RITTAL-CMC-TC-MIB
AI MIB Summary
Standard SNMP MIB module defining data structures for RITTAL-CMC-TC-MIB.
271
Objects
Active
Status
4
Dependencies
Imported Objects
Objects
271 total| Object Name |
|---|
rittal OBJECT IDENTIFIER .1.3.6.1.4.1.2606 |
RFC1213-MIB Unknown .1.3.6.1.4.1.2606 |
cmcTc OBJECT IDENTIFIER .1.3.6.1.4.1.2606.4 |
alarmSensorUnit1Alarm of sensor unit 1 TRAP-TYPE .1.3.6.1.4.1.2606.4.0.1 |
alarmSensorUnit2Alarm of sensor unit 2 TRAP-TYPE .1.3.6.1.4.1.2606.4.0.2 |
alarmSensorUnit3Alarm of sensor unit 3 TRAP-TYPE .1.3.6.1.4.1.2606.4.0.3 |
alarmSensorUnit4Alarm of sensor unit 4 TRAP-TYPE .1.3.6.1.4.1.2606.4.0.4 |
alarmUnit1Alarm of unit 1 TRAP-TYPE .1.3.6.1.4.1.2606.4.0.5 |
alarmUnit2Alarm of unit 2 TRAP-TYPE .1.3.6.1.4.1.2606.4.0.6 |
alarmUnit3Alarm of unit 3 TRAP-TYPE .1.3.6.1.4.1.2606.4.0.7 |
alarmUnit4Alarm of unit 4 TRAP-TYPE .1.3.6.1.4.1.2606.4.0.8 |
alarmValuesAlarm of values measured by external card TRAP-TYPE .1.3.6.1.4.1.2606.4.0.9 |
configChangedThe configuration of the cmc has changed,
this trap is send if new setup is saved.
Configuration can be changed by Terminal, Telnet, Web or SNMP
*** NOT IMPLEMENTED *** TRAP-TYPE .1.3.6.1.4.1.2606.4.0.10 |
cmcTcMibRev OBJECT IDENTIFIER .1.3.6.1.4.1.2606.4.1 |
cmcTcMibMajRevThe Major Revision level.
A change in the major revision level represents a major change
in the architecture of the MIB. A change in the major revision
level may indicate a significant change in the information,
correct interpretation of data may require a MIB document
with the same major revision level.ro INTEGER .1.3.6.1.4.1.2606.4.1.1 |
cmcTcMibMinRevThe Minor Revision level.
A change in the minor revision level may represent some minor
additional support, no changes to any pre-existing information
has occurred.ro INTEGER .1.3.6.1.4.1.2606.4.1.2 |
cmcTcMibConditionThe overall condition (status) of the system represented by
this MIB.
(2) OK
(3) a minor problem, warning condition (yellow LED on CMC)
(4) a major problem (red LED on CMC)
(5) configuration of sensor units changed or
unit detected (red/yellow/green LED on CMC)ro Enumeration .1.3.6.1.4.1.2606.4.1.3 |
cmcTcStatus OBJECT IDENTIFIER .1.3.6.1.4.1.2606.4.2 |
cmcTcStatusDeviceCMCGeneral Status of CMC-TC unit itself
(1) failed
(2) OKro Enumeration .1.3.6.1.4.1.2606.4.2.1 |
cmcTcUnitsConnectedNumber of sensor units connected to the CMC, Port 1 to 4ro INTEGER .1.3.6.1.4.1.2606.4.2.2 |
cmcTcStatusSensorUnit1 OBJECT IDENTIFIER .1.3.6.1.4.1.2606.4.2.3 |
cmcTcUnit1TypeOfDeviceType of sensor unit connected to port 1ro Enumeration .1.3.6.1.4.1.2606.4.2.3.1 |
cmcTcUnit1TextDescriptional text for sensor unit connected to port 1rw DisplayString .1.3.6.1.4.1.2606.4.2.3.2 |
cmcTcUnit1SerialSerialnumber of sensor unit connected to port 1ro INTEGER .1.3.6.1.4.1.2606.4.2.3.3 |
cmcTcUnit1StatusGeneral Status sensor unit connected to port 1
(1) OK
(2) error, e. g. value overflow
(3) configuration of sensor unit has changed, confirmation required
(4) Quit from sensor unit to confirm configuration changes
(5) timeout of sensor unit, confirmation required to unload this unit
(6) sensor unit detected, needs to be confirmed
(7) unit is not available
(8) supply voltage is too low
(9) Firmware upgrade runningro Enumeration .1.3.6.1.4.1.2606.4.2.3.4 |
cmcTcStatusUnit1Sensors OBJECT IDENTIFIER .1.3.6.1.4.1.2606.4.2.3.5 |
cmcTcUnit1NumberOfSensorsNumber of sensors connected to sensor unit 1ro INTEGER .1.3.6.1.4.1.2606.4.2.3.5.1 |
cmcTcUnit1SensorTableHeadline of sensor table SEQUENCE OF CmcTcUnit1SensorEntry .1.3.6.1.4.1.2606.4.2.3.5.2 |
cmcTcUnit1SensorEntryEntries of sensor table CmcTcUnit1SensorEntry .1.3.6.1.4.1.2606.4.2.3.5.2.1 |
unit1SensorIndexIndex for the list of value entries. Its value ranges
between 1 and the value of cmcTcUnit1NumberOfSensors.ro INTEGER .1.3.6.1.4.1.2606.4.2.3.5.2.1.1 |
unit1SensorTypeType of sensor which is connected to sensor unit 1 to sensor[unit1SensorIndex]
1: no sensor connected
2: sensor failure
3: value overflow
4: sensor type 1, access sensor
5: sensor type 2, vibration sensor
6: sensor type 3, motion sensor
7: sensor type 4, smoke sensor
8: sensor type 5, air flow sensor
9: sensor type 6, reserved
10: sensor type 7, temperature sensor
11: sensor type 8, 4..20mA sensor
12: sensor type 9, humidity sensor
13: user sensor with normally opened contact
14: user sensor with normally closed contact
15: door locked sensor from locking device
16: remote unlock sensor (e.g. external keypad)
17: voltage sensor, indicates status of main voltage (OK, NOK)
18: voltage value
19: fan status, from CMC-TC-FAS-Unit
20: cardreader or keypad, connected to I2C port
21: duty cycle of fan, FCS-Unit
22: status of fan, FCS-Unit
23: leakage sensor
24: warning, RittalTopTherm(RTT)-Unit
25: alarm, RittalTopTherm-Unit
26: temperature difference filter monitor, RTT-Unit
27: heatflow RCT-Unit
28: alarm RCT-Unit
29: warning RCT-Unit
30: actual current*10, PSM-Unit
31: status PSM-Unit
32: position PSM-Unit, normal/reversed = circuit 1/2
33: air Flap
34: acoustic sensor
35: DET-AC fault (extinguisher)
36: DET-AC first alarm (extinguisher)
37: DET-AC main alarm (extinguisher)
38: DRC: RFID Tag
40-47: RPM Fan 1.1 - Fan 4.2, LCP
48-55: Air temperature 1.1 - 4.2, LCP
56,57: actual temperature 1,2, LCP
58: water inlet temperature, LCP
59: water outlet temperature, LCP
60: water flow
61: fan speed (desired value)
62: status valve, LCP
63: status LCP
64: temperature difference water temperatures
65: control temperature 1, LCP
66: control temperature 2, LCP
67: condensate pump, duration, LCP
68: condensate pump, cycles, LCP
72: total energy*10 (kWh), PSM
73: total power*10 (kW), PSM
74: frequency*10 (Hz), PSM
75: voltage*10 (V), PSM
76: voltage status, PSM
77: current*10 (A), PSM
78: current status, PSM
79: power*10 (kW) per phase, PSM
80: energy*10 (kWh) per phase, PSM
