SITEBOSS-360-STD-MIB
AI MIB Summary
The SITEBOSS-360-STD-MIB module enables SNMP-based monitoring and management of Asentria SiteBoss 360 wireless access points and controllers, exposing critical operational metrics including RF channel utilization, transmit power levels, client association states, and interface traffic statistics.
MIB module for managing Asentria SiteBoss 360
Main OID:
s360.1.3.6.1.4.1.3052.23
2241
Objects
Active
Status
3
Dependencies
Imported Objects
Objects
2241 total| Object Name |
|---|
s360MIB module for managing Asentria SiteBoss 360 MODULE-IDENTITY .1.3.6.1.4.1.3052.23 |
s360notifications OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.0 |
s360StockSensorUnresponsiveTrapA stock unresponsive trap is issued when a sensor is unresponsive. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.50 |
s360notificationsStockContactClosureTrapA stock contact closure trap is issued when a contact closure event happens. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.110 |
s360notificationsStockTempTrapA stock temperature trap is issued when a temperature event happens. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.120 |
s360notificationsStockHumidityTrapA stock humidity trap is issued when a humidity event happens. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.130 |
s360notificationsStockAnalogTrapA stock analog trap is issued when an analog sensor event happens. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.140 |
s360notificationsStockOutputTrapA stock output trap is issued when an output event happens. That is, depending on the configuration, when an output changes state for any reason, this trap will be sent. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.150 |
s360StockPDCurrentTrapA stock analog trap is issued when a power distribution current event happens. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.180 |
s360StockPDVoltageTrapA stock analog trap is issued when a power distribution voltage event happens. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.190 |
s360StockPDFuseTrapA stock analog trap is issued when a power distribution fuse event happens. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.210 |
s360notificationsStockDbasePfullTrapThe stock database percent full trap is issued when the database size surpasses the threshold. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.501 |
s360notificationsStockDataAlarmTrapThe stock data alarm trap is issued when a data alarm happens. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.503 |
s360notificationsStockNoDataAlarmTrapThe stock no-data alarm trap is issued when the unit has received no data for a configured interval within a configured schedule. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.505 |
s360notificationsStockSchedTrapThe stock scheduled alarm trap is issued when the current time reaches the scheduled alarm time. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.506 |
s360notificationsStockImmediateTrapThe stock immediate alarm trap is issued when the user enters the DOTRAP command. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.507 |
s360StockBattRunningTrapThe stock trap issued when the battery power state change. Gives the unit name, percentage charge of the battery and if unit is running on battery backup (0 is False and 1 is True) NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.508 |
s360notificationsStockCTSTrapA stock CTS trap is issued when an RS-232 CTS event happens. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.510 |
s360notificationsCPEDownTrapA stock CPE Down trap is issued when a CPE Down event happens. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.511 |
s360notificationsFuelSensorDisconnectTrapA stock Fuel Sensor Disconnect trap is issued when a Fuel Sensor Disconnect or Connect (Return to Normal) event happens. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.515 |
s360notificationsFuelSensorVolumeTrapA stock Fuel Sensor Volume trap is issued when a Fuel Sensor Volume event happens NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.519 |
s360notificationsACPowerMonitorAvgVoltageTrapA stock AC power monitor average voltage trap is issued when an AC power monitor average voltage event happens. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.520 |
s360notificationsACPowerMonitorAvgCurrentTrapA stock AC power monitor average current trap is issued when an AC power monitor average current event happens. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.521 |
s360notificationsACPowerMonitorFrequencyTrapA stock AC power monitor frequency trap is issued when an AC power monitor frequency event happens. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.522 |
s360notificationsACPowerMonitorTRPTrapA stock AC power monitor TRP (total real power) trap is issued when an AC power monitor TRP event happens. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.523 |
s360notificationsACPowerMonitorDisconnectTrapA stock AC power monitor disconnect trap is issued when an AC power monitor disconnect event happens. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.524 |
s360notificationsStockScriptTrapA stock script trap is issued when a script triggers an event via a_lib.PostEvent() called with no trap number (or this trap number) specified. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.526 |
s360notificationsFuelSensorVolumeSuddenChangeTrapA stock Fuel Sensor Volume Sudden Change trap is issued when a Fuel Sensor Volume Sudden Change event happens NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.527 |
s360notificationsFuelSensorVolumeSlowChangeTrapA stock Fuel Sensor Volume Slow Change trap is issued when a Fuel Sensor Volume Slow Change event happens NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.528 |
s360notificationsGeneratorNonStartTrapA stock Generator Non-start trap is issued when the unit commands the generator to start as part of the generator exercising feature, and the generator fails to register as started after 30 seconds (as detected by CC generator running detection). NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.536 |
s360notificationsCameraTrapA stock camera trap is issued when a camera event happens. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.539 |
s360notificationsACTotalPowerFactorTrapA stock AC power monitor total power factor trap is issued when an AC power monitor total power factor event happens. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.540 |
s360notificationsResetTrapA stock reset trap is issued when a reset event happens. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.543 |
s360notificationHVACAsentriaControlTrapA stock HVAC Asentria Control trap is issued when an issue with temperature, humidity, fire detection and other HVAC related event happens. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.545 |
s360notificationAccessControlTrapA stock access control trap is issued when an access control device management event happens. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.547 |
s360notificationHVACAirsysControlTrapA stock HVAC Airsys Control trap is issued when an issue related to alarm conditions for the Airsys HVAC system event happens. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.548 |
s360notificationsUserTrap1000This user-defined trap is issued when an event happens that causes a trap with specific trap type 1000. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1000 |
s360notificationsUserTrap1001This user-defined trap is issued when an event happens that causes a trap with specific trap type 1001. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1001 |
s360notificationsUserTrap1002This user-defined trap is issued when an event happens that causes a trap with specific trap type 1002. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1002 |
s360notificationsUserTrap1003This user-defined trap is issued when an event happens that causes a trap with specific trap type 1003. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1003 |
s360notificationsUserTrap1004This user-defined trap is issued when an event happens that causes a trap with specific trap type 1004. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1004 |
s360notificationsUserTrap1005This user-defined trap is issued when an event happens that causes a trap with specific trap type 1005. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1005 |
s360notificationsUserTrap1006This user-defined trap is issued when an event happens that causes a trap with specific trap type 1006. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1006 |
s360notificationsUserTrap1007This user-defined trap is issued when an event happens that causes a trap with specific trap type 1007. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1007 |
s360notificationsUserTrap1008This user-defined trap is issued when an event happens that causes a trap with specific trap type 1008. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1008 |
s360notificationsUserTrap1009This user-defined trap is issued when an event happens that causes a trap with specific trap type 1009. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1009 |
s360notificationsUserTrap1010This user-defined trap is issued when an event happens that causes a trap with specific trap type 1010. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1010 |
s360notificationsUserTrap1011This user-defined trap is issued when an event happens that causes a trap with specific trap type 1011. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1011 |
s360notificationsUserTrap1012This user-defined trap is issued when an event happens that causes a trap with specific trap type 1012. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1012 |
s360notificationsUserTrap1013This user-defined trap is issued when an event happens that causes a trap with specific trap type 1013. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1013 |
s360notificationsUserTrap1014This user-defined trap is issued when an event happens that causes a trap with specific trap type 1014. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1014 |
s360notificationsUserTrap1015This user-defined trap is issued when an event happens that causes a trap with specific trap type 1015. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1015 |
s360notificationsUserTrap1016This user-defined trap is issued when an event happens that causes a trap with specific trap type 1016. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1016 |
s360notificationsUserTrap1017This user-defined trap is issued when an event happens that causes a trap with specific trap type 1017. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1017 |
s360notificationsUserTrap1018This user-defined trap is issued when an event happens that causes a trap with specific trap type 1018. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1018 |
s360notificationsUserTrap1019This user-defined trap is issued when an event happens that causes a trap with specific trap type 1019. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1019 |
s360notificationsUserTrap1020This user-defined trap is issued when an event happens that causes a trap with specific trap type 1020. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1020 |
s360notificationsUserTrap1021This user-defined trap is issued when an event happens that causes a trap with specific trap type 1021. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1021 |
s360notificationsUserTrap1022This user-defined trap is issued when an event happens that causes a trap with specific trap type 1022. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1022 |
s360notificationsUserTrap1023This user-defined trap is issued when an event happens that causes a trap with specific trap type 1023. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1023 |
s360notificationsUserTrap1024This user-defined trap is issued when an event happens that causes a trap with specific trap type 1024. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1024 |
s360notificationsUserTrap1025This user-defined trap is issued when an event happens that causes a trap with specific trap type 1025. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1025 |
s360notificationsUserTrap1026This user-defined trap is issued when an event happens that causes a trap with specific trap type 1026. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1026 |
s360notificationsUserTrap1027This user-defined trap is issued when an event happens that causes a trap with specific trap type 1027. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1027 |
s360notificationsUserTrap1028This user-defined trap is issued when an event happens that causes a trap with specific trap type 1028. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1028 |
s360notificationsUserTrap1029This user-defined trap is issued when an event happens that causes a trap with specific trap type 1029. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1029 |
s360notificationsUserTrap1030This user-defined trap is issued when an event happens that causes a trap with specific trap type 1030. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1030 |
s360notificationsUserTrap1031This user-defined trap is issued when an event happens that causes a trap with specific trap type 1031. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1031 |
s360notificationsUserTrap1032This user-defined trap is issued when an event happens that causes a trap with specific trap type 1032. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1032 |
s360notificationsUserTrap1033This user-defined trap is issued when an event happens that causes a trap with specific trap type 1033. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1033 |
s360notificationsUserTrap1034This user-defined trap is issued when an event happens that causes a trap with specific trap type 1034. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1034 |
s360notificationsUserTrap1035This user-defined trap is issued when an event happens that causes a trap with specific trap type 1035. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1035 |
s360notificationsUserTrap1036This user-defined trap is issued when an event happens that causes a trap with specific trap type 1036. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1036 |
s360notificationsUserTrap1037This user-defined trap is issued when an event happens that causes a trap with specific trap type 1037. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1037 |
s360notificationsUserTrap1038This user-defined trap is issued when an event happens that causes a trap with specific trap type 1038. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1038 |
s360notificationsUserTrap1039This user-defined trap is issued when an event happens that causes a trap with specific trap type 1039. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1039 |
s360notificationsUserTrap1040This user-defined trap is issued when an event happens that causes a trap with specific trap type 1040. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1040 |
s360notificationsUserTrap1041This user-defined trap is issued when an event happens that causes a trap with specific trap type 1041. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1041 |
s360notificationsUserTrap1042This user-defined trap is issued when an event happens that causes a trap with specific trap type 1042. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1042 |
s360notificationsUserTrap1043This user-defined trap is issued when an event happens that causes a trap with specific trap type 1043. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1043 |
s360notificationsUserTrap1044This user-defined trap is issued when an event happens that causes a trap with specific trap type 1044. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1044 |
s360notificationsUserTrap1045This user-defined trap is issued when an event happens that causes a trap with specific trap type 1045. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1045 |
s360notificationsUserTrap1046This user-defined trap is issued when an event happens that causes a trap with specific trap type 1046. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1046 |
s360notificationsUserTrap1047This user-defined trap is issued when an event happens that causes a trap with specific trap type 1047. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1047 |
s360notificationsUserTrap1048This user-defined trap is issued when an event happens that causes a trap with specific trap type 1048. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1048 |
s360notificationsUserTrap1049This user-defined trap is issued when an event happens that causes a trap with specific trap type 1049. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1049 |
s360notificationsUserTrap1050This user-defined trap is issued when an event happens that causes a trap with specific trap type 1050. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1050 |
s360notificationsUserTrap1051This user-defined trap is issued when an event happens that causes a trap with specific trap type 1051. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1051 |
s360notificationsUserTrap1052This user-defined trap is issued when an event happens that causes a trap with specific trap type 1052. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1052 |
s360notificationsUserTrap1053This user-defined trap is issued when an event happens that causes a trap with specific trap type 1053. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1053 |
s360notificationsUserTrap1054This user-defined trap is issued when an event happens that causes a trap with specific trap type 1054. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1054 |
s360notificationsUserTrap1055This user-defined trap is issued when an event happens that causes a trap with specific trap type 1055. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1055 |
s360notificationsUserTrap1056This user-defined trap is issued when an event happens that causes a trap with specific trap type 1056. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1056 |
s360notificationsUserTrap1057This user-defined trap is issued when an event happens that causes a trap with specific trap type 1057. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1057 |
s360notificationsUserTrap1058This user-defined trap is issued when an event happens that causes a trap with specific trap type 1058. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1058 |
s360notificationsUserTrap1059This user-defined trap is issued when an event happens that causes a trap with specific trap type 1059. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1059 |
s360notificationsUserTrap1060This user-defined trap is issued when an event happens that causes a trap with specific trap type 1060. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1060 |
s360notificationsUserTrap1061This user-defined trap is issued when an event happens that causes a trap with specific trap type 1061. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1061 |
s360notificationsUserTrap1062This user-defined trap is issued when an event happens that causes a trap with specific trap type 1062. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1062 |
s360notificationsUserTrap1063This user-defined trap is issued when an event happens that causes a trap with specific trap type 1063. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1063 |
s360notificationsUserTrap1064This user-defined trap is issued when an event happens that causes a trap with specific trap type 1064. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1064 |
s360notificationsUserTrap1065This user-defined trap is issued when an event happens that causes a trap with specific trap type 1065. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1065 |
s360notificationsUserTrap1066This user-defined trap is issued when an event happens that causes a trap with specific trap type 1066. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1066 |
s360notificationsUserTrap1067This user-defined trap is issued when an event happens that causes a trap with specific trap type 1067. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1067 |
s360notificationsUserTrap1068This user-defined trap is issued when an event happens that causes a trap with specific trap type 1068. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1068 |
s360notificationsUserTrap1069This user-defined trap is issued when an event happens that causes a trap with specific trap type 1069. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1069 |
s360notificationsUserTrap1070This user-defined trap is issued when an event happens that causes a trap with specific trap type 1070. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1070 |
s360notificationsUserTrap1071This user-defined trap is issued when an event happens that causes a trap with specific trap type 1071. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1071 |
s360notificationsUserTrap1072This user-defined trap is issued when an event happens that causes a trap with specific trap type 1072. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1072 |
s360notificationsUserTrap1073This user-defined trap is issued when an event happens that causes a trap with specific trap type 1073. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1073 |
s360notificationsUserTrap1074This user-defined trap is issued when an event happens that causes a trap with specific trap type 1074. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1074 |
s360notificationsUserTrap1075This user-defined trap is issued when an event happens that causes a trap with specific trap type 1075. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1075 |
s360notificationsUserTrap1076This user-defined trap is issued when an event happens that causes a trap with specific trap type 1076. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1076 |
s360notificationsUserTrap1077This user-defined trap is issued when an event happens that causes a trap with specific trap type 1077. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1077 |
s360notificationsUserTrap1078This user-defined trap is issued when an event happens that causes a trap with specific trap type 1078. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1078 |
s360notificationsUserTrap1079This user-defined trap is issued when an event happens that causes a trap with specific trap type 1079. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1079 |
s360notificationsUserTrap1080This user-defined trap is issued when an event happens that causes a trap with specific trap type 1080. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1080 |
s360notificationsUserTrap1081This user-defined trap is issued when an event happens that causes a trap with specific trap type 1081. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1081 |
s360notificationsUserTrap1082This user-defined trap is issued when an event happens that causes a trap with specific trap type 1082. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1082 |
s360notificationsUserTrap1083This user-defined trap is issued when an event happens that causes a trap with specific trap type 1083. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1083 |
s360notificationsUserTrap1084This user-defined trap is issued when an event happens that causes a trap with specific trap type 1084. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1084 |
s360notificationsUserTrap1085This user-defined trap is issued when an event happens that causes a trap with specific trap type 1085. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1085 |
s360notificationsUserTrap1086This user-defined trap is issued when an event happens that causes a trap with specific trap type 1086. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1086 |
s360notificationsUserTrap1087This user-defined trap is issued when an event happens that causes a trap with specific trap type 1087. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1087 |
s360notificationsUserTrap1088This user-defined trap is issued when an event happens that causes a trap with specific trap type 1088. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1088 |
s360notificationsUserTrap1089This user-defined trap is issued when an event happens that causes a trap with specific trap type 1089. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1089 |
s360notificationsUserTrap1090This user-defined trap is issued when an event happens that causes a trap with specific trap type 1090. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1090 |
s360notificationsUserTrap1091This user-defined trap is issued when an event happens that causes a trap with specific trap type 1091. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1091 |
s360notificationsUserTrap1092This user-defined trap is issued when an event happens that causes a trap with specific trap type 1092. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1092 |
s360notificationsUserTrap1093This user-defined trap is issued when an event happens that causes a trap with specific trap type 1093. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1093 |
s360notificationsUserTrap1094This user-defined trap is issued when an event happens that causes a trap with specific trap type 1094. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1094 |
s360notificationsUserTrap1095This user-defined trap is issued when an event happens that causes a trap with specific trap type 1095. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1095 |
s360notificationsUserTrap1096This user-defined trap is issued when an event happens that causes a trap with specific trap type 1096. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1096 |
s360notificationsUserTrap1097This user-defined trap is issued when an event happens that causes a trap with specific trap type 1097. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1097 |
s360notificationsUserTrap1098This user-defined trap is issued when an event happens that causes a trap with specific trap type 1098. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1098 |
s360notificationsUserTrap1099This user-defined trap is issued when an event happens that causes a trap with specific trap type 1099. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1099 |
s360notificationsUserTrap1100This user-defined trap is issued when an event happens that causes a trap with specific trap type 1100. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1100 |
s360notificationsUserTrap1101This user-defined trap is issued when an event happens that causes a trap with specific trap type 1101. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1101 |
s360notificationsUserTrap1102This user-defined trap is issued when an event happens that causes a trap with specific trap type 1102. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1102 |
s360notificationsUserTrap1103This user-defined trap is issued when an event happens that causes a trap with specific trap type 1103. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1103 |
s360notificationsUserTrap1104This user-defined trap is issued when an event happens that causes a trap with specific trap type 1104. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1104 |
s360notificationsUserTrap1105This user-defined trap is issued when an event happens that causes a trap with specific trap type 1105. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1105 |
s360notificationsUserTrap1106This user-defined trap is issued when an event happens that causes a trap with specific trap type 1106. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1106 |
s360notificationsUserTrap1107This user-defined trap is issued when an event happens that causes a trap with specific trap type 1107. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1107 |
s360notificationsUserTrap1108This user-defined trap is issued when an event happens that causes a trap with specific trap type 1108. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1108 |
s360notificationsUserTrap1109This user-defined trap is issued when an event happens that causes a trap with specific trap type 1109. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1109 |
s360notificationsUserTrap1110This user-defined trap is issued when an event happens that causes a trap with specific trap type 1110. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1110 |
s360notificationsUserTrap1111This user-defined trap is issued when an event happens that causes a trap with specific trap type 1111. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1111 |
s360notificationsUserTrap1112This user-defined trap is issued when an event happens that causes a trap with specific trap type 1112. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1112 |
s360notificationsUserTrap1113This user-defined trap is issued when an event happens that causes a trap with specific trap type 1113. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1113 |
s360notificationsUserTrap1114This user-defined trap is issued when an event happens that causes a trap with specific trap type 1114. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1114 |
s360notificationsUserTrap1115This user-defined trap is issued when an event happens that causes a trap with specific trap type 1115. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1115 |
s360notificationsUserTrap1116This user-defined trap is issued when an event happens that causes a trap with specific trap type 1116. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1116 |
s360notificationsUserTrap1117This user-defined trap is issued when an event happens that causes a trap with specific trap type 1117. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1117 |
s360notificationsUserTrap1118This user-defined trap is issued when an event happens that causes a trap with specific trap type 1118. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1118 |
s360notificationsUserTrap1119This user-defined trap is issued when an event happens that causes a trap with specific trap type 1119. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1119 |
s360notificationsUserTrap1120This user-defined trap is issued when an event happens that causes a trap with specific trap type 1120. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1120 |
s360notificationsUserTrap1121This user-defined trap is issued when an event happens that causes a trap with specific trap type 1121. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1121 |
s360notificationsUserTrap1122This user-defined trap is issued when an event happens that causes a trap with specific trap type 1122. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1122 |
s360notificationsUserTrap1123This user-defined trap is issued when an event happens that causes a trap with specific trap type 1123. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1123 |
s360notificationsUserTrap1124This user-defined trap is issued when an event happens that causes a trap with specific trap type 1124. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1124 |
s360notificationsUserTrap1125This user-defined trap is issued when an event happens that causes a trap with specific trap type 1125. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1125 |
s360notificationsUserTrap1126This user-defined trap is issued when an event happens that causes a trap with specific trap type 1126. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1126 |
s360notificationsUserTrap1127This user-defined trap is issued when an event happens that causes a trap with specific trap type 1127. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1127 |
s360notificationsUserTrap1128This user-defined trap is issued when an event happens that causes a trap with specific trap type 1128. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1128 |
s360notificationsUserTrap1129This user-defined trap is issued when an event happens that causes a trap with specific trap type 1129. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1129 |
s360notificationsUserTrap1130This user-defined trap is issued when an event happens that causes a trap with specific trap type 1130. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1130 |
s360notificationsUserTrap1131This user-defined trap is issued when an event happens that causes a trap with specific trap type 1131. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1131 |
s360notificationsUserTrap1132This user-defined trap is issued when an event happens that causes a trap with specific trap type 1132. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1132 |
s360notificationsUserTrap1133This user-defined trap is issued when an event happens that causes a trap with specific trap type 1133. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1133 |
s360notificationsUserTrap1134This user-defined trap is issued when an event happens that causes a trap with specific trap type 1134. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1134 |
s360notificationsUserTrap1135This user-defined trap is issued when an event happens that causes a trap with specific trap type 1135. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1135 |
s360notificationsUserTrap1136This user-defined trap is issued when an event happens that causes a trap with specific trap type 1136. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1136 |
s360notificationsUserTrap1137This user-defined trap is issued when an event happens that causes a trap with specific trap type 1137. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1137 |
s360notificationsUserTrap1138This user-defined trap is issued when an event happens that causes a trap with specific trap type 1138. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1138 |
s360notificationsUserTrap1139This user-defined trap is issued when an event happens that causes a trap with specific trap type 1139. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1139 |
s360notificationsUserTrap1140This user-defined trap is issued when an event happens that causes a trap with specific trap type 1140. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1140 |
s360notificationsUserTrap1141This user-defined trap is issued when an event happens that causes a trap with specific trap type 1141. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1141 |
s360notificationsUserTrap1142This user-defined trap is issued when an event happens that causes a trap with specific trap type 1142. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1142 |
s360notificationsUserTrap1143This user-defined trap is issued when an event happens that causes a trap with specific trap type 1143. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1143 |
s360notificationsUserTrap1144This user-defined trap is issued when an event happens that causes a trap with specific trap type 1144. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1144 |
s360notificationsUserTrap1145This user-defined trap is issued when an event happens that causes a trap with specific trap type 1145. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1145 |
s360notificationsUserTrap1146This user-defined trap is issued when an event happens that causes a trap with specific trap type 1146. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1146 |
s360notificationsUserTrap1147This user-defined trap is issued when an event happens that causes a trap with specific trap type 1147. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1147 |
s360notificationsUserTrap1148This user-defined trap is issued when an event happens that causes a trap with specific trap type 1148. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1148 |
s360notificationsUserTrap1149This user-defined trap is issued when an event happens that causes a trap with specific trap type 1149. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1149 |
s360notificationsUserTrap1150This user-defined trap is issued when an event happens that causes a trap with specific trap type 1150. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1150 |
s360notificationsUserTrap1151This user-defined trap is issued when an event happens that causes a trap with specific trap type 1151. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1151 |
s360notificationsUserTrap1152This user-defined trap is issued when an event happens that causes a trap with specific trap type 1152. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1152 |
s360notificationsUserTrap1153This user-defined trap is issued when an event happens that causes a trap with specific trap type 1153. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1153 |
s360notificationsUserTrap1154This user-defined trap is issued when an event happens that causes a trap with specific trap type 1154. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1154 |
s360notificationsUserTrap1155This user-defined trap is issued when an event happens that causes a trap with specific trap type 1155. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1155 |
s360notificationsUserTrap1156This user-defined trap is issued when an event happens that causes a trap with specific trap type 1156. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1156 |
s360notificationsUserTrap1157This user-defined trap is issued when an event happens that causes a trap with specific trap type 1157. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1157 |
s360notificationsUserTrap1158This user-defined trap is issued when an event happens that causes a trap with specific trap type 1158. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1158 |
s360notificationsUserTrap1159This user-defined trap is issued when an event happens that causes a trap with specific trap type 1159. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1159 |
s360notificationsUserTrap1160This user-defined trap is issued when an event happens that causes a trap with specific trap type 1160. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1160 |
s360notificationsUserTrap1161This user-defined trap is issued when an event happens that causes a trap with specific trap type 1161. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1161 |
s360notificationsUserTrap1162This user-defined trap is issued when an event happens that causes a trap with specific trap type 1162. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1162 |
s360notificationsUserTrap1163This user-defined trap is issued when an event happens that causes a trap with specific trap type 1163. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1163 |
s360notificationsUserTrap1164This user-defined trap is issued when an event happens that causes a trap with specific trap type 1164. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1164 |
s360notificationsUserTrap1165This user-defined trap is issued when an event happens that causes a trap with specific trap type 1165. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1165 |
s360notificationsUserTrap1166This user-defined trap is issued when an event happens that causes a trap with specific trap type 1166. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1166 |
s360notificationsUserTrap1167This user-defined trap is issued when an event happens that causes a trap with specific trap type 1167. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1167 |
s360notificationsUserTrap1168This user-defined trap is issued when an event happens that causes a trap with specific trap type 1168. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1168 |
s360notificationsUserTrap1169This user-defined trap is issued when an event happens that causes a trap with specific trap type 1169. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1169 |
s360notificationsUserTrap1170This user-defined trap is issued when an event happens that causes a trap with specific trap type 1170. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1170 |
s360notificationsUserTrap1171This user-defined trap is issued when an event happens that causes a trap with specific trap type 1171. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1171 |
s360notificationsUserTrap1172This user-defined trap is issued when an event happens that causes a trap with specific trap type 1172. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1172 |
s360notificationsUserTrap1173This user-defined trap is issued when an event happens that causes a trap with specific trap type 1173. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1173 |
s360notificationsUserTrap1174This user-defined trap is issued when an event happens that causes a trap with specific trap type 1174. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1174 |
s360notificationsUserTrap1175This user-defined trap is issued when an event happens that causes a trap with specific trap type 1175. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1175 |
s360notificationsUserTrap1176This user-defined trap is issued when an event happens that causes a trap with specific trap type 1176. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1176 |
s360notificationsUserTrap1177This user-defined trap is issued when an event happens that causes a trap with specific trap type 1177. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1177 |
