NETBOTZ-PRD-BOT-MIB

Detailed view of the defined objects, syntax rules, and hierarchical paths.

229
Objects
Active
Status
7
Dependencies

Imported Objects

Objects

229 total
Object Name
netBotz-prd-bot-low-trapNetbotz Low Trap. This trap indicates that a lower limit has been exceeded.
TRAP-TYPE
.1.3.6.1.4.1.5528.30.10.0.1
netBotz-prd-bot-high-trapNetbotz High Trap. This trap indicates that an upper limit has been exceeded.
TRAP-TYPE
.1.3.6.1.4.1.5528.30.10.0.2
netBotz-prd-bot-trap-clearNetbotz Cleared Trap. The trap has been cleared because the value has returned to acceptable limits.
TRAP-TYPE
.1.3.6.1.4.1.5528.30.10.0.3
netBotz-prd-bot-offline-trapNetbotz Device Offline Trap. This trap indicates that a device or function has been determined to be offline.
TRAP-TYPE
.1.3.6.1.4.1.5528.30.10.0.4
netBotz-prd-bot-online-trapNetbotz Device Online Trap. This trap indicates that a device or function has been determined to be online.
TRAP-TYPE
.1.3.6.1.4.1.5528.30.10.0.5
IMPORTSThe reading of the temperature probe, in degrees F or degrees C (depends on netBotz-ismetric).ro
INTEGER
.1.3.6.1.4.1.5528.30.10.1
netBotz-prd-bot-humidityThe reading of the humidity probe, in percent.ro
INTEGER
.1.3.6.1.4.1.5528.30.10.2
netBotz-prd-bot-airflowThe reading of the airflow probe. Each unit represents approximately 40 feet/minute or 13 meters/minute of airflow velocity.ro
INTEGER
.1.3.6.1.4.1.5528.30.10.3
netBotz-prd-bot-audioThe reading of the audio alarm probe on/off.ro
INTEGER
.1.3.6.1.4.1.5528.30.10.4
netBotz-prd-bot-doorajarThe reading of the door switch probe open(0) or closed(1).ro
INTEGER
.1.3.6.1.4.1.5528.30.10.5
netBotz-prd-bot-temp-minThe temperature probe minimum, from 35 to 120 degrees F, or 1 to 50 degrees C (depends on netBotz-ismetric).rw
INTEGER
.1.3.6.1.4.1.5528.30.10.6
netBotz-prd-bot-temp-maxThe temperature probe maximum, from 35 to 120 degrees F, or 1 to 50 degrees C (depends on netBotz-ismetric).rw
INTEGER
.1.3.6.1.4.1.5528.30.10.7
netBotz-prd-bot-humidity-minThe humidity probe minimum, from 10 to 90 percent.rw
INTEGER
.1.3.6.1.4.1.5528.30.10.8
netBotz-prd-bot-humidity-maxThe humidity probe maximum, from 10 to 90 percent.rw
INTEGER
.1.3.6.1.4.1.5528.30.10.9
netBotz-prd-bot-airflow-minsMinutes without airflow before alarm set.rw
INTEGER
.1.3.6.1.4.1.5528.30.10.10
netBotz-prd-bot-audio-secsSeconds of alarm audio before alarm set.rw
INTEGER
.1.3.6.1.4.1.5528.30.10.11
netBotz-prd-bot-temp-enabledTemperature probe alarm enabled(1) or disabled(0).rw
INTEGER
.1.3.6.1.4.1.5528.30.10.12
netBotz-prd-bot-hum-enabledHumidity probe alarm enabled(1) or disabled(0).rw
INTEGER
.1.3.6.1.4.1.5528.30.10.13
netBotz-prd-bot-air-enabledAirflow probe alarm enabled(1) or disabled(0).rw
INTEGER
.1.3.6.1.4.1.5528.30.10.14
netBotz-prd-bot-audio-enabledAudio probe alarm enabled(1) or disabled(0).rw
INTEGER
.1.3.6.1.4.1.5528.30.10.15
netBotz-prd-bot-switch-stateSwitch state setting. The state controls which condition of the door switch indicates an alarm. If set to 0, alarm is set when the switch is closed. If set to 1, alarm is set when the switch is open.rw
INTEGER
.1.3.6.1.4.1.5528.30.10.16
netBotz-prd-bot-switch-enabledDoor switch enabled(1) or disabled(0).rw
INTEGER
.1.3.6.1.4.1.5528.30.10.17
netBotz-prd-bot-audio-levelAudio level setting. This is the relative audio level, from 0-11, above which an alarm will be sent.rw
INTEGER
.1.3.6.1.4.1.5528.30.10.18
netBotz-prd-bot-doorpic-delayNumber of seconds between door alert and first picture.rw
INTEGER
.1.3.6.1.4.1.5528.30.10.19
netBotz-prd-bot-trap-indexThe crawler ID of the last trap.ro
INTEGER
.1.3.6.1.4.1.5528.30.10.20
netBotz-prd-bot-trap-addressThe IP address of the last trap.ro
IpAddress
.1.3.6.1.4.1.5528.30.10.21
netBotz-prd-bot-trap-oidThe object id of the last trap.ro
OBJECT IDENTIFIER
.1.3.6.1.4.1.5528.30.10.22
netBotz-prd-bot-trap-valueThe value of the last object trap.ro
INTEGER
.1.3.6.1.4.1.5528.30.10.23
netBotz-prd-bot-trap-dateThe date and time of a specific trap. This field contains the number of seconds elapsed since midnight (00:00:00), January 1, 1970ro
INTEGER
.1.3.6.1.4.1.5528.30.10.24
netBotz-prd-bot-refreshRate of web page refresh, in seconds. This must be greater than 5 seconds.rw
INTEGER
.1.3.6.1.4.1.5528.30.10.26
netBotz-prd-bot-airflow-levelAirflow alert level. This is the relative level of airflow below which an alarm will be sent. The range is 1-11. Each unit is approximately 40 feet/second or 13 meters/second of airflow velocity.rw
INTEGER
.1.3.6.1.4.1.5528.30.10.27
netBotz-prd-bot-doorpic-countNumber of pictures to take when door activated. These pictures will be sent as attachments to the door alert e-mail. The range is from 0 to 5 pictures.rw
INTEGER
.1.3.6.1.4.1.5528.30.10.28
netBotz-prd-bot-amps1The reading of the first amperage probe, in milliamps.ro
INTEGER
.1.3.6.1.4.1.5528.30.10.29
netBotz-prd-bot-amps1-enabledAmperage[1] probe alarm enabled(1) or disabled(0).rw
INTEGER
.1.3.6.1.4.1.5528.30.10.30
netBotz-prd-bot-amps1-minThe amperage[1] probe minimum, from 0 to 30000 milliamps.rw
INTEGER
.1.3.6.1.4.1.5528.30.10.31
netBotz-prd-bot-amps1-maxThe amperage[1] probe maximum, from 0 to 30000 milliamps.rw
INTEGER
.1.3.6.1.4.1.5528.30.10.32
netBotz-prd-bot-amps2The reading of the second amperage probe, in milliamps.ro
INTEGER
.1.3.6.1.4.1.5528.30.10.34
netBotz-prd-bot-amps2-enabledAmperage[2] probe alarm enabled(1) or disabled(0).rw