81: temporary energy*10 (kWh) per phase, PSM
100: temperature sensor, wireless
101: temperature sensor (combi), wireless
102: humidity sensor, wireless
103: access sensor, wireless
104: user sensor with normally opened contact, wireless
105: user sensor with normally closed contact, wireless
106: analog sensor 4..20mA, wirelessro Enumeration .1.3.6.1.4.1.2606.4.2.3.5.2.1.2 |
unit1SensorTextDescriptional text for each sensor (entry in the table)rw DisplayString .1.3.6.1.4.1.2606.4.2.3.5.2.1.3 |
unit1SensorStatusActual status of the sensorro Enumeration .1.3.6.1.4.1.2606.4.2.3.5.2.1.4 |
unit1SensorValueValue of sensorro INTEGER .1.3.6.1.4.1.2606.4.2.3.5.2.1.5 |
unit1SensorSetHighValue for high setpoint of sensorrw INTEGER .1.3.6.1.4.1.2606.4.2.3.5.2.1.6 |
unit1SensorSetLowValue for low setpoint of sensor,
also used as alarm delayrw INTEGER .1.3.6.1.4.1.2606.4.2.3.5.2.1.7 |
unit1SensorSetWarnValue for warning setpoint of sensor,
also used as fan thresholdrw INTEGER .1.3.6.1.4.1.2606.4.2.3.5.2.1.8 |
unit1SensorHysteresis% -Value for hysteresis for High, Low and Warning,
input in % from actual setpointrw INTEGER .1.3.6.1.4.1.2606.4.2.3.5.2.1.9 |
unit1SensorDisplayFactorFactor of sensor value and setpoints,
devide actual value with this value,
e. g. factor = 10: sensor value = 100, actual value = 10.0ro INTEGER .1.3.6.1.4.1.2606.4.2.3.5.2.1.10 |
unit1SensorScaleStartValue for start value for scaling of 0..100% (4..20mA) sensor,
example: acutal range of value of 4..20mA sensor is from 10 to 60A,
then this variable is set to 10,
also valid for setpointsrw INTEGER .1.3.6.1.4.1.2606.4.2.3.5.2.1.11 |
unit1SensorScaleEndValue for end value for scaling of 0..100% (4..20mA) sensor,
example: acutal range of value of 4..20mA sensor is from 10 to 60A,
then this variable is set to 60,
also valid for setpointsrw INTEGER .1.3.6.1.4.1.2606.4.2.3.5.2.1.12 |
unit1SensorUnitUnit for 0..100% (4..20mA) sensor,
example: acutal range of value of 4..20mA sensor is from 10 to 60A,
then this variable is set to 'A'rw DisplayString .1.3.6.1.4.1.2606.4.2.3.5.2.1.13 |
unit1SensorInfoAdditional information to the sensor,
e. g. Serialnumber, Signal Quality..ro DisplayString .1.3.6.1.4.1.2606.4.2.3.5.2.1.14 |
cmcTcStatusUnit1Outputs OBJECT IDENTIFIER .1.3.6.1.4.1.2606.4.2.3.6 |
cmcTcUnit1NumberOfOutputsNumber of outputs available on sensor unit 1ro INTEGER .1.3.6.1.4.1.2606.4.2.3.6.1 |
cmcTcUnit1OutputTableHeadline of output table SEQUENCE OF CmcTcUnit1OutputEntry .1.3.6.1.4.1.2606.4.2.3.6.2 |
cmcTcUnit1OutputEntryEntries of output table CmcTcUnit1OutputEntry .1.3.6.1.4.1.2606.4.2.3.6.2.1 |
unit1OutputIndexIndex for the list of output entries. Its value ranges
between 1 and the value of cmcTcUnit1NumberOfOutputs.ro INTEGER .1.3.6.1.4.1.2606.4.2.3.6.2.1.1 |
unit1OutputTypeType of output which is connected to sensor unit 1 to output[unit1OutputIndex]
1: no output connected
2: output failure
3: value overflow
4: output type 1, door locking TS8,Ergoform
5: output type 2, universal lock 1, lock with power
6: output type 3, universal lock 2, unlock with power
7: output type 4, fan relay
8: output type 5, fan controlled
9: output type 6, universal relay output
10: output type 7, room door lock
11: output type 8, power output
12: output type 9, door lock with Master key
13: output type 10, door lock FR(i)
14: setpoint (FCS, LCP)
15: setpoint temperature monitoring (LCP)
16: hysteresis of setpoint (LCP)
17: command for remote control of RCT
18: relay PSM, 1=On, 0=Off
19: high setpoint current monitoring PSM
20: low setpoint current monitoring PSM
21: setpoint temperature RTT
22: setpoint temperature monitoring RTT
23: power output 20A
24: door magnet (automatic door release)
30: control mode, LCP
31: min fan speed (fan control), LCP
32: min delta T (fan control), LCP
33: max delta T (fan control), LCP
34: PID controller, KP, LCP
35: PID controller, KI, LCP
36 PID controller, KD, LCP
37 flowrate flowmeter, LCP
38: cw value of water (default: 4187), LCP
39: deltaT, LCP
40: control mode, LCP
42: setpoint high voltage PSM
43: setpoint low voltage PSM
44: setpoint high current PSM
45: setpoint low current PSM
46: command PSMro Enumeration .1.3.6.1.4.1.2606.4.2.3.6.2.1.2 |
unit1OutputTextDescriptional text for each output (entry in the table)rw DisplayString .1.3.6.1.4.1.2606.4.2.3.6.2.1.3 |
unit1OutputStatusActual status of the outputrw Enumeration .1.3.6.1.4.1.2606.4.2.3.6.2.1.4 |
unit1OutputValueValue for outputrw INTEGER .1.3.6.1.4.1.2606.4.2.3.6.2.1.5 |
unit1OutputSetCommand for outputrw Enumeration .1.3.6.1.4.1.2606.4.2.3.6.2.1.6 |
unit1OutputConfigConfiguration for output
1: disable remote control (e.g. keypad)
2: enable remote controlrw Enumeration .1.3.6.1.4.1.2606.4.2.3.6.2.1.7 |
unit1OutputDelayUnsigned Value for delay,
after this time the output will fall into the previous staterw INTEGER .1.3.6.1.4.1.2606.4.2.3.6.2.1.8 |
unit1OutputTimeoutActionState for output if timeout (RS422) occursrw Enumeration .1.3.6.1.4.1.2606.4.2.3.6.2.1.9 |
cmcTcStatusUnit1Msg OBJECT IDENTIFIER .1.3.6.1.4.1.2606.4.2.3.7 |
cmcTcUnit1NumberOfMsgsNumber of messages that can be created with sensor unit 1ro INTEGER .1.3.6.1.4.1.2606.4.2.3.7.1 |
cmcTcUnit1MsgTableHeadline of message table SEQUENCE OF CmcTcUnit1MsgEntry .1.3.6.1.4.1.2606.4.2.3.7.2 |
cmcTcUnit1MsgEntryEntries of message table CmcTcUnit1MsgEntry .1.3.6.1.4.1.2606.4.2.3.7.2.1 |
unit1MsgIndexIndex for the list of message entries. Its value ranges
between 1 and the value of cmcTcUnit1NumberOfMsgs.ro INTEGER .1.3.6.1.4.1.2606.4.2.3.7.2.1.1 |
unit1MsgTextDescriptional text for each message (entry in the table)rw DisplayString .1.3.6.1.4.1.2606.4.2.3.7.2.1.2 |
unit1MsgStatusActual message status
1: not available
2: configuration has changed (sensor new, changed, lost)
3: error
4: OK
5: alarm, e.g. smoke, vibration...
