NETBOTZ-MIB
Detailed view of the defined objects, syntax rules, and hierarchical paths.
534
Objects
Active
Status
4
Dependencies
Imported Objects
Objects
534 total| Object Name |
|---|
netBotz OBJECT IDENTIFIER .1.3.6.1.4.1.5528 |
IMPORTS Unknown .1.3.6.1.4.1.5528 |
netBotz-reg OBJECT IDENTIFIER .1.3.6.1.4.1.5528.10 |
netBotz-generic OBJECT IDENTIFIER .1.3.6.1.4.1.5528.20 |
netBotz-products OBJECT IDENTIFIER .1.3.6.1.4.1.5528.30 |
netBotz-prd-bot OBJECT IDENTIFIER .1.3.6.1.4.1.5528.30.10 |
netBotz-prd-bot-low-trapNetBotz Low Trap. This trap indicates that a lower
limit has been exceeded. TRAP-TYPE .1.3.6.1.4.1.5528.30.10.0.1 |
netBotz-prd-bot-high-trapNetBotz High Trap. This trap indicates that an upper
limit has been exceeded. TRAP-TYPE .1.3.6.1.4.1.5528.30.10.0.2 |
netBotz-prd-bot-trap-clearNetBotz Cleared Trap. The trap has been cleared because
the value has returned to acceptable limits. TRAP-TYPE .1.3.6.1.4.1.5528.30.10.0.3 |
netBotz-prd-bot-offline-trapNetBotz Device Offline Trap. This trap indicates that a device or function
has been determined to be offline. TRAP-TYPE .1.3.6.1.4.1.5528.30.10.0.4 |
netBotz-prd-bot-online-trapNetBotz Device Online Trap. This trap indicates that a device or function
has been determined to be online. TRAP-TYPE .1.3.6.1.4.1.5528.30.10.0.5 |
netBotz-prd-bot-tempThe reading of the temperature probe, in degrees F or degrees C (depends on netBotz-ismetric).ro INTEGER .1.3.6.1.4.1.5528.30.10.1 |
netBotz-prd-bot-humidityThe reading of the humidity probe, in percent.ro INTEGER .1.3.6.1.4.1.5528.30.10.2 |
netBotz-prd-bot-airflowThe reading of the airflow probe. Each unit represents approximately 40 feet/minute or
13 meters/minute of airflow velocity.ro INTEGER .1.3.6.1.4.1.5528.30.10.3 |
netBotz-prd-bot-audioThe reading of the audio alarm probe on/off.ro INTEGER .1.3.6.1.4.1.5528.30.10.4 |
netBotz-prd-bot-doorajarThe reading of the door switch probe open(1) or closed(0).ro INTEGER .1.3.6.1.4.1.5528.30.10.5 |
netBotz-prd-bot-temp-minThe temperature probe minimum, from 35 to 120 degrees F, or 1 to 50 degrees C (depends on netBotz-ismetric).rw INTEGER .1.3.6.1.4.1.5528.30.10.6 |
netBotz-prd-bot-temp-maxThe temperature probe maximum, from 35 to 120 degrees F, or 1 to 50 degrees C (depends on netBotz-ismetric).rw INTEGER .1.3.6.1.4.1.5528.30.10.7 |
netBotz-prd-bot-humidity-minThe humidity probe minimum, from 10 to 90 percent.rw INTEGER .1.3.6.1.4.1.5528.30.10.8 |
netBotz-prd-bot-humidity-maxThe humidity probe maximum, from 10 to 90 percent.rw INTEGER .1.3.6.1.4.1.5528.30.10.9 |
netBotz-prd-bot-airflow-minsMinutes without airflow before alarm set.rw INTEGER .1.3.6.1.4.1.5528.30.10.10 |
netBotz-prd-bot-audio-secsSeconds of alarm audio before alarm set.rw INTEGER .1.3.6.1.4.1.5528.30.10.11 |
netBotz-prd-bot-temp-enabledTemperature probe alarm enabled(1) or disabled(0).rw INTEGER .1.3.6.1.4.1.5528.30.10.12 |
netBotz-prd-bot-hum-enabledHumidity probe alarm enabled(1) or disabled(0).rw INTEGER .1.3.6.1.4.1.5528.30.10.13 |
netBotz-prd-bot-air-enabledAirflow probe alarm enabled(1) or disabled(0).rw INTEGER .1.3.6.1.4.1.5528.30.10.14 |
netBotz-prd-bot-audio-enabledAudio probe alarm enabled(1) or disabled(0).rw INTEGER .1.3.6.1.4.1.5528.30.10.15 |
netBotz-prd-bot-switch-stateSwitch state setting. The state controls which
condition of the door switch indicates an alarm.
If set to 0, alarm is set when the switch is closed.
If set to 1, alarm is set when the switch is open.rw INTEGER .1.3.6.1.4.1.5528.30.10.16 |
netBotz-prd-bot-switch-enabledDoor switch enabled(1) or disabled(0).rw INTEGER .1.3.6.1.4.1.5528.30.10.17 |
netBotz-prd-bot-audio-levelAudio level setting. This is the relative audio level, from 0-11,
above which an alarm will be sent.rw INTEGER .1.3.6.1.4.1.5528.30.10.18 |
netBotz-prd-bot-trap-indexThe crawler ID of the last trap.ro INTEGER .1.3.6.1.4.1.5528.30.10.20 |
netBotz-prd-bot-trap-addressThe IP address of the last trap.ro IpAddress .1.3.6.1.4.1.5528.30.10.21 |
netBotz-prd-bot-trap-oidThe object id of the last trap.ro OBJECT IDENTIFIER .1.3.6.1.4.1.5528.30.10.22 |
netBotz-prd-bot-trap-valueThe value of the last object trap.ro INTEGER .1.3.6.1.4.1.5528.30.10.23 |
netBotz-prd-bot-trap-dateThe date and time of a specific trap. This field
contains the number of seconds elapsed since
midnight (00:00:00), January 1, 1970ro INTEGER .1.3.6.1.4.1.5528.30.10.24 |
netBotz-prd-bot-refreshRate of web page refresh, in seconds. This must be greater than 5 seconds.rw INTEGER .1.3.6.1.4.1.5528.30.10.26 |
netBotz-prd-bot-airflow-levelAirflow alert level. This is the relative level of airflow below which
an alarm will be sent. The range is 1-11. Each unit is approximately 40 feet/second or 13 meters/second of
airflow velocity.rw INTEGER .1.3.6.1.4.1.5528.30.10.27 |
netBotz-prd-bot-doorpic-countNumber of pictures to take when door activated.
These pictures will be sent as attachments to the door alert e-mail.
The range is from 0 to 5 pictures.rw INTEGER .1.3.6.1.4.1.5528.30.10.28 |
netBotz-prd-bot-amps1The reading of the first amperage probe, in milliamps.ro INTEGER .1.3.6.1.4.1.5528.30.10.29 |
netBotz-prd-bot-amps1-enabledAmperage[1] probe alarm enabled(1) or disabled(0).rw INTEGER .1.3.6.1.4.1.5528.30.10.30 |
netBotz-prd-bot-amps1-minThe amperage[1] probe minimum, from 0 to 30000 milliamps.rw INTEGER .1.3.6.1.4.1.5528.30.10.31 |
netBotz-prd-bot-amps1-maxThe amperage[1] probe maximum, from 0 to 30000 milliamps.rw INTEGER .1.3.6.1.4.1.5528.30.10.32 |
netBotz-prd-bot-amps2The reading of the second amperage probe, in milliamps.ro INTEGER .1.3.6.1.4.1.5528.30.10.34 |
netBotz-prd-bot-amps2-enabledAmperage[2] probe alarm enabled(1) or disabled(0).rw INTEGER .1.3.6.1.4.1.5528.30.10.35 |
netBotz-prd-bot-amps2-minThe amperage[2] probe minimum, from 0 to 30000 milliamps.rw INTEGER .1.3.6.1.4.1.5528.30.10.36 |
netBotz-prd-bot-amps2-maxThe amperage[2] probe maximum, from 0 to 30000 milliamps.rw INTEGER .1.3.6.1.4.1.5528.30.10.37 |
netBotz-prd-bot-amps3The reading of the third amperage probe, in milliamps.ro INTEGER .1.3.6.1.4.1.5528.30.10.39 |
netBotz-prd-bot-amps3-enabledAmperage[3] probe alarm enabled(1) or disabled(0).rw INTEGER .1.3.6.1.4.1.5528.30.10.40 |
netBotz-prd-bot-amps3-minThe amperage[3] probe minimum, from 0 to 30000 milliamps.rw INTEGER .1.3.6.1.4.1.5528.30.10.41 |
netBotz-prd-bot-amps3-maxThe amperage[3] probe maximum, from 0 to 30000 milliamps.rw INTEGER .1.3.6.1.4.1.5528.30.10.42 |
netBotz-prd-bot-amps-totalThe total of the readings of all amperage probes, in milliamps.ro INTEGER .1.3.6.1.4.1.5528.30.10.44 |
netBotz-prd-bot-amps-total-enabledTotal amperage alarm enabled(1) or disabled(0).rw INTEGER .1.3.6.1.4.1.5528.30.10.45 |
netBotz-prd-bot-amps-total-minThe total amperage minimum, from 0 to 90000 milliamps.rw INTEGER .1.3.6.1.4.1.5528.30.10.46 |
netBotz-prd-bot-amps-total-maxThe total amperage maximum, from 0 to 90000 milliamps.rw INTEGER .1.3.6.1.4.1.5528.30.10.47 |
netBotz-prd-bot-amps-total-support-enabledTotal Amperage Support enabled(Y) or disabled(N).rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.5528.30.10.48 |
netBotz-prd-bot-amps1-uV-per-10mAThe scaling factor used for the first amperage probe to convert microvolts measured from the
Amp Detect into 10s of milliamps of current. Needs to be set based on the type of Amp Detect module installed.rw INTEGER .1.3.6.1.4.1.5528.30.10.49 |
netBotz-prd-bot-amps2-uV-per-10mAThe scaling factor used for the second amperage probe to convert microvolts measured from the
Amp Detect into 10s of milliamps of current. Needs to be set based on the type of Amp Detect module installed.rw INTEGER .1.3.6.1.4.1.5528.30.10.50 |
netBotz-prd-bot-amps3-uV-per-mAThe scaling factor used for the third amperage probe to convert microvolts measured from the
Amp Detect into 10s of milliamps of current. Needs to be set based on the type of Amp Detect module installed.rw INTEGER .1.3.6.1.4.1.5528.30.10.51 |
netBotz-prd-bot-amps1-max-rangeThe maximum RMS milliamps measureable by the first Amp Detect.rw INTEGER .1.3.6.1.4.1.5528.30.10.52 |
netBotz-prd-bot-amps2-max-rangeThe maximum RMS milliamps measureable by the second Amp Detect.rw INTEGER .1.3.6.1.4.1.5528.30.10.53 |
netBotz-prd-bot-amps3-max-rangeThe maximum RMS milliamps measureable by the third Amp Detect.rw INTEGER .1.3.6.1.4.1.5528.30.10.54 |
netBotz-prd-bot-amps4The reading of the fourth amperage probe, in milliamps.ro INTEGER .1.3.6.1.4.1.5528.30.10.55 |
netBotz-prd-bot-amps4-enabledAmperage[4] probe alarm enabled(1) or disabled(0).rw INTEGER .1.3.6.1.4.1.5528.30.10.56 |
netBotz-prd-bot-amps4-minThe amperage[4] probe minimum, in milliamps.rw INTEGER .1.3.6.1.4.1.5528.30.10.57 |
netBotz-prd-bot-amps4-maxThe amperage[4] probe maximum, in milliamps.rw INTEGER .1.3.6.1.4.1.5528.30.10.58 |
netBotz-prd-bot-amps4-uV-per-10mAThe scaling factor used for the fourth amperage probe to convert microvolts measured from the
Amp Detect into 10s of milliamps of current. Needs to be set based on the type of Amp Detect module installed.rw INTEGER .1.3.6.1.4.1.5528.30.10.60 |
netBotz-prd-bot-amps4-max-rangeThe maximum RMS milliamps measureable by the fourth Amp Detect.rw INTEGER .1.3.6.1.4.1.5528.30.10.61 |
netBotz-prd-bot-ext-temp1The reading of the external temperature probe on port 1, in degrees F or degrees C (depends on netBotz-ismetric).ro INTEGER .1.3.6.1.4.1.5528.30.10.62 |
netBotz-prd-bot-ext-temp2The reading of the external temperature probe on port 2, in degrees F or degrees C (depends on netBotz-ismetric).ro INTEGER .1.3.6.1.4.1.5528.30.10.63 |
netBotz-prd-bot-ext-temp3The reading of the external temperature probe on port 3, in degrees F or degrees C (depends on netBotz-ismetric).ro INTEGER .1.3.6.1.4.1.5528.30.10.64 |
netBotz-prd-bot-ext-temp1-enabledExternal temperature probe on port 1 alarm enabled(1) or disabled(0).rw INTEGER .1.3.6.1.4.1.5528.30.10.66 |
netBotz-prd-bot-ext-temp1-minThe external temperature probe on port 1 probe minimum, in degrees F or degrees C (depends on netBotz-ismetric).rw INTEGER .1.3.6.1.4.1.5528.30.10.67 |
netBotz-prd-bot-ext-temp1-maxThe external temperature probe on port 1 probe maximum, in degrees F or degrees C (depends on netBotz-ismetric).rw INTEGER .1.3.6.1.4.1.5528.30.10.68 |
netBotz-prd-bot-ext-temp2-enabledExternal temperature probe on port 2 alarm enabled(1) or disabled(0).rw INTEGER .1.3.6.1.4.1.5528.30.10.69 |
netBotz-prd-bot-ext-temp2-minThe external temperature probe on port 2 probe minimum, in degrees F or degrees C (depends on netBotz-ismetric).rw INTEGER .1.3.6.1.4.1.5528.30.10.70 |
netBotz-prd-bot-ext-temp2-maxThe external temperature probe on port 2 probe maximum, in degrees F or degrees C (depends on netBotz-ismetric).rw INTEGER .1.3.6.1.4.1.5528.30.10.71 |
netBotz-prd-bot-ext-temp3-enabledExternal temperature probe on port 3 alarm enabled(1) or disabled(0).rw INTEGER .1.3.6.1.4.1.5528.30.10.72 |
netBotz-prd-bot-ext-temp3-minThe external temperature probe on port 3 probe minimum, in degrees F or degrees C (depends on netBotz-ismetric).rw INTEGER .1.3.6.1.4.1.5528.30.10.73 |
netBotz-prd-bot-ext-temp3-maxThe external temperature probe on port 3 probe maximum, in degrees F or degrees C (depends on netBotz-ismetric).rw INTEGER .1.3.6.1.4.1.5528.30.10.74 |
netBotz-prd-bot-ext-temp1-uV-per-degreeCThe scaling factor used for the external temperature probe on port 1 to convert microvolts measured from the
temperature sensor into degrees C. Needs to be set based on the type of temperature sensor module installed.rw INTEGER .1.3.6.1.4.1.5528.30.10.78 |
netBotz-prd-bot-ext-temp1-uV-at-0-degreeCThe offset used for the external temperature probe on port 1 of microvolts measured from the
temperature sensor at zero degrees C. Needs to be set based on the type of temperature sensor module installed.rw INTEGER .1.3.6.1.4.1.5528.30.10.79 |
netBotz-prd-bot-ext-temp1-min-rangeThe minimum temperature measureable by the temperature sensor installed on port 1, in tenths of a degree C.
