ELTEK-GENERIC-MIB
Detailed view of the defined objects, syntax rules, and hierarchical paths.
162
Objects
Active
Status
4
Dependencies
Imported Objects
Objects
162 total| Object Name |
|---|
eltekPlant OBJECT IDENTIFIER .1.3.6.1.4.1.12148.7 |
controlSystem OBJECT IDENTIFIER .1.3.6.1.4.1.12148.7.1 |
systemTime OBJECT IDENTIFIER .1.3.6.1.4.1.12148.7.1.1 |
systemTimeTimeThe system date and time. Used for event timestamps and loggingro DisplayString .1.3.6.1.4.1.12148.7.1.1.1 |
systemInfoRefreshThis object will re-initialize the agent, updating MIB data values.rw Enumeration .1.3.6.1.4.1.12148.7.1.2 |
systemTrapRepeatRateThis object sets the repeat rate of any active traps, in seconds. Entering 0 (zero) will prevent repeating traps - one trap only will be sent per alarm event.rw Integer32 .1.3.6.1.4.1.12148.7.1.3 |
systemSendOffTrapA separate off-trap will be issued when an alarm condition goes off, if this flag is set to 1. Entering 0 (zero) will prevent OFF traps from being transmitted.rw Enumeration .1.3.6.1.4.1.12148.7.1.4 |
dcSystem OBJECT IDENTIFIER .1.3.6.1.4.1.12148.7.2 |
dcPlant OBJECT IDENTIFIER .1.3.6.1.4.1.12148.7.2.1 |
systemSiteInfo OBJECT IDENTIFIER .1.3.6.1.4.1.12148.7.2.1.3 |
systemSiteInfoCustomerThe Customer name (as stored in the Smartpack Control Unit)ro DisplayString .1.3.6.1.4.1.12148.7.2.1.3.1 |
systemSiteInfoLocationThe system/site Location details (as stored in the Smartpack Control Unit).ro DisplayString .1.3.6.1.4.1.12148.7.2.1.3.2 |
systemSiteInfoMessage1The system/site Info Message record #1 (as stored in the Smartpack Control Unit). 31 Bytes.ro DisplayString .1.3.6.1.4.1.12148.7.2.1.3.3 |
systemSiteInfoMessage2The system/site Info Message record #2 (as stored in the Smartpack Control Unit). 31 Bytes.ro DisplayString .1.3.6.1.4.1.12148.7.2.1.3.4 |
systemSiteInfoInstalledDateThe system's Installed Date text string (as stored in the Smartpack Control Unit) 16bytes.ro DisplayString .1.3.6.1.4.1.12148.7.2.1.3.5 |
systemSiteInfoControllerTypeThe system Controller Module currently connected. AL175/MCU=0; AEON Gold=1; AL6000=2; Smartpack=3ro Enumeration .1.3.6.1.4.1.12148.7.2.1.3.6 |
systemSiteInfoSystemSeriaNumThe serial number for the complete systemro DisplayString .1.3.6.1.4.1.12148.7.2.1.3.7 |
systemSiteInfoControllerSeriaNumThe serial number for the system controllerro DisplayString .1.3.6.1.4.1.12148.7.2.1.3.8 |
systemNominalVoltageThe nominal voltage rating. 12V/24V/48V/60V systems 0=48V 1=24V 2=12V 3=26V 4=60Vro Enumeration .1.3.6.1.4.1.12148.7.2.1.4 |
systemOperationalStatusA summary status showing if the system is testing, boosting, floating etc. 0=Float, voltage regulated 1=Float, temperature comp. regulated; 2=equalize 3=battery testro Enumeration .1.3.6.1.4.1.12148.7.2.2 |
battery OBJECT IDENTIFIER .1.3.6.1.4.1.12148.7.3 |
batteryNameA descriptive name of the battery installed in the systemro DisplayString .1.3.6.1.4.1.12148.7.3.1 |
batteryVoltageThe measured battery voltage.ro Integer32 .1.3.6.1.4.1.12148.7.3.2 |
batteryCurrentThe measured battery current.ro Integer32 UNITS "Amperes; i.e. 20 = 20 Amperes" .1.3.6.1.4.1.12148.7.3.3 |
batteryTempThe battery temperaturero Integer32 .1.3.6.1.4.1.12148.7.3.4 |