6: warning of analog value, value reached warning threshold
7: analog value too low, value reached low threshold
8: analog value too high, value reached high threshold
9: output is set to OFF
10: output is set to ON
11: door is open
12: door is closed
13: door is locked
14: door is unlocked by remote input, e.g. external cardreader
15: door is unlocked by reader or keypad connected to I2C
16: door is unlocked by SNMP set command (unit1OutputSet)
17: door is unlocked by WEB
18: door is unlocked by timer
19: no access, wrong keycode or cardnumber
20: orientation of PSM-Unit is circuit 1
21: orientation of PSM-Unit is circuit 2
22: battery low, wireless sensorro Enumeration .1.3.6.1.4.1.2606.4.2.3.7.2.1.3 |
unit1MsgRelaySetup of Alarm relay for this message/alarm
1: no switching of alarm relay
2: switching of alarm relayrw Enumeration .1.3.6.1.4.1.2606.4.2.3.7.2.1.4 |
unit1MsgBeeperSetup of Alarm beeper for this alarm
1: no audible alarm
2: audible alarmrw Enumeration .1.3.6.1.4.1.2606.4.2.3.7.2.1.5 |
unit1MsgTrap1Trap receiver 1 activatedrw Enumeration .1.3.6.1.4.1.2606.4.2.3.7.2.1.6 |
unit1MsgTrap2Trap receiver 2 activatedrw Enumeration .1.3.6.1.4.1.2606.4.2.3.7.2.1.7 |
unit1MsgTrap3Trap receiver 3 activatedrw Enumeration .1.3.6.1.4.1.2606.4.2.3.7.2.1.8 |
unit1MsgTrap4Trap receiver 4 and Event Logging activatedrw Enumeration .1.3.6.1.4.1.2606.4.2.3.7.2.1.9 |
unit1MsgQuitReset of this alarm
1: auto
2: manual, alarm needs confirmation, e. g. with 'C' keyrw Enumeration .1.3.6.1.4.1.2606.4.2.3.7.2.1.10 |
unit1MsgDelayDelay of alarm conditionrw INTEGER .1.3.6.1.4.1.2606.4.2.3.7.2.1.11 |
cmcTcStatusSensorUnit2 OBJECT IDENTIFIER .1.3.6.1.4.1.2606.4.2.4 |
cmcTcUnit2TypeOfDeviceType of sensor unit connected to port 2ro Enumeration .1.3.6.1.4.1.2606.4.2.4.1 |
cmcTcUnit2TextDescriptional text for sensor unit connected to port 2rw DisplayString .1.3.6.1.4.1.2606.4.2.4.2 |
cmcTcUnit2SerialSerialnumber of sensor unit connected to port 2ro INTEGER .1.3.6.1.4.1.2606.4.2.4.3 |
cmcTcUnit2StatusGeneral Status sensor unit connected to port 2
(1) OK
(2) error
(3) configuration of sensor unit has changed, confirmation required
(4) Quit from sensor unit to confirm configuration changes
(5) timeout of sensor unit, confirmation required
(6) sensor unit detected, needs to be confirmed
(8) supply voltage is too low
(9) Firmware upgrade runningro Enumeration .1.3.6.1.4.1.2606.4.2.4.4 |
cmcTcStatusUnit2Sensors OBJECT IDENTIFIER .1.3.6.1.4.1.2606.4.2.4.5 |
cmcTcUnit2NumberOfSensorsNumber of sensors connected to sensor unit 2ro INTEGER .1.3.6.1.4.1.2606.4.2.4.5.1 |
cmcTcUnit2SensorTableHeadline of sensor table SEQUENCE OF CmcTcUnit2SensorEntry .1.3.6.1.4.1.2606.4.2.4.5.2 |
cmcTcUnit2SensorEntryEntries of sensor table CmcTcUnit2SensorEntry .1.3.6.1.4.1.2606.4.2.4.5.2.1 |
unit2SensorIndexIndex for the list of value entries. Its value ranges
between 1 and the value of cmcTcUnit2NumberOfSensors.ro INTEGER .1.3.6.1.4.1.2606.4.2.4.5.2.1.1 |
unit2SensorTypeType of sensor which is connected to sensor unit 2 to sensor[unit2SensorIndex]
1: no sensor connected
2: sensor failure
3: value overflow
4: sensor type 1, access sensor
5: sensor type 2, vibration sensor
6: sensor type 3, motion sensor
7: sensor type 4, smoke sensor
8: sensor type 5, air flow sensor
9: sensor type 6, reserved
10: sensor type 7, temperature sensor
11: sensor type 8, 4..20mA sensor
12: sensor type 9, humidity sensor
13: user sensor with normally opened contact
14: user sensor with normally closed contact
15: door locked sensor from locking device
16: remote unlock sensor (e.g. external keypad)
17: voltage sensor, indicates status of main voltage
18: voltage value
19: fan status
20: cardreader or keypad, connected to I2C port
21: duty cycle of fan, FCS-Unit
22: status of fan, FCS-Unit
23: leakage sensor
24: warning, RittalTopTherm(RTT)-Unit
25: alarm, RittalTopTherm-Unit
26: temperature difference filter monitor, RTT-Unit
27: heatflow RCT-Unit
28: alarm RCT-Unit
29: warning RCT-Unit
30: actual current*10, PSM-Unit
31: status PSM-Unit
32: position PSM-Unit, normal/reversed = circuit 1/2
33: air Flap
34: acoustic sensor
35: DET-AC fault (extinguisher)
36: DET-AC first alarm (extinguisher)
37: DET-AC main alarm (extinguisher)
38: DRC: RFID Tag
40-47: RPM Fan 1.1 - Fan 4.2, LCP
48-55: Air temperature 1.1 - 4.2, LCP
56,57: actual temperature 1,2, LCP
58: water inlet temperature, LCP
59: water outlet temperature, LCP
60: water flow
61: fan speed (desired value)
62: status valve, LCP
63: status LCP
64: temperature difference water temperatures
65: control temperature 1, LCP
66: control temperature 2, LCP
67: condensate pump, duration, LCP
68: condensate pump, cycles, LCP
72: total energy*10 (kWh), PSM
73: total power*10 (kW), PSM
74: frequency*10 (Hz), PSM
75: voltage*10 (V), PSM
76: voltage status, PSM
77: current*10 (A), PSM
78: current status, PSM
79: power*10 (kW) per phase, PSM
80: energy*10 (kWh) per phase, PSM
81: temporary energy*10 (kWh) per phase, PSM
100: temperature sensor, wireless
101: temperature sensor (combi), wireless
102: humidity sensor, wireless
103: access sensor, wireless
104: user sensor with normally opened contact, wireless
105: user sensor with normally closed contact, wireless
106: analog sensor 4..20mA, wirelessro Enumeration .1.3.6.1.4.1.2606.4.2.4.5.2.1.2 |
unit2SensorTextDescriptional text for each sensor (entry in the table)rw DisplayString .1.3.6.1.4.1.2606.4.2.4.5.2.1.3 |
unit2SensorStatusActual status of the sensorro Enumeration .1.3.6.1.4.1.2606.4.2.4.5.2.1.4 |
unit2SensorValueValue of sensorro INTEGER .1.3.6.1.4.1.2606.4.2.4.5.2.1.5 |
unit2SensorSetHighValue for high setpoint of sensorrw INTEGER .1.3.6.1.4.1.2606.4.2.4.5.2.1.6 |
unit2SensorSetLowValue for low setpoint of sensor,
also used as alarm delayrw INTEGER .1.3.6.1.4.1.2606.4.2.4.5.2.1.7 |
unit2SensorSetWarnValue for warning setpoint of sensor,
also used as fan thresholdrw INTEGER .1.3.6.1.4.1.2606.4.2.4.5.2.1.8 |
unit2SensorHysteresis% -Value for hysteresis for High, Low and Warning,
input in % from actual setpointrw INTEGER .1.3.6.1.4.1.2606.4.2.4.5.2.1.9 |
unit2SensorDisplayFactorFactor of sensor value and setpoints,
devide actual value with this value,
e. g. factor = 10: sensor value = 100, actual value = 10.0ro INTEGER .1.3.6.1.4.1.2606.4.2.4.5.2.1.10 |
unit2SensorScaleStartValue for start value for scaling of 0..100% (4..20mA) sensor,
example: acutal range of value of 4..20mA sensor is from 10 to 60A,
then this variable is set to 10,
also valid for setpointsrw INTEGER .1.3.6.1.4.1.2606.4.2.4.5.2.1.11 |
unit2SensorScaleEndValue for end value for scaling of 0..100% (4..20mA) sensor,
example: acutal range of value of 4..20mA sensor is from 10 to 60A,
then this variable is set to 60,
also valid for setpointsrw INTEGER .1.3.6.1.4.1.2606.4.2.4.5.2.1.12 |
unit2SensorUnitUnit for 0..100% (4..20mA) sensor,
example: acutal range of value of 4..20mA sensor is from 10 to 60A,
then this variable is set to 'A'rw DisplayString .1.3.6.1.4.1.2606.4.2.4.5.2.1.13 |
unit2SensorInfoAdditional information to the sensor,
e. g. Serialnumber, Signal Quality..ro DisplayString .1.3.6.1.4.1.2606.4.2.4.5.2.1.14 |