Needs to be set based on the type of temperature sensor module installed.rw INTEGER .1.3.6.1.4.1.5528.30.10.80 |
netBotz-prd-bot-ext-temp1-max-rangeThe maximum temperature measureable by the temperature sensor installed on port 1, in tenths of a degree C.
Needs to be set based on the type of temperature sensor module installed.rw INTEGER .1.3.6.1.4.1.5528.30.10.81 |
netBotz-prd-bot-ext-temp2-uV-per-degreeCThe scaling factor used for the external temperature probe on port 2 to convert microvolts measured from the
temperature sensor into degrees C. Needs to be set based on the type of temperature sensor module installed.rw INTEGER .1.3.6.1.4.1.5528.30.10.82 |
netBotz-prd-bot-ext-temp2-uV-at-0-degreeCThe offset used for the external temperature probe on port 2 of microvolts measured from the
temperature sensor at zero degrees C. Needs to be set based on the type of temperature sensor module installed.rw INTEGER .1.3.6.1.4.1.5528.30.10.83 |
netBotz-prd-bot-ext-temp2-min-rangeThe minimum temperature measureable by the temperature sensor installed on port 2, in tenths of a degree C.
Needs to be set based on the type of temperature sensor module installed.rw INTEGER .1.3.6.1.4.1.5528.30.10.84 |
netBotz-prd-bot-ext-temp2-max-rangeThe maximum temperature measureable by the temperature sensor installed on port 2, in tenths of a degree C.
Needs to be set based on the type of temperature sensor module installed.rw INTEGER .1.3.6.1.4.1.5528.30.10.85 |
netBotz-prd-bot-ext-temp3-uV-per-degreeCThe scaling factor used for the external temperature probe on port 3 to convert microvolts measured from the
temperature sensor into degrees C. Needs to be set based on the type of temperature sensor module installed.rw INTEGER .1.3.6.1.4.1.5528.30.10.86 |
netBotz-prd-bot-ext-temp3-uV-at-0-degreeCThe offset used for the external temperature probe on port 3 of microvolts measured from the
temperature sensor at zero degrees C. Needs to be set based on the type of temperature sensor module installed.rw INTEGER .1.3.6.1.4.1.5528.30.10.87 |
netBotz-prd-bot-ext-temp3-min-rangeThe minimum temperature measureable by the temperature sensor installed on port 3, in tenths of a degree C.
Needs to be set based on the type of temperature sensor module installed.rw INTEGER .1.3.6.1.4.1.5528.30.10.88 |
netBotz-prd-bot-ext-temp3-max-rangeThe maximum temperature measureable by the temperature sensor installed on port 3, in tenths of a degree C.
Needs to be set based on the type of temperature sensor module installed.rw INTEGER .1.3.6.1.4.1.5528.30.10.89 |
netBotz-prd-bot-ext-port1-module-idThe module ID of the sensor module installed on port 1. Blank string indicates that no module is installed.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.5528.30.10.94 |
netBotz-prd-bot-ext-port1-module-typeThe type of sensor module installed on port 1. NONE=no module, AMP=AmpDetect module, TEMP=temperature sensor, DRY=dry contact sensor.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.5528.30.10.95 |
netBotz-prd-bot-ext-port2-module-idThe module ID of the sensor module installed on port 2. Blank string indicates that no module is installed.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.5528.30.10.96 |
netBotz-prd-bot-ext-port2-module-typeThe type of sensor module installed on port 2. NONE=no module, AMP=AmpDetect module, TEMP=temperature sensor, DRY=dry contact sensor.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.5528.30.10.97 |
netBotz-prd-bot-ext-port3-module-idThe module ID of the sensor module installed on port 3. Blank string indicates that no module is installed.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.5528.30.10.98 |
netBotz-prd-bot-ext-port3-module-typeThe type of sensor module installed on port 3. NONE=no module, AMP=AmpDetect module, TEMP=temperature sensor, DRY=dry contact sensor.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.5528.30.10.99 |
netBotz-prd-bot-amp1-total-amp-secondsThe accumulated total of amp-seconds on the AmpDetect on port 1.ro INTEGER .1.3.6.1.4.1.5528.30.10.102 |
netBotz-prd-bot-amp1-total-amp-seconds-since-timeThe UTC time (seconds since 1/1/1970) of the beginning of the accumulated total of amp-seconds on the AmpDetect on port 1.
Writing a value to this attribute resets the accumulated total amp-seconds and sets this time to the current time.rw INTEGER .1.3.6.1.4.1.5528.30.10.103 |
netBotz-prd-bot-amp2-total-amp-secondsThe accumulated total of amp-seconds on the AmpDetect on port 2.ro INTEGER .1.3.6.1.4.1.5528.30.10.104 |
netBotz-prd-bot-amp2-total-amp-seconds-since-timeThe UTC time (seconds since 1/1/1970) of the beginning of the accumulated total of amp-seconds on the AmpDetect on port 2.
Writing a value to this attribute resets the accumulated total amp-seconds and sets this time to the current time.rw INTEGER .1.3.6.1.4.1.5528.30.10.105 |
netBotz-prd-bot-amp3-total-amp-secondsThe accumulated total of amp-seconds on the AmpDetect on port 3.ro INTEGER .1.3.6.1.4.1.5528.30.10.106 |
netBotz-prd-bot-amp3-total-amp-seconds-since-timeThe UTC time (seconds since 1/1/1970) of the beginning of the accumulated total of amp-seconds on the AmpDetect on port 3.
Writing a value to this attribute resets the accumulated total amp-seconds and sets this time to the current time.rw INTEGER .1.3.6.1.4.1.5528.30.10.107 |
netBotz-prd-bot-amp4-total-amp-secondsThe accumulated total of amp-seconds on the AmpDetect on port 4.ro INTEGER .1.3.6.1.4.1.5528.30.10.108 |
netBotz-prd-bot-amp4-total-amp-seconds-since-timeThe UTC time (seconds since 1/1/1970) of the beginning of the accumulated total of amp-seconds on the AmpDetect on port 4.
Writing a value to this attribute resets the accumulated total amp-seconds and sets this time to the current time.rw INTEGER .1.3.6.1.4.1.5528.30.10.109 |
netBotz-prd-bot-amptotal-total-amp-secondsThe accumulated total of amp-seconds on the total of all AmpDetects.ro INTEGER .1.3.6.1.4.1.5528.30.10.110 |
netBotz-prd-bot-amptotal-total-amp-seconds-since-timeThe UTC time (seconds since 1/1/1970) of the beginning of the accumulated total of amp-seconds for all AmpDetects.