s360notificationsUserTrap1178This user-defined trap is issued when an event happens that causes a trap with specific trap type 1178. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1178 |
s360notificationsUserTrap1179This user-defined trap is issued when an event happens that causes a trap with specific trap type 1179. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1179 |
s360notificationsUserTrap1180This user-defined trap is issued when an event happens that causes a trap with specific trap type 1180. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1180 |
s360notificationsUserTrap1181This user-defined trap is issued when an event happens that causes a trap with specific trap type 1181. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1181 |
s360notificationsUserTrap1182This user-defined trap is issued when an event happens that causes a trap with specific trap type 1182. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1182 |
s360notificationsUserTrap1183This user-defined trap is issued when an event happens that causes a trap with specific trap type 1183. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1183 |
s360notificationsUserTrap1184This user-defined trap is issued when an event happens that causes a trap with specific trap type 1184. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1184 |
s360notificationsUserTrap1185This user-defined trap is issued when an event happens that causes a trap with specific trap type 1185. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1185 |
s360notificationsUserTrap1186This user-defined trap is issued when an event happens that causes a trap with specific trap type 1186. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1186 |
s360notificationsUserTrap1187This user-defined trap is issued when an event happens that causes a trap with specific trap type 1187. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1187 |
s360notificationsUserTrap1188This user-defined trap is issued when an event happens that causes a trap with specific trap type 1188. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1188 |
s360notificationsUserTrap1189This user-defined trap is issued when an event happens that causes a trap with specific trap type 1189. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1189 |
s360notificationsUserTrap1190This user-defined trap is issued when an event happens that causes a trap with specific trap type 1190. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1190 |
s360notificationsUserTrap1191This user-defined trap is issued when an event happens that causes a trap with specific trap type 1191. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1191 |
s360notificationsUserTrap1192This user-defined trap is issued when an event happens that causes a trap with specific trap type 1192. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1192 |
s360notificationsUserTrap1193This user-defined trap is issued when an event happens that causes a trap with specific trap type 1193. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1193 |
s360notificationsUserTrap1194This user-defined trap is issued when an event happens that causes a trap with specific trap type 1194. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1194 |
s360notificationsUserTrap1195This user-defined trap is issued when an event happens that causes a trap with specific trap type 1195. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1195 |
s360notificationsUserTrap1196This user-defined trap is issued when an event happens that causes a trap with specific trap type 1196. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1196 |
s360notificationsUserTrap1197This user-defined trap is issued when an event happens that causes a trap with specific trap type 1197. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1197 |
s360notificationsUserTrap1198This user-defined trap is issued when an event happens that causes a trap with specific trap type 1198. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1198 |
s360notificationsUserTrap1199This user-defined trap is issued when an event happens that causes a trap with specific trap type 1199. NOTIFICATION-TYPE .1.3.6.1.4.1.3052.23.0.1199 |
status OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.1 |
eventSensorStatus OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.1.1 |
esPointTableThis table organizes 4 basic attributes of points. A point is a particular sensor on an EventSensor (e.g., temperature, humidity, contact closure 2, output 5, etc.). The 4 point attributes are its name, whether it's in its event state, the point's value as a number and its value as a string. Points are referenced by a point index. The point index is a string of 3 numbers separated by periods. It contains all the information necessary for getting a piece of data off an event sensor; namely, which EventSensor, point class, and which-sensor-of-that-class (a.k.a. point). SEQUENCE OF ESPoint .1.3.6.1.4.1.3052.23.1.1.1 |
esPointEntryEntry for EventSensor point table ESPoint .1.3.6.1.4.1.3052.23.1.1.1.1 |
esIndexESThe part of the point index that refers to an EventSensor. The point index is a string of 3 numbers separated by periods. It contains all the information necessary for getting a piece of data off an event sensor; namely, which EventSensor, point class, and which-sensor-of-that-class (a.k.a. point). This object's allowable values are 1 through 16, and 200. 200 always refers to the EventSensor inside the unit. 1 through 16 refer to additional attached EventSensors. The number corresponding to an EventSensor is determined by the user at the initial configuration time. If there is an internal sensor in the unit, it will always be the first item in the Sensor Events setup menu. For example, if a new EventSensor is configured as the 2nd entry AFTER the internal EventSensor (if one exists) in the Sensor Events Setup Menu, then that EventSensor will be known from then on as EventSensor 2. All point indeces with esIndexES=2 will now refer to that particular EventSensor.ro Integer32 .1.3.6.1.4.1.3052.23.1.1.1.1.1 |
esIndexPCThe part of the point index that refers to point class. The point index is a string of 3 numbers separated by periods. It contains all the information necessary for getting a piece of data off an event sensor; namely, which EventSensor, point class, and which-sensor-of-that-class (a.k.a. point). The values for this object are: 1=temperature sensor 2=contact closure 3=humidity sensor 4=noise sensor 5=analog input 6=output (relay output or power output)ro Integer32 .1.3.6.1.4.1.3052.23.1.1.1.1.2 |
esIndexPointThe part of the point index that delineates which sensor on the EventSensor. So this combined with esIndexPC (Point Class or type) and esIndexES (which EventSensor) uniquely defines each point (sensor or output) attached to a unit. For example, if esIndexES is 3, esIndexPC is 1 and esIndexPoint is 4 then this is the Fourth Temperature Sensor on EventSensor number 3.ro Integer32 .1.3.6.1.4.1.3052.23.1.1.1.1.3 |
esPointNameThe name of the point on an EventSensor. For example, 'AC temp' (in the case of the temperature sensor on an EventSensor). There can be multiple points of the same point class on an EventSensor (e.g., 8 contact closures) and multiple sensor classes on an EventSensor (e.g., temperature, contact closure, humidity). If the point referenced by a given point index is solitary (e.g., temperature sensor, because there can be only one on an EventSensor), then this object reads as '<EventSensor name>'. Setting this object for solitary point indices sets the EventSensor name only. On the other hand, if a given point is among other points of the same point class on an EventSensor, then this object reads as '<Sensor name>'. Setting this object for these NON- solitary point indices sets the sensor name only - not the EventSensor name.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.1.1.1.4 |
esPointInEventStateA number referring to the event state of a point on an EventSensor. This number can have different meanings depending on the point class. If the point class is temperature, humidity, or analog input, then the values of this object are: 1=very low 2=low 3=normal 4=high 5=very high For contact closures the values of this object are: 1=point in event state 2=point in normal state For outputs the values of this object is the numeric code for the logical state of the output: 1 or 2. The logical state of the output is either active/inactive for relay outputs or on/off for power outputs. The logical state of the output has different nomenclature depending on the type of the output (relay output or power output): 1=active (for relay output) or on (for power output) 2=inactive (for relay output) or off (for power output) This is not necessarily representative of physical state of the output. Physical state is energized/de-energized, for both relay and power outputs. For relay outputs, the active logical state corresponds to either the energized physical state or the de-energized physical state depending on how the relay output is configured. For power outputs, the on logical state always corresponds to the energized physical state. For any point class and any point, if the event state is undefined, then the value of this object is 0. For any point class except output, this object is read-only. For outputs, setting this object to 1 puts the output into its active logical state. Setting this object to 2 puts the output into its inactive logical state. Setting this object to any value greater than 2 puts the output into its active logical state for that many seconds (up to 3600), after which time it puts the output into its inactive logical state.rw Integer32 .1.3.6.1.4.1.3052.23.1.1.1.1.5 |
esPointValueIntA read-only number referring to the value of a point on an EventSensor. If the point class is temperature, then this object is the temperature in its configured scale (default is Fahrenheit). If the point class is contact closure, then this object is either 0 (open) or 1 (closed). If the point class is humidity, then this object is the percent relative humidity. If the point class is analog input, then this object is the signed input value in tenths of the configured units. If the point class is an output, then this object is the numeric code for the physical state of the output. 0=de-energized 1=energized This object cannot be used to control the output, i.e, change its logical or physical state (instead use the esPointInEventState object).rw Integer32 (-2147483648..2147483647) .1.3.6.1.4.1.3052.23.1.1.1.1.6 |
esPointValueStrA string referring to the value of a point on an EventSensor. For contact closures this object is either 'Open' or 'Closed'. For outputs this object is a concatenation of the logical state and physical state, separated by '/'. For a relay output this object can be one of the following 4 possible values: Active/Energized Inactive/Energized Active/De-energized Inactve/De-energized For a power output this object can be one of the following 2 possible values: On/Energized Off/De-energized For temperature and humidity point classes, this object is the string representation of the esPointValueInt object. For temperature, 'C' or 'F' is including in the string to indicate scale. For analog inputs, this object is the string representation of the plus/minus input in the configured units appended with the unit name.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.1.1.1.7 |
esPointTimeLastChangeThe time of the last time an event was triggerred for a point on an EventSensor in MM/DD/YY HH:MM:SS format. For contact closures, the possible events are Active and Inactive. For temperature, humidity, and analog inputs, the possible events are Normal, High, Very High, Low, and Very Low. For outputs, this object is a null string.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.1.1.1.8 |
esPointTimetickLastChangeThe time of the last time an event was triggerred for a point on an EventSensor in 100ths of seconds since reset. For contact closures, the possible events are Active and Inactive. For temperature, humidity, and analog inputs, the possible events are Normal, High, Very High, Low, and Very Low. For outputs, this object is 0.ro TimeTicks (SNMPv2-SMI) .1.3.6.1.4.1.3052.23.1.1.1.1.9 |
esPointAliasValueStrFor CC inputs, this is the CC active/inactive alias setting setting value that currently corresponds to the event state. So if the CC input is in the event state, then this object is the active alias setting value. If the CC input is in the normal state, then this object is the inactive alias setting value. For relay/power outputs, this is the output active/inactive alias setting value that currently corresponds to the output state. So if the output is in the active state, then this object is the active alias setting value. If the output is in hte inactive state, then this object is the inactive alias setting value. For non-CC and non-output sensors, this is the same as the esPointValueStr object.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.1.1.1.10 |
esPointClassValueStrFor CC inputs, this is the CC active/inactive class setting setting value that currently corresponds to the event state. So if the CC input is in the event state, then this object is the active class setting value. If the CC input is in the normal state, then this object is the inactive class setting value. For relay/power, analog and temp outputs, this is the output class string given the event (Very High, High, Normal, Low and Very Low). The class string is based upon the chosen string in the class table for e.g. Info, Minor, Major, Minor, Critical etc. If the given event is High, the chosen Class string for this event is what returned.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.1.1.1.11 |
dataEventStatus OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.1.2 |
deStatusTableData Event Status Table SEQUENCE OF DEStatus .1.3.6.1.4.1.3052.23.1.2.1 |
deStatusEntryEventSensor status entry DEStatus .1.3.6.1.4.1.3052.23.1.2.1.1 |
deStatusIndexIndex for Data Eventsro Integer32 .1.3.6.1.4.1.3052.23.1.2.1.1.1 |
deStatusNameData Event namero DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.2.1.1.2 |
deStatusCounterNumber of times a data record has matched this event's equation. Range: 1-999999999ro Integer32 .1.3.6.1.4.1.3052.23.1.2.1.1.3 |
deStatusThresholdNumber of times the equation is matched before an event is triggered. Range: 1-999999999ro Integer32 .1.3.6.1.4.1.3052.23.1.2.1.1.4 |
modemStatusstatus of modem (idle, dialing, connected, etc.)ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.3 |
modemCLIDLogTableTable of numbers of recent dialing parties SEQUENCE OF ModemCLIDLogConfig .1.3.6.1.4.1.3052.23.1.4 |
modemCLIDLogEntryEntry for table of CLID log entries ModemCLIDLogConfig .1.3.6.1.4.1.3052.23.1.4.1 |
modemCLIDLogIndexIndex for table of CLID log entriesro Integer32 .1.3.6.1.4.1.3052.23.1.4.1.1 |
modemCLIDLogNumberrecently logged number of dialing partyrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.4.1.2 |
powerDistributionStatus OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.1.5 |
pdConfigPower Distribution output configurationro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.5.1 |
pdNextGen OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.1.5.4 |
pdnTableTable of power distribution objects arranged according to next-generation methodology (i.e., using multiple PowerBoss power distributors in addition to the on-board power distributor). SEQUENCE OF PowerDistribNextGen .1.3.6.1.4.1.3052.23.1.5.4.1 |
pdnEntryEntry for table of power distribution objects arranged according to next-generation methodology (i.e., using multiple PowerBoss power distributors in addition to the on-board power distributor). PowerDistribNextGen .1.3.6.1.4.1.3052.23.1.5.4.1.1 |
pdnIndexPDIndex for table of power distribution objects, specifically the index that refers to which power distributor. A value of 200 means the internal power distributor. A value from 1 to 16 refers to an external power distributor (PowerBoss), and is the same value as esIndexES, which refers to the PowerBoss as an EventSensor in the eventSensorStatus object table. In other words, pdnIndexPD is the same as esIndexES: esIndexES is used to refer to the PowerBoss as an eventsensor (i.e., control outputs), while pdnIndexPD is used to refer to the PowerBoss when used for power distribution monitoring (i.e., to alarm on output current/voltage/fuse status).ro Integer32 .1.3.6.1.4.1.3052.23.1.5.4.1.1.1 |
pdnIndexOutputIndex for table of power distribution objects, specifically the index that refers to which output on the power distributor specified by pdnIndexPD. For objects where the output is irrelevant, this index should be 1.ro Integer32 .1.3.6.1.4.1.3052.23.1.5.4.1.1.2 |
pdnConfigThe number of outputs on the power distributor specified by pdnIndexPD. pdnIndexOutput should be 1 for this object.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.5.4.1.1.3 |
pdnMainCurrentInEventStateThe event state of the current (i.e. Amps) event of the power distributor specified by pdnIndexPD. pdnIndexOutput should be 1 for this object. Possible values for this object are: 'Very Low', 'Low', 'Normal', 'High', 'Very High'.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.5.4.1.1.4 |
pdnMainCurrentValueThe current drawn, in mA, for the power distributor specified by pdnIndexPD. If pdnIndexPD is 1-16 then this is an external power distributor (PowerBoss) and refers to the current drawn by that PowerBoss and all equipment powered by that PowerBoss. pdnIndexOutput should be 1 for this object.ro Integer32 .1.3.6.1.4.1.3052.23.1.5.4.1.1.5 |
pdnMainCurrentValueStrEssentially pdnMainCurrentValue formatted as a string in units of Amps, with 3 decimal places. pdnIndexOutput should be 1 for this object.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.5.4.1.1.6 |
pdnMainCurrentDeadbandThe deadband, in mA, for the main current sensor for the power distributor specified by pdIndexPD. pdnIndexOutput should be 1 for this object.ro Integer32 .1.3.6.1.4.1.3052.23.1.5.4.1.1.7 |
pdnMainCurrentVHighCurrentThe current, in mA, for the main current sensor's Very High event threshold, for the power distributor specified by pdIndexPD. pdnIndexOutput should be 1 for this object.ro Integer32 .1.3.6.1.4.1.3052.23.1.5.4.1.1.8 |
pdnMainCurrentHighCurrentThe current, in mA, for the main current sensor's High event threshold, for the power distributor specified by pdIndexPD. pdnIndexOutput should be 1 for this object.ro Integer32 .1.3.6.1.4.1.3052.23.1.5.4.1.1.9 |
pdnMainCurrentLowCurrentThe current, in mA, for the main current sensor's Low event threshold, for the power distributor specified by pdIndexPD. pdnIndexOutput should be 1 for this object.ro Integer32 .1.3.6.1.4.1.3052.23.1.5.4.1.1.10 |
pdnMainCurrentVLowCurrentThe current, in mA, for the main current sensor's Very Low event threshold, for the power distributor specified by pdIndexPD. pdnIndexOutput should be 1 for this object.ro Integer32 .1.3.6.1.4.1.3052.23.1.5.4.1.1.11 |
pdnMainVoltageInEventStateThe event state of the voltage event of the power distributor specified by pdnIndexPD. pdnIndexOutput should be 1 for this object. Possible values for this object are: 'Very Low', 'Low', 'Normal', 'High', 'Very High'.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.5.4.1.1.12 |
pdnMainVoltageValueThe voltage, in mV, at the power distributor specified by pdnIndexPD. If pdnIndexPD is 1-16 then this is an external power distributor (PowerBoss) and refers to the voltage at that PowerBoss and all equipment powered by that PowerBoss. pdnIndexOutput should be 1 for this object.ro Integer32 .1.3.6.1.4.1.3052.23.1.5.4.1.1.13 |
pdnMainVoltageValueStrEssentially pdnMainVoltageValue formatted as a string in units of Volts, with 3 decimal places. pdnIndexOutput should be 1 for this object.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.5.4.1.1.14 |
pdnMainVoltageDeadbandThe deadband, in mV, for the main voltage sensor for the power distributor specified by pdIndexPD. pdnIndexOutput should be 1 for this object.ro Integer32 .1.3.6.1.4.1.3052.23.1.5.4.1.1.15 |
pdnMainVoltageVHighVoltageThe voltage, in mA, for the main voltage sensor's Very High event threshold, for the power distributor specified by pdIndexPD. pdnIndexOutput should be 1 for this object.ro Integer32 .1.3.6.1.4.1.3052.23.1.5.4.1.1.16 |
pdnMainVoltageHighVoltageThe voltage, in mV, for the main voltage sensor's High event threshold, for the power distributor specified by pdIndexPD. pdnIndexOutput should be 1 for this object.ro Integer32 .1.3.6.1.4.1.3052.23.1.5.4.1.1.17 |
pdnMainVoltageLowVoltageThe voltage, in mV, for the main voltage sensor's Low event threshold, for the power distributor specified by pdIndexPD. pdnIndexOutput should be 1 for this object.ro Integer32 .1.3.6.1.4.1.3052.23.1.5.4.1.1.18 |
pdnMainVoltageVLowVoltageThe voltage, in mV, for the main voltage sensor's Very Low event threshold, for the power distributor specified by pdIndexPD. pdnIndexOutput should be 1 for this object.ro Integer32 .1.3.6.1.4.1.3052.23.1.5.4.1.1.19 |
pdnMainPowerValueThe power, in Watts, for the power distributor specified by pdIndexPD. pdnIndexOutput should be 1 for this object.ro Integer32 .1.3.6.1.4.1.3052.23.1.5.4.1.1.20 |
pdnMainPowerValueStrThe power, in Watts, for the power distributor specified by pdIndexPD, formatted as a string with the unit name 'Watts'. pdnIndexOutput should be 1 for this object.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.5.4.1.1.21 |
pdnOutputCurrentInEventStateThe event state of the current (i.e. Amps) event of the power distributor output specified by pdnIndexPD and pdnIndexOutput. E.g., for pdnIndexPD=200 and pdnIndexOutput=2, this refers to power output #2 of the internal power distributor. Possible values for this object are: 'Very Low', 'Low', 'Normal', 'High', 'Very High'.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.5.4.1.1.22 |
pdnOutputCurrentValueThe current drawn, in mA, for the power distributor output specified by pdnIndexPD and pdIndexOutput. E.g., if pdIndexPD is 3 then this is an external power distributor (PowerBoss) identified as 'power distributor 3' and refers to the current drawn by a specific power output on that PowerBoss. The specific power output is specified by pdIndexOutput.ro Integer32 .1.3.6.1.4.1.3052.23.1.5.4.1.1.23 |
pdnOutputCurrentValueStrEssentially pdnOutputCurrentValue formatted as a string in units of Amps, with 3 decimal places.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.5.4.1.1.24 |
pdnOutputCurrentDeadbandThe deadband, in mA, for the main current sensor for the power distributor specified by pdIndexPD. The power output is specified by pdnIndexOutput.ro Integer32 .1.3.6.1.4.1.3052.23.1.5.4.1.1.25 |
pdnOutputCurrentVHighCurrentThe current, in mA, for a specific power output's current sensor Very High event threshold, for the power distributor specified by pdIndexPD. The power output is specified by pdnIndexOutput.ro Integer32 .1.3.6.1.4.1.3052.23.1.5.4.1.1.26 |
pdnOutputCurrentHighCurrentThe current, in mA, for a specific power output's current sensor High event threshold, for the power distributor specified by pdIndexPD. The power output is specified by pdnIndexOutput for this object.ro Integer32 .1.3.6.1.4.1.3052.23.1.5.4.1.1.27 |
pdnOutputCurrentLowCurrentThe current, in mA, for a specific power output's current sensor Low event threshold, for the power distributor specified by pdIndexPD. The power output is specified by pdnIndexOutput for this object.ro Integer32 .1.3.6.1.4.1.3052.23.1.5.4.1.1.28 |
pdnOutputCurrentVLowCurrentThe current, in mA, for a specific power output's current sensor Very Low event threshold, for the power distributor specified by pdIndexPD. The power output is specified by pdnIndexOutput for this object.ro Integer32 .1.3.6.1.4.1.3052.23.1.5.4.1.1.29 |
pdnOutputFuseInEventStateThe event state of the fuse event of the power distributor output specified by pdnIndexPD and pdnIndexOutput. E.g., for pdnIndexPD=14 and pdnIndexOutput=2, this refers to power output #2 of the external power distributor (PowerBoss), identified as 'power distributor 14'. Possible values for this object are: 'Very Low', 'Low', 'Normal', 'High', 'Very High'. This object exists only for power distributors with fuse monitoring support.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.5.4.1.1.30 |
pdnOutputFuseValueStrThe state of the fuse of the power distributor output specified by pdnIndexPD and pdnIndexOutput. Possible values for this object are: 'BLOWN' and 'OK'. This object exists only for power distributors with fuse monitoring support.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.5.4.1.1.31 |
pdnMainCombinedStatusCombined status string intended to be parsed by NMS: format: voltageColorCode`voltageEventState`voltageValue`mainCurrentColorCode`mainCurrentEventState`mainCurrentValue`deviceCurrentValue`mainPowerValuero DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.5.4.1.1.32 |
pdnOutputCombinedStatusBlock1Combined status string intended to be parsed by NMS: format: numInBlock~outputCurrentColorCode1`outputCurrentEventState1`outputCurrentValue1`fuseColorCode1`fuseValue1~...ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.5.4.1.1.33 |
pdnOutputCombinedStatusBlock2Combined status string intended to be parsed by NMS: format: numInBlock~outputCurrentColorCode1`outputCurrentEventState1`outputCurrentValue1`fuseColorCode1`fuseValue1~...ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.5.4.1.1.34 |
pdnDeviceCurrentValueCurrent drawn by device in mA. For the internal power distributor device, this is the current drawn by the SiteBoss 571. For an external power distributor device (PowerBoss), this is the current drawn by the PowerBoss. This object exists only for power distributors with device current monitoring support.ro Integer32 .1.3.6.1.4.1.3052.23.1.5.4.1.1.35 |
pdnDeviceCurrentValueStrCurrent drawn by device as a string with units (Amps). For the internal power distributor device, this is the current drawn by the SiteBoss 571. For an external power distributor device (PowerBoss), this is the current drawn by the PowerBoss. This object exists only for power distributors with device current monitoring support.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.5.4.1.1.36 |
pdSystem OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.1.5.5 |
pdSystemCurrentTotal current drawn by all power distributors in system; that is, the sum of all pdnMainCurrentValue objects for all connected power distributors: internal and external.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.5.5.1 |
pdSystemPowerTotal power used by all power distributors in system; that is, the sum of all pdnMainPowerValue objects for all connected power distributors: internal and external.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.5.5.2 |
fuelSensorStatus OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.1.6 |
fsStatusTableFuel sensor status table SEQUENCE OF FSStatus .1.3.6.1.4.1.3052.23.1.6.1 |
fsStatusEntryFuel sensor status table entry FSStatus .1.3.6.1.4.1.3052.23.1.6.1.1 |
fsStatusIndexIndex for fuel sensorsro Integer32 .1.3.6.1.4.1.3052.23.1.6.1.1.1 |
fsStatusNameFuel sensor namero DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.6.1.1.2 |
fsStatusDeviceStateFuel sensor device statero DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.6.1.1.3 |
fsStatusVolumeValueStringFuel volume. Range is -2,147,483,648 to 2,147,483,647. This value reads -999 when the fuel sensor is disconnectedro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.6.1.1.4 |
fsStatusVolumePercentLevelHeight of the fluid in the tank expressed as a percentage of the tank height, in hundredths of a percent.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.6.1.1.7 |
fsStatusVolumeInEventStateCurrent event status of the fuel sensor.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.6.1.1.8 |
fsStatusCombinedCombined status string intended to be parsed by NMS: deviceState`deviceStateColorCode`percentRounded`valueAsFloat`volumeEventState`volumeEventStateColorCode`capacity`units`namero DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.6.1.1.9 |
wirelessModemStatus OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.1.7 |
wmsStatusWireless modem statusro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.7.1 |
wmsSignalWireless modem Signal strengthro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.7.2 |
wmsRSSIWireless modem Signal strength (RSSI)ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.7.3 |
wmsBERWireless modem Bit Error Ratero DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.7.4 |
wmsUpdatedWireless modem info last update timero DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.7.5 |
wmsRegistrationWireless modem registration statusro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.7.6 |
wmsLACWireless modem Location Area Codero DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.7.7 |
wmsCellIDWireless modem Cell IDro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.7.8 |
wmsIMSIWireless modem Internation Mobile Subscriber Identity numberro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.7.9 |
wmsPhnumWireless modem phone numberro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.7.10 |
wmsLocalIPLocal IP address of modem on wireless networkro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.7.11 |
wmsMgfIDWireless modem manufacturer IDro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.7.12 |
wmsModelIDWireless modem model IDro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.7.13 |
wmsIMEIWireless modem International Mobile Equipment Identity numberro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.7.14 |
wmsRevIDWireless modem revision IDro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.7.15 |
wmsNetNameWireless modem network namero DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.7.16 |
wmsGPRSStatusWireless modem (E)GPRS statusro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.7.17 |
wmsBandWireless modem bandro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.7.18 |
wmsChannelWireless modem channelro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.7.19 |
wmsCountryCodeWireless modem country codero DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.7.20 |
wmsNetCodeWireless modem network codero DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.7.21 |
wmsPLMNColorWireless modem PLMN colorro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.7.22 |
wmsBScolorWireless modem BS colorro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.7.23 |
wmsMpRACHWireless modem max power RACHro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.7.24 |
wmsMinRxLevelWireless modem minimum receive levelro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.7.25 |
wmsBaseCoeffWireless modem base coefficientro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.7.26 |
wmsSIMStatusWWireless modem SIM statusro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.7.27 |
wmsICCIDWireless modem SIM ICCIDro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.7.28 |
wmsModemTypeWireless modem typero DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.7.29 |
wmsDualSIMModemInstalledWireless Dual-SIM modem installedro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.7.30 |
wmsDualSIMActiveSIMWireless Dual-SIM active SIMro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.7.31 |
wmsDualSIMDataUsageWireless Dual-SIM data usagero DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.7.32 |
wmsDualSIMLastSIMSwitchReasonWireless Dual-SIM last SIM switch reasonro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.7.33 |
wmsDualSIMPrimaryICCIDWireless Dual-SIM primary ICCIDro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.7.34 |
wmsDualSIMAlternateICCIDWireless Dual-SIM alternate ICCIDro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.7.35 |
acPowerMonitorStatus OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.1.8 |
acpmStatusTableAC power monitor status table SEQUENCE OF ACPMStatus .1.3.6.1.4.1.3052.23.1.8.1 |
acpmStatusEntryAC power monitor status table entry ACPMStatus .1.3.6.1.4.1.3052.23.1.8.1.1 |
acpmsIndexIndex for AC power monitorsro Integer32 .1.3.6.1.4.1.3052.23.1.8.1.1.1 |
acpmsNameName for the AC power monitor device.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.8.1.1.2 |
acpmsAvgVoltageValueStrAverage voltage, in volts. This is calculated using the formula (register * PT ratio * 0.1). This could be either the average of the phase voltages, or the sum of the phase voltages, depending on device configuration.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.8.1.1.3 |
acpmsAvgVoltageMinStrMinimum average voltage value since last reset, in volts.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.8.1.1.4 |
acpmsAvgVoltageMaxStrMaximum average voltage value since last reset, in volts.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.8.1.1.5 |
acpmsAvgVoltageAvgStrAverage average voltage value since last reset, in volts. This is the unit's average of its measurements of the average voltage reported by the AC power monitor device.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.8.1.1.6 |
acpmsAvgVoltageInEventStateEvent state of this AC power monitor voltage (Low, Normal, High, etc.).ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.8.1.1.7 |
acpmsVoltagePhaseAValueStrPhase A voltage, in volts. This is calculated using the formula (register * PT ratio * 0.1).ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.8.1.1.8 |
acpmsVoltagePhaseBValueStrPhase B voltage, in volts. This is calculated using the formula (register * PT ratio * 0.1).ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.8.1.1.9 |
acpmsVoltagePhaseCValueStrPhase C voltage, in volts. This is calculated using the formula (register * PT ratio * 0.1).ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.8.1.1.10 |
acpmsVoltageL1L2ValueLine 1 to Line 2 voltagero DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.8.1.1.11 |
acpmsVoltageL2L3ValueLine 2 to Line 3 voltagero DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.8.1.1.12 |
acpmsVoltageL3L1ValueLine 3 to Line 1 voltagero DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.8.1.1.13 |
acpmsAvgCurrentValueStrAverage current, in amps. This is calculated using the formula (register * CT ratio * 0.001). This could be either the average of the phase currents, or the sum of the phase currents, depending on device configuration.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.8.1.1.14 |
acpmsAvgCurrentMinStrMinimum average current value since last reset, in amps.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.8.1.1.15 |
acpmsAvgCurrentMaxStrMaximum average current value since last reset, in amps.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.8.1.1.16 |
acpmsAvgCurrentAvgStrAverage average current value since last reset, in amps. This is the unit's average of its measurements of the average current reported by the AC power monitor device.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.8.1.1.17 |
acpmsAvgCurrentInEventStateEvent state of this AC power monitor current (Low, Normal, High, etc.).ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.8.1.1.18 |
acpmsCurrentPhaseAValueStrPhase A current, in amps. This is calculated using the formula (register * CT ratio * 0.001).ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.8.1.1.19 |
acpmsCurrentPhaseBValueStrPhase B current, in amps. This is calculated using the formula (register * CT ratio * 0.001).ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.8.1.1.20 |
acpmsCurrentPhaseCValueStrPhase C current, in amps. This is calculated using the formula (register * CT ratio * 0.001).ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.8.1.1.21 |
acpmsAvgFreqValueStrFrequency, in hertz. On the YD2010, this is calculated using the formula (register * 0.00106813). On the WattsOn, this is calculated using the formula (register * 0.1).ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.8.1.1.22 |
acpmsAvgFreqMinStrMinimum frequency value since last reset, in hertz.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.8.1.1.23 |
acpmsAvgFreqMaxStrMaximum frequency value since last reset, in hertz.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.8.1.1.24 |
acpmsAvgFreqAvgStrAverage frequency value since last reset, in hertz. This is the unit's average of its measurements of the average frequency reported by the AC power monitor device.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.8.1.1.25 |
acpmsAvgFreqInEventStateEvent state of this AC power monitor frequency (Low, Normal, High, etc.).ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.8.1.1.26 |
acpmsTRPValueStrTotal real power, in watts. On the YD2010, this is calculated using the formula (register * PT ratio * CT ratio * Urg * 0.4), where Urg is the voltage range taken from register 0x30A. On the WattsOn models, this is calculated using the formula (register * PT * CT).ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.8.1.1.27 |
acpmsTRPMinStrMinimum total real power value since last reset, in watts.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.8.1.1.28 |
acpmsTRPMaxStrMaximum total real power value since last reset, in watts.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.8.1.1.29 |
acpmsTRPAvgStrAverage total real power value since last reset, in watts. This is the unit's average of its measurements of the average total real power reported by the AC power monitor device.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.8.1.1.30 |
acpmsTRPInEventStateEvent state of this AC power monitor total real power (Low, Normal, High, etc.).ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.8.1.1.31 |
acpmsRPPhaseAValueStrPhase A real power, in watts. On the YD2010, this is calculated using the formula (register * PT ratio * CT ratio * Urg * 0.4), where Urg is the voltage range taken from register 0x30A. On the WattsOn, this is calculated using the formula (register * PT * CT).ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.8.1.1.32 |
acpmsRPPhaseBValueStrPhase B real power, in watts. On the YD2010, this is calculated using the formula (register * PT ratio * CT ratio * Urg * 0.4), where Urg is the voltage range taken from register 0x30A. On the WattsOn, this is calculated using the formula (register * PT * CT).ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.8.1.1.33 |
acpmsRPPhaseCValueStrPhase C real power, in watts. On the YD2010, this is calculated using the formula (register * PT ratio * CT ratio * Urg * 0.4), where Urg is the voltage range taken from register 0x30A. On the WattsOn, this is calculated using the formula (register * PT * CT).ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.8.1.1.34 |
acpmsCombinedCombined status string intended to be parsed by NMS: name`deviceState`deviceStateColorCode`voltage`current`frequency`power~voltageEventState`voltageColorCode`currentEventState`currentColorCode`frequencyEventState`freuencyColorCode`powerEventState`powerColorCodero DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.8.1.1.35 |
acpmsTPFValueStrTotal power factor.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.8.1.1.36 |
acpmsTPFMinStrTotal power factor minimum value since last reset.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.8.1.1.37 |
acpmsTPFMaxStrTotal power factor maximum value since last reset.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.8.1.1.38 |
acpmsTPFAvgStrTotal power factor average value since last reset.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.8.1.1.39 |
acpmsTPFInEventStateTotal power factor event state.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.8.1.1.40 |
acpmsPFPhaseAValueStrPhase A power factor.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.8.1.1.41 |
acpmsPFPhaseBValueStrPhase B power factor.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.8.1.1.42 |
acpmsPFPhaseCValueStrPhase C power factor.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.8.1.1.43 |
acpmsTRcPValueStrTotal reactive power, in VAR.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.8.1.1.44 |
acpmsTRcPMinStrTotal reactive power minimum value since last reset, in VAR.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.8.1.1.45 |
acpmsTRcPMaxStrTotal reactive power maximum value since last reset, in VAR.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.8.1.1.46 |
acpmsTRcPAvgStrTotal reactive power average value since last reset, in VAR.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.8.1.1.47 |
acpmsRcPPhaseAValueStrPhase A reactive power, in VAR.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.8.1.1.48 |
acpmsRcPPhaseBValueStrPhase B reactive power, in VAR.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.8.1.1.49 |
acpmsRcPPhaseCValueStrPhase C reactive power, in VAR.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.8.1.1.50 |
acpmsTAPValueStrTotal apparent power, in VA.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.8.1.1.51 |
acpmsTAPMinStrTotal apparent power minimum value since last reset, in VA.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.8.1.1.52 |