cmcTcStatusUnit2Outputs OBJECT IDENTIFIER .1.3.6.1.4.1.2606.4.2.4.6 |
cmcTcUnit2NumberOfOutputsNumber of outputs available on sensor unit 2ro INTEGER .1.3.6.1.4.1.2606.4.2.4.6.1 |
cmcTcUnit2OutputTableHeadline of output table SEQUENCE OF CmcTcUnit2OutputEntry .1.3.6.1.4.1.2606.4.2.4.6.2 |
cmcTcUnit2OutputEntryEntries of output table CmcTcUnit2OutputEntry .1.3.6.1.4.1.2606.4.2.4.6.2.1 |
unit2OutputIndexIndex for the list of output entries. Its value ranges
between 1 and the value of cmcTcUnit2NumberOfOutputs.ro INTEGER .1.3.6.1.4.1.2606.4.2.4.6.2.1.1 |
unit2OutputTypeType of output which is connected to sensor unit 2 to output[unit2OutputIndex]
1: no output connected
2: output failure
3: value overflow
4: output type 1, door locking TS8,Ergoform
5: output type 2, universal lock 1, lock with power
6: output type 3, universal lock 2, unlock with power
7: output type 4, fan relay
8: output type 5, fan controlled
9: output type 6, universal relay output
10: output type 7, room door lock
11: output type 8, power output
12: output type 9, door lock with Master key
13: output type 10, door lock FR(i)
14: setpoint (FCS, RTT)
15: setpoint temperature monitoring (RTT)
16: hysteresis of setpoint (RCT)
17: command for remote control of RCT
18: relay PSM, 1=On, 0=Off
19: high setpoint current monitoring PSM
20: low setpoint current monitoring PSM
21: setpoint temperature RTT
22: setpoint temperature monitoring RTT
23: power output 20A
24: door magnet (automatic door release)
30: control mode LCP
31: min fan speed (fan control) LCP
32: min delta T (fan control) LCP
33: max delta T (fan control) LCP
34: PID controller, KP, LCP
35: PID controller, KI, LCP
36 PID controller, KD, LCP
37 flowrate flowmeter, LCP
38: cw value of water (default: 4187) LCP
39: deltaT, LCP
40: control mode, LCP
42: setpoint high voltage PSM
43: setpoint low voltage PSM
44: setpoint high current PSM
45: setpoint low current PSM
46: command PSMro Enumeration .1.3.6.1.4.1.2606.4.2.4.6.2.1.2 |
unit2OutputTextDescriptional text for each output (entry in the table)rw DisplayString .1.3.6.1.4.1.2606.4.2.4.6.2.1.3 |
unit2OutputStatusActual status of the outputrw Enumeration .1.3.6.1.4.1.2606.4.2.4.6.2.1.4 |
unit2OutputValueSigned value for outputrw INTEGER .1.3.6.1.4.1.2606.4.2.4.6.2.1.5 |
unit2OutputSetCommand for outputrw Enumeration .1.3.6.1.4.1.2606.4.2.4.6.2.1.6 |
unit2OutputConfigConfiguration for output
1: disable remote control (e.g. keypad)
2: enable remote controlrw Enumeration .1.3.6.1.4.1.2606.4.2.4.6.2.1.7 |
unit2OutputDelayUnsigned Value for delay,
after this time the output will fall into the previous staterw INTEGER .1.3.6.1.4.1.2606.4.2.4.6.2.1.8 |
unit2OutputTimeoutActionState for output if timeout (RS422) occursrw Enumeration .1.3.6.1.4.1.2606.4.2.4.6.2.1.9 |
cmcTcStatusUnit2Msg OBJECT IDENTIFIER .1.3.6.1.4.1.2606.4.2.4.7 |
cmcTcUnit2NumberOfMsgsNumber of alarms that can be created with sensor unit 2ro INTEGER .1.3.6.1.4.1.2606.4.2.4.7.1 |
cmcTcUnit2MsgTableHeadline of message table SEQUENCE OF CmcTcUnit2MsgEntry .1.3.6.1.4.1.2606.4.2.4.7.2 |
cmcTcUnit2MsgEntryEntries of message table CmcTcUnit2MsgEntry .1.3.6.1.4.1.2606.4.2.4.7.2.1 |
unit2MsgIndexIndex for the list of alarm entries. Its value ranges
between 1 and the value of cmcTcUnit2NumberOfMsgs.ro INTEGER .1.3.6.1.4.1.2606.4.2.4.7.2.1.1 |
unit2MsgTextDescriptional text for each message (entry in the table)rw DisplayString .1.3.6.1.4.1.2606.4.2.4.7.2.1.2 |
unit2MsgStatusActual message status
1: not available
2: configuration has changed (sensor new, changed, lost)
3: error
4: OK
5: alarm, e.g. smoke, vibration...
6: warning of analog value, value reached warning threshold
7: analog value too low, value reached low threshold
8: analog value too high, value reached high threshold
9: output is set to OFF
10: output is set to ON
11: door is open
12: door is closed
13: door is locked
14: door is unlocked by remote input, e.g. external cardreader
15: door is unlocked by reader or keypad connected to I2C
16: door is unlocked by SNMP set command (unit1OutputSet)
17: door is unlocked by WEB
18: door is unlocked by timer
19: no access, wrong keycode or cardnumber
20: orientation of PSM-Unit is circuit 1
21: orientation of PSM-Unit is circuit 2
22: battery low, wireless sensorro Enumeration .1.3.6.1.4.1.2606.4.2.4.7.2.1.3 |
unit2MsgRelaySetup of Alarm relay for this alarm
2: no switching of alarm relay
1: switching of alarm relayrw Enumeration .1.3.6.1.4.1.2606.4.2.4.7.2.1.4 |
unit2MsgBeeperSetup of Alarm beeper for this alarm
2: no audible alarm
1: audible alarmrw Enumeration .1.3.6.1.4.1.2606.4.2.4.7.2.1.5 |
unit2MsgTrap1Trap receiver 1 activatedrw Enumeration .1.3.6.1.4.1.2606.4.2.4.7.2.1.6 |
unit2MsgTrap2Trap receiver 2 activatedrw Enumeration .1.3.6.1.4.1.2606.4.2.4.7.2.1.7 |
unit2MsgTrap3Trap receiver 3 activatedrw Enumeration .1.3.6.1.4.1.2606.4.2.4.7.2.1.8 |
unit2MsgTrap4Trap receiver 4 and Event Logging activatedrw Enumeration .1.3.6.1.4.1.2606.4.2.4.7.2.1.9 |
unit2MsgQuitReset of this alarm
1: auto
2: manual, alarm needs confirmation, e. g. with 'C' keyrw Enumeration .1.3.6.1.4.1.2606.4.2.4.7.2.1.10 |
unit2MsgDelayDelay of alarm conditionrw INTEGER .1.3.6.1.4.1.2606.4.2.4.7.2.1.11 |
cmcTcStatusSensorUnit3 OBJECT IDENTIFIER .1.3.6.1.4.1.2606.4.2.5 |
cmcTcUnit3TypeOfDeviceType of sensor unit connected to port 3ro Enumeration .1.3.6.1.4.1.2606.4.2.5.1 |
cmcTcUnit3TextDescriptional text for sensor unit connected to port 3rw DisplayString .1.3.6.1.4.1.2606.4.2.5.2 |
cmcTcUnit3SerialSerialnumber of sensor unit connected to port 3ro INTEGER .1.3.6.1.4.1.2606.4.2.5.3 |
cmcTcUnit3StatusGeneral Status sensor unit connected to port 3
(1) OK
(2) error, e. g. value overflow
(3) configuration of sensor unit has changed, confirmation required
(4) Quit from sensor unit to confirm configuration changes
(5) timeout of sensor unit, confirmation required to unload this unit
(6) sensor unit detected, needs to be confirmed
(7) unit is not available
(8) supply voltage is too low
(9) Firmware upgrade runningro Enumeration .1.3.6.1.4.1.2606.4.2.5.4 |
cmcTcStatusUnit3Sensors OBJECT IDENTIFIER .1.3.6.1.4.1.2606.4.2.5.5 |
cmcTcUnit3NumberOfSensorsNumber of sensors connected to sensor unit 3ro INTEGER .1.3.6.1.4.1.2606.4.2.5.5.1 |
cmcTcUnit3SensorTableHeadline of sensor table SEQUENCE OF CmcTcUnit3SensorEntry .1.3.6.1.4.1.2606.4.2.5.5.2 |
cmcTcUnit3SensorEntryEntries of sensor table CmcTcUnit3SensorEntry .1.3.6.1.4.1.2606.4.2.5.5.2.1 |
unit3SensorIndexIndex for the list of value entries. Its value ranges
between 1 and the value of cmcTcUnit3NumberOfSensors.ro INTEGER .1.3.6.1.4.1.2606.4.2.5.5.2.1.1 |
unit3SensorTypeType of sensor which is connected to sensor unit 3 to sensor[unit3SensorIndex]
1: no sensor connected
2: sensor failure
3: value overflow
4: sensor type 1, access sensor
5: sensor type 2, vibration sensor
6: sensor type 3, motion sensor
7: sensor type 4, smoke sensor
8: sensor type 5, air flow sensor
9: sensor type 6, reserved
10: sensor type 7, temperature sensor
11: sensor type 8, 4..20mA sensor
12: sensor type 9, humidity sensor
13: user sensor with normally opened contact
14: user sensor with normally closed contact
15: door locked sensor from locking device