INTEGER
.1.3.6.1.4.1.5528.30.10.35
netBotz-prd-bot-amps2-minThe amperage[2] probe minimum, from 0 to 30000 milliamps.rw
INTEGER
.1.3.6.1.4.1.5528.30.10.36
netBotz-prd-bot-amps2-maxThe amperage[2] probe maximum, from 0 to 30000 milliamps.rw
INTEGER
.1.3.6.1.4.1.5528.30.10.37
netBotz-prd-bot-amps3The reading of the third amperage probe, in milliamps.ro
INTEGER
.1.3.6.1.4.1.5528.30.10.39
netBotz-prd-bot-amps3-enabledAmperage[3] probe alarm enabled(1) or disabled(0).rw
INTEGER
.1.3.6.1.4.1.5528.30.10.40
netBotz-prd-bot-amps3-minThe amperage[3] probe minimum, from 0 to 30000 milliamps.rw
INTEGER
.1.3.6.1.4.1.5528.30.10.41
netBotz-prd-bot-amps3-maxThe amperage[3] probe maximum, from 0 to 30000 milliamps.rw
INTEGER
.1.3.6.1.4.1.5528.30.10.42
netBotz-prd-bot-amps-totalThe total of the readings of all amperage probes, in milliamps.ro
INTEGER
.1.3.6.1.4.1.5528.30.10.44
netBotz-prd-bot-amps-total-enabledTotal amperage alarm enabled(1) or disabled(0).rw
INTEGER
.1.3.6.1.4.1.5528.30.10.45
netBotz-prd-bot-amps-total-minThe total amperage minimum, from 0 to 90000 milliamps.rw
INTEGER
.1.3.6.1.4.1.5528.30.10.46
netBotz-prd-bot-amps-total-maxThe total amperage maximum, from 0 to 90000 milliamps.rw
INTEGER
.1.3.6.1.4.1.5528.30.10.47
netBotz-prd-bot-amps-total-support-enabledTotal Amperage Support enabled(Y) or disabled(N).rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.5528.30.10.48
netBotz-prd-bot-amps1-uV-per-10mAThe scaling factor used for the first amperage probe to convert microvolts measured from the Amp Detect into 10s of milliamps of current. Needs to be set based on the type of Amp Detect module installed.rw
INTEGER
.1.3.6.1.4.1.5528.30.10.49
netBotz-prd-bot-amps2-uV-per-10mAThe scaling factor used for the second amperage probe to convert microvolts measured from the Amp Detect into 10s of milliamps of current. Needs to be set based on the type of Amp Detect module installed.rw
INTEGER
.1.3.6.1.4.1.5528.30.10.50
netBotz-prd-bot-amps3-uV-per-mAThe scaling factor used for the third amperage probe to convert microvolts measured from the Amp Detect into 10s of milliamps of current. Needs to be set based on the type of Amp Detect module installed.rw
INTEGER
.1.3.6.1.4.1.5528.30.10.51
netBotz-prd-bot-amps1-max-rangeThe maximum RMS milliamps measureable by the first Amp Detect.rw
INTEGER
.1.3.6.1.4.1.5528.30.10.52
netBotz-prd-bot-amps2-max-rangeThe maximum RMS milliamps measureable by the second Amp Detect.rw
INTEGER
.1.3.6.1.4.1.5528.30.10.53
netBotz-prd-bot-amps3-max-rangeThe maximum RMS milliamps measureable by the third Amp Detect.rw
INTEGER
.1.3.6.1.4.1.5528.30.10.54
netBotz-prd-bot-amps4The reading of the fourth amperage probe, in milliamps.ro
INTEGER
.1.3.6.1.4.1.5528.30.10.55
netBotz-prd-bot-amps4-enabledAmperage[4] probe alarm enabled(1) or disabled(0).rw
INTEGER
.1.3.6.1.4.1.5528.30.10.56
netBotz-prd-bot-amps4-minThe amperage[4] probe minimum, in milliamps.rw
INTEGER
.1.3.6.1.4.1.5528.30.10.57
netBotz-prd-bot-amps4-maxThe amperage[4] probe maximum, in milliamps.rw
INTEGER
.1.3.6.1.4.1.5528.30.10.58
netBotz-prd-bot-amps4-uV-per-10mAThe scaling factor used for the fourth amperage probe to convert microvolts measured from the Amp Detect into 10s of milliamps of current. Needs to be set based on the type of Amp Detect module installed.rw
INTEGER
.1.3.6.1.4.1.5528.30.10.60
netBotz-prd-bot-amps4-max-rangeThe maximum RMS milliamps measureable by the fourth Amp Detect.rw
INTEGER
.1.3.6.1.4.1.5528.30.10.61
netBotz-prd-bot-ext-temp1The reading of the external temperature probe on port 1, in degrees F or degrees C (depends on netBotz-ismetric).ro
INTEGER
.1.3.6.1.4.1.5528.30.10.62
netBotz-prd-bot-ext-temp2The reading of the external temperature probe on port 2, in degrees F or degrees C (depends on netBotz-ismetric).ro
INTEGER
.1.3.6.1.4.1.5528.30.10.63
netBotz-prd-bot-ext-temp3The reading of the external temperature probe on port 3, in degrees F or degrees C (depends on netBotz-ismetric).ro
INTEGER
.1.3.6.1.4.1.5528.30.10.64
netBotz-prd-bot-ext-temp4The reading of the external temperature probe on port 4, in degrees F or degrees C (depends on netBotz-ismetric).ro
INTEGER
.1.3.6.1.4.1.5528.30.10.65
netBotz-prd-bot-ext-temp1-enabledExternal temperature probe on port 1 alarm enabled(1) or disabled(0).rw
INTEGER
.1.3.6.1.4.1.5528.30.10.66
netBotz-prd-bot-ext-temp1-minThe external temperature probe on port 1 probe minimum, in degrees F or degrees C (depends on netBotz-ismetric).rw
INTEGER
.1.3.6.1.4.1.5528.30.10.67
netBotz-prd-bot-ext-temp1-maxThe external temperature probe on port 1 probe maximum, in degrees F or degrees C (depends on netBotz-ismetric).rw
INTEGER
.1.3.6.1.4.1.5528.30.10.68
netBotz-prd-bot-ext-temp2-enabledExternal temperature probe on port 2 alarm enabled(1) or disabled(0).rw
INTEGER
.1.3.6.1.4.1.5528.30.10.69
netBotz-prd-bot-ext-temp2-minThe external temperature probe on port 2 probe minimum, in degrees F or degrees C (depends on netBotz-ismetric).rw
INTEGER
.1.3.6.1.4.1.5528.30.10.70
netBotz-prd-bot-ext-temp2-maxThe external temperature probe on port 2 probe maximum, in degrees F or degrees C (depends on netBotz-ismetric).rw
INTEGER
.1.3.6.1.4.1.5528.30.10.71
netBotz-prd-bot-ext-temp3-enabledExternal temperature probe on port 3 alarm enabled(1) or disabled(0).rw
INTEGER
.1.3.6.1.4.1.5528.30.10.72
netBotz-prd-bot-ext-temp3-minThe external temperature probe on port 3 probe minimum, in degrees F or degrees C (depends on netBotz-ismetric).rw