acpmsTAPMaxStrTotal apparent power maximum value since last reset, in VA.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.8.1.1.53 |
acpmsTAPAvgStrTotal apparent power average value since last reset, in VA.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.8.1.1.54 |
acpmsAPPhaseAValueStrPhase A apparent power, in VA.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.8.1.1.55 |
acpmsAPPhaseBValueStrPhase B apparent power, in VA.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.8.1.1.56 |
acpmsAPPhaseCValueStrPhase C apparent power, in VA.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.8.1.1.57 |
acpmsTotalEnergyWhTotal energy, in Wh.ro Integer32 .1.3.6.1.4.1.3052.23.1.8.1.1.58 |
acpmsTotalEnergyVARTotal reactive energy, in VAR.ro Integer32 .1.3.6.1.4.1.3052.23.1.8.1.1.59 |
acpmsTotalEnergyVATotal apparent energy, in VA.ro Integer32 .1.3.6.1.4.1.3052.23.1.8.1.1.60 |
acmpsAvgVoltageAlarmDatetimeThe time of the last Average Voltage alarm triggerred in the AC monitor MM/DD/YY HH:MM:SS format. The possible events are High, Very High, Low, and Very Low. For outputs, this object is a null string.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.8.1.1.61 |
acmpsAvgCurrentAlarmDatetimeThe time of the last Average Current alarm triggerred in the AC monitor MM/DD/YY HH:MM:SS format. The possible events are High, Very High, Low, and Very Low. For outputs, this object is a null string.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.8.1.1.62 |
acmpsFreqAlarmDatetimeThe time of the last Frequency alarm triggerred in the AC monitor MM/DD/YY HH:MM:SS format. The possible events are High, Very High, Low, and Very Low. For outputs, this object is a null string.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.8.1.1.63 |
acmpsRealPowerAlarmDatetimeThe time of the last Real Power alarm triggerred in the AC monitor MM/DD/YY HH:MM:SS format. The possible events are High, Very High, Low, and Very Low. For outputs, this object is a null string.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.8.1.1.64 |
acmpsPowerFactorAlarmDatetimeThe time of the last Power Factor alarm triggerred in the AC monitor MM/DD/YY HH:MM:SS format. The possible events are Low, and Very Low. For outputs, this object is a null string.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.8.1.1.65 |
evHVACStatus OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.1.11 |
evHVACStatusBard OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.1.11.2 |
evHVACStatusBardSystem1 OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.1.11.2.1 |
evHVACStatusBardSystem1Stage1 OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.1.11.2.1.1 |
evHVACStatusBardSystem1Stage1CoolingBard HVAC: System 1 stage 1 cooling status.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.2.1.1.1 |
evHVACStatusBardSystem1Stage2 OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.1.11.2.1.2 |
evHVACStatusBardSystem1Stage2CoolingBard HVAC: System 1 stage 2 cooling status.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.2.1.2.1 |
evHVACStatusBardSystem1BlowerBard HVAC: System 1 blower status.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.2.1.3 |
evHVACStatusBardSystem1HeatingBard HVAC: System 1 heating status.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.2.1.4 |
evHVACStatusBardSystem1EconomizerBard HVAC: System 1 heating status.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.2.1.5 |
evHVACStatusBardSystem2 OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.1.11.2.2 |
evHVACStatusBardSystem2Stage1 OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.1.11.2.2.1 |
evHVACStatusBardSystem2Stage1CoolingBard HVAC: System 2 stage 1 cooling status.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.2.2.1.1 |
evHVACStatusBardSystem2Stage2 OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.1.11.2.2.2 |
evHVACStatusBardSystem2Stage2CoolingBard HVAC: System 2 stage 2 cooling status.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.2.2.2.1 |
evHVACStatusBardSystem2BlowerBard HVAC: System 2 blower status.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.2.2.3 |
evHVACStatusBardSystem2HeatingBard HVAC: System 2 heating status.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.2.2.4 |
evHVACStatusBardSystem2EconomizerBard HVAC: System 2 heating status.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.2.2.5 |
evHVACStatusBardTempAvgBard HVAC: Average temperature.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.2.3 |
evHVACStatusBardTempLocalBard HVAC: Local temperature.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.2.4 |
evHVACStatusBardTempRemote OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.1.11.2.5 |
evHVACStatusBardTempRemote1Bard HVAC: Remote 1 temperature.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.2.5.1 |
evHVACStatusBardTempRemote2Bard HVAC: Remote 2 temperature.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.2.5.2 |
evHVACStatusBardDehumidificationBard HVAC: Dehumidification status.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.2.6 |
evHVACStatusBardGeneratorBard HVAC: Backup generator status.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.2.7 |
evHVACStatusBardLEDs OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.1.11.2.7 |
evHVACStatusBardLEDsCooling OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.1.11.2.7.1 |
evHVACStatusBardLEDsCooling1Bard HVAC: Cooling LED 1.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.2.7.1.1 |
evHVACStatusBardLEDsCooling2Bard HVAC: Cooling LED 2.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.2.7.1.2 |
evHVACStatusBardLEDsCooling3Bard HVAC: Cooling LED 3.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.2.7.1.3 |
evHVACStatusBardLEDsCooling4Bard HVAC: Cooling LED 4.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.2.7.1.4 |
evHVACStatusBardLEDsHeating OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.1.11.2.7.2 |
evHVACStatusBardLEDsHeating1Bard HVAC: Heating LED 1.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.2.7.2.1 |
evHVACStatusBardLEDsHeating2Bard HVAC: Heating LED 2.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.2.7.2.2 |
evHVACStatusBardLEDsHeating3Bard HVAC: Heating LED 3.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.2.7.2.3 |
evHVACStatusBardLEDsHeating4Bard HVAC: Heating LED 4.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.2.7.2.4 |
evHVACStatusBardLEDsDeHumid OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.1.11.2.7.3 |
evHVACStatusBardLEDsDeHumid1Bard HVAC: Dehumidification LED 1.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.2.7.3.1 |
evHVACStatusBardAlarmBoardStateBard HVAC: Alarm board state.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.2.8 |
evHVACStatusBardAlarmStatus OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.1.11.2.10 |
evHVACStatusBardASSystem1 OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.1.11.2.10.1 |
evHVACStatusBardASSystem1PowerLossBard HVAC Alarm Status: System 1 power loss.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.2.10.1.1 |
evHVACStatusBardASSystem1LockoutBard HVAC Alarm Status: System 1 ref. lockout.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.2.10.1.2 |
evHVACStatusBardASSystem2 OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.1.11.2.10.2 |
evHVACStatusBardASSystem2PowerLossBard HVAC Alarm Status: System 2 power loss.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.2.10.2.1 |
evHVACStatusBardASSystem2LockoutBard HVAC Alarm Status: System 2 ref. lockout.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.2.10.2.2 |
evHVACStatusBardASFireBard HVAC Alarm Status: Fire / smoke.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.2.10.3 |
evHVACStatusBardASTemp OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.1.11.2.10.4 |
evHVACStatusBardASTempLowAlarmBard HVAC Alarm Status: Low temperature.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.2.10.4.1 |
evHVACStatusBardASTempHighAlarmBard HVAC Alarm Status: High temperature.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.2.10.4.2 |
evHVACStatusBardASTempVHighAlarmBard HVAC Alarm Status: Very high temperature.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.2.10.4.3 |
evHVACStatusBardASFailureBard HVAC Alarm Status: Controller failure.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.2.10.5 |
evHVACStatusBardConnStateConnectivity state: 1 means unit has good connectivity to the Bard HVAC controller, 0 otherwise.ro Integer32 .1.3.6.1.4.1.3052.23.1.11.2.11 |
evHVACStatusAsentria OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.1.11.3 |
evHVACStatusAsentriaSequenceTableAsentria HVAC sequence status table SEQUENCE OF HVACStatusAsentriaSequence .1.3.6.1.4.1.3052.23.1.11.3.1 |
evHVACStatusAsentriaSequenceEntryAsentria HVAC sequence status table entry HVACStatusAsentriaSequence .1.3.6.1.4.1.3052.23.1.11.3.1.1 |
evHVACStatusAsentriaSequenceIndexIndex for Asentria HVAC sequencero Integer32 .1.3.6.1.4.1.3052.23.1.11.3.1.1.1 |
evHVACStatusAsentriaSeqVentTimeAsentria HVAC sequence time spent ventingro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.3.1.1.2 |
evHVACStatusAsentriaSeqCoolTimeAsentria HVAC sequence time spent coolingro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.3.1.1.3 |
evHVACStatusAsentriaSeqHeatTimeAsentria HVAC sequence time spent heatingro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.3.1.1.4 |
evHVACStatusAsentriaSeqIdleTimeAsentria HVAC sequence time spent idlingro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.3.1.1.5 |
evHVACStatusAsentriaUnitTableAsentria HVAC unit status table SEQUENCE OF HVACStatusAsentriaUnit .1.3.6.1.4.1.3052.23.1.11.3.2 |
evHVACStatusAsentriaUnitEntryAsentria HVAC unit status table entry HVACStatusAsentriaUnit .1.3.6.1.4.1.3052.23.1.11.3.2.1 |
evHVACStatusAsentriaUnitIndexIndex for Asentria HVAC unitro Integer32 .1.3.6.1.4.1.3052.23.1.11.3.2.1.1 |
evHVACStatusAsentriaUnitStateAsentria HVAC unit statusro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.3.2.1.2 |
evHVACStatusAsentriaUnitVentTimeAsentria HVAC unit time spent ventingro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.3.2.1.3 |
evHVACStatusAsentriaUnitCoolTimeAsentria HVAC unit time spent coolingro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.3.2.1.4 |
evHVACStatusAsentriaUnitHeatTimeAsentria HVAC unit time spent heatingro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.3.2.1.5 |
evHVACStatusAsentriaUnitIdleTimeAsentria HVAC unit time spent idlingro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.3.2.1.6 |
evHVACStatusAsentriaBackupEventAsentria HVAC backup eventro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.3.3 |
evHVACStatusAsentriaFireEventAsentria HVAC smoke/fire eventro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.3.4 |
evHVACStatusAsentriaTemp OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.1.11.3.5 |
evHVACStatusAsentriaTempOutAsentria HVAC temperature outsidero DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.3.5.1 |
evHVACStatusAsentriaTempInAsentria HVAC temperature insidero DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.3.5.2 |
evHVACStatusAsentriaHumid OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.1.11.3.6 |
evHVACStatusAsentriaHumidOutAsentria HVAC humidity outsidero DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.3.6.1 |
evHVACStatusAsentriaHumidInAsentria HVAC humidity insidero DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.3.6.2 |
evHVACStatusAirsys OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.1.11.4 |
evHVACStatusAirsysAlarm OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.1.11.4.1 |
evHVACStatusAirsysAlarmUnitTableAirsys HVAC unit alarm status table SEQUENCE OF HVACStatusAirsysAlarmUnit .1.3.6.1.4.1.3052.23.1.11.4.1.1 |
evHVACStatusAirsysAlarmUnitEntryAirsys HVAC unit alarm status table entry HVACStatusAirsysAlarmUnit .1.3.6.1.4.1.3052.23.1.11.4.1.1.1 |
evHVACStatusAirsysAlarmUnitIndexIndex for Airsys HVAC unit alarmsro Integer32 .1.3.6.1.4.1.3052.23.1.11.4.1.1.1.1 |
evHVACStatusAirsysAlarmUnitLowPressAirsys HVAC unit low pressure eventro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.4.1.1.1.2 |
evHVACStatusAirsysAlarmUnitHighPressAirsys HVAC unit high pressure eventro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.4.1.1.1.3 |
evHVACStatusAirsysAlarmUnitEvapFanAirsys HVAC unit AC power/evaporator fan overload eventro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.4.1.1.1.4 |
evHVACStatusAirsysAlarmUnitDirtyAirsys HVAC unit dirty filter eventro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.4.1.1.1.5 |
evHVACStatusAirsysAlarmUnitDamperAirsys HVAC unit damper eventro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.4.1.1.1.6 |
evHVACStatusAirsysAlarmUnitSupProbeAirsys HVAC unit supply probe broken eventro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.4.1.1.1.7 |
evHVACStatusAirsysAlarmSmokeFireAirsys HVAC smoke/fire eventro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.4.1.2 |
evHVACStatusAirsysAlarmLowRoomTempAirsys HVAC low temperature eventro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.4.1.3 |
evHVACStatusAirsysAlarmHighRoomTempAirsys HVAC high temperature eventro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.4.1.4 |
evHVACStatusAirsysAlarmPowerAirsys HVAC power failure eventro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.4.1.5 |
evHVACStatusAirsysAlarmpLANAirsys HVAC pLAN eventro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.4.1.6 |
evHVACStatusAirsysAlarmClockAirsys HVAC clock card eventro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.4.1.7 |
evHVACStatusAirsysAlarmHumidProbeAirsys HVAC humidity probe broken eventro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.4.1.8 |
evHVACStatusAirsysAlarmOutProbeAirsys HVAC outdoor probe broken eventro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.4.1.9 |
evHVACStatusAirsysAlarmBothCompressAirsys HVAC both compressors running eventro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.4.1.10 |
evHVACStatusAirsysAlarmGeneratorAirsys HVAC generator running eventro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.4.1.11 |
evHVACStatusAirsysAlarmConnectionAirsys HVAC controller connection eventro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.4.1.12 |
evHVACStatusAirsysAlarmInProbe1Airsys HVAC indoor probe broken eventro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.4.1.13 |
evHVACStatusAirsysAlarmInProbe2Airsys HVAC backup indoor probe broken eventro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.4.1.14 |
evHVACStatusAirsysTempOutAirsys HVAC outdoor temperaturero DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.4.2 |
evHVACStatusAirsysTempInAirsys HVAC indoor temperaturero DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.4.3 |
evHVACStatusAirsysTempInBackupAirsys HVAC backup indoor temperaturero DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.4.4 |
evHVACStatusAirsysHumidInAirsys HVAC indoor humidityro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.4.5 |
evHVACStatusAirsysUnitTableAirsys HVAC unit alarm status table SEQUENCE OF HVACStatusAirsysUnit .1.3.6.1.4.1.3052.23.1.11.4.6 |
evHVACStatusAirsysUnitEntryAirsys HVAC unit alarm status table entry HVACStatusAirsysUnit .1.3.6.1.4.1.3052.23.1.11.4.6.1 |
evHVACStatusAirsysUnitIndexIndex for Airsys HVAC unitro Integer32 .1.3.6.1.4.1.3052.23.1.11.4.6.1.1 |
evHVACStatusAirsysUnitTempSupplyAirsys HVAC unit supply temperaturero DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.4.6.1.2 |
evHVACStatusAirsysUnitFanspeedAirsys HVAC unit fan speedro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.4.6.1.3 |
evHVACStatusAirsysUnitFreeOpeningAirsys HVAC unit free cooling vent opening percentagero DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.4.6.1.4 |
evHVACStatusAirsysUnitStatusAirsys HVAC unit running statusro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.4.6.1.5 |
evHVACStatusAirsysUnitLockedAirsys HVAC unit locked statusro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.4.6.1.6 |
evHVACStatusAirsysUnitCompressorAirsys HVAC unit state of compressorro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.4.6.1.7 |
evHVACStatusAirsysUnitHeaterAirsys HVAC unit state of heaterro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.4.6.1.8 |
evHVACStatusAirsysURuntimeSupplyFanAirsys HVAC unit run time of supply fan in hoursro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.4.6.1.9 |
evHVACStatusAirsysURuntimeCompressorAirsys HVAC unit run time of compressor in hoursro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.4.6.1.10 |
evHVACStatusAirsysURuntimeHeatAirsys HVAC unit run time of heating in hoursro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.4.6.1.11 |
evHVACStatusAirsysURuntimeFreeCoolingAirsys HVAC unit run time of free cooling in hoursro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.4.6.1.12 |
evHVACStatusAirsysUCountSupplyFanAirsys HVAC unit number of times supply fan has startedro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.4.6.1.13 |
evHVACStatusAirsysUCountCompressorAirsys HVAC unit number of times compressor has startedro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.4.6.1.14 |
evHVACStatusAirsysUCountHeatAirsys HVAC unit number of times heating has startedro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.4.6.1.15 |
evHVACStatusAirsysUCountFreeCoolingAirsys HVAC unit number of times free cooling has startedro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.4.6.1.16 |
evHVACStatusAirsysDayAirsys HVAC controller dayro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.4.7 |
evHVACStatusAirsysDateAirsys HVAC controller datero DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.4.8 |
evHVACStatusAirsysTimeAirsys HVAC controller timero DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.4.9 |
evHVACStatusAirsysVersionAirsys HVAC controller software versionro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.1.11.4.10 |
backupBattStatus OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.1.12 |
liBattStatus OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.1.12.1 |
liBattPercentChargeLithium Battery State Charge in Percent (0% to 100%)ro Integer32 .1.3.6.1.4.1.3052.23.1.12.1.1 |
liBattRunningIs the unit running on battery backup: (TRUE/FALSE) or (1/0)ro Integer32 .1.3.6.1.4.1.3052.23.1.12.1.2 |
config OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2 |
eventSensorBasics OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.1 |
esNumberEventSensorsThe number of EventSensors recognized by the unit, including the internal EventSensor. Range: 1-17ro Integer32 .1.3.6.1.4.1.3052.23.2.1.1 |
esTableThe table of what EventSensors are attached to the unit, including the internal EventSensor SEQUENCE OF ESExist .1.3.6.1.4.1.3052.23.2.1.2 |
esEntryTable entry for EventSensor table ESExist .1.3.6.1.4.1.3052.23.2.1.2.1 |
esIndexThis number refers to an EventSensor; it has the same meaning as the esIndexES object (see above), except that this object is used only within the esTable branch. This object's allowable values are 1 through 16, and 200. 200 always refers to the EventSensor inside the unit. 1 through 16 refer to additional attached EventSensors. The number corresponding to an EventSensor is determined by the user at the initial configuration time. If there is an internal sensor in the unit, it will always be the first item in the Sensor Events setup menu. For example, if a new EventSensor is configured as the 2nd entry AFTER the internal EventSensor (if one exists) in the Sensor Events Setup Menu, then that EventSensor will be known from then on as EventSensor 2. All point indeces with esIndex=2 will now refer to that particular EventSensor.ro Integer32 .1.3.6.1.4.1.3052.23.2.1.2.1.1 |
esNameThe name of the EventSensorro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.1.2.1.2 |
esIDThe factory-assigned ID of the EventSensorro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.1.2.1.3 |
esNumberTempSensorsThe number of temperature sensors on the EventSensorro Integer32 .1.3.6.1.4.1.3052.23.2.1.2.1.4 |
esTempReportingModeDescription of how temperature values should be interpreted.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.1.2.1.5 |
esNumberCCsThe number of contact closures on the EventSensor.ro Integer32 .1.3.6.1.4.1.3052.23.2.1.2.1.6 |
esCCReportingModeDescription of how CC values should be interpreted.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.1.2.1.7 |
esNumberHumidSensorsThe number of humidity sensors on the EventSensor.ro Integer32 .1.3.6.1.4.1.3052.23.2.1.2.1.8 |
esHumidReportingModeDescription of how humidity sensor values should be interpreted.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.1.2.1.9 |
esNumberNoiseSensorsThe number of noise sensors on the EventSensor.ro Integer32 .1.3.6.1.4.1.3052.23.2.1.2.1.10 |
esNoiseReportingModeDescription of how noise sensor values should be interpreted.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.1.2.1.11 |
esNumberAirflowSensorsThe number of airflow sensors on the EventSensor.ro Integer32 .1.3.6.1.4.1.3052.23.2.1.2.1.12 |
esAirflowReportingModeDescription of how airflow sensor values should be interpreted.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.1.2.1.13 |
esNumberAnalogThe number of analog inputs on the EventSensor.ro Integer32 .1.3.6.1.4.1.3052.23.2.1.2.1.14 |
esAnalogReportingModeDescription of how analog input values should be interpreted.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.1.2.1.15 |
esNumberOutputsThe number of outputs (relay or power) on the EventSensorro Integer32 .1.3.6.1.4.1.3052.23.2.1.2.1.16 |
esOutputReportingModeDescription of how output values should be interpreted.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.1.2.1.17 |
esTempCombinedStatusCombined status string intended to be parsed by NMS: name`value`scale`eventState`eventColorCodero DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.1.2.1.18 |
esCCCombinedStatusBlock1Combined status string intended to be parsed by NMS: numInBlock~name1`value1`eventColorCode1`alias1~name2`value2`eventColorCode2`alias2~...name8`value8`eventColorCode8`alias8ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.1.2.1.19 |
esCCCombinedStatusBlock2Combined status string intended to be parsed by NMS: numInBlock~name9`value9`eventColorCode9`alias9~name10`value10`eventColorCode10`alias10~...name16`value16`eventColorCode16`alias16ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.1.2.1.20 |
esCCCombinedStatusBlock3Combined status string intended to be parsed by NMS: numInBlock~name17`value17`eventColorCode17`alias17~name18`value18`eventColorCode18`alias18~...name24`value24`eventColorCode24`alias24ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.1.2.1.21 |
esCCCombinedStatusBlock4Combined status string intended to be parsed by NMS: numInBlock~name25`value25`eventColorCode25`alias25~name26`value26`eventColorCode26`alias26~...name32`value32`eventColorCode32`alias32ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.1.2.1.22 |
esCCCombinedStatusBlock5Combined status string intended to be parsed by NMS: numInBlock~name33`value33`eventColorCode33`alias33~name34`value34`eventColorCode34`alias35~...name40`value40`eventColorCode40`alias40ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.1.2.1.23 |
esCCCombinedStatusBlock6Combined status string intended to be parsed by NMS: numInBlock~name41`value41`eventColorCode41`alias41~name42`value42`eventColorCode42`alias43~...name48`value48`eventColorCode48`alias48ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.1.2.1.24 |
esCCCombinedStatusBlock7Combined status string intended to be parsed by NMS: numInBlock~name49`value49`eventColorCode49`alias49~name50`value50`eventColorCode50`alias50~...name56`value56`eventColorCode56`alias56ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.1.2.1.25 |
esCCCombinedStatusBlock8Combined status string intended to be parsed by NMS: numInBlock~name57`value57`eventColorCode57`alias57~name57`value57`eventColorCode564`alias57~...name64`value64`eventColorCode64`alias64ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.1.2.1.26 |
esHumidCombinedStatusCombined status string intended to be parsed by NMS: name`value`eventState`eventColorCodero DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.1.2.1.27 |
esAnalogCombinedStatusBlock1Combined status string intended to be parsed by NMS: numInBlock~name1`value1`units1`eventState`eventColorCode1~name2`value2`units2`eventState`eventColorCode2~...ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.1.2.1.28 |
esAnalogCombinedStatusBlock2Combined status string intended to be parsed by NMS: numInBlock~name9`value9`units9`eventState9`eventColorCode9~...ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.1.2.1.29 |
esAnalogCombinedStatusBlock3Combined status string intended to be parsed by NMS: numInBlock~namex`valuex`unitsx`eventStatex`eventColorCodex~...ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.1.2.1.30 |
esAnalogCombinedStatusBlock4Combined status string intended to be parsed by NMS: numInBlock~namex`valuex`unitsx`eventStatex`eventColorCodex~...ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.1.2.1.31 |
esAnalogCombinedStatusBlock5Combined status string intended to be parsed by NMS: numInBlock~namex`valuex`unitsx`eventStatex`eventColorCodex~...ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.1.2.1.32 |
esAnalogCombinedStatusBlock6Combined status string intended to be parsed by NMS: numInBlock~namex`valuex`unitsx`eventStatex`eventColorCodex~...ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.1.2.1.33 |
esOutputCombinedStatusBlock1Combined status string intended to be parsed by NMS: numInBlock~namex`valuex`unitsx`eventStatex`eventColorCodex~...ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.1.2.1.34 |
esOutputCombinedStatusBlock2Combined status string intended to be parsed by NMS: numInBlock`namex`valuex`aliasx~namey`valuey`aliasy~...namez`valuez`aliaszro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.1.2.1.35 |
esNewSensorsString representing the number of new (attached but unconfigured) EventSensorsro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.1.3 |
eventSensorPointConfig OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.2 |
esPointConfigTempTableThis table organizes 3 basic attributes of temperature sensor points. A point is a particular sensor on an EventSensor. The 3 point attributes organizes in this table are: 1. the configuration item (e.g., enable, name, etc.) 2. the eventsensor on which this point resides 3. the point number (always 1 for temp sensors) Points are referenced by a point config index. The point config index is a string of 2 numbers separated by periods. It contains all the information necessary for getting a piece of data off an event sensor within the context of this emperature point config table ; namely, which EventSensor, and which sensor (a.k.a. point) (always 1 for temperature sensors). SEQUENCE OF ESPointConfigTemp .1.3.6.1.4.1.3052.23.2.2.1 |
esPointConfigTempEntryEntry for EventSensor point config temperature table ESPointConfigTemp .1.3.6.1.4.1.3052.23.2.2.1.1 |
espcTempIndexESThe part of the point index that refers to an EventSensor. The point config index is a string of 2 numbers separated by a period. It contains all the information necessary for getting a piece of data off an event sensor within the the context of the eventsensor point config temperature table; namely, which EventSensor, and which sensor (a.k.a. point). This object's allowable values are 1 through 16, and 200. 200 always refers to the EventSensor inside the unit. 1 through 16 refer to additional attached EventSensors. The number corresponding to an EventSensor is determined by the user at the initial configuration time. If there is an internal sensor in the unit, it will always be the first item in the Sensor Events setup menu. For example, if a new EventSensor is configured as the 2nd entry AFTER the internal EventSensor (if one exists) in the Sensor Events Setup Menu, then that EventSensor will be known from then on as EventSensor 2. All point indeces with esIndexES=2 will now refer to that particular EventSensor.ro Integer32 .1.3.6.1.4.1.3052.23.2.2.1.1.1 |
espcTempIndexPointThe part of the point index that delineates which sensor on the EventSensor. So this combined with espcTempIndexES (which EventSensor) uniquely defines each point attached to a unit within the context of temperature point configuration.ro Integer32 .1.3.6.1.4.1.3052.23.2.2.1.1.2 |
espcTempEnableON/OFF enable this temperature sensorrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.2.1.1.3 |
espcTempScaleScale (C/F) for this temperature sensorrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.2.1.1.4 |
espcTempDeadbandDeadband for this temperature sensor (in floating-point format)rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.2.1.1.5 |
espcTempVHighTempVery high temperature event threshold for this temperature sensor (in floating-point format)rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.2.1.1.6 |
espcTempVHighActionsVery high temperature event actions for this temperature sensorrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.2.1.1.7 |
espcTempVHighTrapnumVery high temperature event trap number for this temperature sensorrw Integer32 .1.3.6.1.4.1.3052.23.2.2.1.1.8 |
espcTempVHighClassVery high temperature event class for this temperature sensorrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.2.1.1.9 |
espcTempHighTempHigh temperature event threshold for this temperature sensor (in floating-point format)rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.2.1.1.10 |
espcTempHighActionsHigh temperature event actions for this temperature sensorrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.2.1.1.11 |
espcTempHighTrapnumHigh temperature event trap number for this temperature sensorrw Integer32 .1.3.6.1.4.1.3052.23.2.2.1.1.12 |
espcTempHighClassHigh temperature event class for this temperature sensorrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.2.1.1.13 |
espcTempNormalActionsReturn-to-normal event actions for this temperature sensorrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.2.1.1.14 |
espcTempNormalTrapnumReturn-to-normal event trap number for this temperature sensorrw Integer32 .1.3.6.1.4.1.3052.23.2.2.1.1.15 |
espcTempNormalClassReturn-to-normal event class for this temperature sensorrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.2.1.1.16 |
espcTempLowTempLow temperature event threshold for this temperature sensor (in floating-point format)rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.2.1.1.17 |
espcTempLowActionsLow temperature event actions for this temperature sensorrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.2.1.1.18 |
espcTempLowTrapnumLow temperature event trap number for this temperature sensorrw Integer32 .1.3.6.1.4.1.3052.23.2.2.1.1.19 |
espcTempLowClassLow temperature event class for this temperature sensorrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.2.1.1.20 |
espcTempVLowTempVery Low temperature event threshold for this temperature sensor (in floating-point format)rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.2.1.1.21 |
espcTempVLowActionsVery Low temperature event actions for this temperature sensorrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.2.1.1.22 |
espcTempVLowTrapnumVery Low temperature event trap number for this temperature sensorrw Integer32 .1.3.6.1.4.1.3052.23.2.2.1.1.23 |
espcTempVLowClassVery Low temperature event class for this temperature sensorrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.2.1.1.24 |
espcTempGroupName for this temperature sensor grouprw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.2.1.1.25 |
esPointConfigCCTableThis table organizes 3 basic attributes of contact closure points. A point is a particular sensor on an EventSensor. The 3 point attributes organizes in this table are: 1. the configuration item (e.g., enable, name, etc.) 2. the eventsensor on which this point resides 3. the point number Points are referenced by a point config index. The point config index is a string of 2 numbers separated by a period. It contains all the information necessary for getting a piece of data off an event sensor within the context of this contact closure point config table ; namely, which EventSensor and which sensor. SEQUENCE OF ESPointConfigCC .1.3.6.1.4.1.3052.23.2.2.2 |
esPointConfigCCEntryEntry for EventSensor point config contact closure table ESPointConfigCC .1.3.6.1.4.1.3052.23.2.2.2.1 |
espcCCIndexESThe part of the point index that refers to an EventSensor. The point config index is a string of 2 numbers separated by a period. It contains all the information necessary for getting a piece of data off an event sensor within the the context of the eventsensor point config contact closure table; namely, which EventSensor and which sensor (a.k.a. point). This object's allowable values are 1 through 16, and 200. 200 always refers to the EventSensor inside the unit. 1 through 16 refer to additional attached EventSensors.ro Integer32 .1.3.6.1.4.1.3052.23.2.2.2.1.1 |
espcCCIndexPointThe part of the point index that delineates which sensor on the EventSensor. So this combined with espcCCIndexES (which EventSensor) uniquely defines each point attached to a unit within the context of contact closure point configuration.ro Integer32 .1.3.6.1.4.1.3052.23.2.2.2.1.2 |
espcCCEnableON/OFF enable for this contact closurerw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.2.2.1.3 |
espcCCNameName for this contact closurerw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.2.2.1.4 |
espcCCEventStateEvent state for this contact closurerw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.2.2.1.5 |
espcCCThresholdEvent threshold (seconds) for this contact closurerw Integer32 .1.3.6.1.4.1.3052.23.2.2.2.1.6 |
espcCCEventActionsEvent actions for this contact closurerw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.2.2.1.7 |
espcCCEventTrapnumEvent trap number for this contact closurerw Integer32 .1.3.6.1.4.1.3052.23.2.2.2.1.8 |
espcCCEventClassEvent class for this contact closurerw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.2.2.1.9 |
espcCCNormalActionsReturn-to-normal actions for this contact closurerw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.2.2.1.10 |
espcCCNormalTrapnumReturn-to-normal trap number for this contact closurerw Integer32 .1.3.6.1.4.1.3052.23.2.2.2.1.11 |
espcCCNormalClassReturn-to-normal class for this contact closurerw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.2.2.1.12 |
espcCCAlarmAliasEvent alias for this contact closurerw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.2.2.1.13 |
espcCCNormalAliasReturn-to-normal alias for this contact closurerw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.2.2.1.14 |
espcCCNormalThresholdEvent threshold (seconds) for this contact closure to return to normalrw Integer32 .1.3.6.1.4.1.3052.23.2.2.2.1.15 |
espcCCOverrideGlobalReminderOverride global reminder interval (evReminderInterval) for this CC.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.2.2.1.16 |
espcCCReminderIntervalIndividual reminder interval for this CC, applicable when the global reminder is overriden.rw Integer32 .1.3.6.1.4.1.3052.23.2.2.2.1.17 |
espcCCGroupName for this contact closure grouprw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.2.2.1.18 |
esPointConfigHumidTableThis table organizes 3 basic attributes of humidity points. A point is a particular sensor on an EventSensor. The 3 point attributes organizes in this table are: 1. the configuration item (e.g., enable, name, etc.) 2. the eventsensor on which this point resides 3. the point number (always 1 for humidity sensors) Points are referenced by a point config index. The point config index is a string of 2 numbers separated by a period. It contains all the information necessary for getting a piece of data off an event sensor within the context of this humidity point config table ; namely, which EventSensor and which sensor. SEQUENCE OF ESPointConfigHumid .1.3.6.1.4.1.3052.23.2.2.3 |
esPointConfigHumidEntryEntry for EventSensor point config humidity table ESPointConfigHumid .1.3.6.1.4.1.3052.23.2.2.3.1 |
espcHumidIndexESThe part of the point index that refers to an EventSensor. The point config index is a string of 2 numbers separated by a period. It contains all the information necessary for getting a piece of data off an event sensor within the the context of the eventsensor point config contact closure table; namely, which EventSensor and which sensor (a.k.a. point). This object's allowable values are 1 through 16, and 200. 200 always refers to the EventSensor inside the unit. 1 through 16 refer to additional attached EventSensors.ro Integer32 .1.3.6.1.4.1.3052.23.2.2.3.1.1 |
espcHumidIndexPointThe part of the point index that delineates which sensor on the EventSensor. So this combined with espcHumidIndexES (which EventSensor) uniquely defines each point attached to a unit within the context of contact closure point configuration.ro Integer32 .1.3.6.1.4.1.3052.23.2.2.3.1.2 |
espcHumidEnableON/OFF enable for this humidity sensorrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.2.3.1.3 |
espcHumidDeadbandDeadband for this humidity sensorrw Integer32 .1.3.6.1.4.1.3052.23.2.2.3.1.4 |
espcHumidVHighHumidVery high event threshold for this humidity sensorrw Integer32 .1.3.6.1.4.1.3052.23.2.2.3.1.5 |
espcHumidVHighActionsVery high event actions for this humidity sensorrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.2.3.1.6 |
espcHumidVHighTrapnumVery high event trap number for this humidity sensorrw Integer32 .1.3.6.1.4.1.3052.23.2.2.3.1.7 |
espcHumidVHighClassVery high event class for this humidity sensorrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.2.3.1.8 |
espcHumidHighHumidHigh event threshold for this humidity sensorrw Integer32 .1.3.6.1.4.1.3052.23.2.2.3.1.9 |
espcHumidHighActionsHigh event actions for this humidity sensorrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.2.3.1.10 |
espcHumidHighTrapnumHigh event trap number for this humidity sensorrw Integer32 .1.3.6.1.4.1.3052.23.2.2.3.1.11 |
espcHumidHighClassHigh event class for this humidity sensorrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.2.3.1.12 |
espcHumidNormalActionsReturn-to-normal actions for this humidity sensorrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.2.3.1.13 |
espcHumidNormalTrapnumReturn-to-normal trap number for this humidity sensorrw Integer32 .1.3.6.1.4.1.3052.23.2.2.3.1.14 |
espcHumidNormalClassReturn-to-normal class for this humidity sensorrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.2.3.1.15 |
espcHumidLowHumidLow event threshold for this humidity sensorrw Integer32 .1.3.6.1.4.1.3052.23.2.2.3.1.16 |
espcHumidLowActionsLow event actions for this humidity sensorrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.2.3.1.17 |
espcHumidLowTrapnumLow event trap number for this humidity sensorrw Integer32 .1.3.6.1.4.1.3052.23.2.2.3.1.18 |
espcHumidLowClassLow event class for this humidity sensorrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.2.3.1.19 |
espcHumidVLowHumidVery low event threshold for this humidity sensorrw Integer32 .1.3.6.1.4.1.3052.23.2.2.3.1.20 |
espcHumidVLowActionsVery low event actions for this humidity sensorrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.2.3.1.21 |
espcHumidVLowTrapnumVery low event trap number for this humidity sensorrw Integer32 .1.3.6.1.4.1.3052.23.2.2.3.1.22 |
espcHumidVLowClassVery low event class for this humidity sensorrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.2.3.1.23 |
espcHumidGroupName for this humidity sensor grouprw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.2.3.1.24 |
esPointConfigAITableThis table organizes 3 basic attributes of analog input points. A point is a particular sensor on an EventSensor. The 3 point attributes organizes in this table are: 1. the configuration item (e.g., enable, name, etc.) 2. the eventsensor on which this point resides 3. the point number Points are referenced by a point config index. The point config index is a string of 2 numbers separated by a period. It contains all the information necessary for getting a piece of data off an event sensor within the context of this analog input point config table ; namely, which EventSensor and which sensor. SEQUENCE OF ESPointConfigAnalogInput .1.3.6.1.4.1.3052.23.2.2.5 |
esPointConfigAIEntryEntry for EventSensor point config analog input table ESPointConfigAnalogInput .1.3.6.1.4.1.3052.23.2.2.5.1 |
espcAIIndexESThe part of the point index that refers to an EventSensor. The point config index is a string of 2 numbers separated by a period. It contains all the information necessary for getting a piece of data off an event sensor within the the context of the eventsensor point config contact closure table; namely, which EventSensor and which sensor (a.k.a. point). This object's allowable values are 1 through 16, and 200. 200 always refers to the EventSensor inside the unit. 1 through 16 refer to additional attached EventSensors.ro Integer32 .1.3.6.1.4.1.3052.23.2.2.5.1.1 |