16: remote unlock sensor (e.g. external keypad)
17: voltage sensor, indicates status of main voltage
18: voltage value
19: fan status
20: cardreader or keypad, connected to I2C port
21: duty cycle of fan, FCS-Unit
22: status of fan, FCS-Unit
23: leakage sensor
24: warning, RittalTopTherm(RTT)-Unit
25: alarm, RittalTopTherm-Unit
26: temperature difference filter monitor, RTT-Unit
27: heatflow RCT-Unit
28: alarm RCT-Unit
29: warning RCT-Unit
30: actual current*10, PSM-Unit
31: status PSM-Unit
32: position PSM-Unit, normal/reversed = circuit 1/2
33: air Flap
34: acoustic sensor
35: DET-AC fault (extinguisher)
36: DET-AC first alarm (extinguisher)
37: DET-AC main alarm (extinguisher)
38: DRC: RFID Tag
40-47: RPM Fan 1.1 - Fan 4.2, LCP
48-55: Air temperature 1.1 - 4.2, LCP
56,57: actual temperature 1,2, LCP
58: water inlet temperature, LCP
59: water outlet temperature, LCP
60: water flow
61: fan speed (desired value)
62: status valve, LCP
63: status LCP
64: temperature difference water temperatures
65: control temperature 1, LCP
66: control temperature 2, LCP
67: condensate pump, duration, LCP
68: condensate pump, cycles, LCP
72: total energy*10 (kWh), PSM
73: total power*10 (kW), PSM
74: frequency*10 (Hz), PSM
75: voltage*10 (V), PSM
76: voltage status, PSM
77: current*10 (A), PSM
78: current status, PSM
79: power*10 (kW) per phase, PSM
80: energy*10 (kWh) per phase, PSM
81: temporary energy*10 (kWh) per phase, PSM
100: temperature sensor, wireless
101: temperature sensor (combi), wireless
102: humidity sensor, wireless
103: access sensor, wireless
104: user sensor with normally opened contact, wireless
105: user sensor with normally closed contact, wireless
106: analog sensor 4..20mA, wirelessro Enumeration .1.3.6.1.4.1.2606.4.2.5.5.2.1.2 |
unit3SensorTextDescriptional text for each sensor (entry in the table)rw DisplayString .1.3.6.1.4.1.2606.4.2.5.5.2.1.3 |
unit3SensorStatusActual status of the sensorro Enumeration .1.3.6.1.4.1.2606.4.2.5.5.2.1.4 |
unit3SensorValueValue of sensorro INTEGER .1.3.6.1.4.1.2606.4.2.5.5.2.1.5 |
unit3SensorSetHighValue for high setpoint of sensorrw INTEGER .1.3.6.1.4.1.2606.4.2.5.5.2.1.6 |
unit3SensorSetLowValue for low setpoint of sensorrw INTEGER .1.3.6.1.4.1.2606.4.2.5.5.2.1.7 |
unit3SensorSetWarnValue for warning setpoint of sensor,
also used as fan thresholdrw INTEGER .1.3.6.1.4.1.2606.4.2.5.5.2.1.8 |
unit3SensorHysteresis% -Value for hysteresis for High, Low and Warning,
input in % from actual setpointrw INTEGER .1.3.6.1.4.1.2606.4.2.5.5.2.1.9 |
unit3SensorDisplayFactorFactor of sensor value and setpoints,
devide actual value with this value,
e. g. factor = 10: sensor value = 100, actual value = 10.0ro INTEGER .1.3.6.1.4.1.2606.4.2.5.5.2.1.10 |
unit3SensorScaleStartValue for start value for scaling of 0..100% (4..20mA) sensor,
example: acutal range of value of 4..20mA sensor is from 10 to 60A,
then this variable is set to 10,
also valid for setpointsrw INTEGER .1.3.6.1.4.1.2606.4.2.5.5.2.1.11 |
unit3SensorScaleEndValue for end value for scaling of 0..100% (4..20mA) sensor,
example: acutal range of value of 4..20mA sensor is from 10 to 60A,
then this variable is set to 60,
also valid for setpointsrw INTEGER .1.3.6.1.4.1.2606.4.2.5.5.2.1.12 |
unit3SensorUnitUnit for 0..100% (4..20mA) sensor,
example: acutal range of value of 4..20mA sensor is from 10 to 60A,
then this variable is set to 'A'rw DisplayString .1.3.6.1.4.1.2606.4.2.5.5.2.1.13 |
unit3SensorInfoAdditional information to the sensor,
e. g. Serialnumber, Signal Quality..ro DisplayString .1.3.6.1.4.1.2606.4.2.5.5.2.1.14 |
cmcTcStatusUnit3Outputs OBJECT IDENTIFIER .1.3.6.1.4.1.2606.4.2.5.6 |
cmcTcUnit3NumberOfOutputsNumber of outputs available on sensor unit 3ro INTEGER .1.3.6.1.4.1.2606.4.2.5.6.1 |
cmcTcUnit3OutputTableHeadline of output table SEQUENCE OF CmcTcUnit3OutputEntry .1.3.6.1.4.1.2606.4.2.5.6.2 |
cmcTcUnit3OutputEntryEntries of output table CmcTcUnit3OutputEntry .1.3.6.1.4.1.2606.4.2.5.6.2.1 |
unit3OutputIndexIndex for the list of output entries. Its value ranges
between 1 and the value of cmcTcUnit3NumberOfOutputs.ro INTEGER .1.3.6.1.4.1.2606.4.2.5.6.2.1.1 |
unit3OutputTypeType of output which is connected to sensor unit 3 to output[unit3OutputIndex]
1: no output connected
2: output failure
3: value overflow
4: output type 1, door locking TS8,Ergoform
5: output type 2, universal lock 1, lock with power
6: output type 3, universal lock 2, unlock with power
7: output type 4, fan relay
8: output type 5, fan controlled
9: output type 6, universal relay output
10: output type 7, room door lock
11: output type 8, power output
12: output type 9, door lock with Master key
13: output type 10, door lock FR(i)
14: setpoint (FCS, RTT)
15: setpoint temperature monitoring (RTT)
16: hysteresis of setpoint (RCT)
17: command for remote control of RCT
18: relay PSM, 1=On, 0=Off
19: high setpoint current monitoring PSM
20: low setpoint current monitoring PSM
21: setpoint temperature RTT
22: setpoint temperature monitoring RTT
23: power output 20A
24: door magnet (automatic door release)
30: control mode LCP
31: min fan speed (fan control) LCP
32: min delta T (fan control) LCP
33: max delta T (fan control) LCP
34: PID controller, KP, LCP
35: PID controller, KI, LCP
36 PID controller, KD, LCP
37 flowrate flowmeter, LCP
38: cw value of water (default: 4187) LCP
39: deltaT, LCP
40: control mode, LCP
42: setpoint high voltage PSM
43: setpoint low voltage PSM
44: setpoint high current PSM
45: setpoint low current PSM
46: command PSMro Enumeration .1.3.6.1.4.1.2606.4.2.5.6.2.1.2 |
unit3OutputTextDescriptional text for each output (entry in the table)rw DisplayString .1.3.6.1.4.1.2606.4.2.5.6.2.1.3 |
unit3OutputStatusActual status of the outputrw Enumeration .1.3.6.1.4.1.2606.4.2.5.6.2.1.4 |
unit3OutputValueValue for outputrw INTEGER .1.3.6.1.4.1.2606.4.2.5.6.2.1.5 |
unit3OutputSetCommand for outputrw Enumeration .1.3.6.1.4.1.2606.4.2.5.6.2.1.6 |
unit3OutputConfigConfiguration for output
1: disable remote control (e.g. keypad)
2: enable remote controlrw Enumeration .1.3.6.1.4.1.2606.4.2.5.6.2.1.7 |
unit3OutputDelayUnsigned Value for delay,
after this time the output will fall into the previous staterw INTEGER .1.3.6.1.4.1.2606.4.2.5.6.2.1.8 |
unit3OutputTimeoutActionState for output if timeout (RS422) occursrw Enumeration .1.3.6.1.4.1.2606.4.2.5.6.2.1.9 |
cmcTcStatusUnit3Msg OBJECT IDENTIFIER .1.3.6.1.4.1.2606.4.2.5.7 |
cmcTcUnit3NumberOfMsgsNumber of alarms that can be created with sensor unit 3ro INTEGER .1.3.6.1.4.1.2606.4.2.5.7.1 |
cmcTcUnit3MsgTableHeadline of message table SEQUENCE OF CmcTcUnit3MsgEntry .1.3.6.1.4.1.2606.4.2.5.7.2 |
cmcTcUnit3MsgEntryEntries of message table CmcTcUnit3MsgEntry .1.3.6.1.4.1.2606.4.2.5.7.2.1 |
unit3MsgIndexIndex for the list of alarm entries. Its value ranges
between 1 and the value of cmcTcUnit3NumberOfMsgs.ro INTEGER .1.3.6.1.4.1.2606.4.2.5.7.2.1.1 |
unit3MsgTextDescriptional text for each message (entry in the table)rw DisplayString .1.3.6.1.4.1.2606.4.2.5.7.2.1.2 |
unit3MsgStatusActual message status
1: not available
2: configuration has changed (sensor new, changed, lost)
3: error
4: OK
5: alarm, e.g. smoke, vibration...
