CMC-MIB
Standard SNMP MIB module defining data structures for CMC-MIB.
Imported Objects
Objects
131 total| Object Name |
|---|
rittal OBJECT IDENTIFIER .1.3.6.1.4.1.2606 |
RFC1213-MIB Unknown .1.3.6.1.4.1.2606 |
cmc OBJECT IDENTIFIER .1.3.6.1.4.1.2606.1 |
alarmTemperature1Alarm temperature 1, temperature 1 exceeds high-setpoint
or falls below low-setpoint of temperature 1 TRAP-TYPE .1.3.6.1.4.1.2606.1.0.1 |
alarmTemperature2Alarm temperature 2, temperature 2 exceeds high-setpoint
or falls below low-setpoint of temperature 2 TRAP-TYPE .1.3.6.1.4.1.2606.1.0.2 |
alarmFan1Alarm fan 1, no current to fan 1 TRAP-TYPE .1.3.6.1.4.1.2606.1.0.3 |
alarmFan2Alarm fan 2, no current to fan 2 TRAP-TYPE .1.3.6.1.4.1.2606.1.0.4 |
alarmVoltageAlarm supply-voltage, voltage exceeds high-setpoint
or falls below low-setpoint of supply-voltage TRAP-TYPE .1.3.6.1.4.1.2606.1.0.5 |
alarmSmokeAlarm smoke-sensor TRAP-TYPE .1.3.6.1.4.1.2606.1.0.6 |
alarmVibrationAlarm vibration-sensor TRAP-TYPE .1.3.6.1.4.1.2606.1.0.7 |
alarmUPS1Alarm UPS1 TRAP-TYPE .1.3.6.1.4.1.2606.1.0.8 |
alarmUPS2Alarm UPS2 TRAP-TYPE .1.3.6.1.4.1.2606.1.0.9 |
alarmDoorAlarm Door/Door lock TRAP-TYPE .1.3.6.1.4.1.2606.1.0.10 |
alarmAnalogAux1Alarm Analog Input Aux1 (4-20mA),
value not OK TRAP-TYPE .1.3.6.1.4.1.2606.1.0.11 |
alarmAnalogAux2Alarm Analog Input Aux2 (4-20mA),
value not OK TRAP-TYPE .1.3.6.1.4.1.2606.1.0.12 |
msgAccessAccess message TRAP-TYPE .1.3.6.1.4.1.2606.1.0.13 |
okTrapTrap for OK- message. This trap is send, if a detected
alarm is gone TRAP-TYPE .1.3.6.1.4.1.2606.1.0.14 |
alarm1Trap 1 TRAP-TYPE .1.3.6.1.4.1.2606.1.0.21 |
alarm2Trap 2 TRAP-TYPE .1.3.6.1.4.1.2606.1.0.22 |
alarm3Trap 3 TRAP-TYPE .1.3.6.1.4.1.2606.1.0.23 |
alarm4Trap 4 TRAP-TYPE .1.3.6.1.4.1.2606.1.0.24 |
alarm5Trap 5 TRAP-TYPE .1.3.6.1.4.1.2606.1.0.25 |
alarm6Trap 6 TRAP-TYPE .1.3.6.1.4.1.2606.1.0.26 |
alarm7Trap 7 TRAP-TYPE .1.3.6.1.4.1.2606.1.0.27 |
alarm8Trap 8 TRAP-TYPE .1.3.6.1.4.1.2606.1.0.28 |
alarm9Trap 9 TRAP-TYPE .1.3.6.1.4.1.2606.1.0.29 |
alarm10Trap 10 TRAP-TYPE .1.3.6.1.4.1.2606.1.0.30 |
alarm11Trap 11 TRAP-TYPE .1.3.6.1.4.1.2606.1.0.31 |
alarm12Trap 12 TRAP-TYPE .1.3.6.1.4.1.2606.1.0.32 |
alarm13Trap 13 TRAP-TYPE .1.3.6.1.4.1.2606.1.0.33 |
alarm14Trap 14 TRAP-TYPE .1.3.6.1.4.1.2606.1.0.34 |
alarm15Trap 15 TRAP-TYPE .1.3.6.1.4.1.2606.1.0.35 |
alarm16Trap 16 TRAP-TYPE .1.3.6.1.4.1.2606.1.0.36 |
alarm17Trap 17 TRAP-TYPE .1.3.6.1.4.1.2606.1.0.37 |
alarm18Trap 18 TRAP-TYPE .1.3.6.1.4.1.2606.1.0.38 |
alarm19Trap 19 TRAP-TYPE .1.3.6.1.4.1.2606.1.0.39 |
alarm20Trap 20 TRAP-TYPE .1.3.6.1.4.1.2606.1.0.40 |
alarm21Trap 21 TRAP-TYPE .1.3.6.1.4.1.2606.1.0.41 |
alarm22Trap 22 TRAP-TYPE .1.3.6.1.4.1.2606.1.0.42 |
alarm23Trap 23 TRAP-TYPE .1.3.6.1.4.1.2606.1.0.43 |
alarm24Trap 24 TRAP-TYPE .1.3.6.1.4.1.2606.1.0.44 |
alarm25Trap 25 TRAP-TYPE .1.3.6.1.4.1.2606.1.0.45 |
alarm26Trap 26 TRAP-TYPE .1.3.6.1.4.1.2606.1.0.46 |
alarm27Trap 27 TRAP-TYPE .1.3.6.1.4.1.2606.1.0.47 |
alarm28Trap 28 TRAP-TYPE .1.3.6.1.4.1.2606.1.0.48 |
alarm29Trap 29 TRAP-TYPE .1.3.6.1.4.1.2606.1.0.49 |