espcAIIndexPointThe part of the point index that delineates which sensor on the EventSensor. So this combined with espcAIIndexES (which EventSensor) uniquely defines each point attached to a unit within the context of contact closure point configuration.ro Integer32 .1.3.6.1.4.1.3052.23.2.2.5.1.2 |
espcAIEnableON/OFF for this analog input sensorrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.2.5.1.3 |
espcAIDeadbandDeadband for this analog input sensorrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.2.5.1.5 |
espcAIVhighValueVery high event threshold (decivolts or tenths of milliamps) for this analog input sensorrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.2.5.1.6 |
espcAIVhighActionsVery high event actions for this analog input sensorrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.2.5.1.7 |
espcAIVhighTrapnumVery high event trap number for this analog input sensorrw Integer32 .1.3.6.1.4.1.3052.23.2.2.5.1.8 |
espcAIVhighClassVery high event class for this analog input sensorrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.2.5.1.9 |
espcAIHighValueHigh event threshold (decivolts or tenths of milliamps) for this analog input sensorrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.2.5.1.10 |
espcAIHighActionsHigh event actions for this analog input sensorrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.2.5.1.11 |
espcAIHighTrapnumHigh event trap number for this analog input sensorrw Integer32 .1.3.6.1.4.1.3052.23.2.2.5.1.12 |
espcAIHighClassHigh event class for this analog input sensorrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.2.5.1.13 |
espcAINormalActionsReturn-to-normal actions for this analog input sensorrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.2.5.1.14 |
espcAINormalTrapnumReturn-to-normal trap number for this analog input sensorrw Integer32 .1.3.6.1.4.1.3052.23.2.2.5.1.15 |
espcAINormalClassReturn-to-normal class for this analog input sensorrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.2.5.1.16 |
espcAILowValueLow event threshold (decivolts or tenths of milliamps) for this analog input sensorrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.2.5.1.17 |
espcAILowActionsLow event actions for this analog input sensorrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.2.5.1.18 |
espcAILowTrapnumLow event trap number for this analog input sensorrw Integer32 .1.3.6.1.4.1.3052.23.2.2.5.1.19 |
espcAILowClassLow event class for this analog input sensorrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.2.5.1.20 |
espcAIVlowValueVery low event threshold (decivolts or tenths of milliamps) for this analog input sensorrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.2.5.1.21 |
espcAIVlowActionsVery low event actions for this analog input sensorrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.2.5.1.22 |
espcAIVlowTrapnumVery low event actions for this analog input sensorrw Integer32 .1.3.6.1.4.1.3052.23.2.2.5.1.23 |
espcAIVlowClassVery low event class for this analog input sensorrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.2.5.1.24 |
espcAIConvUnitNameConverstion unit name for this analog input sensorrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.2.5.1.25 |
espcAIConvHighValueConversion high value for this analog input sensorrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.2.5.1.26 |
espcAIConvHighUnitConversion high unit value for this analog input sensorrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.2.5.1.27 |
espcAIConvLowValueConversion low value for this analog input sensorrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.2.5.1.29 |
espcAIConvLowUnitConversion unit low unit value for this analog input sensorrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.2.5.1.30 |
espcAIDisplayFormatAnalog input display formatrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.2.5.1.32 |
espcAIGroupName for this Analog input grouprw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.2.5.1.33 |
esPointConfigOutputTableThis table organizes configuration items for output points. A point is a particular sensor on an EventSensor. The 3 point attributes organized in this table are: 1. the configuration item (e.g., enable, name, etc.) 2. the eventsensor on which this point resides 3. the point number Points are referenced by a point config index. The point config index is a string of 2 numbers separated by a period. It contains all the information necessary for getting a piece of data off an event sensor within the context of this output config table ; namely, which EventSensor and which sensor. SEQUENCE OF ESPointConfigOutput .1.3.6.1.4.1.3052.23.2.2.6 |
esPointConfigOutputEntryEntry for EventSensor point config output table ESPointConfigOutput .1.3.6.1.4.1.3052.23.2.2.6.1 |
espcOutputIndexESThe part of the point index that refers to an EventSensor. The point config index is a string of 2 numbers separated by a period. It contains all the information necessary for getting a piece of data off an event sensor within the the context of the eventsensor point config contact closure table; namely, which EventSensor and which sensor (a.k.a. point). This object's allowable values are 1 through 16, and 200. 200 always refers to the EventSensor inside the unit. 1 through 16 refer to additional attached EventSensors.ro Integer32 .1.3.6.1.4.1.3052.23.2.2.6.1.1 |
espcOutputIndexPointThe part of the point index that delineates which sensor on the EventSensor. So this combined with espcOutputIndexES (which EventSensor) uniquely defines each point attached to a unit within the context of output point configuration.ro Integer32 .1.3.6.1.4.1.3052.23.2.2.6.1.2 |
espcOutputEnableEnables the output event for this output. This has no effect on whether the relay changes state, only on whether a state change triggers an event.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.2.6.1.3 |
espcOutputActiveStateWhich state is considered the active state: energized/de-energized.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.2.6.1.4 |
espcOutputTypeOutput type: RELAY, POWER, SSR, TTL.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.2.6.1.5 |
espcOutputAliasValueOutput alias corresponding to its event state.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.2.6.1.6 |
espcOutputAliasColorOutput color corresponding to its event state.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.2.6.1.7 |
espcOutputActiveAliasAlias for the output active state.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.2.6.1.10 |
espcOutputActiveColorOutput color (as rendered in the web UI, in RGB hex format) corresponding to the output active state.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.2.6.1.11 |
espcOutputActiveActionsActions for the output active event.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.2.6.1.12 |
espcOutputActiveTrapnumActions for the output active event.rw Integer32 .1.3.6.1.4.1.3052.23.2.2.6.1.13 |
espcOutputActiveClassClass (severity) for the output active event.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.2.6.1.14 |
espcOutputInactiveAliasAlias for the output inactive state.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.2.6.1.20 |
espcOutputInactiveColorOutput color (as rendered in the web UI, in RGB hex format) corresponding to the output inactive state.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.2.6.1.21 |
espcOutputInactiveActionsActions for the output inactive event.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.2.6.1.22 |
espcOutputInactiveTrapnumActions for the output inactive event.rw Integer32 .1.3.6.1.4.1.3052.23.2.2.6.1.23 |
espcOutputInactiveClassClass (severity) for the output inactive event.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.2.6.1.24 |
espcOutputGroupName for this Ouput Grouprw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.2.6.1.25 |
serialPorts OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.3 |
numberPortsNumber of RS-232 ports found. Range: 2 or 4ro Integer32 .1.3.6.1.4.1.3052.23.2.3.1 |
portConfigTablePort config table SEQUENCE OF PortConfig .1.3.6.1.4.1.3052.23.2.3.2 |
portConfigEntryPort config entry PortConfig .1.3.6.1.4.1.3052.23.2.3.2.1 |
portConfigIndexIndex for portsro Integer32 .1.3.6.1.4.1.3052.23.2.3.2.1.1 |
portConfigBaudBaud rate, 19200, 9600, etc.rw Integer32 .1.3.6.1.4.1.3052.23.2.3.2.1.2 |
portConfigDataFormatValue representing word length, parity, and stop bits: 0=8N1, 1=7E1, 2=7O1, 3=7N1, 4=8O2rw Integer32 .1.3.6.1.4.1.3052.23.2.3.2.1.3 |
portConfigStripPtOutputLfsStrip passthrough LFs sent to device on this port: 1=yes, 0=no.rw Integer32 .1.3.6.1.4.1.3052.23.2.3.2.1.4 |
portConfigStripPtInputLfsStrip passthrough LFs received from device on this port: 1=yes, 0=no.rw Integer32 .1.3.6.1.4.1.3052.23.2.3.2.1.5 |
portConfigMaskEnable1=Use the character mask on this port. 0=Do not use the mask. When the mask is enabled, the following ASCII characters are ignored on the port: 0, 1, 4-9, 11, 12, 14-31, 128-255. When the mask is disabled, all characters are accepted on the port.rw Integer32 .1.3.6.1.4.1.3052.23.2.3.2.1.7 |
portConfigDAEnable1=Enable the Data Alarm Evaluator for data on this port. 0=Do not evaluate data on this port.rw Integer32 .1.3.6.1.4.1.3052.23.2.3.2.1.8 |
portConfigStoreAlarmsDPTON/OFF: store alarms received during passthroughrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.3.2.1.9 |
portConfigRecordTimeoutTimeout after last unterminated data received upon which data collected so far is stored as a record.rw Integer32 .1.3.6.1.4.1.3052.23.2.3.2.1.10 |
portConfigDataTypeHow the port interprets incoming data: ASCII/BINARYrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.3.2.1.11 |
portConfigEtxToCRLFON/OFF whether the port translates incoming ETX to CRLFrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.3.2.1.12 |
portConfigMLREnableON/OFF Whether Multiline Records are collected on this port.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.3.2.1.13 |
portConfigMLRStartField1PosPosition of MLR start field 1rw Integer32 .1.3.6.1.4.1.3052.23.2.3.2.1.14 |
portConfigMLRStartField1TextText to match MLR start field 1rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.3.2.1.15 |
portConfigMLRStartField2PosPosition of MLR start field 2rw Integer32 .1.3.6.1.4.1.3052.23.2.3.2.1.16 |
portConfigMLRStartField2TextText to match MLR start field 2rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.3.2.1.17 |
portConfigMLRNumLinesBeforeNumber of lines before the starting line which should be included in the MLRrw Integer32 .1.3.6.1.4.1.3052.23.2.3.2.1.18 |
portConfigMLREndDetectionHow the MLR parser determines what ends an MLR: by FORMULA, number of lines received so far (COUNT), or number of blank lines received so far (BLANKS)rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.3.2.1.19 |
portConfigMLRLineCountNumber of lines in the MLR (used by the end detection mode)rw Integer32 .1.3.6.1.4.1.3052.23.2.3.2.1.20 |
portConfigMLREndField1PosPosition of MLR end field 1rw Integer32 .1.3.6.1.4.1.3052.23.2.3.2.1.21 |
portConfigMLREndField1TextText to match MLR end field 1rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.3.2.1.22 |
portConfigMLREndField2PosPosition of MLR end field 2rw Integer32 .1.3.6.1.4.1.3052.23.2.3.2.1.23 |
portConfigMLREndField2TextText to match MLR end field 2rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.3.2.1.24 |
portConfigMLRUseComplexRulesON/OFF MLR parser uses complex rules (field possitions/ formulas, etc.)rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.3.2.1.25 |
portConfigBufferPTON/OFF records received during passthrough mode are buffered/stored in the databaserw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.3.2.1.26 |
portConfigIdThe text identifer for the portrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.3.2.1.27 |
portConfigModeMode of the serial port.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.3.2.1.28 |
portConfigHskHandshaking mode of the serial port.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.3.2.1.29 |
network OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.4 |
interface OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.4.1 |
ethernet OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.4.1.1 |
ethernet1 OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.4.1.1.1 |
eth1ModeMode of the Ethernet1 interface: STATIC,DHCP,VLANro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.1.1.1.1 |
eth1AddressEthernet1 IP addressrw IpAddress .1.3.6.1.4.1.3052.23.2.4.1.1.1.2 |
eth1SubnetMaskEthernet1 subnet maskrw IpAddress .1.3.6.1.4.1.3052.23.2.4.1.1.1.3 |
eth1RouterEthernet1 routerrw IpAddress .1.3.6.1.4.1.3052.23.2.4.1.1.1.4 |
eth1VLAN OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.4.1.1.1.5 |
eth1VLAN1 OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.4.1.1.1.5.1 |
eth1VLAN1IDEthernet1 VLAN1 IDrw Integer32 .1.3.6.1.4.1.3052.23.2.4.1.1.1.5.1.1 |
eth1VLAN1PriorityEthernet1 VLAN1 priorityrw Integer32 .1.3.6.1.4.1.3052.23.2.4.1.1.1.5.1.2 |
eth1VLAN1AddressEthernet1 VLAN1 IP addressrw IpAddress .1.3.6.1.4.1.3052.23.2.4.1.1.1.5.1.3 |
eth1VLAN1SubnetMaskEthernet1 VLAN1 subnet maskrw IpAddress .1.3.6.1.4.1.3052.23.2.4.1.1.1.5.1.4 |
eth1VLAN1RouterEthernet1 VLAN1 routerrw IpAddress .1.3.6.1.4.1.3052.23.2.4.1.1.1.5.1.5 |
eth1VLAN2 OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.4.1.1.1.5.2 |
eth1VLAN2IDEthernet1 VLAN2 IDrw Integer32 .1.3.6.1.4.1.3052.23.2.4.1.1.1.5.2.1 |
eth1VLAN2PriorityEthernet1 VLAN2 priorityrw Integer32 .1.3.6.1.4.1.3052.23.2.4.1.1.1.5.2.2 |
eth1VLAN2AddressEthernet1 VLAN2 IP addressrw IpAddress .1.3.6.1.4.1.3052.23.2.4.1.1.1.5.2.3 |
eth1VLAN2SubnetMaskEthernet1 VLAN2 subnet maskrw IpAddress .1.3.6.1.4.1.3052.23.2.4.1.1.1.5.2.4 |
eth1VLAN2RouterEthernet1 VLAN2 routerrw IpAddress .1.3.6.1.4.1.3052.23.2.4.1.1.1.5.2.5 |
eth1VLAN3 OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.4.1.1.1.5.3 |
eth1VLAN3IDEthernet1 VLAN3 IDrw Integer32 .1.3.6.1.4.1.3052.23.2.4.1.1.1.5.3.1 |
eth1VLAN3PriorityEthernet1 VLAN3 priorityrw Integer32 .1.3.6.1.4.1.3052.23.2.4.1.1.1.5.3.2 |
eth1VLAN3AddressEthernet1 VLAN3 IP addressrw IpAddress .1.3.6.1.4.1.3052.23.2.4.1.1.1.5.3.3 |
eth1VLAN3SubnetMaskEthernet1 VLAN3 subnet maskrw IpAddress .1.3.6.1.4.1.3052.23.2.4.1.1.1.5.3.4 |
eth1VLAN3RouterEthernet1 VLAN3 routerrw IpAddress .1.3.6.1.4.1.3052.23.2.4.1.1.1.5.3.5 |
eth1VLAN4 OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.4.1.1.1.5.4 |
eth1VLAN4IDEthernet1 VLAN4 IDrw Integer32 .1.3.6.1.4.1.3052.23.2.4.1.1.1.5.4.1 |
eth1VLAN4PriorityEthernet1 VLAN4 priorityrw Integer32 .1.3.6.1.4.1.3052.23.2.4.1.1.1.5.4.2 |
eth1VLAN4AddressEthernet1 VLAN4 IP addressrw IpAddress .1.3.6.1.4.1.3052.23.2.4.1.1.1.5.4.3 |
eth1VLAN4SubnetMaskEthernet1 VLAN4 subnet maskrw IpAddress .1.3.6.1.4.1.3052.23.2.4.1.1.1.5.4.4 |
eth1VLAN4RouterEthernet1 VLAN4 routerrw IpAddress .1.3.6.1.4.1.3052.23.2.4.1.1.1.5.4.5 |
eth1VLAN5 OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.4.1.1.1.5.5 |
eth1VLAN5IDEthernet1 VLAN5 IDrw Integer32 .1.3.6.1.4.1.3052.23.2.4.1.1.1.5.5.1 |
eth1VLAN5PriorityEthernet1 VLAN5 priorityrw Integer32 .1.3.6.1.4.1.3052.23.2.4.1.1.1.5.5.2 |
eth1VLAN5AddressEthernet1 VLAN5 IP addressrw IpAddress .1.3.6.1.4.1.3052.23.2.4.1.1.1.5.5.3 |
eth1VLAN5SubnetMaskEthernet1 VLAN5 subnet maskrw IpAddress .1.3.6.1.4.1.3052.23.2.4.1.1.1.5.5.4 |
eth1VLAN5RouterEthernet1 VLAN5 routerrw IpAddress .1.3.6.1.4.1.3052.23.2.4.1.1.1.5.5.5 |
eth1VLAN6 OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.4.1.1.1.5.6 |
eth1VLAN6IDEthernet1 VLAN6 IDrw Integer32 .1.3.6.1.4.1.3052.23.2.4.1.1.1.5.6.1 |
eth1VLAN6PriorityEthernet1 VLAN6 priorityrw Integer32 .1.3.6.1.4.1.3052.23.2.4.1.1.1.5.6.2 |
eth1VLAN6AddressEthernet1 VLAN6 IP addressrw IpAddress .1.3.6.1.4.1.3052.23.2.4.1.1.1.5.6.3 |
eth1VLAN6SubnetMaskEthernet1 VLAN6 subnet maskrw IpAddress .1.3.6.1.4.1.3052.23.2.4.1.1.1.5.6.4 |
eth1VLAN6RouterEthernet1 VLAN6 routerrw IpAddress .1.3.6.1.4.1.3052.23.2.4.1.1.1.5.6.5 |
eth1MACEthernet1 MACro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.1.1.1.6 |
eth1IPv6 OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.4.1.1.1.7 |
eth1IPv6ModeControls IPv6 operation for this Ethernet interface.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.1.1.1.7.1 |
eth1IPv6Static OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.4.1.1.1.7.2 |
eth1IPv6StaticAddresshe static IPv6 address to use for this interface when in operating in STATIC mode.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.1.1.1.7.2.1 |
eth1IPv6StaticRouterThe IPv6 router to engage as the default router when this interface operates in STATIC mode.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.1.1.1.7.2.2 |
eth1IPv6Auto OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.4.1.1.1.7.3 |
eth1IPv6AutoAddress1One of the automatically-acquired IPv6 addresses.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.1.1.1.7.3.1 |
eth1IPv6AutoAddress2One of the automatically-acquired IPv6 addresses.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.1.1.1.7.3.2 |
eth1IPv6AutoAddress3One of the automatically-acquired IPv6 addresses.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.1.1.1.7.3.3 |
eth1IPv6AutoAddress4One of the automatically-acquired IPv6 addresses.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.1.1.1.7.3.4 |
eth1IPv6LinkLocalAddressThe link local IPv6 address for this interface. This is present when the IPv6 mode is not OFF.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.1.1.1.7.4 |
ethernet2 OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.4.1.1.2 |
eth2ModeMode of the Ethernet2 interface: STATIC,DHCP,VLANro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.1.1.2.1 |
eth2AddressEthernet2 IP addressrw IpAddress .1.3.6.1.4.1.3052.23.2.4.1.1.2.2 |
eth2SubnetMaskEthernet2 subnet maskrw IpAddress .1.3.6.1.4.1.3052.23.2.4.1.1.2.3 |
eth2RouterEthernet2 routerrw IpAddress .1.3.6.1.4.1.3052.23.2.4.1.1.2.4 |
eth2VLAN OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.4.1.1.2.5 |
eth2VLAN1 OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.4.1.1.2.5.1 |
eth2VLAN1IDEthernet2 VLAN1 IDrw Integer32 .1.3.6.1.4.1.3052.23.2.4.1.1.2.5.1.1 |
eth2VLAN1PriorityEthernet2 VLAN1 priorityrw Integer32 .1.3.6.1.4.1.3052.23.2.4.1.1.2.5.1.2 |
eth2VLAN1AddressEthernet2 VLAN1 IP addressrw IpAddress .1.3.6.1.4.1.3052.23.2.4.1.1.2.5.1.3 |
eth2VLAN1SubnetMaskEthernet2 VLAN1 subnet maskrw IpAddress .1.3.6.1.4.1.3052.23.2.4.1.1.2.5.1.4 |
eth2VLAN1RouterEthernet2 VLAN1 routerrw IpAddress .1.3.6.1.4.1.3052.23.2.4.1.1.2.5.1.5 |
eth2VLAN2 OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.4.1.1.2.5.2 |
eth2VLAN2IDEthernet2 VLAN2 IDrw Integer32 .1.3.6.1.4.1.3052.23.2.4.1.1.2.5.2.1 |
eth2VLAN2PriorityEthernet2 VLAN2 priorityrw Integer32 .1.3.6.1.4.1.3052.23.2.4.1.1.2.5.2.2 |
eth2VLAN2AddressEthernet2 VLAN2 IP addressrw IpAddress .1.3.6.1.4.1.3052.23.2.4.1.1.2.5.2.3 |
eth2VLAN2SubnetMaskEthernet2 VLAN2 subnet maskrw IpAddress .1.3.6.1.4.1.3052.23.2.4.1.1.2.5.2.4 |
eth2VLAN2RouterEthernet2 VLAN2 routerrw IpAddress .1.3.6.1.4.1.3052.23.2.4.1.1.2.5.2.5 |
eth2VLAN3 OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.4.1.1.2.5.3 |
eth2VLAN3IDEthernet2 VLAN3 IDrw Integer32 .1.3.6.1.4.1.3052.23.2.4.1.1.2.5.3.1 |
eth2VLAN3PriorityEthernet2 VLAN3 priorityrw Integer32 .1.3.6.1.4.1.3052.23.2.4.1.1.2.5.3.2 |
eth2VLAN3AddressEthernet2 VLAN3 IP addressrw IpAddress .1.3.6.1.4.1.3052.23.2.4.1.1.2.5.3.3 |
eth2VLAN3SubnetMaskEthernet2 VLAN3 subnet maskrw IpAddress .1.3.6.1.4.1.3052.23.2.4.1.1.2.5.3.4 |
eth2VLAN3RouterEthernet2 VLAN3 routerrw IpAddress .1.3.6.1.4.1.3052.23.2.4.1.1.2.5.3.5 |
eth2VLAN4 OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.4.1.1.2.5.4 |
eth2VLAN4IDEthernet2 VLAN4 IDrw Integer32 .1.3.6.1.4.1.3052.23.2.4.1.1.2.5.4.1 |
eth2VLAN4PriorityEthernet2 VLAN4 priorityrw Integer32 .1.3.6.1.4.1.3052.23.2.4.1.1.2.5.4.2 |
eth2VLAN4AddressEthernet2 VLAN4 IP addressrw IpAddress .1.3.6.1.4.1.3052.23.2.4.1.1.2.5.4.3 |
eth2VLAN4SubnetMaskEthernet2 VLAN4 subnet maskrw IpAddress .1.3.6.1.4.1.3052.23.2.4.1.1.2.5.4.4 |
eth2VLAN4RouterEthernet2 VLAN4 routerrw IpAddress .1.3.6.1.4.1.3052.23.2.4.1.1.2.5.4.5 |
eth2VLAN5 OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.4.1.1.2.5.5 |
eth2VLAN5IDEthernet2 VLAN5 IDrw Integer32 .1.3.6.1.4.1.3052.23.2.4.1.1.2.5.5.1 |
eth2VLAN5PriorityEthernet2 VLAN5 priorityrw Integer32 .1.3.6.1.4.1.3052.23.2.4.1.1.2.5.5.2 |
eth2VLAN5AddressEthernet2 VLAN5 IP addressrw IpAddress .1.3.6.1.4.1.3052.23.2.4.1.1.2.5.5.3 |
eth2VLAN5SubnetMaskEthernet2 VLAN5 subnet maskrw IpAddress .1.3.6.1.4.1.3052.23.2.4.1.1.2.5.5.4 |
eth2VLAN5RouterEthernet2 VLAN5 routerrw IpAddress .1.3.6.1.4.1.3052.23.2.4.1.1.2.5.5.5 |
eth2VLAN6 OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.4.1.1.2.5.6 |
eth2VLAN6IDEthernet2 VLAN6 IDrw Integer32 .1.3.6.1.4.1.3052.23.2.4.1.1.2.5.6.1 |
eth2VLAN6PriorityEthernet2 VLAN6 priorityrw Integer32 .1.3.6.1.4.1.3052.23.2.4.1.1.2.5.6.2 |
eth2VLAN6AddressEthernet2 VLAN6 IP addressrw IpAddress .1.3.6.1.4.1.3052.23.2.4.1.1.2.5.6.3 |
eth2VLAN6SubnetMaskEthernet2 VLAN6 subnet maskrw IpAddress .1.3.6.1.4.1.3052.23.2.4.1.1.2.5.6.4 |
eth2VLAN6RouterEthernet2 VLAN6 routerrw IpAddress .1.3.6.1.4.1.3052.23.2.4.1.1.2.5.6.5 |
eth2MACEthernet2 MACro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.1.1.2.6 |
eth2IPv6 OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.4.1.1.2.7 |
eth2IPv6ModeControls IPv6 operation for this Ethernet interface.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.1.1.2.7.1 |
eth2IPv6Static OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.4.1.1.2.7.2 |
eth2IPv6StaticAddresshe static IPv6 address to use for this interface when in operating in STATIC mode.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.1.1.2.7.2.1 |
eth2IPv6StaticRouterThe IPv6 router to engage as the default router when this interface operates in STATIC mode.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.1.1.2.7.2.2 |
eth2IPv6Auto OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.4.1.1.2.7.3 |
eth2IPv6AutoAddress1One of the automatically-acquired IPv6 addresses.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.1.1.2.7.3.1 |
eth2IPv6AutoAddress2One of the automatically-acquired IPv6 addresses.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.1.1.2.7.3.2 |
eth2IPv6AutoAddress3One of the automatically-acquired IPv6 addresses.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.1.1.2.7.3.3 |
eth2IPv6AutoAddress4One of the automatically-acquired IPv6 addresses.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.1.1.2.7.3.4 |
eth2IPv6LinkLocalAddressThe link local IPv6 address for this interface. This is present when the IPv6 mode is not OFF.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.1.1.2.7.4 |
defaultRouterThe default router/gatewayrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.2 |
dnsTableDNS server address table SEQUENCE OF DNSConfig .1.3.6.1.4.1.3052.23.2.4.3 |
dnsEntryDNS server address entry DNSConfig .1.3.6.1.4.1.3052.23.2.4.3.1 |
dnsIndexIndex for DNS server addressro Integer32 .1.3.6.1.4.1.3052.23.2.4.3.1.1 |
dnsAddressDNS server addressrw IpAddress .1.3.6.1.4.1.3052.23.2.4.3.1.2 |
hostnameThe hostname of the unitrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.4 |
hostTableStatic host table SEQUENCE OF HostConfig .1.3.6.1.4.1.3052.23.2.4.5 |
hostEntryStatic host entry HostConfig .1.3.6.1.4.1.3052.23.2.4.5.1 |
hostIndexIndex for static hostro Integer32 .1.3.6.1.4.1.3052.23.2.4.5.1.1 |
hostDeclarationStatic host declaration string (i.e. 'address hostname')rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.5.1.2 |
ncpDuplexFor network command processor: 1=Input characters are echoed; 0=no echo.rw Integer32 .1.3.6.1.4.1.3052.23.2.4.6 |
ncpTimeoutNetwork command processor inactivity timeoutrw Integer32 .1.3.6.1.4.1.3052.23.2.4.7 |
snmp OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.4.8 |
snmpAgentEnableON/OFF for snmp agentrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.8.1 |
snmpNotificationCaptureEnableON/OFF unit receives and stores SNMP traps/informsrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.8.5 |
snmpNotificationCaptureFileFile to which unit stores received SNMP traps/informsrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.8.6 |
snmpNotificationTx OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.4.8.7 |
snmpNtfnAttemptsMaximum of times the unit attempts to send a notification (trap/inform) in 1 cyclerw Integer32 .1.3.6.1.4.1.3052.23.2.4.8.7.1 |
snmpNtfnTimeoutNumber of seconds between retries of sending a notificationrw Integer32 .1.3.6.1.4.1.3052.23.2.4.8.7.2 |
snmpNtfnCyclesNumber of times the unit attempts a group of attempts to send a notification (a cycle)rw Integer32 .1.3.6.1.4.1.3052.23.2.4.8.7.3 |
snmpNtfnSnoozeMinutes between cyclesrw Integer32 .1.3.6.1.4.1.3052.23.2.4.8.7.4 |
snmpProxy OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.4.8.8 |
snmpProxyTableTable of SNMP proxy entries SEQUENCE OF SNMPProxyTable .1.3.6.1.4.1.3052.23.2.4.8.8.1 |
snmpProxyEntryEntry for SNMP proxy table SNMPProxyTable .1.3.6.1.4.1.3052.23.2.4.8.8.1.1 |
snmpProxyIndexIndex for SNMP proxy tablero Integer32 .1.3.6.1.4.1.3052.23.2.4.8.8.1.1.1 |
snmpProxyEgressOIDBranchThe OID branch to trigger the proxy function. This should cover the device to proxy. If blank then this proxy entry is disabled.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.8.8.1.1.2 |
snmpProxyIPThe IP address of the device to proxy.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.8.8.1.1.3 |
snmpProxyPortThe UDP port on which the device to proxy listens.rw Integer32 .1.3.6.1.4.1.3052.23.2.4.8.8.1.1.4 |
snmpProxyIngressOIDBranchThe OID branch to be remapped to egress OID branch to trigger the proxy function. If blank then the egress OID branch is proxied without remapping.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.8.8.1.1.5 |
snmpProxyNameName of this proxy entry.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.8.8.1.1.6 |
snmpPoll OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.4.8.9 |
snmpPModeMode of poll operation: OFF, POLL ONLY (just make the results available to view), or POLL BUFFER (store the results).rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.8.9.1 |
snmpPBufferFileCRDB file in which data is stored.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.8.9.2 |
snmpPBufferAllPeriodPeriod (in seconds) that, if non-zero, all results are buffered in the CRDB regardless of the threshold.rw Integer32 .1.3.6.1.4.1.3052.23.2.4.8.9.3 |
snmpPRequestTableTable of SNMP Poll requests. SEQUENCE OF SNMPPollRequestConfig .1.3.6.1.4.1.3052.23.2.4.8.9.4 |
snmpPRequestEntryEntry for table pf SNMP Poll requests. SNMPPollRequestConfig .1.3.6.1.4.1.3052.23.2.4.8.9.4.1 |
snmpPRequestIndexIndex for table of SNMP Poll requests.ro Integer32 .1.3.6.1.4.1.3052.23.2.4.8.9.4.1.1 |
snmpPRequestDescriptionA description for this single telemetry request; no functional effect.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.8.9.4.1.2 |
snmpPRequestAgentSNMP Agent IP address or hostname for this single telemetry request.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.8.9.4.1.3 |
snmpPRequestReadcomSNMP read community for this single telemetry request.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.8.9.4.1.4 |
snmpPRequestOIDSNMP object identifier for this single telemetry request.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.8.9.4.1.5 |
snmpPRequestPeriodHow many seconds between periodic SNMP polls of this single telemetry request.rw Integer32 .1.3.6.1.4.1.3052.23.2.4.8.9.4.1.6 |
snmpPRequestIDA textual field that is part of the record containing the telemetry result.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.8.9.4.1.7 |
snmpPRequestThresholdControls when new data is stored upon a successful telemetry request.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.8.9.4.1.8 |
snmpPRequestResultStatusStatus of the last attempt for this telemetry request.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.8.9.4.1.10 |
snmpPRequestResultValueThe telemetry value if the last request was successful.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.8.9.4.1.11 |
snmpPRequestResultTimeThe timestamp of the last telemetry request.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.8.9.4.1.12 |
snmpPRequestResultTypeThe type of the telemetry as reported by the agent.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.8.9.4.1.13 |
ftpPush OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.4.9 |
ftpPushEnableEnable FTP push for REGULAR (protocol: FTP) or SECURE (protocol: SFTP) operation, or disable it (OFF)rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.9.1 |
ftpPushServerFTP server to which data should be pushedrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.9.2 |
ftpPushAccountFTP push accountrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.9.5 |
ftpPushDirectoryFTP push directoryrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.9.6 |
ftpPushperiodMinutes between pushesrw Integer32 .1.3.6.1.4.1.3052.23.2.4.9.7 |
ftpPushPushFileTableTable of files to push SEQUENCE OF FTPPushPushFileConfig .1.3.6.1.4.1.3052.23.2.4.9.8 |
ftpPushPushFileEntryEntry for table of files to push FTPPushPushFileConfig .1.3.6.1.4.1.3052.23.2.4.9.8.1 |
ftpPushPushFileIndexIndex for table of files to pushro Integer32 .1.3.6.1.4.1.3052.23.2.4.9.8.1.1 |
ftpPushPushFileON/OFF push this local FILExrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.9.8.1.2 |
ftpPushPushAuditON/OFF push the audit logrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.9.9 |
ftpPushPushAlarmsON/OFF push the alarms/events filerw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.9.10 |
ftpPushRemoteFileTableTable of remote names of files to push SEQUENCE OF FTPPushRemoteFileConfig .1.3.6.1.4.1.3052.23.2.4.9.11 |
ftpPushRemoteFileEntryEntry for table of remote names of files to push FTPPushRemoteFileConfig .1.3.6.1.4.1.3052.23.2.4.9.11.1 |
ftpPushRemoteFileIndexIndex for table of remote names of files to pushro Integer32 .1.3.6.1.4.1.3052.23.2.4.9.11.1.1 |
ftpPushRemoteFileNameremote name of pushed FILEx (name on server)rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.9.11.1.2 |
ftpPushRemoteAlarmNameFilename on server for alarmsrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.9.12 |
ftpPushPassiveON/OFF use ftp passive moderw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.9.13 |
ftpPushIncludeDateON/OFF include the date in the name of the pushed filerw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.9.14 |
ftpPushIncludeTimeON/OFF include the time in the name of the pushed filerw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.9.15 |
ftpPushIncludeSeqON/OFF include a sequence number in the name of the pushed filerw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.9.16 |
ftpPushPermissionsUnix permissions to apply to pushed files (octal notation).rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.9.17 |
ppp OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.4.10 |
pppDial OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.4.10.1 |
pppDialEnableON/OFF PPP dialout enabledrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.10.1.1 |
pppDialNumberphone number to dialrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.10.1.2 |
pppDialIdleTimeoutSeconds of inactivity after which the unit disconnectsrw Integer32 .1.3.6.1.4.1.3052.23.2.4.10.1.5 |
pppDialRetriesNumber of dialing retries for PPPrw Integer32 .1.3.6.1.4.1.3052.23.2.4.10.1.6 |
pppDialCDTimeoutNumber of seconds to wait after dialing for CD before giving uprw Integer32 .1.3.6.1.4.1.3052.23.2.4.10.1.7 |
pppDialLoginTimeoutSeconds to wait to negotiate PPP after connectingrw Integer32 .1.3.6.1.4.1.3052.23.2.4.10.1.8 |
pppDialMdmInitModem init string to use when dialing PPPrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.10.1.9 |
pppDialSuggestIPIP address to suggest as the unit's end (local end) of the PPP linkrw IpAddress .1.3.6.1.4.1.3052.23.2.4.10.1.10 |
pppDialPlainLoginON/OFF look for login/password prompt before negotiating PPPrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.10.1.11 |
pppHost OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.4.10.2 |
pppHostEnableON/OFF Unit accepts PPP negotiationrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.10.2.1 |
pppHostIdleTimeoutSeconds of inactivity after which PPP-hosted link will terminaterw Integer32 .1.3.6.1.4.1.3052.23.2.4.10.2.2 |
pppHostLocalIPLocal IP address to negotiaterw IpAddress .1.3.6.1.4.1.3052.23.2.4.10.2.3 |
pppHostRemoteIPRemote IP address to hand out to PPP peerrw IpAddress .1.3.6.1.4.1.3052.23.2.4.10.2.4 |
routing OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.4.11 |
pppRoutingEnableON/OFF unit routes IP traffic from PPP/Wireless to Ethernetrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.11.1 |
ethRoutingEnableON/OFF unit routes IP traffic from Ethernet to PPP/Wirelessrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.11.2 |
ethRoutingNATEnableON/OFF unit applies NAT on routed IP frames egressing the unit on its PPP interfacerw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.11.3 |
routingInterfaceWhen Ethernet routing is enabled (routing.1), this is the Ethernet interface to which IP frames received on PPP are routedrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.11.4 |
eth2WanRoutingEnableMake ETH2 operate as a WAN port to route outbound traffic arriving on ETH1.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.11.5 |
netSecurity OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.4.12 |
ipRestriction OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.4.12.1 |
ipRestrictionTableTable of IP restrictions SEQUENCE OF IPRestrictionConfig .1.3.6.1.4.1.3052.23.2.4.12.1.1 |
ipRestrictionEntryEntry for table of IP restrictions IPRestrictionConfig .1.3.6.1.4.1.3052.23.2.4.12.1.1.1 |
ipRestrictionIndexIndex for table of IP restrictionsro Integer32 .1.3.6.1.4.1.3052.23.2.4.12.1.1.1.1 |
ipRestrictionEnableON/OFF enable this IP restrictionrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.12.1.1.1.2 |
ipRestrictionMaskIP restriction maskrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.12.1.1.1.3 |
rts OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.4.13 |
rtsFileTableTable of RTS files SEQUENCE OF RTSFileConfig .1.3.6.1.4.1.3052.23.2.4.13.1 |
rtsFileEntryEntry for table of RTS files RTSFileConfig .1.3.6.1.4.1.3052.23.2.4.13.1.1 |
rtsFileIndexIndex for table of RTS filesro Integer32 .1.3.6.1.4.1.3052.23.2.4.13.1.1.1 |
rtsFileModeRTS mode (OFF,LISTEN,PUSH) for FILExrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.13.1.1.2 |
rtsFileShowAnswerShow answer string upon RTS connect for FILExrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.13.1.1.3 |
rtsFileReqXONON/OFF require XON to start flow for FILExrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.13.1.1.4 |
rtsFileTimeoutIdle connection close timer (0 means no timeout) for FILExrw Integer32 .1.3.6.1.4.1.3052.23.2.4.13.1.1.5 |
rtsFileEmptyCloseON/OFF close the socket when FILEx is emptyrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.13.1.1.6 |
rtsFilePushHostHost to which FILEx should be pushed via RTSrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.13.1.1.7 |
rtsFilePushPortTCP port to which FILEx should be pushed via RTSrw Integer32 .1.3.6.1.4.1.3052.23.2.4.13.1.1.8 |
rtsFilePushRetryTimerRetry timer (seconds) for retrying failed RTS push connect attemptsrw Integer32 .1.3.6.1.4.1.3052.23.2.4.13.1.1.9 |
rtsAlarms OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.4.13.2 |
rtsAlarmsModeRTS mode (OFF,LISTEN,PUSH) for alarms filerw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.13.2.1 |
rtsAlarmsShowAnswerShow answer string upon RTS connect for alarms filerw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.13.2.2 |
rtsAlarmsReqXONON/OFF require XON to start flow for alarms filerw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.13.2.3 |
rtsAlarmsTimeoutIdle connection close timer (0 means no timeout) for alarms filerw Integer32 .1.3.6.1.4.1.3052.23.2.4.13.2.4 |
rtsAlarmsEmptyCloseON/OFF close the socket when this file is empty for alarms filerw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.13.2.5 |
rtsAlarmsPushHostHost to which alarms file should be pushed via RTSrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.13.2.6 |
rtsAlarmsPushPortTCP port to which alarms file should be pushed via RTSrw Integer32 .1.3.6.1.4.1.3052.23.2.4.13.2.7 |
rtsAlarmsPushRetryTimerRetry timer (seconds) for retrying failed RTS push connect attemptsrw Integer32 .1.3.6.1.4.1.3052.23.2.4.13.2.8 |
trap OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.4.14 |
trapInclude OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.4.14.1 |
trapIncludeDateTimeON/OFF include date and time in stock trap messagerw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.14.1.1 |
trapIncludeSiteNameON/OFF include site name in stock trap messagerw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.14.1.2 |
trapIncludeSensorIDON/OFF include sensor ID in stock trap messagerw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.14.1.3 |
trapIncludeUDNameON/OFF include user defined name in stock trap messagerw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.14.1.4 |
trapIncludeUDStateON/OFF include user defined state in stock trap messagerw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.14.1.5 |
trapIncludeSourceAddressON/OFF include source IP address in stock trap messagerw IpAddress .1.3.6.1.4.1.3052.23.2.4.14.1.6 |
trapAuthFailEnableON/OFF enable trap sent upon SNMP authentication failurerw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.14.2 |
routeTest OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.4.15 |
routeTestEnableON/OFF enable route testingrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.15.1 |
routeTestPeriodThe period which a route is considered validrw Integer32 .1.3.6.1.4.1.3052.23.2.4.15.2 |
routeTestAddressTableTable of route testing addresses SEQUENCE OF RouteTestConfig .1.3.6.1.4.1.3052.23.2.4.15.3 |
routeTestAddressEntryEntry for table of RTS files RouteTestConfig .1.3.6.1.4.1.3052.23.2.4.15.3.1 |
routeTestAddressIndexIndex for table of RTS filesro Integer32 .1.3.6.1.4.1.3052.23.2.4.15.3.1.1 |
routeTestAddressAddress to ping to see if the route to it is validrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.15.3.1.2 |
wireless OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.4.16 |
wirelessModeWireless mode (OFF,PERMANENT-EDGE)rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.16.1 |
wirelessAPNWireless access point namerw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.16.2 |
wirelessIdleTimeoutWireless idle timeoutrw Integer32 .1.3.6.1.4.1.3052.23.2.4.16.3 |
wirelessDREDefault route enable for wireless network interface. When this is ON, the wireless link, if up, becomes the default route, overriding the default route setting (defaultRouter object). When OFF, the default route setting controls the default route and the wireless link does not become the default route.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.16.9 |
wirelessPPPUsernameUsername for PPP-based wireless modem connections.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.16.10 |
wirelessFirewallEnable wireless modem firewall.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.16.11 |
wirelessKeepaliveThresholdMinutes of no RX activity before sending keep-alive.rw Integer32 .1.3.6.1.4.1.3052.23.2.4.16.12 |
wirelessPPPDebugEnable wireless modem PPP debug.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.16.13 |
wirelessConnectivity OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.4.16.20 |
wirelessConnEnableEnable wireless modem connectivity check.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.16.20.1 |
wirelessConnCheckIntervalWireless connectivity check interval in minutes.rw Integer32 .1.3.6.1.4.1.3052.23.2.4.16.20.2 |
wirelessConnFailThresholdWireless connectivity fail threshold.rw Integer32 .1.3.6.1.4.1.3052.23.2.4.16.20.3 |
wirelessConnIP1Wireless connectivity check IP address 1.rw IpAddress .1.3.6.1.4.1.3052.23.2.4.16.20.10 |
wirelessConnIP2Wireless connectivity check IP address 2.rw IpAddress .1.3.6.1.4.1.3052.23.2.4.16.20.11 |
email OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.4.17 |
emailServerSMTP server to which the unit sends emailrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.17.1 |
emailDomainDomain to use in recipient addressrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.17.2 |
emailAuthEnableON/OFF enable SMTP authenticationrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.17.3 |
netAdvanced OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.4.18 |
arpFilterARP filter coderw Integer32 .1.3.6.1.4.1.3052.23.2.4.18.1 |
web OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.4.19 |
webEnableON/OFF for the web interfacerw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.19.1 |
webPortTCP port on which web interface listensrw Integer32 .1.3.6.1.4.1.3052.23.2.4.19.2 |
webTimeoutWeb interface session timeout (seconds)rw Integer32 .1.3.6.1.4.1.3052.23.2.4.19.3 |
webXMLProxy OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.4.19.4 |
wxpEnableGlobally enables/disables the XML Proxy feature. This feature is not available in the STD software build.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.19.4.1 |
