAlarmFanFailureThe failure of one or more fans in the UPS has been detected.
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.100.1.6.3.23
tlUpsAlarmFuseFailureThe failure of one or more fuses has been detected.
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.100.1.6.3.24
tlUpsAlarmGeneralFaultA general fault in the UPS has been detected.
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.100.1.6.3.25
tlUpsAlarmDiagnosticTestFailedThe result of the last diagnostic test indicates a failure.
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.100.1.6.3.26
tlUpsAlarmCommunicationsLostA problem has been encountered in the communications between the agent and the UPS.
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.100.1.6.3.27
tlUpsAlarmAwaitingPowerThe UPS output is off and the UPS is awaiting the return of input power.
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.100.1.6.3.28
tlUpsAlarmShutdownPendingA upsShutdownAfterDelay countdown is underway.
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.100.1.6.3.29
tlUpsAlarmShutdownImminentThe UPS will turn off power to the load in less than 5 seconds; this may be either a timed shutdown or a low battery shutdown.
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.100.1.6.3.30
tlUpsAlarmTestInProgressA test is in progress, as initiated and indicated by the Test Group. Tests initiated via other implementation-specific mechanisms can indicate the presence of the testing in the alarm table, if desired, via a OBJECT-IDENTITY macro in the MIB document specific to that implementation and are outside the scope of this OBJECT-IDENTITY.
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.100.1.6.3.31
tlUpsAlarmCircuitBreaker1OpenCircuit breakers #1 is open.
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.100.1.6.3.32
tlUpsAlarmCircuitBreaker2OpenCircuit breakers #2 is open.
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.100.1.6.3.33
tlUpsAlarmCircuitBreaker3OpenCircuit breakers #3 is open.
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.100.1.6.3.34
tlUpsAlarmCircuitBreaker4OpenCircuit breakers #4 is open.
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.100.1.6.3.35
tlUpsAlarmCircuitBreaker5OpenCircuit breakers #5 is open.
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.100.1.6.3.36
tlUpsAlarmCircuitBreaker6OpenCircuit breakers #6 is open.
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.100.1.6.3.37
tlUpsAlarmCircuitBreaker7OpenCircuit breakers #7 is open.
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.100.1.6.3.38
tlUpsAlarmCircuitBreaker8OpenCircuit breakers #8 is open.
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.100.1.6.3.39
tlUpsAlarmCurrent1AboveThresholdThe output current on line 1 exceeds load limits.
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.100.1.6.3.40
tlUpsAlarmCurrent2AboveThresholdThe output current on line 2 exceeds load limits.
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.100.1.6.3.41
tlUpsAlarmCurrent3AboveThresholdThe output current on line 3 exceeds load limits.
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.100.1.6.3.42
tlUpsAlarmDevNameThe name of the device, tlDevName, corresponding to the device that is associated with this alarm.rodeprecated
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.850.100.1.6.7
tlUpsAlarmDevLocationThe location of the device, tlDevLocation, corresponding to the device that is associated with this alarm.rodeprecated
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.850.100.1.6.8
tlUpsAlarmCategoryThe category, tlDevEvtCategory, of this alarm.rodeprecated
Integer32
.1.3.6.1.4.1.850.100.1.6.9
tlUpsTest
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.100.1.7
tlUpsTestDateThe date of the last self-test run on the ups, in the format YYYYMMDD.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.850.100.1.7.1
tlUpsTestResultsDetailResult of the last self-test run on the ups.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.850.100.1.7.2
tlUpsControl
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.100.1.8