alarm30Trap 30 TRAP-TYPE .1.3.6.1.4.1.2606.1.0.50 |
alarm31Trap 31 TRAP-TYPE .1.3.6.1.4.1.2606.1.0.51 |
alarm32Trap 32 TRAP-TYPE .1.3.6.1.4.1.2606.1.0.52 |
alarm33Trap 33 TRAP-TYPE .1.3.6.1.4.1.2606.1.0.53 |
alarm34Trap 34 TRAP-TYPE .1.3.6.1.4.1.2606.1.0.54 |
alarm35Trap 35 TRAP-TYPE .1.3.6.1.4.1.2606.1.0.55 |
values OBJECT IDENTIFIER .1.3.6.1.4.1.2606.1.1 |
valueTemperature1Actual value of temperature 1 in deg Cro INTEGER .1.3.6.1.4.1.2606.1.1.1 |
valueTemperature2Actual value of temperature 2 in deg Cro INTEGER .1.3.6.1.4.1.2606.1.1.2 |
valuePowerSupplyActual value of power supply in Vro INTEGER .1.3.6.1.4.1.2606.1.1.3 |
valueAnalogAux1Actual value of aux. analog input 1
(4-20mA = 0-100%)ro INTEGER .1.3.6.1.4.1.2606.1.1.4 |
valueAnalogAux2Actual value of aux. analog input 2
(4-20mA = 0-100%)ro INTEGER .1.3.6.1.4.1.2606.1.1.5 |
table1 OBJECT IDENTIFIER .1.3.6.1.4.1.2606.1.1.6 |
valuesNumberNumber of value-table entriesro INTEGER .1.3.6.1.4.1.2606.1.1.6.1 |
valuesTableHeadline of value-table SEQUENCE OF ValuesEntry .1.3.6.1.4.1.2606.1.1.6.2 |
valuesEntryEntries of value-table ValuesEntry .1.3.6.1.4.1.2606.1.1.6.2.1 |
valuesIndexIndex for the list of value entries. Its value ranges
between 1 and the value of valuesNumber.ro INTEGER .1.3.6.1.4.1.2606.1.1.6.2.1.1 |
valuesTextText of the entry in the value-tablerw DisplayString .1.3.6.1.4.1.2606.1.1.6.2.1.2 |
valuesValueActual value of the value-tablero INTEGER .1.3.6.1.4.1.2606.1.1.6.2.1.3 |
valuesStatusStatus of the valuero Enumeration .1.3.6.1.4.1.2606.1.1.6.2.1.4 |
valuesMaxValueValue for max. alarmrw INTEGER .1.3.6.1.4.1.2606.1.1.6.2.1.5 |
valuesMinValueValue for min. alarmrw INTEGER .1.3.6.1.4.1.2606.1.1.6.2.1.6 |
status OBJECT IDENTIFIER .1.3.6.1.4.1.2606.1.2 |
statusTemperature1Status temperature 1, OK/ too low/ too high
(see setpoints of temperature 1)ro DisplayString .1.3.6.1.4.1.2606.1.2.1 |
statusTemperature2Status temperature 2, OK/ too low/ too high
(see setpoints of temperature 2)ro DisplayString .1.3.6.1.4.1.2606.1.2.2 |
statusFan1Status fan 1, Stop/ running/ faultro DisplayString .1.3.6.1.4.1.2606.1.2.3 |
statusFan2Status fan 2, Stop/ running/ faultro DisplayString .1.3.6.1.4.1.2606.1.2.4 |
statusHeatingStatus heating, On/Offro DisplayString .1.3.6.1.4.1.2606.1.2.5 |
statusPowerSupplyStatus power supply, OK/ too low/ too high
(see setpoints of power supply)ro DisplayString .1.3.6.1.4.1.2606.1.2.6 |
statusAnalogAux1Status aux analog input 1, OK/ too low/ too highro DisplayString .1.3.6.1.4.1.2606.1.2.7 |
statusAnalogAux2Status aux analog input 2, OK/ too low/ too highro DisplayString .1.3.6.1.4.1.2606.1.2.8 |
statusDoor1Status door, open/closed/lockedro DisplayString .1.3.6.1.4.1.2606.1.2.9 |
statusUps1Status UPS 1, OK/ faultro DisplayString .1.3.6.1.4.1.2606.1.2.10 |
statusUps2Status UPS 2, OK/ faultro DisplayString .1.3.6.1.4.1.2606.1.2.11 |
statusSmokeSensorStatus smoke-sensor, OK/ smokero DisplayString .1.3.6.1.4.1.2606.1.2.12 |
statusVibrationSensorStatus vibration sensor, OK/ vibrationro DisplayString .1.3.6.1.4.1.2606.1.2.13 |