INTEGER
.1.3.6.1.4.1.5528.30.10.73
netBotz-prd-bot-ext-temp3-maxThe external temperature probe on port 3 probe maximum, in degrees F or degrees C (depends on netBotz-ismetric).rw
INTEGER
.1.3.6.1.4.1.5528.30.10.74
netBotz-prd-bot-ext-temp4-enabledExternal temperature probe on port 4 alarm enabled(1) or disabled(0).rw
INTEGER
.1.3.6.1.4.1.5528.30.10.75
netBotz-prd-bot-ext-temp4-minThe external temperature probe on port 4 probe minimum, in degrees F or degrees C (depends on netBotz-ismetric).rw
INTEGER
.1.3.6.1.4.1.5528.30.10.76
netBotz-prd-bot-ext-temp4-maxThe external temperature probe on port 4 probe maximum, in degrees F or degrees C (depends on netBotz-ismetric).rw
INTEGER
.1.3.6.1.4.1.5528.30.10.77
netBotz-prd-bot-ext-temp1-uV-per-degreeCThe scaling factor used for the external temperature probe on port 1 to convert microvolts measured from the temperature sensor into degrees C. Needs to be set based on the type of temperature sensor module installed.rw
INTEGER
.1.3.6.1.4.1.5528.30.10.78
netBotz-prd-bot-ext-temp1-uV-at-0-degreeCThe offset used for the external temperature probe on port 1 of microvolts measured from the temperature sensor at zero degrees C. Needs to be set based on the type of temperature sensor module installed.rw
INTEGER
.1.3.6.1.4.1.5528.30.10.79
netBotz-prd-bot-ext-temp1-min-rangeThe minimum temperature measureable by the temperature sensor installed on port 1, in tenths of a degree C. Needs to be set based on the type of temperature sensor module installed.rw
INTEGER
.1.3.6.1.4.1.5528.30.10.80
netBotz-prd-bot-ext-temp1-max-rangeThe maximum temperature measureable by the temperature sensor installed on port 1, in tenths of a degree C. Needs to be set based on the type of temperature sensor module installed.rw
INTEGER
.1.3.6.1.4.1.5528.30.10.81
netBotz-prd-bot-ext-temp2-uV-per-degreeCThe scaling factor used for the external temperature probe on port 2 to convert microvolts measured from the temperature sensor into degrees C. Needs to be set based on the type of temperature sensor module installed.rw
INTEGER
.1.3.6.1.4.1.5528.30.10.82
netBotz-prd-bot-ext-temp2-uV-at-0-degreeCThe offset used for the external temperature probe on port 2 of microvolts measured from the temperature sensor at zero degrees C. Needs to be set based on the type of temperature sensor module installed.rw
INTEGER
.1.3.6.1.4.1.5528.30.10.83
netBotz-prd-bot-ext-temp2-min-rangeThe minimum temperature measureable by the temperature sensor installed on port 2, in tenths of a degree C. Needs to be set based on the type of temperature sensor module installed.rw
INTEGER
.1.3.6.1.4.1.5528.30.10.84
netBotz-prd-bot-ext-temp2-max-rangeThe maximum temperature measureable by the temperature sensor installed on port 2, in tenths of a degree C. Needs to be set based on the type of temperature sensor module installed.rw
INTEGER
.1.3.6.1.4.1.5528.30.10.85
netBotz-prd-bot-ext-temp3-uV-per-degreeCThe scaling factor used for the external temperature probe on port 3 to convert microvolts measured from the temperature sensor into degrees C. Needs to be set based on the type of temperature sensor module installed.rw
INTEGER
.1.3.6.1.4.1.5528.30.10.86
netBotz-prd-bot-ext-temp3-uV-at-0-degreeCThe offset used for the external temperature probe on port 3 of microvolts measured from the temperature sensor at zero degrees C. Needs to be set based on the type of temperature sensor module installed.rw
INTEGER
.1.3.6.1.4.1.5528.30.10.87
netBotz-prd-bot-ext-temp3-min-rangeThe minimum temperature measureable by the temperature sensor installed on port 3, in tenths of a degree C. Needs to be set based on the type of temperature sensor module installed.rw
INTEGER
.1.3.6.1.4.1.5528.30.10.88
netBotz-prd-bot-ext-temp3-max-rangeThe maximum temperature measureable by the temperature sensor installed on port 3, in tenths of a degree C. Needs to be set based on the type of temperature sensor module installed.rw
INTEGER
.1.3.6.1.4.1.5528.30.10.89
netBotz-prd-bot-ext-temp4-uV-per-degreeCThe scaling factor used for the external temperature probe on port 4 to convert microvolts measured from the temperature sensor into degrees C. Needs to be set based on the type of temperature sensor module installed.rw
INTEGER
.1.3.6.1.4.1.5528.30.10.90
netBotz-prd-bot-ext-temp4-uV-at-0-degreeCThe offset used for the external temperature probe on port 4 of microvolts measured from the temperature sensor at zero degrees C. Needs to be set based on the type of temperature sensor module installed.rw
INTEGER
.1.3.6.1.4.1.5528.30.10.91
netBotz-prd-bot-ext-temp4-min-rangeThe minimum temperature measureable by the temperature sensor installed on port 4, in tenths of a degree C. Needs to be set based on the type of temperature sensor module installed.rw
INTEGER
.1.3.6.1.4.1.5528.30.10.92
netBotz-prd-bot-ext-temp4-max-rangeThe maximum temperature measureable by the temperature sensor installed on port 4, in tenths of a degree C. Needs to be set based on the type of temperature sensor module installed.rw
INTEGER
.1.3.6.1.4.1.5528.30.10.93
netBotz-prd-bot-ext-port1-module-idThe module ID of the sensor module installed on port 1. Blank string indicates that no module is installed.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.5528.30.10.94
