AI MIB Summary

The ELTEK-DISTRIBUTED-MIB facilitates SNMP monitoring of ELTEK SmartPack and ComPack power distribution units running WebPower software versions 2.x through 4.7, specifically tracking operational parameters across distributed branch architectures. This module enables the collection of device status, environmental telemetry, and firmware version data for legacy and modern ELTEK power management systems.

An ongoing effort toward a generic MIB for all ELTEK products. Branch overview: Aeongold branch will be 1 AL175 branch will be 2 AL6000 branch will be 3 Internal used branch will be 4 Internal used branch will be 5 OEM Smartpack branch will be 6 ELTEK Common branch will be 7 (SmartPack, MCU, AEON w/WebPower sw V2.x) ELTEK Distributed branch will be 8 (SmartPack w/WebPower sw V3.x) ELTEK Distributed V2 branch will be 9 (SmartPack w/WebPower sw V4.0) ELTEK Distributed V3 branch will be 9 (SmartPack w/WebPower sw V4.1) ELTEK Distributed V4 branch will be 9 (SmartPack w/WebPower sw V4.1, V4.2, V4.3 and compack 1.xx) ELTEK Distributed V5 branch will be 9 (SmartPack w/WebPower sw V4.6) ELTEK Distributed V6 branch will be 9 (SmartPack w/WebPower sw V4.6, Smartpack2 V1.1) ELTEK Distributed V7 branch will be 9 (SmartPack w/WebPower sw V4.7, ComPack V1.04, Smartpack2 V1.1, V1.2)
Main OID:
eltek.1.3.6.1.4.1.12148
338
Objects
Active
Status
3
Dependencies

Imported Objects

Objects

338 total
Object Name
eltekAn ongoing effort toward a generic MIB for all ELTEK products. Branch overview: Aeongold branch will be 1 AL175 branch will be 2 AL6000 branch will be 3 Internal used branch will be 4 Internal used branch will be 5 OEM Smartpack branch will be 6 ELTEK Common branch will be 7 (SmartPack, MCU, AEON w/WebPower sw V2.x) ELTEK Distributed branch will be 8 (SmartPack w/WebPower sw V3.x) ELTEK Distributed V2 branch will be 9 (SmartPack w/WebPower sw V4.0) ELTEK Distributed V3 branch will be 9 (SmartPack w/WebPower sw V4.1) ELTEK Distributed V4 branch will be 9 (SmartPack w/WebPower sw V4.1, V4.2, V4.3 and compack 1.xx) ELTEK Distributed V5 branch will be 9 (SmartPack w/WebPower sw V4.6) ELTEK Distributed V6 branch will be 9 (SmartPack w/WebPower sw V4.6, Smartpack2 V1.1) ELTEK Distributed V7 branch will be 9 (SmartPack w/WebPower sw V4.7, ComPack V1.04, Smartpack2 V1.1, V1.2)
MODULE-IDENTITY
.1.3.6.1.4.1.12148
eltekDistributedPlantV7
OBJECT IDENTIFIER
.1.3.6.1.4.1.12148.9
controlSystem
OBJECT IDENTIFIER
.1.3.6.1.4.1.12148.9.1
systemTime
OBJECT IDENTIFIER
.1.3.6.1.4.1.12148.9.1.1
systemTimeTimeThe system date and time. Used for event timestamps and loggingro
DisplayString
.1.3.6.1.4.1.12148.9.1.1.1
systemInfoRefreshThis is a push button function that will rebuild all the dynamic SNMP tables. When control units are removed or added this function must be executed to make sure the tables are updated.rw
Enumeration
.1.3.6.1.4.1.12148.9.1.2
systemTrapRepeatRateThis object sets the repeat rate of any active traps, in minutes. Entering 0 (zero) will prevent repeating traps - one trap only will be sent per alarm event.rw
Integer32
.1.3.6.1.4.1.12148.9.1.3
systemSendOffTrapA separate off-trap will be issued when an alarm condition goes off, if this flag is set to 1. Entering 0 (zero) will prevent OFF traps from being transmitted.rw
Enumeration
.1.3.6.1.4.1.12148.9.1.4
systemNumOfControlUnitsThe number of Control units in a distributed system.ro
Integer32
.1.3.6.1.4.1.12148.9.1.5
systemControlUnitIndexIndex used for navigating in the table for configurable inputs.ro
Integer32
.1.3.6.1.4.1.12148.9.1.6
systemControlUnitTableThis table contains the status of the programmable inputs. There is one row for each Control unit.
SEQUENCE OF SystemControlUnitEntry
.1.3.6.1.4.1.12148.9.1.7
systemControlUnitEntry
SystemControlUnitEntry
.1.3.6.1.4.1.12148.9.1.7.1
inputControlUnitIDThe ID of which Control unit to be read.ro
Integer32
.1.3.6.1.4.1.12148.9.1.7.1.1
inputUserConfigurable1Programmable input status. The description of the input is found in the systemControlUnitInputTablero
Enumeration
.1.3.6.1.4.1.12148.9.1.7.1.2
inputUserConfigurable2Programmable input status. The description of the input is found in the systemControlUnitInputTablero
Enumeration
.1.3.6.1.4.1.12148.9.1.7.1.3
inputUserConfigurable3Programmable input status. The description of the input is found in the systemControlUnitInputTablero
Enumeration
.1.3.6.1.4.1.12148.9.1.7.1.4
inputUserConfigurable4Programmable input status. The description of the input is found in the systemControlUnitInputTablero
Enumeration
.1.3.6.1.4.1.12148.9.1.7.1.5
inputUserConfigurable5Programmable input status. The description of the input is found in the systemControlUnitInputTablero
Enumeration
.1.3.6.1.4.1.12148.9.1.7.1.6
inputUserConfigurable6Programmable input status. The description of the input is found in the systemControlUnitInputTablero
Enumeration
.1.3.6.1.4.1.12148.9.1.7.1.7
inputUserConfigurable7Programmable input status. The description of the input is found in the systemControlUnitInputTablero
Enumeration
.1.3.6.1.4.1.12148.9.1.7.1.8
inputUserConfigurable8Programmable input status. The description of the input is found in the systemControlUnitInputTablero
Enumeration
.1.3.6.1.4.1.12148.9.1.7.1.9
inputUserConfigurable9Programmable input status. The description of the input is found in the systemControlUnitInputTablero
Enumeration
.1.3.6.1.4.1.12148.9.1.7.1.10
inputUserConfigurable10Programmable input status. The description of the input is found in the systemControlUnitInputTablero
Enumeration
.1.3.6.1.4.1.12148.9.1.7.1.11
systemLinkStatusA flag showing the status of the serial port used between the HEIDI Webpower adapter or embedded WEB/SNMP card and the Smartpack Control system. If this flag shows status linkdown, the propable cause is that the wrong baudrate is set, which again is likely to happen when booting a brand new board. Execute a 'systemInitiateEEPROM' command to fix. Not applicable for ComPack control unitro
Enumeration
.1.3.6.1.4.1.12148.9.1.8
systemInitiateEEPROMPushbutton function that initiates a forced write of default data to the SB70/SB72 eeprom. This function is used for productiontest only. The 3rd party OS used in this application are not able to write default data to EEPROM at boot time. A minimum set of configuration is thus created in RAM. A production test facility must therefore run this command as a part of the production test for the unit to function properly.rwdeprecated