6: warning of analog value, value reached warning threshold
7: analog value too low, value reached low threshold
8: analog value too high, value reached high threshold
9: output is set to OFF
10: output is set to ON
11: door is open
12: door is closed
13: door is locked
14: door is unlocked by remote input, e.g. external cardreader
15: door is unlocked by reader or keypad connected to I2C
16: door is unlocked by SNMP set command (unit1OutputSet)
17: door is unlocked by WEB
18: door is unlocked by timer
19: no access, wrong keycode or cardnumber
20: orientation of PSM-Unit is circuit 1
21: orientation of PSM-Unit is circuit 2
22: battery low, wireless sensorro Enumeration .1.3.6.1.4.1.2606.4.2.5.7.2.1.3 |
unit3MsgRelaySetup of Alarm relay for this alarm
1: no switching of alarm relay
2: switching of alarm relayrw Enumeration .1.3.6.1.4.1.2606.4.2.5.7.2.1.4 |
unit3MsgBeeperSetup of Alarm beeper for this alarm
1: no audible alarm
2: audible alarmrw Enumeration .1.3.6.1.4.1.2606.4.2.5.7.2.1.5 |
unit3MsgTrap1Trap receiver 1 activatedrw Enumeration .1.3.6.1.4.1.2606.4.2.5.7.2.1.6 |
unit3MsgTrap2Trap receiver 2 activatedrw Enumeration .1.3.6.1.4.1.2606.4.2.5.7.2.1.7 |
unit3MsgTrap3Trap receiver 3 activatedrw Enumeration .1.3.6.1.4.1.2606.4.2.5.7.2.1.8 |
unit3MsgTrap4Trap receiver 4 and Event Logging activatedrw Enumeration .1.3.6.1.4.1.2606.4.2.5.7.2.1.9 |
unit3MsgQuitReset of this alarm
1: auto
2: manual, alarm needs confirmation, e. g. with 'C' keyrw Enumeration .1.3.6.1.4.1.2606.4.2.5.7.2.1.10 |
unit3MsgDelayDelay of alarm conditionrw INTEGER .1.3.6.1.4.1.2606.4.2.5.7.2.1.11 |
cmcTcStatusSensorUnit4 OBJECT IDENTIFIER .1.3.6.1.4.1.2606.4.2.6 |
cmcTcUnit4TypeOfDeviceType of sensor unit connected to port 4ro Enumeration .1.3.6.1.4.1.2606.4.2.6.1 |
cmcTcUnit4TextDescriptional text for sensor unit connected to port 4rw DisplayString .1.3.6.1.4.1.2606.4.2.6.2 |
cmcTcUnit4SerialSerialnumber of sensor unit connected to port 4ro INTEGER .1.3.6.1.4.1.2606.4.2.6.3 |
cmcTcUnit4StatusGeneral Status sensor unit connected to port 4
(1) OK
(2) error, e. g. value overflow
(3) configuration of sensor unit has changed, confirmation required
(4) Quit from sensor unit to confirm configuration changes
(5) timeout of sensor unit, confirmation required to unload this unit
(6) sensor unit detected, needs to be confirmed
(7) unit is not available
(8) supply voltage is too low
(9) Firmware upgrade runningro Enumeration .1.3.6.1.4.1.2606.4.2.6.4 |
cmcTcStatusUnit4Sensors OBJECT IDENTIFIER .1.3.6.1.4.1.2606.4.2.6.5 |
cmcTcUnit4NumberOfSensorsNumber of sensors connected to sensor unit 4ro INTEGER .1.3.6.1.4.1.2606.4.2.6.5.1 |
cmcTcUnit4SensorTableHeadline of sensor table SEQUENCE OF CmcTcUnit4SensorEntry .1.3.6.1.4.1.2606.4.2.6.5.2 |
cmcTcUnit4SensorEntryEntries of sensor table CmcTcUnit4SensorEntry .1.3.6.1.4.1.2606.4.2.6.5.2.1 |
unit4SensorIndexIndex for the list of value entries. Its value ranges
between 1 and the value of cmcTcUnit4NumberOfSensors.ro INTEGER .1.3.6.1.4.1.2606.4.2.6.5.2.1.1 |
unit4SensorTypeType of sensor which is connected to sensor unit 4 to sensor[unit4SensorIndex]
1: no sensor connected
2: sensor failure
3: value overflow
4: sensor type 1, access sensor
5: sensor type 2, vibration sensor
6: sensor type 3, motion sensor
7: sensor type 4, smoke sensor
8: sensor type 5, air flow sensor
9: sensor type 6, reserved
10: sensor type 7, temperature sensor
11: sensor type 8, 4..20mA sensor
12: sensor type 9, humidity sensor
13: user sensor with normally opened contact
14: user sensor with normally closed contact
15: door locked sensor from locking device
16: remote unlock sensor (e.g. external keypad)
17: voltage sensor, indicates status of main voltage
18: voltage value
19: fan status
20: cardreader or keypad, connected to I2C port
21: duty cycle of fan, FCS-Unit
22: status of fan, FCS-Unit
23: leakage sensor
24: warning, RittalTopTherm(RTT)-Unit
25: alarm, RittalTopTherm-Unit
26: temperature difference filter monitor, RTT-Unit
27: heatflow RCT-Unit
28: alarm RCT-Unit
29: warning RCT-Unit
30: actual current*10, PSM-Unit
31: status PSM-Unit
32: position PSM-Unit, normal/reversed = circuit 1/2
33: air Flap
34: acoustic sensor
35: DET-AC fault (extinguisher)
36: DET-AC first alarm (extinguisher)
37: DET-AC main alarm (extinguisher)
38: DRC: RFID Tag
40-47: RPM Fan 1.1 - Fan 4.2, LCP
48-55: Air temperature 1.1 - 4.2, LCP
56,57: actual temperature 1,2, LCP
58: water inlet temperature, LCP
59: water outlet temperature, LCP
60: water flow
61: fan speed (desired value)
62: status valve, LCP
63: status LCP
64: temperature difference water temperatures
65: control temperature 1, LCP
66: control temperature 2, LCP
67: condensate pump, duration, LCP
68: condensate pump, cycles, LCP
72: total energy*10 (kWh), PSM
73: total power*10 (kW), PSM
74: frequency*10 (Hz), PSM
75: voltage*10 (V), PSM
76: voltage status, PSM
77: current*10 (A), PSM
78: current status, PSM
79: power*10 (kW) per phase, PSM
80: energy*10 (kWh) per phase, PSM
81: temporary energy*10 (kWh) per phase, PSM
100: temperature sensor, wireless
101: temperature sensor (combi), wireless
102: humidity sensor, wireless
103: access sensor, wireless
104: user sensor with normally opened contact, wireless
105: user sensor with normally closed contact, wireless
106: analog sensor 4..20mA, wirelessro Enumeration .1.3.6.1.4.1.2606.4.2.6.5.2.1.2 |