wxpDeviceTableTable of XML Proxy devices. SEQUENCE OF WebXMLProxyDeviceConfig .1.3.6.1.4.1.3052.23.2.4.19.4.2 |
wxpDeviceEntryEntry for table of XML Proxy devices. WebXMLProxyDeviceConfig .1.3.6.1.4.1.3052.23.2.4.19.4.2.1 |
wxpDeviceIndexIndex for table of XML Proxy devices.ro Integer32 .1.3.6.1.4.1.3052.23.2.4.19.4.2.1.1 |
wxpDeviceEnableEnables/disables this particular XML device configuration.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.19.4.2.1.2 |
wxpDeviceIPAddressIP address for device.rw IpAddress .1.3.6.1.4.1.3052.23.2.4.19.4.2.1.3 |
wxpDevicePortTCP port on which to connect via HTTP to fetch the XML file.rw Integer32 .1.3.6.1.4.1.3052.23.2.4.19.4.2.1.4 |
wxpDeviceRemoteFilePath and name of the XML file on the remote device. E.g., 'xml/telemetry.xml' if the URL for the XML is 'http://<remote device address>/xml/telemetry.xml'.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.19.4.2.1.5 |
wxpDeviceLocalFileName of file in which the remote file content will be cached on the unit. E.g., 'alpha-telemetry.xml' if the URL for the unit-cached XML is intended to be 'http://<unit address>/xmlproxy/alpha-telemetry.xml'.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.19.4.2.1.6 |
wxpDeviceTimeoutHow long in seconds to wait for the device to serve the remote file before cancelling the fetch operation.rw Integer32 .1.3.6.1.4.1.3052.23.2.4.19.4.2.1.7 |
wxpDeviceTimestampTimestamp of last successful XML file fetch/cache operation. If blank then either the device is not configured or there was a fetch error. If not blank, but not updating, then this indicates that the fetch succeeded at one point but then encountered an error.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.19.4.2.1.8 |
ethExpan OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.4.20 |
ethExpanIpIPv4 address of the unit reachable by nodes on the network interface consisting of the Ethernet Expansion Card(s). If this is default (0.0.0.0), then each card will still convey Ethernet traffic (acting as Ethernet switch) among its nodes but those nodes will not be able to communicate with the unit.rw IpAddress .1.3.6.1.4.1.3052.23.2.4.20.1 |
ethExpanMaskIPv4 subnet mask for the Ethernet Expansion network interface.rw IpAddress .1.3.6.1.4.1.3052.23.2.4.20.2 |
ethExpanCardTableTable of Ethernet Expansion cards SEQUENCE OF EthernetExpansionCardConfig .1.3.6.1.4.1.3052.23.2.4.20.3 |
ethExpanCardEntryEntry for table of Ethernet Expansion cards EthernetExpansionCardConfig .1.3.6.1.4.1.3052.23.2.4.20.3.1 |
ethExpanCardIndexIndex for table of Ethernet Expansion cardsro Integer32 .1.3.6.1.4.1.3052.23.2.4.20.3.1.1 |
ethExpanCardMACMAC address for each Ethernet Expansion Card that is bridged together to form the Ethernet Expansion network interface.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.20.3.1.2 |
ethExpanDHCP OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.4.20.6 |
ethExpanDHCPStartIpStarting IP address for serving DHCP addresses on the Ethernet Expansion network interface. If this is default (0.0.0.0) then the unit will not run DHCP to serve addresses.rw IpAddress .1.3.6.1.4.1.3052.23.2.4.20.6.1 |
ethExpanDHCPLeaseTimeLease time for Ethernet Expansion DHCP clients in minutes.rw Integer32 .1.3.6.1.4.1.3052.23.2.4.20.6.2 |
ipv6 OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.4.21 |
ipv6DefaultRouterThe IPv6 default router in use.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.21.1 |
cpe OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.4.22 |
cpeTableTable of CPEs SEQUENCE OF CPEConfig .1.3.6.1.4.1.3052.23.2.4.22.1 |
cpeEntryEntry for table of CPEs CPEConfig .1.3.6.1.4.1.3052.23.2.4.22.1.1 |
cpeIndexIndex for table of CPEsro Integer32 .1.3.6.1.4.1.3052.23.2.4.22.1.1.1 |
cpeHostCPE host (IP address or DNS name)rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.22.1.1.2 |
cpeNameCPE name, informational onlyrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.22.1.1.3 |
cpeDescriptionCPE description, informational onlyrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.22.1.1.4 |
cpeKeepaliveNumber of seconds between each successful ping request.rw Integer32 .1.3.6.1.4.1.3052.23.2.4.22.1.1.5 |
cpeThresholdNumber of unsuccessful pings that triggers the CPE event.rw Integer32 .1.3.6.1.4.1.3052.23.2.4.22.1.1.6 |
cpeEventReminderIntervalCPE event reminder interval (minutes).rw Integer32 .1.3.6.1.4.1.3052.23.2.4.22.1.1.7 |
cpeKeepaliveTicksCPE ping period in 16ths of a second (nonzero overrides keepalive).rw Integer32 .1.3.6.1.4.1.3052.23.2.4.22.1.1.20 |
cpePingSizeNumber of bytes in CPE ping payloadrw Integer32 .1.3.6.1.4.1.3052.23.2.4.22.1.1.21 |
cpeInfoResetSet any number to reset CPE ping stats.ro Integer32 .1.3.6.1.4.1.3052.23.2.4.22.1.1.30 |
cpeInfoNumReqTotal number of requests transmitted.ro Integer32 .1.3.6.1.4.1.3052.23.2.4.22.1.1.31 |
cpeInfoNumGoodRespTotal number of non-corrupt responses.ro Integer32 .1.3.6.1.4.1.3052.23.2.4.22.1.1.32 |
cpeInfoNumBadRespTotal number of corrupt responses.ro Integer32 .1.3.6.1.4.1.3052.23.2.4.22.1.1.33 |
cpeInfoNumLostRespTotal number of requests with no response.ro Integer32 .1.3.6.1.4.1.3052.23.2.4.22.1.1.34 |
cpeInfoPercentLossPercent loss (missing responses / total requests).ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.22.1.1.35 |
cpeInfoPercentBadPercent corrupt (corrupt responses / total requests).ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.22.1.1.36 |
dnp3 OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.4.23 |
dnp3General OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.4.23.1 |
dnp3ModeDNP3 operating mode.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.23.1.1 |
dnp3SelfAddressEnableDNP3 self-address enabled.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.23.1.2 |
dnp3KeepaliveTimeoutKeepalive timeout in seconds.rw Integer32 .1.3.6.1.4.1.3052.23.2.4.23.1.3 |
dnp3MaxRXFragmentSizeMaximum size of a received fragment in bytes.rw Integer32 .1.3.6.1.4.1.3052.23.2.4.23.1.4 |
dnp3MaxTXFragmentSizeMaximum size of a transmitted fragment in bytes.rw Integer32 .1.3.6.1.4.1.3052.23.2.4.23.1.5 |
dnp3UnsolResponseEnableEnable unsolicited responses.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.23.1.6 |
dnp3UnsolResponseTimeoutUnsolicited response confirmation timeout in seconds.rw Integer32 .1.3.6.1.4.1.3052.23.2.4.23.1.7 |
dnp3UnsolResponseRetriesUnsolicited response confirmation timeout retries.rw Integer32 .1.3.6.1.4.1.3052.23.2.4.23.1.8 |
dnp3LogFilterNumeric code to describe what gets logged (for support/troubleshooting analysis only).rw Integer32 .1.3.6.1.4.1.3052.23.2.4.23.1.9 |
dnp3Outstation OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.4.23.2 |
dnp3OutstationTCPPortTCP port on which to listen for connections.rw Integer32 .1.3.6.1.4.1.3052.23.2.4.23.2.1 |
dnp3OutstationDNP3AddressDNP3 address of the outstation.rw Integer32 .1.3.6.1.4.1.3052.23.2.4.23.2.2 |
dnp3OutstationMasterIPAddressIP (v4 or v6) address (non-resolved) of the intended master. Default blank. If non-blank then the outstation drops connections from TCP clients not at this address.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.23.2.3 |
dnp3OutstationMasterDNP3AddressDNP3 address of the intended master upon connection. Range 0 - 65520, default 65520. If set to 0 - 65519 then the outstation discards DNP3 data link frames not from this address. 65520 is not a valid DNP3 address; if set to 65520 then it means the outstation accepts frames from any address.rw Integer32 .1.3.6.1.4.1.3052.23.2.4.23.2.4 |
dnp3OutstationUnsolResponseDNP3AddressDNP3 destination address of unsolicited responses. Range 0 - 65520, default 65520. If set to 65520 then it means the outstation addresses data link frames of unsolicited responses to the source address of the last accepted frame received from the master.rw Integer32 .1.3.6.1.4.1.3052.23.2.4.23.2.5 |
dnp3Master OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.4.23.3 |
dnp3Error OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.4.23.4 |
dnp3DuplicateFragmentCountCount of duplicate fragments received.ro Integer32 .1.3.6.1.4.1.3052.23.2.4.23.4.1 |
dnp3CollidingFragmentCountCount of colliding fragments received.ro Integer32 .1.3.6.1.4.1.3052.23.2.4.23.4.2 |
dnp3UnsolResponseCfmFailCountCount of unsolicited response confirmation failures.ro Integer32 .1.3.6.1.4.1.3052.23.2.4.23.4.3 |
dnp3SolCfmFailCountCount of solicited response confirmation failures.ro Integer32 .1.3.6.1.4.1.3052.23.2.4.23.4.4 |
dnp3ObjParseErrorCountCount of received data object parse errors.ro Integer32 .1.3.6.1.4.1.3052.23.2.4.23.4.5 |
dnp3FrameParseErrorCountCount of received frame parse errors.ro Integer32 .1.3.6.1.4.1.3052.23.2.4.23.4.6 |
dnp3DiscardedFrameCountCount of received frames discarded.ro Integer32 .1.3.6.1.4.1.3052.23.2.4.23.4.7 |
dnp3BadBlockCountCount of received frame blocks with bad CRC.ro Integer32 .1.3.6.1.4.1.3052.23.2.4.23.4.8 |
dnp3UnsolResponseRetryCountCount of retried unsolicited responses.ro Integer32 .1.3.6.1.4.1.3052.23.2.4.23.4.9 |
dnp3UnsupportedFrameCountCount of received frames accepted (good CRC and addressed to the outstation) with an unsupported data link function code.ro Integer32 .1.3.6.1.4.1.3052.23.2.4.23.4.10 |
dnp3Status OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.4.23.5 |
dnp3OutstationCountCount of running outstation instances.ro Integer32 .1.3.6.1.4.1.3052.23.2.4.23.5.1 |
dnp3ConnPeerDescription of the connected peer (the TCP socket endpoint of the master).ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.23.5.2 |
dnp3StartTimeWhen the outstation instance started.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.23.5.3 |
dnp3EventAwaitingSolCfmCountNumber of events reported and awaiting solicited confirmation; usually 0.ro Integer32 .1.3.6.1.4.1.3052.23.2.4.23.5.4 |
dnp3EventAwaitingUnsolCfmCountNumber of events reported and awaiting unsolicited confirmation; usually 0.ro Integer32 .1.3.6.1.4.1.3052.23.2.4.23.5.5 |
dnp3EventCountNumber of total events buffered (that is, existing, maybe reported, but not confirmed).ro Integer32 .1.3.6.1.4.1.3052.23.2.4.23.5.6 |
dnp3EventClass1CountPortion of the total events buffered that are class 1 events.ro Integer32 .1.3.6.1.4.1.3052.23.2.4.23.5.7 |
dnp3EventClass2CountPortion of the total events buffered that are class 2 events.ro Integer32 .1.3.6.1.4.1.3052.23.2.4.23.5.8 |
dnp3EventClass3CountPortion of the total events buffered that are class 3 events.ro Integer32 .1.3.6.1.4.1.3052.23.2.4.23.5.9 |
dnp3RxFragmentTimeTime of the last fragment received.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.23.5.10 |
dnp3TxFragmentTimeTime of the last fragment transmitted.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.23.5.11 |
dnp3TxCachedResponseCountCount of cached responses transmitted.ro Integer32 .1.3.6.1.4.1.3052.23.2.4.23.5.12 |
dnp3TxUnsolResponseCountCount of unsolicited responses transmitted.ro Integer32 .1.3.6.1.4.1.3052.23.2.4.23.5.13 |
dnp3TxSolResponseCountCount of solicited responses transmitted.ro Integer32 .1.3.6.1.4.1.3052.23.2.4.23.5.14 |
dnp3TxFragmentReqCfmCountCount of fragments transmitted that required confirmation.ro Integer32 .1.3.6.1.4.1.3052.23.2.4.23.5.15 |
dnp3RxUnsolResponseCfmCountCount of unsolicited response confirmations received.ro Integer32 .1.3.6.1.4.1.3052.23.2.4.23.5.16 |
dnp3RxSolResponseCfmCountCount of solicited response confirmations received.ro Integer32 .1.3.6.1.4.1.3052.23.2.4.23.5.17 |
dnp3RxFunctionCountCount of total application function codes received.ro Integer32 .1.3.6.1.4.1.3052.23.2.4.23.5.18 |
dnp3RxReadFunctionCountCount of read application function codes received.ro Integer32 .1.3.6.1.4.1.3052.23.2.4.23.5.19 |
dnp3RxWriteFunctionCountCount of write application function codes received.ro Integer32 .1.3.6.1.4.1.3052.23.2.4.23.5.20 |
dnp3RxDirOpFunctionCountCount of direct operate application function codes received.ro Integer32 .1.3.6.1.4.1.3052.23.2.4.23.5.21 |
dnp3RxEnableURCountCount of enable unsolicited application function codes received.ro Integer32 .1.3.6.1.4.1.3052.23.2.4.23.5.22 |
dnp3RxDisableURCountCount of disabled unsolicited application function codes received.ro Integer32 .1.3.6.1.4.1.3052.23.2.4.23.5.23 |
dnp3RxSolObjectCountCount of data objects received in solicited requests.ro Integer32 .1.3.6.1.4.1.3052.23.2.4.23.5.40 |
dnp3TxSolObjectCountCount of data objects transmitted in solicted responses.ro Integer32 .1.3.6.1.4.1.3052.23.2.4.23.5.41 |
dnp3RxFrameTimeTime of the last frame received.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.23.5.42 |
dnp3TxFrameTimeTime of the last frame transmitted.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.4.23.5.43 |
dnp3TxFrameCountCount of total frames transmitted.ro Integer32 .1.3.6.1.4.1.3052.23.2.4.23.5.44 |
dnp3RxAcceptedFrameCountCount of total frames accepted.ro Integer32 .1.3.6.1.4.1.3052.23.2.4.23.5.45 |
dnp3RxSupportedFrameCountCount of total frames accepted with a supported data link function code.ro Integer32 .1.3.6.1.4.1.3052.23.2.4.23.5.46 |
modem OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.5 |
modemFormatModem data format (8N1,7E1,7O1,7N1)rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.5.1 |
modemInitStringInit string for modemrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.5.2 |
modemCallAttemptsMax mumber of times the modem should try to call out until successful connectrw Integer32 .1.3.6.1.4.1.3052.23.2.5.4 |
modemCallDelayMinimum delay (seconds) between calloutsrw Integer32 .1.3.6.1.4.1.3052.23.2.5.5 |
modemCmdTimoutNumber of minutes after which an idle command session via modem is terminatedrw Integer32 .1.3.6.1.4.1.3052.23.2.5.6 |
modemGotoWhen a user connects, where that user is routed (command session, passthrough to port 1, passthrough to port 2, etc.)rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.5.7 |
modemClid OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.5.8 |
modemCLIDEnableON/OFF Calling Line Identification securityrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.5.8.1 |
modemCLIDNumberTableTable of authorized callers identified by phone number SEQUENCE OF ModemCLIDNumberConfig .1.3.6.1.4.1.3052.23.2.5.8.2 |
modemCLIDNumberEntryEntry for table of CLID numbers ModemCLIDNumberConfig .1.3.6.1.4.1.3052.23.2.5.8.2.1 |
modemCLIDNumberIndexIndex for table of CLID numbersro Integer32 .1.3.6.1.4.1.3052.23.2.5.8.2.1.1 |
modemCLIDNumberauhorized CLID numberrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.5.8.2.1.2 |
modemTAPInitStringInit string to use for TAP (pager) connectionsrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.5.9 |
modemTAP8N1ON/OFF: use 8N1 data/parity/stop for TAP connectionsrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.5.10 |
time OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.8 |
clockText string for date and time; e.g. 'SUN 01/02/98 12:34:27'. When setting this object, only the date and time are required; the unit will ignore a specified day of week because it is calculated from the date and time. When this object is included in a notification as a varbind, it represents the time that the triggering event occurred.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.8.1 |
console OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.10 |
consoleDuplexON/OFF characters echoed on telnet command sessionrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.10.1 |
consoleTimeoutMinutes of inactivity after which telnet command session is terminatedrw Integer32 .1.3.6.1.4.1.3052.23.2.10.2 |
consoleConfirmON/OFF Prompt to confirm certain actionsrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.10.7 |
unitSecurity OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.11 |
secCore OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.11.1 |
scShowPasswordPromptON/OFF show password prompt upon loginrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.11.1.1 |
scConsoleLoginRequiredON/OFF login required upon connecting via consolerw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.11.1.2 |
scModemLoginRequiredON/OFF login required upon connecting via modemrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.11.1.3 |
scTelnetLoginRequiredON/OFF login required upon connecting via Telnetrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.11.1.4 |
scTelnetPTLoginRequiredON/OFF login required upon connecting via Telnet to pass- through ports (TCP ports 210x)rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.11.1.5 |
scRTSLoginRequiredON/OFF login required upon connecting to RTS (TCP ports 220x)rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.11.1.6 |
scAuthModeAuthentication mode (USERNAME/PW,PW/USERNAME,PASSWORD ONLY)rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.11.1.7 |
scRightsGroupThe set of aliases used for the 8 available rights levelsrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.11.1.8 |
secUserTableTable of users SEQUENCE OF SecUserConfig .1.3.6.1.4.1.3052.23.2.11.2 |
secUserEntryEntry for table of users SecUserConfig .1.3.6.1.4.1.3052.23.2.11.2.1 |
secUserIndexIndex for table of usersro Integer32 .1.3.6.1.4.1.3052.23.2.11.2.1.1 |
secUserEnableON/OFF enable userrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.11.2.1.2 |
secUserConnectViaMethods by which user is allowed to connect: L=local (console) T=Telnet M=modem F=FTP R=RTS S=SSHrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.11.2.1.5 |
secUserLoginToThe function presented to the user upon login (COMMAND, PASSTHROUGH,MENU)rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.11.2.1.6 |
secUserAccessFileThe default access file associated with the userrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.11.2.1.7 |
secUserPTEscapeToThe function presented to the user upon escaping pass- through: currently only MENUrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.11.2.1.9 |
secUserPPPTypeThe kind of PPP access allowed to this user cannot connect via PPP (NONE), can connect but only to the unit (LOCAL), or can connect and route to Ethernet (ROUTING)rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.11.2.1.10 |
secUserRightsThe rights level granted to this userrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.11.2.1.11 |
secUserEventsReadAccessDENY/ALLOW user to read the events/alarms filerw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.11.2.1.13 |
secUserAuditReadAccessDENY/ALLOW user to read the audit logrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.11.2.1.14 |
secUserEventsWriteAccessDENY/ALLOW user to delete the events filerw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.11.2.1.16 |
secUserAuditWriteAccessDENY/ALLOW user to write to the audit logrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.11.2.1.17 |
secUserExpirationExpiration date/time of this userrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.11.2.1.18 |
secUserCallbackNumber1Number slot 1 the unit calls for dialbackrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.11.2.1.19 |
secUserCallbackNumber2Number slot 2 the unit calls for dialbackrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.11.2.1.20 |
secUserCallbackNumber3Number slot 3 the unit calls for dialbackrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.11.2.1.21 |
secUserChallengeTelnetModeTelnet challenge mode: when user logs in via telnet, unit allows access (OFF), presents a challenge (CHALLENGE), or unit sends a one-time-password (SEND PASSWORD) to a destination configured by secUserChallengeTelnetSendTorw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.11.2.1.22 |
secUserChallengeModemModeModem challenge mode: when user logs in via modem, unit allows access (OFF), presents a challenge (CHALLENGE), sends a one-time-password (SEND PASSWORD) to a destination configured by secUserChallengeTelnetSendTo, or dials a number (CALLBACK) configured with secUserCallbackNumberxrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.11.2.1.23 |
secUserChallengeConsoleModeConsole challenge mode: when user logs in via console, unit allows access (OFF), or presents a challenge (CHALLENGE)rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.11.2.1.24 |
secUserChallengeTelnetSendToEmail action used as the destination address for one-time- password when a user logs in with a challenge mode of SEND PASSWORDrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.11.2.1.25 |
secUserChallengeModemSendToModem action used as the destination phone number for one- time-password when a user logs in with a challenge mode of SEND PASSWORDrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.11.2.1.26 |
secUserChallengeExpirationTime (in minutes) after which a one-time-password is sent that it can be used to log inrw Integer32 .1.3.6.1.4.1.3052.23.2.11.2.1.27 |
secFactory OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.11.3 |
sfEnableON/OFF enable factory accessrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.11.3.1 |
sfSecretSecret used for factory accessrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.11.3.2 |
secSSH OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.11.4 |
secVPN OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.11.5 |
event OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.12 |
evCore OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.12.1 |
evClassNameTableTable of classes SEQUENCE OF EventClassConfig .1.3.6.1.4.1.3052.23.2.12.1.1 |
evClassNameEntryEntry for table of classes EventClassConfig .1.3.6.1.4.1.3052.23.2.12.1.1.1 |
evClassNameIndexIndex for table of classesro Integer32 .1.3.6.1.4.1.3052.23.2.12.1.1.1.1 |
evClassNameClass name for this slotrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.1.1.1.2 |
evReminderIntervalInterval (minutes) between EventSensor reminder eventsrw Integer32 .1.3.6.1.4.1.3052.23.2.12.1.2 |
evLog OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.12.1.3 |
evLogEnableON/OFF enable event logrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.1.3.1 |
evLogStoreAlarmON/OFF store data alarms in event logrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.1.3.2 |
evLogMaxSizemax size (in KB) of event logrw Integer32 .1.3.6.1.4.1.3052.23.2.12.1.3.3 |
evLogStoreSensorON/OFF store EventSensor events in event logrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.1.3.4 |
evLogTimeStampAlarmsON/OFF put timestamps on event log entriesrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.1.3.5 |
evLogPrependNameON/OFF prepend data event name to data alarm records in event logrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.1.3.6 |
evMgmt OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.12.1.4 |
evMgmtReprocessNumber of sensors that have generated events since reset. Write this to reprocess each sensor's last generated event since reset. The value to write determines what kind of events should be reprocessed: 'all': all sensor events 'cc': cc events 'temperature': temperature events 'humidity': humidity events 'analog': analog input eventsrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.1.4.3 |
evData OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.12.2 |
evdCore OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.12.2.1 |
evdExitOnTrueON/OFF: Data alarm evaluator stops checking record against alarm equations when it finds an equation that matchesrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.2.1.1 |
evdFilterActionWhat happens to a record that matches an equation: REJECT/ACCEPTrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.2.1.2 |
evdWildCardCharCharacter (in decimal ASCII code format) used to indicate wildcards in data alarm equationrw Integer32 .1.3.6.1.4.1.3052.23.2.12.2.1.3 |
evdTableTable of data events SEQUENCE OF DataEventConfig .1.3.6.1.4.1.3052.23.2.12.2.2 |
evdEntryEntry for table of data events DataEventConfig .1.3.6.1.4.1.3052.23.2.12.2.2.1 |
evdIndexIndex for table of data eventsro Integer32 .1.3.6.1.4.1.3052.23.2.12.2.2.1.1 |
evdEnableON/OFF enable this data eventrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.2.2.1.2 |
evdNameName for this data eventrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.2.2.1.3 |
evdEquationEquation for this data eventrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.2.2.1.4 |
evdThresholdNumber of equation matches that must happen to trigger this data eventrw Integer32 .1.3.6.1.4.1.3052.23.2.12.2.2.1.5 |
evdAutoClearON/OFF this data alarm is automatically cleared (re-armed) upon reaching the threshold number of matchesrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.2.2.1.6 |
evdClearIntervalInterval at which this alarm is automatically cleared (no bearing with evdAutoClear)rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.2.2.1.7 |
evdClearTimeTie of day (HH:MM) at which this data alarm is cleared (no bearing with evdAutoClear)rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.2.2.1.8 |
evdActionsActions for this data eventrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.2.2.1.9 |
evdClassClass for this data eventrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.2.2.1.10 |
evdTrapNumTrap number for this eventrw Integer32 .1.3.6.1.4.1.3052.23.2.12.2.2.1.11 |
evdModeALARM/FILTER: what is happens when this data event triggers: either generate actions (mode=ALARM) )or ACCEPT/REJECT (via evdFilterAction) the record (mode=FILTER)rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.2.2.1.12 |
evdFieldTableTable of data event fields SEQUENCE OF DataEventFieldConfig .1.3.6.1.4.1.3052.23.2.12.2.3 |
evdFieldEntryEntry for table of data event fields DataEventFieldConfig .1.3.6.1.4.1.3052.23.2.12.2.3.1 |
evdFieldIndexIndex for table of data event fieldsro Integer32 .1.3.6.1.4.1.3052.23.2.12.2.3.1.1 |
evdFieldStartStart position (1-based) for this data event fieldrw Integer32 .1.3.6.1.4.1.3052.23.2.12.2.3.1.2 |
evdFieldLengthNumber of characters this data event field occupiesrw Integer32 .1.3.6.1.4.1.3052.23.2.12.2.3.1.3 |
evdFieldNameStart position (1-based) for this data event fieldrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.2.3.1.4 |
evdFieldLineLine number (1-based, for multiline records) for this data event fieldrw Integer32 .1.3.6.1.4.1.3052.23.2.12.2.3.1.5 |
evdFieldTypeAlpha/Numeric type for this data event fieldrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.2.3.1.6 |
evdMacroTableTable of data event macros SEQUENCE OF DataEventMacroConfig .1.3.6.1.4.1.3052.23.2.12.2.4 |
evdMacroEntryEntry for table of data event macros DataEventMacroConfig .1.3.6.1.4.1.3052.23.2.12.2.4.1 |
evdMacroIndexIndex for table of data event macrosro Integer32 .1.3.6.1.4.1.3052.23.2.12.2.4.1.1 |
evdMacroNameName of this macro for use in data event equationsrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.2.4.1.2 |
evdMacroEquationEquation for this data event macrorw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.2.4.1.3 |
evNoData1 OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.12.3 |
evNoData1EnableON/OFF enable this no data eventrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.3.1 |
evNoData1ActionsActions for this no data eventrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.3.2 |
evNoData1MessageMessage for this no data eventrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.3.3 |
evNoData1TrapNumTrap number for this no data eventrw Integer32 .1.3.6.1.4.1.3052.23.2.12.3.4 |
evNoData1ClassClass for this no data eventrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.3.5 |
evNoData1Sched1BeginSchedule 1 begin time (HH:MM) for this no data eventrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.3.6 |
evNoData1Sched1EndSchedule 1 end time (HH:MM) for this no data eventrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.3.7 |
evNoData1Sched1DurationDuration (minutes) for schedule 1 of this no data eventrw Integer32 .1.3.6.1.4.1.3052.23.2.12.3.8 |
evNoData1Sched2BeginSchedule 2 begin time (HH:MM) for this no data eventrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.3.9 |
evNoData1Sched2EndSchedule 2 end time (HH:MM) for this no data eventrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.3.10 |
evNoData1Sched2DurationDuration (minutes) for schedule 2 of this no data eventrw Integer32 .1.3.6.1.4.1.3052.23.2.12.3.11 |
evNoData1PortEnableTableTable of no data event 1 port enables SEQUENCE OF NoDataEvent1PortEnableConfig .1.3.6.1.4.1.3052.23.2.12.3.12 |
evNoData1PortEnableEntryEntry for table of no data event 1 port enables NoDataEvent1PortEnableConfig .1.3.6.1.4.1.3052.23.2.12.3.12.1 |
evNoData1PortEnableIndexIndex for table of no data event 1 port enablesro Integer32 .1.3.6.1.4.1.3052.23.2.12.3.12.1.1 |
evNoData1PortEnableON/OFF: no data event 1 observes this portrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.3.12.1.2 |
evNoData1ExclusionsExclusions (space-separated MM/DD-formatted dates) for this no data eventrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.3.13 |
evNoData1DaysDays of the week on which this no event is activerw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.3.14 |
evNoData2 OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.12.4 |
evNoData2EnableON/OFF enable this no data eventrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.4.1 |
evNoData2ActionsActions for this no data eventrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.4.2 |
evNoData2MessageMessage for this no data eventrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.4.3 |
evNoData2TrapNumTrap number for this no data eventrw Integer32 .1.3.6.1.4.1.3052.23.2.12.4.4 |
evNoData2ClassClass for this no data eventrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.4.5 |
evNoData2Sched1BeginSchedule 1 begin time (HH:MM) for this no data eventrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.4.6 |
evNoData2Sched1EndSchedule 1 end time (HH:MM) for this no data eventrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.4.7 |
evNoData2Sched1DurationDuration (minutes) for schedule 1 of this no data eventrw Integer32 .1.3.6.1.4.1.3052.23.2.12.4.8 |
evNoData2Sched2BeginSchedule 2 begin time (HH:MM) for this no data eventrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.4.9 |
evNoData2Sched2EndSchedule 2 end time (HH:MM) for this no data eventrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.4.10 |
evNoData2Sched2DurationDuration (minutes) for schedule 2 of this no data eventrw Integer32 .1.3.6.1.4.1.3052.23.2.12.4.11 |
evNoData2PortEnableTableTable of no data event 2 port enables SEQUENCE OF NoDataEvent2PortEnableConfig .1.3.6.1.4.1.3052.23.2.12.4.12 |
evNoData2PortEnableEntryEntry for table of no data event 2 port enables NoDataEvent2PortEnableConfig .1.3.6.1.4.1.3052.23.2.12.4.12.1 |
evNoData2PortEnableIndexIndex for table of no data event 2 port enablesro Integer32 .1.3.6.1.4.1.3052.23.2.12.4.12.1.1 |
evNoData2PortEnableON/OFF: no data event 2 observes this portrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.4.12.1.2 |
evNoData2ExclusionsExclusions (space-separated MM/DD-formatted dates) for this no data eventrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.4.13 |
evNoData2DaysDays of the week on which this no event is activerw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.4.14 |
evSched1 OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.12.5 |
evSched1EnableON/OFF enable this scheduled eventrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.5.1 |
evSched1ActionsActions for this scheduled eventrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.5.2 |
evSched1MessageMessage for this scheduled eventrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.5.3 |
evSched1TrapNumTrap number for this scheduled eventrw Integer32 .1.3.6.1.4.1.3052.23.2.12.5.4 |
evSched1ClassClass for this scheduled eventrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.5.5 |
evSched1SundayTime on Sunday (HH:MM) when this scheduled event triggersrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.5.6 |
evSched1MondayTime on Monday (HH:MM) when this scheduled event triggersrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.5.7 |
evSched1TuesdayTime on Tuesday (HH:MM) when this scheduled event triggersrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.5.8 |
evSched1WednesdayTime on Wednesday (HH:MM) when this scheduled event triggersrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.5.9 |
evSched1ThursdayTime on Thursday (HH:MM) when this scheduled event triggersrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.5.10 |
evSched1FridayTime on Friday (HH:MM) when this scheduled event triggersrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.5.11 |
evSched1SaturdayTime on Saturday (HH:MM) when this scheduled event triggersrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.5.12 |
evSched1ExclusionsExclusions (space-separated MM/DD-formatted dates) for this scheduled eventrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.5.13 |
evSched2 OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.12.6 |
evSched2EnableON/OFF enable this scheduled eventrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.6.1 |
evSched2ActionsActions for this scheduled eventrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.6.2 |
evSched2MessageMessage for this scheduled eventrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.6.3 |
evSched2TrapNumTrap number for this scheduled eventrw Integer32 .1.3.6.1.4.1.3052.23.2.12.6.4 |
evSched2ClassClass for this scheduled eventrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.6.5 |
evSched2SundayTime on Sunday (HH:MM) when this scheduled event triggersrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.6.6 |
evSched2MondayTime on Monday (HH:MM) when this scheduled event triggersrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.6.7 |
evSched2TuesdayTime on Tuesday (HH:MM) when this scheduled event triggersrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.6.8 |
evSched2WednesdayTime on Wednesday (HH:MM) when this scheduled event triggersrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.6.9 |
evSched2ThursdayTime on Thursday (HH:MM) when this scheduled event triggersrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.6.10 |
evSched2FridayTime on Friday (HH:MM) when this scheduled event triggersrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.6.11 |
evSched2SaturdayTime on Saturday (HH:MM) when this scheduled event triggersrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.6.12 |
evSched2ExclusionsExclusions (space-separated MM/DD-formatted dates) for this scheduled eventrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.6.13 |
evShskLowTableTable of serial handshaking low events SEQUENCE OF SerialHandshakingLowEventConfig .1.3.6.1.4.1.3052.23.2.12.7 |
evShskLowEntryEntry for table of serial handshaking low events SerialHandshakingLowEventConfig .1.3.6.1.4.1.3052.23.2.12.7.1 |
evShskLowIndexIndex for table of serial handshaking low eventsro Integer32 .1.3.6.1.4.1.3052.23.2.12.7.1.1 |
evShskLowEnableON/OFF: enable the serial handshaking low event for this portrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.7.1.2 |
evShskLowActionsActions for the serial handshaking low event for this portrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.7.1.3 |
evShskLowMessageMessage for the serial handshaking low event for this portrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.7.1.4 |
evShskLowClassClass for the serial handshaking low event for this portrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.7.1.5 |
evShskLowTrapNumTrap number for the serial handshaking low event for this portrw Integer32 .1.3.6.1.4.1.3052.23.2.12.7.1.6 |
evShskHighTableTable of serial handshaking high events SEQUENCE OF SerialHandshakingHighEventConfig .1.3.6.1.4.1.3052.23.2.12.8 |
evShskHighEntryEntry for table of serial handshaking high events SerialHandshakingHighEventConfig .1.3.6.1.4.1.3052.23.2.12.8.1 |
evShskHighIndexIndex for table of serial handshaking high eventsro Integer32 .1.3.6.1.4.1.3052.23.2.12.8.1.1 |
evShskHighEnableON/OFF: enable the serial handshaking high event for this portrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.8.1.2 |
evShskHighActionsActions for the serial handshaking high event for this portrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.8.1.3 |
evShskHighMessageMessage for the serial handshaking high event for this portrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.8.1.4 |
evShskHighClassClass for the serial handshaking high event for this portrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.8.1.5 |
evShskHighTrapNumTrap number for the serial handshaking high event for this portrw Integer32 .1.3.6.1.4.1.3052.23.2.12.8.1.6 |
evNoSensor OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.12.9 |
evNoSensorTimeoutTimeout (seconds) after which an EventSensor becomes unresponsive that this event is triggeredrw Integer32 .1.3.6.1.4.1.3052.23.2.12.9.1 |
evNoSensorActionsActions for no sensor eventrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.9.2 |
evNoSensorTrapNumTrap number for no sensor eventrw Integer32 .1.3.6.1.4.1.3052.23.2.12.9.3 |
evNoSensorClassClass for no sensor eventrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.9.4 |
fuelSensor OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.12.11 |
fuelSensorGeneralTableThis table organizes general fuel sensor attributes. SEQUENCE OF FuelSensorConfigGeneral .1.3.6.1.4.1.3052.23.2.12.11.1 |
fsGenEntryEntry for fuel sensor general config table. FuelSensorConfigGeneral .1.3.6.1.4.1.3052.23.2.12.11.1.1 |
fsGenIndexWhich fuel sensor in the fuel sensor general config table.ro Integer32 .1.3.6.1.4.1.3052.23.2.12.11.1.1.1 |
fsGenNameFuel sensor name.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.11.1.1.2 |
fsGenSensorTypeType of fuel sensor in use; NONE disables the fuel sensor.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.11.1.1.3 |
fsGenDistanceUnitDistance units in use when setting and indicating tank dimensions.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.11.1.1.4 |
fsGenRawValueTopAnalog input reading corresponding to the SENSOR FULL point.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.11.1.1.5 |
fsGenTopOffsetDistance, in the specified distance unit, between the SENSOR FULL point and the TANK FULL point. The value is positive if the SENSOR FULL point is above the TANK FULL point, and negative if it is below.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.11.1.1.6 |
fsGenRawValueBottomAnalog input reading corresponding to the minimum fluid height measurable by the fuel sensor.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.11.1.1.7 |
fsGenBottomOffsetDistance, in the specified distance unit, between the SENSOR EMPTY point and the TANK EMPTY point. The value is positive if the SENSOR EMPTY point is above the TANK EMPTY point, and negative if it is below.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.11.1.1.8 |
fsGenInputESWhich eventsensor contains the analog input associated with this fuel sensor. Allowed values are 200 (for internal ES), or 1-16.rw Integer32 .1.3.6.1.4.1.3052.23.2.12.11.1.1.9 |
fsGenInputPointWhich analog input point, on the specified eventsensor, that is associated with the fuel sensor.rw Integer32 .1.3.6.1.4.1.3052.23.2.12.11.1.1.10 |
fsGenFilterAveragingFuel sensor filter averaging factor.rw Integer32 .1.3.6.1.4.1.3052.23.2.12.11.1.1.11 |
fsGenSysrepEnableFuel sensor System Reporting enable.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.11.1.1.12 |
fsGenSysrepThresholdFuel sensor System Reporting threshold (floating point value).rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.11.1.1.13 |
fsGenSysrepLimitFuel sensor System Reporting limit.rw Integer32 .1.3.6.1.4.1.3052.23.2.12.11.1.1.14 |
fsGenSysrepPackageFuel sensor System Reporting package number.rw Integer32 .1.3.6.1.4.1.3052.23.2.12.11.1.1.15 |
fsGenGroupFuel sensor ASM profile type.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.11.1.1.16 |
fsGenEnableFuel sensor enable.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.11.1.1.17 |
fsGenFuelTypeType of fuel being measured: DIESEL, PROPANE, NATURAL GAS, HYDROGEN, GASOLINE, OTHER.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.11.1.1.18 |
fuelSensorTankTableThis table organizes tank-specific fuel sensor attributes. SEQUENCE OF FuelSensorConfigTank .1.3.6.1.4.1.3052.23.2.12.11.2 |
fsTankEntryEntry for fuel sensor tank config table. FuelSensorConfigTank .1.3.6.1.4.1.3052.23.2.12.11.2.1 |
fsTankIndexWhich fuel sensor in the fuel sensor tank config table.ro Integer32 .1.3.6.1.4.1.3052.23.2.12.11.2.1.1 |
fsTankHeightHeight of the tank, from the TANK EMPTY point to the TANK FULL point, in the specified distance unit (i.e. TANK HEIGHT). This is a floating point value.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.11.2.1.2 |
fsTankDimATank dimension measurement A for certain tank profiles. For HORIZ OVAL, this is the length of the straight section. This is a floating point value.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.11.2.1.3 |
fsTankDimBTank dimension measurement B for certain tank profiles. For HORIZ OVAL, this is the radius of the curved section. This is a floating point value.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.11.2.1.4 |
fsTankVolumeHow many volume units the tank contains, when full. This is a floating point value.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.11.2.1.5 |