tlUpsWatchdogSupportedIndicates whether or not this UPS supports a watchdog reboot.ro
TruthValue (SNMPv2-TC)
.1.3.6.1.4.1.850.100.1.8.1
tlUpsWatchdogSecsBeforeRebootThe maximum number of seconds that can expire between polls that the engine makes to the UPS for data. If this time runs out, then the UPS will cycle its outputs. Set this to zero to turns disable this feature.rw
NonNegativeInteger (UPS-MIB)
.1.3.6.1.4.1.850.100.1.8.2
tlUpsWellKnownControls
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.100.1.8.3
tlUpsControlSelfTestSet to TRUE to initiate Self Testrw
TruthValue (SNMPv2-TC)
.1.3.6.1.4.1.850.100.1.8.3.1
tlUpsControlRampSet to TRUE to initiate Ramprw
TruthValue (SNMPv2-TC)
.1.3.6.1.4.1.850.100.1.8.3.2
tlUpsControlShedSet to TRUE to initiate Shedrw
TruthValue (SNMPv2-TC)
.1.3.6.1.4.1.850.100.1.8.3.3
tlUpsControlUpsOnSet to TRUE to turn UPS onrw
TruthValue (SNMPv2-TC)
.1.3.6.1.4.1.850.100.1.8.3.4
tlUpsControlUpsOffSet to TRUE to turn UPS offrw
TruthValue (SNMPv2-TC)
.1.3.6.1.4.1.850.100.1.8.3.5
tlUpsConfig
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.100.1.9
tlUpsConfigBattReplDateThe date on which the battery was last replaced, in the format YYYYMMDD.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.850.100.1.9.1
tlUpsOutlet
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.100.1.10
tlUpsOutletNumOutletsThe number of available Outlets in this device.ro
NonNegativeInteger (UPS-MIB)
.1.3.6.1.4.1.850.100.1.10.1
tlUpsOutletTableA list of all device Outlets for all devices.
SEQUENCE OF TlUpsOutletEntry
.1.3.6.1.4.1.850.100.1.10.2
tlUpsOutletEntryAn entry containing Outlet information applicable to a particular device managed by this agent.
TlUpsOutletEntry
.1.3.6.1.4.1.850.100.1.10.2.1
tlUpsOutletIndexThis is the index number of this Outlet for the device indicated by tlDeviceIndex.ro
PositiveInteger (UPS-MIB)
.1.3.6.1.4.1.850.100.1.10.2.1.1
tlUpsOutletStateThe current state of the Outlet.ro
Enumeration
.1.3.6.1.4.1.850.100.1.10.2.1.2
tlUpsOutletTypeThis is a bit field that indicates the type of this Outlet. When 0, the outlet is not controllable and has none of the other features indicated in the bit map. When non-zero, the features present for this outlet can be interpreted with the definition. Bit Display 0 Reserved, may be 1 or 0 1 Controllable 2 3 4 5 6 7 8 9 10 11 12 13 14 15ro
Integer32
.1.3.6.1.4.1.850.100.1.10.2.1.3
tlUpsOutletControlControls the state of the Outlet.rw
Enumeration
.1.3.6.1.4.1.850.100.1.10.2.1.4
tlUpsOutletNameA string identifying the devices attached to the output(s) of the device.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.850.100.1.10.2.1.5
tlUpsOutletRampActionThe ramp action to take on the Outlet.rw
Enumeration
.1.3.6.1.4.1.850.100.1.10.2.1.6
tlUpsOutletRampDataTypeThe type of data associated with ramp action.rw
Enumeration
.1.3.6.1.4.1.850.100.1.10.2.1.7
tlUpsOutletRampDataThe data value associated with type of ramp data.rw
Integer32
.1.3.6.1.4.1.850.100.1.10.2.1.8
tlUpsOutletShedActionThe shed action to take on the Outlet.rw
Enumeration
.1.3.6.1.4.1.850.100.1.10.2.1.9
tlUpsOutletShedDataTypeThe type of data associated with shed action.rw
Enumeration
.1.3.6.1.4.1.850.100.1.10.2.1.10
tlUpsOutletShedDataThe data value associated with type of shed data.rw
Integer32
.1.3.6.1.4.1.850.100.1.10.2.1.11
tlUpsOutletGroupNdxtlUpsOutletGroupIndex of corresponding outlet group, or 0 if ungrouped.rw
Integer32
.1.3.6.1.4.1.850.100.1.10.2.1.12
tlUpsOutletCurrentThe value of this outlet's current, represented as 0.1A.ro
PositiveInteger UNITS "0.1 RMS Amp"
.1.3.6.1.4.1.850.100.1.10.2.1.13
tlUpsOutletPowerThe value of this outlet's power in watts.ro
PositiveInteger (UPS-MIB)
.1.3.6.1.4.1.850.100.1.10.2.1.14
tlUpsOutletGroup
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.100.1.11
tlUpsOutletNumOutletGroupsThe number of available Outlet Groups in this device.ro
NonNegativeInteger (UPS-MIB)
.1.3.6.1.4.1.850.100.1.11.1
tlUpsOutletGroupTableA list of device outlet group entries. The number of entries is given by the value of tlUpsOutletNumOutletGroups.