statusMessageMessage from CMCro DisplayString .1.3.6.1.4.1.2606.1.2.14 |
valueOperatingTimeOperating time CMC-unitro DisplayString .1.3.6.1.4.1.2606.1.2.15 |
statusUnitUnit of temperature-values, Celsius or Fahrenheitro Enumeration .1.3.6.1.4.1.2606.1.2.16 |
statusDoor2Status door, open/closed/lockedro DisplayString .1.3.6.1.4.1.2606.1.2.17 |
table OBJECT IDENTIFIER .1.3.6.1.4.1.2606.1.2.18 |
statusNumberNumber of status-table entriesro INTEGER .1.3.6.1.4.1.2606.1.2.18.1 |
statusTableHeadline of table SEQUENCE OF StatusEntry .1.3.6.1.4.1.2606.1.2.18.2 |
statusEntryA list of status entries. The number of
entries is given by the value of statusNumber. StatusEntry .1.3.6.1.4.1.2606.1.2.18.2.1 |
statusIndexIndex fo the list of status entries. Its value ranges
between 1 and the value of statusNumber.ro INTEGER .1.3.6.1.4.1.2606.1.2.18.2.1.1 |
statusTextText of the entry in the status-tablerw DisplayString .1.3.6.1.4.1.2606.1.2.18.2.1.2 |
statusStatusStatus of the table entryro Enumeration .1.3.6.1.4.1.2606.1.2.18.2.1.3 |
set OBJECT IDENTIFIER .1.3.6.1.4.1.2606.1.3 |
statusAccessStatus accessrw DisplayString .1.3.6.1.4.1.2606.1.3.1 |
setDoor1Set door, see tablerw Enumeration .1.3.6.1.4.1.2606.1.3.2 |
setMessageSet messagerw DisplayString .1.3.6.1.4.1.2606.1.3.3 |
setFaultSet fault, see tablerw Enumeration .1.3.6.1.4.1.2606.1.3.4 |
setDoor2Set door, see tablerw Enumeration .1.3.6.1.4.1.2606.1.3.5 |
relayControl OBJECT IDENTIFIER .1.3.6.1.4.1.2606.1.3.6 |
relaytableMaxNumNumber of table entriesro INTEGER .1.3.6.1.4.1.2606.1.3.6.1 |
relayTableHeadline of table for relay control SEQUENCE OF RelayEntry .1.3.6.1.4.1.2606.1.3.6.2 |
relayEntryEntries RelayEntry .1.3.6.1.4.1.2606.1.3.6.2.1 |
relaytableIndexIndex for the relay-table. Its value ranges
between 1 and relaytableMaxNumro INTEGER .1.3.6.1.4.1.2606.1.3.6.2.1.1 |
relaytableTextDescription-Text for each relay in the tablerw DisplayString .1.3.6.1.4.1.2606.1.3.6.2.1.2 |
relaytableStatusStatus of relays in the tablerw Enumeration .1.3.6.1.4.1.2606.1.3.6.2.1.3 |
setpoints OBJECT IDENTIFIER .1.3.6.1.4.1.2606.1.4 |
setpointFan1Setpoint Fan 1 in C, Fan 1 will start
if temperature 1 exceeds this valuerw INTEGER .1.3.6.1.4.1.2606.1.4.1 |
setpointFan2Setpoint Fan 2 in C, Fan 2 will start
if temperature 2 exceeds this valuerw INTEGER .1.3.6.1.4.1.2606.1.4.2 |
setpointHeatingSetpoint heating in C, heating will start
if lowest value of temperature 1 and 2 falls below this valuerw INTEGER .1.3.6.1.4.1.2606.1.4.3 |
setpointHighTemperature1Setpoint high value alarm temperature 1rw INTEGER .1.3.6.1.4.1.2606.1.4.4 |
setpointLowTemperature1Setpoint low value alarm temperature 1rw INTEGER .1.3.6.1.4.1.2606.1.4.5 |
setpointHighTemperature2Setpoint high value alarm temperature 2rw INTEGER .1.3.6.1.4.1.2606.1.4.6 |
setpointLowTemperature2Setpoint low value alarm temperature 2rw INTEGER .1.3.6.1.4.1.2606.1.4.7 |
setpointHighVoltageSetpoint high value supply voltage alarmrw INTEGER .1.3.6.1.4.1.2606.1.4.8 |
setpointLowVoltageSetpoint low value supply voltage alarmrw INTEGER .1.3.6.1.4.1.2606.1.4.9 |