Enumeration
.1.3.6.1.4.1.12148.9.1.9
systemLastDigInputThe last Prog.Input that generated a trap. Used by Traps only.ro
Integer32
.1.3.6.1.4.1.12148.9.1.10
systemTrapCounterThe number of times a trap has been repeated.. Only acessible for Traps.ro
Counter32
.1.3.6.1.4.1.12148.9.1.11
systemHeartBeatTrapRepeatRateThe repeat rate for the systemHeartBeatTrap. Setting this value to zero will disable the HeartBeatTrap.rw
Integer32
.1.3.6.1.4.1.12148.9.1.12
systemResetManualAlarmsA pushutton that resets all manually resettable alarms in the controlsystem. Alarms that is not manually resettable will not be affected by this.rw
Enumeration
.1.3.6.1.4.1.12148.9.1.13
systemControlUnitInputIndexIndex used for navigating in the table for configurable inputs.ro
Integer32
.1.3.6.1.4.1.12148.9.1.14
systemControlUnitInputTableThis table contains the description of the programmable inputs. There is one row for each Control unit. Programmable input alarms will have description attached to the traps that explains the alarm. Default description is: ProgInput <Control unit ID>.x
SEQUENCE OF SystemControlUnitInputEntry
.1.3.6.1.4.1.12148.9.1.15
systemControlUnitInputEntry
SystemControlUnitInputEntry
.1.3.6.1.4.1.12148.9.1.15.1
inputUnitIDThe ID of which Control unit to be read.ro
Integer32
.1.3.6.1.4.1.12148.9.1.15.1.1
inputUserConfigurableText1Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Control unit ID>.1.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.12148.9.1.15.1.2
inputUserConfigurableText2Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Control unit ID>.2.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.12148.9.1.15.1.3
inputUserConfigurableText3Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Control unit ID>.3.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.12148.9.1.15.1.4
inputUserConfigurableText4Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Control unit ID>.4.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.12148.9.1.15.1.5
inputUserConfigurableText5Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Control unit ID>.5.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.12148.9.1.15.1.6
inputUserConfigurableText6Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Control unit ID>.6.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.12148.9.1.15.1.7
inputUserConfigurableText7Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Control unit ID>.7.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.12148.9.1.15.1.8
inputUserConfigurableText8Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Control unit ID>.8.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.12148.9.1.15.1.9
inputUserConfigurableText9Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Control unit ID>.9.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.12148.9.1.15.1.10
inputUserConfigurableText10Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Control unit ID>.10.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.12148.9.1.15.1.11
systemResetCtrlSystemA pushbutton function that resets the control system. Configuration data will be kept.rwdeprecated
Enumeration
.1.3.6.1.4.1.12148.9.1.16
ioUnits
OBJECT IDENTIFIER
.1.3.6.1.4.1.12148.9.1.17
ioUnitNumberOfUnitsro
Integer32
.1.3.6.1.4.1.12148.9.1.17.1
ioUnitsIndexro
Integer32
.1.3.6.1.4.1.12148.9.1.17.2
ioUnitsTable
SEQUENCE OF IoUnitsEntry
.1.3.6.1.4.1.12148.9.1.17.3
ioUnitsEntry
IoUnitsEntry
.1.3.6.1.4.1.12148.9.1.17.3.1
ioUnitIDro
Integer32
.1.3.6.1.4.1.12148.9.1.17.3.1.1
ioUnitOutDoorTemp1The measured value of the temperature input. Depending on the global setting in the Control unit, this value will be presented in Celsius or Fahrenheit.ro
Integer32 UNITS "Deg. C/F; i.e. 25 = 25 Deg."
.1.3.6.1.4.1.12148.9.1.17.3.1.2
ioUnitOutDoorTemp2The measured value of the temperature input. Depending on the global setting in the Control unit, this value will be presented in Celsius or Fahrenheit.ro
Integer32 UNITS "Deg. C/F; i.e. 25 = 25 Deg."
.1.3.6.1.4.1.12148.9.1.17.3.1.3
ioUnitFanSpeed1The speed of the cooling/ circulation fan. The speed is a percentage of max RPM.ro
Integer32 UNITS "Percent %"
.1.3.6.1.4.1.12148.9.1.17.3.1.4
ioUnitFanSpeedDeltaValue1The deviation of the cooling/circulation fans speed set value. Is a percentage of the desired value.ro
Integer32 UNITS "Percent %"
.1.3.6.1.4.1.12148.9.1.17.3.1.5
ioUnitFanSpeed2The speed of the cooling/ circulation fan. The speed is a percentage of max RPM.ro
Integer32 UNITS "Percent %"
.1.3.6.1.4.1.12148.9.1.17.3.1.6
ioUnitFanSpeedDeltaValue2The deviation of the cooling/circulation fans speed set value. Is a percentage of the desired value.ro
Integer32 UNITS "Percent %"
.1.3.6.1.4.1.12148.9.1.17.3.1.7
ioUnitProgInputText1Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <I/Ounit ID>.1ro
DisplayString
.1.3.6.1.4.1.12148.9.1.17.3.1.8
ioUnitProgInputStatus1Programmable input status.ro
Enumeration
.1.3.6.1.4.1.12148.9.1.17.3.1.9
ioUnitProgInputText2Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <I/Ounit ID>.2ro
DisplayString
.1.3.6.1.4.1.12148.9.1.17.3.1.10
ioUnitProgInputStatus2Programmable input status.ro
Enumeration
.1.3.6.1.4.1.12148.9.1.17.3.1.11
ioUnitProgInputText3Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <I/Ounit ID>.3ro
DisplayString
.1.3.6.1.4.1.12148.9.1.17.3.1.12
ioUnitProgInputStatus3Programmable input status.ro
Enumeration
.1.3.6.1.4.1.12148.9.1.17.3.1.13
ioUnitProgInputText4Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <I/Ounit ID>.4ro
DisplayString
.1.3.6.1.4.1.12148.9.1.17.3.1.14
ioUnitProgInputStatus4Programmable input status.ro
Enumeration
.1.3.6.1.4.1.12148.9.1.17.3.1.15
ioUnitProgInputText5Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <I/Ounit ID>.5ro
DisplayString
.1.3.6.1.4.1.12148.9.1.17.3.1.16
ioUnitProgInputStatus5Programmable input status.ro
Enumeration
.1.3.6.1.4.1.12148.9.1.17.3.1.17
ioUnitProgInputText6Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <I/Ounit ID>.6ro
DisplayString
.1.3.6.1.4.1.12148.9.1.17.3.1.18
ioUnitProgInputStatus6Programmable input status.ro
Enumeration
.1.3.6.1.4.1.12148.9.1.17.3.1.19
ioUnitProgInputValue1The value read on input.ro
Integer32 UNITS "1/100 Volt; i.e. 500 = 5.00V"
.1.3.6.1.4.1.12148.9.1.17.3.1.20
ioUnitProgInputValue2The value read on input.ro