batteryBreakerStatusThe state of the battery fuse/breaker can be either closed(0) or open(1)ro Enumeration .1.3.6.1.4.1.12148.7.3.5 |
batteryChargeCurrentLimitCtrlControl field for the battery charge limitation feature; 0=inactive, 1=active.rw Enumeration .1.3.6.1.4.1.12148.7.3.6 |
batteryChargeCurrentLimitValueBattery charging current limit valuerw Integer32 .1.3.6.1.4.1.12148.7.3.7 |
batteryTempCompEnableEnable (0) or Disable (1) Battery Temperature Compensated output regulation moderw Enumeration .1.3.6.1.4.1.12148.7.3.8 |
batteryFloatVoltConfigThe Voltage at which the DC System float charges.rw Integer32 .1.3.6.1.4.1.12148.7.3.9 |
batteryEqualizeVoltConfigThe Voltage at which the DC System boost charges the batteries.rw Integer32 .1.3.6.1.4.1.12148.7.3.10 |
batteryHighMajorAlarmVoltageConfigThe High Battery Voltage alarm limit set voltagerw Integer32 .1.3.6.1.4.1.12148.7.3.11 |
batteryHighMinorAlarmVoltageConfigThe High Battery Voltage alarm limit set voltagerw Integer32 UNITS "1/100 Volt; i.e. 5400 = 54.00V" .1.3.6.1.4.1.12148.7.3.12 |
batteryLowMajorAlarmVoltageConfigThe Low Battery Voltage Alarm limit set voltagerw Integer32 UNITS "1/100 Volt; i.e. 5400 = 54.00V" .1.3.6.1.4.1.12148.7.3.13 |
batteryLowMinorAlarmVoltageConfigThe Very Low Battery Voltage Alarm limit set voltagerw Integer32 UNITS "1/100 Volt; i.e. 5400 = 54.00V" .1.3.6.1.4.1.12148.7.3.14 |
batteryStartManualTestThis pushbutton will start a manual battery test if otherwise the system allows it.rw Enumeration .1.3.6.1.4.1.12148.7.3.15 |
batteryStartManualBoostThis pushbutton will start a manual battery boost if otherwise the system allows it.rw Enumeration .1.3.6.1.4.1.12148.7.3.16 |
batteryLVD OBJECT IDENTIFIER .1.3.6.1.4.1.12148.7.3.17 |
batteryLVDStatusContactor is closed(0) or open(1)ro Enumeration .1.3.6.1.4.1.12148.7.3.17.1 |
batteryLVDDisconnectVoltageThe Contactor Disconnect Voltagerw Integer32 .1.3.6.1.4.1.12148.7.3.17.2 |
batteryLVDConnectVoltageThe Contactor Reconnect Voltagerw Integer32 .1.3.6.1.4.1.12148.7.3.17.3 |
batteryMidpoint OBJECT IDENTIFIER .1.3.6.1.4.1.12148.7.3.18 |
batteryMidpointDeltaLimitVoltageThe allowable deviation of the midpoint battery voltage from the theoretical. Exceeding this value in either direction (+/-) causes an alarm staterw Integer32 UNITS "1/100 Volt; i.e. 25 = 2.50V" .1.3.6.1.4.1.12148.7.3.18.1 |
batteryMidpointIndexAn index of Battery Strings, for the batteryMidpointControlTable and batteryMidpointStatusTable arraysro Integer32 .1.3.6.1.4.1.12148.7.3.18.2 |
batteryMidpointControlTableA table of settings related to Battery Symmetry (midpoint) Monitoring SEQUENCE OF BatteryMidpointControlEntry .1.3.6.1.4.1.12148.7.3.18.3 |
batteryMidpointControlEntrySettings related to Battery Symmetry (midpoint) Monitoring, corresponding to the batteryMidpointIndex value BatteryMidpointControlEntry .1.3.6.1.4.1.12148.7.3.18.3.1 |
midpointEnableIDThe rectifier ID number of the rectifier record.ro Integer32 .1.3.6.1.4.1.12148.7.3.18.3.1.1 |
midpointEnableEnable (1) or Disable (0) the Battery Monitor channel which corresponds to the batteryMidpointIndex valuerw Enumeration .1.3.6.1.4.1.12148.7.3.18.3.1.2 |