Writing a value to this attribute resets the accumulated total amp-seconds and sets this time to the current time.rw INTEGER .1.3.6.1.4.1.5528.30.10.111 |
netBotz-prd-bot-ext-dry1The current value of the external dry contact sensor on Ext1: 0=Open, 1=Closed, -1=N/Aro INTEGER .1.3.6.1.4.1.5528.30.10.112 |
netBotz-prd-bot-ext-dry2The current value of the external dry contact sensor on Ext2: 0=Open, 1=Closed, -1=N/Aro INTEGER .1.3.6.1.4.1.5528.30.10.113 |
netBotz-prd-bot-ext-dry3The current value of the external dry contact sensor on Ext3: 0=Open, 1=Closed, -1=N/Aro INTEGER .1.3.6.1.4.1.5528.30.10.114 |
netBotz-prd-bot-ext-dry4The current value of the external dry contact sensor on Ext4: 0=Open, 1=Closed, -1=N/Aro INTEGER .1.3.6.1.4.1.5528.30.10.115 |
netBotz-prd-bot-ext-dry1-alarm-valueThe value to generate alarms on for the external dry contact sensor on Ext1: 0=Open, 1=Closedrw INTEGER .1.3.6.1.4.1.5528.30.10.116 |
netBotz-prd-bot-ext-dry1-enabledExternal dry contact sensor on Ext1 alarm enabled(1) or disabled(0).rw INTEGER .1.3.6.1.4.1.5528.30.10.117 |
netBotz-prd-bot-ext-dry2-alarm-valueThe value to generate alarms on for the external dry contact sensor on Ext2: 0=Open, 1=Closedrw INTEGER .1.3.6.1.4.1.5528.30.10.118 |
netBotz-prd-bot-ext-dry2-enabledExternal dry contact sensor on Ext2 alarm enabled(1) or disabled(0).rw INTEGER .1.3.6.1.4.1.5528.30.10.119 |
netBotz-prd-bot-ext-dry3-alarm-valueThe value to generate alarms on for the external dry contact sensor on Ext3: 0=Open, 1=Closedrw INTEGER .1.3.6.1.4.1.5528.30.10.120 |
netBotz-prd-bot-ext-dry3-enabledExternal dry contact sensor on Ext3 alarm enabled(1) or disabled(0).rw INTEGER .1.3.6.1.4.1.5528.30.10.121 |
netBotz-prd-bot-ext-dry4-alarm-valueThe value to generate alarms on for the external dry contact sensor on Ext4: 0=Open, 1=Closedrw INTEGER .1.3.6.1.4.1.5528.30.10.122 |
netBotz-prd-bot-ext-dry4-enabledExternal dry contact sensor on Ext4 alarm enabled(1) or disabled(0).rw INTEGER .1.3.6.1.4.1.5528.30.10.123 |
netBotz-prd-bot-ext-dry1-labelThe sensor name/label for the dry contact sensor on Ext1rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.5528.30.10.124 |
netBotz-prd-bot-ext-dry1-open-labelThe sensor name/label for the open(0) state for the dry contact sensor on Ext1rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.5528.30.10.125 |
netBotz-prd-bot-ext-dry1-closed-labelThe sensor name/label for the closed(0) state for the dry contact sensor on Ext1rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.5528.30.10.126 |
netBotz-prd-bot-ext-dry1-open-to-close-millisThe minimum number of milliseconds that the dry contact sensor on Ext1
must read closed before the state is changed from open to closed.rw INTEGER .1.3.6.1.4.1.5528.30.10.127 |
netBotz-prd-bot-ext-dry1-close-to-open-millisThe minimum number of milliseconds that the dry contact sensor on Ext1
must read openbefore the state is changed from closed to open.rw INTEGER .1.3.6.1.4.1.5528.30.10.128 |
netBotz-prd-bot-ext-dry1-responseThe type of alert response for the dry contact sensor on Ext1: ALERT=e-mail with no
pictures, CAMERA=e-mail with pictures from camera.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.5528.30.10.129 |
netBotz-prd-bot-ext-dry2-labelThe sensor name/label for the dry contact sensor on Ext2rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.5528.30.10.130 |
netBotz-prd-bot-ext-dry2-open-labelThe sensor name/label for the open(0) state for the dry contact sensor on Ext2rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.5528.30.10.131 |
netBotz-prd-bot-ext-dry2-closed-labelThe sensor name/label for the closed(0) state for the dry contact sensor on Ext2rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.5528.30.10.132 |
netBotz-prd-bot-ext-dry2-open-to-close-millisThe minimum number of milliseconds that the dry contact sensor on Ext2
must read closed before the state is changed from open to closed.rw INTEGER .1.3.6.1.4.1.5528.30.10.133 |
netBotz-prd-bot-ext-dry2-close-to-open-millisThe minimum number of milliseconds that the dry contact sensor on Ext2
must read openbefore the state is changed from closed to open.rw INTEGER .1.3.6.1.4.1.5528.30.10.134 |
netBotz-prd-bot-ext-dry2-responseThe type of alert response for the dry contact sensor on Ext2: ALERT=e-mail with no
pictures, CAMERA=e-mail with pictures from camera.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.5528.30.10.135 |
netBotz-prd-bot-ext-dry3-labelThe sensor name/label for the dry contact sensor on Ext3rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.5528.30.10.136 |
netBotz-prd-bot-ext-dry3-open-labelThe sensor name/label for the open(0) state for the dry contact sensor on Ext3rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.5528.30.10.137 |
netBotz-prd-bot-ext-dry3-closed-labelThe sensor name/label for the closed(0) state for the dry contact sensor on Ext3rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.5528.30.10.138 |
netBotz-prd-bot-ext-dry3-open-to-close-millisThe minimum number of milliseconds that the dry contact sensor on Ext3
must read closed before the state is changed from open to closed.rw INTEGER .1.3.6.1.4.1.5528.30.10.139 |
netBotz-prd-bot-ext-dry3-close-to-open-millisThe minimum number of milliseconds that the dry contact sensor on Ext3
must read openbefore the state is changed from closed to open.rw INTEGER .1.3.6.1.4.1.5528.30.10.140 |
netBotz-prd-bot-ext-dry3-responseThe type of alert response for the dry contact sensor on Ext3: ALERT=e-mail with no
pictures, CAMERA=e-mail with pictures from camera.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.5528.30.10.141 |
netBotz-prd-bot-cam-motionThe current motion reading for the camera motion sensor (0=none, 1=motion detected)ro INTEGER .1.3.6.1.4.1.5528.30.10.148 |
netBotz-prd-bot-cam-motion-enabledCamera motion sensor alarm enabled(1) or disabled(0).rw INTEGER .1.3.6.1.4.1.5528.30.10.149 |
netBotz-prd-bot-cam-motion-sensitivityCamera motion sensor sensitivity: 1=max, 15=min, 0=disabled.rw INTEGER .1.3.6.1.4.1.5528.30.10.150 |
netBotz-prd-bot-cam-motion-delayCamera motion sensor delay. This is the minimum number of milliseconds of detected
motion required before the alarm is triggered.rw INTEGER .1.3.6.1.4.1.5528.30.10.151 |
netBotz-prd-bot-camera-event-autocycleEnables (1) or disables (0) the option to have the camera-based responses to
alarm conditions automatically cycle as long as the condition persists.rw INTEGER .1.3.6.1.4.1.5528.30.10.152 |
netBotz-prd-bot-num-pix-before-alarmControls the number of pictures to be captured before any triggered alarm.rw INTEGER .1.3.6.1.4.1.5528.30.10.153 |
netBotz-prd-bot-delay-before-event-pixControls the number of milliseconds before the first picture is captured
after any triggered alarm.rw INTEGER .1.3.6.1.4.1.5528.30.10.154 |
netBotz-prd-bot-delay-between-event-pixControls the number of milliseconds between pictures captured
after any triggered alarm.rw INTEGER .1.3.6.1.4.1.5528.30.10.155 |
netBotz-prd-bot-cam-motion-area-of-motionCamera motion sensor area of motion: 1=max, 15=min, 0=disabled.rw INTEGER .1.3.6.1.4.1.5528.30.10.156 |
netBotz-prd-bot-cam-pix-for-duration-of-alertsCamera images gathered for duration of camera related alert: 0=no, 1=yes.rw INTEGER .1.3.6.1.4.1.5528.30.10.157 |
netBotz-prd-bot-camera-enabledControls whether the camera is enabled or not: 0=no, 1=yes. Changing this will reboot the appliance.rw INTEGER .1.3.6.1.4.1.5528.30.10.158 |
netBotz-prd-bot-camera-is-flippedControls whether the camera image is flipped 180 degress or not: 0=no, 1=yes. Changing this will reboot the appliance.rw INTEGER .1.3.6.1.4.1.5528.30.10.159 |
netBotz-prd-bot-camera-brightnessSets the brightness on the camera, from 20 to 180 (20 is low, 180 is high).rw INTEGER .1.3.6.1.4.1.5528.30.10.160 |
netBotz-prd-crawlers OBJECT IDENTIFIER .1.3.6.1.4.1.5528.30.20 |
netbotz-crawlers OBJECT IDENTIFIER .1.3.6.1.4.1.5528.30.20.5528 |
netBotz-prd-crl-mib2 OBJECT IDENTIFIER .1.3.6.1.4.1.5528.30.20.5528.1 |
netBotz-prd-crl-mib2-pingNetBotz device ping. This object indicates the status of a ping
on a device monitored by a NetBotz device.ro INTEGER .1.3.6.1.4.1.5528.30.20.5528.1.3 |
netBotz-prd-crl-ping-offline-trapNetBotz Ping Trap. This trap indicates that replies to a set of pings were not received from a monitored IP address. TRAP-TYPE .1.3.6.1.4.1.5528.30.20.5528.1.3.0.4 |
netBotz-prd-crl-ping-online-trapNetBotz Ping Trap. This trap indicates that replies to a set of pings were received from a monitored IP address after
a period when no replies had been received. TRAP-TYPE .1.3.6.1.4.1.5528.30.20.5528.1.3.0.5 |
netBotz-prd-crl-mib2-uptimeThe uptime of a device monitored by a NetBotz device.ro TimeTicks (SNMPv2-SMI) .1.3.6.1.4.1.5528.30.20.5528.1.8 |
netBotz-prd-crl-uptime-online-trapNetBotz Uptime Trap. This trap indicates that a device restart has been detected due to the uptime of the device
being reported as less than the previously reported reading. TRAP-TYPE .1.3.6.1.4.1.5528.30.20.5528.1.8.0.5 |
netBotz-prd-crl-mib2-snmpstatusThe SNMP status of a device monitored by a NetBotz device.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.5528.30.20.5528.1.9 |
netBotz-prd-crl-snmp-offline-trapNetBotz SNMP Offline Trap. This trap indicates that an SNMP request was
not possible on an IP address. TRAP-TYPE .1.3.6.1.4.1.5528.30.20.5528.1.9.0.4 |
netBotz-prd-crl-snmp-online-trapNetBotz SNMP Online Trap. This trap indicates that an SNMP request succeeded
on an IP address where it had previously failed. TRAP-TYPE .1.3.6.1.4.1.5528.30.20.5528.1.9.0.5 |
netBotz-prd-crl-mib2if OBJECT IDENTIFIER .1.3.6.1.4.1.5528.30.20.5528.2 |
netBotz-prd-crl-mib2if-opstatusThe operational status of a device monitored by a NetBotz device.ro INTEGER .1.3.6.1.4.1.5528.30.20.5528.2.6 |
netBotz-prd-crl-opstatus-mismatch-trapNetBotz Interface Status Mismatch Trap. This trap indicates that the operational
status of a device interface does not match the administrative status. TRAP-TYPE .1.3.6.1.4.1.5528.30.20.5528.2.6.0.1 |
netBotz-prd-crl-opstatus-match-trapNetBotz Interface Status Match Trap. This trap indicates that the operational
status of a device interface now matches the administrative status. This trap indicates
a transition from a state in which the administrative and operational status did not match. TRAP-TYPE .1.3.6.1.4.1.5528.30.20.5528.2.6.0.2 |
netBotz-prd-crl-opstatus-offline-trapNetBotz Interface Offline Trap. This trap indicates that an interface on a device
did not respond to an SNMP query on the ifAdminStatus or ifOperStatus objects. TRAP-TYPE .1.3.6.1.4.1.5528.30.20.5528.2.6.0.4 |
netBotz-prd-crltrap OBJECT IDENTIFIER .1.3.6.1.4.1.5528.30.21 |
netBotz-prd-crl-trap-indexThe ID of the crawler which sent the last trap.ro INTEGER .1.3.6.1.4.1.5528.30.21.20 |
netBotz-prd-crl-trap-addressThe IP address of the last trap.ro IpAddress .1.3.6.1.4.1.5528.30.21.21 |
netBotz-prd-crl-trap-oidThe object id of the attribute on the target device which is the concern of the last trap.ro OBJECT IDENTIFIER .1.3.6.1.4.1.5528.30.21.22 |
netBotz-prd-crl-trap-botoidThe object id of the attribute on the NetBotz device which is the concern of the last trap.ro OBJECT IDENTIFIER .1.3.6.1.4.1.5528.30.21.23 |
netBotz-prd-crl-trap-valueThe value of the attribute associated with the last trap.ro INTEGER .1.3.6.1.4.1.5528.30.21.24 |
netBotz-prd-crl-trap-dateThe date and time of a specific trap. This field
contains the number of seconds elapsed since
midnight (00:00:00), January 1, 1970ro INTEGER .1.3.6.1.4.1.5528.30.21.25 |
netBotz-prd-crl-trap-attribThe identification number of the attribute in errorro INTEGER .1.3.6.1.4.1.5528.30.21.26 |
netBotz-prd-crl-trap-descDescription or name of the attribute in errorro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.5528.30.21.27 |
netBotz-prd-bot-traps OBJECT IDENTIFIER .1.3.6.1.4.1.5528.30.100 |
netBotz-prd-bot-temperature-traps OBJECT IDENTIFIER .1.3.6.1.4.1.5528.30.100.1 |
