Home/Catalog/CMC-MIB

CMC-MIB

AI MIB Summary

Standard SNMP MIB module defining data structures for CMC-MIB.

131
Objects
Active
Status
4
Dependencies

Imported Objects

Objects

131 total
Object Name
rittal
OBJECT IDENTIFIER
.1.3.6.1.4.1.2606
RFC1213-MIB
Unknown
.1.3.6.1.4.1.2606
cmc
OBJECT IDENTIFIER
.1.3.6.1.4.1.2606.1
alarmTemperature1Alarm temperature 1, temperature 1 exceeds high-setpoint or falls below low-setpoint of temperature 1
TRAP-TYPE
.1.3.6.1.4.1.2606.1.0.1
alarmTemperature2Alarm temperature 2, temperature 2 exceeds high-setpoint or falls below low-setpoint of temperature 2
TRAP-TYPE
.1.3.6.1.4.1.2606.1.0.2
alarmFan1Alarm fan 1, no current to fan 1
TRAP-TYPE
.1.3.6.1.4.1.2606.1.0.3
alarmFan2Alarm fan 2, no current to fan 2
TRAP-TYPE
.1.3.6.1.4.1.2606.1.0.4
alarmVoltageAlarm supply-voltage, voltage exceeds high-setpoint or falls below low-setpoint of supply-voltage
TRAP-TYPE
.1.3.6.1.4.1.2606.1.0.5
alarmSmokeAlarm smoke-sensor
TRAP-TYPE
.1.3.6.1.4.1.2606.1.0.6
alarmVibrationAlarm vibration-sensor
TRAP-TYPE
.1.3.6.1.4.1.2606.1.0.7
alarmUPS1Alarm UPS1
TRAP-TYPE
.1.3.6.1.4.1.2606.1.0.8
alarmUPS2Alarm UPS2
TRAP-TYPE
.1.3.6.1.4.1.2606.1.0.9
alarmDoorAlarm Door/Door lock
TRAP-TYPE
.1.3.6.1.4.1.2606.1.0.10
alarmAnalogAux1Alarm Analog Input Aux1 (4-20mA), value not OK
TRAP-TYPE
.1.3.6.1.4.1.2606.1.0.11
alarmAnalogAux2Alarm Analog Input Aux2 (4-20mA), value not OK
TRAP-TYPE
.1.3.6.1.4.1.2606.1.0.12
msgAccessAccess message
TRAP-TYPE
.1.3.6.1.4.1.2606.1.0.13
okTrapTrap for OK- message. This trap is send, if a detected alarm is gone
TRAP-TYPE
.1.3.6.1.4.1.2606.1.0.14
alarm1Trap 1
TRAP-TYPE
.1.3.6.1.4.1.2606.1.0.21
alarm2Trap 2
TRAP-TYPE
.1.3.6.1.4.1.2606.1.0.22
alarm3Trap 3
TRAP-TYPE
.1.3.6.1.4.1.2606.1.0.23
alarm4Trap 4
TRAP-TYPE
.1.3.6.1.4.1.2606.1.0.24
alarm5Trap 5
TRAP-TYPE
.1.3.6.1.4.1.2606.1.0.25
alarm6Trap 6
TRAP-TYPE
.1.3.6.1.4.1.2606.1.0.26
alarm7Trap 7
TRAP-TYPE
.1.3.6.1.4.1.2606.1.0.27
alarm8Trap 8
TRAP-TYPE
.1.3.6.1.4.1.2606.1.0.28
alarm9Trap 9
TRAP-TYPE
.1.3.6.1.4.1.2606.1.0.29
alarm10Trap 10
TRAP-TYPE
.1.3.6.1.4.1.2606.1.0.30
alarm11Trap 11
TRAP-TYPE
.1.3.6.1.4.1.2606.1.0.31
alarm12Trap 12
TRAP-TYPE
.1.3.6.1.4.1.2606.1.0.32
alarm13Trap 13
TRAP-TYPE
.1.3.6.1.4.1.2606.1.0.33
alarm14Trap 14
TRAP-TYPE
.1.3.6.1.4.1.2606.1.0.34
alarm15Trap 15
TRAP-TYPE
.1.3.6.1.4.1.2606.1.0.35
alarm16Trap 16
TRAP-TYPE
.1.3.6.1.4.1.2606.1.0.36
alarm17Trap 17
TRAP-TYPE
.1.3.6.1.4.1.2606.1.0.37
alarm18Trap 18
TRAP-TYPE
.1.3.6.1.4.1.2606.1.0.38
alarm19Trap 19
TRAP-TYPE
.1.3.6.1.4.1.2606.1.0.39
alarm20Trap 20
TRAP-TYPE
.1.3.6.1.4.1.2606.1.0.40
alarm21Trap 21
TRAP-TYPE
.1.3.6.1.4.1.2606.1.0.41