SEQUENCE OF TlUpsOutletGroupEntry
.1.3.6.1.4.1.850.100.1.11.2
tlUpsOutletGroupEntryAn entry containing outlet group information applicable to a particular device managed by this agent
TlUpsOutletGroupEntry
.1.3.6.1.4.1.850.100.1.11.2.1
tlUpsOutletGroupIndexThis is the index number of this load group for the device.ro
PositiveInteger (UPS-MIB)
.1.3.6.1.4.1.850.100.1.11.2.1.1
tlUpsOutletGroupRowStatusRow status for the tlUpsOutletGroupTablerw
RowStatus (SNMPv2-TC)
.1.3.6.1.4.1.850.100.1.11.2.1.2
tlUpsOutletGroupNameThe name of this outlet group.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.850.100.1.11.2.1.3
tlUpsOutletGroupDescA description for this outlet group.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.850.100.1.11.2.1.4
tlUpsOutletGroupStateThe current state of the outlet group.ro
Enumeration
.1.3.6.1.4.1.850.100.1.11.2.1.5
tlUpsOutletGroupControlControls the state of every outlet associated with the group.rw
Enumeration
.1.3.6.1.4.1.850.100.1.11.2.1.6
tlUpsMainOutlet
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.100.1.12
tlUpsMainOutletStateThe current state of the main output of the device.ro
Enumeration
.1.3.6.1.4.1.850.100.1.12.1
tlUpsMainOutletControllableIndicates if this device has controllable outletsro
TruthValue (SNMPv2-TC)
.1.3.6.1.4.1.850.100.1.12.2
tlUpsMainOutletControlControls the state of the main outlet of the device.rw
Enumeration
.1.3.6.1.4.1.850.100.1.12.3
tlUpsTraps
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.100.2
tlUpsTrapAlarmEntryAddedV1This trap is sent each time an alarm is inserted into to the alarm table.
NOTIFICATION-TYPE
.1.3.6.1.4.1.850.100.2.0.3
tlUpsTrapAlarmEntryRemovedV1This trap is sent each time an alarm is removed from the alarm table.
NOTIFICATION-TYPE
.1.3.6.1.4.1.850.100.2.0.4
tlUpsTrapAlarmEntryAddedThis trap is sent each time an alarm is inserted into to the alarm table.
NOTIFICATION-TYPE
.1.3.6.1.4.1.850.100.2.3
tlUpsTrapAlarmEntryRemovedThis trap is sent each time an alarm is removed from the alarm table.
NOTIFICATION-TYPE
.1.3.6.1.4.1.850.100.2.4
tlUpsTrapSystemStartupUsed to inform another entity of an engine's startup. The varbinds that follow are: OBJ1 = tlEngineType Obj1Value = The type of engine providing this data OBJ2 = tlEngineSoftwareVersion Obj2Value = The current version of the engine OBJ3 = tlEngineMACAddr Obj3Value = The MAC address of the engine OBJ4 = tlUpsSnmpCardSerialNum Obj4Value = The serial number of the SNMPWEBCARD [should be 0 on PC] --- if this trap is extended, place all static OIDs above this mark. all objects below --- the number of devices (tlNumDevices) is explicit as per device for enumeration by --- the target receiver OBJ5 = tlNumDevices Obj5Value = The number of devices attached --- The following objects will be replicated per each device: OBJ6 = The OID for an entry of tlDevManufacturer, indexed by device Obj6Value = The device's manufacturer OBJ7 = The OID for an entry of tlDevModel, indexed by device Obj7Value = The device's model name OBJ8 = The OID for an entry of tlDevName, indexed by device Obj8Value = The device's display name OBJ9 = The OID for an entry of tlDevLocation, indexed by device Obj9Value = The device's location OBJ10 = The OID for an entry of tlDevRegion, indexed by device Obj10Value= The device's region OBJ11 = The OID for an entry of tlDevProtocol, indexed by device Obj11Value= The device's protocol (display string format)