Integer32 UNITS "1/100 Volt; i.e. 500 = 5.00V"
.1.3.6.1.4.1.12148.9.1.17.3.1.21
ioUnitProgInputValue3The value read on input.ro
Integer32 UNITS "1/100 Volt; i.e. 500 = 5.00V"
.1.3.6.1.4.1.12148.9.1.17.3.1.22
ioUnitProgInputValue4The value read on input.ro
Integer32 UNITS "1/100 Volt; i.e. 500 = 5.00V"
.1.3.6.1.4.1.12148.9.1.17.3.1.23
ioUnitProgInputValue5The value read on input.ro
Integer32 UNITS "1/100 Volt; i.e. 500 = 5.00V"
.1.3.6.1.4.1.12148.9.1.17.3.1.24
ioUnitProgInputValue6The value read on input.ro
Integer32 UNITS "1/100 Volt; i.e. 500 = 5.00V"
.1.3.6.1.4.1.12148.9.1.17.3.1.25
systemServiceModeThis is a switch function to activate (1) or deactivate (0) servicemode. Status can also be read. Servicemode prevent the system to operate relays or send traps or mail.rwdeprecated
Enumeration
.1.3.6.1.4.1.12148.9.1.18
dcSystem
OBJECT IDENTIFIER
.1.3.6.1.4.1.12148.9.2
dcPlant
OBJECT IDENTIFIER
.1.3.6.1.4.1.12148.9.2.1
systemSiteInfo
OBJECT IDENTIFIER
.1.3.6.1.4.1.12148.9.2.1.3
systemSiteInfoCustomerThe Customer name (as stored in the Control Unit).ro
DisplayString
.1.3.6.1.4.1.12148.9.2.1.3.1
systemSiteInfoLocationThe system/site Location details (as stored in the Control Unit).ro
DisplayString
.1.3.6.1.4.1.12148.9.2.1.3.2
systemSiteInfoMessage1The system/site Info Message record #1 (as stored in the Control Unit). 31 Bytes.ro
DisplayString
.1.3.6.1.4.1.12148.9.2.1.3.3
systemSiteInfoMessage2The system/site Info Message record #2 (as stored in the Control Unit). 31 Bytes.ro
DisplayString
.1.3.6.1.4.1.12148.9.2.1.3.4
systemSiteInfoInstalledDateThe system's Installed Date text string (as stored in the Control Unit) 16bytes.ro
DisplayString
.1.3.6.1.4.1.12148.9.2.1.3.5
systemSiteInfoControllerTypeThe system Controller Module currently connected. 0 = AL175 1 = AL4000 (Aeon Gold) 2 = AL6000 3 = AL175OEM 4 = MCU 5 = SmartPack 6 = ComPackro
Enumeration
.1.3.6.1.4.1.12148.9.2.1.3.6
systemSiteInfoSystemSeriaNumThe serial number for the complete system.ro
DisplayString
.1.3.6.1.4.1.12148.9.2.1.3.7
systemSiteInfoControllerSeriaNumThe serial number for Control unit 1.ro
DisplayString
.1.3.6.1.4.1.12148.9.2.1.3.8
systemNominalVoltageThe nominal voltage rating. 24V/48V/60V systems. 0=48V 1=24V 2=Not used 3=Not used 4=60Vro
Enumeration
.1.3.6.1.4.1.12148.9.2.1.4
systemOperationalStatusA summary status showing if the system is testing, boosting, floating etc. 0=Float, voltage regulated 1=Float, temperature comp. regulated; 2=boost 3=battery testro
Enumeration
.1.3.6.1.4.1.12148.9.2.2
battery
OBJECT IDENTIFIER
.1.3.6.1.4.1.12148.9.3
batteryNameA descriptive name of the battery installed in the system.ro
DisplayString
.1.3.6.1.4.1.12148.9.3.1
batteryVoltageThe measured battery voltage.ro
Integer32
.1.3.6.1.4.1.12148.9.3.2
batteryCurrentThe measured total battery current. This is the sum of all the enabled shunt measurements in the system. Negative battery current indicates discharging of the batteries. Positive battery current indicates charging of the batteries. Note that the units measured may be i Amperes or in Deciamperes depending on global system settingsro
Integer32 UNITS "Amperes or DeciAmperes"
.1.3.6.1.4.1.12148.9.3.3
batteryTempThe highest value of the enabled battery temperature measurements. Depending on the global setting in the Control unit, this value will be presented in Celsius or Fahrenheit.ro
Integer32
.1.3.6.1.4.1.12148.9.3.4
batteryBreakerStatusThe state of the battery fuses/breakers can be either normal(0) or alarm(1).ro
Enumeration
.1.3.6.1.4.1.12148.9.3.5
batteryChargeCurrentLimitCtrlEnable/disable of the battery charge current limitation feature; 0=disable, 1=enable.rw
Enumeration
.1.3.6.1.4.1.12148.9.3.6
batteryChargeCurrentLimitValueBattery charging current limit value. Used only when AC source is mains feed. Note that the units measured may be i Amperes or in Deciamperes depending on global system settingsrw
Integer32
.1.3.6.1.4.1.12148.9.3.7
batteryTempCompEnableEnable (0) or Disable (1) of Battery Temperature Compensated output regulation moderw
Enumeration
.1.3.6.1.4.1.12148.9.3.8
batteryFloatVoltConfigThe Voltage at which the DC System float charges. Acts as reference voltage when running temperature compensated charging.rw
Integer32
.1.3.6.1.4.1.12148.9.3.9
batteryBoostVoltConfigThe Voltage at which the DC System boost charges the batteries.rw
Integer32
.1.3.6.1.4.1.12148.9.3.10
batteryHighMajorAlarmVoltageConfigThe Major High Battery Voltage alarm limit set voltagerw
Integer32 UNITS "1/100 Volt; i.e. 5400 = 54.00V"
.1.3.6.1.4.1.12148.9.3.11
batteryHighMinorAlarmVoltageConfigThe Minor High Battery Voltage alarm limit set voltagerw
Integer32 UNITS "1/100 Volt; i.e. 5400 = 54.00V"
.1.3.6.1.4.1.12148.9.3.12
batteryLowMajorAlarmVoltageConfigThe Major Low Battery Voltage Alarm limit set voltagerw
Integer32 UNITS "1/100 Volt; i.e. 5400 = 54.00V"
.1.3.6.1.4.1.12148.9.3.13
batteryLowMinorAlarmVoltageConfigThe Minor Low Battery Voltage Alarm limit set voltagerw
Integer32 UNITS "1/100 Volt; i.e. 5400 = 54.00V"
.1.3.6.1.4.1.12148.9.3.14
batteryStartManualTestThis pushbutton will start or stop a manual battery test if the system allows it.rw
Enumeration
.1.3.6.1.4.1.12148.9.3.15
batteryStartManualBoostThis pushbutton will start or stop a manual battery boost if the system allows it.rw
Enumeration
.1.3.6.1.4.1.12148.9.3.16
batteryLVD
OBJECT IDENTIFIER
.1.3.6.1.4.1.12148.9.3.17
batteryLVDStatusThe Battery Contactor is connected(0), disconnected(1) or disabled(2)ro
Enumeration
.1.3.6.1.4.1.12148.9.3.17.1
batteryLVDDisconnectVoltageThe Battery Contactors Disconnect Voltagerw
Integer32
.1.3.6.1.4.1.12148.9.3.17.2
batteryLVDConnectVoltageThe Battery Contactors Reconnect Voltagerw
Integer32
.1.3.6.1.4.1.12148.9.3.17.3
batteryBanksNumofBanksThe number of Control units that is used to measure battery parameters.ro
Integer32
.1.3.6.1.4.1.12148.9.3.18
batteryBanks
OBJECT IDENTIFIER
.1.3.6.1.4.1.12148.9.3.19
batterySymmetryDeltaLimitVoltageThe allowable deviation of the symmetry voltage from the theoretical. Exceeding this value in either direction (+/-) causes an alarm state.rw
Integer32 UNITS "1/100 Volt; i.e. 150 = 1.50V"
.1.3.6.1.4.1.12148.9.3.19.1
batteryBanksIndexIndex used for navigating the rows 1..8 of batteryBanksTablero
Integer32
.1.3.6.1.4.1.12148.9.3.19.2
batteryBanksTableA table of up to 8 battery banks. Each banks may have up to 8 symmetry measuments.
