Home/Catalog/BATTERY-MIB

BATTERY-MIB

AI MIB Summary

The BATTERY-MIB standardizes the monitoring of battery health parameters, including voltage, current, charge capacity, and remaining runtime, for networked devices and their internal components. It enables systems administrators to track critical power supply status and predict battery depletion through standardized SNMP object retrieval.

This MIB module defines a set of objects for monitoring batteries of networked devices and of their components. Copyright (c) 2015 IETF Trust and the persons identified as authors of the code. All rights reserved. Redistribution and use in source and binary forms, with or without modification, is permitted pursuant to, and subject to the license terms contained in, the Simplified BSD License set forth in Section 4.c of the IETF Trust's Legal Provisions Relating to IETF Documents (http://trustee.ietf.org/license-info). This version of this MIB module is part of RFC 7577; see the RFC itself for full legal notices.
Main OID:
batteryMIB.1.3.6.1.2.1.233
47
Objects
Active
Status
5
Dependencies

Imported Objects

Objects

47 total
Object Name
batteryMIB
MODULE-IDENTITY
.1.3.6.1.2.1.233
batteryNotifications
OBJECT IDENTIFIER
.1.3.6.1.2.1.233.0
batteryChargingStateNotification
NOTIFICATION-TYPE
.1.3.6.1.2.1.233.0.1
batteryLowNotification
NOTIFICATION-TYPE
.1.3.6.1.2.1.233.0.2
batteryCriticalNotification
NOTIFICATION-TYPE
.1.3.6.1.2.1.233.0.3
batteryTemperatureNotification
NOTIFICATION-TYPE
.1.3.6.1.2.1.233.0.4
batteryAgingNotification
NOTIFICATION-TYPE
.1.3.6.1.2.1.233.0.5
batteryConnectedNotification
NOTIFICATION-TYPE
.1.3.6.1.2.1.233.0.6
batteryDisconnectedNotification
NOTIFICATION-TYPE
.1.3.6.1.2.1.233.0.7
batteryObjects
OBJECT IDENTIFIER
.1.3.6.1.2.1.233.1
batteryTable
SEQUENCE OF BatteryEntry
.1.3.6.1.2.1.233.1.1
batteryEntry
BatteryEntry
.1.3.6.1.2.1.233.1.1.1
batteryIdentifierro
SnmpAdminString (SNMP-FRAMEWORK-MIB)
.1.3.6.1.2.1.233.1.1.1.1
batteryFirmwareVersionro
SnmpAdminString (SNMP-FRAMEWORK-MIB)
.1.3.6.1.2.1.233.1.1.1.2
batteryTypero
Enumeration
.1.3.6.1.2.1.233.1.1.1.3
batteryTechnologyro
Unsigned32
.1.3.6.1.2.1.233.1.1.1.4
batteryDesignVoltagero
Unsigned32 UNITS "millivolt"
.1.3.6.1.2.1.233.1.1.1.5
batteryNumberOfCellsro
Unsigned32
.1.3.6.1.2.1.233.1.1.1.6
batteryDesignCapacityro
Unsigned32 UNITS "milliampere hours"
.1.3.6.1.2.1.233.1.1.1.7
batteryMaxChargingCurrentro
Unsigned32 UNITS "milliampere"
.1.3.6.1.2.1.233.1.1.1.8
batteryTrickleChargingCurrentro
Unsigned32 UNITS "milliampere"
.1.3.6.1.2.1.233.1.1.1.9
batteryActualCapacityro
Unsigned32 UNITS "milliampere hours"
.1.3.6.1.2.1.233.1.1.1.10
batteryChargingCycleCountro
Unsigned32
.1.3.6.1.2.1.233.1.1.1.11
batteryLastChargingCycleTimero
DateAndTime (SNMPv2-TC)
.1.3.6.1.2.1.233.1.1.1.12
batteryChargingOperStatero
Enumeration
.1.3.6.1.2.1.233.1.1.1.13
batteryChargingAdminStaterw
Enumeration
.1.3.6.1.2.1.233.1.1.1.14
batteryActualChargero
Unsigned32 UNITS "milliampere hours"
.1.3.6.1.2.1.233.1.1.1.15
batteryActualVoltagero
Unsigned32 UNITS "millivolt"
.1.3.6.1.2.1.233.1.1.1.16
batteryActualCurrentro
Integer32 UNITS "milliampere"
.1.3.6.1.2.1.233.1.1.1.17
batteryTemperaturero
Integer32 UNITS "deci-degrees Celsius"
.1.3.6.1.2.1.233.1.1.1.18
batteryAlarmLowChargerw
Unsigned32 UNITS "milliampere hours"
.1.3.6.1.2.1.233.1.1.1.19
batteryAlarmLowVoltagerw
Unsigned32 UNITS "millivolt"
.1.3.6.1.2.1.233.1.1.1.20
batteryAlarmLowCapacityrw
Unsigned32 UNITS "milliampere hours"
.1.3.6.1.2.1.233.1.1.1.21
batteryAlarmHighCycleCountrw
Unsigned32
.1.3.6.1.2.1.233.1.1.1.22
batteryAlarmHighTemperaturerw
Integer32 UNITS "deci-degrees Celsius"
.1.3.6.1.2.1.233.1.1.1.23
batteryAlarmLowTemperaturerw
Integer32 UNITS "deci-degrees Celsius"
.1.3.6.1.2.1.233.1.1.1.24
batteryCellIdentifierro
SnmpAdminString (SNMP-FRAMEWORK-MIB)
.1.3.6.1.2.1.233.1.1.1.25
batteryConformance
OBJECT IDENTIFIER
.1.3.6.1.2.1.233.2
batteryCompliances
OBJECT IDENTIFIER
.1.3.6.1.2.1.233.2.1
batteryCompliance
Unknown
.1.3.6.1.2.1.233.2.1.1
batteryGroups
OBJECT IDENTIFIER
.1.3.6.1.2.1.233.2.2
batteryDescriptionGroup
Unknown
.1.3.6.1.2.1.233.2.2.1
batteryStatusGroup
Unknown
.1.3.6.1.2.1.233.2.2.2
batteryAdminGroup
Unknown
.1.3.6.1.2.1.233.2.2.3
batteryAlarmThresholdsGroup
Unknown
.1.3.6.1.2.1.233.2.2.4
batteryNotificationsGroup
Unknown
.1.3.6.1.2.1.233.2.2.5
batteryPerCellNotificationsGroup
Unknown
.1.3.6.1.2.1.233.2.2.6