netBotz-prd-bot-ext-port1-module-typeThe type of sensor module installed on port 1. NONE=no module, AMP=AmpDetect module, TEMP=temperature sensor, DRY=dry contact sensor.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.5528.30.10.95
netBotz-prd-bot-ext-port2-module-idThe module ID of the sensor module installed on port 2. Blank string indicates that no module is installed.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.5528.30.10.96
netBotz-prd-bot-ext-port2-module-typeThe type of sensor module installed on port 2. NONE=no module, AMP=AmpDetect module, TEMP=temperature sensor, DRY=dry contact sensor.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.5528.30.10.97
netBotz-prd-bot-ext-port3-module-idThe module ID of the sensor module installed on port 3. Blank string indicates that no module is installed.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.5528.30.10.98
netBotz-prd-bot-ext-port3-module-typeThe type of sensor module installed on port 3. NONE=no module, AMP=AmpDetect module, TEMP=temperature sensor, DRY=dry contact sensor.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.5528.30.10.99
netBotz-prd-bot-ext-port4-module-idThe module ID of the sensor module installed on port 4. Blank string indicates that no module is installed.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.5528.30.10.100
netBotz-prd-bot-ext-port4-module-typeThe type of sensor module installed on port 4. NONE=no module, AMP=AmpDetect module, TEMP=temperature sensor, DRY=dry contact sensor.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.5528.30.10.101
netBotz-prd-bot-amp1-total-amp-secondsThe accumulated total of amp-seconds on the AmpDetect on port 1.ro
INTEGER
.1.3.6.1.4.1.5528.30.10.102
netBotz-prd-bot-amp1-total-amp-seconds-since-timeThe UTC time (seconds since 1/1/1970) of the beginning of the accumulated total of amp-seconds on the AmpDetect on port 1. Writing a value to this attribute resets the accumulated total amp-seconds and sets this time to the current time.rw
INTEGER
.1.3.6.1.4.1.5528.30.10.103
netBotz-prd-bot-amp2-total-amp-secondsThe accumulated total of amp-seconds on the AmpDetect on port 2.ro
INTEGER
.1.3.6.1.4.1.5528.30.10.104
netBotz-prd-bot-amp2-total-amp-seconds-since-timeThe UTC time (seconds since 1/1/1970) of the beginning of the accumulated total of amp-seconds on the AmpDetect on port 2. Writing a value to this attribute resets the accumulated total amp-seconds and sets this time to the current time.rw
INTEGER
.1.3.6.1.4.1.5528.30.10.105
netBotz-prd-bot-amp3-total-amp-secondsThe accumulated total of amp-seconds on the AmpDetect on port 3.ro
INTEGER
.1.3.6.1.4.1.5528.30.10.106
netBotz-prd-bot-amp3-total-amp-seconds-since-timeThe UTC time (seconds since 1/1/1970) of the beginning of the accumulated total of amp-seconds on the AmpDetect on port 3. Writing a value to this attribute resets the accumulated total amp-seconds and sets this time to the current time.rw
INTEGER
.1.3.6.1.4.1.5528.30.10.107
netBotz-prd-bot-amp4-total-amp-secondsThe accumulated total of amp-seconds on the AmpDetect on port 4.ro
INTEGER
.1.3.6.1.4.1.5528.30.10.108
netBotz-prd-bot-amp4-total-amp-seconds-since-timeThe UTC time (seconds since 1/1/1970) of the beginning of the accumulated total of amp-seconds on the AmpDetect on port 4. Writing a value to this attribute resets the accumulated total amp-seconds and sets this time to the current time.rw
INTEGER
.1.3.6.1.4.1.5528.30.10.109
netBotz-prd-bot-amptotal-total-amp-secondsThe accumulated total of amp-seconds on the total of all AmpDetects.ro
INTEGER
.1.3.6.1.4.1.5528.30.10.110
netBotz-prd-bot-amptotal-total-amp-seconds-since-timeThe UTC time (seconds since 1/1/1970) of the beginning of the accumulated total of amp-seconds for all AmpDetects. Writing a value to this attribute resets the accumulated total amp-seconds and sets this time to the current time.rw
INTEGER
.1.3.6.1.4.1.5528.30.10.111
netBotz-prd-bot-ext-dry1The current value of the external dry contact sensor on Ext1: 0=Open, 1=Closed, -1=N/Aro
INTEGER
.1.3.6.1.4.1.5528.30.10.112
netBotz-prd-bot-ext-dry2The current value of the external dry contact sensor on Ext2: 0=Open, 1=Closed, -1=N/Aro
INTEGER
.1.3.6.1.4.1.5528.30.10.113
netBotz-prd-bot-ext-dry3The current value of the external dry contact sensor on Ext3: 0=Open, 1=Closed, -1=N/Aro
INTEGER
.1.3.6.1.4.1.5528.30.10.114
netBotz-prd-bot-ext-dry4The current value of the external dry contact sensor on Ext4: 0=Open, 1=Closed, -1=N/Aro
INTEGER
.1.3.6.1.4.1.5528.30.10.115
netBotz-prd-bot-ext-dry1-alarm-valueThe value to generate alarms on for the external dry contact sensor on Ext1: 0=Open, 1=Closedrw
INTEGER
.1.3.6.1.4.1.5528.30.10.116
netBotz-prd-bot-ext-dry1-enabledExternal dry contact sensor on Ext1 alarm enabled(1) or disabled(0).rw
INTEGER
.1.3.6.1.4.1.5528.30.10.117
netBotz-prd-bot-ext-dry2-alarm-valueThe value to generate alarms on for the external dry contact sensor on Ext2: 0=Open, 1=Closedrw
INTEGER
.1.3.6.1.4.1.5528.30.10.118
netBotz-prd-bot-ext-dry2-enabledExternal dry contact sensor on Ext2 alarm enabled(1) or disabled(0).rw
INTEGER
.1.3.6.1.4.1.5528.30.10.119
netBotz-prd-bot-ext-dry3-alarm-valueThe value to generate alarms on for the external dry contact sensor on Ext3: 0=Open, 1=Closedrw
INTEGER
.1.3.6.1.4.1.5528.30.10.120
netBotz-prd-bot-ext-dry3-enabledExternal dry contact sensor on Ext3 alarm enabled(1) or disabled(0).rw
INTEGER
.1.3.6.1.4.1.5528.30.10.121