batteryMidpointStatusTableA table of values and/or measurements related to Battery Symmetry (midpoint) Monitoring SEQUENCE OF BatteryMidpointStatusEntry .1.3.6.1.4.1.12148.7.3.18.4 |
batteryMidpointStatusEntryValues related to Battery Symmetry (midpoint) Monitoring, corresponding to the batteryMidpointIndex value BatteryMidpointStatusEntry .1.3.6.1.4.1.12148.7.3.18.4.1 |
midpointStatusIDThe rectifier ID number of the rectifier record.ro Integer32 .1.3.6.1.4.1.12148.7.3.18.4.1.1 |
midpointStatusStatus (0=Normal; 1=Alarm) of the Battery Monitor channel which corresponds to the batteryMidpointIndex valuero Enumeration .1.3.6.1.4.1.12148.7.3.18.4.1.2 |
midpointDeltaVoltageThe measured battery voltage deviation from midpoint of the Battery Monitor channel which corresponds to the batteryMidpointIndex value.ro Integer32 UNITS "1/100 Volt; i.e. 25 = 2.5V." .1.3.6.1.4.1.12148.7.3.18.4.1.3 |
loadDistribution OBJECT IDENTIFIER .1.3.6.1.4.1.12148.7.4 |
loadDistributionCurrentThe total load currentro Integer32 UNITS "Amperes; i.e. 20 = 20 Amperes" .1.3.6.1.4.1.12148.7.4.1 |
loadDistributionBreakerStatusThe state of the load fuse/breaker can be either closed(0) or open(1)ro Enumeration .1.3.6.1.4.1.12148.7.4.2 |
loadDistributionLVDStatus OBJECT IDENTIFIER .1.3.6.1.4.1.12148.7.4.3 |
loadLVD1EnableStatusThe status of contactors configuration. 'enabled' means that the contactor is i n use. 'disabled' means that the contactor is disconfigured and not in use.ro Enumeration .1.3.6.1.4.1.12148.7.4.3.1 |
loadLVD1StatusThe A Bus (primary loads) Contactor is closed(0) or open(1)ro Enumeration .1.3.6.1.4.1.12148.7.4.3.2 |
loadLVD1ConnectVoltageThe A Bus (primary loads) Contactor Connect Voltagerw Integer32 .1.3.6.1.4.1.12148.7.4.3.3 |
loadLVD1DisconnectVoltageThe A Bus (primary loads) Contactor Disconnect Voltagerw Integer32 .1.3.6.1.4.1.12148.7.4.3.4 |
loadLVD2EnableStatusThe status of contactors configuration. 'enabled' means that the contactor is i n use. 'disabled' means that the contactor is disconfigured and not in use.ro Enumeration .1.3.6.1.4.1.12148.7.4.3.5 |
loadLVD2StatusThe B Bus (secondary loads) Contactor is closed(0) or open(1)ro Enumeration .1.3.6.1.4.1.12148.7.4.3.6 |
loadLVD2ConnectVoltageThe B Bus (secondary loads) Contactor Connect Voltagerw Integer32 .1.3.6.1.4.1.12148.7.4.3.7 |
loadLVD2DisconnectVoltageThe B Bus (secondary loads) Contactor Disconnect Voltagerw Integer32 .1.3.6.1.4.1.12148.7.4.3.8 |
loadLVD3EnableStatusThe status of contactors configuration. 'enabled' means that the contactor is i n use. 'disabled' means that the contactor is disconfigured and not in use.ro Enumeration .1.3.6.1.4.1.12148.7.4.3.9 |
loadLVD3StatusThe C Bus (critical loads) Contactor is closed(0) or open(1)ro Enumeration .1.3.6.1.4.1.12148.7.4.3.10 |
loadLVD3ConnectVoltageThe C Bus (critical loads) Contactor Connect Voltagerw Integer32 .1.3.6.1.4.1.12148.7.4.3.11 |
loadLVD3DisconnectVoltageThe C Bus (critical loads) Contactor Disconnect Voltagerw Integer32 .1.3.6.1.4.1.12148.7.4.3.12 |
rectifier OBJECT IDENTIFIER .1.3.6.1.4.1.12148.7.5 |
rectifierInstalledRectifiersThe installed number of rectifiers for this DC Power System.ro Integer32 .1.3.6.1.4.1.12148.7.5.1 |