setpointLowAux1Setpoint low value Aux input 1 alarmrw INTEGER .1.3.6.1.4.1.2606.1.4.10 |
setpointHighAux1Setpoint high value Aux input 1 alarmrw INTEGER .1.3.6.1.4.1.2606.1.4.11 |
setpointLowAux2Setpoint low value Aux input 2 alarmrw INTEGER .1.3.6.1.4.1.2606.1.4.12 |
setpointHighAux2Setpoint high value Aux input alarmrw INTEGER .1.3.6.1.4.1.2606.1.4.13 |
trapControl OBJECT IDENTIFIER .1.3.6.1.4.1.2606.1.5 |
setTrapRepeatEnable/disable repeating of traps. If enabled, traps will
be repeated after a repeat time, set in setTrapRepeatTime.
Repeating can be stopped by setting setTrapQuit to quitTraprw Enumeration .1.3.6.1.4.1.2606.1.5.1 |
setTrapRepeatTimeTime value (sec) for trap-repeating, if setTrapRepeat is enabledrw INTEGER .1.3.6.1.4.1.2606.1.5.2 |
setTrapQuitQuit trap to stop repeating.rw Enumeration .1.3.6.1.4.1.2606.1.5.3 |
traps OBJECT IDENTIFIER .1.3.6.1.4.1.2606.1.5.4 |
traptableNumberNumber of trapTable entries. The number of trap-receiverro INTEGER .1.3.6.1.4.1.2606.1.5.4.1 |
trapTableA list of trap-receiver entries SEQUENCE OF TrapTableEntry .1.3.6.1.4.1.2606.1.5.4.2 |
trapTableEntryEntries of trapTable TrapTableEntry .1.3.6.1.4.1.2606.1.5.4.2.1 |
trapIndexIndex for the trap-receiver-table. Its value ranges between
1 and the value of traptableNumberro INTEGER .1.3.6.1.4.1.2606.1.5.4.2.1.1 |
trapStatusEnable or disable trap receiverrw Enumeration .1.3.6.1.4.1.2606.1.5.4.2.1.2 |
trapIPaddressIP-address of trap-receiverrw DisplayString .1.3.6.1.4.1.2606.1.5.4.2.1.3 |
More MIBs from RITTAL GmbH &
Browse all RITTAL GmbH &MIBs →Standard SNMP MIB module defining data structures for RITTAL-CMC-TC-MIB.
The RITTAL-CMC-III-MIB enables SNMP-based monitoring and management of Rittal CMC III climate control units, exposing critical environmental telemetry such as temperature, humidity, fan status, and alarm states. This module facilitates the collection of operational metrics required for data center infrastructure monitoring and automated alerting within Rittal's environmental control ecosystem.
The RITTAL-CMC-III-PRODUCTS-MIB enables SNMP-based monitoring and management of Rittal CMC III climate control units, exposing device status, environmental sensor readings, and operational parameters for data center cooling infrastructure.
The RITTAL-CMC-III-CAPABILITY-MIB defines private OID structures for the Rittal CMC III (Climate Control Module) SNMP agent to expose hardware capability attributes, including supported sensor types, interface availability, and feature set enumerations. This module enables network management systems to dynamically detect the specific configuration and functional limits of the CMC III controller for accurate polling and alarm correlation.
The RITTAL-SMI-MIB module enables SNMP-based monitoring and management of Rittal enterprise infrastructure, specifically tracking environmental telemetry such as temperature, humidity, and door status for server cabinets, along with power distribution unit (PDU) metrics and alarm states.