alarm22Trap 22
TRAP-TYPE
.1.3.6.1.4.1.2606.1.0.42
alarm23Trap 23
TRAP-TYPE
.1.3.6.1.4.1.2606.1.0.43
alarm24Trap 24
TRAP-TYPE
.1.3.6.1.4.1.2606.1.0.44
alarm25Trap 25
TRAP-TYPE
.1.3.6.1.4.1.2606.1.0.45
alarm26Trap 26
TRAP-TYPE
.1.3.6.1.4.1.2606.1.0.46
alarm27Trap 27
TRAP-TYPE
.1.3.6.1.4.1.2606.1.0.47
alarm28Trap 28
TRAP-TYPE
.1.3.6.1.4.1.2606.1.0.48
alarm29Trap 29
TRAP-TYPE
.1.3.6.1.4.1.2606.1.0.49
alarm30Trap 30
TRAP-TYPE
.1.3.6.1.4.1.2606.1.0.50
alarm31Trap 31
TRAP-TYPE
.1.3.6.1.4.1.2606.1.0.51
alarm32Trap 32
TRAP-TYPE
.1.3.6.1.4.1.2606.1.0.52
alarm33Trap 33
TRAP-TYPE
.1.3.6.1.4.1.2606.1.0.53
alarm34Trap 34
TRAP-TYPE
.1.3.6.1.4.1.2606.1.0.54
alarm35Trap 35
TRAP-TYPE
.1.3.6.1.4.1.2606.1.0.55
values
OBJECT IDENTIFIER
.1.3.6.1.4.1.2606.1.1
valueTemperature1Actual value of temperature 1 in deg Cro
INTEGER
.1.3.6.1.4.1.2606.1.1.1
valueTemperature2Actual value of temperature 2 in deg Cro
INTEGER
.1.3.6.1.4.1.2606.1.1.2
valuePowerSupplyActual value of power supply in Vro
INTEGER
.1.3.6.1.4.1.2606.1.1.3
valueAnalogAux1Actual value of aux. analog input 1 (4-20mA = 0-100%)ro
INTEGER
.1.3.6.1.4.1.2606.1.1.4
valueAnalogAux2Actual value of aux. analog input 2 (4-20mA = 0-100%)ro
INTEGER
.1.3.6.1.4.1.2606.1.1.5
table1
OBJECT IDENTIFIER
.1.3.6.1.4.1.2606.1.1.6
valuesNumberNumber of value-table entriesro
INTEGER
.1.3.6.1.4.1.2606.1.1.6.1
valuesTableHeadline of value-table
SEQUENCE OF ValuesEntry
.1.3.6.1.4.1.2606.1.1.6.2
valuesEntryEntries of value-table
ValuesEntry
.1.3.6.1.4.1.2606.1.1.6.2.1
valuesIndexIndex for the list of value entries. Its value ranges between 1 and the value of valuesNumber.ro
INTEGER
.1.3.6.1.4.1.2606.1.1.6.2.1.1
valuesTextText of the entry in the value-tablerw
DisplayString
.1.3.6.1.4.1.2606.1.1.6.2.1.2
valuesValueActual value of the value-tablero
INTEGER
.1.3.6.1.4.1.2606.1.1.6.2.1.3
valuesStatusStatus of the valuero
Enumeration
.1.3.6.1.4.1.2606.1.1.6.2.1.4
valuesMaxValueValue for max. alarmrw
INTEGER
.1.3.6.1.4.1.2606.1.1.6.2.1.5
valuesMinValueValue for min. alarmrw
INTEGER
.1.3.6.1.4.1.2606.1.1.6.2.1.6
status
OBJECT IDENTIFIER
.1.3.6.1.4.1.2606.1.2
statusTemperature1Status temperature 1, OK/ too low/ too high (see setpoints of temperature 1)ro
DisplayString
.1.3.6.1.4.1.2606.1.2.1
statusTemperature2Status temperature 2, OK/ too low/ too high (see setpoints of temperature 2)ro
DisplayString
.1.3.6.1.4.1.2606.1.2.2
statusFan1Status fan 1, Stop/ running/ faultro
DisplayString
.1.3.6.1.4.1.2606.1.2.3
statusFan2Status fan 2, Stop/ running/ faultro
DisplayString
.1.3.6.1.4.1.2606.1.2.4
statusHeatingStatus heating, On/Offro
DisplayString
.1.3.6.1.4.1.2606.1.2.5