netBotz-prd-bot-ext-dry4-alarm-valueThe value to generate alarms on for the external dry contact sensor on Ext4: 0=Open, 1=Closedrw
INTEGER
.1.3.6.1.4.1.5528.30.10.122
netBotz-prd-bot-ext-dry4-enabledExternal dry contact sensor on Ext4 alarm enabled(1) or disabled(0).rw
INTEGER
.1.3.6.1.4.1.5528.30.10.123
netBotz-prd-bot-ext-dry1-labelThe sensor name/label for the dry contact sensor on Ext1rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.5528.30.10.124
netBotz-prd-bot-ext-dry1-open-labelThe sensor name/label for the open(0) state for the dry contact sensor on Ext1rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.5528.30.10.125
netBotz-prd-bot-ext-dry1-closed-labelThe sensor name/label for the closed(0) state for the dry contact sensor on Ext1rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.5528.30.10.126
netBotz-prd-bot-ext-dry1-open-to-close-millisThe minimum number of milliseconds that the dry contact sensor on Ext1 must read closed before the state is changed from open to closed.rw
INTEGER
.1.3.6.1.4.1.5528.30.10.127
netBotz-prd-bot-ext-dry1-close-to-open-millisThe minimum number of milliseconds that the dry contact sensor on Ext1 must read openbefore the state is changed from closed to open.rw
INTEGER
.1.3.6.1.4.1.5528.30.10.128
netBotz-prd-bot-ext-dry1-responseThe type of alert response for the dry contact sensor on Ext1: ALERT=e-mail with no pictures, CAMERA=e-mail with pictures from camera.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.5528.30.10.129
netBotz-prd-bot-ext-dry2-labelThe sensor name/label for the dry contact sensor on Ext2rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.5528.30.10.130
netBotz-prd-bot-ext-dry2-open-labelThe sensor name/label for the open(0) state for the dry contact sensor on Ext2rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.5528.30.10.131
netBotz-prd-bot-ext-dry2-closed-labelThe sensor name/label for the closed(0) state for the dry contact sensor on Ext2rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.5528.30.10.132
netBotz-prd-bot-ext-dry2-open-to-close-millisThe minimum number of milliseconds that the dry contact sensor on Ext2 must read closed before the state is changed from open to closed.rw
INTEGER
.1.3.6.1.4.1.5528.30.10.133
netBotz-prd-bot-ext-dry2-close-to-open-millisThe minimum number of milliseconds that the dry contact sensor on Ext2 must read openbefore the state is changed from closed to open.rw
INTEGER
.1.3.6.1.4.1.5528.30.10.134
netBotz-prd-bot-ext-dry2-responseThe type of alert response for the dry contact sensor on Ext2: ALERT=e-mail with no pictures, CAMERA=e-mail with pictures from camera.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.5528.30.10.135
netBotz-prd-bot-ext-dry3-labelThe sensor name/label for the dry contact sensor on Ext3rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.5528.30.10.136
netBotz-prd-bot-ext-dry3-open-labelThe sensor name/label for the open(0) state for the dry contact sensor on Ext3rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.5528.30.10.137
netBotz-prd-bot-ext-dry3-closed-labelThe sensor name/label for the closed(0) state for the dry contact sensor on Ext3rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.5528.30.10.138
netBotz-prd-bot-ext-dry3-open-to-close-millisThe minimum number of milliseconds that the dry contact sensor on Ext3 must read closed before the state is changed from open to closed.rw
INTEGER
.1.3.6.1.4.1.5528.30.10.139
netBotz-prd-bot-ext-dry3-close-to-open-millisThe minimum number of milliseconds that the dry contact sensor on Ext3 must read openbefore the state is changed from closed to open.rw
INTEGER
.1.3.6.1.4.1.5528.30.10.140
netBotz-prd-bot-ext-dry3-responseThe type of alert response for the dry contact sensor on Ext3: ALERT=e-mail with no pictures, CAMERA=e-mail with pictures from camera.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.5528.30.10.141
netBotz-prd-bot-ext-dry4-labelThe sensor name/label for the dry contact sensor on Ext4rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.5528.30.10.142
netBotz-prd-bot-ext-dry4-open-labelThe sensor name/label for the open(0) state for the dry contact sensor on Ext4rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.5528.30.10.143
netBotz-prd-bot-ext-dry4-closed-labelThe sensor name/label for the closed(0) state for the dry contact sensor on Ext4rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.5528.30.10.144
netBotz-prd-bot-ext-dry4-open-to-close-millisThe minimum number of milliseconds that the dry contact sensor on Ext4 must read closed before the state is changed from open to closed.rw
INTEGER
.1.3.6.1.4.1.5528.30.10.145
netBotz-prd-bot-ext-dry4-close-to-open-millisThe minimum number of milliseconds that the dry contact sensor on Ext4 must read openbefore the state is changed from closed to open.rw
INTEGER
.1.3.6.1.4.1.5528.30.10.146
netBotz-prd-bot-ext-dry4-responseThe type of alert response for the dry contact sensor on Ext4: ALERT=e-mail with no pictures, CAMERA=e-mail with pictures from camera.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.5528.30.10.147
netBotz-prd-bot-traps
OBJECT IDENTIFIER
.1.3.6.1.4.1.5528.30.100
netBotz-prd-bot-temperature-traps
OBJECT IDENTIFIER
.1.3.6.1.4.1.5528.30.100.1
netBotz-prd-bot-temperature-low-trapNetbotz Temperature Low Trap. This trap indicates that the lower limit for temperature has been exceeded.