BATTERY-MIB Technical Reference Overview

The BATTERY-MIB SNMP MIB module published by Default defines 47 managed OID objects, including 32 scalar/column metrics, 1 SNMP tables, and 7 trap/notification events anchored at base OID .1.3.6.1.2.1.233. Key tabular structures include batteryTable. Monitored SNMP traps/notifications include batteryAgingNotification, batteryChargingStateNotification, batteryConnectedNotification, batteryCriticalNotification, batteryDisconnectedNotification, batteryLowNotification.

Key OID Definitions in BATTERY-MIB

batteryMIBMODULE-IDENTITYnot-accessible
.1.3.6.1.2.1.233

This MIB module defines a set of objects for monitoring batteries of networked devices and of their components. Copyright (c) 2015 IETF Trust and the persons identified as authors of the code. All rights reserved. Redistribution and use in source and binary forms, with or without modification, is permitted pursuant to, and subject to the license terms contained in, the Simplified BSD License set forth in Section 4.c of the IETF Trust's Legal Provisions Relating to IETF Documents (http://trustee.ietf.org/license-info). This version of this MIB module is part of RFC 7577; see the RFC itself for full legal notices.

batteryTableSEQUENCEnot-accessible
.1.3.6.1.2.1.233.1.1

This table provides information on batteries. It contains one conceptual row per battery in a managed entity. Batteries are indexed by the entPhysicalIndex of the entPhysicalTable defined in the ENTITY-MIB (RFC 6933). For implementations of the BATTERY-MIB, an implementation of the ENTITY-MIB complying with the entity4CRCompliance MODULE-COMPLIANCE statement of the ENTITY-MIB is required. If batteries are replaced, and the replacing battery uses the same physical connector as the replaced battery, then the replacing battery SHOULD be indexed with the same value of object entPhysicalIndex as the replaced battery.

batteryAgingNotificationNOTIFICATION-TYPEnot-accessible
.1.3.6.1.2.1.233.0.5

This notification can be generated when the actual capacity (batteryActualCapacity) falls below a threshold defined by object batteryAlarmLowCapacity or when the charging cycle count of the battery (batteryChargingCycleCount) exceeds the threshold defined by object batteryAlarmHighCycleCount. If the aging has been detected for a single cell or a set of cells of the battery and not for the entire battery, then object batteryCellIdentifier should be set to a value that identifies the cell or set of cells. Otherwise, the value of object batteryCellIdentifier should be set to the empty string when this notification is generated. This notification should not be sent again for the same battery or cell, respectively, before an indication of a maintenance action has been detected, such as a battery disconnection event or a reinitialization of the battery monitoring system.