unit4SensorTextDescriptional text for each sensor (entry in the table)rw DisplayString .1.3.6.1.4.1.2606.4.2.6.5.2.1.3 |
unit4SensorStatusActual status of the sensorro Enumeration .1.3.6.1.4.1.2606.4.2.6.5.2.1.4 |
unit4SensorValueValue of sensorro INTEGER .1.3.6.1.4.1.2606.4.2.6.5.2.1.5 |
unit4SensorSetHighValue for high setpoint of sensorrw INTEGER .1.3.6.1.4.1.2606.4.2.6.5.2.1.6 |
unit4SensorSetLowValue for low setpoint of sensorrw INTEGER .1.3.6.1.4.1.2606.4.2.6.5.2.1.7 |
unit4SensorSetWarnValue for warning setpoint of sensor,
also used as fan thresholdrw INTEGER .1.3.6.1.4.1.2606.4.2.6.5.2.1.8 |
unit4SensorHysteresis% -Value for hysteresis for High, Low and Warning,
input in % from actual setpointrw INTEGER .1.3.6.1.4.1.2606.4.2.6.5.2.1.9 |
unit4SensorDisplayFactorFactor of sensor value and setpoints,
devide actual value with this value,
e. g. factor = 10: sensor value = 100, actual value = 10.0ro INTEGER .1.3.6.1.4.1.2606.4.2.6.5.2.1.10 |
unit4SensorScaleStartValue for start value for scaling of 0..100% (4..20mA) sensor,
example: acutal range of value of 4..20mA sensor is from 10 to 60A,
then this variable is set to 10,
also valid for setpointsrw INTEGER .1.3.6.1.4.1.2606.4.2.6.5.2.1.11 |
unit4SensorScaleEndValue for end value for scaling of 0..100% (4..20mA) sensor,
example: acutal range of value of 4..20mA sensor is from 10 to 60A,
then this variable is set to 60,
also valid for setpointsrw INTEGER .1.3.6.1.4.1.2606.4.2.6.5.2.1.12 |
unit4SensorUnitUnit for 0..100% (4..20mA) sensor,
example: acutal range of value of 4..20mA sensor is from 10 to 60A,
then this variable is set to 'A'rw DisplayString .1.3.6.1.4.1.2606.4.2.6.5.2.1.13 |
unit4SensorInfoAdditional information to the sensor,
e. g. Serialnumber, Signal Quality..ro DisplayString .1.3.6.1.4.1.2606.4.2.6.5.2.1.14 |
cmcTcStatusUnit4Outputs OBJECT IDENTIFIER .1.3.6.1.4.1.2606.4.2.6.6 |
cmcTcUnit4NumberOfOutputsNumber of outputs available on sensor unit 4ro INTEGER .1.3.6.1.4.1.2606.4.2.6.6.1 |
cmcTcUnit4OutputTableHeadline of output table SEQUENCE OF CmcTcUnit4OutputEntry .1.3.6.1.4.1.2606.4.2.6.6.2 |
cmcTcUnit4OutputEntryEntries of output table CmcTcUnit4OutputEntry .1.3.6.1.4.1.2606.4.2.6.6.2.1 |
unit4OutputIndexIndex for the list of output entries. Its value ranges
between 1 and the value of cmcTcUnit4NumberOfOutputs.ro INTEGER .1.3.6.1.4.1.2606.4.2.6.6.2.1.1 |
unit4OutputTypeType of output which is connected to sensor unit 4 to output[unit4OutputIndex]
1: no output connected
2: output failure
3: value overflow
4: output type 1, door locking TS8,Ergoform
5: output type 2, universal lock 1, lock with power
6: output type 3, universal lock 2, unlock with power
7: output type 4, fan relay
8: output type 5, fan controlled
9: output type 6, universal relay output
10: output type 7, room door lock
11: output type 8, power output
12: output type 9, door lock with Master key
13: output type 10, door lock FR(i)
14: setpoint (FCS, RTT)
15: setpoint temperature monitoring (RTT)
16: hysteresis of setpoint (RCT)
17: command for remote control of RCT
18: relay PSM, 1=On, 0=Off
19: high setpoint current monitoring PSM
20: low setpoint current monitoring PSM
21: setpoint temperature RTT
22: setpoint temperature monitoring RTT
23: power output 20A
24: door magnet (automatic door release)
30: control mode LCP
31: min fan speed (fan control) LCP
32: min delta T (fan control) LCP
33: max delta T (fan control) LCP
34: PID controller, KP, LCP
35: PID controller, KI, LCP
36 PID controller, KD, LCP
37 flowrate flowmeter, LCP
38: cw value of water (default: 4187) LCP
39: deltaT, LCP
40: control mode, LCP
42: setpoint high voltage PSM
43: setpoint low voltage PSM
44: setpoint high current PSM
45: setpoint low current PSM
46: command PSMro Enumeration .1.3.6.1.4.1.2606.4.2.6.6.2.1.2 |
unit4OutputTextDescriptional text for each output (entry in the table)rw DisplayString .1.3.6.1.4.1.2606.4.2.6.6.2.1.3 |
unit4OutputStatusActual status of the outputrw Enumeration .1.3.6.1.4.1.2606.4.2.6.6.2.1.4 |
unit4OutputValueValue for outputrw INTEGER .1.3.6.1.4.1.2606.4.2.6.6.2.1.5 |
unit4OutputSetCommand for outputrw Enumeration .1.3.6.1.4.1.2606.4.2.6.6.2.1.6 |
unit4OutputConfigConfiguration for output
1: disable remote control (e.g. keypad)
2: enable remote controlrw Enumeration .1.3.6.1.4.1.2606.4.2.6.6.2.1.7 |
unit4OutputDelayUnsigned Value for delay,
after this time the output will fall into the previous staterw INTEGER .1.3.6.1.4.1.2606.4.2.6.6.2.1.8 |
unit4OutputTimeoutActionState for output if timeout (RS422) occursrw Enumeration .1.3.6.1.4.1.2606.4.2.6.6.2.1.9 |
cmcTcStatusUnit4Msg OBJECT IDENTIFIER .1.3.6.1.4.1.2606.4.2.6.7 |
cmcTcUnit4NumberOfMsgsNumber of alarms that can be created with sensor unit 4ro INTEGER .1.3.6.1.4.1.2606.4.2.6.7.1 |
cmcTcUnit4MsgTableHeadline of message table SEQUENCE OF CmcTcUnit4MsgEntry .1.3.6.1.4.1.2606.4.2.6.7.2 |
cmcTcUnit4MsgEntryEntries of message table CmcTcUnit4MsgEntry .1.3.6.1.4.1.2606.4.2.6.7.2.1 |
unit4MsgIndexIndex for the list of alarm entries. Its value ranges
between 1 and the value of cmcTcUnit4NumberOfMsgs.ro INTEGER .1.3.6.1.4.1.2606.4.2.6.7.2.1.1 |
unit4MsgTextDescriptional text for each message (entry in the table)rw DisplayString .1.3.6.1.4.1.2606.4.2.6.7.2.1.2 |
unit4MsgStatusActual message status
1: not available
2: configuration has changed (sensor new, changed, lost)
3: error
4: OK
5: alarm, e.g. smoke, vibration...