TRAP-TYPE
.1.3.6.1.4.1.5528.30.100.1.0.1
netBotz-prd-bot-temperature-high-trapNetbotz Temperature High Trap. This trap indicates that the upper limit for temperature has been exceeded.
TRAP-TYPE
.1.3.6.1.4.1.5528.30.100.1.0.2
netBotz-prd-bot-temperature-trap-clearNetbotz Temperature Cleared Trap. The trap has been cleared because the temperature value has returned to acceptable limits.
TRAP-TYPE
.1.3.6.1.4.1.5528.30.100.1.0.3
netBotz-prd-bot-humidity-traps
OBJECT IDENTIFIER
.1.3.6.1.4.1.5528.30.100.2
netBotz-prd-bot-humidity-low-trapNetbotz Humidity Low Trap. This trap indicates that the lower limit for humidity has been exceeded.
TRAP-TYPE
.1.3.6.1.4.1.5528.30.100.2.0.1
netBotz-prd-bot-humidity-high-trapNetbotz Humidity High Trap. This trap indicates that the upper limit for humidity has been exceeded.
TRAP-TYPE
.1.3.6.1.4.1.5528.30.100.2.0.2
netBotz-prd-bot-humidity-trap-clearNetbotz Humidity Cleared Trap. The trap has been cleared because the humidity value has returned to acceptable limits.
TRAP-TYPE
.1.3.6.1.4.1.5528.30.100.2.0.3
netBotz-prd-bot-airflow-traps
OBJECT IDENTIFIER
.1.3.6.1.4.1.5528.30.100.3
netBotz-prd-bot-airflow-low-trapNetbotz Airflow Low Trap. This trap indicates that the lower limit for airflow has been exceeded.
TRAP-TYPE
.1.3.6.1.4.1.5528.30.100.3.0.1
netBotz-prd-bot-airflow-trap-clearNetbotz Airflow Cleared Trap. The trap has been cleared because the airflow value has returned to acceptable limits.
TRAP-TYPE
.1.3.6.1.4.1.5528.30.100.3.0.3
netBotz-prd-bot-audio-traps
OBJECT IDENTIFIER
.1.3.6.1.4.1.5528.30.100.4
netBotz-prd-bot-audio-high-trapNetbotz Audio High Trap. This trap indicates that the upper limit for audio has been exceeded.
TRAP-TYPE
.1.3.6.1.4.1.5528.30.100.4.0.2
netBotz-prd-bot-audio-trap-clearNetbotz Audio Cleared Trap. The trap has been cleared because the audio value has returned to acceptable limits.
TRAP-TYPE
.1.3.6.1.4.1.5528.30.100.4.0.3
netBotz-prd-bot-door-traps
OBJECT IDENTIFIER
.1.3.6.1.4.1.5528.30.100.5
netBotz-prd-bot-door-trap-trippedNetbotz Door Sensor Tripped Trap. This trap indicates that the door sensor has been triggered (i.e. opened, if the thresdhold has been set to trip on open, closed if otherwise).
TRAP-TYPE
.1.3.6.1.4.1.5528.30.100.5.0.2
netBotz-prd-bot-door-trap-clearNetbotz Door Cleared Trap. The trap has been cleared because the door sensor has returned to normal (i.e. been closed, if the threshold has been set to trip on open).
TRAP-TYPE
.1.3.6.1.4.1.5528.30.100.5.0.3
netBotz-prd-bot-amp1-traps
OBJECT IDENTIFIER
.1.3.6.1.4.1.5528.30.100.6
netBotz-prd-bot-amp1-low-trapNetbotz Amp1 Low Trap. This trap indicates that the lower limit for the first amp detect has been exceeded.
TRAP-TYPE
.1.3.6.1.4.1.5528.30.100.6.0.1
netBotz-prd-bot-amp1-high-trapNetbotz Amp1 High Trap. This trap indicates that the upper limit for the first amp detect has been exceeded.
TRAP-TYPE
.1.3.6.1.4.1.5528.30.100.6.0.2
netBotz-prd-bot-amp1-trap-clearNetbotz Amp1 Cleared Trap. The trap has been cleared because the first amp detect value has returned to acceptable limits.
TRAP-TYPE
.1.3.6.1.4.1.5528.30.100.6.0.3
netBotz-prd-bot-amp1-sensor-unpluggedNetbotz Amp 1 Sensor Unplugged Trap. The sensor for the first AmpDetect is unplugged or malfunctioning.
TRAP-TYPE
.1.3.6.1.4.1.5528.30.100.6.0.6
netBotz-prd-bot-amp1-sensor-repluggedNetbotz Amp 1 Sensor Replugged Trap. The sensor for the first AmpDetect was unplugged, but has been reconnected.
TRAP-TYPE
.1.3.6.1.4.1.5528.30.100.6.0.7
netBotz-prd-bot-amp2-traps
OBJECT IDENTIFIER
.1.3.6.1.4.1.5528.30.100.7
netBotz-prd-bot-amp2-low-trapNetbotz Amp2 Low Trap. This trap indicates that the lower limit for the second amp detect has been exceeded.
TRAP-TYPE
.1.3.6.1.4.1.5528.30.100.7.0.1
netBotz-prd-bot-amp2-high-trapNetbotz Amp2 High Trap. This trap indicates that the upper limit for the second amp detect has been exceeded.
TRAP-TYPE
.1.3.6.1.4.1.5528.30.100.7.0.2
netBotz-prd-bot-amp2-trap-clearNetbotz Amp2 Cleared Trap. The trap has been cleared because the second amp detect value has returned to acceptable limits.
TRAP-TYPE
.1.3.6.1.4.1.5528.30.100.7.0.3
netBotz-prd-bot-amp2-sensor-unpluggedNetbotz Amp 2 Sensor Unplugged Trap. The sensor for the second AmpDetect is unplugged or malfunctioning.
TRAP-TYPE
.1.3.6.1.4.1.5528.30.100.7.0.6
netBotz-prd-bot-amp2-sensor-repluggedNetbotz Amp 2 Sensor Replugged Trap. The sensor for the second AmpDetect was unplugged, but has been reconnected.