netBotz-prd-bot-temperature-low-trapNetBotz Temperature Low Trap. This trap indicates that the lower
limit for temperature has been exceeded. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.1.0.1 |
netBotz-prd-bot-temperature-high-trapNetBotz Temperature High Trap. This trap indicates that the upper
limit for temperature has been exceeded. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.1.0.2 |
netBotz-prd-bot-temperature-trap-clearNetBotz Temperature Cleared Trap. The trap has been cleared because
the temperature value has returned to acceptable limits. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.1.0.3 |
netBotz-prd-bot-humidity-traps OBJECT IDENTIFIER .1.3.6.1.4.1.5528.30.100.2 |
netBotz-prd-bot-humidity-low-trapNetBotz Humidity Low Trap. This trap indicates that the lower
limit for humidity has been exceeded. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.2.0.1 |
netBotz-prd-bot-humidity-high-trapNetBotz Humidity High Trap. This trap indicates that the upper
limit for humidity has been exceeded. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.2.0.2 |
netBotz-prd-bot-humidity-trap-clearNetBotz Humidity Cleared Trap. The trap has been cleared because
the humidity value has returned to acceptable limits. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.2.0.3 |
netBotz-prd-bot-airflow-traps OBJECT IDENTIFIER .1.3.6.1.4.1.5528.30.100.3 |
netBotz-prd-bot-airflow-low-trapNetBotz Airflow Low Trap. This trap indicates that the lower
limit for airflow has been exceeded. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.3.0.1 |
netBotz-prd-bot-airflow-trap-clearNetBotz Airflow Cleared Trap. The trap has been cleared because
the airflow value has returned to acceptable limits. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.3.0.3 |
netBotz-prd-bot-audio-traps OBJECT IDENTIFIER .1.3.6.1.4.1.5528.30.100.4 |
netBotz-prd-bot-audio-high-trapNetBotz Audio High Trap. This trap indicates that the upper
limit for audio has been exceeded. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.4.0.2 |
netBotz-prd-bot-audio-trap-clearNetBotz Audio Cleared Trap. The trap has been cleared because
the audio value has returned to acceptable limits. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.4.0.3 |
netBotz-prd-bot-door-traps OBJECT IDENTIFIER .1.3.6.1.4.1.5528.30.100.5 |
netBotz-prd-bot-door-trap-trippedNetBotz Door Sensor Tripped Trap. This trap indicates that the door sensor
has been triggered (i.e. opened, if the thresdhold has been set to trip on open, closed if otherwise). TRAP-TYPE .1.3.6.1.4.1.5528.30.100.5.0.2 |
netBotz-prd-bot-door-trap-clearNetBotz Door Cleared Trap. The trap has been cleared because
the door sensor has returned to normal (i.e. been closed, if the threshold has been set to trip on open). TRAP-TYPE .1.3.6.1.4.1.5528.30.100.5.0.3 |
netBotz-prd-bot-amp1-traps OBJECT IDENTIFIER .1.3.6.1.4.1.5528.30.100.6 |
netBotz-prd-bot-amp1-low-trapNetBotz Amp1 Low Trap. This trap indicates that the lower
limit for the first amp detect has been exceeded. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.6.0.1 |
netBotz-prd-bot-amp1-high-trapNetBotz Amp1 High Trap. This trap indicates that the upper
limit for the first amp detect has been exceeded. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.6.0.2 |
netBotz-prd-bot-amp1-trap-clearNetBotz Amp1 Cleared Trap. The trap has been cleared because
the first amp detect value has returned to acceptable limits. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.6.0.3 |
netBotz-prd-bot-amp1-sensor-unpluggedNetBotz Amp 1 Sensor Unplugged Trap. The sensor for the first AmpDetect is unplugged or malfunctioning. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.6.0.6 |
netBotz-prd-bot-amp1-sensor-repluggedNetBotz Amp 1 Sensor Replugged Trap. The sensor for the first AmpDetect was unplugged, but has been reconnected. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.6.0.7 |
netBotz-prd-bot-amp2-traps OBJECT IDENTIFIER .1.3.6.1.4.1.5528.30.100.7 |
netBotz-prd-bot-amp2-low-trapNetBotz Amp2 Low Trap. This trap indicates that the lower
limit for the second amp detect has been exceeded. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.7.0.1 |
netBotz-prd-bot-amp2-high-trapNetBotz Amp2 High Trap. This trap indicates that the upper
limit for the second amp detect has been exceeded. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.7.0.2 |
netBotz-prd-bot-amp2-trap-clearNetBotz Amp2 Cleared Trap. The trap has been cleared because
the second amp detect value has returned to acceptable limits. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.7.0.3 |
netBotz-prd-bot-amp2-sensor-unpluggedNetBotz Amp 2 Sensor Unplugged Trap. The sensor for the second AmpDetect is unplugged or malfunctioning. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.7.0.6 |
netBotz-prd-bot-amp2-sensor-repluggedNetBotz Amp 2 Sensor Replugged Trap. The sensor for the second AmpDetect was unplugged, but has been reconnected. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.7.0.7 |
netBotz-prd-bot-amp3-traps OBJECT IDENTIFIER .1.3.6.1.4.1.5528.30.100.8 |
netBotz-prd-bot-amp3-low-trapNetBotz Amp3 Low Trap. This trap indicates that the lower
limit for the third amp detect has been exceeded. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.8.0.1 |
netBotz-prd-bot-amp3-high-trapNetBotz Amp3 High Trap. This trap indicates that the upper
limit for the third amp detect has been exceeded. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.8.0.2 |
netBotz-prd-bot-amp3-trap-clearNetBotz Amp3 Cleared Trap. The trap has been cleared because
the third amp detect value has returned to acceptable limits. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.8.0.3 |
netBotz-prd-bot-amp3-sensor-unpluggedNetBotz Amp 3 Sensor Unplugged Trap. The sensor for the third AmpDetect is unplugged or malfunctioning. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.8.0.6 |
netBotz-prd-bot-amp3-sensor-repluggedNetBotz Amp 3 Sensor Replugged Trap. The sensor for the third AmpDetect was unplugged, but has been reconnected. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.8.0.7 |
netBotz-prd-bot-amp4-traps OBJECT IDENTIFIER .1.3.6.1.4.1.5528.30.100.9 |
netBotz-prd-bot-amp4-low-trapNetBotz Amp4 Low Trap. This trap indicates that the lower
limit for the fourth amp detect has been exceeded. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.9.0.1 |
netBotz-prd-bot-amp4-high-trapNetBotz Amp4 High Trap. This trap indicates that the upper
limit for the fourth amp detect has been exceeded. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.9.0.2 |
netBotz-prd-bot-amp4-trap-clearNetBotz Amp4 Cleared Trap. The trap has been cleared because
the fourth amp detect value has returned to acceptable limits. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.9.0.3 |
netBotz-prd-bot-amp4-sensor-unpluggedNetBotz Amp 4 Sensor Unplugged Trap. The sensor for the fourth AmpDetect is unplugged or malfunctioning. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.9.0.6 |
netBotz-prd-bot-amp4-sensor-repluggedNetBotz Amp 4 Sensor Replugged Trap. The sensor for the fourth AmpDetect was unplugged, but has been reconnected. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.9.0.7 |
netBotz-prd-bot-amp-total-traps OBJECT IDENTIFIER .1.3.6.1.4.1.5528.30.100.10 |
netBotz-prd-bot-amp-total-low-trapNetBotz Total Amps Low Trap. This trap indicates that the lower
limit for the total amperage has been exceeded. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.10.0.1 |
netBotz-prd-bot-amp-total-high-trapNetBotz Total Amps High Trap. This trap indicates that the upper
limit for the total amperage has been exceeded. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.10.0.2 |
netBotz-prd-bot-amp-total-trap-clearNetBotz Total Amps Cleared Trap. The trap has been cleared because
the total amperage value has returned to acceptable limits. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.10.0.3 |
netBotz-prd-bot-ext-temp1-traps OBJECT IDENTIFIER .1.3.6.1.4.1.5528.30.100.11 |
netBotz-prd-bot-ext-temp1-low-trapNetBotz External Temperature 1 Low Trap. This trap indicates that the lower
limit for external temperature probe on port 1 has been exceeded. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.11.0.1 |
netBotz-prd-bot-ext-temp1-high-trapNetBotz External Temperature 1 High Trap. This trap indicates that the upper
limit for external temperature probe on port 1 has been exceeded. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.11.0.2 |
netBotz-prd-bot-ext-temp1-trap-clearNetBotz External Temperature 1 Cleared Trap. The trap has been cleared because
the temperature value for the temperature probe on port 1 has returned to acceptable limits. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.11.0.3 |
netBotz-prd-bot-ext-temp1-sensor-unpluggedNetBotz External Temperature 1 Sensor Unplugged Trap. The sensor is unplugged or malfunctioning. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.11.0.6 |
netBotz-prd-bot-ext-temp1-sensor-repluggedNetBotz External Temperature 1 Sensor Replugged Trap. The sensor was unplugged, but has been reconnected. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.11.0.7 |
netBotz-prd-bot-ext-temp2-traps OBJECT IDENTIFIER .1.3.6.1.4.1.5528.30.100.12 |
netBotz-prd-bot-ext-temp2-low-trapNetBotz External Temperature 2 Low Trap. This trap indicates that the lower
limit for external temperature probe on port 2 has been exceeded. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.12.0.1 |
netBotz-prd-bot-ext-temp2-high-trapNetBotz External Temperature 2 High Trap. This trap indicates that the upper
limit for external temperature probe on port 2 has been exceeded. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.12.0.2 |
netBotz-prd-bot-ext-temp2-trap-clearNetBotz External Temperature 2 Cleared Trap. The trap has been cleared because
the temperature value for the temperature probe on port 2 has returned to acceptable limits. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.12.0.3 |
netBotz-prd-bot-ext-temp2-sensor-unpluggedNetBotz External Temperature 2 Sensor Unplugged Trap. The sensor is unplugged or malfunctioning. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.12.0.6 |
netBotz-prd-bot-ext-temp2-sensor-repluggedNetBotz External Temperature 2 Sensor Replugged Trap. The sensor was unplugged, but has been reconnected. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.12.0.7 |
netBotz-prd-bot-ext-temp3-traps OBJECT IDENTIFIER .1.3.6.1.4.1.5528.30.100.13 |
netBotz-prd-bot-ext-temp3-low-trapNetBotz External Temperature 3 Low Trap. This trap indicates that the lower
limit for external temperature probe on port 3 has been exceeded. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.13.0.1 |
netBotz-prd-bot-ext-temp3-high-trapNetBotz External Temperature 3 High Trap. This trap indicates that the upper
limit for external temperature probe on port 3 has been exceeded. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.13.0.2 |
netBotz-prd-bot-ext-temp3-trap-clearNetBotz External Temperature 3 Cleared Trap. The trap has been cleared because
the temperature value for the temperature probe on port 3 has returned to acceptable limits. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.13.0.3 |
netBotz-prd-bot-ext-temp3-sensor-unpluggedNetBotz External Temperature 3 Sensor Unplugged Trap. The sensor is unplugged or malfunctioning. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.13.0.6 |
netBotz-prd-bot-ext-temp3-sensor-repluggedNetBotz External Temperature 3 Sensor Replugged Trap. The sensor was unplugged, but has been reconnected. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.13.0.7 |
netBotz-prd-bot-ext-temp4-traps OBJECT IDENTIFIER .1.3.6.1.4.1.5528.30.100.14 |
netBotz-prd-bot-ext-temp4-low-trapNetBotz External Temperature 4 Low Trap. This trap indicates that the lower
limit for external temperature probe on port 4 has been exceeded. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.14.0.1 |