SEQUENCE OF BatteryBanksEntry
.1.3.6.1.4.1.12148.9.3.19.3
batteryBanksEntry
BatteryBanksEntry
.1.3.6.1.4.1.12148.9.3.19.3.1
batteryBankIDThe ID of the selected row in the table. i.e. the battery bank.ro
Integer32
.1.3.6.1.4.1.12148.9.3.19.3.1.1
batteryBanksSymmetry1enableEnable/Disable the individual symmetry input. If disabled this will read 0 volts and the alarm flag will be turned off.rw
Enumeration
.1.3.6.1.4.1.12148.9.3.19.3.1.2
batteryBanksSymmetry1statusContains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Errorro
Enumeration
.1.3.6.1.4.1.12148.9.3.19.3.1.3
batteryBanksSymmetry1deltaVoltageThe difference between the measured value and the expected value. The expected value is calculated by taking the measured total batteryvoltage and divide it with the number of battery blocks. You'll then have the theoretical correct value for each battery block.ro
Integer32 UNITS "1/100 Volt; i.e. 100 = 1.00V"
.1.3.6.1.4.1.12148.9.3.19.3.1.4
batteryBanksSymmetry2enableEnable/Disable the individual symmetry input. If disabled this will read 0 volts and the alarm flag will be turned off.rw
Enumeration
.1.3.6.1.4.1.12148.9.3.19.3.1.5
batteryBanksSymmetry2statusContains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Errorro
Enumeration
.1.3.6.1.4.1.12148.9.3.19.3.1.6
batteryBanksSymmetry2deltaVoltageThe difference between the measured value and the expected value. The expected value is calculated by taking the measured total batteryvoltage and divide it with the number of battery blocks. You'll then have the theoretical correct value for each battery block.ro
Integer32 UNITS "1/100 Volt; i.e. 100 = 1.00V"
.1.3.6.1.4.1.12148.9.3.19.3.1.7
batteryBanksSymmetry3enableEnable/Disable the individual symmetry input. If disabled this will read 0 volts and the alarm flag will be turned off.rw
Enumeration
.1.3.6.1.4.1.12148.9.3.19.3.1.8
batteryBanksSymmetry3statusContains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Errorro
Enumeration
.1.3.6.1.4.1.12148.9.3.19.3.1.9
batteryBanksSymmetry3deltaVoltageThe difference between the measured value and the expected value. The expected value is calculated by taking the measured total batteryvoltage and divide it with the number of battery blocks. You'll then have the theoretical correct value for each battery block.ro
Integer32 UNITS "1/100 Volt; i.e. 100 = 1.00V"
.1.3.6.1.4.1.12148.9.3.19.3.1.10
batteryBanksSymmetry4enableEnable/Disable the individual symmetry input. If disabled this will read 0 volts and the alarm flag will be turned off.rw
Enumeration
.1.3.6.1.4.1.12148.9.3.19.3.1.11
batteryBanksSymmetry4statusContains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Errorro
Enumeration
.1.3.6.1.4.1.12148.9.3.19.3.1.12
batteryBanksSymmetry4deltaVoltageThe difference between the measured value and the expected value. The expected value is calculated by taking the measured total batteryvoltage and divide it with the number of battery blocks. You'll then have the theoretical correct value for each battery block.ro
Integer32 UNITS "1/100 Volt; i.e. 100 = 1.00V"
.1.3.6.1.4.1.12148.9.3.19.3.1.13
batteryBanksSymmetry5enableEnable/Disable the individual symmetry input. If disabled this will read 0 volts and the alarm flag will be turned off.rw
Enumeration
.1.3.6.1.4.1.12148.9.3.19.3.1.14
batteryBanksSymmetry5statusContains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Errorro
Enumeration
.1.3.6.1.4.1.12148.9.3.19.3.1.15
batteryBanksSymmetry5deltaVoltageThe difference between the measured value and the expected value. The expected value is calculated by taking the measured total batteryvoltage and divide it with the number of battery blocks. You'll then have the theoretical correct value for each battery block.ro
Integer32 UNITS "1/100 Volt; i.e. 100 = 1.00V"
.1.3.6.1.4.1.12148.9.3.19.3.1.16
batteryBanksSymmetry6enableEnable/Disable the individual symmetry input. If disabled this will read 0 volts and the alarm flag will be turned off.rw
Enumeration
.1.3.6.1.4.1.12148.9.3.19.3.1.17
batteryBanksSymmetry6statusContains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Errorro
Enumeration
.1.3.6.1.4.1.12148.9.3.19.3.1.18
batteryBanksSymmetry6deltaVoltageThe difference between the measured value and the expected value. The expected value is calculated by taking the measured total batteryvoltage and divide it with the number of battery blocks. You'll then have the theoretical correct value for each battery block.ro
Integer32 UNITS "1/100 Volt; i.e. 100 = 1.00V"
.1.3.6.1.4.1.12148.9.3.19.3.1.19
batteryBanksSymmetry7enableEnable/Disable the individual symmetry input. If disabled this will read 0 volts and the alarm flag will be turned off.rw
Enumeration
.1.3.6.1.4.1.12148.9.3.19.3.1.20
batteryBanksSymmetry7statusContains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Errorro
Enumeration
.1.3.6.1.4.1.12148.9.3.19.3.1.21
batteryBanksSymmetry7deltaVoltageThe difference between the measured value and the expected value. The expected value is calculated by taking the measured total batteryvoltage and divide it with the number of battery blocks. You'll then have the theoretical correct value for each battery block.ro
Integer32 UNITS "1/100 Volt; i.e. 100 = 1.00V"
.1.3.6.1.4.1.12148.9.3.19.3.1.22
batteryBanksSymmetry8enableEnable/Disable the individual symmetry input. If disabled this will read 0 volts and the alarm flag will be turned off.rw
Enumeration
.1.3.6.1.4.1.12148.9.3.19.3.1.23
batteryBanksSymmetry8statusContains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Errorro
Enumeration
.1.3.6.1.4.1.12148.9.3.19.3.1.24
batteryBanksSymmetry8deltaVoltageThe difference between the measured value and the expected value. The expected value is calculated by taking the measured total batteryvoltage and divide it with the number of battery blocks. You'll then have the theoretical correct value for each battery block.ro
Integer32 UNITS "1/100 Volt; i.e. 100 = 1.00V"
.1.3.6.1.4.1.12148.9.3.19.3.1.25
batteryBanksNumberOfStringsNumber of strings in the power system.ro
Integer32
.1.3.6.1.4.1.12148.9.3.19.4
batteryBanksExtensionIndexIndex used for navigating the rows 1..14 of batteryBanksExtensionTablero
Integer32
.1.3.6.1.4.1.12148.9.3.19.5
batteryBanksExtensionTableThis table shows the measured value on the symmetry inputs.
SEQUENCE OF BatteryBanksExtensionEntry
.1.3.6.1.4.1.12148.9.3.19.6
batteryBanksExtensionEntry
BatteryBanksExtensionEntry
.1.3.6.1.4.1.12148.9.3.19.6.1
batteryBanksExtensionIDThe ID of the selected row in the table. i.e. the battery bank.ro
Integer32
.1.3.6.1.4.1.12148.9.3.19.6.1.1
batteryBanksExtensionSymmetryInputValue1The measured voltage on the symmetry input.ro
Integer32 UNITS "1/100 Volt; i.e. 1200 = 12.00V"
.1.3.6.1.4.1.12148.9.3.19.6.1.2
batteryBanksExtensionSymmetryInputValue2The measured voltage on the symmetry input.ro
Integer32 UNITS "1/100 Volt; i.e. 1200 = 12.00V"
.1.3.6.1.4.1.12148.9.3.19.6.1.3
batteryBanksExtensionSymmetryInputValue3The measured voltage on the symmetry input.ro
Integer32 UNITS "1/100 Volt; i.e. 1200 = 12.00V"
.1.3.6.1.4.1.12148.9.3.19.6.1.4
batteryBanksExtensionSymmetryInputValue4The measured voltage on the symmetry input.ro
Integer32 UNITS "1/100 Volt; i.e. 1200 = 12.00V"
.1.3.6.1.4.1.12148.9.3.19.6.1.5
batteryBanksExtensionSymmetryInputValue5The measured voltage on the symmetry input.ro
Integer32 UNITS "1/100 Volt; i.e. 1200 = 12.00V"
.1.3.6.1.4.1.12148.9.3.19.6.1.6
batteryBanksExtensionSymmetryInputValue6The measured voltage on the symmetry input.ro
Integer32 UNITS "1/100 Volt; i.e. 1200 = 12.00V"
.1.3.6.1.4.1.12148.9.3.19.6.1.7
batteryBanksExtensionSymmetryInputValue7The measured voltage on the symmetry input.ro
Integer32 UNITS "1/100 Volt; i.e. 1200 = 12.00V"
.1.3.6.1.4.1.12148.9.3.19.6.1.8
batteryBanksExtensionSymmetryInputValue8The measured voltage on the symmetry input.ro
Integer32 UNITS "1/100 Volt; i.e. 1200 = 12.00V"
.1.3.6.1.4.1.12148.9.3.19.6.1.9
batteryCapacityData
OBJECT IDENTIFIER
.1.3.6.1.4.1.12148.9.3.20
batteryTimeToDisconnectRemaining time to low voltage battery disconnect.ro
Integer32 UNITS "Minutes; 40 = 40 minutes"
.1.3.6.1.4.1.12148.9.3.20.1
batteryCapacityLeftCapacity left in the battery.ro
Integer32 UNITS "Ah/%; 23 = 23 Ah or in %"
.1.3.6.1.4.1.12148.9.3.20.2
batteryCapacityUsedCapacity consumed.ro
Integer32 UNITS "Ah/%; 23 = 23 Ah or in %"
.1.3.6.1.4.1.12148.9.3.20.3
batteryCapacityTotalThis is the total Capacity of the battery. This value is the installed capacity compensated with the last battery tests quality levelro
Integer32 UNITS "Ah/%; 23 = 23 Ah or in %"
.1.3.6.1.4.1.12148.9.3.20.4
batteryQualityThis is the battery quality (%) of the latest battery test.ro
Integer32 UNITS "%"
.1.3.6.1.4.1.12148.9.3.20.5
batteryMonitorUnits
OBJECT IDENTIFIER
.1.3.6.1.4.1.12148.9.3.21
battmonNumberOfUnitsNumber of battery monitor units in the power system.ro
Integer32
.1.3.6.1.4.1.12148.9.3.21.1
battmonUnitsIndexIndex used for navigating the rows 1..14 of battmonUnitsTablero
Integer32
.1.3.6.1.4.1.12148.9.3.21.2
battmonUnitsTableA table of up to 14 battery monitor control units.