TRAP-TYPE
.1.3.6.1.4.1.5528.30.100.7.0.7
netBotz-prd-bot-amp3-traps
OBJECT IDENTIFIER
.1.3.6.1.4.1.5528.30.100.8
netBotz-prd-bot-amp3-low-trapNetbotz Amp3 Low Trap. This trap indicates that the lower limit for the third amp detect has been exceeded.
TRAP-TYPE
.1.3.6.1.4.1.5528.30.100.8.0.1
netBotz-prd-bot-amp3-high-trapNetbotz Amp3 High Trap. This trap indicates that the upper limit for the third amp detect has been exceeded.
TRAP-TYPE
.1.3.6.1.4.1.5528.30.100.8.0.2
netBotz-prd-bot-amp3-trap-clearNetbotz Amp3 Cleared Trap. The trap has been cleared because the third amp detect value has returned to acceptable limits.
TRAP-TYPE
.1.3.6.1.4.1.5528.30.100.8.0.3
netBotz-prd-bot-amp3-sensor-unpluggedNetbotz Amp 3 Sensor Unplugged Trap. The sensor for the third AmpDetect is unplugged or malfunctioning.
TRAP-TYPE
.1.3.6.1.4.1.5528.30.100.8.0.6
netBotz-prd-bot-amp3-sensor-repluggedNetbotz Amp 3 Sensor Replugged Trap. The sensor for the third AmpDetect was unplugged, but has been reconnected.
TRAP-TYPE
.1.3.6.1.4.1.5528.30.100.8.0.7
netBotz-prd-bot-amp4-traps
OBJECT IDENTIFIER
.1.3.6.1.4.1.5528.30.100.9
netBotz-prd-bot-amp4-low-trapNetbotz Amp4 Low Trap. This trap indicates that the lower limit for the fourth amp detect has been exceeded.
TRAP-TYPE
.1.3.6.1.4.1.5528.30.100.9.0.1
netBotz-prd-bot-amp4-high-trapNetbotz Amp4 High Trap. This trap indicates that the upper limit for the fourth amp detect has been exceeded.
TRAP-TYPE
.1.3.6.1.4.1.5528.30.100.9.0.2
netBotz-prd-bot-amp4-trap-clearNetbotz Amp4 Cleared Trap. The trap has been cleared because the fourth amp detect value has returned to acceptable limits.
TRAP-TYPE
.1.3.6.1.4.1.5528.30.100.9.0.3
netBotz-prd-bot-amp4-sensor-unpluggedNetbotz Amp 4 Sensor Unplugged Trap. The sensor for the fourth AmpDetect is unplugged or malfunctioning.
TRAP-TYPE
.1.3.6.1.4.1.5528.30.100.9.0.6
netBotz-prd-bot-amp4-sensor-repluggedNetbotz Amp 4 Sensor Replugged Trap. The sensor for the fourth AmpDetect was unplugged, but has been reconnected.
TRAP-TYPE
.1.3.6.1.4.1.5528.30.100.9.0.7
netBotz-prd-bot-amp-total-traps
OBJECT IDENTIFIER
.1.3.6.1.4.1.5528.30.100.10
netBotz-prd-bot-amp-total-low-trapNetbotz Total Amps Low Trap. This trap indicates that the lower limit for the total amperage has been exceeded.
TRAP-TYPE
.1.3.6.1.4.1.5528.30.100.10.0.1
netBotz-prd-bot-amp-total-high-trapNetbotz Total Amps High Trap. This trap indicates that the upper limit for the total amperage has been exceeded.
TRAP-TYPE
.1.3.6.1.4.1.5528.30.100.10.0.2
netBotz-prd-bot-amp-total-trap-clearNetbotz Total Amps Cleared Trap. The trap has been cleared because the total amperage value has returned to acceptable limits.
TRAP-TYPE
.1.3.6.1.4.1.5528.30.100.10.0.3
netBotz-prd-bot-ext-temp1-traps
OBJECT IDENTIFIER
.1.3.6.1.4.1.5528.30.100.11
netBotz-prd-bot-ext-temp1-low-trapNetbotz External Temperature 1 Low Trap. This trap indicates that the lower limit for external temperature probe on port 1 has been exceeded.
TRAP-TYPE
.1.3.6.1.4.1.5528.30.100.11.0.1
netBotz-prd-bot-ext-temp1-high-trapNetbotz External Temperature 1 High Trap. This trap indicates that the upper limit for external temperature probe on port 1 has been exceeded.
TRAP-TYPE
.1.3.6.1.4.1.5528.30.100.11.0.2
netBotz-prd-bot-ext-temp1-trap-clearNetbotz External Temperature 1 Cleared Trap. The trap has been cleared because the temperature value for the temperature probe on port 1 has returned to acceptable limits.
TRAP-TYPE
.1.3.6.1.4.1.5528.30.100.11.0.3
netBotz-prd-bot-ext-temp1-sensor-unpluggedNetbotz External Temperature 1 Sensor Unplugged Trap. The sensor is unplugged or malfunctioning.
TRAP-TYPE
.1.3.6.1.4.1.5528.30.100.11.0.6
netBotz-prd-bot-ext-temp1-sensor-repluggedNetbotz External Temperature 1 Sensor Replugged Trap. The sensor was unplugged, but has been reconnected.
TRAP-TYPE
.1.3.6.1.4.1.5528.30.100.11.0.7
netBotz-prd-bot-ext-temp2-traps
OBJECT IDENTIFIER
.1.3.6.1.4.1.5528.30.100.12
netBotz-prd-bot-ext-temp2-low-trapNetbotz External Temperature 2 Low Trap. This trap indicates that the lower limit for external temperature probe on port 2 has been exceeded.
TRAP-TYPE
.1.3.6.1.4.1.5528.30.100.12.0.1
netBotz-prd-bot-ext-temp2-high-trapNetbotz External Temperature 2 High Trap. This trap indicates that the upper limit for external temperature probe on port 2 has been exceeded.
TRAP-TYPE
.1.3.6.1.4.1.5528.30.100.12.0.2
netBotz-prd-bot-ext-temp2-trap-clearNetbotz External Temperature 2 Cleared Trap. The trap has been cleared because the temperature value for the temperature probe on port 2 has returned to acceptable limits.
TRAP-TYPE
.1.3.6.1.4.1.5528.30.100.12.0.3
netBotz-prd-bot-ext-temp2-sensor-unpluggedNetbotz External Temperature 2 Sensor Unplugged Trap. The sensor is unplugged or malfunctioning.