netBotz-prd-bot-ext-temp4-high-trapNetBotz External Temperature 4 High Trap. This trap indicates that the upper
limit for external temperature probe on port 4 has been exceeded. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.14.0.2 |
netBotz-prd-bot-ext-temp4-trap-clearNetBotz External Temperature 4 Cleared Trap. The trap has been cleared because
the temperature value for the temperature probe on port 4 has returned to acceptable limits. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.14.0.3 |
netBotz-prd-bot-ext-temp4-sensor-unpluggedNetBotz External Temperature 4 Sensor Unplugged Trap. The sensor is unplugged or malfunctioning. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.14.0.6 |
netBotz-prd-bot-ext-temp4-sensor-repluggedNetBotz External Temperature 4 Sensor Replugged Trap. The sensor was unplugged, but has been reconnected. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.14.0.7 |
netBotz-prd-bot-ext-dry1-traps OBJECT IDENTIFIER .1.3.6.1.4.1.5528.30.100.15 |
netBotz-prd-bot-ext-dry1-triggered-trapNetBotz External Dry Contact 1 Triggered Trap. This trap indicates that the state of the
dry contact sensor on Ext1 matches the alarm value. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.15.0.2 |
netBotz-prd-bot-ext-dry1-trap-clearNetBotz External Dry Contact 1 Cleared Trap. The trap has been cleared because
the state of the dry contact sensor on Ext1 no longer matches the alarm value. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.15.0.3 |
netBotz-prd-bot-ext-dry2-traps OBJECT IDENTIFIER .1.3.6.1.4.1.5528.30.100.16 |
netBotz-prd-bot-ext-dry2-triggered-trapNetBotz External Dry Contact 2 Triggered Trap. This trap indicates that the state of the
dry contact sensor on Ext2 matches the alarm value. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.16.0.2 |
netBotz-prd-bot-ext-dry2-trap-clearNetBotz External Dry Contact 2 Cleared Trap. The trap has been cleared because
the state of the dry contact sensor on Ext2 no longer matches the alarm value. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.16.0.3 |
netBotz-prd-bot-ext-dry3-traps OBJECT IDENTIFIER .1.3.6.1.4.1.5528.30.100.17 |
netBotz-prd-bot-ext-dry3-triggered-trapNetBotz External Dry Contact 3 Triggered Trap. This trap indicates that the state of the
dry contact sensor on Ext3 matches the alarm value. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.17.0.2 |
netBotz-prd-bot-ext-dry3-trap-clearNetBotz External Dry Contact 3 Cleared Trap. The trap has been cleared because
the state of the dry contact sensor on Ext3 no longer matches the alarm value. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.17.0.3 |
netBotz-prd-bot-ext-dry4-traps OBJECT IDENTIFIER .1.3.6.1.4.1.5528.30.100.18 |
netBotz-prd-bot-ext-dry4-triggered-trapNetBotz External Dry Contact 4 Triggered Trap. This trap indicates that the state of the
dry contact sensor on Ext4 matches the alarm value. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.18.0.2 |
netBotz-prd-bot-ext-dry4-trap-clearNetBotz External Dry Contact 4 Cleared Trap. The trap has been cleared because
the state of the dry contact sensor on Ext4 no longer matches the alarm value. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.18.0.3 |
netBotz-prd-bot-amp5-traps OBJECT IDENTIFIER .1.3.6.1.4.1.5528.30.100.19 |
netBotz-prd-bot-amp5-low-trapNetBotz Amp 5 Low Trap. This trap indicates that the lower
limit for the fifth amp detect has been exceeded. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.19.0.1 |
netBotz-prd-bot-amp5-high-trapNetBotz Amp 5 High Trap. This trap indicates that the upper
limit for the fifth amp detect has been exceeded. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.19.0.2 |
netBotz-prd-bot-amp5-trap-clearNetBotz Amp 5 Cleared Trap. The trap has been cleared because
the fifth amp detect value has returned to acceptable limits. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.19.0.3 |
netBotz-prd-bot-amp5-sensor-unpluggedNetBotz Amp 5 Sensor Unplugged Trap. The sensor for the fifth AmpDetect is unplugged or malfunctioning. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.19.0.6 |
netBotz-prd-bot-amp5-sensor-repluggedNetBotz Amp 5 Sensor Replugged Trap. The sensor for the fifth AmpDetect was unplugged, but has been reconnected. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.19.0.7 |
netBotz-prd-bot-amp6-traps OBJECT IDENTIFIER .1.3.6.1.4.1.5528.30.100.20 |
netBotz-prd-bot-amp6-low-trapNetBotz Amp 6 Low Trap. This trap indicates that the lower
limit for the sixth amp detect has been exceeded. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.20.0.1 |
netBotz-prd-bot-amp6-high-trapNetBotz Amp 6 High Trap. This trap indicates that the upper
limit for the sixth amp detect has been exceeded. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.20.0.2 |
netBotz-prd-bot-amp6-trap-clearNetBotz Amp 6 Cleared Trap. The trap has been cleared because
the sixth amp detect value has returned to acceptable limits. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.20.0.3 |
netBotz-prd-bot-amp6-sensor-unpluggedNetBotz Amp 6 Sensor Unplugged Trap. The sensor for the sixth AmpDetect is unplugged or malfunctioning. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.20.0.6 |
netBotz-prd-bot-amp6-sensor-repluggedNetBotz Amp 6 Sensor Replugged Trap. The sensor for the sixth AmpDetect was unplugged, but has been reconnected. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.20.0.7 |
netBotz-prd-bot-amp7-traps OBJECT IDENTIFIER .1.3.6.1.4.1.5528.30.100.21 |
netBotz-prd-bot-amp7-low-trapNetBotz Amp 7 Low Trap. This trap indicates that the lower
limit for the seventh amp detect has been exceeded. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.21.0.1 |
netBotz-prd-bot-amp7-high-trapNetBotz Amp 7 High Trap. This trap indicates that the upper
limit for the seventh amp detect has been exceeded. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.21.0.2 |
netBotz-prd-bot-amp7-trap-clearNetBotz Amp 7 Cleared Trap. The trap has been cleared because
the seventh amp detect value has returned to acceptable limits. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.21.0.3 |
netBotz-prd-bot-amp7-sensor-unpluggedNetBotz Amp 7 Sensor Unplugged Trap. The sensor for the seventh AmpDetect is unplugged or malfunctioning. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.21.0.6 |
netBotz-prd-bot-amp7-sensor-repluggedNetBotz Amp 7 Sensor Replugged Trap. The sensor for the seventh AmpDetect was unplugged, but has been reconnected. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.21.0.7 |
netBotz-prd-bot-ext-temp5-traps OBJECT IDENTIFIER .1.3.6.1.4.1.5528.30.100.22 |
netBotz-prd-bot-ext-temp5-low-trapNetBotz External Temperature 5 Low Trap. This trap indicates that the lower
limit for external temperature probe on port 5 has been exceeded. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.22.0.1 |
netBotz-prd-bot-ext-temp5-high-trapNetBotz External Temperature 5 High Trap. This trap indicates that the upper
limit for external temperature probe on port 5 has been exceeded. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.22.0.2 |
netBotz-prd-bot-ext-temp5-trap-clearNetBotz External Temperature 5 Cleared Trap. The trap has been cleared because
the temperature value for the temperature probe on port 5 has returned to acceptable limits. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.22.0.3 |
netBotz-prd-bot-ext-temp5-sensor-unpluggedNetBotz External Temperature 5 Sensor Unplugged Trap. The sensor is unplugged or malfunctioning. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.22.0.6 |
netBotz-prd-bot-ext-temp5-sensor-repluggedNetBotz External Temperature 5 Sensor Replugged Trap. The sensor was unplugged, but has been reconnected. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.22.0.7 |
netBotz-prd-bot-ext-temp6-traps OBJECT IDENTIFIER .1.3.6.1.4.1.5528.30.100.23 |
netBotz-prd-bot-ext-temp6-low-trapNetBotz External Temperature 6 Low Trap. This trap indicates that the lower
limit for external temperature probe on port 6 has been exceeded. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.23.0.1 |
netBotz-prd-bot-ext-temp6-high-trapNetBotz External Temperature 6 High Trap. This trap indicates that the upper
limit for external temperature probe on port 6 has been exceeded. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.23.0.2 |
netBotz-prd-bot-ext-temp6-trap-clearNetBotz External Temperature 6 Cleared Trap. The trap has been cleared because
the temperature value for the temperature probe on port 6 has returned to acceptable limits. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.23.0.3 |
netBotz-prd-bot-ext-temp6-sensor-unpluggedNetBotz External Temperature 6 Sensor Unplugged Trap. The sensor is unplugged or malfunctioning. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.23.0.6 |
netBotz-prd-bot-ext-temp6-sensor-repluggedNetBotz External Temperature 6 Sensor Replugged Trap. The sensor was unplugged, but has been reconnected. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.23.0.7 |
netBotz-prd-bot-ext-temp7-traps OBJECT IDENTIFIER .1.3.6.1.4.1.5528.30.100.24 |
netBotz-prd-bot-ext-temp7-low-trapNetBotz External Temperature 7 Low Trap. This trap indicates that the lower
limit for external temperature probe on port 7 has been exceeded. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.24.0.1 |
netBotz-prd-bot-ext-temp7-high-trapNetBotz External Temperature 7 High Trap. This trap indicates that the upper
limit for external temperature probe on port 7 has been exceeded. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.24.0.2 |
netBotz-prd-bot-ext-temp7-trap-clearNetBotz External Temperature 7 Cleared Trap. The trap has been cleared because
the temperature value for the temperature probe on port 7 has returned to acceptable limits. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.24.0.3 |
netBotz-prd-bot-ext-temp7-sensor-unpluggedNetBotz External Temperature 7 Sensor Unplugged Trap. The sensor is unplugged or malfunctioning. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.24.0.6 |
netBotz-prd-bot-ext-temp7-sensor-repluggedNetBotz External Temperature 7 Sensor Replugged Trap. The sensor was unplugged, but has been reconnected. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.24.0.7 |
netBotz-prd-bot-ext-dry5-traps OBJECT IDENTIFIER .1.3.6.1.4.1.5528.30.100.25 |
netBotz-prd-bot-ext-dry5-triggered-trapNetBotz External Dry Contact 5 Triggered Trap. This trap indicates that the state of the
dry contact sensor on Ext5 matches the alarm value. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.25.0.2 |
netBotz-prd-bot-ext-dry5-trap-clearNetBotz External Dry Contact 5 Cleared Trap. The trap has been cleared because
the state of the dry contact sensor on Ext5 no longer matches the alarm value. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.25.0.3 |
netBotz-prd-bot-ext-dry6-traps OBJECT IDENTIFIER .1.3.6.1.4.1.5528.30.100.26 |
netBotz-prd-bot-ext-dry6-triggered-trapNetBotz External Dry Contact 6 Triggered Trap. This trap indicates that the state of the
dry contact sensor on Ext6 matches the alarm value. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.26.0.2 |
netBotz-prd-bot-ext-dry6-trap-clearNetBotz External Dry Contact 6 Cleared Trap. The trap has been cleared because
the state of the dry contact sensor on Ext6 no longer matches the alarm value. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.26.0.3 |
netBotz-prd-bot-ext-dry7-traps OBJECT IDENTIFIER .1.3.6.1.4.1.5528.30.100.27 |
netBotz-prd-bot-ext-dry7-triggered-trapNetBotz External Dry Contact 7 Triggered Trap. This trap indicates that the state of the
dry contact sensor on Ext7 matches the alarm value. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.27.0.2 |
netBotz-prd-bot-ext-dry7-trap-clearNetBotz External Dry Contact 7 Cleared Trap. The trap has been cleared because
the state of the dry contact sensor on Ext7 no longer matches the alarm value. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.27.0.3 |
netBotz-prd-bot-camera-motion-traps OBJECT IDENTIFIER .1.3.6.1.4.1.5528.30.100.28 |