NOTIFICATION-TYPE
.1.3.6.1.4.1.850.100.2.5
tlUpsTrapSystemShutdownUsed to inform another entity of an engine's startup. The varbinds that follow are: OBJ1 = tlEngineType Obj1Value = The type of engine providing this data OBJ2 = tlEngineSoftwareVersion Obj2Value = The current version of the engine OBJ3 = tlEngineMACAddr Obj3Value = The MAC address of the engine OBJ4 = tlUpsSnmpCardSerialNum Obj4Value = The serial number of the SNMPWEBCARD [should be 0 on PC] --- if this trap is extended, place all static OIDs above this mark. all objects below --- the number of devices (tlNumDevices) is explicit as per device for enumeration by --- the target receiver OBJ5 = tlNumDevices Obj5Value = The number of devices attached --- The following objects will be replicated per each device: OBJ6 = The OID for an entry of tlDevManufacturer, indexed by device Obj6Value = The device's manufacturer OBJ7 = The OID for an entry of tlDevModel, indexed by device Obj7Value = The device's model name OBJ8 = The OID for an entry of tlDevName, indexed by device Obj8Value = The device's display name OBJ9 = The OID for an entry of tlDevLocation, indexed by device Obj9Value = The device's location OBJ10 = The OID for an entry of tlDevRegion, indexed by device Obj10Value= The device's region OBJ11 = The OID for an entry of tlDevProtocol, indexed by device Obj11Value= The device's protocol (display string format)
NOTIFICATION-TYPE
.1.3.6.1.4.1.850.100.2.6
tlEnviroSense
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.101
tlEnvEnvironment
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.101.1
tlEnvTemperatureData
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.101.1.1
tlEnvTemperatureCThe ambient temperature (C).ro
Integer32
.1.3.6.1.4.1.850.101.1.1.1
tlEnvTemperatureFThe ambient temperature (F).ro
Integer32
.1.3.6.1.4.1.850.101.1.1.2
tlEnvTemperatureLowLimitThe lower alarm limit for ambient temperature (F).rw
Integer32
.1.3.6.1.4.1.850.101.1.1.3
tlEnvTemperatureHighLimitThe upper alarm limit for ambient temperature (F).rw
Integer32
.1.3.6.1.4.1.850.101.1.1.4
tlEnvTemperatureInAlarmIndicates whether or not temperature is in alarm.ro
TruthValue (SNMPv2-TC)
.1.3.6.1.4.1.850.101.1.1.5
tlEnvHumidityData
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.101.1.2
tlEnvHumidityThe ambient humidity (%).ro
Integer32
.1.3.6.1.4.1.850.101.1.2.1
tlEnvHumidityLowLimitThe lower alarm limit for ambient humidity (%).rw
Integer32
.1.3.6.1.4.1.850.101.1.2.2
tlEnvHumidityHighLimitThe upper alarm limit for ambient humidity (%).rw
Integer32
.1.3.6.1.4.1.850.101.1.2.3
tlEnvHumidityInAlarmIndicates whether or not humidity is in alarm.ro
TruthValue (SNMPv2-TC)
.1.3.6.1.4.1.850.101.1.2.4
tlEnvContacts
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.101.2
tlEnvContactTableA table of contacts.
SEQUENCE OF TlEnvContactEntry
.1.3.6.1.4.1.850.101.2.1
tlEnvContactEntryAn entry containing information applicable to a particular contact.