fsTankVolumeUnitName of the unit representing fluid volume in the tank. This is only used for display purposes; it does not affect the volume calculation.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.11.2.1.6 |
fsTankShapeThe shape of the fuel tank. A value of LINEAR produces a fluid volume reading that is directly proportional to fluid height. The HORIZ CYL and HORIZ OVAL settings use a hard-coded formula to calculate the volume. The CUSTOM setting uses a strapping table that must be configured as well (see fuelSensorCustomTankTable).rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.11.2.1.7 |
fuelSensorCustomTankTableThis table organizes the custom tank strapping table. Each fuel sensor has a table of height/volume pairs in service only when the tank shape (fsTankShape) in CUSTOM. This allows the unit to calculate volumes for nonstandard tank shapes, to the degree that accurate height/volume measurements can be configured. This SNMP table has two indexes: the first for which fuel sensor and the second for which height/volume pair. SEQUENCE OF FuelSensorConfigCustomTankStrapping .1.3.6.1.4.1.3052.23.2.12.11.3 |
fsCustomTankEntryEntry for fuel sensor custom tank config table. FuelSensorConfigCustomTankStrapping .1.3.6.1.4.1.3052.23.2.12.11.3.1 |
fsCustomTankIndexFSWhich fuel sensor in the fuel sensor tank config table. This is the first of two indexes for this SNMP table.ro Integer32 .1.3.6.1.4.1.3052.23.2.12.11.3.1.1 |
fsCustomTankIndexDatumWhich hight/volume pair: there are 32 pairs per fuel sensor. This is the second of two indexes for this SNMP table.ro Integer32 .1.3.6.1.4.1.3052.23.2.12.11.3.1.2 |
fsCustomTankHeightHeight of custom tank height/volume pair. This is a floating point value.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.11.3.1.3 |
fsCustomTankVolumeVolume of custom tank height/volume pair. This is a floating point value.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.11.3.1.4 |
fuelSensorVolumeTableThis table organizes volume-event-specific fuel sensor attributes. SEQUENCE OF FuelSensorConfigVolume .1.3.6.1.4.1.3052.23.2.12.11.4 |
fsVolumeEntryEntry for fuel sensor volume event config table. FuelSensorConfigVolume .1.3.6.1.4.1.3052.23.2.12.11.4.1 |
fsVolumeIndexWhich fuel sensor in the fuel sensor volume event config table.ro Integer32 .1.3.6.1.4.1.3052.23.2.12.11.4.1.1 |
fsVolumeEnableEnable fuel sensor volume events.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.11.4.1.2 |
fsVolumeDeadbandFuel sensor deadband (hysteresis). This is a floating point value.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.11.4.1.3 |
fsVolumeVHighValueFuel sensor volume very high event threshold value. This is a floating point value.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.11.4.1.4 |
fsVolumeVHighActionsFuel sensor volume very high event threshold actions.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.11.4.1.5 |
fsVolumeVHighTrapNumFuel sensor volume very high event threshold trap number.rw Integer32 .1.3.6.1.4.1.3052.23.2.12.11.4.1.6 |
fsVolumeVHighClassFuel sensor volume very high event threshold class (severity).rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.11.4.1.7 |
fsVolumeHighValueFuel sensor volume high event threshold value. This is a floating point value.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.11.4.1.8 |
fsVolumeHighActionsFuel sensor volume high event threshold actions.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.11.4.1.9 |
fsVolumeHighTrapNumFuel sensor volume high event threshold trap number.rw Integer32 .1.3.6.1.4.1.3052.23.2.12.11.4.1.10 |
fsVolumeHighClassFuel sensor volume high event threshold class (severity).rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.11.4.1.11 |
fsVolumeNormalActionsFuel sensor volume return to normal actions.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.11.4.1.12 |
fsVolumeNormalTrapNumFuel sensor volume return to normal trap number.rw Integer32 .1.3.6.1.4.1.3052.23.2.12.11.4.1.13 |
fsVolumeNormalClassFuel sensor volume return to normal class (severity).rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.11.4.1.14 |
fsVolumeLowValueFuel sensor volume low event threshold value. This is a floating point value.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.11.4.1.15 |
fsVolumeLowActionsFuel sensor volume low event threshold actions.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.11.4.1.16 |
fsVolumeLowTrapNumFuel sensor volume low event threshold trap number.rw Integer32 .1.3.6.1.4.1.3052.23.2.12.11.4.1.17 |
fsVolumeLowClassFuel sensor volume low event threshold class (severity).rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.11.4.1.18 |
fsVolumeVLowValueFuel sensor volume very low event threshold value. This is a floating point value.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.11.4.1.19 |
fsVolumeVLowActionsFuel sensor volume very low event threshold actions.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.11.4.1.20 |
fsVolumeVLowTrapNumFuel sensor volume very low event threshold trap number.rw Integer32 .1.3.6.1.4.1.3052.23.2.12.11.4.1.21 |
fsVolumeVLowClassFuel sensor volume very low event threshold class (severity).rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.11.4.1.22 |
fuelSensorDisconnectTableThis table organizes disconnect-event-specific fuel sensor attributes. SEQUENCE OF FuelSensorConfigDisconnect .1.3.6.1.4.1.3052.23.2.12.11.5 |
fsDiscEntryEntry for fuel sensor disconnect event config table. FuelSensorConfigDisconnect .1.3.6.1.4.1.3052.23.2.12.11.5.1 |
fsDiscIndexWhich fuel sensor in the fuel sensor disconnect event config table.ro Integer32 .1.3.6.1.4.1.3052.23.2.12.11.5.1.1 |
fsDiscEnableFuel sensor disconnect event enable.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.11.5.1.2 |
fsDiscHighValueHigh end of input value range when fuel sensor is disconnected. This is in the units of the analog input value.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.11.5.1.3 |
fsDiscLowValueLow end of input value range when fuel sensor is disconnected. This is in the units of the analog input value.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.11.5.1.4 |
fsDiscActionsFuel sensor disconnect event actions.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.11.5.1.5 |
fsDiscTrapNumFuel sensor disconnect event trap number.rw Integer32 .1.3.6.1.4.1.3052.23.2.12.11.5.1.6 |
fsDiscClassFuel sensor disconnect event class (severity).rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.11.5.1.7 |
fsDiscNormalActionsFuel sensor disconnect return to normal actions.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.11.5.1.8 |
fsDiscNormalTrapNumFuel sensor disconnect return to normal trap number.rw Integer32 .1.3.6.1.4.1.3052.23.2.12.11.5.1.9 |
fsDiscNormalClassFuel sensor disconnect return to normal class (severity).rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.11.5.1.10 |
fuelSensorSuddenChangeTableThis table organizes sudden-change-event-specific fuel sensor attributes. SEQUENCE OF FuelSensorConfigSuddenChange .1.3.6.1.4.1.3052.23.2.12.11.6 |
fsSuddenChangeEntryEntry for fuel sensor sudden change event config table. FuelSensorConfigSuddenChange .1.3.6.1.4.1.3052.23.2.12.11.6.1 |
fsSuddenChangeIndexWhich fuel sensor in the fuel sensor sudden change event config table.ro Integer32 .1.3.6.1.4.1.3052.23.2.12.11.6.1.1 |
fsSuddenChangeEnableFuel volume sudden change event enable.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.11.6.1.2 |
fsSuddenChangeTimeFuel volume sudden change event time (minutes): what duration defines 'sudden'.rw Integer32 .1.3.6.1.4.1.3052.23.2.12.11.6.1.3 |
fsSuddenChangeAmplitudeFuel volume sudden change event amplitude: what amount (in fuel volume units) over the duration (fsSuddenChangeTime) defines enough change.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.11.6.1.4 |
fsSuddenChangeActionsFuel volume sudden change event actions.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.11.6.1.5 |
fsSuddenChangeTrapNumFuel volume sudden change event trap number.rw Integer32 .1.3.6.1.4.1.3052.23.2.12.11.6.1.6 |
fsSuddenChangeClassFuel volume sudden change event class (severity).rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.11.6.1.7 |
fuelSensorSlowChangeTableThis table organizes slow-change-event-specific fuel sensor attributes. SEQUENCE OF FuelSensorConfigSlowChange .1.3.6.1.4.1.3052.23.2.12.11.7 |
fsSlowChangeEntryEntry for fuel sensor slow change event config table. FuelSensorConfigSlowChange .1.3.6.1.4.1.3052.23.2.12.11.7.1 |
fsSlowChangeIndexWhich fuel sensor in the fuel sensor slow change event config table.ro Integer32 .1.3.6.1.4.1.3052.23.2.12.11.7.1.1 |
fsSlowChangeEnableFuel volume slow change event enable.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.11.7.1.2 |
fsSlowChangeTimeFuel volume slow change event time (minutes): what duration defines 'slow'.rw Integer32 .1.3.6.1.4.1.3052.23.2.12.11.7.1.3 |
fsSlowChangeAmplitudeFuel volume slow change event amplitude: what amount (in fuel volume units) over the duration (fsSlowChangeTime) defines enough change.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.11.7.1.4 |
fsSlowChangeActionsFuel volume slow change event actions.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.11.7.1.5 |
fsSlowChangeTrapNumFuel volume slow change event trap number.rw Integer32 .1.3.6.1.4.1.3052.23.2.12.11.7.1.6 |
fsSlowChangeClassFuel volume slow change event class (severity).rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.11.7.1.7 |
acPowerMonitor OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.12.12 |
acpmGeneralTableThis table organizes general AC power monitor attributes. SEQUENCE OF ACPMConfigGeneral .1.3.6.1.4.1.3052.23.2.12.12.1 |
acpmGenEntryEntry for AC power monitor general config table. ACPMConfigGeneral .1.3.6.1.4.1.3052.23.2.12.12.1.1 |
acpmGenIndexWhich AC power monitor in the AC power monitor general config table.ro Integer32 .1.3.6.1.4.1.3052.23.2.12.12.1.1.1 |
acpmGenDeviceModel of the AC power monitor device. The unit needs this setting to know which registers to poll for the various data items, among other things.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.1.1.2 |
acpmGenNameName for the AC power monitor device.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.1.1.3 |
acpmGenAddressModbus address of the AC power monitor device.rw Integer32 .1.3.6.1.4.1.3052.23.2.12.12.1.1.4 |
acpmGenPtRatioRatio of secondary turns to primary turns on potential transformers (PT).rw Integer32 .1.3.6.1.4.1.3052.23.2.12.12.1.1.5 |
acpmGenCtRatioRatio of secondary turns to primary turns on current transformers (CT).rw Integer32 .1.3.6.1.4.1.3052.23.2.12.12.1.1.6 |
acpmGenPowerTypeType of power being monitored.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.1.1.7 |
acpmGenSysrepPackageSystem reporting package number.rw Integer32 .1.3.6.1.4.1.3052.23.2.12.12.1.1.8 |
acpmGenGroupASM profile group.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.1.1.9 |
acpmGenEnableAC power monitor enable.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.1.1.10 |
acpmAvgVoltageTableThis table organizes AC power monitor average voltage attributes. SEQUENCE OF ACPMConfigAvgVoltage .1.3.6.1.4.1.3052.23.2.12.12.2 |
acpmAvgVoltageEntryEntry for AC power monitor average voltage config table. ACPMConfigAvgVoltage .1.3.6.1.4.1.3052.23.2.12.12.2.1 |
acpmAvgVoltageIndexWhich AC power monitor in the AC power monitor average voltage config table.ro Integer32 .1.3.6.1.4.1.3052.23.2.12.12.2.1.1 |
acpmAvgVoltageEnableEnable AC power monitor average voltage events.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.2.1.2 |
acpmAvgVoltageDeadbandDeadband (hysteresis) for average voltage event. This is a floating point value.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.2.1.3 |
acpmAvgVoltageVHighValueVery high event threshold. This is a floating point value.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.2.1.4 |
acpmAvgVoltageVHighActionsVery high event actions.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.2.1.5 |
acpmAvgVoltageVHighTrapNumVery high event trap number.rw Integer32 .1.3.6.1.4.1.3052.23.2.12.12.2.1.6 |
acpmAvgVoltageVHighClassVery high event class.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.2.1.7 |
acpmAvgVoltageHighValueHigh event threshold. This is a floating point value.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.2.1.8 |
acpmAvgVoltageHighActionsHigh event actions.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.2.1.9 |
acpmAvgVoltageHighTrapNumHigh event trap number.rw Integer32 .1.3.6.1.4.1.3052.23.2.12.12.2.1.10 |
acpmAvgVoltageHighClassHigh event class.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.2.1.11 |
acpmAvgVoltageNormalActionsReturn to normal actions.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.2.1.12 |
acpmAvgVoltageNormalTrapNumReturn to normal trap number.rw Integer32 .1.3.6.1.4.1.3052.23.2.12.12.2.1.13 |
acpmAvgVoltageNormalClassReturn to normal class.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.2.1.14 |
acpmAvgVoltageLowValueLow event threshold. This is a floating point value.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.2.1.15 |
acpmAvgVoltageLowActionsLow event actions.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.2.1.16 |
acpmAvgVoltageLowTrapNumLow event trap number.rw Integer32 .1.3.6.1.4.1.3052.23.2.12.12.2.1.17 |
acpmAvgVoltageLowClassLow event class.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.2.1.18 |
acpmAvgVoltageVLowValueVery low event threshold. This is a floating point value.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.2.1.19 |
acpmAvgVoltageVLowActionsVery low event actions.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.2.1.20 |
acpmAvgVoltageVLowTrapNumVery low event trap number.rw Integer32 .1.3.6.1.4.1.3052.23.2.12.12.2.1.21 |
acpmAvgVoltageVLowClassVery low event class.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.2.1.22 |
acpmAvgVoltageSysrepEnableSystem reporting enable for average voltage telemetry.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.2.1.23 |
acpmAvgVoltageSysrepThresholdSystem reporting threshold for average voltage telemetry. This is a floating point value.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.2.1.24 |
acpmAvgVoltageSysrepLimitSystem reporting limit for average voltage telemetry.rw Integer32 .1.3.6.1.4.1.3052.23.2.12.12.2.1.25 |
acpmAvgCurrentTableThis table organizes AC power monitor average current attributes. SEQUENCE OF ACPMConfigAvgCurrent .1.3.6.1.4.1.3052.23.2.12.12.3 |
acpmAvgCurrentEntryEntry for AC power monitor average current config table. ACPMConfigAvgCurrent .1.3.6.1.4.1.3052.23.2.12.12.3.1 |
acpmAvgCurrentIndexWhich AC power monitor in the AC power monitor average current config table.ro Integer32 .1.3.6.1.4.1.3052.23.2.12.12.3.1.1 |
acpmAvgCurrentEnableEnable AC power monitor average current events.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.3.1.2 |
acpmAvgCurrentDeadbandDeadband (hysteresis) for average current event. This is a floating point value.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.3.1.3 |
acpmAvgCurrentVHighValueVery high event threshold. This is a floating point value.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.3.1.4 |
acpmAvgCurrentVHighActionsVery high event actions.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.3.1.5 |
acpmAvgCurrentVHighTrapNumVery high event trap number.rw Integer32 .1.3.6.1.4.1.3052.23.2.12.12.3.1.6 |
acpmAvgCurrentVHighClassVery high event class.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.3.1.7 |
acpmAvgCurrentHighValueHigh event threshold. This is a floating point value.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.3.1.8 |
acpmAvgCurrentHighActionsHigh event actions.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.3.1.9 |
acpmAvgCurrentHighTrapNumHigh event trap number.rw Integer32 .1.3.6.1.4.1.3052.23.2.12.12.3.1.10 |
acpmAvgCurrentHighClassHigh event class.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.3.1.11 |
acpmAvgCurrentNormalActionsReturn to normal actions.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.3.1.12 |
acpmAvgCurrentNormalTrapNumReturn to normal trap number.rw Integer32 .1.3.6.1.4.1.3052.23.2.12.12.3.1.13 |
acpmAvgCurrentNormalClassReturn to normal class.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.3.1.14 |
acpmAvgCurrentLowValueLow event threshold. This is a floating point value.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.3.1.15 |
acpmAvgCurrentLowActionsLow event actions.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.3.1.16 |
acpmAvgCurrentLowTrapNumLow event trap number.rw Integer32 .1.3.6.1.4.1.3052.23.2.12.12.3.1.17 |
acpmAvgCurrentLowClassLow event class.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.3.1.18 |
acpmAvgCurrentVLowValueVery low event threshold. This is a floating point value.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.3.1.19 |
acpmAvgCurrentVLowActionsVery low event actions.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.3.1.20 |
acpmAvgCurrentVLowTrapNumVery low event trap number.rw Integer32 .1.3.6.1.4.1.3052.23.2.12.12.3.1.21 |
acpmAvgCurrentVLowClassVery low event class.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.3.1.22 |
acpmAvgCurrentSysrepEnableSystem reporting enable for average current telemetry.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.3.1.23 |
acpmAvgCurrentSysrepThresholdSystem reporting threshold for average current telemetry. This is a floating point value.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.3.1.24 |
acpmAvgCurrentSysrepLimitSystem reporting limit for average current telemetry.rw Integer32 .1.3.6.1.4.1.3052.23.2.12.12.3.1.25 |
acpmFreqTableThis table organizes AC power monitor frequency attributes. SEQUENCE OF ACPMConfigFreq .1.3.6.1.4.1.3052.23.2.12.12.4 |
acpmFreqEntryEntry for AC power monitor frequency config table. ACPMConfigFreq .1.3.6.1.4.1.3052.23.2.12.12.4.1 |
acpmFreqIndexWhich AC power monitor in the AC power monitor frequency config table.ro Integer32 .1.3.6.1.4.1.3052.23.2.12.12.4.1.1 |
acpmFreqEnableEnable AC power monitor frequency events.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.4.1.2 |
acpmFreqDeadbandDeadband (hysteresis) for frequency event. This is a floating point value.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.4.1.3 |
acpmFreqVHighValueVery high event threshold. This is a floating point value.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.4.1.4 |
acpmFreqVHighActionsVery high event actions.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.4.1.5 |
acpmFreqVHighTrapNumVery high event trap number.rw Integer32 .1.3.6.1.4.1.3052.23.2.12.12.4.1.6 |
acpmFreqVHighClassVery high event class.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.4.1.7 |
acpmFreqHighValueHigh event threshold. This is a floating point value.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.4.1.8 |
acpmFreqHighActionsHigh event actions.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.4.1.9 |
acpmFreqHighTrapNumHigh event trap number.rw Integer32 .1.3.6.1.4.1.3052.23.2.12.12.4.1.10 |
acpmFreqHighClassHigh event class.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.4.1.11 |
acpmFreqNormalActionsReturn to normal actions.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.4.1.12 |
acpmFreqNormalTrapNumReturn to normal trap number.rw Integer32 .1.3.6.1.4.1.3052.23.2.12.12.4.1.13 |
acpmFreqNormalClassReturn to normal class.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.4.1.14 |
acpmFreqLowValueLow event threshold. This is a floating point value.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.4.1.15 |
acpmFreqLowActionsLow event actions.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.4.1.16 |
acpmFreqLowTrapNumLow event trap number.rw Integer32 .1.3.6.1.4.1.3052.23.2.12.12.4.1.17 |
acpmFreqLowClassLow event class.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.4.1.18 |
acpmFreqVLowValueVery low event threshold. This is a floating point value.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.4.1.19 |
acpmFreqVLowActionsVery low event actions.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.4.1.20 |
acpmFreqVLowTrapNumVery low event trap number.rw Integer32 .1.3.6.1.4.1.3052.23.2.12.12.4.1.21 |
acpmFreqVLowClassVery low event class.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.4.1.22 |
acpmFreqSysrepEnableSystem reporting enable for frequency telemetry.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.4.1.23 |
acpmFreqSysrepThresholdSystem reporting threshold for frequency telemetry. This is a floating point value.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.4.1.24 |
acpmFreqSysrepLimitSystem reporting limit for frequency telemetry.rw Integer32 .1.3.6.1.4.1.3052.23.2.12.12.4.1.25 |
acpmTotalRealPowerTableThis table organizes AC power monitor total real power attributes. SEQUENCE OF ACPMConfigTRP .1.3.6.1.4.1.3052.23.2.12.12.5 |
acpmTRPEntryEntry for AC power monitor total real power config table. ACPMConfigTRP .1.3.6.1.4.1.3052.23.2.12.12.5.1 |
acpmTRPIndexWhich AC power monitor in the AC power monitor total real power config table.ro Integer32 .1.3.6.1.4.1.3052.23.2.12.12.5.1.1 |
acpmTRPEnableEnable AC power monitor total real power events.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.5.1.2 |
acpmTRPDeadbandDeadband (hysteresis) for total real power event. This is a floating point value.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.5.1.3 |
acpmTRPVHighValueVery high event threshold. This is a floating point value.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.5.1.4 |
acpmTRPVHighActionsVery high event actions.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.5.1.5 |
acpmTRPVHighTrapNumVery high event trap number.rw Integer32 .1.3.6.1.4.1.3052.23.2.12.12.5.1.6 |
acpmTRPVHighClassVery high event class.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.5.1.7 |
acpmTRPHighValueHigh event threshold. This is a floating point value.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.5.1.8 |
acpmTRPHighActionsHigh event actions.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.5.1.9 |
acpmTRPHighTrapNumHigh event trap number.rw Integer32 .1.3.6.1.4.1.3052.23.2.12.12.5.1.10 |
acpmTRPHighClassHigh event class.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.5.1.11 |
acpmTRPNormalActionsReturn to normal actions.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.5.1.12 |
acpmTRPNormalTrapNumReturn to normal trap number.rw Integer32 .1.3.6.1.4.1.3052.23.2.12.12.5.1.13 |
acpmTRPNormalClassReturn to normal class.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.5.1.14 |
acpmTRPLowValueLow event threshold. This is a floating point value.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.5.1.15 |
acpmTRPLowActionsLow event actions.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.5.1.16 |
acpmTRPLowTrapNumLow event trap number.rw Integer32 .1.3.6.1.4.1.3052.23.2.12.12.5.1.17 |
acpmTRPLowClassLow event class.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.5.1.18 |
acpmTRPVLowValueVery low event threshold. This is a floating point value.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.5.1.19 |
acpmTRPVLowActionsVery low event actions.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.5.1.20 |
acpmTRPVLowTrapNumVery low event trap number.rw Integer32 .1.3.6.1.4.1.3052.23.2.12.12.5.1.21 |
acpmTRPVLowClassVery low event class.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.5.1.22 |
acpmTRPSysrepEnableSystem reporting enable for total real power telemetry.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.5.1.23 |
acpmTRPSysrepThresholdSystem reporting threshold for total real power telemetry. This is a floating point value.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.5.1.24 |
acpmTRPSysrepLimitSystem reporting limit for total real power telemetry.rw Integer32 .1.3.6.1.4.1.3052.23.2.12.12.5.1.25 |
acpmDisconnectTableThis table organizes AC power monitor device disconnect event attributes. SEQUENCE OF ACPMConfigDisconnect .1.3.6.1.4.1.3052.23.2.12.12.6 |
acpmDisconnectEntryEntry for AC power monitor device disconnect event config table. ACPMConfigDisconnect .1.3.6.1.4.1.3052.23.2.12.12.6.1 |
acpmDisconnectIndexWhich AC power monitor in the AC power monitor device disconnect event config table.ro Integer32 .1.3.6.1.4.1.3052.23.2.12.12.6.1.1 |
acpmDisconnectEnableEnable AC power monitor device disconnect event.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.6.1.2 |
acpmDisconnectActionsActions for disconnect event.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.6.1.3 |
acpmDisconnectTrapNumTrap number for disconnect event.rw Integer32 .1.3.6.1.4.1.3052.23.2.12.12.6.1.4 |
acpmDisconnectClassClass for disconnect event.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.6.1.5 |
acpmDisconnectNormalActionsActions for disconnect return to normal event.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.6.1.6 |
acpmDisconnectNormalTrapNumTrap number for disconnect return to normal event.rw Integer32 .1.3.6.1.4.1.3052.23.2.12.12.6.1.7 |
acpmDisconnectNormalClassClass for disconnect return to normal event.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.6.1.8 |
acpmTotalPowerFactorTableThis table organizes AC power monitor device total power factor event attributes. SEQUENCE OF ACPMConfigTotalPowerFactor .1.3.6.1.4.1.3052.23.2.12.12.7 |
acpmTPFEntryEntry for AC power monitor device total power factor event config table. ACPMConfigTotalPowerFactor .1.3.6.1.4.1.3052.23.2.12.12.7.1 |
acpmTPFIndexWhich AC power monitor in the AC power monitor device disconnect event config table.ro Integer32 .1.3.6.1.4.1.3052.23.2.12.12.7.1.1 |
acpmTPFEnableEnable AC power monitor device disconnect event.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.7.1.2 |
acpmTPFDeadbandDeadband (hysteresis).rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.7.1.3 |
acpmTPFNormalActionsNormal actions.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.7.1.4 |
acpmTPFNormalTrapNumNormal trap number.rw Integer32 .1.3.6.1.4.1.3052.23.2.12.12.7.1.5 |
acpmTPFNormalClassNormal class.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.7.1.6 |
acpmTPFLowValueLow threshold.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.7.1.7 |
acpmTPFLowActionsLow actions.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.7.1.8 |
acpmTPFLowTrapNumLow trap number.rw Integer32 .1.3.6.1.4.1.3052.23.2.12.12.7.1.9 |
acpmTPFLowClassLow class.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.7.1.10 |
acpmTPFVLowValueVery Low threshold.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.7.1.11 |
acpmTPFVLowActionsVery Low actions.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.7.1.12 |
acpmTPFVLowTrapNumVery Low trap number.rw Integer32 .1.3.6.1.4.1.3052.23.2.12.12.7.1.13 |
acpmTPFVLowClassVery Low class.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.7.1.14 |
acpmTPFSysrepEnableSystem reporting enable.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.7.1.15 |
acpmTPFSysrepThresholdSystem reporting threshold.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.12.7.1.16 |
acpmTPFSysrepLimitSystem reporting limit.rw Integer32 .1.3.6.1.4.1.3052.23.2.12.12.7.1.17 |
evReset OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.12.16 |
evResetEnableEnable/disable reset event. This event is triggered when the unit finishes booting.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.16.1 |
evResetDelayNumber of seconds to wait after unit finishes booting before triggering the reset event.rw Integer32 .1.3.6.1.4.1.3052.23.2.12.16.2 |
evResetActionsActions for reset event.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.16.3 |
evResetMessageMessage for reset event.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.16.4 |
evResetTrapnumTrap number for reset event.rw Integer32 .1.3.6.1.4.1.3052.23.2.12.16.5 |
evResetClassClass (severity) for reset event.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.16.6 |
evGlobal OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.12.18 |
evGlobalActionsGlobal event actions.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.18.2 |
evGlobalTrapnumGlobal trap number.rw Integer32 .1.3.6.1.4.1.3052.23.2.12.18.3 |
evHVAC OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.12.19 |
evHVACBard OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.12.19.2 |
evHVACBardLocal OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.12.19.2.1 |
evHVACBardIPAddressIP address of the Bard HVAC controller.rw IpAddress .1.3.6.1.4.1.3052.23.2.12.19.2.1.1 |
evHVACBardPortTCP port of the Bard HVAC controller interface.rw Integer32 .1.3.6.1.4.1.3052.23.2.12.19.2.1.2 |
evHVACBardTimeoutSeconds to wait for a response from the Bard HVAC controller.rw Integer32 .1.3.6.1.4.1.3052.23.2.12.19.2.1.3 |
evHVACBardXMLStatusXML status page of the Bard HVAC controller.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.2.1.4 |
evHVACBardXMLSettingsXML settings page of the Bard HVAC controller.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.2.1.5 |
evHVACBardWebSettingsHTMLWeb settings page of the Bard HVAC controller.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.2.1.6 |
evHVACBardAlarm OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.12.19.2.1.7 |
evHVACBardAlarmEnableEnable/disable the Bard HVAC Alarm event.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.2.1.7.1 |
evHVACBardAlarmActionsActions for the Bard HVAC Alarm event.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.2.1.7.2 |
evHVACBardAlarmTrapnumTrap number for the Bard HVAC Alarm event.rw Integer32 .1.3.6.1.4.1.3052.23.2.12.19.2.1.7.3 |
evHVACBardAlarmClassClass (severity) for the Bard HVAC Alarm event.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.2.1.7.4 |
evHVACBardAlarmNormalActionsActions for the Bard HVAC Alarm Return to Normal event.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.2.1.7.5 |
evHVACBardAlarmNormalTrapnumTrap number for the Bard HVAC Alarm Return to Normal event.rw Integer32 .1.3.6.1.4.1.3052.23.2.12.19.2.1.7.6 |
evHVACBardAlarmNormalClassClass (severity) for the Bard HVAC Alarm Return to Normal event.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.2.1.7.7 |
evHVACBardResetSet to any value to reset the Bard HVAC controller. Always reads zero.rw Integer32 .1.3.6.1.4.1.3052.23.2.12.19.2.1.8 |
evHVACBardDefaultSet to any value to restore default settings on the Bard HVAC controller. Always reads zero.rw Integer32 .1.3.6.1.4.1.3052.23.2.12.19.2.1.9 |
evHVACBardSynchronized OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.12.19.2.2 |
evHVACBardTempScaleScale used, Celsius or Fahrenheit (C or F).rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.2.2.1 |
evHVACBardCoolThresholdCooling threshold to turn on HVAC cooling elements (economizer/compressor).rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.2.2.2 |
evHVACBardCoolThresholdStateSynchronization status of previous object: ERROR (with possible description), PENDING, or OK.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.2.2.3 |
evHVACBardHeatThresholdHeating threshold to turn on HVAC heating elements (economizer/compressor).rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.2.2.4 |
evHVACBardHeatDiffHeating differential to turn on HVAC heating elements. The heating threshold is calculated by subtracting this number from the current cool threshold.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.2.2.5 |
evHVACBardHeatDiffStateSynchronization status of previous object: ERROR (with possible description), PENDING, or OK.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.2.2.6 |
evHVACBardBlowerContinuous blower operation enable.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.2.2.7 |
evHVACBardBlowerStateSynchronization status of previous object: ERROR (with possible description), PENDING, or OK.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.2.2.8 |
evHVACBardAlternateAlternate lead-lag sequence for the economizer.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.2.2.9 |
evHVACBardAlternateStateSynchronization status of previous object: ERROR (with possible description), PENDING, or OK.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.2.2.10 |
evHVACBardChangeoverLead-lag changeover time in days.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.2.2.11 |
evHVACBardChangeoverStateSynchronization status of previous object: ERROR (with possible description), PENDING, or OK.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.2.2.12 |
evHVACBardBlowDiffEnable to run blowers if two sensors have a difference of 5 F or greater.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.2.2.13 |
evHVACBardBlowDiffStateSynchronization status of previous object: ERROR (with possible description), PENDING, or OK.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.2.2.14 |
evHVACBardOffDelay3 minute lead/4 minute lag unit off delay enable.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.2.2.15 |
evHVACBardOffDelayStateSynchronization status of previous object: ERROR (with possible description), PENDING, or OK.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.2.2.16 |
evHVACBardRunMinRun the compressor for at least 3 minutes before shutting off enable.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.2.2.17 |
evHVACBardRunMinStateSynchronization status of previous object: ERROR (with possible description), PENDING, or OK.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.2.2.18 |
evHVACBardDiff OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.12.19.2.2.19 |
evHVACBardStage1DiffTemperature differential between stages 1 and 2.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.2.2.19.1 |
evHVACBardStage1DiffStateSynchronization status of previous object: ERROR (with possible description), PENDING, or OK.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.2.2.19.2 |
evHVACBardStage2DiffTemperature differential between stages 2 and 3.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.2.2.19.3 |
evHVACBardStage2DiffStateSynchronization status of previous object: ERROR (with possible description), PENDING, or OK.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.2.2.19.4 |
evHVACBardStage3DiffTemperature differential between stages 3 and 4.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.2.2.19.5 |
evHVACBardStage3DiffStateSynchronization status of previous object: ERROR (with possible description), PENDING, or OK.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.2.2.19.6 |
evHVACBardCoolDisableDbCooling disable deadband.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.2.2.20 |
evHVACBardCoolDisableDbStateSynchronization status of previous object: ERROR (with possible description), PENDING, or OK.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.2.2.21 |
evHVACBardCoolEnableDbCooling enable deadband.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.2.2.22 |
evHVACBardCoolEnableDbStateSynchronization status of previous object: ERROR (with possible description), PENDING, or OK.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.2.2.23 |
evHVACBardHeatDbHeating deadband.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.2.2.24 |
evHVACBardHeatDbStateSynchronization status of previous object: ERROR (with possible description), PENDING, or OK.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.2.2.25 |
evHVACBardHeatPumpHeat pump logic enable.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.2.2.26 |
evHVACBardHeatPumpStateSynchronization status of previous object: ERROR (with possible description), PENDING, or OK.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.2.2.27 |
evHVACBardCompressorsSynchronization status of previous object: ERROR (with possible description), PENDING, or OK.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.2.2.28 |
evHVACBardCompressorsStateSynchronization status of previous object: ERROR (with possible description), PENDING, or OK.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.2.2.29 |
evHVACBardEconomizerSynchronization status of previous object: ERROR (with possible description), PENDING, or OK.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.2.2.30 |
evHVACBardEconomizerStateSynchronization status of previous object: ERROR (with possible description), PENDING, or OK.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.2.2.31 |
evHVACBardTemp OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.12.19.2.2.32 |
evHVACBardTempLowValueLow alarm for temperature.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.2.2.32.1 |
evHVACBardTempLowValueStateSynchronization status of previous object: ERROR (with possible description), PENDING, or OK.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.2.2.32.2 |
evHVACBardTempHighValueHigh alarm for temperature.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.2.2.32.3 |
evHVACBardTempHighValueStateSynchronization status of previous object: ERROR (with possible description), PENDING, or OK.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.2.2.32.4 |
evHVACBardTempVHighValueVery high alarm for temperature.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.2.2.32.5 |
evHVACBardTempVHighValueStateSynchronization status of previous object: ERROR (with possible description), PENDING, or OK.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.2.2.32.6 |
evHVACBardOverrideThe HVAC controller override.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.2.2.33 |
evHVACBardOverrideStateSynchronization status of previous object: ERROR (with possible description), PENDING, or OK.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.2.2.34 |
evHVACBardLockEnable the external controller lock.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.2.2.35 |
evHVACBardLockStateSynchronization status of previous object: ERROR (with possible description), PENDING, or OK.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.2.2.36 |
evHVACBardLeadUnitWhich HVAC unit is currently the lead unit.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.2.2.37 |
evHVACBardLeadUnitStateSynchronization status of previous object: ERROR (with possible description), PENDING, or OK.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.2.2.38 |
evHVACBardComfortEnable comfort mode.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.2.2.39 |
evHVACBardComfortStateSynchronization status of previous object: ERROR (with possible description), PENDING, or OK.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.2.2.40 |
evHVACAsentria OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.12.19.3 |
evHVACAsentriaSensorListTableAsentria HVAC temperature/humidity sensor list table SEQUENCE OF HVACAsentriaSensorList .1.3.6.1.4.1.3052.23.2.12.19.3.1 |
evHVACAsentriaSensorListEntryAsentria HVAC temperature/humidity sensor list table entry HVACAsentriaSensorList .1.3.6.1.4.1.3052.23.2.12.19.3.1.1 |
evHVACAsentriaSensorListIndexIndex for Asentria HVAC temperature/humidity sensorro Integer32 .1.3.6.1.4.1.3052.23.2.12.19.3.1.1.1 |
evHVACAsentriaSensorListESAsentria HVAC temperature/humidity sensor EventSensor numberrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.3.1.1.2 |
evHVACAsentriaSensorListPTAsentria HVAC temperature/humidity sensor pointrw Integer32 .1.3.6.1.4.1.3052.23.2.12.19.3.1.1.3 |
evHVACAsentriaSensorListTypeAsentria HVAC temperature/humidity sensor typerw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.3.1.1.4 |
evHVACAsentriaSensorListLocAsentria HVAC temperature/humidity sensor locationrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.3.1.1.5 |
evHVACAsentriaOverrideAsentria HVAC controller overriderw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.3.2 |
evHVACAsentriaScheduleAsentria HVAC unit primary/lead swap schedulerw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.3.3 |
evHVACAsentriaPrimaryAsentria HVAC primary/lead unit to operaterw Integer32 .1.3.6.1.4.1.3052.23.2.12.19.3.4 |
evHVACAsentriaMethodAsentria HVAC controller temperature/humidity calculation methodrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.3.5 |
evHVACAsentriaAlarm OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.12.19.3.6 |
evHVACAsentriaAlarmLagNormEnableAsentria HVAC enable for normal/idle alarm notification on lag unitrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.3.6.1 |
evHVACAsentriaAlarmLagNormActionsAsentria HVAC actions to perform for normal/idle alarm notification on lag unitrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.3.6.2 |
evHVACAsentriaAlarmLagNormTrapNumAsentria HVAC trap number for normal/idle alarm notification on lag unitrw Integer32 .1.3.6.1.4.1.3052.23.2.12.19.3.6.3 |
evHVACAsentriaAlarmLagNormClassAsentria HVAC alarm class for normal/idle alarm notification on lag unitrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.3.6.4 |
evHVACAsentriaAlarmLagVentEnableAsentria HVAC enable for venting alarm notification on lag unitrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.3.6.5 |
evHVACAsentriaAlarmLagVentActionsAsentria HVAC actions to perform for venting alarm notification on lag unitrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.3.6.6 |
evHVACAsentriaAlarmLagVentTrapNumAsentria HVAC trap number for venting alarm notification on lag unitrw Integer32 .1.3.6.1.4.1.3052.23.2.12.19.3.6.7 |