netBotz-prd-bot-camera-motion-trap-trippedNetBotz Camera Motion Sensor Tripped Trap. This trap indicates that the camera motion sensor
has been triggered (motion has been detected). TRAP-TYPE .1.3.6.1.4.1.5528.30.100.28.0.2 |
netBotz-prd-bot-camera-motion-trap-clearNetBotz Camera Motion Cleared Trap. The trap has been cleared because
the camera motion sensor has returned to normal (no longer is detecting motion). TRAP-TYPE .1.3.6.1.4.1.5528.30.100.28.0.3 |
netBotz-prd-bot-ext-humi1-traps OBJECT IDENTIFIER .1.3.6.1.4.1.5528.30.100.29 |
netBotz-prd-bot-ext-humi1-low-trapNetBotz External Humidity 1 Low Trap. This trap indicates that the lower
limit for external humidity probe on port 1 has been exceeded. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.29.0.1 |
netBotz-prd-bot-ext-humi1-high-trapNetBotz External Humidity 1 High Trap. This trap indicates that the upper
limit for external humidity probe on port 1 has been exceeded. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.29.0.2 |
netBotz-prd-bot-ext-humi1-trap-clearNetBotz External Humidity 1 Cleared Trap. The trap has been cleared because
the humidity value for the humidity probe on port 1 has returned to acceptable limits. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.29.0.3 |
netBotz-prd-bot-ext-humi1-sensor-unpluggedNetBotz External Humidity 1 Sensor Unplugged Trap. The sensor is unplugged or malfunctioning. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.29.0.6 |
netBotz-prd-bot-ext-humi1-sensor-repluggedNetBotz External Humidity 1 Sensor Replugged Trap. The sensor was unplugged, but has been reconnected. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.29.0.7 |
netBotz-prd-bot-ext-humi2-traps OBJECT IDENTIFIER .1.3.6.1.4.1.5528.30.100.30 |
netBotz-prd-bot-ext-humi2-low-trapNetBotz External Humidity 2 Low Trap. This trap indicates that the lower
limit for external humidity probe on port 2 has been exceeded. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.30.0.1 |
netBotz-prd-bot-ext-humi2-high-trapNetBotz External Humidity 2 High Trap. This trap indicates that the upper
limit for external humidity probe on port 2 has been exceeded. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.30.0.2 |
netBotz-prd-bot-ext-humi2-trap-clearNetBotz External Humidity 2 Cleared Trap. The trap has been cleared because
the humidity value for the humidity probe on port 2 has returned to acceptable limits. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.30.0.3 |
netBotz-prd-bot-ext-humi2-sensor-unpluggedNetBotz External Humidity 2 Sensor Unplugged Trap. The sensor is unplugged or malfunctioning. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.30.0.6 |
netBotz-prd-bot-ext-humi2-sensor-repluggedNetBotz External Humidity 2 Sensor Replugged Trap. The sensor was unplugged, but has been reconnected. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.30.0.7 |
netBotz-prd-bot-ext-humi3-traps OBJECT IDENTIFIER .1.3.6.1.4.1.5528.30.100.31 |
netBotz-prd-bot-ext-humi3-low-trapNetBotz External Humidity 3 Low Trap. This trap indicates that the lower
limit for external humidity probe on port 3 has been exceeded. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.31.0.1 |
netBotz-prd-bot-ext-humi3-high-trapNetBotz External Humidity 3 High Trap. This trap indicates that the upper
limit for external humidity probe on port 3 has been exceeded. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.31.0.2 |
netBotz-prd-bot-ext-humi3-trap-clearNetBotz External Humidity 3 Cleared Trap. The trap has been cleared because
the humidity value for the humidity probe on port 3 has returned to acceptable limits. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.31.0.3 |
netBotz-prd-bot-ext-humi3-sensor-unpluggedNetBotz External Humidity 3 Sensor Unplugged Trap. The sensor is unplugged or malfunctioning. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.31.0.6 |
netBotz-prd-bot-ext-humi3-sensor-repluggedNetBotz External Humidity 3 Sensor Replugged Trap. The sensor was unplugged, but has been reconnected. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.31.0.7 |
netBotz-prd-bot-ext-humi4-traps OBJECT IDENTIFIER .1.3.6.1.4.1.5528.30.100.32 |
netBotz-prd-bot-ext-humi4-low-trapNetBotz External Humidity 4 Low Trap. This trap indicates that the lower
limit for external humidity probe on port 4 has been exceeded. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.32.0.1 |
netBotz-prd-bot-ext-humi4-high-trapNetBotz External Humidity 4 High Trap. This trap indicates that the upper
limit for external humidity probe on port 4 has been exceeded. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.32.0.2 |
netBotz-prd-bot-ext-humi4-trap-clearNetBotz External Humidity 4 Cleared Trap. The trap has been cleared because
the humidity value for the humidity probe on port 4 has returned to acceptable limits. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.32.0.3 |
netBotz-prd-bot-ext-humi4-sensor-unpluggedNetBotz External Humidity 4 Sensor Unplugged Trap. The sensor is unplugged or malfunctioning. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.32.0.6 |
netBotz-prd-bot-ext-humi4-sensor-repluggedNetBotz External Humidity 4 Sensor Replugged Trap. The sensor was unplugged, but has been reconnected. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.32.0.7 |
netBotz-prd-bot-ext-humi5-traps OBJECT IDENTIFIER .1.3.6.1.4.1.5528.30.100.33 |
netBotz-prd-bot-ext-humi5-low-trapNetBotz External Humidity 5 Low Trap. This trap indicates that the lower
limit for external humidity probe on port 5 has been exceeded. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.33.0.1 |
netBotz-prd-bot-ext-humi5-high-trapNetBotz External Humidity 5 High Trap. This trap indicates that the upper
limit for external humidity probe on port 5 has been exceeded. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.33.0.2 |
netBotz-prd-bot-ext-humi5-trap-clearNetBotz External Humidity 5 Cleared Trap. The trap has been cleared because
the humidity value for the humidity probe on port 5 has returned to acceptable limits. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.33.0.3 |
netBotz-prd-bot-ext-humi5-sensor-unpluggedNetBotz External Humidity 5 Sensor Unplugged Trap. The sensor is unplugged or malfunctioning. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.33.0.6 |
netBotz-prd-bot-ext-humi5-sensor-repluggedNetBotz External Humidity 5 Sensor Replugged Trap. The sensor was unplugged, but has been reconnected. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.33.0.7 |
netBotz-prd-bot-ext-humi6-traps OBJECT IDENTIFIER .1.3.6.1.4.1.5528.30.100.34 |
netBotz-prd-bot-ext-humi6-low-trapNetBotz External Humidity 6 Low Trap. This trap indicates that the lower
limit for external humidity probe on port 6 has been exceeded. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.34.0.1 |
netBotz-prd-bot-ext-humi6-high-trapNetBotz External Humidity 6 High Trap. This trap indicates that the upper
limit for external humidity probe on port 6 has been exceeded. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.34.0.2 |
netBotz-prd-bot-ext-humi6-trap-clearNetBotz External Humidity 6 Cleared Trap. The trap has been cleared because
the humidity value for the humidity probe on port 6 has returned to acceptable limits. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.34.0.3 |
netBotz-prd-bot-ext-humi6-sensor-unpluggedNetBotz External Humidity 6 Sensor Unplugged Trap. The sensor is unplugged or malfunctioning. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.34.0.6 |
netBotz-prd-bot-ext-humi6-sensor-repluggedNetBotz External Humidity 6 Sensor Replugged Trap. The sensor was unplugged, but has been reconnected. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.34.0.7 |
netBotz-prd-bot-ext-humi7-traps OBJECT IDENTIFIER .1.3.6.1.4.1.5528.30.100.35 |
netBotz-prd-bot-ext-humi7-low-trapNetBotz External Humidity 7 Low Trap. This trap indicates that the lower
limit for external humidity probe on port 7 has been exceeded. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.35.0.1 |
netBotz-prd-bot-ext-humi7-high-trapNetBotz External Humidity 7 High Trap. This trap indicates that the upper
limit for external humidity probe on port 7 has been exceeded. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.35.0.2 |
netBotz-prd-bot-ext-humi7-trap-clearNetBotz External Humidity 7 Cleared Trap. The trap has been cleared because
the humidity value for the humidity probe on port 7 has returned to acceptable limits. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.35.0.3 |
netBotz-prd-bot-ext-humi7-sensor-unpluggedNetBotz External Humidity 7 Sensor Unplugged Trap. The sensor is unplugged or malfunctioning. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.35.0.6 |
netBotz-prd-bot-ext-humi7-sensor-repluggedNetBotz External Humidity 7 Sensor Replugged Trap. The sensor was unplugged, but has been reconnected. TRAP-TYPE .1.3.6.1.4.1.5528.30.100.35.0.7 |
netBotz-prd-WallBotz-300 OBJECT IDENTIFIER .1.3.6.1.4.1.5528.30.1000 |
netBotz-prd-RackBotz-300 OBJECT IDENTIFIER .1.3.6.1.4.1.5528.30.1001 |
netBotz-prd-RackBotz-300U OBJECT IDENTIFIER .1.3.6.1.4.1.5528.30.1002 |
netBotz-prd-WallBotz-400 OBJECT IDENTIFIER .1.3.6.1.4.1.5528.30.1003 |
netBotz-prd-RackBotz-400 OBJECT IDENTIFIER .1.3.6.1.4.1.5528.30.1004 |
netBotz-prd-RackBotz-303 OBJECT IDENTIFIER .1.3.6.1.4.1.5528.30.1006 |
netBotz-prd-WallBotz-310 OBJECT IDENTIFIER .1.3.6.1.4.1.5528.30.1007 |
netBotz-prd-RackBotz-310 OBJECT IDENTIFIER .1.3.6.1.4.1.5528.30.1008 |
netBotz-prd-WallBotz-300B OBJECT IDENTIFIER .1.3.6.1.4.1.5528.30.1009 |
netBotz-prd-WallBotz-300C OBJECT IDENTIFIER .1.3.6.1.4.1.5528.30.1100 |
netBotz-prd-RackBotz-300C OBJECT IDENTIFIER .1.3.6.1.4.1.5528.30.1101 |
netBotz-prd-RackBotz-300UC OBJECT IDENTIFIER .1.3.6.1.4.1.5528.30.1102 |
netBotz-prd-WallBotz-400C OBJECT IDENTIFIER .1.3.6.1.4.1.5528.30.1103 |
netBotz-prd-RackBotz-400C OBJECT IDENTIFIER .1.3.6.1.4.1.5528.30.1104 |
netBotz-prd-RackBotz-303C OBJECT IDENTIFIER .1.3.6.1.4.1.5528.30.1106 |
netBotz-prd-WallBotz-310C OBJECT IDENTIFIER .1.3.6.1.4.1.5528.30.1107 |
netBotz-prd-RackBotz-310C OBJECT IDENTIFIER .1.3.6.1.4.1.5528.30.1108 |
netBotz-prd-WallBotz-300BC OBJECT IDENTIFIER .1.3.6.1.4.1.5528.30.1109 |
netBotz-prd-WallBotz-300E OBJECT IDENTIFIER .1.3.6.1.4.1.5528.30.1200 |
netBotz-prd-RackBotz-300E OBJECT IDENTIFIER .1.3.6.1.4.1.5528.30.1201 |
netBotz-prd-RackBotz-300UE OBJECT IDENTIFIER .1.3.6.1.4.1.5528.30.1202 |
netBotz-prd-WallBotz-400E OBJECT IDENTIFIER .1.3.6.1.4.1.5528.30.1203 |
netBotz-prd-RackBotz-400E OBJECT IDENTIFIER .1.3.6.1.4.1.5528.30.1204 |
netBotz-prd-RackBotz-303E OBJECT IDENTIFIER .1.3.6.1.4.1.5528.30.1206 |
netBotz-prd-WallBotz-310E OBJECT IDENTIFIER .1.3.6.1.4.1.5528.30.1207 |
netBotz-prd-RackBotz-310E OBJECT IDENTIFIER .1.3.6.1.4.1.5528.30.1208 |
netBotz-prd-WallBotz-300BE OBJECT IDENTIFIER .1.3.6.1.4.1.5528.30.1209 |
expPortTableA list of expansion port entries. SEQUENCE OF ExpPortEntry .1.3.6.1.4.1.5528.31 |
expPortEntryAn expansion port entry for a single port ExpPortEntry .1.3.6.1.4.1.5528.31.1 |
expPort-module-idThe module ID of the sensor module installed. Blank string indicates that no module is installed.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.5528.31.1.1 |
expPort-module-typeThe type of sensor module installed. NONE=no module, AMP=AmpDetect module, TEMP=temperature sensor, DRY=dry contact sensor.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.5528.31.1.2 |
expPort-labelThe label for the expansion port. Ports default to the label 'Extn', for port n.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.5528.31.1.3 |
expPort-ampsThe reading of the amperage probe, in milliamps.ro INTEGER .1.3.6.1.4.1.5528.31.1.20 |
expPort-total-amp-secondsThe accumulated total of amp-seconds on the AmpDetect.ro INTEGER .1.3.6.1.4.1.5528.31.1.21 |
expPort-total-amp-seconds-since-timeThe UTC time (seconds since 1/1/1970) of the beginning of the accumulated total of amp-seconds on the AmpDetect.