TlEnvContactEntry
.1.3.6.1.4.1.850.101.2.1.1
tlEnvContactIndexThe table row index for the contact.ro
PositiveInteger (UPS-MIB)
.1.3.6.1.4.1.850.101.2.1.1.1
tlEnvContactNameThe name or description of the contact.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.850.101.2.1.1.2
tlEnvContactStatusThe current status of the contact.ro
Enumeration
.1.3.6.1.4.1.850.101.2.1.1.3
tlEnvContactConfigThe configuration of the contact.rw
Enumeration
.1.3.6.1.4.1.850.101.2.1.1.4
tlCooling
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.103
tlCoolingEnvironment
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.103.1
tlCoolingIdent
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.103.1.1
tlCoolingModelThe model name for the AC Unit.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.850.103.1.1.1
tlCoolingManufacturerThe manufacturer of the AC Unit.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.850.103.1.1.2
tlCoolingSerialNumberThe serial number of the AC unit.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.850.103.1.1.3
tlCoolingFirmwareVersionThe firmware version of the AC Unit.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.850.103.1.1.4
tlCoolingHostSoftwareVersionThe hardware version of the AC unit.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.850.103.1.1.5
tlCoolingNameThe user defined name for the AC Unit.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.850.103.1.1.6
tlCoolingLocationThe user defined location of the AC Unit.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.850.103.1.1.7
tlCoolingStatus
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.103.1.2
tlCoolingCondOutletTempThe condenser outlet air stream temperature in tenths of degrees in the units Celcius/Fahrenheit as specified in tlCoolingDisplayUnits.ro
INTEGER
.1.3.6.1.4.1.850.103.1.2.1
tlCoolingCondInletTempThe condenser inlet air stream temperature in tenths of degrees in the units Celcius/Fahrenheit as specified in tlCoolingDisplayUnits.ro
INTEGER
.1.3.6.1.4.1.850.103.1.2.2
tlCoolingRefrigerantTempThe temperature of the refrigerant in the suction line. This is displayed in tenths of degrees in the units Celcius/Fahrenheit as specified in tlCoolingDisplayUnits.ro
INTEGER
.1.3.6.1.4.1.850.103.1.2.3
tlCoolingEvapSurfaceTempThe surface temperature of the evaporator in tenths of degrees in the units Celcius/Fahrenheit as specified in tlCoolingDisplayUnits.ro
INTEGER
.1.3.6.1.4.1.850.103.1.2.4
tlCoolingSuctionPressureThe pressure of the compressor suction line in tenths of (Mpa/psi) depending on the value of tlCoolingDisplayUnits.ro
INTEGER
.1.3.6.1.4.1.850.103.1.2.5
tlCoolingDischargePressureThe pressure of the compressor discharge line in tenths of (Mpa/psi) depending on the value of tlCoolingDisplayUnits.ro
INTEGER
.1.3.6.1.4.1.850.103.1.2.6
tlCoolingEvapFanSpeedThe current speed of the evaporator fan.ro
Enumeration
.1.3.6.1.4.1.850.103.1.2.7
tlCoolingCondFanSpeedThe current speed of the condenser fan.ro
Enumeration
.1.3.6.1.4.1.850.103.1.2.8
tlCoolingCompFrequencyThe operating frequency of the compressor in tenths of Arms.ro
INTEGER
.1.3.6.1.4.1.850.103.1.2.9
tlCoolingEEVPercentageThe opening percentage of the EEV.ro
INTEGER
.1.3.6.1.4.1.850.103.1.2.10
tlCoolingUnitCurrentThe the total current draw of the unit in tenths of Arms.ro
INTEGER
.1.3.6.1.4.1.850.103.1.2.11
tlCoolingFanCurrentThethe current draw of the Evaporator and Condenser fans in tents of Arms.ro
INTEGER
.1.3.6.1.4.1.850.103.1.2.12
tlCoolingCompCurrentThe operating current of the compressor in Arms.ro
INTEGER
.1.3.6.1.4.1.850.103.1.2.13
tlCoolingReturnAirTempThe return air temperature in tenths of degrees in the units Celcius/Fahrenheit as specified in tlCoolingDisplayUnits.ro
INTEGER
.1.3.6.1.4.1.850.103.1.2.14
tlCoolingSuctionTempThe temperature of the compressor suction line in tenths of degrees in the units Celcius/Fahrenheit as specified in tlCoolingDisplayUnits.ro
INTEGER
.1.3.6.1.4.1.850.103.1.2.15
tlCoolingSupplyAirTempThe supply air temperature in tenths of degrees in the units Celcius/Fahrenheit as specified in tlCoolingDisplayUnits.ro