SEQUENCE OF BattmonUnitsEntry
.1.3.6.1.4.1.12148.9.3.21.3
battmonUnitsEntry
BattmonUnitsEntry
.1.3.6.1.4.1.12148.9.3.21.3.1
batteryMonitorIDThe ID of the selected rowro
Integer32
.1.3.6.1.4.1.12148.9.3.21.3.1.1
batteryMonitorSymmetry1statusContains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Errorro
Enumeration
.1.3.6.1.4.1.12148.9.3.21.3.1.2
batteryMonitorSymmetry1InputValueThe measured voltage on the symmetry input.ro
Integer32 UNITS "1/100 Volt; i.e. 1200 = 12.00V"
.1.3.6.1.4.1.12148.9.3.21.3.1.3
batteryMonitorSymmetry2statusContains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Errorro
Enumeration
.1.3.6.1.4.1.12148.9.3.21.3.1.4
batteryMonitorSymmetry2InputValueThe measured voltage on the symmetry input.ro
Integer32 UNITS "1/100 Volt; i.e. 1200 = 12.00V"
.1.3.6.1.4.1.12148.9.3.21.3.1.5
batteryMonitorSymmetry3statusContains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Errorro
Enumeration
.1.3.6.1.4.1.12148.9.3.21.3.1.6
batteryMonitorSymmetry3InputValueThe measured voltage on the symmetry input.ro
Integer32 UNITS "1/100 Volt; i.e. 1200 = 12.00V"
.1.3.6.1.4.1.12148.9.3.21.3.1.7
batteryMonitorSymmetry4statusContains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Errorro
Enumeration
.1.3.6.1.4.1.12148.9.3.21.3.1.8
batteryMonitorSymmetry4InputValueThe measured voltage on the symmetry input.ro
Integer32 UNITS "1/100 Volt; i.e. 1200 = 12.00V"
.1.3.6.1.4.1.12148.9.3.21.3.1.9
batteryMonitorCurrentValueThe measured current to/from the battery. Note that the units measured may be i Amperes or in Deciamperes depending on global system settingsro
Integer32 UNITS "Amperes or DeciAmperes"
.1.3.6.1.4.1.12148.9.3.21.3.1.10
batteryMonitorFuseStatusThe state of the battery fuse/breaker can be either normal(0) or alarm(1).ro
Enumeration
.1.3.6.1.4.1.12148.9.3.21.3.1.11
batteryMonitorTemperatureThe battery temperature.ro
Integer32 UNITS "Deg. C/F; i.e. 25 = 25 Deg."
.1.3.6.1.4.1.12148.9.3.21.3.1.12
batteryHighMajorTempAlarmLevelThis is the Major High Temperature Alarm level.rw
Integer32 UNITS "Deg. C/F; i.e. 25 = 25 Deg."
.1.3.6.1.4.1.12148.9.3.22
batteryHighMinorTempAlarmLevelThis is the Minor High Temperature Alarm level.rw
Integer32 UNITS "Deg. C/F; i.e. 25 = 25 Deg."
.1.3.6.1.4.1.12148.9.3.23
loadDistribution
OBJECT IDENTIFIER
.1.3.6.1.4.1.12148.9.4
loadDistributionCurrentThe total load current Note that the units measured may be i Amperes or in Deciamperes depending on global system settingsro
Integer32 UNITS "Amperes or DeciAmperes"
.1.3.6.1.4.1.12148.9.4.1
loadDistributionBreakerStatusThe state of the load fuses/breakers can be either normal(0) or alarm(1)ro
Enumeration
.1.3.6.1.4.1.12148.9.4.2
loadDistributionLVDStatus
OBJECT IDENTIFIER
.1.3.6.1.4.1.12148.9.4.3
loadLVD1EnableThe status of contactors configuration. 'enabled' means that the contactor is in use. 'disabled' means that the contactor is disconfigured and not in use.ro
Enumeration
.1.3.6.1.4.1.12148.9.4.3.1
loadLVD1StatusThe load Contactor 1 is connected(0), disconnected(1) or disabled(2)ro
Enumeration
.1.3.6.1.4.1.12148.9.4.3.2
loadLVD1ConnectVoltageLVLD1 Connect Voltagerw
Integer32
.1.3.6.1.4.1.12148.9.4.3.3
loadLVD1DisconnectVoltageLVLD1 Disconnect Voltagerw
Integer32
.1.3.6.1.4.1.12148.9.4.3.4
loadLVD2EnableThe status of contactors configuration. 'enabled' means that the contactor is in use. 'disabled' means that the contactor is disconfigured and not in use.ro
Enumeration
.1.3.6.1.4.1.12148.9.4.3.5
loadLVD2StatusThe load Contactor 2 is connected(0), disconnected(1) or disabled(2)ro
Enumeration
.1.3.6.1.4.1.12148.9.4.3.6
loadLVD2ConnectVoltageLVLD2 Connect Voltagerw
Integer32
.1.3.6.1.4.1.12148.9.4.3.7
loadLVD2DisconnectVoltageLVLD2 Disconnect Voltagerw
Integer32
.1.3.6.1.4.1.12148.9.4.3.8
loadLVD3EnableThe status of contactors configuration. 'enabled' means that the contactor is in use. 'disabled' means that the contactor is disconfigured and not in use.ro
Enumeration
.1.3.6.1.4.1.12148.9.4.3.9
loadLVD3StatusThe load Contactor 3 is connected(0), disconnected(1) or disabled(2)ro
Enumeration
.1.3.6.1.4.1.12148.9.4.3.10
loadLVD3ConnectVoltageLVLD3 Connect Voltagerw
Integer32
.1.3.6.1.4.1.12148.9.4.3.11
loadLVD3DisconnectVoltageLVLD3 Disconnect Voltagerw
Integer32
.1.3.6.1.4.1.12148.9.4.3.12
loadMonitorUnits
OBJECT IDENTIFIER
.1.3.6.1.4.1.12148.9.4.4
loadmonitorNumberOfUnitsro
Integer32
.1.3.6.1.4.1.12148.9.4.4.1
loadMonitorUnitsIndexro
Integer32
.1.3.6.1.4.1.12148.9.4.4.2
loadMonitorUnitsTable
SEQUENCE OF LoadMonitorUnitsEntry
.1.3.6.1.4.1.12148.9.4.4.3
loadMonitorUnitsEntry
LoadMonitorUnitsEntry
.1.3.6.1.4.1.12148.9.4.4.3.1
loadMonitorIDro
Integer32
.1.3.6.1.4.1.12148.9.4.4.3.1.1
loadMonitorFuseStatus1The state of the load fuses/breakers can be either normal(0) or alarm(1)ro
Enumeration
.1.3.6.1.4.1.12148.9.4.4.3.1.2
loadMonitorCurrent1The current consumed by this load branch. Note that the units measured may be i Amperes or in Deciamperes depending on global system settingsro
Integer32 UNITS "Amperes or DeciAmperes"
.1.3.6.1.4.1.12148.9.4.4.3.1.3
loadMonitorFuseStatus2The state of the load fuses/breakers can be either normal(0) or alarm(1)ro
Enumeration
.1.3.6.1.4.1.12148.9.4.4.3.1.4
loadMonitorCurrent2The current consumed by this load branch. Note that the units measured may be i Amperes or in Deciamperes depending on global system settingsro
Integer32 UNITS "Amperes or DeciAmperes"
.1.3.6.1.4.1.12148.9.4.4.3.1.5
loadMonitorFuseStatus3The state of the load fuses/breakers can be either normal(0) or alarm(1)ro
Enumeration
.1.3.6.1.4.1.12148.9.4.4.3.1.6
loadMonitorCurrent3The current consumed by this load branch. Note that the units measured may be i Amperes or in Deciamperes depending on global system settingsro
Integer32 UNITS "Amperes or DeciAmperes"
.1.3.6.1.4.1.12148.9.4.4.3.1.7
loadMonitorFuseStatus4The state of the load fuses/breakers can be either normal(0) or alarm(1)ro
Enumeration
.1.3.6.1.4.1.12148.9.4.4.3.1.8
loadMonitorCurrent4The current consumed by this load branch. Note that the units measured may be i Amperes or in Deciamperes depending on global system settingsro
Integer32 UNITS "Amperes or DeciAmperes"
.1.3.6.1.4.1.12148.9.4.4.3.1.9