statusPowerSupplyStatus power supply, OK/ too low/ too high (see setpoints of power supply)ro
DisplayString
.1.3.6.1.4.1.2606.1.2.6
statusAnalogAux1Status aux analog input 1, OK/ too low/ too highro
DisplayString
.1.3.6.1.4.1.2606.1.2.7
statusAnalogAux2Status aux analog input 2, OK/ too low/ too highro
DisplayString
.1.3.6.1.4.1.2606.1.2.8
statusDoor1Status door, open/closed/lockedro
DisplayString
.1.3.6.1.4.1.2606.1.2.9
statusUps1Status UPS 1, OK/ faultro
DisplayString
.1.3.6.1.4.1.2606.1.2.10
statusUps2Status UPS 2, OK/ faultro
DisplayString
.1.3.6.1.4.1.2606.1.2.11
statusSmokeSensorStatus smoke-sensor, OK/ smokero
DisplayString
.1.3.6.1.4.1.2606.1.2.12
statusVibrationSensorStatus vibration sensor, OK/ vibrationro
DisplayString
.1.3.6.1.4.1.2606.1.2.13
statusMessageMessage from CMCro
DisplayString
.1.3.6.1.4.1.2606.1.2.14
valueOperatingTimeOperating time CMC-unitro
DisplayString
.1.3.6.1.4.1.2606.1.2.15
statusUnitUnit of temperature-values, Celsius or Fahrenheitro
Enumeration
.1.3.6.1.4.1.2606.1.2.16
statusDoor2Status door, open/closed/lockedro
DisplayString
.1.3.6.1.4.1.2606.1.2.17
table
OBJECT IDENTIFIER
.1.3.6.1.4.1.2606.1.2.18
statusNumberNumber of status-table entriesro
INTEGER
.1.3.6.1.4.1.2606.1.2.18.1
statusTableHeadline of table
SEQUENCE OF StatusEntry
.1.3.6.1.4.1.2606.1.2.18.2
statusEntryA list of status entries. The number of entries is given by the value of statusNumber.
StatusEntry
.1.3.6.1.4.1.2606.1.2.18.2.1
statusIndexIndex fo the list of status entries. Its value ranges between 1 and the value of statusNumber.ro
INTEGER
.1.3.6.1.4.1.2606.1.2.18.2.1.1
statusTextText of the entry in the status-tablerw
DisplayString
.1.3.6.1.4.1.2606.1.2.18.2.1.2
statusStatusStatus of the table entryro
Enumeration
.1.3.6.1.4.1.2606.1.2.18.2.1.3
set
OBJECT IDENTIFIER
.1.3.6.1.4.1.2606.1.3
statusAccessStatus accessrw
DisplayString
.1.3.6.1.4.1.2606.1.3.1
setDoor1Set door, see tablerw
Enumeration
.1.3.6.1.4.1.2606.1.3.2
setMessageSet messagerw
DisplayString
.1.3.6.1.4.1.2606.1.3.3
setFaultSet fault, see tablerw
Enumeration
.1.3.6.1.4.1.2606.1.3.4
setDoor2Set door, see tablerw
Enumeration
.1.3.6.1.4.1.2606.1.3.5
relayControl
OBJECT IDENTIFIER
.1.3.6.1.4.1.2606.1.3.6
relaytableMaxNumNumber of table entriesro
INTEGER
.1.3.6.1.4.1.2606.1.3.6.1
relayTableHeadline of table for relay control
SEQUENCE OF RelayEntry
.1.3.6.1.4.1.2606.1.3.6.2
relayEntryEntries
RelayEntry
.1.3.6.1.4.1.2606.1.3.6.2.1
relaytableIndexIndex for the relay-table. Its value ranges between 1 and relaytableMaxNumro
INTEGER
.1.3.6.1.4.1.2606.1.3.6.2.1.1
relaytableTextDescription-Text for each relay in the tablerw
DisplayString
.1.3.6.1.4.1.2606.1.3.6.2.1.2