evHVACAsentriaAlarmLagVentClassAsentria HVAC alarm class for venting alarm notification on lag unitrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.3.6.8 |
evHVACAsentriaAlarmLagCoolEnableAsentria HVAC enable for cooling alarm notification on lag unitrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.3.6.9 |
evHVACAsentriaAlarmLagCoolActionsAsentria HVAC actions to perform for cooling alarm notification on lag unitrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.3.6.10 |
evHVACAsentriaAlarmLagCoolTrapNumAsentria HVAC trap number for cooling alarm notification on lag unitrw Integer32 .1.3.6.1.4.1.3052.23.2.12.19.3.6.11 |
evHVACAsentriaAlarmLagCoolClassAsentria HVAC alarm class for cooling alarm notification on lag unitrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.3.6.12 |
evHVACAsentriaAlarmLagHeatEnableAsentria HVAC enable for heating alarm notification on lag unitrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.3.6.13 |
evHVACAsentriaAlarmLagHeatActionsAsentria HVAC actions to perform for heating alarm notification on lag unitrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.3.6.14 |
evHVACAsentriaAlarmLagHeatTrapNumAsentria HVAC trap number for heating alarm notification on lag unitrw Integer32 .1.3.6.1.4.1.3052.23.2.12.19.3.6.15 |
evHVACAsentriaAlarmLagHeatClassAsentria HVAC alarm class for heating alarm notification on lag unitrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.3.6.16 |
evHVACAsentriaFire OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.12.19.3.7 |
evHVACAsentriaFireESAsentria HVAC fire/smoke alarm EventSensor numberrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.3.7.1 |
evHVACAsentriaFirePTAsentria HVAC fire/smoke alarm point numberrw Integer32 .1.3.6.1.4.1.3052.23.2.12.19.3.7.2 |
evHVACAsentriaFireActionsAsentria HVAC actions to perform for fire/smoke alarm notificationrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.3.7.3 |
evHVACAsentriaFireTrapnumAsentria HVAC trap number for fire/smoke alarm notificationrw Integer32 .1.3.6.1.4.1.3052.23.2.12.19.3.7.4 |
evHVACAsentriaFireClassAsentria HVAC alarm class for fire/smoke alarm notificationrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.3.7.5 |
evHVACAsentriaFireNormActionsAsentria HVAC return to normal actions to perform for fire/smoke alarm notificationrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.3.7.6 |
evHVACAsentriaFireNormTrapNumAsentria HVAC return to normal trap number for fire/smoke alarm notificationrw Integer32 .1.3.6.1.4.1.3052.23.2.12.19.3.7.7 |
evHVACAsentriaFireNormClassAsentria HVAC return to normal class for fire/smoke alarm notificationrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.3.7.8 |
evHVACAsentriaUnitTableAsentria HVAC unit table SEQUENCE OF HVACAsentriaUnit .1.3.6.1.4.1.3052.23.2.12.19.3.8 |
evHVACAsentriaUnitEntryAsentria HVAC unit table entry HVACAsentriaUnit .1.3.6.1.4.1.3052.23.2.12.19.3.8.1 |
evHVACAsentriaUnitIndexIndex for Asentria HVAC unitro Integer32 .1.3.6.1.4.1.3052.23.2.12.19.3.8.1.1 |
evHVACAsentriaUnitEnableAsentria HVAC unit enablerw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.3.8.1.2 |
evHVACAsentriaUnitFanRelayESEventSensor number of relay to control the fan on Asentria HVAC controllerrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.3.8.1.3 |
evHVACAsentriaUnitFanRelayPTPoint number of relay to control the fan on Asentria HVAC controllerrw Integer32 .1.3.6.1.4.1.3052.23.2.12.19.3.8.1.4 |
evHVACAsentriaUnitVentRelayESEventSensor number of relay to control the vent on Asentria HVAC controllerrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.3.8.1.5 |
evHVACAsentriaUnitVentRelayPTPoint number of relay to control the vent on Asentria HVAC controllerrw Integer32 .1.3.6.1.4.1.3052.23.2.12.19.3.8.1.6 |
evHVACAsentriaUnitTimeresetResets the time counter for Asentria HVAC unitrw Integer32 .1.3.6.1.4.1.3052.23.2.12.19.3.8.1.7 |
evHVACAsentriaSeqTimeresetResets the time counter for Asentria HVAC sequence numberrw Integer32 .1.3.6.1.4.1.3052.23.2.12.19.3.8.1.8 |
evHVACAsentriaUnitStage1CoolESEventSensor number of relay to control compressor stage 1 on Asentria HVAC controllerrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.3.8.1.20 |
evHVACAsentriaUnitStage1CoolPTPoint number of relay to control compressor stage 1 on Asentria HVAC controllerrw Integer32 .1.3.6.1.4.1.3052.23.2.12.19.3.8.1.21 |
evHVACAsentriaUnitStage1HeatESEventSensor number of relay to control heater stage 1 on Asentria HVAC controllerrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.3.8.1.22 |
evHVACAsentriaUnitStage1HeatPTPoint number of relay to control heater stage 1 on Asentria HVAC controllerrw Integer32 .1.3.6.1.4.1.3052.23.2.12.19.3.8.1.23 |
evHVACAsentriaUnitStage2CoolESEventSensor number of relay to control compressor stage 2 on Asentria HVAC controllerrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.3.8.1.30 |
evHVACAsentriaUnitStage2CoolPTPoint number of relay to control compressor stage 2 on Asentria HVAC controllerrw Integer32 .1.3.6.1.4.1.3052.23.2.12.19.3.8.1.31 |
evHVACAsentriaUnitStage2HeatESEventSensor number of relay to control heater stage 2 on Asentria HVAC controllerrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.3.8.1.32 |
evHVACAsentriaUnitStage2HeatPTPoint number of relay to control heater stage 2 on Asentria HVAC controllerrw Integer32 .1.3.6.1.4.1.3052.23.2.12.19.3.8.1.33 |
evHVACAsentriaTemp OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.12.19.3.9 |
evHVACAsentriaTempScaleAsentria HVAC controller temperature scalerw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.3.9.1 |
evHVACAsentriaTempCoolThreshTemperature above this threshold before cooling via Asentria HVAC controllerrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.3.9.2 |
evHVACAsentriaTempHeatThreshTemperature below this threshold before heating via Asentria HVAC controllerrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.3.9.3 |
evHVACAsentriaTempEnableAsentria HVAC temperature alarm enablerw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.3.9.4 |
evHVACAsentriaTempEventDeadbandAsentria HVAC temperature alarm event deadbandrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.3.9.5 |
evHVACAsentriaTempVLowValueAsentria HVAC temperature alarm event very low valuerw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.3.9.6 |
evHVACAsentriaTempVLowActionsAsentria HVAC temperature alarm event very low actionsrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.3.9.7 |
evHVACAsentriaTempVLowTrapNumAsentria HVAC temperature alarm event very low trap numberrw Integer32 .1.3.6.1.4.1.3052.23.2.12.19.3.9.8 |
evHVACAsentriaTempVLowClassAsentria HVAC temperature alarm event very low classrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.3.9.9 |
evHVACAsentriaTempLowValueAsentria HVAC temperature alarm event low valuerw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.3.9.10 |
evHVACAsentriaTempLowActionsAsentria HVAC temperature alarm event low actionsrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.3.9.11 |
evHVACAsentriaTempLowTrapNumAsentria HVAC temperature alarm event low trap numberrw Integer32 .1.3.6.1.4.1.3052.23.2.12.19.3.9.12 |
evHVACAsentriaTempLowClassAsentria HVAC temperature alarm event low classrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.3.9.13 |
evHVACAsentriaTempNormalActionsAsentria HVAC temperature alarm event return to normal actionsrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.3.9.14 |
evHVACAsentriaTempNormalTrapNumAsentria HVAC temperature alarm event return to normal trap numberrw Integer32 .1.3.6.1.4.1.3052.23.2.12.19.3.9.15 |
evHVACAsentriaTempNormalClassAsentria HVAC temperature alarm event return to normal classrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.3.9.16 |
evHVACAsentriaTempHighValueAsentria HVAC temperature alarm event high valuerw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.3.9.17 |
evHVACAsentriaTempHighActionsAsentria HVAC temperature alarm event high actionsrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.3.9.18 |
evHVACAsentriaTempHighTrapNumAsentria HVAC temperature alarm event high trap numberrw Integer32 .1.3.6.1.4.1.3052.23.2.12.19.3.9.19 |
evHVACAsentriaTempHighClassAsentria HVAC temperature alarm event high classrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.3.9.20 |
evHVACAsentriaTempVHighValueAsentria HVAC temperature alarm event very high valuerw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.3.9.21 |
evHVACAsentriaTempVHighActionsAsentria HVAC temperature alarm event very high actionsrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.3.9.22 |
evHVACAsentriaTempVHighTrapNumAsentria HVAC temperature alarm event very high trap numberrw Integer32 .1.3.6.1.4.1.3052.23.2.12.19.3.9.23 |
evHVACAsentriaTempVHighClassAsentria HVAC temperature alarm event very high classrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.3.9.24 |
evHVACAsentriaTempDeadbandAsentria HVAC temperature deadband before stopping current staterw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.3.9.25 |
evHVACAsentriaTempDifferenceAsentria HVAC temperature step before changing statesrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.3.9.26 |
evHVACAsentriaHumid OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.12.19.3.10 |
evHVACAsentriaHumidInThreshHumidity above this threshold before cooling via Asentria HVAC controllerrw Integer32 .1.3.6.1.4.1.3052.23.2.12.19.3.10.2 |
evHVACAsentriaHumidOutThreshHumidity above this threshold before not allowing venting via Asentria HVAC controllerrw Integer32 .1.3.6.1.4.1.3052.23.2.12.19.3.10.3 |
evHVACAsentriaHumidEnableAsentria HVAC humidity alarm enablerw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.3.10.4 |
evHVACAsentriaHumidEventDeadbandAsentria HVAC humidity alarm event deadbandrw Integer32 .1.3.6.1.4.1.3052.23.2.12.19.3.10.5 |
evHVACAsentriaHumidVLowValueAsentria HVAC humidity alarm event very low valuerw Integer32 .1.3.6.1.4.1.3052.23.2.12.19.3.10.6 |
evHVACAsentriaHumidVLowActionsAsentria HVAC humidity alarm event very low actionsrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.3.10.7 |
evHVACAsentriaHumidVLowTrapNumAsentria HVAC humidity alarm event very low trap numberrw Integer32 .1.3.6.1.4.1.3052.23.2.12.19.3.10.8 |
evHVACAsentriaHumidVLowClassAsentria HVAC humidity alarm event very low classrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.3.10.9 |
evHVACAsentriaHumidLowValueAsentria HVAC humidity alarm event low valuerw Integer32 .1.3.6.1.4.1.3052.23.2.12.19.3.10.10 |
evHVACAsentriaHumidLowActionsAsentria HVAC humidity alarm event low actionsrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.3.10.11 |
evHVACAsentriaHumidLowTrapNumAsentria HVAC humidity alarm event low trap numberrw Integer32 .1.3.6.1.4.1.3052.23.2.12.19.3.10.12 |
evHVACAsentriaHumidLowClassAsentria HVAC humidity alarm event low classrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.3.10.13 |
evHVACAsentriaHumidNormalActionsAsentria HVAC humidity alarm event return to normal actionsrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.3.10.14 |
evHVACAsentriaHumidNormalTrapNumAsentria HVAC humidity alarm event return to normal trap numberrw Integer32 .1.3.6.1.4.1.3052.23.2.12.19.3.10.15 |
evHVACAsentriaHumidNormalClassAsentria HVAC humidity alarm event return to normal classrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.3.10.16 |
evHVACAsentriaHumidHighValueAsentria HVAC humidity alarm event high valuerw Integer32 .1.3.6.1.4.1.3052.23.2.12.19.3.10.17 |
evHVACAsentriaHumidHighActionsAsentria HVAC humidity alarm event high actionsrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.3.10.18 |
evHVACAsentriaHumidHighTrapNumAsentria HVAC humidity alarm event high trap numberrw Integer32 .1.3.6.1.4.1.3052.23.2.12.19.3.10.19 |
evHVACAsentriaHumidHighClassAsentria HVAC humidity alarm event high classrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.3.10.20 |
evHVACAsentriaHumidVHighValueAsentria HVAC humidity alarm event very high valuerw Integer32 .1.3.6.1.4.1.3052.23.2.12.19.3.10.21 |
evHVACAsentriaHumidVHighActionsAsentria HVAC humidity alarm event very high actionsrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.3.10.22 |
evHVACAsentriaHumidVHighTrapNumAsentria HVAC humidity alarm event very high trap numberrw Integer32 .1.3.6.1.4.1.3052.23.2.12.19.3.10.23 |
evHVACAsentriaHumidVHighClassAsentria HVAC humidity alarm event very high classrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.3.10.24 |
evHVACAsentriaHumidDeadbandAsentria HVAC humidity deadband before stopping current staterw Integer32 .1.3.6.1.4.1.3052.23.2.12.19.3.10.25 |
evHVACAsentriaHumidDifferenceAsentria HVAC humidity step before changing statesrw Integer32 .1.3.6.1.4.1.3052.23.2.12.19.3.10.26 |
evHVACAirsys OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.12.19.4 |
evHVACAirsysGeneral OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.12.19.4.1 |
evHVACAirsysGeneratorLogicAirsys HVAC generator logicrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.1.1 |
evHVACAirsysFreeModeAirsys HVAC free moderw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.1.2 |
evHVACAirsysRemoteEnableAirsys HVAC remote control enablerw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.1.3 |
evHVACAirsysHVACRotationAirsys HVAC rotate unit lead/lagrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.1.4 |
evHVACAirsysRotationRuntimeAirsys HVAC rotation runtime periodrw Integer32 .1.3.6.1.4.1.3052.23.2.12.19.4.1.5 |
evHVACAirsysAlarm OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.12.19.4.2 |
evHVACAirsysUnitTableAirsys HVAC unit table SEQUENCE OF HVACAirsysUnit .1.3.6.1.4.1.3052.23.2.12.19.4.2.1 |
evHVACAirsysUnitEntryAirsys HVAC unit table entry HVACAirsysUnit .1.3.6.1.4.1.3052.23.2.12.19.4.2.1.1 |
evHVACAirsysUnitIndexIndex for Airsys HVAC unitro Integer32 .1.3.6.1.4.1.3052.23.2.12.19.4.2.1.1.1 |
evHVACAirsysULowPEnableAirsys HVAC unit low pressure alarm enablerw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.2.1.1.2 |
evHVACAirsysULowPActionsAirsys HVAC actions to perform for low pressure alarm notificationrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.2.1.1.3 |
evHVACAirsysULowPTrapnumAirsys HVAC trap number for low pressure alarm notificationrw Integer32 .1.3.6.1.4.1.3052.23.2.12.19.4.2.1.1.4 |
evHVACAirsysULowPClassAirsys HVAC alarm class for low pressure alarm notificationrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.2.1.1.5 |
evHVACAirsysULowPNormActionsAirsys HVAC return to normal actions to perform for low pressure alarm notificationrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.2.1.1.6 |
evHVACAirsysULowPNormTrapNumAirsys HVAC return to normal trap number for low pressure alarm notificationrw Integer32 .1.3.6.1.4.1.3052.23.2.12.19.4.2.1.1.7 |
evHVACAirsysULowPNormClassAirsys HVAC return to normal class for low pressure alarm notificationrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.2.1.1.8 |
evHVACAirsysUHighPEnableAirsys HVAC unit high pressure alarm enablerw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.2.1.1.9 |
evHVACAirsysUHighPActionsAirsys HVAC actions to perform for high pressure alarm notificationrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.2.1.1.10 |
evHVACAirsysUHighPTrapnumAirsys HVAC trap number for high pressure alarm notificationrw Integer32 .1.3.6.1.4.1.3052.23.2.12.19.4.2.1.1.11 |
evHVACAirsysUHighPClassAirsys HVAC alarm class for high pressure alarm notificationrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.2.1.1.12 |
evHVACAirsysUHighPNormActionsAirsys HVAC return to normal actions to perform for high pressure alarm notificationrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.2.1.1.13 |
evHVACAirsysUHighPNormTrapNumAirsys HVAC return to normal trap number for high pressure alarm notificationrw Integer32 .1.3.6.1.4.1.3052.23.2.12.19.4.2.1.1.14 |
evHVACAirsysUHighPNormClassAirsys HVAC return to normal class for high pressure alarm notificationrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.2.1.1.15 |
evHVACAirsysUEvapFanEnableAirsys HVAC unit evaporator fan alarm enablerw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.2.1.1.16 |
evHVACAirsysUEvapFanActionsAirsys HVAC actions to perform for evaporator fan alarm notificationrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.2.1.1.17 |
evHVACAirsysUEvapFanTrapnumAirsys HVAC trap number for evaporator fan alarm notificationrw Integer32 .1.3.6.1.4.1.3052.23.2.12.19.4.2.1.1.18 |
evHVACAirsysUEvapFanClassAirsys HVAC alarm class for evaporator fan alarm notificationrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.2.1.1.19 |
evHVACAirsysUEvapFanNormActionsAirsys HVAC return to normal actions to perform for evaporator fan alarm notificationrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.2.1.1.20 |
evHVACAirsysUEvapFanNormTrapNumAirsys HVAC return to normal trap number for evaporator fan alarm notificationrw Integer32 .1.3.6.1.4.1.3052.23.2.12.19.4.2.1.1.21 |
evHVACAirsysUEvapFanNormClassAirsys HVAC return to normal class for evaporator fan alarm notificationrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.2.1.1.22 |
evHVACAirsysUDirtyEnableAirsys HVAC unit dirty filter alarm enablerw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.2.1.1.23 |
evHVACAirsysUDirtyActionsAirsys HVAC actions to perform for dirty filter alarm notificationrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.2.1.1.24 |
evHVACAirsysUDirtyTrapnumAirsys HVAC trap number for dirty filter alarm notificationrw Integer32 .1.3.6.1.4.1.3052.23.2.12.19.4.2.1.1.25 |
evHVACAirsysUDirtyClassAirsys HVAC alarm class for dirty filter alarm notificationrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.2.1.1.26 |
evHVACAirsysUDirtyNormActionsAirsys HVAC return to normal actions to perform for dirty filter alarm notificationrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.2.1.1.27 |
evHVACAirsysUDirtyNormTrapNumAirsys HVAC return to normal trap number for dirty filter alarm notificationrw Integer32 .1.3.6.1.4.1.3052.23.2.12.19.4.2.1.1.28 |
evHVACAirsysUDirtyNormClassAirsys HVAC return to normal class for dirty filter alarm notificationrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.2.1.1.29 |
evHVACAirsysUInProbeEnableAirsys HVAC unit indoor probe broken alarm enablerw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.2.1.1.30 |
evHVACAirsysUInProbeActionsAirsys HVAC actions to perform for indoor probe broken alarm notificationrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.2.1.1.31 |
evHVACAirsysUInProbeTrapnumAirsys HVAC trap number for indoor probe broken alarm notificationrw Integer32 .1.3.6.1.4.1.3052.23.2.12.19.4.2.1.1.32 |
evHVACAirsysUInProbeClassAirsys HVAC alarm class for indoor probe broken alarm notificationrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.2.1.1.33 |
evHVACAirsysUInProbeNormActionsAirsys HVAC return to normal actions to perform for indoor probe broken alarm notificationrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.2.1.1.34 |
evHVACAirsysUInProbeNormTrapNumAirsys HVAC return to normal trap number for indoor probe broken alarm notificationrw Integer32 .1.3.6.1.4.1.3052.23.2.12.19.4.2.1.1.35 |
evHVACAirsysUInProbeNormClassAirsys HVAC return to normal class for indoor probe broken alarm notificationrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.2.1.1.36 |
evHVACAirsysUDamperEnableAirsys HVAC unit high pressure alarm enablerw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.2.1.1.37 |
evHVACAirsysUDamperActionsAirsys HVAC actions to perform for high pressure alarm notificationrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.2.1.1.38 |
evHVACAirsysUDamperTrapnumAirsys HVAC trap number for high pressure alarm notificationrw Integer32 .1.3.6.1.4.1.3052.23.2.12.19.4.2.1.1.39 |
evHVACAirsysUDamperClassAirsys HVAC alarm class for high pressure alarm notificationrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.2.1.1.40 |
evHVACAirsysUDamperNormActionsAirsys HVAC return to normal actions to perform for high pressure alarm notificationrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.2.1.1.41 |
evHVACAirsysUDamperNormTrapNumAirsys HVAC return to normal trap number for high pressure alarm notificationrw Integer32 .1.3.6.1.4.1.3052.23.2.12.19.4.2.1.1.42 |
evHVACAirsysUDamperNormClassAirsys HVAC return to normal class for high pressure alarm notificationrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.2.1.1.43 |
evHVACAirsysUSupProbeEnableAirsys HVAC unit supply probe broken alarm enablerw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.2.1.1.44 |
evHVACAirsysUSupProbeActionsAirsys HVAC actions to perform for supply probe broken alarm notificationrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.2.1.1.45 |
evHVACAirsysUSupProbeTrapnumAirsys HVAC trap number for supply probe broken alarm notificationrw Integer32 .1.3.6.1.4.1.3052.23.2.12.19.4.2.1.1.46 |
evHVACAirsysUSupProbeClassAirsys HVAC alarm class for supply probe broken alarm notificationrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.2.1.1.47 |
evHVACAirsysUSupProbeNormActionsAirsys HVAC return to normal actions to perform for supply probe broken alarm notificationrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.2.1.1.48 |
evHVACAirsysUSupProbeNormTrapNumAirsys HVAC return to normal trap number for supply probe broken alarm notificationrw Integer32 .1.3.6.1.4.1.3052.23.2.12.19.4.2.1.1.49 |
evHVACAirsysUSupProbeNormClassAirsys HVAC return to normal class for supply probe broken alarm notificationrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.2.1.1.50 |
evHVACAirsysSmokeFireEnableAirsys HVAC unit smoke/fire alarm enablerw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.2.2 |
evHVACAirsysSmokeFireActionsAirsys HVAC actions to perform for smoke/fire alarm notificationrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.2.3 |
evHVACAirsysSmokeFireTrapnumAirsys HVAC trap number for smoke/fire alarm notificationrw Integer32 .1.3.6.1.4.1.3052.23.2.12.19.4.2.4 |
evHVACAirsysSmokeFireClassAirsys HVAC alarm class for smoke/fire alarm notificationrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.2.5 |
evHVACAirsysSmokeFireNormActionsAirsys HVAC return to normal actions to perform for smoke/fire alarm notificationrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.2.6 |
evHVACAirsysSmokeFireNormTrapNumAirsys HVAC return to normal trap number for smoke/fire alarm notificationrw Integer32 .1.3.6.1.4.1.3052.23.2.12.19.4.2.7 |
evHVACAirsysSmokeFireNormClassAirsys HVAC return to normal class for smoke/fire alarm notificationrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.2.8 |
evHVACAirsysLowRoomTempEnableAirsys HVAC unit low room temperature alarm enablerw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.2.9 |
evHVACAirsysLowRoomTempActionsAirsys HVAC actions to perform for low room temperature alarm notificationrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.2.10 |
evHVACAirsysLowRoomTempTrapnumAirsys HVAC trap number for low room temperature alarm notificationrw Integer32 .1.3.6.1.4.1.3052.23.2.12.19.4.2.11 |
evHVACAirsysLowRoomTempClassAirsys HVAC alarm class for low room temperature alarm notificationrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.2.12 |
evHVACAirsysLowRoomTempNormActionsAirsys HVAC return to normal actions to perform for low room temperature alarm notificationrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.2.13 |
evHVACAirsysLowRoomTempNormTrapNumAirsys HVAC return to normal trap number for low room temperature alarm notificationrw Integer32 .1.3.6.1.4.1.3052.23.2.12.19.4.2.14 |
evHVACAirsysLowRoomTempNormClassAirsys HVAC return to normal class for low room temperature alarm notificationrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.2.15 |
evHVACAirsysHighRoomTempEnableAirsys HVAC unit high room temperature alarm enablerw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.2.16 |
evHVACAirsysHighRoomTempActionsAirsys HVAC actions to perform for high room temperature alarm notificationrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.2.17 |
evHVACAirsysHighRoomTempTrapnumAirsys HVAC trap number for high room temperature alarm notificationrw Integer32 .1.3.6.1.4.1.3052.23.2.12.19.4.2.18 |
evHVACAirsysHighRoomTempClassAirsys HVAC alarm class for high room temperature alarm notificationrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.2.19 |
evHVACAirsysHighRoomTempNormActionsAirsys HVAC return to normal actions to perform for high room temperature alarm notificationrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.2.20 |
evHVACAirsysHighRoomTempNormTrapNumAirsys HVAC return to normal trap number for high room temperature alarm notificationrw Integer32 .1.3.6.1.4.1.3052.23.2.12.19.4.2.21 |
evHVACAirsysHighRoomTempNormClassAirsys HVAC return to normal class for high room temperature alarm notificationrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.2.22 |
evHVACAirsysPowerEnableAirsys HVAC unit power failure alarm enablerw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.2.23 |
evHVACAirsysPowerActionsAirsys HVAC actions to perform for power failure alarm notificationrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.2.24 |
evHVACAirsysPowerTrapnumAirsys HVAC trap number for power failure alarm notificationrw Integer32 .1.3.6.1.4.1.3052.23.2.12.19.4.2.25 |
evHVACAirsysPowerClassAirsys HVAC alarm class for power failure alarm notificationrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.2.26 |
evHVACAirsysPowerNormActionsAirsys HVAC return to normal actions to perform for power failure alarm notificationrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.2.27 |
evHVACAirsysPowerNormTrapNumAirsys HVAC return to normal trap number for power failure alarm notificationrw Integer32 .1.3.6.1.4.1.3052.23.2.12.19.4.2.28 |
evHVACAirsysPowerNormClassAirsys HVAC return to normal class for power failure alarm notificationrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.2.29 |
evHVACAirsyspLANEnableAirsys HVAC unit pLAN alarm enablerw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.2.30 |
evHVACAirsyspLANActionsAirsys HVAC actions to perform for pLAN alarm notificationrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.2.31 |
evHVACAirsyspLANTrapnumAirsys HVAC trap number for pLAN alarm notificationrw Integer32 .1.3.6.1.4.1.3052.23.2.12.19.4.2.32 |
evHVACAirsyspLANClassAirsys HVAC alarm class for pLAN alarm notificationrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.2.33 |
evHVACAirsyspLANNormActionsAirsys HVAC return to normal actions to perform for pLAN alarm notificationrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.2.34 |
evHVACAirsyspLANNormTrapNumAirsys HVAC return to normal trap number for pLAN alarm notificationrw Integer32 .1.3.6.1.4.1.3052.23.2.12.19.4.2.35 |
evHVACAirsyspLANNormClassAirsys HVAC return to normal class for pLAN alarm notificationrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.2.36 |
evHVACAirsysClockEnableAirsys HVAC unit clock alarm enablerw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.2.37 |
evHVACAirsysClockActionsAirsys HVAC actions to perform for clock alarm notificationrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.2.38 |
evHVACAirsysClockTrapnumAirsys HVAC trap number for clock alarm notificationrw Integer32 .1.3.6.1.4.1.3052.23.2.12.19.4.2.39 |
evHVACAirsysClockClassAirsys HVAC alarm class for clock alarm notificationrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.2.40 |
evHVACAirsysClockNormActionsAirsys HVAC return to normal actions to perform for clock alarm notificationrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.2.41 |
evHVACAirsysClockNormTrapNumAirsys HVAC return to normal trap number for clock alarm notificationrw Integer32 .1.3.6.1.4.1.3052.23.2.12.19.4.2.42 |
evHVACAirsysClockNormClassAirsys HVAC return to normal class for clock alarm notificationrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.2.43 |
evHVACAirsysHumidProbeEnableAirsys HVAC unit humidity probe broken alarm enablerw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.2.44 |
evHVACAirsysHumidProbeActionsAirsys HVAC actions to perform for humidity probe broken alarm notificationrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.2.45 |
evHVACAirsysHumidProbeTrapnumAirsys HVAC trap number for humidity probe broken alarm notificationrw Integer32 .1.3.6.1.4.1.3052.23.2.12.19.4.2.46 |
evHVACAirsysHumidProbeClassAirsys HVAC alarm class for humidity probe broken alarm notificationrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.2.47 |
evHVACAirsysHumidProbeNormActionsAirsys HVAC return to normal actions to perform for humidity probe broken alarm notificationrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.2.48 |
evHVACAirsysHumidProbeNormTrapNumAirsys HVAC return to normal trap number for humidity probe broken alarm notificationrw Integer32 .1.3.6.1.4.1.3052.23.2.12.19.4.2.49 |
evHVACAirsysHumidProbeNormClassAirsys HVAC return to normal class for humidity probe broken alarm notificationrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.2.50 |
evHVACAirsysOutProbeEnableAirsys HVAC unit outdoor probe broken alarm enablerw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.2.51 |
evHVACAirsysOutProbeActionsAirsys HVAC actions to perform for outdoor probe broken alarm notificationrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.2.52 |
evHVACAirsysOutProbeTrapnumAirsys HVAC trap number for outdoor probe broken alarm notificationrw Integer32 .1.3.6.1.4.1.3052.23.2.12.19.4.2.53 |
evHVACAirsysOutProbeClassAirsys HVAC alarm class for outdoor probe broken alarm notificationrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.2.54 |
evHVACAirsysOutProbeNormActionsAirsys HVAC return to normal actions to perform for outdoor probe broken alarm notificationrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.2.55 |
evHVACAirsysOutProbeNormTrapNumAirsys HVAC return to normal trap number for outdoor probe broken alarm notificationrw Integer32 .1.3.6.1.4.1.3052.23.2.12.19.4.2.56 |
evHVACAirsysOutProbeNormClassAirsys HVAC return to normal class for outdoor probe broken alarm notificationrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.2.57 |
evHVACAirsysBothCompressEnableAirsys HVAC unit both compressors on alarm enablerw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.2.58 |
evHVACAirsysBothCompressActionsAirsys HVAC actions to perform for both compressors on alarm notificationrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.2.59 |
evHVACAirsysBothCompressTrapnumAirsys HVAC trap number for both compressors on alarm notificationrw Integer32 .1.3.6.1.4.1.3052.23.2.12.19.4.2.60 |
evHVACAirsysBothCompressClassAirsys HVAC alarm class for both compressors on alarm notificationrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.2.61 |
evHVACAirsysBothCompressNormActionsAirsys HVAC return to normal actions to perform for both compressors on alarm notificationrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.2.62 |
evHVACAirsysBothCompressNormTrapNumAirsys HVAC return to normal trap number for both compressors on alarm notificationrw Integer32 .1.3.6.1.4.1.3052.23.2.12.19.4.2.63 |
evHVACAirsysBothCompressNormClassAirsys HVAC return to normal class for both compressors on alarm notificationrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.2.64 |
evHVACAirsysGeneratorEnableAirsys HVAC unit generator running alarm enablerw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.2.65 |
evHVACAirsysGeneratorActionsAirsys HVAC actions to perform for generator running alarm notificationrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.2.66 |
evHVACAirsysGeneratorTrapnumAirsys HVAC trap number for generator running alarm notificationrw Integer32 .1.3.6.1.4.1.3052.23.2.12.19.4.2.67 |
evHVACAirsysGeneratorClassAirsys HVAC alarm class for generator running alarm notificationrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.2.68 |
evHVACAirsysGeneratorNormActionsAirsys HVAC return to normal actions to perform for generator running alarm notificationrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.2.69 |
evHVACAirsysGeneratorNormTrapNumAirsys HVAC return to normal trap number for generator running alarm notificationrw Integer32 .1.3.6.1.4.1.3052.23.2.12.19.4.2.70 |
evHVACAirsysGeneratorNormClassAirsys HVAC return to normal class for generator running alarm notificationrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.2.71 |
evHVACAirsysConnectionEnableAirsys HVAC unit lost connection alarm enablerw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.2.72 |
evHVACAirsysConnectionActionsAirsys HVAC actions to perform for lost connection alarm notificationrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.2.73 |
evHVACAirsysConnectionTrapnumAirsys HVAC trap number for lost connection alarm notificationrw Integer32 .1.3.6.1.4.1.3052.23.2.12.19.4.2.74 |
evHVACAirsysConnectionClassAirsys HVAC alarm class for lost connection alarm notificationrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.2.75 |
evHVACAirsysConnectionNormActionsAirsys HVAC return to normal actions to perform for lost connection alarm notificationrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.2.76 |
evHVACAirsysConnectionNormTrapNumAirsys HVAC return to normal trap number for lost connection alarm notificationrw Integer32 .1.3.6.1.4.1.3052.23.2.12.19.4.2.77 |
evHVACAirsysConnectionNormClassAirsys HVAC return to normal class for lost connection alarm notificationrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.2.78 |
evHVACAirsysTemp OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.12.19.4.3 |
evHVACAirsysTempBaseThreshAirsys HVAC temperature base thresholdrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.3.1 |
evHVACAirsysTempCoolDeadbandAirsys HVAC temperature cool deadbandrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.3.2 |
evHVACAirsysTempHeatDeadbandAirsys HVAC temperature heat deadbandrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.3.3 |
evHVACAirsysTempHighValueAirsys HVAC high temperature alarm valuerw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.3.4 |
evHVACAirsysTempLowValueAirsys HVAC low temperature alarm valuerw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.19.4.3.5 |
evHVACAirsysHumid OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.12.19.4.4 |
evHVACAirsysHumidMaxFreeAirsys HVAC return to normal class for lost connection alarm notificationrw Integer32 .1.3.6.1.4.1.3052.23.2.12.19.4.4.1 |
evHVACAirsysHumidDeadbandAirsys HVAC return to normal class for lost connection alarm notificationrw Integer32 .1.3.6.1.4.1.3052.23.2.12.19.4.4.2 |
evEvps OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.12.20 |
evpsEnableEVPS (Emerson Vortex Power System) enable.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.20.1 |
evpsIPAddressEVPS IP address.rw IpAddress .1.3.6.1.4.1.3052.23.2.12.20.2 |
evpsPortEVPS IP web port.rw Integer32 .1.3.6.1.4.1.3052.23.2.12.20.3 |
evpsTimeoutEVPS IP timeout.rw Integer32 .1.3.6.1.4.1.3052.23.2.12.20.4 |
accessControl OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.12.21 |
acActionsActions for the access control event.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.21.2 |
acTrapnumTrap number for the access control event.rw Integer32 .1.3.6.1.4.1.3052.23.2.12.21.3 |
acClassClass (severity) for the access control event.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.21.4 |
accessControlDeviceTableTable of access control devices for Access Control Device Management. SEQUENCE OF AccessControlDevice .1.3.6.1.4.1.3052.23.2.12.21.10 |
accessControlDeviceEntryEntry for table of access control devices for Access Control Device Management. AccessControlDevice .1.3.6.1.4.1.3052.23.2.12.21.10.1 |
acdIndexIndex for table of access control devices for Access Control Device Management.ro Integer32 .1.3.6.1.4.1.3052.23.2.12.21.10.1.1 |
acdEnableEnable management for this access control device.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.21.10.1.2 |
acdNameThe name of the access control device for informational purpose only.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.21.10.1.3 |
acdReaderThe kind of reader (Weigand etc.) for access control device.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.21.10.1.4 |
acdReaderESIndex of the reader interface hardware instance allocated as the access control device.rw Integer32 .1.3.6.1.4.1.3052.23.2.12.21.10.1.5 |
acdReaderPointWhich wiegand on the wiegand EventSensor to use for as the access control device.rw Integer32 .1.3.6.1.4.1.3052.23.2.12.21.10.1.6 |
acdRelayTypeType of relay which activates the door strike.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.21.10.1.7 |
acdRelayESWhich relay EventSensor is connected to the door strike.rw Integer32 .1.3.6.1.4.1.3052.23.2.12.21.10.1.8 |
acdRelayPointWhich relay on the relay EventSensor is connected to the door strike.rw Integer32 .1.3.6.1.4.1.3052.23.2.12.21.10.1.9 |
acdActiveStateEnergized/De-Energized, esp. for wiegand relayrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.21.10.1.10 |
acdStateACTIVE/INACTIVErw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.21.10.1.11 |
acdNormalClassNormal classrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.21.10.1.12 |
acdEventClassEvent/alarm classrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.21.10.1.13 |
acdOpenTimeHow many seconds that the lock should be held open upon access granted.rw Integer32 .1.3.6.1.4.1.3052.23.2.12.21.10.1.14 |
acdExtraOpenTimeHow long in the case of special usersrw Integer32 .1.3.6.1.4.1.3052.23.2.12.21.10.1.15 |
acdExitBtnEnabledEnabled if an exit-button is to be configuredrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.21.10.1.16 |
acdExitBtnESExit Button ES indexrw Integer32 .1.3.6.1.4.1.3052.23.2.12.21.10.1.17 |
acdExitBtnPointExit Button point indexrw Integer32 .1.3.6.1.4.1.3052.23.2.12.21.10.1.18 |
acdExitBtnPushStateOpen/Close if it maches the state then the button is considered pushed.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.21.10.1.19 |
acdExitOpenTimehow long the door lock/unlocked for exitrw Integer32 .1.3.6.1.4.1.3052.23.2.12.21.10.1.20 |
acdExitOpenDelayhow long to wait after exit button before starting openrw Integer32 .1.3.6.1.4.1.3052.23.2.12.21.10.1.21 |
acdExitEvtDisableON/OFF to disable sending exit button events to ASMrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.21.10.1.22 |
acdLastCardwhat was the last card # readrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.21.10.1.23 |
acdLastDatewhen was the last date that a vaild card was readrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.21.10.1.24 |
acdLastStatuswhat was the status of the last card readrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.21.10.1.25 |
acdLastSecondshow many seconds since the last GOOD card was readrw Integer32 .1.3.6.1.4.1.3052.23.2.12.21.10.1.26 |
accessControlUserTableTable of access control users for Access Control Device Management. SEQUENCE OF AccessControlUser .1.3.6.1.4.1.3052.23.2.12.21.11 |
accessControlUserEntryEntry for table of ACD users for Access Control Device Management. AccessControlUser .1.3.6.1.4.1.3052.23.2.12.21.11.1 |
acuIndexUserIndex of the user (1 to 500).rw Integer32 .1.3.6.1.4.1.3052.23.2.12.21.11.1.1 |
acuEnableEnable for the user.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.21.11.1.2 |
acuNameName for the user.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.21.11.1.3 |
acuSnUser Rfid Card Numberrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.21.11.1.4 |
acuPinKeypad Pinrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.21.11.1.5 |
acuScheduleWhich schedule in the table to userw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.21.11.1.6 |
acuExtratimeIs this user disabled and needs special timeoutsrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.21.11.1.7 |
acuSecurityLevel1-low,2-med,3=highrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.21.11.1.8 |
acuTimesAllowedHow many times can the user swipe their cardrw Integer32 .1.3.6.1.4.1.3052.23.2.12.21.11.1.9 |
acuTimesAccessedHow many times has the card been swipedrw Integer32 .1.3.6.1.4.1.3052.23.2.12.21.11.1.10 |
accessControlScheduleTableTable of access control devices schedule used on a user for Access Control Device Management. SEQUENCE OF AccessControlSchedule .1.3.6.1.4.1.3052.23.2.12.21.12 |
accessControlScheduleEntryEntry for table of access control devices schedule for Access Control Device Management. AccessControlSchedule .1.3.6.1.4.1.3052.23.2.12.21.12.1 |
acsNameThe configured name for the access control schedulerw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.21.12.1.1 |
acsSunComma separated sting of star-time:end-time e.g. 08:00-12:30,1330-1630rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.21.12.1.2 |
acsMonComma separated sting of star-time:end-time e.g. 08:00-12:30,1330-1630rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.21.12.1.3 |
acsTueComma separated sting of star-time:end-time e.g. 08:00-12:30,1330-1630rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.21.12.1.4 |
acsWedComma separated sting of star-time:end-time e.g. 08:00-12:30,1330-1630rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.21.12.1.5 |
acsThuComma separated sting of star-time:end-time e.g. 08:00-12:30,1330-1630rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.21.12.1.6 |
