LHX-MIB
Imported Objects
Objects
84 total| Object Name |
|---|
raritanThis MIB describes the SNMP functions of the
Schroff Varistar LHX heat exchanger
supported by Raritan devices. MODULE-IDENTITY .1.3.6.1.4.1.13742 |
lhxgw OBJECT IDENTIFIER .1.3.6.1.4.1.13742.9 |
traps OBJECT IDENTIFIER .1.3.6.1.4.1.13742.9.0 |
trapInformation OBJECT IDENTIFIER .1.3.6.1.4.1.13742.9.0.0 |
deviceNameThe user-defined name for the Device.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.13742.9.0.0.1 |
deviceInetAddressTypeThe type of address formatro InetAddressType (INET-ADDRESS-MIB) .1.3.6.1.4.1.13742.9.0.0.2 |
deviceInetIPAddressThe current IP address. A value of 0.0.0.0 indicates an
error or an unset option.ro InetAddress (INET-ADDRESS-MIB) .1.3.6.1.4.1.13742.9.0.0.3 |
lhxErrorCodeThe LHX error code (F1 - F25, EP).ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.13742.9.0.0.4 |
portIdA unique value for the physical port, the LHX controlller
is connected to.
Its value ranges between 1 and the value of portCount.ro Integer32 .1.3.6.1.4.1.13742.9.0.0.5 |
probeIdThe physical Sensor ID (F1 - F7).ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.13742.9.0.0.6 |
fanIdThe Fan ID (M1 - M6).ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.13742.9.0.0.7 |
powerSupplyIdThe Power Supply ID (1, 2).ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.13742.9.0.0.8 |
oldSensorStateThe old sensor state used in Sensor State Transition traps.ro SensorStateEnumeration .1.3.6.1.4.1.13742.9.0.0.9 |
sensorTypeIdA unique value for the type of sensor.ro GwSensorTypeEnumeration .1.3.6.1.4.1.13742.9.0.0.10 |
sensorIdA unique value for each sensor. Its value
ranges between 1 and the value of sensorCount.ro Integer32 .1.3.6.1.4.1.13742.9.0.0.11 |
oldOperationalStateThe old operational state used in Operational State Transition traps.ro OperationalStateEnumeration .1.3.6.1.4.1.13742.9.0.0.12 |
agentInetPortNumberThe UDP port number used for accessing
the SNMP agent on the device.
Examples:
If the associated device MIB (PX2-MIB, EMD-MIB) has deviceCascadeType set to portForwarding, then
master: 50500
slave 1:50501
slave 2: 50502
......
If cascading mode is not portForwarding and default (Standard) ports are being used, then
port: 161ro InetPortNumber (INET-ADDRESS-MIB) .1.3.6.1.4.1.13742.9.0.0.13 |
lhxSensorFailureA sensor failure (broken or short circuit) occurred. NOTIFICATION-TYPE .1.3.6.1.4.1.13742.9.0.1 |
lhxFanFailureA fan motor failure occurred. NOTIFICATION-TYPE .1.3.6.1.4.1.13742.9.0.2 |
lhxPowerSupplyFailureA power supply failure occurred. NOTIFICATION-TYPE .1.3.6.1.4.1.13742.9.0.3 |
lhxThresholdAirOutletThe air outlet temperature threshold was crossed. NOTIFICATION-TYPE .1.3.6.1.4.1.13742.9.0.4 |
lhxThresholdAirInletThe air inlet temperature threshold was crossed. NOTIFICATION-TYPE .1.3.6.1.4.1.13742.9.0.5 |
lhxThresholdWaterInletThe water inlet temperature threshold was crossed. NOTIFICATION-TYPE .1.3.6.1.4.1.13742.9.0.6 |
lhxDoorOpenedThe door was opened. NOTIFICATION-TYPE .1.3.6.1.4.1.13742.9.0.7 |