relaytableStatusStatus of relays in the tablerw
Enumeration
.1.3.6.1.4.1.2606.1.3.6.2.1.3
setpoints
OBJECT IDENTIFIER
.1.3.6.1.4.1.2606.1.4
setpointFan1Setpoint Fan 1 in C, Fan 1 will start if temperature 1 exceeds this valuerw
INTEGER
.1.3.6.1.4.1.2606.1.4.1
setpointFan2Setpoint Fan 2 in C, Fan 2 will start if temperature 2 exceeds this valuerw
INTEGER
.1.3.6.1.4.1.2606.1.4.2
setpointHeatingSetpoint heating in C, heating will start if lowest value of temperature 1 and 2 falls below this valuerw
INTEGER
.1.3.6.1.4.1.2606.1.4.3
setpointHighTemperature1Setpoint high value alarm temperature 1rw
INTEGER
.1.3.6.1.4.1.2606.1.4.4
setpointLowTemperature1Setpoint low value alarm temperature 1rw
INTEGER
.1.3.6.1.4.1.2606.1.4.5
setpointHighTemperature2Setpoint high value alarm temperature 2rw
INTEGER
.1.3.6.1.4.1.2606.1.4.6
setpointLowTemperature2Setpoint low value alarm temperature 2rw
INTEGER
.1.3.6.1.4.1.2606.1.4.7
setpointHighVoltageSetpoint high value supply voltage alarmrw
INTEGER
.1.3.6.1.4.1.2606.1.4.8
setpointLowVoltageSetpoint low value supply voltage alarmrw
INTEGER
.1.3.6.1.4.1.2606.1.4.9
setpointLowAux1Setpoint low value Aux input 1 alarmrw
INTEGER
.1.3.6.1.4.1.2606.1.4.10
setpointHighAux1Setpoint high value Aux input 1 alarmrw
INTEGER
.1.3.6.1.4.1.2606.1.4.11
setpointLowAux2Setpoint low value Aux input 2 alarmrw
INTEGER
.1.3.6.1.4.1.2606.1.4.12
setpointHighAux2Setpoint high value Aux input alarmrw
INTEGER
.1.3.6.1.4.1.2606.1.4.13
trapControl
OBJECT IDENTIFIER
.1.3.6.1.4.1.2606.1.5
setTrapRepeatEnable/disable repeating of traps. If enabled, traps will be repeated after a repeat time, set in setTrapRepeatTime. Repeating can be stopped by setting setTrapQuit to quitTraprw
Enumeration
.1.3.6.1.4.1.2606.1.5.1
setTrapRepeatTimeTime value (sec) for trap-repeating, if setTrapRepeat is enabledrw
INTEGER
.1.3.6.1.4.1.2606.1.5.2
setTrapQuitQuit trap to stop repeating.rw
Enumeration
.1.3.6.1.4.1.2606.1.5.3
traps
OBJECT IDENTIFIER
.1.3.6.1.4.1.2606.1.5.4
traptableNumberNumber of trapTable entries. The number of trap-receiverro
INTEGER
.1.3.6.1.4.1.2606.1.5.4.1
trapTableA list of trap-receiver entries
SEQUENCE OF TrapTableEntry
.1.3.6.1.4.1.2606.1.5.4.2
trapTableEntryEntries of trapTable
TrapTableEntry
.1.3.6.1.4.1.2606.1.5.4.2.1
trapIndexIndex for the trap-receiver-table. Its value ranges between 1 and the value of traptableNumberro
INTEGER
.1.3.6.1.4.1.2606.1.5.4.2.1.1
trapStatusEnable or disable trap receiverrw
Enumeration
.1.3.6.1.4.1.2606.1.5.4.2.1.2
trapIPaddressIP-address of trap-receiverrw
DisplayString
.1.3.6.1.4.1.2606.1.5.4.2.1.3
CMC-MIB - SNMP MIB Reference | MIBs Explorer