rectifierRectifiersActiveThe actual number of active rectifiers in this DC Power System.ro Integer32 .1.3.6.1.4.1.12148.7.5.2 |
rectifierTotalCurrentThe DC system's total available currentro Integer32 UNITS "Amperes; i.e. 20 = 20 Amperes" .1.3.6.1.4.1.12148.7.5.3 |
rectifierUtilizationUtilization in % of available rectifier capacityro Integer32 .1.3.6.1.4.1.12148.7.5.4 |
rectifierStatus OBJECT IDENTIFIER .1.3.6.1.4.1.12148.7.5.5 |
rectifierStatusNoIndexA starting index for the rectifierStatusTable arrayrw Integer32 .1.3.6.1.4.1.12148.7.5.5.1 |
rectifierStatusTableA table listing up to sixteen sequential recifiers, starting from the rectifier number specified by rectifierStatusNoIndex SEQUENCE OF RectifierStatusEntry .1.3.6.1.4.1.12148.7.5.5.2 |
rectifierStatusEntryA row of rectifier status data corresponding to the rectifierStatusNoIndex value RectifierStatusEntry .1.3.6.1.4.1.12148.7.5.5.2.1 |
rectifierStatusIDThe rectifier ID number of the rectifier record.ro Integer32 .1.3.6.1.4.1.12148.7.5.5.2.1.1 |
rectifierStatusStatusThe operational status of the rectifier record. absent (0), active (1), failed (2), walkin (3), disabledbycommand (4)ro Enumeration .1.3.6.1.4.1.12148.7.5.5.2.1.2 |
rectifierStatusOutputCurrentThe rectifier current of the rectifier record.ro Integer32 .1.3.6.1.4.1.12148.7.5.5.2.1.3 |
rectifierStatusOutputVoltageThe rectifier voltage of the rectifier record.ro Integer32 .1.3.6.1.4.1.12148.7.5.5.2.1.4 |
rectifierStatusTempThe heatsink temperature of the rectifier record.ro Integer32 .1.3.6.1.4.1.12148.7.5.5.2.1.5 |
rectifierStatusTypeThe rectifier article number string of the rectifier record.ro DisplayString .1.3.6.1.4.1.12148.7.5.5.2.1.6 |
rectifierStatusSKUThe rectifier Stock Keeping Unit number or other user-defined ID of the rectifier record.ro DisplayString .1.3.6.1.4.1.12148.7.5.5.2.1.7 |
rectifierStatusSerialNoThe rectifier serial number string of the rectifier record.ro DisplayString .1.3.6.1.4.1.12148.7.5.5.2.1.8 |
rectifierStatusRevisionLevelThe rectifier version number string of the rectifier record.ro DisplayString .1.3.6.1.4.1.12148.7.5.5.2.1.9 |
acDistribution OBJECT IDENTIFIER .1.3.6.1.4.1.12148.7.6 |
acVoltage1The AC Voltage of phase 1ro Integer32 UNITS "Volts AC" .1.3.6.1.4.1.12148.7.6.1 |
acVoltage2The AC Voltage of phase 2ro Integer32 UNITS "Volts AC" .1.3.6.1.4.1.12148.7.6.2 |
acVoltage3The AC Voltage of phase 3ro Integer32 UNITS "Volts AC" .1.3.6.1.4.1.12148.7.6.3 |
alarmGroup OBJECT IDENTIFIER .1.3.6.1.4.1.12148.7.7 |
alarmWellknownAlarms OBJECT IDENTIFIER .1.3.6.1.4.1.12148.7.7.1 |
alarmMajorHighBattVoltThe Very High Battery Voltage Alarmro Enumeration .1.3.6.1.4.1.12148.7.7.1.1 |
alarmMinorHighBattVoltThe High Battery Voltage alarmro Enumeration .1.3.6.1.4.1.12148.7.7.1.2 |
alarmMajorLowBattVoltThe Very Low Battery Voltage Alarmro Enumeration .1.3.6.1.4.1.12148.7.7.1.3 |
alarmMinorLowBattVoltThe Low Battery Voltage Alarmro Enumeration .1.3.6.1.4.1.12148.7.7.1.4 |
alarmMajorBatteryHighTempTemperature much too high alarm, or temperature compensation circuit / probe failure alarmro Enumeration .1.3.6.1.4.1.12148.7.7.1.5 |