loadMonitorFuseStatus5The state of the load fuses/breakers can be either normal(0) or alarm(1)ro
Enumeration
.1.3.6.1.4.1.12148.9.4.4.3.1.10
loadMonitorCurrent5The current consumed by this load branch. Note that the units measured may be i Amperes or in Deciamperes depending on global system settingsro
Integer32 UNITS "Amperes or DeciAmperes"
.1.3.6.1.4.1.12148.9.4.4.3.1.11
loadMonitorFuseStatus6The state of the load fuses/breakers can be either normal(0) or alarm(1)ro
Enumeration
.1.3.6.1.4.1.12148.9.4.4.3.1.12
loadMonitorCurrent6The current consumed by this load branch. Note that the units measured may be i Amperes or in Deciamperes depending on global system settingsro
Integer32 UNITS "Amperes or DeciAmperes"
.1.3.6.1.4.1.12148.9.4.4.3.1.13
loadMonitorFuseStatus7The state of the load fuses/breakers can be either normal(0) or alarm(1)ro
Enumeration
.1.3.6.1.4.1.12148.9.4.4.3.1.14
loadMonitorCurrent7The current consumed by this load branch. Note that the units measured may be i Amperes or in Deciamperes depending on global system settingsro
Integer32 UNITS "Amperes or DeciAmperes"
.1.3.6.1.4.1.12148.9.4.4.3.1.15
loadMonitorFuseStatus8The state of the load fuses/breakers can be either normal(0) or alarm(1)ro
Enumeration
.1.3.6.1.4.1.12148.9.4.4.3.1.16
loadMonitorCurrent8The current consumed by this load branch. Note that the units measured may be i Amperes or in Deciamperes depending on global system settingsro
Integer32 UNITS "Amperes or DeciAmperes"
.1.3.6.1.4.1.12148.9.4.4.3.1.17
rectifier
OBJECT IDENTIFIER
.1.3.6.1.4.1.12148.9.5
rectifierInstalledRectifiersThe number of installed rectifiers for this DC Power System.ro
Integer32
.1.3.6.1.4.1.12148.9.5.1
rectifierRectifiersActiveNot Used!ro
Integer32
.1.3.6.1.4.1.12148.9.5.2
rectifierTotalCurrentThe DC system's total delivered rectifier currentro
Integer32 UNITS "DeciAmperes; i.e. 20 = 2,0 Amperes"
.1.3.6.1.4.1.12148.9.5.3
rectifierUtilizationUtilization in % of available rectifier capacityro
Integer32
.1.3.6.1.4.1.12148.9.5.4
rectifierStatus
OBJECT IDENTIFIER
.1.3.6.1.4.1.12148.9.5.5
rectifierStatusNoIndexAn offset for the rectifierStatusTable array. The rectifier status table has a fixed number of 20 rows. This OID sets the offset for the rectifier in the first row i.e. setting the index to 11 will give a range from rectifier ID12 to ID31. Setting the index to 0 will give a range from rectifier ID1 to ID20.rw
Integer32
.1.3.6.1.4.1.12148.9.5.5.1
rectifierStatusTableA table listing up to 20 recifiers, starting from the rectifier number specified by rectifierStatusNoIndex
SEQUENCE OF RectifierStatusEntry
.1.3.6.1.4.1.12148.9.5.5.2
rectifierStatusEntryA row of rectifier status data corresponding to the rectifierStatusNoIndex value
RectifierStatusEntry
.1.3.6.1.4.1.12148.9.5.5.2.1
rectifierStatusIDThe rectifier ID number of the rectifier.ro
Integer32
.1.3.6.1.4.1.12148.9.5.5.2.1.1
rectifierStatusStatusThe operational status of the rectifier record. Not Present (0), normal (1), alarm (2), notUsed (3), disabled (4)ro
Enumeration
.1.3.6.1.4.1.12148.9.5.5.2.1.2
rectifierStatusOutputCurrentThe output current of the rectifier.ro
Integer32
.1.3.6.1.4.1.12148.9.5.5.2.1.3
rectifierStatusOutputVoltageThe rectifier voltage of the rectifier record.ro
Integer32
.1.3.6.1.4.1.12148.9.5.5.2.1.4
rectifierStatusTempThe input air temperature of the rectifier.ro
Integer32
.1.3.6.1.4.1.12148.9.5.5.2.1.5
rectifierStatusTypeThe rectifier article number string of the rectifier record.ro
DisplayString
.1.3.6.1.4.1.12148.9.5.5.2.1.6
rectifierStatusSKUThe rectifier part number.ro
DisplayString
.1.3.6.1.4.1.12148.9.5.5.2.1.7
rectifierStatusSerialNoThe rectifier serial number string of the rectifier record.ro
DisplayString
.1.3.6.1.4.1.12148.9.5.5.2.1.8
rectifierStatusRevisionLevelThe rectifier HW revision number string of the rectifier record.ro
DisplayString
.1.3.6.1.4.1.12148.9.5.5.2.1.9
acDistribution
OBJECT IDENTIFIER
.1.3.6.1.4.1.12148.9.6
acVoltage1The AC Voltage of phase 1ro
Integer32 UNITS "Volts AC"
.1.3.6.1.4.1.12148.9.6.1
acVoltage2The AC Voltage of phase 2ro
Integer32 UNITS "Volts AC"
.1.3.6.1.4.1.12148.9.6.2
acVoltage3The AC Voltage of phase 3ro
Integer32 UNITS "Volts AC"
.1.3.6.1.4.1.12148.9.6.3
alarmGroup
OBJECT IDENTIFIER
.1.3.6.1.4.1.12148.9.7
alarmWellknownAlarms
OBJECT IDENTIFIER
.1.3.6.1.4.1.12148.9.7.1
alarmMajorHighBattVoltThe Major High Battery Voltage Alarmro
Enumeration
.1.3.6.1.4.1.12148.9.7.1.1
alarmMinorHighBattVoltThe Minor High Battery Voltage alarmro
Enumeration
.1.3.6.1.4.1.12148.9.7.1.2
alarmMajorLowBattVoltThe Major Low Battery Voltage Alarmro
Enumeration
.1.3.6.1.4.1.12148.9.7.1.3
alarmMinorLowBattVoltThe Minor Low Battery Voltage Alarmro
Enumeration
.1.3.6.1.4.1.12148.9.7.1.4
alarmMajorBatteryHighTempThe Major High Battery Temperature alarm.ro
Enumeration
.1.3.6.1.4.1.12148.9.7.1.5
alarmMinorBatteryHighTempThe Minor High Battery Temperature alarm.ro
Enumeration
.1.3.6.1.4.1.12148.9.7.1.6
alarmBatteryDisconnectOpenThe Battery Disconnect Contactor alarmro
Enumeration
.1.3.6.1.4.1.12148.9.7.1.7
alarmLVD1openThe load Contactor 1 alarm. The contactor disconnect voltage has been reached and the contactor has disconnected.ro
Enumeration
.1.3.6.1.4.1.12148.9.7.1.8
alarmLVD2openThe load Contactor 2 alarm. The contactor disconnect voltage has been reached and the contactor has disconnected.ro
Enumeration
.1.3.6.1.4.1.12148.9.7.1.9
alarmLVD3openThe load Contactor 3 alarm. The contactor disconnect voltage has been reached and the contactor has disconnected.ro
Enumeration
.1.3.6.1.4.1.12148.9.7.1.10
alarmACmainsThe AC voltage has dropped below critical level, or one or more AC input phases was lost.ro
Enumeration
.1.3.6.1.4.1.12148.9.7.1.11
alarmBatteryBreakerOpenA battery breaker/fuse alarm.ro
Enumeration
.1.3.6.1.4.1.12148.9.7.1.12
alarmDistributionBreakerOpenA Load Distribution breaker/fuse alarm.ro
Enumeration
.1.3.6.1.4.1.12148.9.7.1.13
alarmMajorRectifierThis is a Major Rectifier alarm.ro
Enumeration
.1.3.6.1.4.1.12148.9.7.1.14
alarmMinorRectifierThis is a Minor Rectifier alarm.ro
Enumeration
.1.3.6.1.4.1.12148.9.7.1.15
alarmMajorBatterySymmetryBattery Symmetry Delta Voltage Major alarm.ro