Writing a value to this attribute resets the accumulated total amp-seconds and sets this time to the current time.rw INTEGER .1.3.6.1.4.1.5528.31.1.22 |
expPort-amps-enabledAmperage probe alarm enabled(1) or disabled(0).rw INTEGER .1.3.6.1.4.1.5528.31.1.23 |
expPort-amps-minThe amperage probe minimum, from 0 to 30000 milliamps.rw INTEGER .1.3.6.1.4.1.5528.31.1.24 |
expPort-amps-maxThe amperage probe maximum, from 0 to 30000 milliamps.rw INTEGER .1.3.6.1.4.1.5528.31.1.25 |
expPort-amps-uV-per-10mAThe scaling factor used for the amperage probe to convert microvolts measured from the
Amp Detect into 10s of milliamps of current. Needs to be set based on the type of Amp Detect module installed.rw INTEGER .1.3.6.1.4.1.5528.31.1.26 |
expPort-amps-max-rangeThe maximum RMS milliamps measureable by the AmpDetect.rw INTEGER .1.3.6.1.4.1.5528.31.1.27 |
expPort-ext-tempThe reading of the external temperature probe, in degrees F or degrees C (depends on netBotz-ismetric).ro INTEGER .1.3.6.1.4.1.5528.31.1.40 |
expPort-ext-temp-enabledExternal temperature probe alarm enabled(1) or disabled(0).rw INTEGER .1.3.6.1.4.1.5528.31.1.41 |
expPort-ext-temp-minThe external temperature probe minimum, in degrees F or degrees C (depends on netBotz-ismetric).rw INTEGER .1.3.6.1.4.1.5528.31.1.42 |
expPort-ext-temp-maxThe external temperature probe maximum, in degrees F or degrees C (depends on netBotz-ismetric).rw INTEGER .1.3.6.1.4.1.5528.31.1.43 |
expPort-ext-temp-uV-per-degreeCThe scaling factor used for the external temperature probe to convert microvolts measured from the
temperature sensor into degrees C. Needs to be set based on the type of temperature sensor module installed.rw INTEGER .1.3.6.1.4.1.5528.31.1.44 |
expPort-ext-temp-uV-at-0-degreeCThe offset used for the external temperature probe of microvolts measured from the
temperature sensor at zero degrees C. Needs to be set based on the type of temperature sensor module installed.rw INTEGER .1.3.6.1.4.1.5528.31.1.45 |
expPort-ext-temp-min-rangeThe minimum temperature measureable by the temperature sensor, in tenths of a degree C.
Needs to be set based on the type of temperature sensor module installed.rw INTEGER .1.3.6.1.4.1.5528.31.1.46 |
expPort-ext-temp-max-rangeThe maximum temperature measureable by the temperature sensor, in tenths of a degree C.
Needs to be set based on the type of temperature sensor module installed.rw INTEGER .1.3.6.1.4.1.5528.31.1.47 |
expPort-ext-dryThe current value of the external dry contact sensor: 0=Open, 1=Closed, -1=N/Aro INTEGER .1.3.6.1.4.1.5528.31.1.60 |
expPort-ext-dry-alarm-valueThe value to generate alarms on for the external dry contact sensor: 0=Open, 1=Closedrw INTEGER .1.3.6.1.4.1.5528.31.1.61 |
expPort-ext-dry-enabledExternal dry contact sensor alarm enabled(1) or disabled(0).rw INTEGER .1.3.6.1.4.1.5528.31.1.62 |
expPort-ext-dry-labelThe sensor name/label for the dry contact sensorrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.5528.31.1.63 |
expPort-ext-dry-open-labelThe sensor name/label for the open(0) state for the dry contact sensorrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.5528.31.1.64 |
expPort-ext-dry-closed-labelThe sensor name/label for the closed(0) state for the dry contact sensorrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.5528.31.1.65 |
expPort-ext-dry-open-to-close-millisThe minimum number of milliseconds that the dry contact sensor
must read closed before the state is changed from open to closed.rw INTEGER .1.3.6.1.4.1.5528.31.1.66 |
expPort-ext-dry-close-to-open-millisThe minimum number of milliseconds that the dry contact sensor
must read openbefore the state is changed from closed to open.rw INTEGER .1.3.6.1.4.1.5528.31.1.67 |
expPort-ext-dry-responseThe type of alert response for the dry contact sensor: ALERT=e-mail with no
pictures, CAMERA=e-mail with pictures from camera.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.5528.31.1.68 |
expPort-ext-humiThe reading of the external humidity probe, in percent.ro INTEGER .1.3.6.1.4.1.5528.31.1.80 |
expPort-ext-humi-enabledExternal humidity probe alarm enabled(1) or disabled(0).rw INTEGER .1.3.6.1.4.1.5528.31.1.81 |
expPort-ext-humi-minThe external humidity probe minimum, in percent.rw INTEGER .1.3.6.1.4.1.5528.31.1.82 |
expPort-ext-humi-maxThe external humidity probe maximum, in percent.rw INTEGER .1.3.6.1.4.1.5528.31.1.83 |
expPort-ext-humi-uV-per-percentThe scaling factor used for the external humidity probe to convert microvolts measured from the
humidity sensor into percent. Needs to be set based on the type of humidity sensor module installed.rw INTEGER .1.3.6.1.4.1.5528.31.1.84 |
expPort-ext-humi-uV-at-0-percentThe offset used for the external humidity probe of microvolts measured from the
humidity sensor at zero percent. Needs to be set based on the type of humidity sensor module installed.rw INTEGER .1.3.6.1.4.1.5528.31.1.85 |
expPort-ext-humi-min-rangeThe minimum humidity measureable by the humidity sensor, in percent.
Needs to be set based on the type of humidity sensor module installed.rw INTEGER .1.3.6.1.4.1.5528.31.1.86 |
expPort-ext-humi-max-rangeThe maximum humidity measureable by the humidity sensor, in percent.
Needs to be set based on the type of humidity sensor module installed.rw INTEGER .1.3.6.1.4.1.5528.31.1.87 |
netBotz-metric OBJECT IDENTIFIER .1.3.6.1.4.1.5528.32 |
netBotz-metric-onboard OBJECT IDENTIFIER .1.3.6.1.4.1.5528.32.10 |
netBotz-metric-onboard-modelThe model description of the appliance.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.5528.32.10.1 |
netBotz-metric-onboard-tempThe reading of the built-in temperature probe, in tenths of a degree C.ro INTEGER .1.3.6.1.4.1.5528.32.10.2 |
netBotz-metric-onboard-humidityThe reading of the built-in humidity probe, in percent.ro INTEGER .1.3.6.1.4.1.5528.32.10.3 |
netBotz-metric-onboard-airflowThe reading of the built-in airflow probe, in meters/minute.ro INTEGER .1.3.6.1.4.1.5528.32.10.4 |
netBotz-metric-onboard-audioThe reading of the built-in audio alarm probe on/off.ro INTEGER .1.3.6.1.4.1.5528.32.10.5 |
netBotz-metric-onboard-doorajarThe reading of the door switch probe open(1) or closed(0).ro INTEGER .1.3.6.1.4.1.5528.32.10.6 |
netBotz-metric-onboard-temp-minThe temperature probe minimum, from 1 to 50 degrees C in tenths of a degree C.ro INTEGER .1.3.6.1.4.1.5528.32.10.7 |
netBotz-metric-onboard-temp-maxThe temperature probe maximum, from 1 to 50 degrees C in tenths of a degree C.ro INTEGER .1.3.6.1.4.1.5528.32.10.8 |
netBotz-metric-onboard-humidity-minThe humidity probe minimum, from 10 to 90 percent.ro INTEGER .1.3.6.1.4.1.5528.32.10.9 |
netBotz-metric-onboard-humidity-maxThe humidity probe maximum, from 10 to 90 percent.ro INTEGER .1.3.6.1.4.1.5528.32.10.10 |
netBotz-metric-onboard-airflow-minsMinutes without airflow before alarm set.ro INTEGER .1.3.6.1.4.1.5528.32.10.11 |
netBotz-metric-onboard-audio-secsSeconds of alarm audio before alarm set.ro INTEGER .1.3.6.1.4.1.5528.32.10.12 |
netBotz-metric-onboard-switch-stateSwitch state setting. The state controls which condition of the door switch indicates an alarm. If set to 0, alarm is set when the switch is closed. If set to 1, alarm is set when the switch is open.ro INTEGER .1.3.6.1.4.1.5528.32.10.13 |
netBotz-metric-onboard-audio-levelAudio level setting, this is the relative audio level, from 0-11, above which an alarm will be sent.ro INTEGER .1.3.6.1.4.1.5528.32.10.14 |
netBotz-metric-onboard-airflow-levelAirflow alert level. This is the level, in meters per second, below which an alarm will be sent.ro INTEGER .1.3.6.1.4.1.5528.32.10.15 |
netBotz-metric-onboard-cam-motionThe current motion reading for the camera motion sensor (0=none, 1=motion detected, -1=not licensed).ro INTEGER .1.3.6.1.4.1.5528.32.10.16 |
netBotz-metric-onboard-cam-motion-sensitivityCamera motion sensor sensitivity: 1=max, 15=min, 0=disabled.ro INTEGER .1.3.6.1.4.1.5528.32.10.17 |
netBotz-snmp OBJECT IDENTIFIER .1.3.6.1.4.1.5528.40 |
netBotz-snmp-traptargetTarget of traps from the NetBotz device. This field contains the
IP address where NetBotz traps are to be sent.rw IpAddress .1.3.6.1.4.1.5528.40.1 |
netBotz-snmp-communityThe read/write community of the NetBotz device.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.5528.40.2 |
netBotz-snmp-timeoutSNMP Timeout period.rw INTEGER .1.3.6.1.4.1.5528.40.3 |
netBotz-snmp-retriesSNMP Retry count.rw INTEGER .1.3.6.1.4.1.5528.40.4 |
netBotz-userid-1The userID of the supervisor account (write-only).rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.5528.40.5 |
netBotz-password-1The password of the supervisor account (write-only).rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.5528.40.6 |
netBotz-userid-2The userID of the full read access account (write-only).rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.5528.40.7 |
netBotz-password-2The password of the full read access account (write-only).rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.5528.40.8 |
netBotz-userid-3The userID of the minimum read access account (write-only).rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.5528.40.9 |
netBotz-password-3The password of the minimum read access account (write-only).rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.5528.40.10 |
netBotz-snmp-traptarget2Second target of traps from the NetBotz device. This field contains an additional
IP address where NetBotz traps are to be sent.rw IpAddress .1.3.6.1.4.1.5528.40.11 |
netBotz-snmp-read-communityThe read-only community of the NetBotz device.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.5528.40.12 |
netBotz-device OBJECT IDENTIFIER .1.3.6.1.4.1.5528.50 |
netBotz-dev-hostNetBotz device's host name.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.5528.50.1 |
netBotz-dev-domainNetBotz device's default DNS domain.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.5528.50.2 |
netBotz-dev-ipNetBotz device's IP address.rw IpAddress .1.3.6.1.4.1.5528.50.3 |
netBotz-dev-netmaskNetBotz device's netmask.rw IpAddress .1.3.6.1.4.1.5528.50.4 |
netBotz-dev-gatewayNetBotz device's default gateway/router. 0.0.0.0 if not defined.rw IpAddress .1.3.6.1.4.1.5528.50.5 |
netBotz-dev-primarydnsPrimary Domain Name Server. 0.0.0.0 if not defined.rw IpAddress .1.3.6.1.4.1.5528.50.6 |
netBotz-dev-secondarydnsSecondary Domain Name Server. 0.0.0.0 if not defined.rw IpAddress .1.3.6.1.4.1.5528.50.7 |
netBotz-dev-smtpSMTP server address. This is the mail server used for sending alert e-mails.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.5528.50.8 |
netBotz-dev-smtpportSMTP port. Port number of SMTP server used for sending alert e-mails.rw INTEGER .1.3.6.1.4.1.5528.50.9 |
netBotz-dev-popportPOP port. Currently, not used.rw INTEGER .1.3.6.1.4.1.5528.50.10 |
netBotz-dev-loglevelThis field contains the log level of the NetBotz device.