alarmMinorBatteryHighTempTemperature much too high alarmro Enumeration .1.3.6.1.4.1.12148.7.7.1.6 |
alarmBatteryDisconnectOpenThe Battery Disconnect Contactor alarmro Enumeration .1.3.6.1.4.1.12148.7.7.1.7 |
alarmLVD1openThe A Bus (primary loads) Contactor alarm. The contactor dropout voltage has been reached and the contactor will release.ro Enumeration .1.3.6.1.4.1.12148.7.7.1.8 |
alarmLVD2openThe B Bus (secondary loads) Contactor alarm. The contactor dropout voltage has been reached and the contactor will release.ro Enumeration .1.3.6.1.4.1.12148.7.7.1.9 |
alarmLVD3openThe C Bus (critical loads) Contactor alarm. The contactor dropout voltage has been reached and the contactor will release.ro Enumeration .1.3.6.1.4.1.12148.7.7.1.10 |
alarmACmainsThe AC voltage has dropped below critical level, or one or more AC input phases was lost.ro Enumeration .1.3.6.1.4.1.12148.7.7.1.11 |
alarmBatteryBreakerOpenBattery string disconnect breaker/fuse alarmro Enumeration .1.3.6.1.4.1.12148.7.7.1.12 |
alarmDistributionBreakerOpenThe Load Distribution breaker/fuse alarmro Enumeration .1.3.6.1.4.1.12148.7.7.1.13 |
alarmMajorRectifierThis is a 'multiple rectifiers have failed' alarmro Enumeration .1.3.6.1.4.1.12148.7.7.1.14 |
alarmMinorRectifierThis is a 'one rectifier has failed' alarmro Enumeration .1.3.6.1.4.1.12148.7.7.1.15 |
alarmMajorBatteryMidpointBattery Symmetry (midpoint) Delta Voltage is badly out of limits alarmro Enumeration .1.3.6.1.4.1.12148.7.7.1.16 |
alarmMinorBatteryMidpointBattery Symmetry (midpoint) Delta Voltage out of limits alarmro Enumeration .1.3.6.1.4.1.12148.7.7.1.17 |
alarmBatteryLifeEndedThe battery capacity has dropped below critical level. A battery test has measured the fully charged capacity to be too low, and thus probably the battery lifecycle to be near expired.ro Enumeration .1.3.6.1.4.1.12148.7.7.1.18 |
alarmBatteryTestmodeEnteredThe system has lowered the battery charge voltage in order to discharge the batteries to a predefinend level. When the criteria for stopping the battery testing is reached, the charge voltage is increased to commence normal charging.ro Enumeration .1.3.6.1.4.1.12148.7.7.1.19 |
alarmBatteryBoostmodeEnteredThe system has increased the battery charge voltage in order to equalize the battery cells charging. When the criteria for stopping the battery equalizing is reached, the charge voltage is lowered to commence normal charging.ro Enumeration .1.3.6.1.4.1.12148.7.7.1.20 |
alarmUserConfigurable1Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm.ro Enumeration .1.3.6.1.4.1.12148.7.7.1.21 |
alarmUserConfigurable2Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm.ro Enumeration .1.3.6.1.4.1.12148.7.7.1.22 |
alarmUserConfigurable3Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm.ro Enumeration .1.3.6.1.4.1.12148.7.7.1.23 |
alarmUserConfigurable4Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm.ro Enumeration .1.3.6.1.4.1.12148.7.7.1.24 |
alarmUserConfigurable5Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm.ro Enumeration .1.3.6.1.4.1.12148.7.7.1.25 |
alarmUserConfigurable6Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm.ro Enumeration .1.3.6.1.4.1.12148.7.7.1.26 |