lhxMaximumCoolingRequestMaximum cooling was requested. NOTIFICATION-TYPE .1.3.6.1.4.1.13742.9.0.8 |
lhxEmergencyCoolingEmergency cooling was activated. NOTIFICATION-TYPE .1.3.6.1.4.1.13742.9.0.9 |
lhxWaterLeakWater leakage was detected. NOTIFICATION-TYPE .1.3.6.1.4.1.13742.9.0.10 |
lhxThresholdHumidityThe humidity threshold was crossed. NOTIFICATION-TYPE .1.3.6.1.4.1.13742.9.0.11 |
lhxExternalWaterCoolingFailureAn external water cooling failure occurred. NOTIFICATION-TYPE .1.3.6.1.4.1.13742.9.0.12 |
lhxThresholdWaterOutletThe water outlet temperature threshold was crossed. NOTIFICATION-TYPE .1.3.6.1.4.1.13742.9.0.13 |
lhxParameterDataLossData loss in parameter memory was detected. NOTIFICATION-TYPE .1.3.6.1.4.1.13742.9.0.14 |
lhxStBusErrorAn ST-Bus communication error was detected. NOTIFICATION-TYPE .1.3.6.1.4.1.13742.9.0.15 |
lhxCollectiveFaultAn error was detected. NOTIFICATION-TYPE .1.3.6.1.4.1.13742.9.0.16 |
gwSensorStateChangeSensor State Change. NOTIFICATION-TYPE .1.3.6.1.4.1.13742.9.0.17 |
gwLhxOperationalStateChangeOperational State Change. NOTIFICATION-TYPE .1.3.6.1.4.1.13742.9.0.18 |
lhxVoltageLowThe supply voltage of an LHX became low. NOTIFICATION-TYPE .1.3.6.1.4.1.13742.9.0.19 |
lhxBaseElectronicsFailureThe base electronics of an LHX controller failed. NOTIFICATION-TYPE .1.3.6.1.4.1.13742.9.0.20 |
lhxCondenserPumpFailureAn LHX condenser pump failed. NOTIFICATION-TYPE .1.3.6.1.4.1.13742.9.0.21 |
configuration OBJECT IDENTIFIER .1.3.6.1.4.1.13742.9.1 |
portCountThe number of lhx units supported.ro Integer32 .1.3.6.1.4.1.13742.9.1.1 |
sensorCountTableA list of lhx sensor count extries. SEQUENCE OF SensorCountEntryStruct .1.3.6.1.4.1.13742.9.1.2 |
sensorCountEntryAn entry containing the number of lhx sensors of a certain type. SensorCountEntryStruct .1.3.6.1.4.1.13742.9.1.2.1 |
sensorCountThe number of sensors.ro Integer32 .1.3.6.1.4.1.13742.9.1.2.1.1 |
lhx OBJECT IDENTIFIER .1.3.6.1.4.1.13742.9.1.3 |
lhxConfigurationTableA list of lhx controller configuration extries.
The number of entries is given by the value of portCount. SEQUENCE OF LhxConfigurationEntryStruct .1.3.6.1.4.1.13742.9.1.3.1 |
lhxConfigurationEntryAn entry containing parameters for an lhx. LhxConfigurationEntryStruct .1.3.6.1.4.1.13742.9.1.3.1.1 |
operationalStateThe operational state of the lhx controller.
To switch LHX power state while controller is connected,
set operationalState to 1 (off) or 2 (on).
Switching power state while LHX is disconnected or to
0 (disconnected) is undefined.rw OperationalStateEnumeration .1.3.6.1.4.1.13742.9.1.3.1.1.1 |
setpointVentilatorsThe setpoint of the ventilators.rw Integer32 .1.3.6.1.4.1.13742.9.1.3.1.1.2 |
setpointWaterValveThe setpoint of the water valve.rw Integer32 .1.3.6.1.4.1.13742.9.1.3.1.1.3 |
defaultFanSpeedThe 'default' fan speed during normal operation in per mill.
Default is 80% (= 800).rw Integer32 .1.3.6.1.4.1.13742.9.1.3.1.1.4 |
maximumCoolingStateIndicates whether maximum cooling was requested or not.
To request maximum cooling, set maximumCoolingState to 1 (true).