batteryChargingStateNotificationNOTIFICATION-TYPEnot-accessible
.1.3.6.1.2.1.233.0.1

This notification can be generated when a charging state of the battery (indicated by the value of object batteryChargingOperState) is triggered by an event other than a write action to object batteryChargingAdminState. Such an event may, for example, be triggered by a local battery controller.

batteryConnectedNotificationNOTIFICATION-TYPEnot-accessible
.1.3.6.1.2.1.233.0.6

This notification can be generated when it has been detected that a battery has been connected. The battery can be identified by the value of object batteryIdentifier as well as by the value of index entPhysicalIndex that is contained in the OID of object batteryIdentifier.

batteryCriticalNotificationNOTIFICATION-TYPEnot-accessible
.1.3.6.1.2.1.233.0.3

This notification can be generated when the current charge of the battery falls so low that it cannot provide a sufficient power supply function for regular operation of the powered device(s). The battery needs to be charged before it can be used for regular power supply again. The battery may still provide sufficient power for a 'sleep' mode of a powered device(s) or for a transition into an 'off' mode. If the critical state is caused by a single cell or a set of cells of the battery, then object batteryCellIdentifier should be set to a value that identifies the cell or set of cells. Otherwise, the value of object batteryCellIdentifier should be set to the empty string when this notification is generated. The notification should not be sent again for the same battery before either the battery charge has increased through charging to a non-critical value or an indication of a maintenance action has been detected, such as a battery disconnection event or a reinitialization of the battery monitoring system. This notification should not be sent when the battery is in a charging mode, i.e., the value of object batteryChargingOperState is charging(2).

batteryDisconnectedNotificationNOTIFICATION-TYPEnot-accessible
.1.3.6.1.2.1.233.0.7

This notification can be generated when it has been detected that one or more batteries have been disconnected.

batteryLowNotificationNOTIFICATION-TYPEnot-accessible
.1.3.6.1.2.1.233.0.2

This notification can be generated when the current charge (batteryActualCharge) or the current voltage (batteryActualVoltage) of the battery falls below a threshold defined by object batteryAlarmLowCharge or object batteryAlarmLowVoltage, respectively. Note that, typically, this notification is generated in a state where the battery is still sufficiently charged to keep the device(s) that it powers operational for some time. If the charging state of the battery has become critical, i.e., the device(s) powered by the battery must go to a 'sleep' or 'off' state, then the batteryCriticalNotification should be used instead. If the low charge or voltage has been detected for a single cell or a set of cells of the battery and not for the entire battery, then object batteryCellIdentifier should be set to a value that identifies the cell or set of cells. Otherwise, the value of object batteryCellIdentifier should be set to the empty string when this notification is generated. The notification should not be sent again for the same battery or cell before either (a) the current voltage or the current charge, respectively, has become higher than the corresponding threshold through charging or (b) an indication of a maintenance action has been detected, such as a battery disconnection event or a reinitialization of the battery monitoring system. This notification should not be sent when the battery is in a charging mode, i.e., the value of object batteryChargingOperState is charging(2).

batteryTemperatureNotificationNOTIFICATION-TYPEnot-accessible
.1.3.6.1.2.1.233.0.4

This notification can be generated when the measured temperature (batteryTemperature) rises above the threshold defined by object batteryAlarmHighTemperature or falls below the threshold defined by object batteryAlarmLowTemperature. If the low or high temperature has been detected for a single cell or a set of cells of the battery and not for the entire battery, then object batteryCellIdentifier should be set to a value that identifies the cell or set of cells. Otherwise, the value of object batteryCellIdentifier should be set to the empty string when this notification is generated. It may occur that the temperature alternates between values slightly below and slightly above a threshold. For limiting the notification rate in such a case, this notification should not be sent again for the same battery or cell, respectively, within a time interval of 10 minutes. An exception to the rate limitations occurs immediately after the reinitialization of the battery monitoring system. At this point in time, if the battery temperature is above the threshold defined by object batteryAlarmHighTemperature or below the threshold defined by object batteryAlarmLowTemperature, respectively, then this notification should be sent, independent of the time at which previous notifications for the same battery or cell, respectively, had been sent.

batteryAdminGroupunknownnot-accessible
.1.3.6.1.2.1.233.2.2.3

A compliant implementation does not have to implement the object contained in this group.