alarmUserConfigurable7Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm.ro Enumeration .1.3.6.1.4.1.12148.7.7.1.27 |
alarmUserConfigurable8Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm.ro Enumeration .1.3.6.1.4.1.12148.7.7.1.28 |
alarmUserConfigurable9Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm.ro Enumeration .1.3.6.1.4.1.12148.7.7.1.29 |
alarmUserConfigurable10Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm.ro Enumeration .1.3.6.1.4.1.12148.7.7.1.30 |
alarmUserConfigurable11Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm.ro Enumeration .1.3.6.1.4.1.12148.7.7.1.31 |
alarmUserConfigurable12Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm.ro Enumeration .1.3.6.1.4.1.12148.7.7.1.32 |
alarmUserConfigurable13Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm.ro Enumeration .1.3.6.1.4.1.12148.7.7.1.33 |
alarmUserConfigurable14Generic alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm.ro Enumeration .1.3.6.1.4.1.12148.7.7.1.34 |
dcSystemTrapsThis branch contains the Alarm Notification Traps, which duplicate the alarmGroup OIDs. Each alarm condition is represented by a Alarm Condition Trap and an associated OFF Trap, which is optionally transmitted according to the state of OID systemSendOffTrap Unknown .1.3.6.1.4.1.12148.7.8 |
alarmMajorHighBattVoltTrapThe Very High Battery Voltage alarm NOTIFICATION-TYPE .1.3.6.1.4.1.12148.7.8.1 |
alarmMinorHighBattVoltTrapThe High Battery Voltage alarm NOTIFICATION-TYPE .1.3.6.1.4.1.12148.7.8.2 |
alarmMajorLowBattVoltTrapThe Very Low Battery Voltage Alarm NOTIFICATION-TYPE .1.3.6.1.4.1.12148.7.8.3 |
alarmMinorLowBattVoltTrapThe Low Battery Voltage Alarm NOTIFICATION-TYPE .1.3.6.1.4.1.12148.7.8.4 |
alarmMajorBatteryHighTempTrapHigh Battery temperature alarm or Temperature Compensation circuit / probe failure alarm NOTIFICATION-TYPE .1.3.6.1.4.1.12148.7.8.5 |
alarmMinorBatteryHighTempTrapHigh Battery temperature alarm NOTIFICATION-TYPE .1.3.6.1.4.1.12148.7.8.6 |
alarmBatteryDisconnectOpenTrapThe Battery Disconnect Contactor alarm NOTIFICATION-TYPE .1.3.6.1.4.1.12148.7.8.7 |
alarmLVD1openTrapThe A Bus (primary loads) Contactor is open alarm NOTIFICATION-TYPE .1.3.6.1.4.1.12148.7.8.8 |
alarmLVD2openTrapThe B Bus (secondary loads) Contactor is open alarm NOTIFICATION-TYPE .1.3.6.1.4.1.12148.7.8.9 |
alarmLVD3openTrapThe C Bus (critical loads) Contactor alarm. The contactor dropout voltage has been reached and the contactor is released. NOTIFICATION-TYPE .1.3.6.1.4.1.12148.7.8.10 |
alarmACmainsTrapThe AC voltage has dropped below critical level, or one or more AC input phases was lost. NOTIFICATION-TYPE .1.3.6.1.4.1.12148.7.8.11 |
alarmBatteryBreakerOpenTrapBattery string disconnect breaker/fuse alarm NOTIFICATION-TYPE .1.3.6.1.4.1.12148.7.8.12 |
alarmDistributionBreakerOpenTrapThe Load Distribution breaker/fuse alarm NOTIFICATION-TYPE .1.3.6.1.4.1.12148.7.8.13 |
alarmMajorRectifierTrapThis is a 'multiple rectifiers have failed' alarm NOTIFICATION-TYPE .1.3.6.1.4.1.12148.7.8.14 |
alarmMinorRectifierTrapThis is a 'one rectifier has failed' alarm NOTIFICATION-TYPE .1.3.6.1.4.1.12148.7.8.15 |