Setting maximumCoolingState to 2 (false) is undefined,
set alertState to 2 (false) instead.rw TruthValue (SNMPv2-TC) .1.3.6.1.4.1.13742.9.1.3.1.1.5 |
alertStateIndicates whether LHX controler is in alert state or not.
To acknowledge alert status, set alertState to 2 (false).
Setting alertState to 1 (true) is undefined.rw TruthValue (SNMPv2-TC) .1.3.6.1.4.1.13742.9.1.3.1.1.6 |
modelThe model indentifier of an LHX controller.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.13742.9.1.3.1.1.7 |
fwVersionThe firmware version of an LHX controller.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.13742.9.1.3.1.1.8 |
gwSensors OBJECT IDENTIFIER .1.3.6.1.4.1.13742.9.1.4 |
sensorConfigurationTableA list of lhx sensor configuration extries.
The number of entries is given by the value of portCount. SEQUENCE OF SensorConfigurationEntryStruct .1.3.6.1.4.1.13742.9.1.4.1 |
sensorConfigurationEntryAn entry containing parameters for an lhx. SensorConfigurationEntryStruct .1.3.6.1.4.1.13742.9.1.4.1.1 |
portIdxA unique value for each port. Its value
ranges between 1 and the value of portCount. Integer32 .1.3.6.1.4.1.13742.9.1.4.1.1.1 |
sensorTypeIdxA unique value for the type of sensor. Integer32 .1.3.6.1.4.1.13742.9.1.4.1.1.2 |
sensorIdxA unique value for each sensor. Its value
ranges between 1 and the value of sensorCount. Integer32 .1.3.6.1.4.1.13742.9.1.4.1.1.3 |
sensorLabelThe short ID of the sensor (e.g. F1, M2).ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.13742.9.1.4.1.1.4 |
sensorUnitThe base units.
This parameter does not apply to state sensors.ro SensorUnitsEnumeration .1.3.6.1.4.1.13742.9.1.4.1.1.5 |
sensorDecimalDigitsThe number of digits displayed to the right of the decimal point.
This parameter does not apply to state sensors.ro Unsigned32 .1.3.6.1.4.1.13742.9.1.4.1.1.6 |
sensorMaximumThe largest possible value.
The value of this OID variable should be scaled by
sensorDecimalDigits. For example, if the value is 1 and
sensorDecimalDigits is 2, then actual value is 0.01.
This parameter does not apply to state sensors.ro Integer32 .1.3.6.1.4.1.13742.9.1.4.1.1.7 |
sensorMinimumThe smallest possible value.
The value of this OID variable should be scaled by
sensorDecimalDigits. For example, if the value is 1 and
sensorDecimalDigits is 2, then actual value is 0.01.
This parameter does not apply to state sensors.ro Integer32 .1.3.6.1.4.1.13742.9.1.4.1.1.8 |
sensorHysteresisThe hysteresis used for deassertions.
The value of this OID variable should be scaled by
sensorDecimalDigits. For example, if the value is 1 and
sensorDecimalDigits is 2, then actual value is 0.01.
This parameter does not apply to state sensors.rw Unsigned32 .1.3.6.1.4.1.13742.9.1.4.1.1.9 |
sensorLowerCriticalThresholdThe lower critical threshold.
The value of this OID variable should be scaled by
sensorDecimalDigits. For example, if the value is 1 and
sensorDecimalDigits is 2, then actual value is 0.01.
This parameter does not apply to state sensors.rw Integer32 .1.3.6.1.4.1.13742.9.1.4.1.1.10 |
sensorLowerWarningThresholdThe lower non-critical (warning) threshold.
The value of this OID variable should be scaled by
sensorDecimalDigits. For example, if the value is 1 and
sensorDecimalDigits is 2, then actual value is 0.01.
This parameter does not apply to state sensors.rw Integer32 .1.3.6.1.4.1.13742.9.1.4.1.1.11 |
sensorUpperCriticalThresholdThe upper critical threshold.
The value of this OID variable should be scaled by
sensorDecimalDigits. For example, if the value is 1 and
sensorDecimalDigits is 2, then actual value is 0.01.