INTEGER
.1.3.6.1.4.1.850.103.1.2.16
tlCoolingRunTimes
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.103.1.3
tlCoolingAirFilterRunHoursTotal hours the air filter has been under operation.ro
Integer32
.1.3.6.1.4.1.850.103.1.3.1
tlCoolingEvapFanRunDaysTotal days the evaporator fan has been under operation.ro
Integer32
.1.3.6.1.4.1.850.103.1.3.2
tlCoolingCondFanRunDaysTotal days the condenser fan has been under operation.ro
Integer32
.1.3.6.1.4.1.850.103.1.3.3
tlCoolingCompressorRunDaysTotal days the compressor has been under operation.ro
Integer32
.1.3.6.1.4.1.850.103.1.3.4
tlCoolingCondPumpRunDaysTotal days the condensate pump has been under operation.ro
Integer32
.1.3.6.1.4.1.850.103.1.3.5
tlCoolingAtomizerRunDaysTotal days the atomizer has been under operation.ro
Integer32
.1.3.6.1.4.1.850.103.1.3.6
tlCoolingConfig
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.103.1.4
tlCoolingOnOffTurn the unit off or on.rw
Enumeration
.1.3.6.1.4.1.850.103.1.4.1
tlCoolingSetPointTempThe set point temperature the unit will control the temperature to in tenths of degrees in Celcius or Fahrenheit based upon tleCoolDisplayUnits.rw
INTEGER
.1.3.6.1.4.1.850.103.1.4.2
tlCoolingAutoStartSpecified if the unit should start automatically on power up.rw
Enumeration
.1.3.6.1.4.1.850.103.1.4.3
tlCoolingFanSpeedOverrideSpeed of evaporator fan set by the user.rw
Enumeration
.1.3.6.1.4.1.850.103.1.4.4
tlCoolingControlTypeWhich temperature to be used as a control point.rw
Enumeration
.1.3.6.1.4.1.850.103.1.4.5
tlCoolingCurrentRemoteTempThe external remote temperature in tenths of degrees in Celcius or Fahrenheit depending upon value of tlCoolingDisplayUnitsrw
INTEGER
.1.3.6.1.4.1.850.103.1.4.6
tlCoolingDisplayUnitsSelects English or Metric display for all readings.rw
Enumeration
.1.3.6.1.4.1.850.103.1.4.7
tlCoolingBeepOnKeyIndicates if the display sounds a beep when a key is pressed.rw
Enumeration
.1.3.6.1.4.1.850.103.1.4.8
tlCoolingOutputRelaySourceThe alarm level that causes the ouput relay to activate.rw
Enumeration
.1.3.6.1.4.1.850.103.1.4.9
tlCoolingOffOnLeakIndicates if the unit should stop cooling when leak input is activated.rw
Enumeration
.1.3.6.1.4.1.850.103.1.4.10
tlCoolingOffOnInputContactIndicates if the unit should stop cooling when input contact is activated.rw
Enumeration
.1.3.6.1.4.1.850.103.1.4.11
tlCoolingInputContactTypeThe input contact type.rw
Enumeration
.1.3.6.1.4.1.850.103.1.4.12
tlCoolingOutputRelayDefaultType of contact to make when output relay is activated.rw
Enumeration
.1.3.6.1.4.1.850.103.1.4.13
tlCoolingAirFilterIntervalThe number of weeks before the air filter needs to be changed.rw
Integer32
.1.3.6.1.4.1.850.103.1.4.14
tlCoolingWaterLeakContactTypeThe input contact type.rw
Enumeration
.1.3.6.1.4.1.850.103.1.4.15
tlCoolingThresholds
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.103.1.5
tlCoolingMaxAirFilterRunHoursThe maximum interval for air filter run hours before warning is annunciated.rw
Integer32
.1.3.6.1.4.1.850.103.1.5.1
tlCoolingEnableAirFilterAlarmWhen enabled indicated that an alarm should occur when the maximum number of air filter run hours has been exceeded.rw
Enumeration
.1.3.6.1.4.1.850.103.1.5.2
tlCoolingMaxSupplyTempMaximum allowed supply air temperature before firing an alarm.rw
INTEGER
.1.3.6.1.4.1.850.103.1.5.3
tlCoolingMinSupplyTempMinimum allowed supply air temperature allowed before firing an alarm.rw
INTEGER
.1.3.6.1.4.1.850.103.1.5.4
tlCoolingTempDiffAlarmMaximum allowed air temperature deviation from set allowed before firing an alarm.rw
INTEGER
.1.3.6.1.4.1.850.103.1.5.5
tlCoolingMaxReturnAirTempWhen enabled indicated that an alarm should occur when the maximum number of air filter run hours has been exceeded.rw
INTEGER
.1.3.6.1.4.1.850.103.1.5.6
tlCoolingAlarm
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.103.6
tlCoolingWellKnownAlarms
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.103.6.3
tlCoolingSupplyAirSensorFaultThe supply air sensor is in fault.