Enumeration
.1.3.6.1.4.1.12148.9.7.1.16
alarmMinorBatterySymmetryBattery Symmetry Delta Voltage Minor alarmro
Enumeration
.1.3.6.1.4.1.12148.9.7.1.17
alarmBatteryLifeEndedThe battery quality has dropped below critical level. A battery test has measured the fully charged capacity to be too low, and thus probably the battery lifecycle to be near expired.ro
Enumeration
.1.3.6.1.4.1.12148.9.7.1.18
alarmBatteryTestmodeEnteredThe system has lowered the battery charge voltage in order to discharge the batteries to a predefined level. When the criteria for stopping the battery testing is reached, the charge voltage is increased to commence normal charging.ro
Enumeration
.1.3.6.1.4.1.12148.9.7.1.19
alarmBatteryBoostmodeEnteredThe system has increased the battery charge voltage in order to boost the battery. When the criteria for stopping the battery boost is reached, the charge voltage is lowered to commence normal charging.ro
Enumeration
.1.3.6.1.4.1.12148.9.7.1.20
alarmIoUnitTemp1High or low temperature alarm 1 from any of the IO units.ro
Enumeration
.1.3.6.1.4.1.12148.9.7.1.21
alarmIoUnitTemp2High or low temperature alarm 2 from any of the IO units.ro
Enumeration
.1.3.6.1.4.1.12148.9.7.1.22
alarmIoUnitDeltaFanSpeed1Delta fan speed 1 from any of the IO units.ro
Enumeration
.1.3.6.1.4.1.12148.9.7.1.23
alarmIoUnitDeltaFanSpeed2Delta fan speed 2 from any of the IO units.ro
Enumeration
.1.3.6.1.4.1.12148.9.7.1.24
alarmMajorSolarThis is a Major Solar alarm.ro
Enumeration
.1.3.6.1.4.1.12148.9.7.1.25
alarmMinorSolarThis is a Major Solar alarm.ro
Enumeration
.1.3.6.1.4.1.12148.9.7.1.26
alarmMajorRectifierCapacityThis is a Major Rectifier Capacity alarm.ro
Enumeration
.1.3.6.1.4.1.12148.9.7.1.27
alarmMinorRectifierCapacityThis is a Minor Rectifier Capacity alarm.ro
Enumeration
.1.3.6.1.4.1.12148.9.7.1.28
dcSystemTrapsThis branch contains the Alarm Notification Traps, which duplicate the alarmGroup OIDs. Each alarm condition is represented by a Alarm Condition Trap and an associated OFF Trap, which is optionally transmitted according to the state of OID systemSendOffTrap
Unknown
.1.3.6.1.4.1.12148.9.8
alarmMajorHighBattVoltTrapThe Major High Battery Voltage alarm
NOTIFICATION-TYPE
.1.3.6.1.4.1.12148.9.8.1
alarmMinorHighBattVoltTrapThe Minor High Battery Voltage alarm
NOTIFICATION-TYPE
.1.3.6.1.4.1.12148.9.8.2
alarmMajorLowBattVoltTrapThe Major Low Battery Voltage Alarm
NOTIFICATION-TYPE
.1.3.6.1.4.1.12148.9.8.3
alarmMinorLowBattVoltTrapThe Minor Low Battery Voltage Alarm
NOTIFICATION-TYPE
.1.3.6.1.4.1.12148.9.8.4
alarmMajorBatteryHighTempTrapThe Major High Battery Temperature alarm.
NOTIFICATION-TYPE
.1.3.6.1.4.1.12148.9.8.5
alarmMinorBatteryHighTempTrapThe Minor High Battery Temperature alarm.
NOTIFICATION-TYPE
.1.3.6.1.4.1.12148.9.8.6
alarmBatteryDisconnectOpenTrapThe Battery Disconnect Contactor alarm
NOTIFICATION-TYPE
.1.3.6.1.4.1.12148.9.8.7
alarmLVD1openTrapThe load Contactor 1 alarm. The contactor disconnect voltage has been reached and the contactor has disconnected.
NOTIFICATION-TYPE
.1.3.6.1.4.1.12148.9.8.8
alarmLVD2openTrapThe load Contactor 2 alarm. The contactor disconnect voltage has been reached and the contactor has disconnected.
NOTIFICATION-TYPE
.1.3.6.1.4.1.12148.9.8.9
alarmLVD3openTrapThe load Contactor 3 alarm. The contactor disconnect voltage has been reached and the contactor has disconnected.
NOTIFICATION-TYPE
.1.3.6.1.4.1.12148.9.8.10
alarmACmainsTrapThe AC voltage has dropped below critical level, or one or more AC input phases was lost.
NOTIFICATION-TYPE
.1.3.6.1.4.1.12148.9.8.11
alarmBatteryBreakerOpenTrapA battery breaker/fuse alarm.
NOTIFICATION-TYPE
.1.3.6.1.4.1.12148.9.8.12
alarmDistributionBreakerOpenTrapA Load Distribution breaker/fuse alarm.
NOTIFICATION-TYPE
.1.3.6.1.4.1.12148.9.8.13
alarmMajorRectifierTrapThis is a Major Rectifier alarm.
NOTIFICATION-TYPE
.1.3.6.1.4.1.12148.9.8.14
alarmMinorRectifierTrapThis is a Minor Rectifier alarm.
NOTIFICATION-TYPE
.1.3.6.1.4.1.12148.9.8.15
alarmMajorBatterySymmetryTrapBattery Symmetry Delta Voltage Major alarm
NOTIFICATION-TYPE
.1.3.6.1.4.1.12148.9.8.16
alarmMinorBatterySymmetryTrapBattery Symmetry Delta Voltage Minor alarm
NOTIFICATION-TYPE
.1.3.6.1.4.1.12148.9.8.17
alarmBatteryLifeEndedTrapThe battery quality has dropped below critical level. A battery test has measured the fully charged capacity to be too low, and thus probably the battery lifecycle to be near expired.
NOTIFICATION-TYPE
.1.3.6.1.4.1.12148.9.8.18
alarmBatteryTestmodeEnteredTrapThe system has lowered the battery charge voltage in order to discharge the batteries to a predefined level. When the criteria for stopping the battery testing is reached, the charge voltage is increased to commence normal charging.
NOTIFICATION-TYPE
.1.3.6.1.4.1.12148.9.8.19
alarmBatteryBoostmodeEnteredTrapThe system has increased the battery charge voltage in order to boost the battery. When the criteria for stopping the battery boost is reached, the charge voltage is lowered to commence normal charging.
NOTIFICATION-TYPE
.1.3.6.1.4.1.12148.9.8.20
alarmController1proginputTrapProgrammable input alarm for Control unit 1. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Control unit ID>.x.
NOTIFICATION-TYPE
.1.3.6.1.4.1.12148.9.8.21
alarmController2proginputTrapProgrammable input alarm for Control unit 2. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Control unit ID>.x.
NOTIFICATION-TYPE
.1.3.6.1.4.1.12148.9.8.22
alarmController3proginputTrapProgrammable input alarm for Control unit 3. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Control unit ID>.x.
NOTIFICATION-TYPE
.1.3.6.1.4.1.12148.9.8.23
alarmController4proginputTrapProgrammable input alarm for Control unit 4. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Control unit ID>.x.
NOTIFICATION-TYPE
.1.3.6.1.4.1.12148.9.8.24
alarmController5proginputTrapProgrammable input alarm for Control unit 5. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Control unit ID>.x.
NOTIFICATION-TYPE
.1.3.6.1.4.1.12148.9.8.25
alarmController6proginputTrapProgrammable input alarm for Control unit 6. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Control unit ID>.x.