acsFriComma separated sting of star-time:end-time e.g. 08:00-12:30,1330-1630rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.21.12.1.7 |
acsSatComma separated sting of star-time:end-time e.g. 08:00-12:30,1330-1630rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.21.12.1.8 |
acsStartDaterw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.21.12.1.9 |
acsEndDaterw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.21.12.1.10 |
acsDateLimitationrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.21.12.1.11 |
acsDayRangerw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.21.12.1.12 |
acsAllowedDaysrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.21.12.1.13 |
acsMonthRangerw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.21.12.1.14 |
acsAllowedMonthsrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.21.12.1.15 |
acsExceptionsrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.21.12.1.16 |
acsExceptionDaterw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.21.12.1.17 |
acsExceptionNamerw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.21.12.1.18 |
telemetry OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.12.22 |
telemetryTable SEQUENCE OF TelemetryPoint .1.3.6.1.4.1.3052.23.2.12.22.1 |
telemetryEntryEntry for table of telemetry points TelemetryPoint .1.3.6.1.4.1.3052.23.2.12.22.1.1 |
telemetryPointIndexIndex for table of telemetry points.ro Integer32 .1.3.6.1.4.1.3052.23.2.12.22.1.1.1 |
telemetryPointNameName of telemetry point for information purpose only.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.22.1.1.2 |
telemetryPointKeyKey for telemetry point that specifies the telemetry data source.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.22.1.1.3 |
telemetryPointTypeDNP3 type for telemetry pointrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.22.1.1.4 |
telemetryPointClassDNP3 class for telemetry pointrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.22.1.1.5 |
telemetryPointDeadbandDeadband for telemetry pointrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.22.1.1.6 |
telemetryPointShortcodeShortcode for telemetry pointrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.22.1.1.7 |
siteSecurity OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.12.23 |
siteSecurityZoneTable SEQUENCE OF SiteSecurityZone .1.3.6.1.4.1.3052.23.2.12.23.1 |
siteSecurityZoneEntryEntry for table of site-security points SiteSecurityZone .1.3.6.1.4.1.3052.23.2.12.23.1.1 |
sitesecZoneEnableON/OFFrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.23.1.1.1 |
sitesecZoneDisarmedON/OFF to disarm security. ON disarms security.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.23.1.1.2 |
sitesecZoneNameName given to the zone by setting configurationrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.23.1.1.3 |
sitesecZoneStatePossible states are : DISABLED/DISARMED/ARMED/ACTIVATED/INTRUDERrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.23.1.1.4 |
sitesecZoneSensorESES index to and intrusion sensor (door, motion, etc)rw Integer32 .1.3.6.1.4.1.3052.23.2.12.23.1.1.5 |
sitesecZoneSensorPointPoint index to intrusion sensorrw Integer32 .1.3.6.1.4.1.3052.23.2.12.23.1.1.6 |
sitesecZoneIntrusionThresholdhow long to wait for a disarm eventrw Integer32 .1.3.6.1.4.1.3052.23.2.12.23.1.1.7 |
sitesecZoneReaderwhich reader(s) disarm this zonerw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.23.1.1.8 |
sitesecZoneReaderThresholdhow old the reader event can be for disarmingrw Integer32 .1.3.6.1.4.1.3052.23.2.12.23.1.1.9 |
sitesecZoneButtonEnablerw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.23.1.1.10 |
sitesecZoneButtonEScontact es to manually arm/disarm siterw Integer32 .1.3.6.1.4.1.3052.23.2.12.23.1.1.11 |
sitesecZoneButtonPointcontact point to manually arm/disarm siterw Integer32 .1.3.6.1.4.1.3052.23.2.12.23.1.1.12 |
sitesecZoneButtonTypeMOMENTARY/TOGGLErw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.23.1.1.13 |
sitesecZoneButtonThresholdArmhow long button press to armrw Integer32 .1.3.6.1.4.1.3052.23.2.12.23.1.1.14 |
sitesecZoneButtonThresholdDisarmhow long button press to disarmrw Integer32 .1.3.6.1.4.1.3052.23.2.12.23.1.1.15 |
sitesecZoneSirenEnablerw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.23.1.1.16 |
sitesecZoneSirenESan es location of a relay for a sirenrw Integer32 .1.3.6.1.4.1.3052.23.2.12.23.1.1.17 |
sitesecZoneSirenPointa point location of a relay for a siredrw Integer32 .1.3.6.1.4.1.3052.23.2.12.23.1.1.18 |
sitesecZoneRearmDelaya delay after a rearm event before the site is actually rearmedrw Integer32 .1.3.6.1.4.1.3052.23.2.12.23.1.1.19 |
sitesecZoneEventClassThe event class to report to ASM for an intruder alarmrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.23.1.1.20 |
siteSecurityDoorAjarTable SEQUENCE OF SiteSecurityDoorAjar .1.3.6.1.4.1.3052.23.2.12.23.2 |
siteSecurityDoorAjarEntry SiteSecurityDoorAjar .1.3.6.1.4.1.3052.23.2.12.23.2.1 |
siteSecurityDoorAjarEnablerw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.23.2.1.1 |
siteSecurityDoorAjarNameName given for this door ajar sensorrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.23.2.1.2 |
siteSecurityDoorAjarESES sensor input for door left ajarrw Integer32 .1.3.6.1.4.1.3052.23.2.12.23.2.1.3 |
siteSecurityDoorAjarPointPoint sensor input for door left ajarrw Integer32 .1.3.6.1.4.1.3052.23.2.12.23.2.1.4 |
siteSecurityDoorAjarThresholdNormala threshold to wait for door left ajarrw Integer32 .1.3.6.1.4.1.3052.23.2.12.23.2.1.5 |
siteSecurityDoorAjarThresholdExtratimea threshold to wait for door left ajar, for a disabled personrw Integer32 .1.3.6.1.4.1.3052.23.2.12.23.2.1.6 |
mediaCamera OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.12.24 |
mediaCameraTable SEQUENCE OF MediaCameraSEQ .1.3.6.1.4.1.3052.23.2.12.24.1 |
mediaCameraEntryEntry for table of IP Camera MediaCameraSEQ .1.3.6.1.4.1.3052.23.2.12.24.1.1 |
mediaCameraEanbleAccept FTP connections from this IP camera.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.24.1.1.1 |
mediaCemeraNameDescriptive name for camerarw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.24.1.1.2 |
mediaCameraHostAddress of IP camera.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.24.1.1.3 |
mediaCameraEventIntervalMax time between images before being considered as a new event.rw Integer32 .1.3.6.1.4.1.3052.23.2.12.24.1.1.4 |
mediaCameraImagesNumber of images currently.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.24.1.1.5 |
mediaCameraCountTodayNumber of new images for current dayro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.24.1.1.6 |
mediaCameraCountYesterdayNumber of new images yesterdayro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.12.24.1.1.7 |
action OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.14 |
actionCallNumberTableTable of phone numbers to dial for modem actions SEQUENCE OF ActionCallNumberConfig .1.3.6.1.4.1.3052.23.2.14.1 |
actionCallNumberEntryEntry for table of phone numbers to dial for modem actions ActionCallNumberConfig .1.3.6.1.4.1.3052.23.2.14.1.1 |
actionCallNumberIndexIndex for table of phone numbers to dial for modem actionsro Integer32 .1.3.6.1.4.1.3052.23.2.14.1.1.1 |
actionCallNumberThe number to dial for this action slotrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.14.1.1.2 |
actionPagerTableTable of pager configurations SEQUENCE OF ActionPagerConfig .1.3.6.1.4.1.3052.23.2.14.2 |
actionPagerEntryEntry for table of pager configurations ActionPagerConfig .1.3.6.1.4.1.3052.23.2.14.2.1 |
actionPagerIndexindex for table of pager configurationsro Integer32 .1.3.6.1.4.1.3052.23.2.14.2.1.1 |
actionPagerTypetype of this pager configurationrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.14.2.1.2 |
actionPagerNumberphone number to dial for this pager configurationrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.14.2.1.3 |
actionPagerIDID to use for this pager configurationrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.14.2.1.4 |
actionPagerMessagemessage to use for this pager configurationrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.14.2.1.5 |
actionPagerPostCalloutDelaySeconds to wait after dialing before sending IDrw Integer32 .1.3.6.1.4.1.3052.23.2.14.2.1.6 |
actionPagerPostIDDelaySeconds to wait after sending ID to send messagerw Integer32 .1.3.6.1.4.1.3052.23.2.14.2.1.7 |
actionSched OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.14.3 |
actionSchedEnableON/OFF enable action schedulerw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.14.3.1 |
actionSchedBeginaction schedule begin time (HH:MM)rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.14.3.2 |
actionSchedEndaction schedule end time (HH:MM)rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.14.3.3 |
actionSchedWeekdaysOnlyON/OFF whether the action schedule applies to weekdays only (ON) or all days (OFF)rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.14.3.4 |
actionAsentria OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.14.4 |
actionAsentriaRequireAckON/OFF Asentria action requires an ack from the receiverrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.14.4.1 |
actionAsentriaVersionversion 1.0 or 1.1rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.14.4.2 |
actionAsentriaTCPPortTCP port used for TCP-based Asentria alarmsrw Integer32 .1.3.6.1.4.1.3052.23.2.14.4.3 |
actionHostTableTable of network hosts to use for network-based actions SEQUENCE OF ActionHostConfig .1.3.6.1.4.1.3052.23.2.14.6 |
actionHostEntryEntry for table of network hosts to use for network-based actions ActionHostConfig .1.3.6.1.4.1.3052.23.2.14.6.1 |
actionHostIndexIndex for table of network hosts to use for network-based actionsro Integer32 .1.3.6.1.4.1.3052.23.2.14.6.1.1 |
actionHostHostname/IP address used as destination for network-based action (e.g., trap)rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.14.6.1.2 |
actionEmailTableTable of email addresses to use for email actions SEQUENCE OF ActionEmailConfig .1.3.6.1.4.1.3052.23.2.14.7 |
actionEmailEntryEntry for table of email addresses to use for email actions ActionEmailConfig .1.3.6.1.4.1.3052.23.2.14.7.1 |
actionEmailIndexIndex for table of email addresses to use for email actionsro Integer32 .1.3.6.1.4.1.3052.23.2.14.7.1.1 |
actionEmailemail addressrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.14.7.1.2 |
actionParseErrorWhen a user attempts to configure an invalid action setting/ object, this object says why it was invalid.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.14.8 |
sys OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.16 |
sysTime OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.16.1 |
sysTimeAutoDSTON/OFF automatically adjust for Daylight Savings Timerw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.16.1.1 |
sysTimeGMTOffsetAbsolute value of offset (hours) from GMT of the timezonerw Integer32 .1.3.6.1.4.1.3052.23.2.16.1.2 |
sysTimeGMTDirectionDirection (AHEAD/BEHIND) of timezone relative to GMTrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.16.1.3 |
sysTimeNet OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.16.1.4 |
sysTimeNetEnableNetwork time moderw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.16.1.4.1 |
sysTimeNetHostTableTable of hosts to use for network time services SEQUENCE OF NetworkTimeHostConfig .1.3.6.1.4.1.3052.23.2.16.1.4.2 |
sysTimeNetHostEntryEntry for table of hosts to use for network time services NetworkTimeHostConfig .1.3.6.1.4.1.3052.23.2.16.1.4.2.1 |
sysTimeNetHostIndexIndex for table of hosts to use for network time servicesro Integer32 .1.3.6.1.4.1.3052.23.2.16.1.4.2.1.1 |
sysTimeNetHosthost to use for network time servicesrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.16.1.4.2.1.2 |
sysPT OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.16.2 |
sysPTTimeoutTimeout (minutes) of inactivity after which a pass-through session is terminated (0 means it never terminates)rw Integer32 .1.3.6.1.4.1.3052.23.2.16.2.1 |
sysPTEndPausenumber of 16ths of a second between escape characters received on pass-through origin IO handle that are reuired for the escape characters to register as pass-through escape characters in the pass-through escape sequence. Set to 0 to make the escape character register as part of the pass- through escape sequence without requiring a pause.rw Integer32 .1.3.6.1.4.1.3052.23.2.16.2.2 |
sysPTJoinableEnable joinable pass-through sessions.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.16.2.3 |
sysMTUMaximum transfer unit for ethernet interfacesrw Integer32 .1.3.6.1.4.1.3052.23.2.16.3 |
sysAnswerStringString displayed upon loginrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.16.4 |
sysEventFileIDID string for events filerw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.16.6 |
sysEscapeCharacterDecimal ASCII code of the system escape characterrw Integer32 .1.3.6.1.4.1.3052.23.2.16.7 |
sysTimeStamp OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.16.8 |
sysTimeStampTimeFormatFormat of time stamp: HH:MM,HH:MM:SS,BLANKrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.16.8.1 |
sysTimeStampDateFormatFormat of date stamp: MM/DD,MM/DD/YY,MM/DD/YYYY,BLANKrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.16.8.2 |
sysTimeStampSpaceAfterON/OFF Inlude a space after timestamprw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.16.8.3 |
sysLog OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.16.9 |
sysLogModeSyslog mode: disabled, emit UDP (REMOTE), save in a rotating file set (FILE), or emit on a listening socket (SERVER)rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.16.9.1 |
sysLoghostSyslog host: destination machine when syslog mode is REMOTErw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.16.9.2 |
sysLogFilterString describing what functions place data in the syslogrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.16.9.3 |
sysLogFileSizeSize (in KB) of syslog files (when syslog mode is SERVER or FILE)rw Integer32 .1.3.6.1.4.1.3052.23.2.16.9.4 |
sysLogFileCountNumber of files in syslog file set (when syslog mode is SERVER or FILE)rw Integer32 .1.3.6.1.4.1.3052.23.2.16.9.5 |
sysLogListenPortTCP port on which the unit listens for a connection on which syslog data is dumped (when syslog mode is SERVER)rw Integer32 .1.3.6.1.4.1.3052.23.2.16.9.6 |
sysCRDB OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.16.10 |
sysCRDBCapacityCapacity of Call Record Database (in KB)ro Integer32 .1.3.6.1.4.1.3052.23.2.16.10.1 |
sysCRDBPercentFullPercent of the CRDB usedro Integer32 .1.3.6.1.4.1.3052.23.2.16.10.2 |
sysCRDBFileIDTableTable of CRDB file IDs SEQUENCE OF CRDBFileIDConfig .1.3.6.1.4.1.3052.23.2.16.10.3 |
sysCRDBFileIDEntryEntry for table of CRDB file IDs CRDBFileIDConfig .1.3.6.1.4.1.3052.23.2.16.10.3.1 |
sysCRDBFileIDIndexIndex for table of CRDB file IDsro Integer32 .1.3.6.1.4.1.3052.23.2.16.10.3.1.1 |
sysCRDBFileIDID of CRDB file for this port-associated file xrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.16.10.3.1.2 |
sysCRDBFileEnforceMinTableTable of CRDB file minimum size enforcement settings SEQUENCE OF CRDBFileEnforceMinConfig .1.3.6.1.4.1.3052.23.2.16.10.4 |
sysCRDBFileEnforceMinEntryEntry for table of CRDB file minimum size enforcement settings CRDBFileEnforceMinConfig .1.3.6.1.4.1.3052.23.2.16.10.4.1 |
sysCRDBFileEnforceMinIndexIndex for table of CRDB file minimum size enforcement settingsro Integer32 .1.3.6.1.4.1.3052.23.2.16.10.4.1.1 |
sysCRDBFileEnforceMinON/OFF: enforce minimum size for this CRDB file xrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.16.10.4.1.2 |
sysCharMaskCharacter mask used for ignoring certain characters on serial ports when assembling data records (when port mode is ASCII)rw OCTET STRING .1.3.6.1.4.1.3052.23.2.16.11 |
sysPromptPrompt to use in a commnand sessionrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.16.12 |
sysBootStatusString describing the boot status of the unit (Booted OK/ still bootingro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.16.13 |
sysLoc OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.16.14 |
sysLocLatitudeLatitude portion of geographic coordinates as stringrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.16.14.1 |
sysLocLongitudeLongitude portion of geographic coordinates as stringrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.16.14.2 |
sysLocXOffsetX-offset portion of geographic coordinates as stringrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.16.14.3 |
sysLocYOffsetY offset portion of geographic coordinates as stringrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.16.14.4 |
sysLocAngleAngle portion of geographic coordinates as stringrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.16.14.5 |
sysLocAltitudeAltitude as stringrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.16.14.6 |
sysAssetMgmt OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.16.15 |
sysAMManufacturerDevice manufacturerro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.16.15.1 |
sysAMProductDevice product description (i.e., model or model number)ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.16.15.2 |
sysAMSerialNumberManufacturer serial number for devicero DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.16.15.3 |
sysAMHardwareOptionsHardware options currently installed on devicero DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.16.15.4 |
sysAMSoftwareVersionCurrently-running software version on devicero DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.16.15.5 |
sysAMSiteNameSite Name of device (user definable, also known as the siteName object under the productIds branch.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.16.15.6 |
sysFileTransfer OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.16.17 |
sysFileTransferStatusStart/cancel file transfer, or check transfer status. To start, set this object to 'start'. To cancel, set this object to 'cancel'. To check status, get the objectrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.16.17.1 |
sysFileTransferURLURL (describing protocol, host, directory, and file) on which file transfer function operates.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.16.17.2 |
sysFileTransferUsernameUsername for user account at the resource specified by sysFileTransferURL.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.16.17.3 |
sysFileTransferPasswordPassword for user account at the resource specified by sysFileTransferURL.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.16.17.4 |
sysUpdate OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.16.18 |
sysUpdateStatusCheck time/result of last update attempt.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.16.18.1 |
auditLog OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.17 |
auditLogEnableON/OFF enable audit logrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.17.1 |
auditLogStoreResetsON/OFF audit log stores when the unit resetsrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.17.2 |
auditLogStoreCommandsON/OFF audit log stores commands entered in a command sessionrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.17.3 |
auditLogStoreOutputsON/OFF audit log stores output (relay output and power output) activityrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.17.4 |
auditLogStoreAlarmActionsON/OFF audit log stores action delivery activityrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.17.5 |
auditLogStorePwdFailuresON/OFF audit log stores when user was denied loginrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.17.6 |
auditLogStoreLoginsON/OFF audit log stores when a user was allowed loginrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.17.7 |
auditLogStoreSHSKON/OFF audit log stores serial handshaking status (regardless of serial handshaking event)rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.17.8 |
auditLogStorePassthroughON/OFF audit log stores pass-through activityrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.17.9 |
auditLogStoreInactivityON/OFF audit log stores when sessions expire due to inactivityrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.17.10 |
auditLogStorePollingON/OFF audit log stores CRDB polling activityrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.17.11 |
auditLogMaxSizeMaximum size (in KB) of audit logrw Integer32 .1.3.6.1.4.1.3052.23.2.17.12 |
scripting OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.18 |
scrGlobalEnableON/OFF enable scriptingrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.18.1 |
scrDTRCtrlPortEnableTableTable of DTR control port enables SEQUENCE OF ScriptingDTRCtrlPortEnableConfig .1.3.6.1.4.1.3052.23.2.18.2 |
scrDTRCtrlPortEnableEntryEntry for table of DTR control port enables ScriptingDTRCtrlPortEnableConfig .1.3.6.1.4.1.3052.23.2.18.2.1 |
scrDTRCtrlPortEnableIndexIndex for table of DTR control port enablesro Integer32 .1.3.6.1.4.1.3052.23.2.18.2.1.1 |
scrDTRCtrlPortEnableON/OFF enable DTR control of scripting for this portrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.18.2.1.2 |
scrTableTable of scripts SEQUENCE OF ScriptingConfig .1.3.6.1.4.1.3052.23.2.18.3 |
scrEntryEntry for table of scripts ScriptingConfig .1.3.6.1.4.1.3052.23.2.18.3.1 |
scrIndexIndex for table of scriptsro Integer32 .1.3.6.1.4.1.3052.23.2.18.3.1.1 |
scrEnableON/OFF enable this scriptrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.18.3.1.2 |
scrNameName of this scriptrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.18.3.1.3 |
scrFilenameFilename for this scriptrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.18.3.1.4 |
scrRunAlwaysON/OFF: this script always runsrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.18.3.1.5 |
scrRunAtStartupON/OFF: this script runs at startuprw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.18.3.1.6 |
scrRunScheduledON/OFF: this script runs at a certain time of dayrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.18.3.1.7 |
scrScheduleTimeTime of day (HH:MM) this script is scheduled to runrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.18.3.1.8 |
scrArgumentsArguments for this scriptrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.18.3.1.9 |
scrRepeatIntervalHow often this script runs (minutes)rw Integer32 .1.3.6.1.4.1.3052.23.2.18.3.1.10 |
scrVolatileStringTableTable of volatile string settings for use in scripts. SEQUENCE OF ScriptingVolatileString .1.3.6.1.4.1.3052.23.2.18.4 |
scrVolatileStringEntryEntry for table of volatile script string settings ScriptingVolatileString .1.3.6.1.4.1.3052.23.2.18.4.1 |
scrVolatileStringIndexIndex for table of volatile script string settingsro Integer32 .1.3.6.1.4.1.3052.23.2.18.4.1.1 |
scrVolatileStringVolatile string for use in scripts. Use this object to cache frequently-changing string values or string values that do not need to persist through reset. This object corresponds to the scripting.vstring[] setting key branch; use those keys in scripts and you can view or change their values with this object.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.18.4.1.2 |
scrVolatileIntTableTable of volatile integer settings for use in scripts. SEQUENCE OF ScriptingVolatileInt .1.3.6.1.4.1.3052.23.2.18.5 |
scrVolatileIntEntryEntry for table of volatile script integer settings ScriptingVolatileInt .1.3.6.1.4.1.3052.23.2.18.5.1 |
scrVolatileIntIndexIndex for table of volatile script integer settingsro Integer32 .1.3.6.1.4.1.3052.23.2.18.5.1.1 |
scrVolatileIntVolatile integer for use in scripts. Use this object to cache frequently-changing integer values or integer values that do not need to persist through reset. This object corresponds to the scripting.vint[] setting key branch; use those keys in scripts and you can view or change their values with this object.rw Integer32 .1.3.6.1.4.1.3052.23.2.18.5.1.2 |
scrNonVolatileStringTableTable of non-volatile string settings for use in scripts. SEQUENCE OF ScriptingNonVolatileString .1.3.6.1.4.1.3052.23.2.18.6 |
scrNonVolatileStringEntryEntry for table of non-volatile script string settings ScriptingNonVolatileString .1.3.6.1.4.1.3052.23.2.18.6.1 |
scrNonVolatileStringIndexIndex for table of non-volatile script string settingsro Integer32 .1.3.6.1.4.1.3052.23.2.18.6.1.1 |
scrNonVolatileStringNon-volatile string for use in scripts. Use this object to store values that need to persist through reset. This object corresponds to the scripting.nvstring[] setting key branch; use those keys in scripts and you can view or change their values with this object. Note: to store frequently- changing integers, use the scrVolatileString object, otherwise your scripts may cause unnecessary wear of the non-volatile storage medium on the unit.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.18.6.1.2 |
scrNonVolatileIntTableTable of non-volatile integer settings for use in scripts. SEQUENCE OF ScriptingNonVolatileInt .1.3.6.1.4.1.3052.23.2.18.7 |
scrNonVolatileIntEntryEntry for table of non-volatile script integer settings ScriptingNonVolatileInt .1.3.6.1.4.1.3052.23.2.18.7.1 |
scrNonVolatileIntIndexIndex for table of non-volatile script integer settingsro Integer32 .1.3.6.1.4.1.3052.23.2.18.7.1.1 |
scrNonVolatileIntNon-volatile integer for use in scripts. Use this object to store integer values that need to persist through reset. This object corresponds to the scripting.nvint[] setting key branch; use those keys in scripts and you can view or change their values with this object. Note: to store frequently- changing integers, use the scrVolatileInt object, otherwise your scripts may cause unnecessary wear of the non-volatile storage medium on the unit.rw Integer32 .1.3.6.1.4.1.3052.23.2.18.7.1.2 |
generator OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.19 |
genSet OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.19.1 |
genSetEnableEnable genset functionality; that is, a generator is in use.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.19.1.1 |
genSetRelay OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.19.1.2 |
genSetRelayEsWhich EventSensor has the relay which starts the generator, for genset relay configuration 1 only. This object maps to the same setting as genSetRelayTableEs.1.rw Integer32 .1.3.6.1.4.1.3052.23.2.19.1.2.1 |
genSetRelayPointWhich relay starts the generator, for genset relay configuration 1 only. This object maps to the same setting as genSetRelayTablePoint.1.rw Integer32 .1.3.6.1.4.1.3052.23.2.19.1.2.2 |
genSetRelayRunningstateWhich relay state corresponds with the generator starting/running. This object maps to the same setting as genSetRelayTableRunningstate.1.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.19.1.2.3 |
genSetRelayTableTable of relays for genset ignition. SEQUENCE OF GenSetRelaySequence .1.3.6.1.4.1.3052.23.2.19.1.2.5 |
genSetRelayTableEntryEntry for table of relays for genset ignition. GenSetRelaySequence .1.3.6.1.4.1.3052.23.2.19.1.2.5.1 |
genSetRelayTableIndexIndex for table of relays for genset ignition.ro Integer32 .1.3.6.1.4.1.3052.23.2.19.1.2.5.1.1 |
genSetRelayTableEnableEnable this relay for starting the generator.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.19.1.2.5.1.2 |
genSetRelayTableEsWhich EventSensor has the relay which starts the generator, for this genset relay configuration specified by the table index.rw Integer32 .1.3.6.1.4.1.3052.23.2.19.1.2.5.1.3 |
genSetRelayTablePointWhich relay point on the EventSensor used for starting the generator, for this genset relay configuration specified by the table index.rw Integer32 .1.3.6.1.4.1.3052.23.2.19.1.2.5.1.4 |
genSetRelayTableRunningstateWhich relay state corresponds with the generator starting/running, for this genset relay configuration specified by the table index.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.19.1.2.5.1.5 |
genSetCC OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.19.1.3 |
genSetCCEnableEnable generator running detection functionality; that is, the associated CC is valid for determining if generator is running.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.19.1.3.1 |
genSetCCEsWhich CC EventSensor has the CC which is connected to the genertor running detection monitor.rw Integer32 .1.3.6.1.4.1.3052.23.2.19.1.3.2 |
genSetCCPointWhich CC is connected to the genertor running detection monitor.rw Integer32 .1.3.6.1.4.1.3052.23.2.19.1.3.3 |
genSetCCRunningStateWhich CC physical state corresponds with the generator running.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.19.1.3.4 |
genSetCCDelayHow long (in seconds) to wait for the generator to indicate itself as running after engaging the generator-starting mechanism.rw Integer32 .1.3.6.1.4.1.3052.23.2.19.1.3.5 |
genRun OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.19.2 |
genRunModeGenerator Exercising function main operating mode; set to INHIBIT to inhibit exercising the generator.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.19.2.1 |
genRunSchedSchedule number(s) which govern(s) when Generator Exercising function runs.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.19.2.2 |
genRunDurationNumber of seconds that generator should run, started when the generator needs to start by SCHEDULE or by being forced to start.rw Integer32 .1.3.6.1.4.1.3052.23.2.19.2.3 |
genRunForceWrite 1 to this to force the generator exercising to start. Always reads as 0.rw Integer32 .1.3.6.1.4.1.3052.23.2.19.2.4 |
genRunReqasmRequire ASM connectivity before starting the generator from a schedule.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.19.2.5 |
genRunStatusStatus of Generator Exercising function.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.19.2.6 |
genRunNonstartEvent OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.19.2.7 |
genRunNonstartEventEnableEnable generator non-start event.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.19.2.7.1 |
genRunNonstartEventActionsActions for generator non-start event.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.19.2.7.2 |
genRunNonstartEventTrapTrap number for generator non-start event.rw Integer32 .1.3.6.1.4.1.3052.23.2.19.2.7.3 |
genRunNonstartEventClassClass (severity) for generator non-start event.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.19.2.7.4 |
calendar OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.2.20 |
schedTableTable of schedules SEQUENCE OF ScheduleConfig .1.3.6.1.4.1.3052.23.2.20.1 |
schedEntryEntry for table of schedules. ScheduleConfig .1.3.6.1.4.1.3052.23.2.20.1.1 |
schedIndexIndex for table of schedules.ro Integer32 .1.3.6.1.4.1.3052.23.2.20.1.1.1 |
schedEnableEnable this schedule.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.20.1.1.2 |
schedStartThis is of the form 'mm/dd/yy hh:mm:ss'. This controls on which date/time the schedule starts.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.20.1.1.3 |
schedRepeatModeControls in which way the schedule should repeat.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.20.1.1.4 |
schedRepeatFreqControls how often the schedule should repeat: every nth day, week, month, or year.rw Integer32 .1.3.6.1.4.1.3052.23.2.20.1.1.5 |
schedRepeatEndModeControls how the repeating schedule should end.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.20.1.1.6 |
schedRepeatEndAfterNumber of times this schedule should be repeated; relevant when the repeat end mode is AFTER.rw Integer32 .1.3.6.1.4.1.3052.23.2.20.1.1.7 |
schedRepeatEndOnDate/time (in the form 'mm/yy/dd hh:mm:ss' or blank string) after which repeating should end, relevant when repeat end mode is ON DATE.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.20.1.1.8 |
schedRepeatWeeklySunRun this schedule on Sunday(s); relevant when repeat mode is weekly.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.20.1.1.9 |
schedRepeatWeeklyMonRun this schedule on Monday(s); relevant when repeat mode is weekly.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.20.1.1.10 |
schedRepeatWeeklyTueRun this schedule on Tuesday(s); relevant when repeat mode is weekly.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.20.1.1.11 |
schedRepeatWeeklyWedRun this schedule on Wednesday(s); relevant when repeat mode is weekly.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.20.1.1.12 |
schedRepeatWeeklyThuRun this schedule on Thursday(s); relevant when repeat mode is weekly.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.20.1.1.13 |
schedRepeatWeeklyFriRun this schedule on Friday(s); relevant when repeat mode is weekly.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.20.1.1.14 |
schedRepeatWeeklySatRun this schedule on Saturday(s); relevant when repeat mode is weekly.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.20.1.1.15 |
schedRepeatMonthlyModeEACH means the schedule runs on specific dates of the month. ON THE means the schedule runs on calculated dates of the month according to which day that month starts.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.20.1.1.16 |
schedRepeatMonthlyDatesComma-separated list of dates of a month on which this schedule should run, relevant when repeat monthly mode is EACH.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.20.1.1.17 |
schedRepeatMonthlyOnTheControls on which day of the month this schedule should run, relevant when repeat monthly mode is ON THE.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.20.1.1.18 |
schedRepeatMonthlyOnDayControls the day of week on which this schedule is run, relevant when repeat monthly mode is ON THErw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.20.1.1.19 |
schedRepeatYearlyJanRun this schedule in January, relevant when repeat mode is YEARLY.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.20.1.1.20 |
schedRepeatYearlyFebRun this schedule in February, relevant when repeat mode is YEARLY.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.20.1.1.21 |
schedRepeatYearlyMarRun this schedule in March, relevant when repeat mode is YEARLY.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.20.1.1.22 |
schedRepeatYearlyAprRun this schedule in April, relevant when repeat mode is YEARLY.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.20.1.1.23 |
schedRepeatYearlyMayRun this schedule in May, relevant when repeat mode is YEARLY.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.20.1.1.24 |
schedRepeatYearlyJunRun this schedule in June, relevant when repeat mode is YEARLY.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.20.1.1.25 |
schedRepeatYearlyJulRun this schedule in July, relevant when repeat mode is YEARLY.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.20.1.1.26 |
schedRepeatYearlyAugRun this schedule in August, relevant when repeat mode is YEARLY.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.20.1.1.27 |
schedRepeatYearlySepRun this schedule in September, relevant when repeat mode is YEARLY.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.20.1.1.28 |
schedRepeatYearlyOctRun this schedule in October, relevant when repeat mode is YEARLY.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.20.1.1.29 |
schedRepeatYearlyNovRun this schedule in November, relevant when repeat mode is YEARLY.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.20.1.1.30 |
schedRepeatYearlyDecRun this schedule in December, relevant when repeat mode is YEARLY.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.20.1.1.31 |
schedRepeatYearlyOnTheControls on which day of the month this schedule should run, relevant when repeat mode is YEARLY.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.20.1.1.32 |
schedRepeatYearlyOnDayControls the day of week on which this schedule is run, relevant when repeat mode is YEARLY.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.20.1.1.33 |
schedNextTriggerWhen this schedule will next trigger.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.2.20.1.1.34 |
productIds OBJECT IDENTIFIER .1.3.6.1.4.1.3052.23.3 |
siteNameSite Name string; Max 40 characters.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.3.1 |
thisProductThis is a factory configured string for the product name.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.3.2 |
stockTrapStringThe message defined for the event that triggers a trap.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.3.3 |
trapEventTypeNumberThe user-defined trap variable for the type of event that happened. Definitions: 4 Scheduled 7 Serial Handshaking Low 8 Serial Handshaking High 10 Contact Closure Active 11 Contact Closure Inactive 12 Temperature High 13 Temperature Very High 14 Temperature Low 15 Temperature Very Low 16 Temperature Return to Normal 17 Humidity High 18 Humidity Very High 19 Humidity Low 20 Humidity Very Low 21 Humidity Return to Normal 26 Analog High 27 Analog Very High 28 Analog Low 29 Analog Very Low 30 Analog Normal 40 EventSensor Unresponsive 41 Custom 42 CPE Down 44 CPE Normal 49 Fuel Sensor Disconnect 50 Fuel Sensor Disconnect Return to Normal 56 Fuel Sensor 57 AC Power Monitor Average Voltage Very Low 58 AC Power Monitor Average Voltage Low 59 AC Power Monitor Average Voltage Return to Normal 60 AC Power Monitor Average Voltage High 61 AC Power Monitor Average Voltage Very High 62 AC Power Monitor Average Current Very Low 63 AC Power Monitor Average Current Low 64 AC Power Monitor Average Current Return to Normal 65 AC Power Monitor Average Current High 66 AC Power Monitor Average Current Very High 67 AC Power Monitor Frequency Very Low 68 AC Power Monitor Frequency Low 69 AC Power Monitor Frequency Return to Normal 70 AC Power Monitor Frequency High 71 AC Power Monitor Frequency Very High 72 AC Power Monitor Total Real Power Very Low 73 AC Power Monitor Total Real Power Low 74 AC Power Monitor Total Real Power Return to Normal 75 AC Power Monitor Total Real Power High 76 AC Power Monitor Total Real Power Very High 77 AC Power Monitor Disconnect 78 AC Power Monitor Disconnect Return to Normal 81 Fuel Sensor Volume Sudden Change 82 Fuel Sensor Volume Slow Change 83 CPE Down Reminder 84 AC Power Monitor Total Power Factor Very Low 85 AC Power Monitor Total Power Factor Low 86 AC Power Monitor Total Power Factor Return to Normal 100 Contact Closure Active Reminder 101 Temperature High Reminder 102 Temperature High Very Reminder 103 Temperature Low Reminder 104 Temperature Very Low Reminder 105 Humidity High Reminder 106 Humidity Very High Reminder 107 Humidity Low Reminder 108 Humidity Very Low Reminder 109 Analog High Reminder 110 Analog Very High Reminder 111 Analog Low Reminder 112 Analog Very Low Reminder 130 Relay Output Active 131 Relay Output Inactive 132 Power Output On 133 Power Output Off 161 Camera 164 Reset 166 Fuel Sensor Levels Auto Adjustro Integer32 .1.3.6.1.4.1.3052.23.3.4 |
trapEventTypeNameThe user-defined trap variable for the string corresponding to the event type.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.3.5 |
trapIncludedValueThe user-defined trap variable for the generic included value.ro Integer32 (-2147483648..2147483647) .1.3.6.1.4.1.3052.23.3.6 |
trapIncludedStringThe user-defined trap variable for the generic included string.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.3.7 |
trapTypeStringThe cause of the trap, added for DL880 compatibility.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.3.8 |
trapEventClassNumberThe user-defined trap variable for the configurable class number associated with the triggering event.ro Integer32 .1.3.6.1.4.1.3052.23.3.9 |
trapEventClassNameThe user-defined trap variable for the configurable class name associated with the class number.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.3.10 |
keyInterfaceThis object represents a setting key interface. When setting this object, the value to set is the 'sk' command you would enter on the command line (without the 'sk'). To get the result of the operation, read this object after you write it. For example, to configure EventSensor 1 contact closure 34 event actions to be an SNMP InformRequest to host foo, set this object to: 'event.sensor[1].cc[34].eventactions=inform(foo)'. The SNMP response is the result of the operation: if setting that key to that value was a success then the SNMP response will be a success and the response value will be what you had set. If you subsequently read this object then you will see a message 'OK: ...'. If setting that key to that value failed then the SNMP response will be a failure (a badValue response). If you subsequently read this object then the value returned is the reason that setting that key to that value failed. For another example, to read user 3's pass-through access for port 7, set this object to: 'sec.user[3].port[7].ptaccess'. The SNMP response is the result of the operation: if reading that key is a success then the SNMP response will be a success and the response value will be what you had SET (i.e., the opertion of reading a key, which is just the key itself with no '=' operator, and this is not the key value you want to read). If you subsequently read this object then the value returned is the value of the key you want to read. If reading that key failed (e.g., if the key is invalid) then the SNMP response to your SNMP set operation (the value you set being the invalid key to read) will be a failure (a badValue response). If you subsequently read this object then the value returned is the reason that reading that key failed (i.e., 'invalid key').rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.3052.23.4 |