This parameter does not apply to state sensors.rw Integer32 .1.3.6.1.4.1.13742.9.1.4.1.1.12 |
sensorUpperWarningThresholdThe upper non-critical (warning) threshold.
The value of this OID variable should be scaled by
sensorDecimalDigits. For example, if the value is 1 and
sensorDecimalDigits is 2, then actual value is 0.01.
This parameter does not apply to state sensors.rw Integer32 .1.3.6.1.4.1.13742.9.1.4.1.1.13 |
sensorEnabledThresholdsA bit string which indicates which thresholds are enabled.
This parameter does not apply to state sensors.rw Bits .1.3.6.1.4.1.13742.9.1.4.1.1.14 |
sensorThresholdMaximumThe largest possible threshold value.
The value of this OID variable should be scaled by
sensorDecimalDigits. For example, if the value is 1 and
sensorDecimalDigits is 2, then actual value is 0.01.
This parameter does not apply to state sensors.ro Integer32 .1.3.6.1.4.1.13742.9.1.4.1.1.15 |
sensorThresholdMinimumThe smallest possible threshold value.
The value of this OID variable should be scaled by
sensorDecimalDigits. For example, if the value is 1 and
sensorDecimalDigits is 2, then actual value is 0.01.
This parameter does not apply to state sensors.ro Integer32 .1.3.6.1.4.1.13742.9.1.4.1.1.16 |
sensorNameThe descriptive ID of the sensor (e.g. Fan Speed 1).ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.13742.9.1.4.1.1.17 |
measurements OBJECT IDENTIFIER .1.3.6.1.4.1.13742.9.2 |
sensorMeasurementsTableA list of external sensor entries. The number of
entries is given by the value of sensorCount
for the LHX. SEQUENCE OF SensorMeasurementsEntryStruct .1.3.6.1.4.1.13742.9.2.1 |
sensorMeasurementsEntryAn entry containing measurement objects for an external sensor. SensorMeasurementsEntryStruct .1.3.6.1.4.1.13742.9.2.1.1 |
measurementsSensorIsAvailableIs the sensor available?ro TruthValue (SNMPv2-TC) .1.3.6.1.4.1.13742.9.2.1.1.1 |
measurementsSensorStateThe sensor state.ro SensorStateEnumeration .1.3.6.1.4.1.13742.9.2.1.1.2 |
measurementsSensorValueThe sensor reading.
This parameter does not apply to state sensors.ro Integer32 .1.3.6.1.4.1.13742.9.2.1.1.3 |
measurementsSensorTimeStampThe sensor reading timestamp.ro Unsigned32 .1.3.6.1.4.1.13742.9.2.1.1.4 |
conformance OBJECT IDENTIFIER .1.3.6.1.4.1.13742.9.3 |
compliances OBJECT IDENTIFIER .1.3.6.1.4.1.13742.9.3.1 |
groups OBJECT IDENTIFIER .1.3.6.1.4.1.13742.9.3.2 |
More MIBs from Raritan
Browse all RaritanMIBs →SNMP MIB module
The PDU-MIB enables SNMP-based monitoring and management of Raritan Dominion PX Power Distribution Units, providing access to power metrics such as voltage, current, power consumption, and outlet-level status for individual PDU ports.
SNMP MIB module
The RemoteKVMDevice-MIB enables SNMP-based monitoring and management of Raritan KX enterprise KVM-over-IP devices, specifically tracking session states, port connectivity, and hardware status indicators for remote console access.
The ASSETMANAGEMENT-MIB enables Raritan Computer devices to expose inventory attributes, including asset identifiers, serial numbers, and hardware configuration details, via SNMP for centralized asset tracking. This module facilitates the automated discovery and management of physical and logical asset records within enterprise infrastructure environments.
The RARITANCCv2-MIB enables SNMP-based monitoring and management of Raritan Inc. Power Distribution Units (PDUs) and KVM over IP devices, specifically exposing metrics for power consumption, outlet status, environmental sensors, and remote console session states.