NOTIFICATION-TYPE
.1.3.6.1.4.1.12148.9.8.26
alarmController7proginputTrapProgrammable input alarm for Control unit 7. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Control unit ID>.x.
NOTIFICATION-TYPE
.1.3.6.1.4.1.12148.9.8.27
alarmController8proginputTrapProgrammable input alarm for Control unit 8. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Control unit ID>.x.
NOTIFICATION-TYPE
.1.3.6.1.4.1.12148.9.8.28
infoHeartBeatTrapWhen enabled, this trap will be transmitted at regular inervals. This trap is not intended to be an alarm but more like some information that the system is alive and the link is up.
NOTIFICATION-TYPE
.1.3.6.1.4.1.12148.9.8.29
alarmIoUnitTemp1TrapHigh or low temperature alarm 1 from any of the IO units.
NOTIFICATION-TYPE
.1.3.6.1.4.1.12148.9.8.30
alarmIoUnitTemp2TrapHigh or low temperature alarm 2 from any of the IO units.
NOTIFICATION-TYPE
.1.3.6.1.4.1.12148.9.8.31
alarmIoUnitDeltaFanSpeed1TrapDelta fan speed 1 from any of the IO units. Occurs if the fan speed deviation is above/below the configured level.
NOTIFICATION-TYPE
.1.3.6.1.4.1.12148.9.8.32
alarmIoUnitDeltaFanSpeed2TrapDelta fan speed 2 from any of the IO units. Occurs if the fan speed deviation is above/below the configured level.
NOTIFICATION-TYPE
.1.3.6.1.4.1.12148.9.8.33
alarmIoUnit1proginputTrapProgrammable input alarm for IO Unit 1. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <IO Unit ID>.x.
NOTIFICATION-TYPE
.1.3.6.1.4.1.12148.9.8.34
alarmIoUnit2proginputTrapProgrammable input alarm for IO Unit 2. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <IO Unit ID>.x.
NOTIFICATION-TYPE
.1.3.6.1.4.1.12148.9.8.35
alarmIoUnit3proginputTrapProgrammable input alarm for IO Unit 3. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <IO Unit ID>.x.
NOTIFICATION-TYPE
.1.3.6.1.4.1.12148.9.8.36
alarmIoUnit4proginputTrapProgrammable input alarm for IO Unit 4. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <IO Unit ID>.x.
NOTIFICATION-TYPE
.1.3.6.1.4.1.12148.9.8.37
alarmIoUnit5proginputTrapProgrammable input alarm for IO Unit 5. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <IO Unit ID>.x.
NOTIFICATION-TYPE
.1.3.6.1.4.1.12148.9.8.38
alarmIoUnit6proginputTrapProgrammable input alarm for IO Unit 6. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <IO Unit ID>.x.
NOTIFICATION-TYPE
.1.3.6.1.4.1.12148.9.8.39
alarmIoUnit7proginputTrapProgrammable input alarm for IO Unit 7. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <IO Unit ID>.x.
NOTIFICATION-TYPE
.1.3.6.1.4.1.12148.9.8.40
alarmIoUnit8proginputTrapProgrammable input alarm for IO Unit 8. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <IO Unit ID>.x.
NOTIFICATION-TYPE
.1.3.6.1.4.1.12148.9.8.41
alarmIoUnit9proginputTrapProgrammable input alarm for IO Unit 9. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <IO Unit ID>.x.
NOTIFICATION-TYPE
.1.3.6.1.4.1.12148.9.8.42
alarmIoUnit10proginputTrapProgrammable input alarm for IO Unit 10. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <IO Unit ID>.x.
NOTIFICATION-TYPE
.1.3.6.1.4.1.12148.9.8.43
alarmIoUnit11proginputTrapProgrammable input alarm for IO Unit 11. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <IO Unit ID>.x.
NOTIFICATION-TYPE
.1.3.6.1.4.1.12148.9.8.44
alarmIoUnit12proginputTrapProgrammable input alarm for IO Unit 12. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <IO Unit ID>.x.
NOTIFICATION-TYPE
.1.3.6.1.4.1.12148.9.8.45
alarmIoUnit13proginputTrapProgrammable input alarm for IO Unit 13. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <IO Unit ID>.x.
NOTIFICATION-TYPE
.1.3.6.1.4.1.12148.9.8.46
alarmIoUnit14proginputTrapProgrammable input alarm for IO Unit 14. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <IO Unit ID>.x.
NOTIFICATION-TYPE
.1.3.6.1.4.1.12148.9.8.47
alarmMajorSolarChargerTrapThe Major Solar Charger alarm
NOTIFICATION-TYPE
.1.3.6.1.4.1.12148.9.8.48
alarmMinorSolarChargerTrapThe Minor Solar Charger alarm
NOTIFICATION-TYPE
.1.3.6.1.4.1.12148.9.8.49
alarmMajorRectifierCapacityTrapThe Major Rectifier Capacity alarm
NOTIFICATION-TYPE
.1.3.6.1.4.1.12148.9.8.50
alarmMinorRectifierCapacityTrapThe Minor Rectifier Capacity alarm
NOTIFICATION-TYPE
.1.3.6.1.4.1.12148.9.8.51
solarCharger
OBJECT IDENTIFIER
.1.3.6.1.4.1.12148.9.9
solarChargerInstalledsolarChargersThe number of installed solar chargers for this DC Power System.ro
Integer32
.1.3.6.1.4.1.12148.9.9.1
solarChargersActiveNot Used!ro
Integer32
.1.3.6.1.4.1.12148.9.9.2
solarChargerTotalCurrentThe DC system's total delivered solar currentro
Integer32 UNITS "DeciAmperes; i.e. 20 = 2,0 Amperes"
.1.3.6.1.4.1.12148.9.9.3
solarChargerUtilizationUtilization in % of available solar capacityro
Integer32
.1.3.6.1.4.1.12148.9.9.4
solarChargerStatus
OBJECT IDENTIFIER
.1.3.6.1.4.1.12148.9.9.5
solarChargerStatusNoIndexAn offset for the solarStatusTable array. The solar status table has a fixed number of 20 rows. This OID sets the offset for the solarcharger in the first row i.e. setting the index to 11 will give a range from solarcharger ID12 to ID31. Setting the index to 0 will give a range from solarcharger ID1 to ID20.rw
Integer32
.1.3.6.1.4.1.12148.9.9.5.1
solarChargerStatusTableA table listing up to 20 solarchargers, starting from the solarcharger number specified by solarStatusNoIndex
SEQUENCE OF SolarChargerStatusEntry
.1.3.6.1.4.1.12148.9.9.5.2
solarChargerStatusEntryA row of rectifier status data corresponding to the rectifierStatusNoIndex value
SolarChargerStatusEntry
.1.3.6.1.4.1.12148.9.9.5.2.1
solarChargerStatusIDThe ID number of the solarcharger.ro
Integer32
.1.3.6.1.4.1.12148.9.9.5.2.1.1
solarChargerStatusStatusThe operational status of the solarcharger record. Not Present (0), normal (1), alarm (2), notUsed (3), disabled (4)ro
Enumeration
.1.3.6.1.4.1.12148.9.9.5.2.1.2
solarChargerOutputCurrentThe output current of the solarcharger.ro
Integer32
.1.3.6.1.4.1.12148.9.9.5.2.1.3
solarChargerOutputVoltageThe output voltage of the solarcharger.ro
Integer32
.1.3.6.1.4.1.12148.9.9.5.2.1.4
solarChargerTempThe input air temperature of the solarcharger.ro
Integer32
.1.3.6.1.4.1.12148.9.9.5.2.1.5
solarChargerTypeThe article number string of the solarcharger.ro
DisplayString
.1.3.6.1.4.1.12148.9.9.5.2.1.6
solarChargerSKUThe solarcharger part number.ro
DisplayString
.1.3.6.1.4.1.12148.9.9.5.2.1.7
solarChargerSerialNoThe serial number string of the solarcharger.ro
DisplayString
.1.3.6.1.4.1.12148.9.9.5.2.1.8
solarChargerRevisionLevelThe HW revision number string of the solarcharger.ro
DisplayString
.1.3.6.1.4.1.12148.9.9.5.2.1.9