TRAP-TYPE
.1.3.6.1.4.1.5528.30.100.12.0.6
netBotz-prd-bot-ext-temp2-sensor-repluggedNetbotz External Temperature 2 Sensor Replugged Trap. The sensor was unplugged, but has been reconnected.
TRAP-TYPE
.1.3.6.1.4.1.5528.30.100.12.0.7
netBotz-prd-bot-ext-temp3-traps
OBJECT IDENTIFIER
.1.3.6.1.4.1.5528.30.100.13
netBotz-prd-bot-ext-temp3-low-trapNetbotz External Temperature 3 Low Trap. This trap indicates that the lower limit for external temperature probe on port 3 has been exceeded.
TRAP-TYPE
.1.3.6.1.4.1.5528.30.100.13.0.1
netBotz-prd-bot-ext-temp3-high-trapNetbotz External Temperature 3 High Trap. This trap indicates that the upper limit for external temperature probe on port 3 has been exceeded.
TRAP-TYPE
.1.3.6.1.4.1.5528.30.100.13.0.2
netBotz-prd-bot-ext-temp3-trap-clearNetbotz External Temperature 3 Cleared Trap. The trap has been cleared because the temperature value for the temperature probe on port 3 has returned to acceptable limits.
TRAP-TYPE
.1.3.6.1.4.1.5528.30.100.13.0.3
netBotz-prd-bot-ext-temp3-sensor-unpluggedNetbotz External Temperature 3 Sensor Unplugged Trap. The sensor is unplugged or malfunctioning.
TRAP-TYPE
.1.3.6.1.4.1.5528.30.100.13.0.6
netBotz-prd-bot-ext-temp3-sensor-repluggedNetbotz External Temperature 3 Sensor Replugged Trap. The sensor was unplugged, but has been reconnected.
TRAP-TYPE
.1.3.6.1.4.1.5528.30.100.13.0.7
netBotz-prd-bot-ext-temp4-traps
OBJECT IDENTIFIER
.1.3.6.1.4.1.5528.30.100.14
netBotz-prd-bot-ext-temp4-low-trapNetbotz External Temperature 4 Low Trap. This trap indicates that the lower limit for external temperature probe on port 4 has been exceeded.
TRAP-TYPE
.1.3.6.1.4.1.5528.30.100.14.0.1
netBotz-prd-bot-ext-temp4-high-trapNetbotz External Temperature 4 High Trap. This trap indicates that the upper limit for external temperature probe on port 4 has been exceeded.
TRAP-TYPE
.1.3.6.1.4.1.5528.30.100.14.0.2
netBotz-prd-bot-ext-temp4-trap-clearNetbotz External Temperature 4 Cleared Trap. The trap has been cleared because the temperature value for the temperature probe on port 4 has returned to acceptable limits.
TRAP-TYPE
.1.3.6.1.4.1.5528.30.100.14.0.3
netBotz-prd-bot-ext-temp4-sensor-unpluggedNetbotz External Temperature 4 Sensor Unplugged Trap. The sensor is unplugged or malfunctioning.
TRAP-TYPE
.1.3.6.1.4.1.5528.30.100.14.0.6
netBotz-prd-bot-ext-temp4-sensor-repluggedNetbotz External Temperature 4 Sensor Replugged Trap. The sensor was unplugged, but has been reconnected.
TRAP-TYPE
.1.3.6.1.4.1.5528.30.100.14.0.7
netBotz-prd-bot-ext-dry1-traps
OBJECT IDENTIFIER
.1.3.6.1.4.1.5528.30.100.15
netBotz-prd-bot-ext-dry1-triggered-trapNetbotz External Dry Contact 1 Triggered Trap. This trap indicates that the state of the dry contact sensor on Ext1 matches the alarm value.
TRAP-TYPE
.1.3.6.1.4.1.5528.30.100.15.0.2
netBotz-prd-bot-ext-dry1-trap-clearNetbotz External Dry Contact 1 Cleared Trap. The trap has been cleared because the state of the dry contact sensor on Ext1 no longer matches the alarm value.
TRAP-TYPE
.1.3.6.1.4.1.5528.30.100.15.0.3
netBotz-prd-bot-ext-dry2-traps
OBJECT IDENTIFIER
.1.3.6.1.4.1.5528.30.100.16
netBotz-prd-bot-ext-dry2-triggered-trapNetbotz External Dry Contact 2 Triggered Trap. This trap indicates that the state of the dry contact sensor on Ext2 matches the alarm value.
TRAP-TYPE
.1.3.6.1.4.1.5528.30.100.16.0.2
netBotz-prd-bot-ext-dry2-trap-clearNetbotz External Dry Contact 2 Cleared Trap. The trap has been cleared because the state of the dry contact sensor on Ext2 no longer matches the alarm value.
TRAP-TYPE
.1.3.6.1.4.1.5528.30.100.16.0.3
netBotz-prd-bot-ext-dry3-traps
OBJECT IDENTIFIER
.1.3.6.1.4.1.5528.30.100.17
netBotz-prd-bot-ext-dry3-triggered-trapNetbotz External Dry Contact 3 Triggered Trap. This trap indicates that the state of the dry contact sensor on Ext3 matches the alarm value.
TRAP-TYPE
.1.3.6.1.4.1.5528.30.100.17.0.2
netBotz-prd-bot-ext-dry3-trap-clearNetbotz External Dry Contact 3 Cleared Trap. The trap has been cleared because the state of the dry contact sensor on Ext3 no longer matches the alarm value.
TRAP-TYPE
.1.3.6.1.4.1.5528.30.100.17.0.3
netBotz-prd-bot-ext-dry4-traps
OBJECT IDENTIFIER
.1.3.6.1.4.1.5528.30.100.18
netBotz-prd-bot-ext-dry4-triggered-trapNetbotz External Dry Contact 4 Triggered Trap. This trap indicates that the state of the dry contact sensor on Ext4 matches the alarm value.
TRAP-TYPE
.1.3.6.1.4.1.5528.30.100.18.0.2
netBotz-prd-bot-ext-dry4-trap-clearNetbotz External Dry Contact 4 Cleared Trap. The trap has been cleared because the state of the dry contact sensor on Ext4 no longer matches the alarm value.
TRAP-TYPE
.1.3.6.1.4.1.5528.30.100.18.0.3