alarmMajorBatteryMidpointTrapBattery Symmetry (midpoint) Delta Voltage out of 'major fault' limits alarm NOTIFICATION-TYPE .1.3.6.1.4.1.12148.7.8.16 |
alarmMinorBatteryMidpointTrapBattery Symmetry (midpoint) Delta Voltage out of limits alarm NOTIFICATION-TYPE .1.3.6.1.4.1.12148.7.8.17 |
alarmBatteryLifeEndedTrapThe battery capacity has dropped below critical level. A battery test has measured the fully charged capacity to be too low, and thus probably the battery lifecycle to be near expired. NOTIFICATION-TYPE .1.3.6.1.4.1.12148.7.8.18 |
alarmBatteryTestmodeEnteredTrapThe system has lowered the battery charge voltage in order to discharge the batteries to a predefinend level. When the criteria for stopping the battery testing is reached, the charge voltage is increased to commence normal charging. NOTIFICATION-TYPE .1.3.6.1.4.1.12148.7.8.19 |
alarmBatteryBoostmodeEnteredTrapThe system has increased the battery charge voltage in order to equalize the battery cells charging. When the criteria for stopping the battery equalizing is reached, the charge voltage is lowered to commence normal charging. NOTIFICATION-TYPE .1.3.6.1.4.1.12148.7.8.20 |
alarmUserConfigurable1TrapGeneric alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm. NOTIFICATION-TYPE .1.3.6.1.4.1.12148.7.8.21 |
alarmUserConfigurable2TrapGeneric alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm. NOTIFICATION-TYPE .1.3.6.1.4.1.12148.7.8.22 |
alarmUserConfigurable3TrapGeneric alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm. NOTIFICATION-TYPE .1.3.6.1.4.1.12148.7.8.23 |
alarmUserConfigurable4TrapGeneric alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm. NOTIFICATION-TYPE .1.3.6.1.4.1.12148.7.8.24 |
alarmUserConfigurable5TrapGeneric alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm. NOTIFICATION-TYPE .1.3.6.1.4.1.12148.7.8.25 |
alarmUserConfigurable6TrapGeneric alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm. NOTIFICATION-TYPE .1.3.6.1.4.1.12148.7.8.26 |
alarmUserConfigurable7TrapGeneric alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm. NOTIFICATION-TYPE .1.3.6.1.4.1.12148.7.8.27 |
alarmUserConfigurable8TrapGeneric alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm. NOTIFICATION-TYPE .1.3.6.1.4.1.12148.7.8.28 |
alarmUserConfigurable9TrapGeneric alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm. NOTIFICATION-TYPE .1.3.6.1.4.1.12148.7.8.29 |
alarmUserConfigurable10TrapGeneric alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm. NOTIFICATION-TYPE .1.3.6.1.4.1.12148.7.8.30 |
alarmUserConfigurable11TrapGeneric alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm. NOTIFICATION-TYPE .1.3.6.1.4.1.12148.7.8.31 |
alarmUserConfigurable12TrapGeneric alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm. NOTIFICATION-TYPE .1.3.6.1.4.1.12148.7.8.32 |
alarmUserConfigurable13TrapGeneric alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm. NOTIFICATION-TYPE .1.3.6.1.4.1.12148.7.8.33 |
alarmUserConfigurable14TrapGeneric alarm linked to user specified alarms. These have no specific name in the MIB. User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm. NOTIFICATION-TYPE .1.3.6.1.4.1.12148.7.8.34 |