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.103.6.3.1
tlCoolingReturnAirSensorFaultThe return air sensor is in fault.
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.103.6.3.2
tlCoolingCondenserInletAirSensorFaultThe condenser inlet air sensor is in fault.
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.103.6.3.3
tlCoolingCondenserOutletAirSensorFaultThe condenser outlet air sensor is in fault.
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.103.6.3.4
tlCoolingSuctionTemperatureSensorFaultThe suction temperature sensor is in fault.
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.103.6.3.5
tlCoolingEvaporatorTemperatureSensorFaultThe evaporator temperature sensor is in fault.
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.103.6.3.6
tlCoolingAirFilterCloggedThe air filter is clogged.
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.103.6.3.7
tlCoolingAirFilterRunHoursViolationThe air filter run hours was violated.
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.103.6.3.8
tlCoolingSuctionPressureSensorFaultThe suction pressure sensor is in fault.
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.103.6.3.9
tlCoolingInverterCommunicationsFaultThe inverter communications is in fault.
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.103.6.3.10
tlCoolingRemoteShutdownViaInputContactA remote shutdown was triggerd by an input contact.
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.103.6.3.11
tlCoolingCondensatePumpFaultThe condensate pump is in fault.
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.103.6.3.12
tlCoolingLowRefrigerantStartupFaultThe low refrigerant startup is in fault.
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.103.6.3.13
tlCoolingCondenserFanFaultThe condenser fan is in fault.
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.103.6.3.14
tlCoolingCondenserFailureThe condenser has failed.
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.103.6.3.15
tlCoolingEvaporatorCoolingFailureThe evaporator cooling is in fault.
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.103.6.3.16
tlCoolingReturnAirTempHighThe return air temperature is high.
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.103.6.3.17
tlCoolingSupplyAirTempHighThe supply air temperature is high.
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.103.6.3.18
tlCoolingEvaporatorFailureThe evaporator has failed.
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.103.6.3.19
tlCoolingEvaporatorFreezeUpThe evaporator is frozen.
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.103.6.3.20
tlCoolingDischargePressureHighThe discharge pressure is high.
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.103.6.3.21
tlCoolingPressureGaugeFailureThe pressure gauge has failed.
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.103.6.3.22
tlCoolingDischargePressurePersistentHighThe discharge pressure is persistently high.
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.103.6.3.23
tlCoolingSuctionPressureLowStartFailureCannot start due to low suction pressure.
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.103.6.3.24
tlCoolingSuctionPressureLowThe suction pressure is low.
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.103.6.3.25
tlCoolingSuctionPressurePersistentLowThe suction pressure is persistently low.
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.103.6.3.26
tlCoolingStartupLinePressureImbalanceThe startup line pressure is in imbalance.
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.103.6.3.27
tlCoolingCompressorFailureThe compressor has failed.
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.103.6.3.28
tlCoolingCurrentLimitThe current is out of range.
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.103.6.3.29
tlCoolingWaterLeakWater is leaking.
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.103.6.3.30
tlCoolingFanUnderCurrentThe fan is under current.
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.103.6.3.31
tlCoolingFanOverCurrentThe fan is over current.
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.103.6.3.32
tlCoolingDischargePressureSensorFaultThe discharge pressure sensor is in fault.
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.103.6.3.33
tlCoolingWaterFullWater is Full.
OBJECT IDENTIFIER
.1.3.6.1.4.1.850.103.6.3.34