Log messages will be filtered, so that only same or lower-level
messages will be passed. The default log level is 5, for warnings
and lower levels. The log levels are the following:
1 - emergency
2 - alert
3 - critical
4 - error
5 - warning
6 - notice
7 - info
8 - tracerw INTEGER .1.3.6.1.4.1.5528.50.11 |
netBotz-dev-primaryemailThe primary email addresses for alerts and messages (list separated by commas for multiple addresses).rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.5528.50.14 |
netBotz-dev-secondaryemailThe secondary email address for alerts and messages (list separated by commas for multiple addresses).rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.5528.50.15 |
netBotz-dev-serialnoThe serial number of the NetBotz device.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.5528.50.17 |
netBotz-dev-popPOP server name. Currently, not used.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.5528.50.18 |
netBotz-dev-versionThe current NetBotz device firmware version.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.5528.50.19 |
netBotz-dev-registeredIndicates if the device has been registered with NetBotz, Inc. 1=registered, 0=not registered.ro INTEGER .1.3.6.1.4.1.5528.50.20 |
netBotz-default-appletSetting to control if default web page should launch applet by default(1) or the HTML status page(0).rw INTEGER .1.3.6.1.4.1.5528.50.21 |
netBotz-guibar-colorSetting for color of GUI bar (RGB). Value = 0xRRGGBB.rw INTEGER .1.3.6.1.4.1.5528.50.22 |
netBotz-localeThe locale ID of the NetBotz device. Format is ISO 639 language (lower case),
an underscore, and ISO 3166 country (upper case). Some locales are just the ISO 639 language code.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.5528.50.23 |
netBotz-timezoneThe timezone ID of the NetBotz device.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.5528.50.24 |
netBotz-24hourpreferredIndicates if 24-hour(1) versus 12-hour(0) time format is preferred.rw INTEGER .1.3.6.1.4.1.5528.50.25 |
netBotz-utc-clockCurrent time of clock on NetBotz device, in UTC seconds (seconds since 1/1/1970 12:00am GMT).rw INTEGER .1.3.6.1.4.1.5528.50.26 |
netBotz-ismetricUnits are metric (1) or U.S. (0). Applies to temperature and airflow rate.ro INTEGER .1.3.6.1.4.1.5528.50.27 |
netBotz-alert-urlThe URL, if defined, to which non-picture alerts are HTTP POSTedrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.5528.50.28 |
netBotz-picture-alert-urlThe URL, if defined, to which picture alerts are HTTP POSTed, using multipart/form-data
encoding.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.5528.50.29 |
netBotz-sensor-data-urlThe URL, if defined, to which sensor data is periodically HTTP POSTed.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.5528.50.30 |
netBotz-alert-url-logonThe user ID and password, if defined, used for POSTing non-picture alerts.
Field is write-only, and formatted /rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.5528.50.31 |
netBotz-picture-alert-url-logonThe user ID and password, if defined, used for POSTing picture alerts.
Field is write-only, and formatted /rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.5528.50.32 |
netBotz-sensor-data-url-logonThe user ID and password, if defined, used for POSTing sensor data.
Field is write-only, and formatted /rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.5528.50.33 |
netBotz-sensor-data-url-periodDefault number of minutes between periodic sensor data HTTP POSTs.rw INTEGER .1.3.6.1.4.1.5528.50.34 |
netBotz-sensor-data-url-flagsOption flags for data POSTs of sensor data. Bit 0=1 if current picture
should be included. Bits 1-31 are reserved.rw INTEGER .1.3.6.1.4.1.5528.50.35 |
netBotz-dev-backup-smtpBackup SMTP server address. This is the backup mail server used for sending alert e-mails.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.5528.50.36 |
netBotz-dev-tertiarydnsTertiary Domain Name Server. 0.0.0.0 if not defined.rw IpAddress .1.3.6.1.4.1.5528.50.37 |
netBotz-dev-ntp-serverNTP (Network Time Protocol) Server configured for appliance.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.5528.50.38 |
netBotz-dev-ntp-periodHours between automatic refreshes of the appliance clock using the NTP server.rw INTEGER .1.3.6.1.4.1.5528.50.39 |
netBotz-dev-socks-serverSocks V4 or V5 proxy server configured for appliance.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.5528.50.40 |
netBotz-dev-socks-portnumPort number of Socks Proxy.rw INTEGER .1.3.6.1.4.1.5528.50.41 |
netBotz-dev-socks-user-idUser ID for Socks V4 or V5 proxy server configured for appliance.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.5528.50.42 |
netBotz-dev-socks-passwordPassword for Socks V4 or V5 proxy server configured for appliance.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.5528.50.43 |
netBotz-alert-ftp-siteThe hostname or dotted-decimal IP address of the FTP server to
deliver alerts torw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.5528.50.44 |
netBotz-alert-ftp-pathThe directory on the FTP server to store alerts in.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.5528.50.45 |
netBotz-alert-ftp-filenameThe base filename for the files on the FTP server to store alerts in.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.5528.50.46 |
netBotz-alert-ftp-logonThe user-id and password on the FTP server to store alerts in.
Field is write-only, and formatted /rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.5528.50.47 |
netBotz-sensor-ftp-siteThe hostname or dotted-decimal IP address of the FTP server to
deliver periodic sensor reports torw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.5528.50.48 |
netBotz-sensor-ftp-pathThe directory on the FTP server to store periodic sensor reports in.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.5528.50.49 |
netBotz-sensor-ftp-filenameThe base filename for the files on the FTP server to store periodic sensor reports in.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.5528.50.50 |
netBotz-sensor-ftp-logonThe user-id and password on the FTP server to store sensor reports in.
Field is write-only, and formatted /rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.5528.50.51 |
netBotz-sensor-ftp-periodThe period, in minutes, between delivery of sensor data reports.rw INTEGER .1.3.6.1.4.1.5528.50.52 |
netBotz-use-syslogEnable syslogrw INTEGER .1.3.6.1.4.1.5528.50.53 |
netBotz-syslog-addressHost address to use for sysloggingrw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.5528.50.54 |
netBotz-syslog-facilitySyslog facility coderw INTEGER .1.3.6.1.4.1.5528.50.55 |
netBotz-color-balanceColor balance for color camera. AUTO=automatic, FLUOR=fluorescent, DAY=daylight,
INCAND=incandescent, x/y=Custom (scale red by x/64, scale blue by y/64)rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.5528.50.56 |
netBotz-addonapp OBJECT IDENTIFIER .1.3.6.1.4.1.5528.60 |
device-crawlers-trap-target-index OBJECT IDENTIFIER .1.3.6.1.4.1.5528.60.2 |
branch-checker-trap-target-index OBJECT IDENTIFIER .1.3.6.1.4.1.5528.60.3 |
vendor-netBotz OBJECT IDENTIFIER .1.3.6.1.4.1.5528.60.5528 |
device-crawlers-trap OBJECT IDENTIFIER .1.3.6.1.4.1.5528.60.5528.2 |
netBotz-device-crawlers-value-low-alert-trapNetBotz Device Crawlers Value Low Trap. This trap indicates that the lower limit on a monitored value has been exceeded. TRAP-TYPE .1.3.6.1.4.1.5528.60.5528.2.0.1 |
netBotz-device-crawlers-value-high-alert-trapNetBotz Device Crawlers Value High Trap. This trap indicates that the upper limit on a monitored value has been exceeded. TRAP-TYPE .1.3.6.1.4.1.5528.60.5528.2.0.2 |
netBotz-device-crawlers-clear-alert-trapNetBotz Device Crawlers Clear Trap. This trap indicates that the previous alert condition has been cleared. TRAP-TYPE .1.3.6.1.4.1.5528.60.5528.2.0.3 |
netBotz-device-crawlers-offline-alert-trapNetBotz Device Crawlers Offline Trap. This trap indicates that a monitored target could not be contacted. TRAP-TYPE .1.3.6.1.4.1.5528.60.5528.2.0.4 |
netBotz-device-crawlers-online-alert-trapNetBotz Device Crawlers Online Trap. This trap indicates that a monitored target that previously could not be contacted has now been contacted successfully. TRAP-TYPE .1.3.6.1.4.1.5528.60.5528.2.0.5 |
netBotz-device-crawlers-ifopstatus-alert-trapNetBotz Device Crawlers Interface Operational Status Trap. This trap indicates that one or more of a monitored target's network interfaces operational status is not equal to the desired status. TRAP-TYPE .1.3.6.1.4.1.5528.60.5528.2.0.8 |
branch-checker-trap OBJECT IDENTIFIER .1.3.6.1.4.1.5528.60.5528.3 |
netBotz-branch-checker-clear-alert-trapNetBotz Branch Checker Clear Trap. This trap indicates that the previous alert condition has been cleared. TRAP-TYPE .1.3.6.1.4.1.5528.60.5528.3.0.3 |
netBotz-branch-checker-offline-alert-trapNetBotz Branch Checker Offline Trap. This trap indicates that a monitored target could not be contacted. TRAP-TYPE .1.3.6.1.4.1.5528.60.5528.3.0.4 |
netBotz-branch-checker-online-alert-trapNetBotz Branch Checker Online Trap. This trap indicates that a monitored target that previously could not be contacted has now been contacted successfully. TRAP-TYPE .1.3.6.1.4.1.5528.60.5528.3.0.5 |
netBotz-branch-checker-target-error-trapNetBotz Branch Target Error Trap. This trap indicates that a monitored target could be contacted, but not withing the timeout period specified. TRAP-TYPE .1.3.6.1.4.1.5528.60.5528.3.0.12 |
netBotz-addonapp-trap OBJECT IDENTIFIER .1.3.6.1.4.1.5528.61 |
device-crawlers-trap-attrib OBJECT IDENTIFIER .1.3.6.1.4.1.5528.61.2 |
device-crawlers-trap-indexThe ID of the device crawler which sent the last trap.ro INTEGER .1.3.6.1.4.1.5528.61.2.20 |
device-crawlers-trap-addressThe IP address of the appliance actually creating the last trap.ro IpAddress .1.3.6.1.4.1.5528.61.2.21 |
device-crawlers-trap-oidThe object id of the attribute on the device crawlers target device which is the concern of the last trap. The second to last element indicates the index of the source of the problem (1=ICMP Ping, 2=SNMP Agent Status, 256-10239=Network Interfaces 1-9984, 10240 and above, indicates Advanced crawlers data). The last element is the decimal representation of the IP address of the source of the problem.ro OBJECT IDENTIFIER .1.3.6.1.4.1.5528.61.2.22 |
device-crawlers-trap-botoidThe object id of the device crawlers attribute on the NetBotz device which is the concern of the last trap.ro OBJECT IDENTIFIER .1.3.6.1.4.1.5528.61.2.23 |
device-crawlers-trap-valueThe integer value of the device crawlers attribute associated with the last trap.ro INTEGER .1.3.6.1.4.1.5528.61.2.24 |
device-crawlers-trap-stringvalueThe string representation of the value of the device crawlers attribute associated with the last trap.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.5528.61.2.25 |
device-crawlers-trap-dateThe date and time of a specific device crawlers trap. This field contains the number of seconds elapsed since midnight (00:00:00), January 1, 1970ro INTEGER .1.3.6.1.4.1.5528.61.2.26 |
device-crawlers-trap-attrib-indexThe identification number of the device crawlers attribute in errorro INTEGER .1.3.6.1.4.1.5528.61.2.27 |
device-crawlers-crawlers-trap-descDescription of the Device Crawlers Trap Attributero DisplayString (SNMPv2-TC) .1.3.6.1.4.1.5528.61.2.28 |
branch-checker-trap-attrib OBJECT IDENTIFIER .1.3.6.1.4.1.5528.61.3 |
branch-checker-trap-indexThe ID of the branch checker which sent the last trap.ro INTEGER .1.3.6.1.4.1.5528.61.3.20 |
branch-checker-trap-addressThe IP address of the appliance actually creating the last trap.ro IpAddress .1.3.6.1.4.1.5528.61.3.21 |
branch-checker-trap-oidThe object id of the attribute on the branch checker target device which is the concern of the last trap The second to last element is the index of the source of the problem (256-260=SMTP Server, 1024-1026=DNS Server, 1536-1538=Web Server, 2048-2052=Generic Server). The last element is the decimal representation of the IP address of the source of the problem.ro OBJECT IDENTIFIER .1.3.6.1.4.1.5528.61.3.22 |
branch-checker-trap-botoidThe object id of the branch checker attribute on the NetBotz device which is the concern of the last trap. The second to last element is the index of the source of the problem (256-260=SMTP Server, 1024-1026=DNS Server, 1536-1538=Web Server, 2048-2052=Generic Server). The last element is the decimal representation of the IP address of the source of the problem.ro OBJECT IDENTIFIER .1.3.6.1.4.1.5528.61.3.23 |
branch-checker-trap-valueThe integer value of the branch checker attribute associated with the last trap.ro INTEGER .1.3.6.1.4.1.5528.61.3.24 |
branch-checker-trap-stringvalueThe string representation of the value of the branch checker attribute associated with the last trap.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.5528.61.3.25 |
branch-checker-trap-dateThe date and time of a specific branch checker trap. This field contains the number of seconds elapsed since midnight (00:00:00), January 1, 1970ro INTEGER .1.3.6.1.4.1.5528.61.3.26 |
branch-checker-trap-attrib-indexThe identification number of the branch checker attribute in errorro INTEGER .1.3.6.1.4.1.5528.61.3.27 |
branch-checker-trap-descDescription of the Branch Checker Trap Attributero DisplayString (SNMPv2-TC) .1.3.6.1.4.1.5528.61.3.28 |