6: warning of analog value, value reached warning threshold
7: analog value too low, value reached low threshold
8: analog value too high, value reached high threshold
9: output is set to OFF
10: output is set to ON
11: door is open
12: door is closed
13: door is locked
14: door is unlocked by remote input, e.g. external cardreader
15: door is unlocked by reader or keypad connected to I2C
16: door is unlocked by SNMP set command (unit1OutputSet)
17: door is unlocked by WEB
18: door is unlocked by timer
19: no access, wrong keycode or cardnumber
20: orientation of PSM-Unit is circuit 1
21: orientation of PSM-Unit is circuit 2
22: battery low, wireless sensorro Enumeration .1.3.6.1.4.1.2606.4.2.6.7.2.1.3 |
unit4MsgRelaySetup of Alarm relay for this alarm
1: no switching of alarm relay
2: switching of alarm relayrw Enumeration .1.3.6.1.4.1.2606.4.2.6.7.2.1.4 |
unit4MsgBeeperSetup of Alarm beeper for this alarm
1: no audible alarm
2: audible alarmrw Enumeration .1.3.6.1.4.1.2606.4.2.6.7.2.1.5 |
unit4MsgTrap1Trap receiver 1 activatedrw Enumeration .1.3.6.1.4.1.2606.4.2.6.7.2.1.6 |
unit4MsgTrap2Trap receiver 2 activatedrw Enumeration .1.3.6.1.4.1.2606.4.2.6.7.2.1.7 |
unit4MsgTrap3Trap receiver 3 activatedrw Enumeration .1.3.6.1.4.1.2606.4.2.6.7.2.1.8 |
unit4MsgTrap4Trap receiver 4 and Event Logging activatedrw Enumeration .1.3.6.1.4.1.2606.4.2.6.7.2.1.9 |
unit4MsgQuitReset of this alarm
1: auto
2: manual, alarm needs confirmation, e. g. with 'C' keyrw Enumeration .1.3.6.1.4.1.2606.4.2.6.7.2.1.10 |
unit4MsgDelayDelay of alarm conditionrw INTEGER .1.3.6.1.4.1.2606.4.2.6.7.2.1.11 |
cmcTcStatusExtUnit OBJECT IDENTIFIER .1.3.6.1.4.1.2606.4.2.7 |
cmcTcValuesRelaySetup of Alarm relay for alarm ext. unit(s)
1: no switching of alarm relay
2: switching of alarm relayrw Enumeration .1.3.6.1.4.1.2606.4.2.7.1 |
cmcTcValuesBeeperSetup of Alarm beeper for alarm ext. unit(s)
1: no audible alarm
2: audible alarmrw Enumeration .1.3.6.1.4.1.2606.4.2.7.2 |
cmcTcValuesTrap1Trap receiver 1 activatedrw Enumeration .1.3.6.1.4.1.2606.4.2.7.3 |
cmcTcValuesTrap2Trap receiver 2 activatedrw Enumeration .1.3.6.1.4.1.2606.4.2.7.4 |
cmcTcValuesTrap3Trap receiver 3 activatedrw Enumeration .1.3.6.1.4.1.2606.4.2.7.5 |
cmcTcValuesTrap4Trap receiver 4 and Event Logging activatedrw Enumeration .1.3.6.1.4.1.2606.4.2.7.6 |
cmcTcNumberOfValuesNumber of values availabel on extension units connected to the CMCro INTEGER .1.3.6.1.4.1.2606.4.2.7.7 |
cmcTcValuesTableHeadline of values-table SEQUENCE OF CmcTcValuesEntry .1.3.6.1.4.1.2606.4.2.7.8 |
cmcTcValuesEntryEntries of values-table CmcTcValuesEntry .1.3.6.1.4.1.2606.4.2.7.8.1 |
valuesIndexIndex for the list of value entries. Its value ranges
between 1 and the value of cmcTcNumberOfValues.ro INTEGER .1.3.6.1.4.1.2606.4.2.7.8.1.1 |
valuesTextDescriptional text for each value (entry in the table)
of the extension cardrw DisplayString .1.3.6.1.4.1.2606.4.2.7.8.1.2 |
valuesStatusActual status of the value of the extension cardro Enumeration .1.3.6.1.4.1.2606.4.2.7.8.1.3 |
valuesValueValue of sensorro INTEGER .1.3.6.1.4.1.2606.4.2.7.8.1.4 |
valuesSetHighValue for high setpoint of sensorrw INTEGER .1.3.6.1.4.1.2606.4.2.7.8.1.5 |
valuesSetLowValue for low setpoint of sensorrw INTEGER .1.3.6.1.4.1.2606.4.2.7.8.1.6 |
valuesHysteresis% -Value for hysteresis for High and Low setpoints,
input in % from actual setpointrw INTEGER .1.3.6.1.4.1.2606.4.2.7.8.1.7 |
cmcTcSetup OBJECT IDENTIFIER .1.3.6.1.4.1.2606.4.3 |
cmcTcSetupGeneral OBJECT IDENTIFIER .1.3.6.1.4.1.2606.4.3.1 |
cmcTcSetTempUnitUnit of all temperature values and setpoints, Celsius or Fahrenheitrw Enumeration .1.3.6.1.4.1.2606.4.3.1.1 |
cmcTcSetBeeperAudible alarm in CMC-TC unit:
(2): beeper is on
(1): beeper is off (general)rw Enumeration .1.3.6.1.4.1.2606.4.3.1.2 |
cmcTcQuitRelayEnable or disable acknowledging currently active alarm relay
(with 'C' on CMC-TC).rw Enumeration .1.3.6.1.4.1.2606.4.3.1.3 |
cmcTcLogicRelayLogic of alarm relay:
(1) Relay will pick up in case of an alarm
(2) Relay will release in case of an alarm
(3) Relay off (general)rw Enumeration .1.3.6.1.4.1.2606.4.3.1.4 |
cmcTcWebAccessWeb access via HTTP:
(1) view only
(2) full Access, read and set
(3) Web disabled (general)rw Enumeration .1.3.6.1.4.1.2606.4.3.1.5 |
cmcTcSetupDateactual Date in format DD.MM.YYYYrw DisplayString .1.3.6.1.4.1.2606.4.3.1.6 |
cmcTcSetupTimeactual Time in format HH:MM:SS, HH (0-23), MM (0-59), SS (0-59)rw DisplayString .1.3.6.1.4.1.2606.4.3.1.7 |
cmcTcTimerTable1 OBJECT IDENTIFIER .1.3.6.1.4.1.2606.4.3.1.8 |
cmcTcTimerNumberNumber of value-table entries=number of outlets available on this unitro INTEGER .1.3.6.1.4.1.2606.4.3.1.8.1 |
cmcTcTimerTableHeadline of status-table SEQUENCE OF CmcTcTimerEntry .1.3.6.1.4.1.2606.4.3.1.8.2 |
cmcTcTimerEntryEntries of timer-table CmcTcTimerEntry .1.3.6.1.4.1.2606.4.3.1.8.2.1 |
cmcTcTimerIndexIndex for the list of timer entries. Its value ranges
between 1 and the value of cmcTcTimerNumber.ro INTEGER .1.3.6.1.4.1.2606.4.3.1.8.2.1.1 |
cmcTcTimerStatusActual status of the timerro Enumeration .1.3.6.1.4.1.2606.4.3.1.8.2.1.2 |
cmcTcTimerDayOfWeekSelection of day of week for timer to switchrw Enumeration .1.3.6.1.4.1.2606.4.3.1.8.2.1.3 |
cmcTcTimeOnTime to switch on current function,
Format: HH:MMrw DisplayString .1.3.6.1.4.1.2606.4.3.1.8.2.1.4 |
cmcTcTimeOffTime to switch off current function,
Format: HH:MMrw DisplayString .1.3.6.1.4.1.2606.4.3.1.8.2.1.5 |
cmcTcTimeControlControl via RTCrw Enumeration .1.3.6.1.4.1.2606.4.3.1.8.2.1.6 |
cmcTcTimerFunctionFunction which is controlled via timer
1: unlock via keypad 1 on unit 1 or remote input lock 1 is disabled
2: unlock via keypad 2 on unit 1 or remote input lock 2 is disabled
3 unlock via keypad 1 on unit 2 or remote input lock 1 is disabled
4: unlock via keypad 2 on unit 2 or remote input lock 2 is disabled
5: unlock via keypad 1 on unit 3 or remote input lock 1 is disabled
6: unlock via keypad 2 on unit 3 or remote input lock 2 is disabled
7: unlock via keypad 1 on unit 4 or remote input lock 1 is disabled
8: unlock via keypad 2 on unit 4 or remote input lock 2 is disabled
9: Lock of door 1 on unit 1 will be unlocked
10: Lock of door 2 on unit 1 will be unlocked
11: Lock of door 1 on unit 2 will be unlocked
12: Lock of door 2 on unit 2 will be unlocked
13: Lock of door 1 on unit 3 will be unlocked
14: Lock of door 2 on unit 3 will be unlocked
15: Lock of door 1 on unit 4 will be unlocked
16: Lock of door 2 on unit 4 will be unlocked
17-20: sending Traps to this Trap receiver will be disabled
21: sending SMS will be disabled generally
22-25: Scheduled alarm off
26-29: sending SMS to phone number 1..4 will be disabledrw Enumeration .1.3.6.1.4.1.2606.4.3.1.8.2.1.7 |
cmcTcTrapControl OBJECT IDENTIFIER .1.3.6.1.4.1.2606.4.4 |
cmcTcTraps OBJECT IDENTIFIER .1.3.6.1.4.1.2606.4.4.7 |
cmcTcTraptableNumberNumber of trapTable entries. The number of trap-receiverro INTEGER .1.3.6.1.4.1.2606.4.4.7.1 |
cmcTcTrapTableTableA list of trap-receiver entries SEQUENCE OF CmcTcTrapTableEntry .1.3.6.1.4.1.2606.4.4.7.2 |
cmcTcTrapTableEntryEntries of trapTable CmcTcTrapTableEntry .1.3.6.1.4.1.2606.4.4.7.2.1 |
trapIndexIndex for the trap-receiver-table. Its value ranges between
1 and the value of traptableNumberro INTEGER .1.3.6.1.4.1.2606.4.4.7.2.1.1 |
trapStatusEnable or disable trap receiverrw Enumeration .1.3.6.1.4.1.2606.4.4.7.2.1.2 |
trapIPaddressIP-address of trap-receiverrw DisplayString .1.3.6.1.4.1.2606.4.4.7.2.1.3 |
cmcTcControl OBJECT IDENTIFIER .1.3.6.1.4.1.2606.4.5 |
cmcTcQuitUnitCommand to quit (acknowledge) alarms of CMC-TC unit.
Setting to 'quit' (2) will have same result as pressing 'C' on Units.
Variable is automatically set back to 'noQuit' (1).rw Enumeration .1.3.6.1.4.1.2606.4.5.1 |