batteryAlarmThresholdsGroupunknownnot-accessible
.1.3.6.1.2.1.233.2.2.4

A compliant implementation does not have to implement the objects contained in this group.

batteryComplianceunknownnot-accessible
.1.3.6.1.2.1.233.2.1.1

The compliance statement for implementations of the BATTERY-MIB module. A compliant implementation MUST implement the objects defined in the mandatory groups batteryDescriptionGroup and batteryStatusGroup. Note that this compliance statement requires compliance with the entity4CRCompliance MODULE-COMPLIANCE statement of the ENTITY-MIB (RFC 6933).

batteryDescriptionGroupunknownnot-accessible
.1.3.6.1.2.1.233.2.2.1

A compliant implementation MUST implement the objects contained in this group.

batteryNotificationsGroupunknownnot-accessible
.1.3.6.1.2.1.233.2.2.5

A compliant implementation does not have to implement the notifications contained in this group.

batteryPerCellNotificationsGroupunknownnot-accessible
.1.3.6.1.2.1.233.2.2.6

A compliant implementation does not have to implement the object contained in this group.

batteryStatusGroupunknownnot-accessible
.1.3.6.1.2.1.233.2.2.2

A compliant implementation MUST implement the objects contained in this group.

batteryActualCapacityUnsigned32read-only
.1.3.6.1.2.1.233.1.1.1.10

This object provides the actual capacity of the battery in units of mAh. Typically, the actual capacity of a battery decreases with time and with usage of the battery. It is usually lower than the design capacity. Note that the actual capacity needs to be measured and is typically an estimate based on observed discharging and charging cycles of the battery. A value of 'ffffffff'H indicates that the actual capacity cannot be determined.

batteryActualChargeUnsigned32read-only
.1.3.6.1.2.1.233.1.1.1.15

This object provides the actual charge of the battery in units of mAh. Note that the actual charge needs to be measured and is typically an estimate based on observed discharging and charging cycles of the battery. A value of 'ffffffff'H indicates that the actual charge cannot be determined.

batteryActualCurrentInteger32read-only
.1.3.6.1.2.1.233.1.1.1.17

This object provides the actual charging or discharging current of the battery in units of mA. The charging current is represented by positive values, and the discharging current is represented by negative values. A value of '7fffffff'H indicates that the actual current cannot be determined.

batteryActualVoltageUnsigned32read-only
.1.3.6.1.2.1.233.1.1.1.16

This object provides the actual voltage of the battery in units of mV. A value of 'ffffffff'H indicates that the actual voltage cannot be determined.

batteryAlarmHighCycleCountUnsigned32read-write
.1.3.6.1.2.1.233.1.1.1.22

This object provides the upper-threshold value for object batteryChargingCycleCount. If the value of object batteryChargingCycleCount rises above this threshold, a battery aging alarm will be raised. The alarm procedure may include generating a batteryAgingNotification. A value of 0 indicates that no alarm will be raised for any value of object batteryChargingCycleCount.

batteryAlarmHighTemperatureInteger32read-write
.1.3.6.1.2.1.233.1.1.1.23

This object provides the upper-threshold value for object batteryTemperature. If the value of object batteryTemperature rises above this threshold, a battery high temperature alarm will be raised. The alarm procedure may include generating a batteryTemperatureNotification. A value of '7fffffff'H indicates that no alarm will be raised for any value of object batteryTemperature.

batteryAlarmLowCapacityUnsigned32read-write
.1.3.6.1.2.1.233.1.1.1.21

This object provides the lower-threshold value for object batteryActualCapacity. If the value of object batteryActualCapacity falls below this threshold, a battery aging alarm will be raised. The alarm procedure may include generating a batteryAgingNotification. A value of 0 indicates that no alarm will be raised for any value of object batteryActualCapacity.

batteryAlarmLowChargeUnsigned32read-write
.1.3.6.1.2.1.233.1.1.1.19

This object provides the lower-threshold value for object batteryActualCharge. If the value of object batteryActualCharge falls below this threshold, a low-battery alarm will be raised. The alarm procedure may include generating a batteryLowNotification. This object should be set to a value such that when the batteryLowNotification is generated, the battery is still sufficiently charged to keep the device(s) that it powers operational for a time long enough to take actions before the powered device(s) enters a 'sleep' or 'off' state. A value of 0 indicates that no alarm will be raised for any value of object batteryActualVoltage.

More MIBs from Default